Technical Data NXPLUS C
Technical Data NXPLUS C
Technical Data NXPLUS C
NXPLUS C
SF6-Insulated, Metal-Enclosed and
Metal-Clad Medium-Voltage
Switchgear
Content
1 General Data ......................................................................................................................................4
1.1 Ratings ........................................................................................................................................4
1.2 Dimensions, Transport Weights ................................................................................................15
1.3 Service Life, Maintenance.........................................................................................................16
1.4 Low-voltage Wiring ...................................................................................................................16
1.5 Low-voltage Compartment ........................................................................................................16
1.6 Wiring duct for external control wires ........................................................................................16
1.7 Ready-for-Service Indicator ......................................................................................................17
2 Encapsulation...................................................................................................................................18
2.1 Property of Material...................................................................................................................18
2.2 Pressure, Pressure Relief .........................................................................................................18
2.3 Weight and Volume of Gas .......................................................................................................19
3 Insulation ..........................................................................................................................................21
3.1 SF6 - Gas , Density, Temperature, Fission Products ................................................................21
3.2 Electrical and Dielectrically Properties of SF6 ...........................................................................22
3.3 Insulation stressing ...................................................................................................................23
3.4 Resistance at Gas Loss ............................................................................................................23
3.5 Partial Discharge Parameter .....................................................................................................23
4 Busbar, Earth Bus ............................................................................................................................24
4.1 Electrical Data Busbar ..............................................................................................................24
4.2 Electrical Data Earth Bus ..........................................................................................................24
4.3 Mechanical Parameter, Dimensions Busbar .............................................................................24
4.4 Mechanical Parameter, Dimensions Earth Bus ........................................................................25
4.5 Busbar Supports .......................................................................................................................25
4.6 Cast Resin Insulation, Electrical Parameter ..............................................................................25
5 Cable Termination, Cable Test ........................................................................................................27
6 Vacuum Circuit Breaker ...................................................................................................................28
6.1 Electrical Data ...........................................................................................................................28
6.2 Switching Class.........................................................................................................................30
6.3 Operating Times, Operating Sequences, Contacts ..................................................................31
6.4 Motor Drive, Releases, Solenoids .............................................................................................33
6.5 Maintenance .............................................................................................................................37
7 Vacuum-Contactor ...........................................................................................................................38
