Company Profile and Technical Brochure

Download as pdf or txt
Download as pdf or txt
You are on page 1of 51

Company Profile and Technical Brochure

Growth Chart 45000


45000

37500

30000
Sales (Rs. In Lacs)

30000

22500 20000

15000
15000
10000
7500 7200
4474
2616 3424
1605 2172
0 385 1015 1160 1322

1995-96 96-97 97-98 98-99 99-2000 00-01 01-02 02-03 03-04 04-05 05-06 06-07 07-08 08-09 09-10
Year
THE POWER IS WITHIN... and breadth of the country has been set up to forge
intimate relationship with its numerous clients.

“GLOSTER CABLES LIMITED” was incorporated in


Quality and service are the cornerstones of Gloster Cables.
the year 1995, with Fort Gloster Industries Limited
An extremely stringent vendor selection mechanism
(FGI) as one of the Equity Participants. FGI are also our
ensures all raw materials are sourced only from the top
Technical & Marketing Collaborators. Manufacturers of
manufacturers in their respective fields, irrespective of their
Quality Power and Control Cables, we have inherited
premium pricing. It has a state-of-the-art in-house
the 'GLOSTER' brand name, and along with it, the high
PVC/XLPE compounding plant and is well-equipped with
standards of manufacturing and quality, that FGI is
all manufacturing and testing facilities.
renowned for.

In its efforts to manufacture an outstanding product, a


The Plant has been accredited for conforming to the
state-of-the-art infrastructure equipped with
quality standards of ISO 9001:2000 by DNV.
sophisticated machinery and testing equipment has

Located at around 35 kms from Secunderabad on been created at its manufacturing units with a total area

National Highway NH 7, the plant encompasses an of 41,000 sqmtrs plant just off Hyderabad.

area of 41,000 sq.mts., with a total built-up area of


23,000 sq.mts. Production facilities have been
designed to match customer expectations and are
compatible with the requirements of the National and
International Standards. A vigilant internal quality
control cell ensures that every Gloster Cable is tested to
conform to the highest standards in the state-of-the-art
in-house laboratory.

Far outperforming the rest of the industry with a


scorching CAGR of almost 40%, the ISO 9001:2000
company, has chalked out an ambitious growth plan
aimed at catapulting it into an Rs 450 crore company
by FY 2009-10.

Obsessed with a vision of delivering not only a product AREA OF THE MANUFACTURING UNIT
UNIT - 1 UNIT - 2 TOTAL
of the highest quality but also ensuring utmost
Built-up area 10000 13000 23000
customer satisfaction through prompt and
Open area 8000 10000 18000
personalized service, a highly networked marketing
Total area (Sq.Mtrs) 18000 23000 41000
and distribution arrangement spread across the length
PRODUCT RANGE
GRADE TYPE OF CABLE RANGE
Single Core upto 1000mm2
PVC/XLPE Power Cables
Multi Core upto 630mm2
1.1 KV Grade Cables
(Low Voltage) PVC/XLPE Control Cables 1.5mm2 , 2.5mm2: upto 61 Core

3.3 KV to 33 KV Grade Cables Single Core upto 1000mm2


XLPE Power Cables
(High Voltage) Three Core upto 400mm2

SPECIAL APPLICATION CABLES


Copper Conductor Cables for both High and Low Voltage

Aerial Bunched Cables for both High and Low Voltage

FRLS / HR Cables for both High and Low Voltage

Airport Lighting Cables

Cables for other Special Application

FUTURE EXPANSION PROGRAMME


Domestic Cables

Instrumentation Cables

Elastomeric Insulated Cables

Mining Cables

Extra High Voltage Cables

Turnkey Cabling Projects

2
MAJOR CUSTOMER LIST
IRON AND STEEL DEFENCE & RESEARCH CENTRE

• Bhushan Steel & Strips • Raipur Alloys • Abhishek Steels • Ordnance Factory , Tiruchirapally • Military Engineering
Ltd., AP • AGP Steels Pvt. Ltd., Medak • Bilasaraika Spong Services, Belgaum • Hyudai Motor India Ltd., TN • MRF
Iron P. Ltd., A.P., • Drolia Electro Steels P. Ltd., Raipur Ltd., TN • Ashok Leyland ltd., Chennai • DRDO
• FLSMIDTH Minerals Pvt. Ltd. • Gasha Steels Pvt. Ltd., Jagadalpur, • DIVI's Laboratories Ltd., AP • Bharat
Palakkad • Jaiswal NECO Ltd.(SPD), Chennai • Jaycee Dynamics Ltd., AP • Indian Navy, INS Vasura, Jamnagar
Sponge Profiles P. Ltd., AP • Kairally Steel & Alloys P. Ltd., • Department of Atomic Energy, Indore • Military
Engineering Services, Vasco • Institute for Plasma Research,
Pallakad • Kalyani Steels Ltd., Hospet • Kirloskar ferrous
Gandhinagar • National Defence Academy , Pune
Ind. Ltd., Bovinhalli • Mahendra Sponge & Power P. Ltd.,
• Ordnance Factory , Ambasari • Director General Naval
Raipur • Mangal Sponge & Steel Ltd., Raipur • Raipur
Project, Mumbai • Centre for Advanced technology, Indore
Sponge & Power Ltd.,Raipur • Ramnivash Ispat Ltd., • Bhabha Atomice reserch Centre, Mumbai • Ordnance
Medak • Salem Steel Plant , Salem • Satyarth Steel & Factory , Jabalpur • Central Fuel Research, Dhanbad
Power Ltd., Raipur • SJK Steels Ltd., Hyderabad • Steel
Abrasive Ltd., Raipur • Steel Authority Of India Ltd., Bhilai PAPER
Plant • Steel Industries Ltd., Kerala • Sunder Ispat Ltd., AP
• Tamilnadu Papers & Newsprint Ltd., TN • The Mysore
• Tirupathi Udyog, AP • Hindalco Industries Ltd., Dahej
Paper Mills Ltd., karnataka • The Sirpur Paper Mills Ltd.,
• Ispat Industries Ltd., Mumbai• Mondovi Pallest Ltd.,
AP • Shesayee Paper & Boards Ltd., Eorde • Ballarpur
Thane • Mukand Ltd., Thane • S.A.L. Steels Ltd., Gujarat.
Industries ltd., AP • Andhra Pradesh Paper mills Ltd., AP
• Steelco Gujarat Ltd. • SWIL Ltd., Bharuch • Vikram
• West Coast Paper Mills Limited • Ramdas Paper Board
Ispat, Raigad • Ballasore Alloys Ltd., Orissa • Bhihar
• J.K.Paper Limited • J.K.Coporation Limited
Sponge iron Ltd., Chandil • Haldia Steels Ltd., WB • Jindal
Stainless Ltd., Orissa • Neelachal Ispat Ltd., Dhubri • Ram LIGHTING
Saroop Lohh Udyog • Satyam Iron & Steel Co.Ltd.,
Ranigunj • Scan Steel Ltd., Rajgangapur • Shivam Iron & • Glaxo Pharmaceuticals • Bajaj Electricals, AP • Philips
India Ltd., AP • Bajaj Electricals, Mumbai
Steel Co. Ltd., Jharkhand • Shri Madhav Ispat Ltd., Orissa
• Shrishti Ispat Ltd., Orissa
PHARMACEUTICAL
POWER AND ENERGY • Vamsi Organics P.Ltd., AP • Smithkline Becham
• Uttaranchal Power Corp.Ltd., Dehradun • National Pharmaceuticals, Banglore • Satyam Plasticizers &
Hydroelctric Power, HP • Nuclear Power Corporation of Chemicals, AP • Reliance Cellulose Products Ltd., AP
•Dr. Reddy's Lab • Tonira Pharma Ltd., Baroda • Taiyo
India , Raj. • BSES Rajdhani Power Ltd., Delhi •BSES
Lucid P. Ltd., Aurangabad • Sovereign Pharma, Daman •
Yamina Power Ltd., Delhi • Jaipur Vidyut Vitaran Nigam
Ranbaxy Laboratories Ltd., Goa • Emcure Pharmaceuticals
Limited • Amrit Bio Energy • Maharshi Solar technology
P.Ltd., Pune • Serum Institute of India, Pune • Ronit
P.Ltd., AP • Karnataka Power Transmission Corp., Banglore Pharma Ltd., AP • Mega Fine Pharma P.Ltd., Nasik
• Kerala State Electricity Board, Kochi • Chattisgarh State
Electricity Co.Ltd., Raipur • AP Power Generation Corp. TEXTILE AND JUTE
Ltd, AP • Jaiprakash Industries ltd., Sikkim • CESC Ltd.,
Kolkatta • Gujrath Paguthan Energy Corp., Bharuch • Maharaja Shree Umaid Mills Ltd., Rajasthan • Vijay Anand
textile Mills P.Ltd., AP • VKSM Cotton Mills Ltd., Coimbatore
• Gujrath Electric Company, vadodara • Ahmedabad
• Surya Lakshmi Cotton Mills Ltd., AP • Suryavanshi Spinng
Electricity Co.Ltd., Gujrath • Adani Energy Limited
Mills Ltd., AP • Sanghi Polysters Ltd., AP • Raymond Ltd.,
Bilaspur • KalaiMangal textiles, Coimbatore • Selvapathy
AUTOMOBILE
Spinning Mills , Coimbatore • GTN Textiles Ltd., Alwaye
• TM Tyres & Tubes P.Ltd., AP • Mahindra & Mahindra • Grasim industries Ltd., Karnataka • GTN Textiles Ltd.,
Ltd., AP • Hyudai Motor India Ltd., TN • MRF Ltd., TN Medak,A.P., • Welspun India Ltd., Gujrath • Surya Lakshmi
Cotton Mills Ltd., Nagpur • Maruti textiles Ltd., Surat
• Ashok Leyland ltd., Chennai • Tata Engineering &
• DCL Polyesters Ltd., Nagpur • Arvind Mills Ltd., santej
locomotive Co.Ltd, Pune
• Ludlow jute Mills, Howrah

3
MAJOR CUSTOMER LIST
SUGAR & FOOD CHEMICALS & FERTILISERS

• The SIRSA Co-op. Sugar Mills Ltd., Haryana • The Ltd., Baroda • Gujrath Heavy Chemicals Ltd., Veraval
Pratappur Sugar & Industries Ltd. • Sarjoo sahakari Chinni • Gujrath Narmda Fertilisers, Bharuch • Gujrath Paguthan
Mills, UP • Dwarikesh Sugar Industires Ltd., UP • Lakshmi Energy Corp., Gujrath • Gujrath state Fertilisers Ltd.,
Sugar Mills Ltd., Uttaranchal • Kisan Sahakari Chinni mills vadodara • Hemani organics & chemicals P.Ltd.,
Ltd., UP • Ch. Devilal Co-op. Sugar Mills Ltd., UP Ankaleshwar • Hindustan Antibiotics Ltd., Pune •Nirma
• Arunachal Sugar Mills Ltd., TN • Chilwaria Sugars • India Ltd., Gujrath • Rashtriya Chemicals & Fertilisers ltd., Thane
Glycols Limited • Balarampur Chinni Mills • Van Melle • IFFCO , Kandla • Indo Rama Petrochemicals • Indian
Confectionary (I) P.Ltd., TN • Vimala Feeds P.Ltd., AP • The Petrochemicals • Saurashtra Chemicals • Tata Chemicals
Trident Sugars Ltd., AP • The Mysore Sugar Co.Ltd., Ltd., Gujrath • Uranium Corporation of India ltd., Raipur
Karnataka • The Nizam Sugars Ltd., AP • SCM Sugars Ltd., • Hind Lever Chemicals Ltd., WB •Meghalaya Carbide &
Karnataka • Shamanur Sugars Ltd., Karnataka • Naranja Chemicals P. Ltd.
Sahakari Sakhar Karkhana, Bidar • Mysore Fruit Products
Ltd., AP • Shakti Sugars Ltd., Orissa • SPR Sugars P.Ltd., PETROLEUM & REFINERIES
Banglore • KCP Sugar & industries Ltd., AP • Kamlapur •Manglore Refineries & Petrochemical • Bharath
Sugar Industries , Karnataka • HIC ABF Special Foods Petroleum Corporation, AP • Kochi refinery Ltd., Kochi
P.Ltd., Kochi • Ganapati Sugar industries Ltd., Medak,A.P., •HPCL, Vizag • IOCL, AP • ONGC, TN • Cochin
• Gayatri Sugars Ltd., AP • Davengare Sugar Co.Ltd., refineries Ltd., Kerala • IOCL, Gujrath Refinery Ltd.,
Karnataka • Bannari Amman Sugars Ltd., Kerala • West Gujrath • ONGC, Ankleshwar • Mumbai Refineries Ltd.,
Kenya Sugars • Walchandnagar Industires Ltd., Pune Mumbai • Chiripaul Petrochemical Ltd., Gujrath • IPCL,
• Parakh Foods Ltd., Pune • IDMC Limited • Pooja Food Bharuch • Gail (India) Ltd., Bharuch • HPCL, Mumbai
products Ltd., Purnea • Numaligarh Reifinery Ltd., Assam • South Asian
Petrochemicals Ltd., WB
CEMENT
DAIRY
• Maharaja Shree Umaid Mills Ltd., Rajasthan • Binani
Cements Limited • JK Lakshmi Cement Limited • Shree •Amudham Dairy Product Pvt.Ltd., TN • Kanakpura Milk
Cements Limited • The Associated cement companies Chilling Centre, karnataka • NDDB Mega Dairy Project,
Ltd.,TN • The India Cements Ltd., TN • Vasavdatta Karnataka • NDDB , AP • Sabar dairy, AP • Tumkara distr.
Cement , Gulbarga • Arsmeta Cement Plant, Chattisgarh Co-op.Milk producers Ltd., AP • Baroda District CO-op.
• Dalmia Cement • Orient Cement • Penna Cements Milk, Baroda • Dudhsagar dairy, Mehsana • Indian dairy
• Chettinad Cement Corporation Limited • Sourashtra
Machinery Co.Ltd., Gujarat • Mother Dairy, Gujarat
Cement Ltd., Gujrath • Digvijay Cement, Gujrath • NDDB, Anand
• My Home cement Ind. Ltd., AP • Sonadih Cement Plant
• Hirimi Cement Works
INFORMATION TECHNOLOGY
COAL & MINERAL • Arihant Techno Park • Satyam Computers • Cyber Park •
HCL Computers • IBM • Motorola • Pristige Technology
• National Mineral Development Corp., MP • Cochin
Park • WIPRO
Minerals & Rutile Ltd, Kerala • Indian Rare Earths Ltd., TN
• Indian Rare Earths Ltd., Kerala • National Mineral UTILITIES
Development Corp., karnataka • Uranium Corporation of
• Airport Authorities Of India • Central Organisation
India ltd., Raipur
Railway • Northern Railway • Global Auto • Hero Motors
• North Western Railway • KESCO • Airport Authorities Of
CHEMICALS & FERTILISERS
India • ABG Shipyard • Central Railway • Western Railway
• Ashoka Distillers & Chemicals P.Ltd., Delhi • EID Parry • Konkan Railway • Cochin Shipyard • Integrated Coach
India ltd., TN • FACT Limited, Kerala • Godavari Fertilisers Factory • Mormugoa Port Trust, Goa • National Highways
& Chemicals Ltd., Karnataka • Shree Rayalseema Alkalies Authorities Of India • Airport Authorities Of India Calicut
• EMPEE Sugars & Chemical Ltd., AP • Madras Fertilisers Airport • Vishakhapattanam Port Trust, Vishakhapattnam
Ltd, Chennai • Asian Paints Gujrath • Alkalies & Chemicals • South West Port • Airport Authorities Of India

4
MAJOR CUSTOMER LIST
SERVICE (HOTEL/EDUCATION/PORT/HOSPITAL) ENGINEERING
(OEM'S/COMMUNICATION/AIRPORT/IT/CONSULTANTS)
• Central Railway, MP • Arihant Educational Society, AP
• Bank of Baroda, AP • Dataware Design Lab P.Ltd., TN • Schaltech Automation P.Ltd., AP • Transformer & Elctrical
• Hotel Babylon International P.Ltd., AP • Hyderabad kerala Ltd., Kerala • Tranvancore Titanium Products
Control University, AP • M.M.Publication, Kerala • PSG Ltd.,Kerala • Alfa Laval India Ltd., Pune • Thermax Babcok
Industrial Institute , TN • MES College of Engineering, & Wilcox Ltd., Pune • Fag Bearings India Ltd., Baroda
Kerala • Rajan Hotels P.Ltd., Chennai • Sankara Eye • Emco Ltd., Mumbai • Filatex India Ltd., Daman • Megi
Hospital, AP • Shree Sadguru Seva Sangh trust, AP Control systems P.Ltd., Goa • Ion Exchange (India) Ltd.,
• Siddharth Academy of Eduction, AP • Shri Kanchi Mumbai • Kalpataru Properties, Thane • National
Kamkoti Medical Trust, kerala • Vishakhapattanam Port Highways Authority of India, Pune • Rainbow Plastic
Trust, Vishakhapattnam • VSNL, Pune • Western Railways, Industry, Daman • Sahara India Ltd., Pune • National
Ahmedabad • MIDC, Mhape •Goa State Co-op. state Aluminim Company, Orissa • Lurgi India Co.Ltd., Kolkata
Bank, Panaji • Hyatt Regency, Goa • I.I.M., Indore • • Exide Industries Ltd., Kolkata • Paharpur Cooling Towers
Indian Institute of Geomagnetism, Mumbai • Mormugao Ltd., Kolkata•Bhutan Constructions
Port Trust, Goa • National Institute of fashion Design,
Ahmedabad • State Bank of India, Mumbai • Indian EPC CONTRACTOR
Institute of Management, Indore Mumbai • Municipal
•Subhash Projects & marketing Ltd., Karnataka • SNC
Corporation of Pharola, Aurangabad • Tulsi Eye Hospital,
Lavalin/Acres INC. • Bharat heavy Electricals Ltd., Hardwar
Nashik • Aisan Hotels Ltd., Kolkata
• Aargee Consultant P.Ltd., Delhi • Omaxe Limited • Jeet
Builders • AREVA T&D India Limited • Bajaj Eco-Tec India
ENGINEERING
(OEM'S/COMMUNICATION/AIRPORT/IT/CONSULTANTS) Limited • Voltas Limited, Secunderabad • Shriram EPC
Limited, Chennai • Singhal Enterprises Pvt.Ltd., Raigarh
•HCL Computers, Noida • Indira Gandhi International • Tata Honeywell Ltd., Pune • Quilon Consulting
Airport, Delhi • Controls & Switchgear Co.Ltd., Delhi • Engineers, Trivendram • Reunion Engineering Co.Ltd., AP
Procter & Gamble India Ltd., Delhi • Greater Noida • Samsung Engineering Ltd., Baroda • P.L.Raju
Industrial Development Authority • Amar Raja Batteries Construction Ltd., AP • Nagarjuna Construction Co.Ltd.,
Ltd., AP • Apollo Tyres Ltd., kerala • Samaria Pipes P.Ltd., AP • Kumar Raja Associates, Vishakhapatnam • KW Kumar
AP • Controls & Schematics Ltd., AP • Heritage Granites Raju , AP • L&T Komatsu Limited, Karnataka • Kirloskar
Ltd.,TN • Hindustan Sanitaryware & Inds.Ltd., AP Electric Co.Ltd., Banglore • Siemens Ltd., Banglore
• Hyderabad Industries Ltd., AP • India Meters Ltd., • IVRCL Infrastructure & Porjects ltd., AP • Harrisons
Chennai • Indian telephone Indutries Ltd., Karnataka Mallyalam ltd., kerala • M/s Greaves Ltd., Chennai • FEE
• ITC, Banglore • Kamal Wineries, AP • Kerala Minerals India P.Ltd., Chennai • Bharat heavy Electricals
Karkarshakha Federation Ltd., Kerala • Kerry Jost Ltd., AP • HCL Technologies Limited • K B Contractors
Engineering Ltd., AP • Babuchand Engineers, Kochi • BTP • Pokarna Limited • Mantri Developers
India Ltd., TN • Cethar vessels P.Ltd., TN • Markwel Hose • MAYTAS • Promac Engineering • Purvankara Projects
Industries Ltd., AP • Mahindra Holidays & Resort India • Seimens Limited • Best & Crompton Engg.Ltd., AP
• J.K.Paper Limited • J.K.Coporation Limited • Kirloskar
Ltd., Karnataka • Nithiya Packaging P.Ltd., Kerala
Brothers Ltd., Kolkatta • Danielli Engineering, Kolkata
• Pokarna Ltd., TN • Pomona Farms & Products, TN
• Durgapur Porjects Ltd., WB • Thermax Ltd., Pune
• Prime Properties Developers, Kerala • Satellite Printing
• Kirloskar Brothers Ltd., Pune • Larsen & Toubro Limited,
P.Ltd., TN • Vatech Vabag Ltd., Chennai • Max India Ltd.,
Mumbai • M/s Greaves Ltd., Pune • Krupp Industries
Karnataka • National Aerospace Laboratories, Karnataka
Limited,Pune • Hindustan Dorr Oliver Ltd., Mumbai
•Popuri Enggineering Consultancy AP • Rank Cranes P. Ltd., AP
• Elecon Engineering Co.Ltd., Baroda • Crompton Greaves
• Reliance Fire & Safety Equipments, AP • Schaltech
Ltd., Mumbai • Batliboi Ltd., Mumbai • Bechtel
Automation P.Ltd., AP • Transformer & Elctrical kerala Ltd.,
International Ltd., Mumbai • Bells Control Ltd., Mumbai
Kerala • Tranvancore Titanium Products Ltd., Kerala • Blue Star Ltd., Mumbai • BSES Ltd., Mumbai • Bajaj
• Popuri Enggineering Consultancy AP • Rank Cranes Electricals Ltd., Mumbai • Godrej & Boyce • John Galt
P.Ltd., AP • Reliance Fire & Safety Equipments, AP International

5
LIST OF MACHINERY
S.NO. MACHINERY PARTICULARS CODE MAKE NO OF YEAR CAPACITY
NO M/C

WIRE DRAWING MACHINES


1 10 Die Wire Drawing Machine WD-001 ALIND-HYD'BAD 1 1995 120 MT
2 7 Die Wire Drawing Machine WD-002 SPUTNIC-HYD,BAD 1 1996 25 MT
3 11 Die Wire Drawing Machine WD-003 MAJI ENGG-CAL 1 2000 140 MT
4 13 Die Fine Wire Drawing Machine WD-004 VINDHYA,REWA 1 2004 35 MT
5 13 Die Wire Drawing Machine WD-005 MPI MACHINE, Gwalio 1 2006 200 MT

ANNEALING FURANCE
6 500 Kg Aluminium Annealing
Furnace AN-001 SPUTNIC-HYD,BAD 1 1996 50 MT
7 2000 Kg Aluminium Annealing
Furnace AN-002 BENGAL LINN-CAL. 1 1998 150 MT

STRANDING AND BUNCHING MACHINES


8 1+6 Bobbin Tubular Strander (18") ST - 001 ALIND-HYD'BAD 1 1996 430 KMS
9 1+6 Bobbin Tubular Strander (20") ST - 002 MAJI ENGG-CAL 1 2000 450 KMS
10 1+6 Bobbin Tubular Strander (8") ST - 003 MAJI ENGG-CAL 1 2000 300 KMS
11 19 Bobbin Stranding Machine ST - 004 PIPARIA ENGG- 1 1998 200 KMS
12 18+24 Bobbin Stranding Machine ST - 005 MAJI ENGG-CAL 1 2000 200 KMS
13 12+18 Bobbin Stranding Machine ST - 006 PARMICO - DELHI 1 1996 200 KMS
14 54 Bobbin Stranding Machine ST - 007 PARMICO - DELHI 1 1996 250 KMS
15 20" Bobbin Size Bunching Machine ST - 008 MAJI ENGG-CAL 1 1996 500 KMS
16 1+6+12+18 Bobbin Stranding
Machine ST - 009 MPI MACHINE, Gwalio 1 2006 300 KMS
17 1+6+12+18+24 Bobbin
Stranding Machine ST-010 MPI MACHINE, Gwalio 1 2005 300 KMS
18 Skip Strander ST-011 MAIFIAR, Thane 1 2007 1500 KMS
19 630mm Bunching machine ST-012 MINIMAX,Delhi 1 2007 1000 KMS

LAYING UP MACHINES
20 1+3 Core Laying Up Machine
(54Inch) LU - 001 PARMICO - DELHI 1 1996 125 KMS
21 1+3 Core Laying Up Machine
(63Inch) LU - 002 FGI - CALCUTTA 1 2000 130 KMS
22 1+3 Core Laying Up Machine (48") LU - 003 TRAFALGAR - CAL 1 1998 250 KMS
23 1+3 Core Laying Up Machine (27") LU - 004 GCL - HYD' BAD 1 2001 200 KMS
24 1+3 Core Laying Up Machine (48") LU - 005 MAJI ENGG-CAL 1 2005 250 KMS
25 (1+3)630 Bobbin Laying Up
Machine LU - 006 GCL - HYD' BAD 1 2007 200 KMS
26 Copper Taping & Core Identification
Machine LU - 007 MPI MACHINE, Gwalio 1 2005 100 KMS

6
LIST OF MACHINERY
S.NO. MACHINERY PARTICULARS CODE MAKE NO OF YEAR CAPACITY
NO M/C

LAYING UP MACHINES
27 Copper Taping & Core Identification
Machine LU - 007 VINDHYA,REWA 1 2007 100 KMS
28 1+3 Drum Twister (2500 mm) LU - 007 MAIFIAR, Thane 1 2006 230 KMS
29 Double Twist Laying Machine LU - 008 Machino Technike.Than 1 2005 500 KMS
30 Single twist Laying machine LU-009 Machino Technike.Than 1 2007 500 KMS
31 1+3 Drum Twister (1850 mm) LU - 010 MAIFIAR, Thane 1 2007 400 KMS

PVC / XLPE EXTRUDERS


32 45 MM Extruder Machine EX - 001 SUPERMAC - DELHI 1 1996 9.5 MT
33 65 MM Extruder Machine EX - 002 SUPERMAC - DELHI 1 1996 14.5 MT
34 65 MM Extruder Machine (New) EX - 003 GCL - HYD' BAD 1 2001 27 MT
35 120 MM Extruder Machine with
auto loader EX - 004 SUPERMAC - DELHI 1 1996 150 MT
36 80 MM Extruder Machine with
auto loader EX - 005 ROYLE Extrusion , Pune 1 2001 150 MT
37 80 MM Extruder Machine with
auto loader EX - 006 ROYLE Extrusion , Pune 1 2002 100 MT
38 150 MM Sheathing Extruder
Machine with auto load EX - 007 ROYLE Extrusion , Pune 1 2004 350 MT
39 65mm, 80 mm, 120 mm, Triple
Extruder Machine for 11KV / 33
KV with loader EX - 008 ROYLE Extrusion , Pune 1 2005 150 MT
40 45 MM Extruder Machine EX - 009 ROYLE Extrusion , Pune 1 2007 9.5 MT
41 65 MM Extruder Machine EX - 010 ROYLE Extrusion , Pune 1 2007 14.5 MT
42 80 MM Extruder Machine with
auto loader EX - 011 ROYLE Extrusion , Pune 1 2007 150 MT
43 120 MM Extruder Machine with
auto loader EX - 012 SUPERMAC - DELHI 1 2007 150 MT

SPARK TESTING MACHINES


44 SPARK TESTING MACHINES : SP-001 TELE FLEX 1 1996 0-15 K.V
45 SPARK TESTING MACHINES : SP-002 TELE FLEX 1 1996 0-15 K.V
46 SPARK TESTING MACHINES : SP-003 TELE FLEX 1 1997 0-15 K.V
47 SPARK TESTING MACHINES : SP-004 TELE FLEX 1 1998 0-15 K.V
48 SPARK TESTING MACHINES : SP-005 TELE FLEX 1 1998 0-30 K.V
49 SPARK TESTING MACHINES : SP-006 TELE FLEX 1 1998 0-30 K.V
50 SPARK TESTING MACHINES : SP-007 TELE FLEX 1 2001 0-30 K.V
51 SPARK TESTING MACHINES : SP-008 TELE FLEX 1 2001 0-30 K.V
52 SPARK TESTING MACHINES : SP-009 CAT-CANTROLS 1 2007 0-15 K.V
53 SPARK TESTING MACHINES : SP-010 CAT-CANTROLS 1 2007 0-15 K.V
54 SPARK TESTING MACHINES : SP-011 CAT-CANTROLS 1 2007 0-15 K.V

7
LIST OF MACHINERY
S.NO. MACHINERY PARTICULARS CODE MAKE NO OF YEAR CAPACITY
NO M/C

ARMOURING MACHINES
55 56 Bobbin Armouring Machine AM-001 PARMICO - DELHI 1 1996 150 KMS

56 24 Bobbin Armouring Machine AM-002 NEW FAMOUS-HYD 1 2007 200 KMS

57 30 Bobbin Armouring Machine AM-003 Vindhya kables, Rew 1 1998 175 KMS

58 24 Bobbin Armouring Machine AM-004 GCL - HYD ' BAD 1 2001 205 KMS

59 42 Bobbin Armouring Machine AM-005 GCL - HYD ' BAD 1 2001 200 KMS

60 72 Bobbin Armouring Machine AM-006 Vindhya kables, Rew 1 2005 250 KMS

61 48 Bobbin Armouring Machine AM-007 MPI MACHINES,Gwal 1 2006 200 KMS

ARMOURING MACHINES
62 30 Bobbin Armouring Machine AM-008 Vindhya kables, Rew 1 2007 175 KMS