7.1 Electrical Data ...........................................................................................................................38
7.2 Operating Times, Operating Sequences, Contacts ..................................................................38
7.3 Motor Drive, Releases, Solenoids .............................................................................................39
7.4 Maintenance .............................................................................................................................41
8 Three-Position-Switch ......................................................................................................................42
8.1 Rated Values ............................................................................................................................42
8.2 Operating Times .......................................................................................................................42
8.3 Motor Drive ...............................................................................................................................43
8.4 Maintenance .............................................................................................................................45
9 Three-Position-Disconnector............................................................................................................46
9.1 Electrical Data ...........................................................................................................................46
9.2 Switching Class.........................................................................................................................46
10 Three-Position-Switch-Disconnector ............................................................................................48
10.1 Electrical Data ...........................................................................................................................48
10.2 Switching Class.........................................................................................................................49
11 Make-Proof Earthing Switch .........................................................................................................50
11.1 Make-Proof Earthing Switch at Feeder .....................................................................................50
11.2 2nd earthing switch for fuse .......................................................................................................50
Number of document 802-9100.9 Siemens AG, EM MS S PLM page 2 of 60
Issue: November 24, 2015 Oliver Nöldner
Erlangen
for internal use only
1 General Data
1.1 Ratings
7.2 kV 12 kV 15 kV 17.5 kV 24 kV
Ring-main panel 1s 20kA 25kA 20kA 25kA 20kA 25kA 20kA 25kA 20kA -
7.2 kV 12 kV 15 kV 17.5 kV 24 kV
Switch disconnector 50kA 63kA 50kA 63kA 50kA 63kA 50kA 63kA 50kA -
panel
Ring-main panel 80kA 80kA 80kA 63kA 63kA
7.2 kV 12 kV 15 kV 17.5 kV 24 kV
Switch disconnector 52kA 65kA 52kA 65kA 52kA 65kA 52kA 65kA 52kA -
panel
Ring-main panel 82kA 82kA 82kA 65kA 65kA
7.2 kV 12 kV 15 kV 17.5 kV 24 kV
7.2 kV 12 kV 15 kV 17.5 kV 24 kV
1.1.42 Permissible currents for 25O C 30O C 35O C 40O C 45O C 50O C 55O C
50Hz [A] [A] [A] [A] [A] [A] [A]
Busbar 1250A 1400 1350 1300 1250 1200 1150 1100
Busbar 1600A 2000 1950 1900 1850 1800 1750 1700
Busbar 2000A 2530 2440 2350 2250 2150 2045 1935
Busbar 2500A 2860 2770 2680 2580 2480 2375 2265
1.1.43 Permissible currents for 25O C 30O C 35O C 40O C 45O C 50O C 55O C
50Hz, Feeder SBB [A] [A] [A] [A] [A] [A] [A]
Circuit breaker panel 630A 720 690 660 630 600 570 540
Circuit breaker panel 1000A 1145 1109 1071 1032 992 950 905
Circuit breaker panel 1000A 1145 1109 1071 1032 992 950 905
(30,000 operating cycles)
Circuit breaker panel 1250A 1370 1330 1290 1250 1210 1170 1130
Circuit breaker panel 1250A 1395 1350 1305 1255 1205 1155 1100
(30,000 operating cycles)
1.1.44 Permissible currents for 25O C 30O C 35O C 40O C 45O C 50O C 55O C
50Hz, Feeder DBB [A] [A] [A] [A] [A] [A] [A]
Circuit breaker panel 1000A 1120 1090 1055 1015 975 935 890
Incoming sectionalizer 1250A 1400 1350 1300 1250 1200 1150 1100
Bus coupler 1000A 1120 1090 1055 1015 975 935 890
1.1.45 Permissible currents for 25O C 30O C 35O C 40O C 45O C 50O C 55O C
60Hz [A] [A] [A] [A] [A] [A] [A]
Busbar 1250A 1344 1296 1248 1200 1152 1104 1056
Busbar 1600A 1920 1872 1824 1776 1728 1680 1632
Busbar 2000A 2429 2342 2256 2160 2064 1963 1858
Busbar 2500A 2740 2659 2573 2477 2381 2280 2174
1.1.46 Permissible currents for 25O C 30O C 35O C 40O C 45O C 50O C 55O C
60Hz, Feeder SBB [A] [A] [A] [A] [A] [A] [A]
Circuit breaker panel 630A 690 662 634 605 576 547 518
Circuit breaker panel 1000A 1102 1065 1028 991 952 912 869