63 30 Bobbin Armouring Machine AM-009 Vindhya kables, Rew 1 2007 175 KMS

64 16 Bobbin Armouring Machine AM-010 NEW FAMOUS-HYD 1 2007 175 KMS

CABLE REWINDING MACHINES


65 54'' Bobbin Rewinding Machine RW - 001 GCL - HYD ' BAD 1 1997 UPTO 20MM

66 72'' Bobbin Rewinding Machine RW - 002 FGI - CALCUTTA 1 1997 UPTO 30MM

67 80'' Bobbin Rewinding Machine RW - 003 CREST - HYD' BAD 1 1997 UPTO 80MM

68 104'' Bobbin Rewinding Machine RW - 004 FGI - CALCUTTA 1 1997 UPTO 80MM

69 104'' Bobbin Rewinding M/C with


D.C drive RW - 005 TECHMACH - CAL 1 1998 UPTO 80MM

70 72'' Bobbin Rewinding Machine RW - 006 B.BHAVANI-AHMEDA 1 2007 UPTO 30MM

71 72'' Bobbin Rewinding Machine RW - 007 B.BHAVANI-AHMEDA 1 2007 UPTO 30MM

WIRE WELDING MACHINES


72 Cold Pressure Welding Machine CS - 001 --- 1 1997 ---

73 Cold Pressure Welding Machine CS - 002 --- 1 1997 ---

74 Cold Pressure Welding Machine CS - 003 --- 1 1998 ---

75 Cold Pressure Welding Machine CS - 004 --- 1 1998 ---

76 Cold Pressure Welding Machine CS - 005 --- 1 1999 ---

77 Butt Welding Machine BW - 001 --- 1 1997-98 ---

78 Butt Welding Machine BW - 002 --- 1 1997 ---

79 Butt Welding Machine BW - 003 --- 1 1999 ---

80 Butt Welding Machine BW - 004 --- 1 1999 ---

81 Butt Welding Machine BW - 005 --- 1 2000 ---

82 Grinding Machine GM - 001 --- 1 1997 ---

83 Hot Hydraulic Press HP - 001 S.A.ASSOCIATES 1 1997 250 K N

8
LIST OF MACHINERY
S.NO. MACHINERY PARTICULARS CODE MAKE NO OF YEAR CAPACITY
NO M/C

GENERATORS
84 Generator GN - 003 CUMMINS KIRLOSKAR 1 2000 250 K V A
85 Generator GN - 004 CUMMINS KIRLOSKAR 1 2006 380 K V A
86 Generator GN - 005 CUMMINS KIRLOSKAR 1 2006 380 K V A
87 Generator GN - 007 CUMMINS KIRLOSKAR 1 2001 250 K V A
88 Generator GN - 008 CATERPILLER 1 2007 1000 K V A

UTILITIES
89 Air Compressor AC - 001 ELGI/METRO 1 1997 5 HP
90 Air Compressor AC - 002 ELGI/METRO 1 1997 5 HP
91 Air Compressor AC - 003 ELGI/METRO 1 1997 5 HP
92 Air Compressor AC - 004 ELGI/METRO 1 1998 5 HP
93 Air Compressor AC - 005 ELGI/METRO 2 2000 10 HP
94 Air Compressor AC - 006 ELGI/METRO 1 2004 15 HP
95 Screw Type Air Compressor AC - 006 I.R 1 2005 15 HP

VULCANISING
96 Vulcanising Chamber VC - 001 GCL HYD,BAD 1 2002
97 Steam Boiler SB - 001 Thermax , Pune 1 2007 600 Lts/Hour
98 Vulcanising Chamber VC - 002 GCL HYD,BAD 1 2002
99 Steam Boiler SB - 002 Shanthi Bolier , Hyd' Bad 1 2004 1500 Lts/Hour
100 Steam Boiler SB - 003 Thermax , Pune 1 2007 1500 Lts/Hour
101 Vulcanising Chamber VC - 003 GCL HYD,BAD 1 2002
102 Fork Lift 2 2000 GODREJ-5 T

PVC COMPOUND MIXTURES


103 25 HP Mixture for 120 MM Extruder Oswal Engg - Bombay 1 2005 300 KMS
104 20 HP Mixture for 65 MM Extruder SUPERMAC - DELHI 1 2005 1000 KMS
105 20 HP Mixture for 150 MM Extruder SUPERMAC - DELHI
106 15 HP Mixture for 65 MM Extruder SUPERMAC - DELHI 1 1996 100 KMS
107 10 HP Mixture for 45 MM Extruder SUPERMAC - DELHI 1 2000 130 KMS
108 15 HP Mixture for 65 MM Extruder SUPERMAC - DELHI 1 1998 250 KMS
109 10 HP Mixture for 45 MM Extruder SUPERMAC - DELHI 1 2001 200 KMS

SPOOLING MACHINES
110 Aluminium Wire Spooling Machine GCL - HYD' BAD 2 1996 20 MT
111 G.I.Wire/Strip spooling Machine GCL - HYD' BAD 3 2007 30 MT
112 G.I.Wire/Strip spooling Machine GCL - HYD' BAD 3 2007 30 MT
113 G.I.Strip spooling Machine MAJIENGG - CAL 3 1996 30 MT
114 G.I.Wire spooling Machine MAJIENGG - CAL 3 1999 30 MT

9
LIST OF TESTING AND QUALITY CONTROL INSTRUMENTS

S.NO INSTRUMENTS RANGE LEAST COUNT


CABLES UPTO 1.1 KV

1 "Universal" Heating Oven 0 to 400° C 1° C


2 Hot Set Test Oven 0 to 400° C 1° C
3 Vaccum Oven for Water absorbtion 0 to 150° C 1 Millibar
4 Thermal Stability Test Apparatus 0 to 400° C 0.1°C
5 Million Megohm Meter 1 Ohm to 1x109 1 Ohm
6 Ageing Oven 4 Cell 0 to 400° C 1°C
7 Tesnile Testing Machine 0 to 250 KGF 0.1 KGF
8 Tesnile Testing Machine 0 to 1000 KGF 1 KGF
9 weighing Balance 0 to 5 KG 1 Gram
10 Physical Weighing Balance 0 to 500 Grams 0.001 Gram
11 Conditioning Chember 30°c to -40°c RH 15 to 80% 1°C
12 Water Bath 90°C 1°C
13 AC High Voltage Tester 0 to 10 KV (40 KVA) 500
14 DC High Voltage Tester 0 to 2.5 KV 0.05 KV
15 Digital Micro - Ohm Meter (Teleflex) -2 nos 200 µ to 20 K Ohm 1µ
16 Digital Micro - Ohm Meter (Sivananda) -2 nos 200 µ to 20 K Ohm 1µ
17 Digital Vernier Calliper (Mirutoyo) 0 to 150 MM 0.01 MM
18 Micro Meter (Mitutoyo) 0 to 25 MM 0.01 MM
19 Fault Locater Meter (Teleflex) - -
20 Hot Deformation Test Apparatus with Weights As Per IS: 10810 1.0 Gram
21 Flammability Test Apparatus with As Per IS: 10810 -
Bunson Burner
22 Capacitance Meter Staranded -
23 Torsion Test Machine (Motorised) 60 to 70 Turn/Minuts -
24 Megger 2500 Volt 5000 M 1.0 M
25 Glass Thermo Meter 190°C to 210°C 0.1°C
26 Glass Thermo Meter 0 to 250°C 1°C
27 Hygrometer RH 50% -
28 Cold Impect Test Apparatus - -
29 Temperature Indicator 0 to 1200°C 1°c
30 Dielectric Retention Tester (KV) 0 to 100 KV 5 KV

10
LIST OF TESTING AND QUALITY CONTROL INSTRUMENTS

S.NO INSTRUMENTS RANGE LEAST COUNT


HT CABLES
1 Shield Room For HV Test - -
2 Partial Discharge Detector 0 to 100 ° C -
3 HV Test Set 375 KVA, 75 KV -
4 Heat Cycle Test Equipment -
5 Impulse Generator 0 to 300 KV 1 KV
6 Capaciatance Tandelta Bridge - -

FRLS TEST EQUIPMENTS

1 Oxygen Index and Temperature Index - -


2 Smoke Density Tester - -
3 Halogen Acid Gas Tester - -
FLAMMABILITY TEST
1 Swedish Chimmney - -
2 Vertical Flammability Test - -
3 For Flammability Test as per - -
IEEE - 383 (for bunched cables)

MAJOR RAW MATERIAL SOURCES


RAW MATERIAL PARTICULARS SOURCES

ALUMINIUM ROD/WIRE • ALUMINIUM INDIA • NATIONAL ALUMINMIUM CO LTD.,


• HINDALCO INDUSTRIES LTD • THE MADRAS ALUMINIUM CO LTD
COPPER ROD/WIRE • STERLITE INDUSTRIES LTD • HINDUATAN COPPER LIMITED
• HINDALCO INDUSTRIES LTD
DOP/ STABILIZERS / CATALYSTS • LALITHA CHEM INDUSTRIES (P)LTD • K L J PLASTICIZERS
GI WIRE / STRIP • USHA MARTIN INDUSTRIES • TATA SSL LTD
• SAHANI STRIPS & WIRES PVT LTD
PVC RESIN • FINOLEX INDUSTRIES LIMITED • RELIANCE INDUSTRIES LTD
• INDIAN PETROCHEMICALS CORPORATION LTD
COPPER TAPE • THE INDIAN SMELTING & REFINNING CO LTD
• ABHAYAUTO TRADE P LTD
LT / HT XLPE • M/s.POLYLINK POLYMERS • KALPANA INDUSTRIES LTD
• K L J POLYMERS & CHEMICALS
SEMICONDUCTING • SUN PETROCHEMICALS PVT .LTD • KALPANA INDUSTRIES LTD
• M/s.POLYLINK POLYMERS
PVC COMPOUND • IN-HOUSE PRODUCTION

11
LOW VOLTAGE CABLES
Low Voltage Cables are manufactured with PVC and XLPE, as insulation has the following superior features:
XLPE insulation. PVC Cables are manufactured • Low dielectric loss.
according to IS:1554 (Part I) up to 1.1KV grade. • Higher power rating and higher emergency
overload rating.
XLPE Cables are manufactured according to IS:7098
• Superior short circuit rating.
(Part -I), up to and including the latest amendments.
• Much better insulation resistance
All cables have the ISI Certification.
• Higher resistance to moisture
• Capacity to withstand localized hot spot
PVC, as insulation and sheath compounds, has the
temperature, very vital to steel plants, power
following superior features:
stations, etc.
• Strong and made for easy handling • Resistant to chemicals and corrosive gases, etc.
• Resistant to water, moisture, oils and chemicals • Exhibits better properties, such as resistance to
• PVC black compounds can resist ultraviolet vibration, impact, ageing and hot deformation.
degradation • Termination and jointing methods are very easy,
• Specially formulated PVC is flame retardant and simple and non-expensive as compared to
reduces emission of halogens and smoke other cables.

DESIGN AND CONSTRUCTION

CONDUCTORS
The conductors of power cables are made from
electrical purity aluminium, and those of control cables
are of annealed high conductivity copper. However,
copper conductor power cables can also be supplied
against orders. All conductors conform to IS:8130-1984.

INSULATION
High quality PVC base compound is used for PVC Cables
and high quality Cross Linked Polyethylene (XLPE)
unfilled insulating compound is used for XLPE Cables.

12
LOW VOLTAGE CABLES
LAYING UP 2 Core red and black
In multicore cables, cores are laid up as per the above 3 Core red, yellow and blue
color scheme and interstices are filled up wherever 4 Core red, yellow, blue and black (also 3½ core
necessary to make the laid up cable circular. reduced neutral is black)
5 Core red, yellow, blue, black and grey
INNER SHEATH
For cables having more than 5 cores:
For all cables having two or more cores, a common
Two adjacent cores (counting and direction core) in
covering (inner sheath) is applied over the laid up cores
each layer are coloured blue and yellow respectively
either by extruded sheath of PVC Compound or
and the remaining cores are grey.
wrapping of thermoplastic or proofed tapes.
Alternatively, cores with number printing can be offered.
ARMOURING
For multi-core cables, armouring is applied over the
inner sheath. In case of cables where the fictitious
diameter over the inner sheath does not exceed TESTING AND
13mm., the armour consists of galvanised round steel QUALITY ASSURANCE
wires; above this size, normally the armour is of
The various tests carried out on Low Voltage cables are
galvanised formed steel wires. Any metallic,
classified in three different groups: • Routine Tests
non-metallic wire/strip can be available on request.
• Type Tests and • Acceptance Tests.

OUTER SHEATH
ROUTINE TESTS
Outer sheath is extruded over the armouring. In case of
The following tests constitute Routine Tests which are
multi-core unarmoured cables, over the inner sheath,
carried out on each and every length of cable as per
whereas, in case of unarmoured single-core cables, it is
extruded over the insulation. This is always black in relevant IS specification before it leaves the factory.

colour for best resistance to outdoor exposure. Any


(A) Conductor Resistance Test
other colour can be available on request.
The Test ensures that conductor resistance is within the

CORE IDENTIFICATION specified limit, thereby verifying that the continuity of

Colour Scheme: Cores are identified by the colour conductor is maintained throughout the cable length
scheme of insulation. The following colour scheme is and that the conductor has the required electrical
normally adopted: section D.C. resistance is measured at room
1 Core red, black, yellow, blue or natural temperature and is then corrected to standard
(non pigmented) reference temperature of 20°C.

13
LOW VOLTAGE CABLES
(B) High Voltage Test PACKING
The test ensures that insulation will safely Cables are normally supplied in wooden drums.
withstand the rated voltage with permissible Special drums are also provided on request. While
variation in normal operation. installing LT PVC/LT XLPE cables, the following
minimum bending radii should be observed in order so
TYPE TESTS
that the cable, especially insulation, may not undergo
These tests are carried out on samples taken from
damage. Wherever possible larger bending radii
each production lot as per relevant IS specification.
should be used.
They are carried out to prove conformity as regards
the general qualities and design to the specification CABLES EXPOSED TO SUN
of particular type of cables. On account of heating of the exposed cable due to solar
radiation, the rating of the cable installed out-doors and
ACCEPTENCE TESTS not shielded from the sun is less than if so shielded. To
These tests are again carried out as per relevant IS
reduce the effect of solar radiation, it is recommended
specification in the presence of the concerned
that the cable should be shielded from the direct rays of
Inspecting Authority for testing, approval and release
the Sun without restricting the ventilation.
of material offered for inspection.

14
HIGH VOLTAGE CABLES
Cross Linked Polyethylene Cable i.e. XLPE Cable was LOW DIELECTRIC LOSSES:
developed in late 1970 to overcome the susceptibility XLPE Cables have low dielectric loss angle. Moreover,
of PILC Cables to ingress of moisture. Hence the these losses occur continuously in every charged cable
advent of XLPE cables marked the beginning of a whether it carries load or not. Hence use of XLPE Cable at
gradual but steady replacement of Paper Cables in higher voltage would result in considerable saving in costs.
almost all voltage applications.
LOWER CHARGING CURRENTS:
The excellent thermal properties of XLPE Cable permit The charging currents are considerably lower

maximum continuous conductor operating permitting close setting of protection relays.

temperature of 90o C and short circuit temperature of


EASY LAYING AND INSTALLATION:
250o C. Moreover, it has low dielectric loss, which does
Low weight and small bending radii make laying and
not vary much over the entire operating temperature
installation of cable very easy. The cable requires less
range. These characteristics, along with the low
supports due to low weight.
dielectric constant, make XLPE Cable particularly
suitable for high voltage applications. Given below are HIGH SAFETY:
additional outstanding features. Cables have High safety against mechanical damage
and vibrations.
HIGH CONTINUOUS CURRENT RATING:
Its ability to withstand higher operating temperature of
0
90 C enables much higher current rating than those of
PVC or PILC cables.

HIGH SHORT CIRCUIT RATING:


Maximum allowable conductor temperature during
short circuit of 2500 C is considerably higher than for
PVC or PILC Cables resulting in greater short circuit
withstand capacity.

HIGH EMERGENCY LOAD CAPACITY:


XLPE Cables can be operated even at 1300 C during
emergency, therefore in systems, where cables are
installed in parallel; failure of one of two cables will not
bring down the system capacity for some time.

15
HIGH VOLTAGE CABLES
APPLICATIONS: CONDUCTOR SCREENING
Conductor screening is employed for all cables above
1 Used extensively in all power generating plants and
industrial plants. 3.3 KV grade in the form of a semi conducting
2 Used in chemical and fertilizer units where cables extrusion over the conductor.
are exposed to chemical corrosion.
XLPE INSULATION
3 Used in heavy industries where severe load
High quality XLPE unfilled insulating compound of
fluctuations occur.
4 Used in systems where there are frequent over natural color is used for insulation. Insulation is applied

voltages. by extrusion process and is chemically cross-linked by


5 Used at higher ambient temperatures on account silane process.
of their higher operating temperatures.
INSULATION SCREENING
6 Used even under most difficult cable route
The cables rated above 3.3 KV are provided with
conditions such as city distribution network.
insulation shielding over the insulation. The screening
is provided with an extruded layer of semi conducting
compound. Over the semi conducting covering, a
DESIGN AND CONTRUCTION
metallic screen in the form of copper tape is provided.
CONDUCTOR
CORE SHIELDING
The conductors made from E.C. grade aluminum
XLPE insulation and insulation shielding are all
wires, are stranded together and compacted. All sizes
extruded in one operation by a special process. This
of conductors of single or three core cables are circular
process ensures perfect bonding of inner and outer
in shape.
shielding with insulation. The bond prevents the
Conductor construction and testing comply to IS 8130-
formation of cavities at the surface of the conductor
1984 as amended up to date.
when the cable is subjected to bends. The void
Cables with copper conductor can also be offered.
formation, at the interface of the semi conducting layer

EXTRUDED SEMI-CONDUCTING
CONDUCTOR SHIELDING

ALUMINIUM CONDUCTOR

XLPE INSULATION
OUTER SHEATH
EXTRUDED SEMI-CONDUCTING
ARMOUR CORE SHIELDING

TAPE WRAPPING COPPER TAPE SCREENING

FILLER CORE IDENTIFICATION TAPE


16
HIGH VOLTAGE CABLES
and insulation, too is eliminated even during heating TESTING AND QUALITY
and cooling cycles in the operation. ASSURANCE
INNER SHEATH (COMMON COVERING) XLPE Cables are manufactured under advanced
In case of multi core cables, cores are stranded together manufacturing and testing facilities. The cables are
with suitable non-hygroscopic fillers in the interstices and type tested and routine tested in accordance with
provided with common covering of plastic tapes IS - 7098 (Part - II) 1985.
wrapping. As an alternative to wrapped inner sheath,
The following tests are carried out as routine tests on
extruded PVC inner sheath can also be provided.
every length of cables manufactured:
ARMOURING:
a) Conductor resistance test
Armouring is applied over the inner sheath and
b) Partial discharge tes
normally comprise of galvanized Steel Wire or
c) High Voltage test
galvanized Steel Strips for multi core Cables. For
Mining use and other special applications, double
Wire/Strip armoured cables with Tinned Copper wires
can also be offered. Single core armoured cables are TEST VOLTAGES:
provided with non-magnetic armour consisting of hard
The following test voltage is applied between
drawn flat or round aluminum wires.
conductor and screen / armour:
OUTER SHEATH:
VOLTAGE RATING TEST VOLTAGE
A tough Outer Sheath of Heat Resisting PVC OF CABLES
compound (Type ST2) as per IS - 5831 is extruded over
1.9/3.3 or 3.3/3.3KV 10 KV (rms) for 5 Minutes
the armouring in case of armoured cables or over non-
3.8/6.6 KV (E) 12 KV (rms) for 5 Minutes
magnetic metallic tape covering the insulation or over
the non-magnetic metallic part of insulation screening 6.35/11 KV (E) 17 KV (rms) for 5 Minutes

in case of unarmoured single core cables. This is always 11/11 KV (UE) 28 KV (rms) for 5 Minutes

black in color for best resistance to outdoor exposure. 12.7/22 KV (E) 32 KV (rms) for 5 Minutes
The Outer Sheath is embossed with “Gloster”, the 19/33 KV (E) 48 KV (rms) for 5 Minutes
voltage grade and the year of manufacture.
In order to achieve consistency in quality, in addition to
CORE IDENTIFICATION
above tests, rigorous quality control measures are
The Core identification complies with the
effected at every stage of production. Accordingly every
requirements of IS-7098 (Part II) as shown below:
batch of raw materials and process cables are tested to
• By numerals (1, 2, 3) printed on cores.
check for their physical and electrical properties.
OR
• By colored strips applied on the cores.

17
SHORT CIRCUIT RATING OF
XLPE CABLES:
300

Thermally admissible short circuit current for cables of 200

1.1KV to 33 KV garde are depicted in the graph


100
below:-Full load conductor temperature prior to short
circuit 90o C 1K
50 A Sq mm
(KA rms) 1000

Maximum short circuit conductor temperature: 250o C 800


630

20 500

Formula Ik = 0.094 A / √ t 400

300
Ik : Short Circuit Current In KA (rms) 10 240
225
185
t: Duration of short circuit in seconds 150
5 120
2
A: Area of aluminum conductor in mm 95

Short circuit ratings of cables for one-second duration 70

2 50
are given in the respective tables 1-10. For any other
35

duration of t seconds divide the value given in the


1 25
01 02 05 10 20 50
respective table by (√ t).
t (sec)

OPERATING CHARACTERISTICS:
The construction data and current rating of cables with aluminum conductor are shown in tables. These are based on
standard conditions of installations as provided below:

Maximum continuous operating conductor temperature


for PVC/HR PVC Cables = 70o C / 85o C
Maximum continuous operating conductor
temperature for XLPE Cables = 90o C

Standard ground temperature = 30 o C

Ambient air temperature = 40 o C

Thermal Resistivity of soil = 150 o C


Depth of laying (for cables laid direct in ground) = 75 cms for cables up to 1.1 KV
90 cms for cables up to 11 KV
(E) / (UE) grade
= 105 cms for 22KV and 33 KV grade cables

18
FLOW CHART FOR MANUFACTURING PROCESSES & QUALITY CONTROL CHECKS
• LT PVC CABLES CONFORMING TO IS:1554 PART - I
• LT XLPE CABLES CONFORMING TO IS:7098 PART - I
• HT CABLES CONFORMING TO IS:7098 PART - II

ALUMINIUM / COPPER WIRE ROD

WIRE DRAWING

ANNEALING

TEST ON WIRE

CONDUCTOR STRANDING

TEST ON STRANDED CONDUCTOR

HT CABLES LT PVC/XLPE CABLES


CONDUCTOR SCREENING
XLPE INSULATION TRIPLE EXTRUSION
TEST ON PVC/XLPE COMPOUND
INSULATION SCREENING
CURING
EXTRUSION OF LT PVC/XLPE INSULATION
TEST ON CORE
CURING (XLPE CABLES)
COPPER TAPING
TEST ON CORE
PD TEST ON CORE
SINGLE CORE UNARMOURED CABLE

LAYING UP OF CORES (FOR MULTICORE CABLES)

INNER SHEATHING (LAPPING OF THERMOPLASTIC TAPES OR


SINGLE CORE

ARMOURED

EXTRUSION OF PVC)
CABLE

TEST ON ARMOUR WIRES/STRIPS

ARMOURING

TEST ON PVC COMPOUND

EXTRUSION OF PVC OUTER SHEATH

TESTING ON FINISHED CABLE

SEALING OF BOTH ENDS OF CABLE

PACKING

STOCK PROCESS TEST


19
1.1 KV SINGLE CORE ALUMINIUM CONDUCTOR, PVC INSULATED ARMOURED / UN - ARMOURED
PVC OUTER SHEATH CABLE CONFORMING TO IS : 1554 (Part - I) TABLE - 1

UN ARMOURED CABLES ARMOURED CABLES


AYY Single Layer - wire (AYWY) Single Layer - Strip (AYFaY)

Nominal Nominal Nominal Approx. Approx. Nominal Nominal Minimum Approx. Approx. Nominal Minimum Approx. Approx.
size of thickness thickness overall weight of thickness of diameter thickness overall weight of thickness thickness overall weight of
conductor of insulation of outer diameter Aluminum insulation of armour of outer diameter Aluminum of armour of outer diameter Aluminum
sheath of cable cable wire sheath of cable cable strip sheath of cable cable

Sq. mm mm mm mm Kg/Km mm mm mm mm Kg/Km mm mm mm Kg/Km


PVC POWER & CONTROL CABLES

4 1.0 1.8 8.4 100 1.3 1.4 1.24 11 160 - - - -


6 1.0 1.8 8.8 110 1.3 1.4 1.24 12 180 - - - -
10 1.0 1.8 9.4 135 1.3 1.4 1.24 13 210 - - - -
16 1.0 1.8 10.6 163 1.3 1.4 1.24 14 260 - - - -

25 1.2 1.8 12.0 220 1.5 1.4 1.24 16 320 - - - -


35 1.2 1.8 13.0 265 1.5 1.4 1.24 17 360 - - - -

50 1.4 1.8 15.0 333 1.7 1.4 1.24 19 440 - - - -


70 1.4 1.8 16.0 415 1.7 1.4 1.4 21 550 - - - -

95 1.6 1.8 18.0 520 1.9 1.6 1.4 23 680 0.8 1.4 21 660
120 1.6 2.0 21.0 650 1.9 1.6 1.4 24 820 0.8 1.4 23 750

150 1.8 2.0 22.0 760 2.1 1.6 1.4 26 970 0.8 1.4 24 900
185 2.0 2.0 24.0 950 2.3 1.6 1.4 29 1150 0.8 1.4 27 1050
240 2.2 2.0 27.0 1190 2.5 1.6 1.56 32 1400 0.8 1.4 30 1300

300 2.4 2.0 30.0 1420 2.7 1.6 1.56 34 1700 0.8 1.56 33 1600
400 2.6 2.2 34.0 1800 3.0 2.0 1.56 39 2200 0.8 1.56 37 1950
500 3.0 2.2 37.0 2300 3.4 2.0 1.72 43 2750 0.8 1.56 40 2450

630 3.4 2.4 42.0 2880 3.9 2.0 1.88 48 3350 0.8 1.72 45 3100
800 3.4 2.4 47.0 3200 3.9 2.0 1.88 52 4000 0.8 1.88 49 3700
1000 3.4 2.6 51.0 4050 3.9 2.5 2.04 59 4900 0.8 2.04 55 4600

20
1.1 KV TWO CORE ALUMINIUM CONDUCTOR, PVC INSULATED ARMOURED / UN - ARMOURED
PVC OUTER SHEATH CABLE CONFORMING TO IS : 1554 (Part - I) TABLE - 2

UN ARMOURED CABLES ARMOURED CABLES


AYY Single Layer - wire (AYWY) Single Layer - Strip (AYFaY)

Nominal Nominal Minimum Nominal Approx. Approx. Nominal Minimum Approx. Approx. Nominal Minimum Approx. Approx.
size of thickness thickness thickness overall weight of diameter thickness overall weight of thickness thickness overall weight of
conductor of insulation of inner of outer diameter Aluminum of armour of outer diameter Aluminum of armour of outer diameter Aluminum
sheath sheath of cable cable wire sheath of cable cable strip sheath of cable cable

Sq. mm mm mm mm mm Kg /Km mm mm mm Kg /Km mm mm mm Kg /Km

4 1.0 0.3 1.8 15.0 250 1.40 1.24 17.0 520 - - - -


PVC POWER & CONTROL CABLES

6 1.0 0.3 1.8 17.0 300 1.40 1.24 19.0 630 - - - -


10 1.0 0.3 1.8 18.0 370 1.40 1.24 20.0 720 - - - -
16 1.0 0.3 1.8 16.5 300 1.60 1.40 20.0 720 0.8 1.40 18.0 520

25 1.2 0.3 2.0 19.0 440 1.60 1.40 22.0 860 0.8 1.40 20.0 700
35 1.2 0.3 2.0 21.0 520 1.60 1.40 23.5 1000 0.8 1.40 22.0 760
50 1.4 0.3 2.0 23.0 650 1.60 1.56 26.0 1250 0.8 1.40 25.0 950
70 1.4 0.3 2.0 26.0 830 1.60 1.56 29.0 1450 0.8 1.56 27.0 1220

95 1.6 0.4 2.2 30.0 1100 2.00 1.56 33.0 2000 0.8 1.56 30.5 1500
120 1.6 0.4 2.2 32.0 1250 2.00 1.72 35.0 2350 0.8 1.56 32.0 1800
150 1.8 0.4 2.4 34.0 1550 2.00 1.72 37.0 2700 0.8 1.72 34.5 2100
185 2.0 0.5 2.4 38.0 1950 2.00 1.88 41.0 3100 0.8 1.88 37.5 2450

240 2.2 0.5 2.6 42.0 2400 2.50 2.04 47.0 4100 0.8 2.04 42.5 2950
300 2.4 0.6 2.8 46.0 2900 2.50 2.20 49.0 4900 0.8 2.20 47.5 3600
400 2.6 0.7 3.2 51.0 3700 3.15 2.52 57.0 6500 0.8 2.36 52.0 4400

500 3.0 0.7 3.4 53.0 4700 3.15 2.84 63.0 7900 0.8 2.68 55.0 5500
630 3.4 0.7 3.8 64.0 5900 4.00 3.00 71.0 10000 0.8 2.84 65.0 6800