Circuit breaker panel 1000A 1102 1065 1028 991 952 912 869
(30,000 operating cycles)
Circuit breaker panel 1250A 1315 1277 1238 1200 1162 1123 1085
Circuit breaker panel 1250A 1350 1310 1265 1220 1170 1120 1070
(30,000 operating cycles)
1.1.47 Permissible currents for 25O C 30O C 35O C 40O C 45O C 50O C 55O C
60Hz, Feeder DBB [A] [A] [A] [A] [A] [A] [A]
Circuit breaker panel 1000A 1079 1046 1013 974 936 898 854
Incoming sectionalizer 1250A 1344 1296 1248 1200 1152 1104 1056
Bus coupler 1000A 1079 1046 1013 974 936 898 854
Hint: The NXPLUS C Double-Busbar will be delivered in single panels (A- and B-side
separately)
1.2.5 Low.voltage boxes Panel width 600 mm
aproximate weight Height 761 mm 55 kg
(depending to installed secondary Height 1161 mm 90 kg
devices) Panel width 900 mm
Height 761 mm 70 kg
Height 1161 mm 120 kg
2 Encapsulation
NXPLUS C Double-Busbar
circuit breaker panel 1000A: A- side 3.0 kg
B- side 3.1 kg
incoming sectionalizer 1250A: A- side 3.2 kg
B- side 3.2 kg
bus coupler 1000A: A- side 3.0 kg
B- side 3.1 kg
2.3.2 Amount of gas to be evacuated none,
and refilled for maintenance switchgear is welded gastight for life-time
3 Insulation
3.1.16 Pressure SF6 related to ambient air NXPLUS C: 500 hPA at 20° Celsius
temperature (relative pressure = overpressure)
4.3.4 Length of busbar section (one bay) feeder current ≤ 1250A: 600 mm,
feeder current > 1250A (900mm): 695 mm
feeder current > 1250A (1200mm): 940 mm
bus sectionalizer (900mm): 295 mm
bus sectionalizer (1200mm): 340 mm
4.3.5 Maximum distance between busbar feeder current ≤ 1250A: 600 mm,
supports feeder current > 1250A (900mm): 695 mm
feeder current > 1250A (1200mm): 940 mm
4.3.6 Type of busbar-joint bolted
4.3.7 Expansion joints none
every section of busbar has 2 mm
tolerance in length
4.3.8 Silver-plated clamps of busbar joint thickness of layer 6 μm
4.3.9 Clearance between phases 110 mm
(between pole centres)
DC 30 V: 17.5 Ω
DC 32 V: 17.5 Ω
DC 48 V: 65.0 Ω
DC 60 V: 65.0 Ω
DC 110 V: 340 Ω
DC 120 V: 340 Ω
DC 125 V: 340 Ω
DC 127 V: 340 Ω
DC 220 V: 1330 Ω
DC 240 V: 1330 Ω
AC 100 V: 224 Ω
AC 110 V: 224 Ω
AC 120 V: 224 Ω
AC 125 V: 224 Ω Ω
AC 230 V: 1200 Ω
AC 240 V: 1200 Ω
6.4.9 Pickup current and holding current 0.47 A at 24 V DC
of undervoltage release
6.4.10 Inrush current of releases max. 9 A, max. 100 ms (at DC 24 V)
6.4.11 Voltage range of auxiliary voltages AC
closing solenoid: 85 to 110 % U
shunt releases: 85 to 110 % U
DC
closing solenoid: 85 to 110 % U
shunt releases: 70 to 110 % U
6.4.12 Voltage range of undervoltage 0 ≤ U < 35 % of UN release must drop out and
release (AC and DC) must release c.b.
35 ≤ U ≤ 70 % of UN release can drop out and
can release c.b.
70 < U ≤ 100 % of UN release must not drop out
must not release c.b.
6.4.13 Power consumption during spring 600 W (DC), 750 VA (AC)
charging (power consumption of motor)
6.4.14 Insulation level of auxiliary and 1 kV AC, 1 s
control circuits Option: 2 kV AC, 1 s
6.4.15 Breaking capacity of auxiliary contacts time factor of auxiliary circuit
t = L/R = 20 ms
DC 24 V: 10 A
DC 30 V: 10 A
DC 32 V: 10 A
DC 48 V: 9A
DC 60 V: 7A
DC 110 V: 4A
DC 125 V: 4A
DC 127 V: 4A
DC 220 V: 2A
DC 240 V: 2A
AC 100 V: 10 A
Number of document 802-9100.9 Siemens AG, EM MS S PLM page 35 of 60
Issue: November 24, 2015 Oliver Nöldner
Erlangen
for internal use only
AC 110 V: 10 A
AC 120 V: 10 A
AC 125 V: 10 A
AC 230 V: 10 A
AC 240 V: 10 A
6.4.16 Power (at rated voltage)
- for closing the vacuum circuit-breaker 140 W / 140 VA
- for tripping the vacuum circuit-breaker140 W / 140 VA
6.4.17 Tripping current per panel acc. to operating voltage, refer to power
consumption
6.4.18 Minimum pickup current of n.a. (refer to minimum voltage acc. 6.4.11)
tripping solenoid
6.4.19 Trip coil resistance depending to voltage of auxiliary circuits
6.4.20 Changing of auxiliary contacts for no
open/close possible
6.4.21 Number of auxiliary contacts Circuit breaker with 1 shunt release
normally open/close small auxiliary switch 6NO + 6NC
5NO + 5NC at disposal
1NO + 1NC is used for internal control of c.b.
4NO + 4NC at customers disposal
Attention: SIPROTEC or conventional control
needs further auxiliary contacts
large auxiliary switch 12NO + 12NC
11NO + 7NC at disposal
1NO + 1NC is used for internal control of c.b.
10NO + 6NC at customers disposal
Attention: SIPROTEC or conventional control
needs further auxiliary contacts
Circuit breaker with 2 shunt releases
small auxiliary switch 6NO + 6NC
5NO + 5NC at disposal
2NO + 1NC is used for internal control of c.b.
3NO + 4NC at customers disposal
Attention: SIPROTEC or conventional control
needs further auxiliary contacts
large auxiliary switch 12NO + 12NC
11NO + 7NC at disposal
2NO + 1NC is used for internal control of c.b.