1.1 KV THREE CORE ALUMINIUM CONDUCTOR, PVC INSULATED ARMOURED / UN - ARMOURED


PVC OUTER SHEATH CABLE CONFORMING TO IS : 1554 (Part - I) TABLE - 3

UN ARMOURED CABLES ARMOURED CABLES


AYY Single Layer - wire (AYWY) Single Layer - Strip (AYFY)

Nominal Nominal Minimum Nominal Approx. Approx. Nominal Minimum Approx. Approx. Nominal Minimum Approx. Approx.
size of thickness thickness thickness overall weight of diameter thickness overall weight of thickness thickness overall weight of
conductor of insulation of inner of outer diameter Aluminum of armour of outer diameter Aluminum of armour of outer diameter Aluminum
sheath sheath of cable cable wire sheath of cable cable strip sheath of cable cable

Sq. mm mm mm mm mm Kg /Km mm mm mm Kg /Km mm mm mm Kg /Km

4 1.0 0.3 1.8 16.0 270 1.4 1.24 18.0 600 - - - -


6 1.0 0.3 1.8 17.5 350 1.4 1.24 19.5 680 - - - -
10 1.0 0.3 1.8 19 410 1.4 1.24 21.0 820 - - - -
16 1.0 0.3 1.8 19 400 1.6 1.40 21.0 850 0.8 1.40 20.0 630

25 1.2 0.3 2.0 22.0 630 1.6 1.40 24.0 1150 0.8 1.40 23.0 900
35 1.2 0.3 2.0 24.0 700 1.6 1.40 27.0 1250 0.8 1.40 24.0 1000
50 1.4 0.3 2.0 27.0 920 1.6 1.56 30.0 1550 0.8 1.56 28.0 1300
70 1.4 0.4 2.2 30.0 1200 2.0 1.56 33.5 2100 0.8 1.56 31.0 1600

95 1.6 0.4 2.2 33.5 1550 2.0 1.72 38.0 2600 0.8 1.56 35.0 2000
120 1.6 0.4 2.2 36.0 1800 2.0 1.72 40.0 2900 0.8 1.72 37.0 2300
150 1.8 0.5 2.4 40.0 2200 2.0 1.88 44.0 3500 0.8 1.88 42.0 2800
185 2.0 0.5 2.6 44.0 2700 2.5 2.04 49.0 4500 0.8 1.88 45.5 3300

240 2.2 0.6 2.8 49.5 3450 2.5 2.20 54.0 5500 0.8 2.2 51.0 4200
300 2.4 0.6 3.0 54.5 4200 2.5 2.36 60.0 6500 0.8 2.36 56.0 5000
400 2.6 0.7 3.4 61.5 5400 3.15 2.68 68.0 8600 0.8 2.52 63.0 6300

500 3.0 0.7 3.6 68.5 6850 3.15 3.00 74.0 11000 0.8 2.84 70.0 7800
630 3.4 0.7 4.0 76.5 8700 4.00 3.00 84.0 14000 0.8 3.00 78.0 9650

21
1.1 KV 3 1/2 CORE ALUMINIUM CONDUCTOR, PVC INSULATED ARMOURED / UN - ARMOURED
PVC OUTER SHEATH CABLE CONFORMING TO IS : 1554 (Part - I) TABLE - 4

UN ARMOURED CABLES ARMOURED CABLES


AYY Single Layer - wire (AYWY) Single Layer - Strip (AYFaY)

Nominal Nominal Minimum Nominal Approx. Approx. Nominal Minimum Approx. Approx. Nominal Minimum Approx. Approx.
size of thickness thickness thickness overall weight of diameter thickness overall weight of thickness thickness overall weight of
conductor of insulation of inner of outer diameter Aluminum of armour of outer diameter Aluminum of armour of outer diameter Aluminum
Main/Neutral sheath sheath of cable cable wire sheath of cable cable strip sheath of cable cable

Sq. mm mm mm mm mm Kg /Km mm mm mm Kg /Km mm mm mm Kg /Km

25 1.2 / 1.0 0.3 2.0 23.5 660 1.6 1.40 26.0 1200 0.8 1.40 24.0 920
PVC POWER & CONTROL CABLES

35 1.2 / 1.0 0.3 2.0 25.0 800 1.6 1.40 28.0 1400 0.8 1.40 26.0 1100

50 1.4 / 1.2 0.3 2.0 28.0 1000 1.6 1.56 33.0 1900 0.8 1.56 29.0 1400
70 1.4 / 1.2 0.4 2.2 32.0 1350 2.0 1.56 36.0 2300 0.8 1.56 33.0 1800

95 1.6 / 1.4 0.4 2.2 36.0 1750 2.0 1.72 41.0 2900 0.8 1.56 37.0 2200
120 1.6 / 1.4 0.5 2.4 39.5 2150 2.0 1.88 44.0 3300 0.8 1.72 40.0 2650

150 1.8 / 1.4 0.5 2.4 43.0 2500 2.0 1.88 48.0 3900 0.8 1.88 44.0 3100
185 2.0 / 1.6 0.5 2.6 47.0 3100 2.5 2.04 53.0 5000 0.8 2.04 48.5 3700
240 2.2 / 1.6 0.6 3.0 53.5 4000 2.5 2.36 59.5 6300 0.8 2.2 54.5 4750

300 2.4 / 1.8 0.6 3.2 59.0 4800 3.15 2.52 67.0 8000 0.8 2.36 60.0 5700
400 2.6 / 2.0 0.7 3.4 66.0 6200 3.15 2.68 74.0 9600 0.8 2.68 67.0 7000
500 3.0 / 2.2 0.7 3.8 76.0 7900 4.00 3.00 83.0 13400 0.8 2.84 76.0 8800
630 3.4 / 2.4 0.7 4.0 86.0 9900 4.00 3.00 91.5 15900 0.8 3.00 85.0 11000

1.1 KV FOUR CORE ALUMINIUM CONDUCTOR, PVC INSULATED ARMOURED / UN - ARMOURED


PVC OUTER SHEATH CABLE CONFORMING TO IS : 1554 (Part - I) TABLE - 5

UN ARMOURED CABLES ARMOURED CABLES


AYY Single Layer - wire (AYWY) Single Layer - Strip (AYFY)

Nominal Nominal Minimum Nominal Approx. Approx. Nominal Minimum Approx. Approx. Nominal Minimum Approx. Approx.
size of thickness thickness thickness overall weight of diameter thickness overall weight of thickness thickness overall weight of
conductor of insulation of inner of outer diameter Aluminum of armour of outer diameter Aluminum of armour of outer diameter Aluminum
sheath sheath of cable cable wire sheath of cable cable strip sheath of cable cable

Sq. mm mm mm mm mm Kg /Km mm mm mm Kg /Km mm mm mm Kg /Km

4 1.0 0.3 1.8 16.5 330 1.4 1.24 19.0 660 - - - -


6 1.0 0.3 1.8 18 400 1.4 1.24 21.0 770 - - - -
10 1.0 0.3 1.8 20 500 1.6 1.40 22.0 820 0.8 1.40 21.0 750
16 1.0 0.3 2 20 520 1.6 1.40 24.0 1000 0.8 1.40 23.0 800

25 1.2 0.3 2.0 24.0 700 1.6 1.40 26.5 1300 0.8 1.40 25.0 1000
35 1.2 0.3 2.0 26.0 900 1.6 1.56 29.0 1500 0.8 1.40 27.0 1200

50 1.4 0.4 2.2 30.0 1200 2.0 1.56 33.5 2100 0.8 1.56 31.0 1550
70 1.4 0.4 2.2 33.5 1500 2.0 1.56 37.0 2500 0.8 1.56 34.0 1900

95 1.6 0.4 2.4 38.0 2000 2.0 1.72 41.5 3100 0.8 1.72 39.0 2500
120 1.6 0.5 2.4 41.0 2350 2.0 1.88 45.0 3700 0.8 1.88 42.0 2900

150 1.8 0.5 2.6 45.5 2900 2.5 2.04 50.0 4750 0.8 1.88 47.0 3500
185 2.0 0.6 2.8 50.0 3600 2.5 2.2 55.0 5700 0.8 2.04 52.0 4200
240 2.2 0.6 3.0 56.0 4500 2.5 2.36 61.0 6800 0.8 2.36 58.0 5300

300 2.4 0.7 3.4 61.5 6100 3.15 2.68 68.0 9200 0.8 2.52 64.0 6900
400 2.6 0.7 3.6 69.0 6900 3.15 2.84 76.0 10800 0.8 2.84 70.0 8000
500 3.0 0.7 4.0 81.0 8600 4.00 3.00 85.5 15000 0.8 3.00 80.0 10400
630 3.4 0.7 4.0 92.0 10800 4.00 3.00 95.5 17800 0.8 3.00 91.0 12900

22
1.1 KV 1.5 Sq.mm COPPER CONDUCTOR , PVC INSULATED ARMOURED / UN - ARMOURED
PVC OUTER SHEATH COPPER CONTROL CABLE CONFORMING TO IS : 1554 (Part - I) TABLE - 6

UN ARMOURED CABLES ARMOURED CABLES


YY Single Layer - wire (YWY) Single Layer - Strip (YFY)

Number Nominal Minimum Nominal Approx. Approx. Nominal Minimum Approx. Approx. Nominal Minimum Approx. Approx.
of cores thickness thickness thickness overall weight of diameter thickness overall weight of thickness thickness overall weight of
of insulation of inner of outer diameter cable of armour of outer diameter cable of armour of outer diameter cable
sheath sheath of cable wire sheath of cable strip sheath of cable

mm mm mm mm Kg /Km mm mm mm Kg /Km mm mm mm Kg /Km

2 0.8 0.3 1.8 12.5 170.0 1.4 1.24 14.5 410 - - - -


PVC POWER & CONTROL CABLES

3 0.8 0.3 1.8 13.0 200.0 1.4 1.24 15.0 460 - - - -


4 0.8 0.3 1.8 14.0 240.0 1.4 1.24 16.0 520 - - - -
5 0.8 0.3 1.8 15.0 300.0 1.4 1.24 17.0 590 - - - -

6 0.8 0.3 1.8 16.0 320.0 1.4 1.24 18.0 630 - - - -


7 0.8 0.3 1.8 16.0 340.0 1.4 1.24 18.0 650 - - - -
8 0.8 0.3 1.8 17.0 380.0 1.4 1.24 19.0 720 - - - -
9 0.8 0.3 1.8 18.0 430.0 1.4 1.24 20.0 800 - - - -

10 0.8 0.3 1.8 19.0 460.0 1.4 1.40 22.0 900 - - - -


12 0.8 0.3 1.8 20.0 520.0 1.6 1.40 23.0 1010 0.8 1.24 21.0 800
14 0.8 0.3 1.8 21.0 580.0 1.6 1.40 24.0 1100 0.8 1.4 22.0 870
16 0.8 0.3 1.8 22.0 670.0 1.6 1.40 25.0 1200 0.8 1.4 23.5 970

19 0.8 0.3 2.0 23.0 750.0 1.6 1.40 26.0 1320 0.8 1.4 24.0 1060
24 0.8 0.3 2.0 26.5 940.0 1.6 1.40 29.0 1600 0.8 1.4 27.5 1300
27 0.8 0.3 2.0 27.0 1020.0 1.6 1.40 30.0 1720 0.8 1.40 28.0 1400
30 0.8 0.3 2.0 28.0 1100.0 1.6 1.40 31.0 1800 0.8 1.40 29.0 1500

37 0.8 0.3 2.0 30.0 1300.0 1.6 1.40 33.0 2050 0.8 1.40 31.0 1700
44 0.8 0.3 2.0 33.5 1600.0 1.6 1.56 37.0 2400 0.8 1.56 34.5 2050
61 0.8 0.4 2.2 38.0 2100.0 2.0 1.56 41.0 3300 0.8 1.56 38.0 2600

1.1 KV 2.5 Sq.mm COPPER CONDUCTOR , PVC INSULATED ARMOURED / UN - ARMOURED


PVC OUTER SHEATH COPPER CONTROL CABLE CONFORMING TO IS : 1554 (Part - I) TABLE - 7

UN ARMOURED CABLES ARMOURED CABLES


YY Single Layer - wire (YWY) Single Layer - Strip (YFY)

Number Nominal Minimum Nominal Approx. Approx. Nominal Minimum Approx. Approx. Nominal Minimum Approx. Approx.
of cores thickness thickness thickness overall weight of diameter thickness overall weight of thickness thickness overall weight of
of insulation of inner of outer diameter cable of armour of outer diameter cable of armour of outer diameter cable
sheath sheath of cable wire sheath of cable strip sheath of cable

mm mm mm mm Kg /Km mm mm mm Kg /Km mm mm mm Kg /Km

2 0.9 0.3 1.8 13.0 220 1.4 1.24 16.0 510 - - - -


3 0.9 0.3 1.8 14 270 1.4 1.24 17.0 560 - - - -
4 0.9 0.3 1.8 15 310 1.4 1.24 18.0 640 - - - -

5 0.9 0.3 1.8 16 360 1.4 1.24 19.0 700 - - - -


6 0.9 0.3 1.8 17.0 410 1.4 1.24 20.0 820 - - - -
7 0.9 0.3 1.8 17.0 460 1.4 1.24 20.0 850 - - - -

8 0.9 0.3 1.8 18.0 520 1.4 1.4 21.5 980 - - - -


9 0.9 0.3 1.8 19.0 580 1.6 1.4 23.5 1100 0.8 1.4 22 900
10 0.9 0.3 1.8 21.0 620 1.6 1.4 25.0 1200 0.8 1.4 24 940

12 0.9 0.3 2.0 22.0 720 1.6 1.4 26.0 1300 0.8 1.4 24.5 1060
14 0.9 0.3 2 23.0 810 1.6 1.4 27.0 1420 0.8 1.4 25.0 1150
16 0.9 0.3 2.0 24.0 940 1.6 1.4 29.0 1600 0.8 1.4 27.0 1280

19 0.9 0.3 2.0 25.0 1050 1.6 1.40 30.0 1700 0.8 1.4 28.0 1400
24 0.9 0.3 2.0 28.0 1300 1.6 1.56 34.0 2100 0.8 1.4 32.0 1720
27 0.9 0.3 2.0 29.0 1430 1.6 1.56 35.0 2280 0.8 1.4 33.0 1860

30 0.9 0.3 2.0 30.0 1560 1.6 1.56 36.0 2400 0.8 1.56 34.0 2020
37 0.9 0.4 2.2 32.0 1880 2.0 1.56 39.0 3000 0.8 1.56 36.0 2400

44 0.9 0.4 2.2 37.0 2250 2.0 1.56 43.0 3600 0.8 1.56 40.0 2800
61 0.9 0.4 2.2 40.0 2950 2.0 1.72 48.0 4450 0.8 1.56 45.0 3600

23
CALCULATED VALUE OF A.C. RESISTANCE OF ALUMINIUM CONDUCTOR, REACTANCE & CAPACITANCE OF PVC CABLE TABLE - 8

Nominal Reactance @ 50Hz (Ohm / Km) Capacitance @ 50Hz (M Farads / Km)


AC resistance
size of
@ 700C
conductor Single Core Cables Single Core Cables
Twin & Twin &
Multicore Multicore
(Sq.mm) Ohm / km Unarmoured Armoured Unarmoured Armoured

4 8.89 0.132 0.153 0.098 0.80 0.50 0.24


6 5.53 0.127 0.148 0.096 0.68 0.55 0.26
10 3.70 0.118 0.138 0.091 0.82 0.66 0.32

16 2.29 0.110 0.128 0.085 1.00 0.80 0.41


PVC POWER & CONTROL CABLES

25 1.44 0.105 0.120 0.083 1.06 0.88 0.41


35 1.04 0.100 0.114 0.082 1.20 1.00 0.46

50 0.769 0.098 0.110 0.082 1.22 1.02 0.48


70 0.532 0.091 0.103 0.076 1.44 1.20 0.56
95 0.384 0.088 0.101 0.076 1.48 1.26 0.57

120 0.302 0.086 0.096 0.075 1.60 1.42 0.62


150 0.248 0.085 0.094 0.074 1.60 1.42 0.63
185 0.198 0.084 0.092 0.074 1.61 1.43 0.63
0.073
240 0.152 0.082 0.090 1.70 1.52 0.66
300 0.122 0.080 0.088 0.073 1.72 1.55 0.68
400 0.096 0.080 0.088 0.072 1.80 1.60 0.71

CURRENT RATING (A.C.) FOR MULTI CORE 650 / 1100 VOLTS ARMOURED OR UNARMOURED ALUMINIUM / COPPER PVC
& HR PVC CABLES CONFORMING TO IS : 1554 (Part - 1) TABLE - 9
GENERAL PURPOSE INSULATION HEAT - RESISTANCE INSULATION
Nominal size
of conductor ALUMINIUM CONDUCTOR COPPER CONDUCTOR ALUMINIUM CONDUCTOR COPPER CONDUCTOR

Laid in Ground Laid in Air Laid in Ground Laid in Air Laid in Ground Laid in Air Laid in Ground Laid in Air

Sq.mm Amp. Amp. Amp. Amp. Amp. Amp. Amp. Amp.

1.5 16 13 21 17 18 16 24 21
2.5 21 18 27 24 24 22 30 28
4 28 23 36 30 32 28 41 37

6 35 30 45 39 42 36 51 47
10 46 40 60 52 57 48 69 63
16 60 50 77 66 71 62 88 80

25 76 70 99 90 94 85 113 110
35 92 86 120 110 120 104 137 134

50 110 105 145 135 151 127 166 164


70 135 130 175 165 182 157 200 198

95 165 155 210 200 224 188 240 240


120 185 180 240 230 254 218 275 276

150 210 205 270 265 290 248 309 318


185 235 240 300 305 333 290 343 366
240 275 280 345 355 393 339 395 420

300 305 315 385 400 442 381 440 480


400 335 375 425 435 508 450 486 546

24
CURRENT RATING (A.C.) FOR THREE SINGLE CORE 650 / 1100 VOLTS PVC CABLES CONFORMING TO IS : 1554 (Part - 1) TABLE - 10

Nominal size ALUMINIUM CONDUCTOR COPPER CONDUCTOR


of conductor Laid in Ground Laid in Air Laid in Ground Laid in Air

Sq.mm Amp. Amp. Amp. Amp.

1.5 17 15 22 20
2.5 24 21 30 27
4 31 27 39 35

6 39 35 49 44
10 51 47 65 60
PVC POWER & CONTROL CABLES

16 66 64 85 82
25 86 84 110 110

35 100 105 130 130


50 120 130 155 165
70 140 155 190 205
95 175 190 220 245

120 195 220 250 280


150 220 250 280 320
185 240 290 305 370
240 270 335 345 425

300 295 380 375 475


400 325 435 400 550
500 345 480 425 590

630 390 550 470 660


800 450 610 - -
1000 500 680 - -

CURRENT RATING (A.C.) FOR COPPER CONDUCTOR 1.1 KV PVC INSULATED CONTROL CABLES
CONFORMING TO IS : 1554 (Part - 1) TABLE - 11
GENERAL PURPOSE HEAT - RESISTANCE GENERAL PURPOSE HEAT - RESISTANCE
INSULATION INSULATION INSULATION INSULATION
1.5 Sq.mm 2.5 Sq.mm 1.5 Sq.mm 2.5 Sq.mm 1.5 Sq.mm 2.5 Sq.mm 1.5 Sq.mm 2.5 Sq.mm
No. of No. of
Cores Laid in Laid Laid in Laid in Laid in Laid in Laid in Laid in Cores Laid in Laid Laid in Laid in Laid in Laid in Laid in Laid in
Ground in Air Ground Air Ground Air Ground Air Ground in Air Ground Air Ground Air Ground Air

Amp. Amp. Amp. Amp. Amp. Amp. Amp. Amp. Amp. Amp. Amp. Amp. Amp. Amp. Amp. Amp.

2 23 20 32 27 26 24 38 32 16 11 9 15 13 13 11 17 15
3 21 17 27 24 24 21 30 28
4 21 17 27 24 24 21 30 28 19 10 9 14 12 11 11 16 14
24 9 8 13 11 10 10 14 13
5 27 17 27 24 24 21 30 28
6 15 13 21 18 17 16 24 21 27 9 8 12 10 10 10 13 12
7 14 13 20 17 16 15 22 20 30 9 7 12 10 10 8 13 12
37 8 7 11 9 9 8 12 10
10 13 11 18 15 15 13 20 16
12 12 10 17 14 14 12 19 16 44 7 7 10 9 8 7 11 10
52 6 6 9 8 7 7 10 10
14 11 10 16 13 13 12 18 15 61 6 6 8 8 7 7 9 9

25
1.1 KV SINGLE CORE ALUMINIUM CONDUCTOR, XLPE INSULATED, ARMOURED / UN-ARMOURED,
PVC OUTER SHEATH CABLES CONFORMING TO IS:7098 (Part - I) TABLE - 12

UN-ARMOURED CABLES ARMOURED CABLES


A2YY Single Layer - Wire (A2XWY) Single Layer - Strip (A2XFaY)

Nominal Nominal Nominal Approx. Approx. Nominal Nominal Minimum Approx. Approx. Nominal Minimum Approx. Approx.
size of thickness thickness overall weight of thickness of diameter thickness overall weight of thickness thickness overall weight of
conductor of insulation of outer diameter Aluminium insulation of armour of outer diameter Aluminium of armour of outer diameter Aluminium
sheath of cable cable wire sheath of cable cable strip sheath of cable cable
Sq. mm mm mm mm Kg/Km mm mm mm mm Kg/Km mm mm mm Kg/Km

4 0.7 1.8 9.0 70 1.0 1.4 1.24 11.5 160 - - - -


XLPE POWER & CONTROL CABLES

6 0.7 1.8 10.0 88 1.0 1.4 1.24 12.5 180 - - - -


10 0.7 1.8 11.0 100 1.0 1.4 1.24 13.0 210 - - - -
16 0.7 1.8 12.0 140 1.0 1.4 1.24 14.0 260 - - - -

25 0.9 1.8 14.0 190 1.2 1.4 1.24 16.0 320 - - - -


35 0.9 1.8 15.0 230 1.2 1.4 1.24 17.0 360 - - - -
50 1.0 1.8 16.0 300 1.3 1.4 1.24 18.0 440 - - - -
70 1.1 1.8 18.0 380 1.4 1.4 1.24 20.0 550 - - - -

95 1.1 1.8 20.0 450 1.4 1.6 1.40 22.0 680 0.8 1.40 20.0 660
120 1.2 1.8 22.0 550 1.5 1.6 1.40 24.0 820 0.8 1.40 22.0 770
150 1.4 2.0 24.0 680 1.7 1.6 1.40 25.5 970 0.8 1.40 24.0 860
185 1.6 2.0 26.0 830 1.9 1.6 1.40 28.0 1100 0.8 1.40 26.5 950

240 1.7 2.0 29.0 1020 2.0 1.6 1.40 30.5 1300 0.8 1.40 29.0 1250
300 1.8 2.0 31.5 1200 2.1 1.6 1.56 33.0 1600 0.8 1.56 31.5 1500
400 2.0 2.2 35.0 1600 2.4 2.0 1.56 38.0 2100 0.8 1.56 35.0 1800
500 2.2 2.2 39.0 1950 2.6 2.0 1.56 41.0 2500 0.8 1.56 39.0 2250

630 2.4 2.2 44.0 2420 2.8 2.0 1.72 45.5 3300 0.8 1.72 43.0 2850
800 2.6 2.4 48.0 3000 3.1 2.0 1.88 51.0 3600 0.8 1.72 48.0 3400
1000 2.8 2.6 52.0 3700 3.3 2.5 2.04 56.0 4300 0.8 1.88 54.0 4100

26
1.1 KV TWO CORE ALUMINIUM CONDUCTOR, XLPE INSULATED, ARMOURED / UN-ARMOURED,
PVC OUTER SHEATH CABLES CONFORMING TO IS:7098 (Part - I) TABLE - 13

UN-ARMOURED CABLES ARMOURED CABLES


A2XY Single Layer - Wire (A2XWY) Single Layer - Strip (A2XFY)

Nominal Nominal Minimum Nominal Approx. Approx. Nominal Minimum Approx. Approx. Nominal Minimum Approx. Approx.
size of thickness thickness thickness overall weight of diameter thickness overall weight of thickness thickness overall weight of
conductor of insulation of inner of outer diameter Aluminium of armour of outer diameter Aluminium of armour of outer diameter Aluminium
sheath sheath of cable cable wire sheath of cable cable strip sheath of cable cable

Sq. mm mm mm mm mm Kg /Km mm mm mm Kg /Km mm mm mm Kg /Km

4 0.7 0.3 1.8 13.5 220 1.40 1.24 16.0 440 - - - -


XLPE POWER & CONTROL CABLES

6 0.7 0.3 1.8 15.0 280 1.40 1.24 17.0 550 - - - -


10 0.7 0.3 1.8 16.0 300 1.40 1.24 18.0 600 - - - -
16 0.7 0.3 1.8 15.0 280 1.40 1.40 18.0 580 - - - -

25 0.9 0.3 2.0 18.0 380 1.60 1.40 21.0 780 0.8 1.40 19.0 600
35 0.9 0.3 2.0 19.5 450 1.60 1.40 22.0 900 0.8 1.40 21.0 700
50 1.0 0.3 2.0 21.5 560 1.60 1.40 24.0 1100 0.8 1.40 22.5 850

70 1.1 0.3 2.0 25.0 770 1.60 1.56 27.0 1300 0.8 1.56 25.0 1050
95 1.1 0.4 2.2 27.5 980 2.00 1.56 30.5 1800 0.8 1.56 28.0 1350
120 1.2 0.4 2.2 29.5 1150 2.00 1.56 33.0 2000 0.8 1.56 30.5 1550

150 1.4 0.4 2.2 33.0 1400 2.00 1.72 36.5 2400 0.8 1.72 34.0 1850
185 1.6 0.5 2.4 37.0 1700 2.00 1.88 40.0 2800 0.8 1.72 37.0 2200
240 1.7 0.5 2.6 42.0 2200 2.50 2.04 45.0 3750 0.8 1.88 41.5 2700

300 1.8 0.6 2.8 45.0 2650 2.50 2.20 49.5 4400 0.8 2.04 45.0 3200
400 2.0 0.6 3.0 51.0 3400 2.50 2.36 55.0 5300 0.8 2.36 51.0 4000
500 2.2 0.7 3.4 56.0 4200 3.15 2.68 62.0 7000 0.8 2.52 57.0 4950
630 2.4 0.7 3.6 62.0 5300 3.15 2.84 67.0 8400 0.8 2.68 62.0 6000

1.1 KV THREE CORE ALUMINIUM CONDUCTOR, XLPE INSULATED, ARMOURED / UN-ARMOURED,


PVC OUTER SHEATH CABLES CONFORMING TO IS:7098 (Part - I) TABLE - 14

UN-ARMOURED CABLES ARMOURED CABLES


A2XY Single Layer - Wire (A2XWY) Single Layer - Strip (A2XFY)

Nominal Nominal Minimum Nominal Approx. Approx. Nominal Minimum Approx. Approx. Nominal Minimum Approx. Approx.
size of thickness thickness thickness overall weight of diameter thickness overall weight of thickness thickness overall weight of
conductor of insulation of inner of outer diameter Aluminium of armour of outer diameter Aluminium of armour of outer diameter Aluminium
sheath sheath of cable cable wire sheath of cable cable strip sheath of cable cable

Sq. mm mm mm mm mm Kg /Km mm mm mm Kg /Km mm mm mm Kg /Km

4 0.7 0.3 1.8 14.0 250 1.40 1.24 16.5 500 - - - -


6 0.7 0.3 1.8 15.5 300 1.40 1.24 17.5 600 - - - -
10 0.7 0.3 1.8 17.0 350 1.40 1.24 19.5 660 - - - -
16 0.7 0.3 1.8 17.0 350 1.60 1.40 20.0 750 0.8 1.24 18.5 540

25 0.9 0.3 2.0 20.5 500 1.60 1.40 23.0 950 0.8 1.40 21.0 750
35 0.9 0.3 2.0 22.0 600 1.60 1.40 25.0 1150 0.8 1.40 23.0 900

50 1.0 0.3 2.0 25.0 780 1.60 1.56 27.5 1400 0.8 1.40 26.0 1050
70 1.1 0.4 2.2 28.5 1050 2.00 1.56 32.0 1900 0.8 1.56 29.5 1450

95 1.1 0.4 2.2 31.0 1300 2.00 1.56 35.0 2300 0.8 1.56 32.0 1700
120 1.2 0.4 2.2 34.0 1600 2.00 1.72 38.0 2700 0.8 1.56 35.0 2050

150 1.4 0.5 2.4 38.0 2000 2.00 1.88 42.0 3200 0.8 1.72 39.0 2450
185 1.6 0.5 2.6 42.0 2400 2.50 2.04 47.0 3800 0.8 1.88 43.0 2700
240 1.7 0.6 2.8 47.0 3050 2.50 2.20 52.0 4900 0.8 2.04 48.0 3650

300 1.8 0.6 3.0 52.0 3800 2.50 2.36 57.0 5800 0.8 2.20 52.0 4400
400 2.0 0.7 3.2 59.0 4700 3.15 2.68 65.0 7800 0.8 2.52 59.0 5500
500 2.2 0.7 3.6 65.0 6000 3.15 2.84 71.0 9400 0.8 2.68 65.0 6700
630 2.4 0.7 3.8 72.0 7500 4.00 3.00 80.0 12000 0.8 2.84 72.0 8300

27
1.1 KV 3 1/2 CORE ALUMINIUM CONDUCTOR, XLPE INSULATED, ARMOURED / UN-ARMOURED,
PVC OUTER SHEATH CABLES CONFORMING TO IS:7098 (Part - I) TABLE - 15