9NO + 6NC at customers disposal
Attention: SIPROTEC or conventional control
needs further auxiliary contacts
6.4.22 Technical data auxiliary contacts Rated insulation voltage: AC/DC 250V
Insulation: Class C
Continuous current: 10A
Making current: 50A
6.4.23 Label “Spring charged” “Spring charged” white with black background
“Spring discharged” black with white background
6.4.24 Auxiliary switch “Spring charged” 1NO + 1NC
6.5 Maintenance
6.5.1 Mechanical life endurance 10,000 operating cycles
vacuum-interrupter 3AH55
6.5.2 Mechanical life endurance 30,000 operating cycles
vacuum-interrupter 3AH25
6.5.3 Mechanical life endurance 10,000 operating cycles
circuit-breaker drive 3AH55
6.5.4 Mechanical life endurance 30,000 operating cycles
circuit-breaker drive 3AH25
6.5.5 Number of breaking operations 10,000 operating cycles
at rated current 3AH55
6.5.6 Number of breaking operations 30,000 operating cycles
at rated current 3AH25
6.5.7 Number of breaking operations 50 operating cycles
at rated short circuit current
6.5.8 Maintenance 3AH55 no maintenance required
6.5.9 Maintenance 3AH25 no maintenance required
6.5.10 Time after which inspection no maintenance required
of c.b. contacts required
6.5.11 Visual inspection no maintenance required
6.5.12 Mechanical life of auxiliary contacts 1.000.000 operating cycles
6.5.13 Switching of capacitive loads Class CC1 and CC2
Class BC1 and BC2
7 Vacuum-Contactor
AC 110 V
pickup 132 VA, 1.2 A
AC 230 V
pickup 138 VA, 0.6 A
AC 240 V
pickup 168 VA, 0.7 A
7.3.6 Duration of power consumption of 200 ms to 1 s
pick-up load of latch release
solenoid –K2S
7.3.7 Miniature circuit breaker DC 110 V: 16 A
with C-characteristic DC 120 V: 16 A
DC 125 V: 16 A
DC 220 V: 10 A
AC 110 V: 16 A
AC 230 V: 10 A
AC 240 V: 10 A
7.3.8 Voltage range of auxiliary voltages 85 to 110 % Ua
7.3.9 Voltage range of electrical open-circuit principle
de-latching –K2S 85 to 110 % Ua
closed-circuit current
0 ≤ U < 35 % of UN release must drop out and
must release de-latching.
35 ≤ U ≤ 70 % of UN release can drop out and
can release de-latching.
70 < U ≤ 100 % of UN release must not drop out
must not release de-latching
7.3.10 Insulation level of auxiliary and 2 kV AC, 1 min
control circuits
7.3.11 Breaking capacity of auxiliary contacts time factor of auxiliary circuit
t = L/R = 20 ms
DC 24 V: 10 A
DC 48 V: 9A
DC 60 V: 7A
DC 110 V: 4A
DC 125 V: 4A
DC 220 V: 2A
AC 110 V: 10 A
AC 220 V: 10 A
7.3.12 Changing of auxiliary contacts for no
open/close possible
7.3.13 Number of auxiliary contacts Vacuum-Contactor without mechanical latching
normally open/close small auxiliary switch 4NO + 4NC
1NO is used for electromechanical counter
3NO + 4NC at customers disposal
Attention: SIPROTEC or conventional control
needs further auxiliary contacts
large auxiliary switch 6NO + 6NC
1NO is used for electromechanical counter
5NO + 6NC at customers disposal
Number of document 802-9100.9 Siemens AG, EM MS S PLM page 40 of 60
Issue: November 24, 2015 Oliver Nöldner
Erlangen
for internal use only
7.4 Maintenance
7.4.1 Mechanical life endurance vacuum-interrupter: 1.000.000
operating cycles
operating mechanism 100.000
with mechanical latching
8 Three-Position-Switch
8.4 Maintenance
8.4.1 Operating cycles 1,000; 2,000; 5,000 (acc. to application)
8.4.2 Maintenance after operation with n.a. it is not allowed to switch short circuit currents
short circuit current
9 Three-Position-Disconnector
10 Three-Position-Switch-Disconnector
12 Current Transformer
12.1.1 Type of current transformer toroidal-core current transformer 4MC4
13 Voltage Transformer
14 Used Materials
15 Heat of combustion
16.3 Water
16.3.1 Litres per switchgear-panel * Year 2000: 564 l
(l/panel) Year 2006: 307 l
Year 2009: 392 l
Year 2012: 372 l