UN-ARMOURED CABLES ARMOURED CABLES


A2XY Single Layer - Wire (A2XWY) Single Layer - Strip (A2XFY)

Nominal Nominal Minimum Nominal Approx. Approx. Nominal Minimum Approx. Approx. Nominal Minimum Approx. Approx.
size of thickness thickness thickness overall weight of diameter thickness overall weight of thickness thickness overall weight of
conductor of insulation of inner of outer diameter Aluminium of armour of outer diameter Aluminium of armour of outer diameter Aluminium
Main/Neutral sheath sheath of cable cable wire sheath of cable cable strip sheath of cable cable
Sq. mm mm mm mm mm Kg/Km mm mm mm Kg/Km mm mm mm Kg/Km

25 0.9/0.7 0.3 2.0 21.5 560 1.60 1.40 24.0 1080 0.8 1.40 22.0 830
XLPE POWER & CONTROL CABLES

35 0.9/0.7 0.3 2.0 23.0 680 1.60 1.40 26.0 1250 0.8 1.40 24.0 950

50 1.0/0.9 0.3 2.0 26.0 880 1.60 1.56 29.0 1550 0.8 1.40 27.0 1200
70 1.1/0.9 0.4 2.2 30.0 1200 2.00 1.56 33.5 2100 0.8 1.56 31.0 1600

95 1.1/1.0 0.4 2.2 33.0 1500 2.00 1.56 36.5 2500 0.8 1.56 34.0 1900
120 1.2/1.1 0.4 2.2 36.5 1850 2.00 1.72 40.5 3000 0.8 1.72 38.0 2350

150 1.4/1.1 0.5 2.4 40.5 2250 2.00 1.88 44.0 3500 0.8 1.72 41.5 2770
185 1.6/1.1 0.5 2.6 45.0 2800 2.50 2.04 49.5 4500 0.8 1.88 46.0 3300
240 1.7/1.2 0.6 2.8 51.0 3500 2.50 2.20 55.0 5500 0.8 2.04 51.5 4200

300 1.8/1.4 0.6 3.0 56.0 4200 2.50 2.36 60.0 6500 0.8 2.20 57.0 4950
400 2.0/1.6 0.7 3.4 63.0 5500 3.15 2.68 68.0 8700 0.8 2.52 64.0 6300
500 2.2/1.7 0.7 3.6 69.5 6800 3.15 2.84 75.5 10700 0.8 2.68 70.0 7850
630 2.4/1.8 0.7 4.0 77.5 8800 4.00 3.00 84.5 14200 0.8 3.00 78.0 9800

1.1 KV FOUR CORE ALUMINIUM CONDUCTOR, XLPE INSULATED, ARMOURED / UN-ARMOURED,


PVC OUTER SHEATH CABLES CONFORMING TO IS:7098 (Part - I) TABLE - 16

UN-ARMOURED CABLES ARMOURED CABLES


A2XY Single Layer - Wire (A2XWY) Single Layer - Strip (A2XFY)

Nominal Nominal Minimum Nominal Approx. Approx. Nominal Minimum Approx. Approx. Nominal Minimum Approx. Approx.
size of thickness thickness thickness overall weight of diameter thickness overall weight of thickness thickness overall weight of
conductor of insulation of inner of outer diameter Aluminium of armour of outer diameter Aluminium of armour of outer diameter cable
sheath sheath of cable cable wire sheath of cable cable strip sheath of cable
Sq. mm mm mm mm mm Kg/Km mm mm mm Kg/Km mm mm mm Kg/Km

4 0.7 0.3 1.8 15.0 280 1.40 1.24 17.0 550 - - - -


6 0.7 0.3 1.8 17.0 330 1.40 1.24 19.0 660 - - - -
10 0.7 0.3 1.8 19.5 400 1.40 1.40 21.0 770 - - - -
16 0.7 0.3 1.8 19.0 430 1.60 1.40 21.0 850 0.8 1.40 20.0 680

25 0.9 0.3 2.0 23.5 600 1.60 1.40 25.0 1150 0.8 1.40 23.0 900
35 0.9 0.3 2.0 24.5 770 1.60 1.40 27.0 1400 0.8 1.40 25.0 1100
50 1.0 0.3 2.0 27.0 950 1.60 1.56 30.0 1650 0.8 1.56 28.0 1350
70 1.1 0.4 2.2 32.0 1350 2.00 1.56 35.0 2300 0.8 1.56 33.0 1750

95 1.1 0.4 2.2 35.0 1700 2.00 1.72 39.0 2800 0.8 1.56 34.0 2150
120 1.2 0.5 2.4 38.5 2100 2.00 1.88 42.0 3200 0.8 1.72 39.0 2600
150 1.4 0.5 2.6 43.0 2600 2.50 2.04 48.0 4200 0.8 1.88 44.0 3150
185 1.6 0.5 2.8 47.5 3150 2.50 2.20 52.0 5000 0.8 2.04 49.0 3800

240 1.7 0.6 3.0 53.0 4000 2.50 2.36 58.0 6000 0.8 2.20 54.0 4700
300 1.8 0.7 3.2 59.0 5400 3.15 2.52 65.0 8300 0.8 2.36 60.0 6300
400 2.0 0.7 3.6 66.0 6100 3.15 2.84 72.0 9400 0.8 2.68 67.0 7000

500 2.2 0.7 3.8 73.0 7600 4.00 3.00 81.0 13000 0.8 2.84 74.0 8650
630 2.4 0.7 4.0 81.0 9500 4.00 3.00 88.0 15000 0.8 3.00 81.0 10900

28
1.1 KV 1.5 Sq.mm SOLID COPPER CONDUCTOR, XLPE INSULATED, ARMOURED / UN-ARMOURED,
PVC OUTER SHEATH COPPER CONTROL CABLES CONFORMING TO IS:7098 (Part - I) TABLE - 17

UN-ARMOURED CABLES ARMOURED CABLES


2XY Single Layer - Wire (2XWY) Single Layer - Strip (2XFY)

Number Nominal Minimum Nominal Approx. Approx. Nominal Minimum Approx. Approx. Nominal Minimum Approx. Approx.
of thickness thickness thickness overall weight of diameter thickness overall weight of thickness thickness overall weight of
cores of insulation of inner of outer diameter cable of armour of outer diameter cable of armour of outer diameter cable
sheath sheath of cable wire sheath of cable strip sheath of cable
Sq. mm mm mm mm mm Kg/Km mm mm mm Kg/Km mm mm mm Kg/Km

2 0.7 0.3 1.8 11.0 160.0 1.4 1.24 13.5 350 - - - -


3 0.7 0.3 1.8 11.5 180.0 1.4 1.24 14.0 410 - - - -
XLPE POWER & CONTROL CABLES

4 0.7 0.3 1.8 12.5 210.0 1.4 1.24 15.0 470 - - - -


5 0.7 0.3 1.8 13.0 240.0 1.4 1.24 15.5 500 - - - -

6 0.7 0.3 1.8 14.0 270.0 1.4 1.24 16.5 580 - - - -


7 0.7 0.3 1.8 14.0 290.0 1.4 1.24 16.5 600 - - - -
8 0.7 0.3 1.8 15.0 300.0 1.4 1.24 17.0 630 - - - -
9 0.7 0.3 1.8 16.0 340.0 1.4 1.24 18.5 700 - - - -

10 0.7 0.3 1.8 17.0 360.0 1.4 1.24 19.5 740 - - - -


12 0.7 0.3 1.8 17.5 410.0 1.4 1.24 20.0 800 - - - -
14 0.7 0.3 1.8 18.5 460.0 1.4 1.40 21.0 900 - - - -
16 0.7 0.3 1.8 19.0 510.0 1.6 1.40 22.5 1050 0.8 1.40 21.0 840

19 0.7 0.3 1.8 20.0 580.0 1.6 1.40 23.0 1150 0.8 1.40 21.5 920
24 0.7 0.3 2.0 21.5 720.0 1.6 1.40 26.0 1400 0.8 1.40 24.0 1100
27 0.7 0.3 2.0 24.0 800.0 1.6 1.40 26.5 1500 0.8 1.40 25.0 1200
30 0.7 0.3 2.0 24.5 850.0 1.6 1.40 27.0 1550 0.8 1.40 25.5 1280

37 0.7 0.3 2.0 26.0 1020.0 1.6 1.40 28.5 1750 0.8 1.40 27.0 1500
44 0.7 0.3 2.0 29.0 1200.0 1.6 1.56 32.0 2050 0.8 1.40 30.5 1700
52 0.7 0.3 2.0 30.0 1350.0 1.6 1.56 33.0 2250 0.8 1.56 31.5 1900
61 0.7 0.4 2.2 32.5 1580.0 2.0 1.56 36.5 2800 0.8 1.56 34.0 2150

1.1 KV 2.5 Sq.mm SOLID COPPER CONDUCTOR, XLPE INSULATED, ARMOURED / UN-ARMOURED,
PVC OUTER SHEATH COPPER CONTROL CABLES CONFORMING TO IS:7098 (Part - I) TABLE - 18

UN-ARMOURED CABLES ARMOURED CABLES


2XY Single Layer - Wire (2XWY) Single Layer - Strip (2XFY)

Number Nominal Minimum Nominal Approx. Approx. Nominal Minimum Approx. Approx. Nominal Minimum Approx. Approx.
of thickness thickness thickness overall weight of diameter thickness overall weight of diameter thickness overall weight of
cores of insulation of inner of outer diameter cable of armour of outer diameter cable of armour of outer diameter cable
sheath sheath of cable wire sheath of cable strip sheath of cable
mm mm mm mm Kg/Km mm mm mm Kg/Km mm mm mm Kg/Km

2 0.7 0.3 1.8 12.0 190 1.4 1.24 14.5 430 - - - -


3 0.7 0.3 1.8 14.0 230 1.4 1.24 15.0 490 - - - -
4 0.7 0.3 1.8 15.0 250 1.4 1.24 16.0 520 - - - -
5 0.7 0.3 1.8 16.0 300 1.4 1.24 17.0 600 - - - -
6 0.7 0.3 1.8 17.0 340 1.4 1.24 18.0 680 - - - -
7 0.7 0.3 1.8 17.0 380 1.4 1.24 18.0 710 - - - -
8 0.7 0.3 1.8 18.0 400 1.4 1.24 19.0 800 - - - -
9 0.7 0.3 1.8 20.0 450 1.4 1.40 20.0 900 - - - -
10 0.7 0.3 1.8 22.0 500 1.6 1.40 22.0 1000 0.8 1.40 20.0 800
12 0.7 0.3 1.8 22.5 580 1.6 1.40 22.5 1100 0.8 1.40 21.0 900
14 0.7 0.3 1.8 23.0 650 1.6 1.40 23.0 1210 0.8 1.40 21.5 1000
16 0.7 0.3 2.0 24.5 720 1.6 1.40 24.5 1320 0.8 1.40 23.0 1100
19 0.7 0.3 2.0 25.0 800 1.6 1.40 25.0 1450 0.8 1.40 23.5 1200
24 0.7 0.3 2.0 28.0 1020 1.6 1.40 28.5 1700 0.8 1.40 27.0 1420
27 0.7 0.3 2.0 29.0 1100 1.6 1.40 29.0 1850 0.8 1.40 27.5 1550
30 0.7 0.3 2.0 30.0 1200 1.6 1.40 29.5 1980 0.8 1.40 28.0 1680
37 0.7 0.3 2.2 32.0 1400 1.6 1.56 32.0 2300 0.8 1.40 30.0 1950
44 0.7 0.4 2.2 36.0 1700 2.0 1.56 36.0 2900 0.8 1.56 34.0 2300
52 0.7 0.4 2.2 37.5 1950 2.0 1.56 38.0 3200 0.8 1.56 35.5 2600
61 0.7 0.4 2.2 39.5 2250 2.0 1.56 40.0 3600 0.8 1.56 37.5 2900

29
3.3 KV, SINGLE CORE, ALUMINIUM CONDUCTOR, XLPE INSULATED, UNSCREENED, ARMOURED / UNARMOURED
AND PVC SHEATHED CABLES CONFORMING TO IS : 7098 ( PART - 2 ) TABLE - 19

UNARMOURED CABLE HARD DRAWN ALUMINIUM WIRE ARMOUR CURRENT RATING


Nominal Nominal Nominal Approx Approx wt Nominal Nominal Minimum Approx Approx wt Direct In Air
area of thickness thickness overall dia of cable thickness dia of thickness overall dia of cable in ground 40°C
conductor of insulation of sheath of cable of insulation Aluminium of sheath of cable 30°C
wire

Sq mm mm mm mm kg/km mm mm mm mm kg/km Amps Amps

25 2.2 1.8 14.0 240 2.5 1.4 1.24 17.0 340 97 104
35 2.2 1.8 15.0 280 2.5 1.4 1.24 18.0 390 115 127
50 2.2 1.8 17.0 330 2.5 1.4 1.4 19.0 460 136 153
70 2.2 1.8 18.0 410 2.5 1.6 1.4 21.0 580 166 192

95 2.2 2.0 20.0 550 2.5 1.6 1.4 23.0 700 196 237
120 2.2 2.0 22.0 620 2.5 1.6 1.4 24.0 790 225 275
HIGH VOLTAGE CABLES

150 2.2 2.0 23.0 720 2.5 1.6 1.4 26.0 900 253 317
185 2.2 2.0 25.0 850 2.5 1.6 1.4 28.0 1050 285 362

240 2.2 2.0 27.0 1040 2.5 1.6 1.56 30.0 1280 330 433
300 2.2 2.0 29.0 1240 2.6 1.6 1.56 33.0 1510 373 504
400 2.2 2.2 33.0 1550 2.6 2.0 1.56 36.0 1900 427 598
500 2.4 2.2 36.0 1930 2.8 2.0 1.56 40.0 2300 485 694

630 2.6 2.2 40.0 2410 3.1 2.0 1.72 44.0 2880 551 815
800 2.8 2.4 45.0 3120 3.3 2.0 1.88 50.0 3680 625 969
1000 3.0 2.6 50.0 3880 3.6 2.5 2.04 55.0 4620 692 1103

3.8 / 6.6 KV, SINGLE CORE, ALUMINIUM CONDUCTOR, XLPE INSULATED,SCREENED, ARMOURED / UNARMOURED
AND PVC SHEATHED CABLES CONFORMING TO IS : 7098 ( PART - 2 ) TABLE - 20
UNARMOURED CABLE HARD DRAWN ALUMINIUM WIRE ARMOUR CURRENT RATING
Nominal
Nominal Nominal Nominal Approx Approx wt Minimum Approx Approx wt Direct
dia of In Air
area of thickness thickness overall dia of cable thickness overall dia of cable in ground
Aluminium 40°C
conductor of insulation of sheath of cable of sheath of cable 30°C
wire
Sq mm mm mm mm kg/km mm mm mm kg/km Amps Amps

25 2.8 1.8 18.0 350 1.6 1.40 20.0 470 97 106


35 2.8 2.0 19.0 420 1.6 1.40 21.0 520 118 130
50 2.8 2.0 20.0 470 1.6 1.40 22.0 580 136 156
70 2.8 2.0 22.0 570 1.6 1.40 24.0 690 166 196

95 2.8 2.0 23.0 680 1.6 1.40 25.0 800 197 239
120 2.8 2.0 25.0 780 1.6 1.40 27.0 910 224 277
150 2.8 2.0 26.0 880 1.6 1.56 28.0 1040 252 318
185 2.8 2.0 28.0 1030 1.6 1.56 30.0 1200 284 368

240 2.8 2.2 31.0 1260 2.0 1.56 33.0 1500 329 440
300 3.0 2.2 33.0 1500 2.0 1.56 36.0 1750 372 509
400 3.3 2.2 37.0 1840 2.0 1.72 40.0 2160 427 602
500 3.5 2.4 41.0 2290 2.0 1.72 43.0 2590 485 699

630 3.5 2.4 44.0 2770 2.0 1.88 48.0 3180 551 817
800 3.5 2.6 49.0 3500 2.5 2.04 53.0 4050 624 965
1000 3.6 2.8 54.0 4280 2.5 2.20 57.0 4860 692 1096

30
6.35 / 11 KV, SINGLE CORE, ALUMINIUM CONDUCTOR, XLPE INSULATED, ARMOURED / UNARMOURED
AND PVC SHEATHED CABLES CONFORMING TO IS : 7098 ( PART - 2 ) TABLE - 21
UNARMOURED CABLE HARD DRAWN ALUMINIUM WIRE ARMOUR CURRENT RATING
Nominal
Nominal Nominal Nominal Approx Approx wt Minimum Approx Approx wt Direct
dia of In Air
area of thickness thickness overall dia of cable thickness overall dia of cable in ground
Aluminium 40°C
conductor of insulation of sheath of cable of sheath of cable 30°C
wire
Sq mm mm mm mm kg/km mm mm mm kg/km Amps Amps

25 3.6 2.0 20.0 420 1.6 1.40 22.0 530 97 107


35 3.6 2.0 21.0 470 1.6 1.40 23.0 590 115 134
50 3.6 2.0 22.0 530 1.6 1.40 24.0 650 135 160
70 3.6 2.0 23.0 630 1.6 1.40 25.0 760 165 200

95 3.6 2.0 25.0 740 1.6 1.40 27.0 880 197 245
120 3.6 2.0 26.0 850 1.6 1.56 29.0 1010 224 286
150 3.6 2.0 28.0 960 1.6 1.56 30.0 1130 251 324
HIGH VOLTAGE CABLES

185 3.6 2.2 30.0 1140 2.0 1.56 33.0 1370 283 373

240 3.6 2.2 32.0 1350 2.0 1.56 35.0 1600 328 445
300 3.6 2.2 35.0 1570 2.0 1.56 37.0 1840 371 513
400 3.6 2.2 38.0 1880 2.0 1.72 41.0 2200 425 603
500 3.6 2.4 41.0 2300 2.0 1.72 44.0 2600 484 705

630 3.6 2.4 45.0 2790 2.0 1.88 48.0 3190 550 821
800 3.6 2.6 49.0 3520 2.5 2.04 53.0 4060 623 964
1000 3.6 2.8 54.0 4280 2.5 2.20 57.0 4880 690 1094

11 / 11 KV, SINGLE CORE, ALUMINIUM CONDUCTOR, XLPE INSULATED, ARMOURED / UNARMOURED


AND PVC SHEATHED CABLES CONFORMING TO IS : 7098 ( PART - 2 ) TABLE - 22
UNARMOURED CABLE HARD DRAWN ALUMINIUM WIRE ARMOUR CURRENT RATING
Nominal
Nominal Nominal Nominal Approx Approx wt Minimum Approx Approx wt Direct
dia of In Air
area of thickness thickness overall dia of cable thickness overall dia of cable in ground
Aluminium 40°C
conductor of insulation of sheath of cable of sheath of cable 30°C
wire
Sq mm mm mm mm kg/km mm mm mm kg/km Amps Amps

25 5.5 2.0 24.0 560 1.6 1.40 26.0 700 97 112


35 5.5 2.0 25.0 620 1.6 1.40 27.0 760 115 137
50 5.5 2.0 26.0 690 1.6 1.56 28.0 860 136 165
70 5.5 2.0 27.0 790 1.6 1.56 30.0 970 166 206

95 5.5 2.0 29.0 920 1.6 1.56 31.0 1100 198 250
120 5.5 2.2 31.0 1060 2.0 1.56 34.0 1300 225 291
150 5.5 2.2 32.0 1180 2.0 1.56 35.0 1430 252 330
185 5.5 2.2 34.0 1340 2.0 1.56 37.0 1610 285 379

240 5.5 2.2 36.0 1570 2.0 1.72 39.0 1880 330 450
300 5.5 2.2 39.0 1800 2.0 1.72 42.0 2140 373 518
400 5.5 2.4 42.0 2170 2.0 1.88 45.0 2560 427 608
500 5.5 2.4 45.0 2570 2.0 1.88 48.0 2980 486 709

630 5.5 2.6 49.0 3130 2.5 2.04 53.0 3680 553 822
800 5.5 2.8 54.0 3890 2.5 2.20 57.0 4480 628 964
1000 5.5 2.8 58.0 4630 2.5 2.20 61.0 5250 697 1090

31
12.7 / 22 KV, SINGLE CORE, ALUMINIUM CONDUCTOR, XLPE INSULATED, ARMOURED / UNARMOURED
AND PVC SHEATHED CABLES CONFORMING TO IS : 7098 ( PART - 2 ) TABLE - 23
UNARMOURED CABLE HARD DRAWN ALUMINIUM WIRE ARMOUR CURRENT RATING
Nominal
Nominal Nominal Nominal Approx Approx wt Minimum Approx Approx wt Direct
dia of In Air
area of thickness thickness overall dia of cable thickness overall dia of cable in ground
Aluminium 40°C
conductor of insulation of sheath of cable of sheath of cable 30°C
wire
Sq mm mm mm mm kg/km mm mm mm kg/km Amps Amps

35 6.0 2.0 26.0 670 1.6 1.40 28.0 810 114 143
50 6.0 2.0 27.0 740 1.6 1.56 29.0 910 134 167
70 6.0 2.0 28.0 840 1.6 1.56 31.0 1030 164 207
95 6.0 2.2 31.0 1000 2.0 1.56 33.0 1240 195 253

120 6.0 2.2 32.0 1120 2.0 1.56 35.0 1360 221 291
150 6.0 2.2 33.0 1240 2.0 1.56 36.0 1500 250 333
HIGH VOLTAGE CABLES

185 6.0 2.2 35.0 1400 2.0 1.56 38.0 1680 280 380
240 6.0 2.2 37.0 1630 2.0 1.72 40.0 1960 326 450

300 6.0 2.2 40.0 1870 2.0 1.72 43.0 2220 367 521
400 6.0 2.4 43.0 2250 2.0 1.88 46.0 2640 420 616
500 6.0 2.6 47.0 2700 2.5 2.04 50.0 3220 478 709
630 6.0 2.6 50.0 3210 2.5 2.04 54.0 3770 545 828

800 6.0 2.8 55.0 3980 2.5 2.2 58.0 4580 618 975
1000 6.0 3.0 59.0 4790 2.5 2.36 63.0 5410 685 1107

19 / 33 KV, SINGLE CORE, ALUMINIUM CONDUCTOR, XLPE INSULATED, ARMOURED / UNARMOURED


AND PVC SHEATHED CABLES CONFORMING TO IS : 7098 ( PART - 2 ) TABLE - 24
UNARMOURED CABLE HARD DRAWN ALUMINIUM WIRE ARMOUR CURRENT RATING
Nominal
Nominal Nominal Nominal Approx Approx wt Minimum Approx Approx wt Direct
dia of In Air
area of thickness thickness overall dia of cable thickness overall dia of cable in ground
Aluminium 40°C
conductor of insulation of sheath of cable of sheath of cable 30°C
wire
Sq mm mm mm mm kg/km mm mm mm kg/km Amps Amps

50 8.8 2.2 33.0 1060 2.0 1.56 36.0 1320 135 170
70 8.8 2.2 35.0 1180 2.0 1.56 37.0 1450 165 212
95 8.8 2.2 36.0 1320 2.0 1.72 39.0 1640 196 258
120 8.8 2.2 38.0 1450 2.0 1.72 41.0 1780 223 297

150 8.8 2.2 39.0 1580 2.0 1.72 42.0 1920 250 339
185 8.8 2.4 42.0 1810 2.0 1.72 44.0 2120 282 386
240 8.8 2.4 44.0 2060 2.0 1.88 47.0 2460 326 464
300 8.8 2.6 46.0 2370 2.5 2.04 50.0 2890 369 526

400 8.8 2.6 49.0 2730 2.5 2.04 53.0 3280 423 617
500 8.8 2.8 53.0 3220 2.5 2.20 57.0 3790 481 713
630 8.8 2.8 56.0 3770 2.5 2.20 60.0 4380 549 832
800 8.8 3.0 61.0 4590 2.5 2.36 65.0 5230 620 978

1000 8.8 3.2 65.0 5360 3.15 2.52 70.0 6380 686 1110

32
1.9 / 3.3 KV & 3.3 / 3.3 KV, THREE CORE, ALUMINIUM CONDUCTOR, XLPE INSULATED, ARMOURED,
AND PVC SHEATHED CABLES CONFORMING TO IS : 7098 ( PART - 2 ) TABLE - 25
ROUND GALVANISED STEEL WIRE ARMOURED FLAT GALVANISED STEEL STRIP ARMOURED CURRENT RATING
Nominal Nominal Nominal Minimum Approx Approx Nominal Minimum Approx Approx
Nominal Direct in
thickness thickness diameter thickness overall weight of dimensions thickness overall weight of In Air
area of ground
of of inner of round of outer diameter cable of flat of outer diameter cable 40°C
conductor 30°C
insulation sheath wire sheath of cable strip sheath of cable

Sq mm mm mm mm mm mm kg/km mm mm mm kg/km Amps Amps

25 2.2 0.3 1.6 1.56 33.0 1360.0 4.0x0.80 1.40 29.5 1070.0 93 97
35 2.2 0.3 1.6 1.56 35.0 1410.0 4.0x0.80 1.56 33.5 1260.0 111 119

50 2.2 0.4 2.0 1.56 35.0 1970.0 4.0x0.80 1.56 32.5 1450.0 132 148
70 2.2 0.4 2.0 1.56 38.0 2340.0 4.0x0.80 1.56 36.0 1760.0 160 179

95 2.2 0.4 2.0 1.72 42.0 2740.0 4.0x0.80 1.72 39.5 2120.0 192 219
HIGH VOLTAGE CABLES

120 2.2 0.5 2.0 1.88 45.0 3130.0 4.0x0.80 1.72 42.5 2430.0 218 253

150 2.2 0.5 2.5 2.04 49.0 3880.0 4.0x0.80 1.88 45.5 2780.0 245 290
185 2.2 0.5 2.5 2.04 53.0 4410.0 4.0x0.80 2.04 49.0 3260.0 275 330

240 2.2 0.6 2.5 2.20 58.0 5240.0 4.0x0.80 2.20 54.0 3960.0 318 391
300 2.2 0.6 2.5 2.36 62.5 6020.0 4.0x0.80 2.20 58.0 4590.0 360 453

400 2.2 0.7 3.15 2.68 70.0 7850.0 4.0x0.80 2.52 64.0 5600.0 410 530

3.8 / 6.6 KV, THREE CORE, ALUMINIUM CONDUCTOR, XLPE INSULATED, ARMOURED,
AND PVC SHEATHED CABLES CONFORMING TO IS : 7098 ( PART - 2 ) TABLE - 26
ROUND GALVANISED STEEL WIRE ARMOURED FLAT GALVANISED STEEL STRIP ARMOURED CURRENT RATING
Nominal Nominal Nominal Minimum Approx Approx Nominal Minimum Approx Approx
Nominal Direct in
thickness thickness diameter thickness overall weight of dimensions thickness overall weight of In Air
area of ground
of of inner of round of outer diameter cable of flat of outer diameter cable 40°C
conductor 30°C
insulation sheath wire sheath of cable strip sheath of cable

Sq mm mm mm mm mm mm kg/km mm mm mm kg/km Amps Amps

25 2.8 0.4 2.00 1.72 38.0 2260.0 4.0x0.80 1.56 36.0 1590.0 94 100
35 2.8 0.4 2.00 1.72 41.0 2470.0 4.0x0.80 1.72 38.0 1790.0 111 121

50 2.8 0.5 2.00 1.88 44.0 2840.0 4.0x0.80 1.72 41.0 2060.0 130 145
70 2.8 0.5 2.00 1.88 47.0 3240.0 4.0x0.80 1.88 45.0 2450.0 160 181

95 2.8 0.5 2.50 2.04 52.0 4140.0 4.0x0.80 1.88 49.0 2870.0 191 221
120 2.8 0.6 2.50 2.20 55.0 4710.0 4.0x0.80 2.04 52.0 3280.0 217 254

150 2.8 0.6 2.50 2.20 58.0 5210.0 4.0x0.80 2.20 55.0 3750.0 243 290
185 2.8 0.6 2.50 2.36 63.0 5960.0 4.0x0.80 2.20 59.0 4320.0 274 330

240 2.8 0.7 3.15 2.52 70.0 7640.0 4.0x0.80 2.36 65.0 5160.0 317 390
300 3.0 0.7 3.15 2.68 76.0 8830.0 4.0x0.80 2.52 71.0 6110.0 358 450

400 3.3 0.7 4.00 3.00 86.0 11770.0 4.0x0.80 2.84 79.0 7550.0 408 525

33
6.6 / 6.6 KV & 6.35 / 11 KV, THREE CORE, ALUMINIUM CONDUCTOR, XLPE INSULATED, ARMOURED,
AND PVC SHEATHED CABLES CONFORMING TO IS : 7098 ( PART - 2 ) TABLE - 27
ROUND GALVANISED STEEL WIRE ARMOURED FLAT GALVANISED STEEL STRIP ARMOURED CURRENT RATING
Nominal Nominal Nominal Minimum Approx Approx Nominal Minimum Approx Approx
Nominal Direct in
thickness thickness diameter thickness overall weight of dimensions thickness overall weight of In Air
area of ground
of of inner of round of outer diameter cable of flat of outer diameter cable 40°C
conductor 30°C
insulation sheath wire sheath of cable strip sheath of cable

Sq mm mm mm mm mm mm kg/km mm mm mm kg/km Amps Amps

25 3.6 0.4 2.0 1.72 42.0 2540.0 4.0x0.80 1.72 40.0 1830.0 93 100
35 3.6 0.5 2.0 1.88 45.0 2890.0 4.0x0.80 1.72 42.0 2050.0 111 121

50 3.6 0.5 2.5 2.04 48.0 3600.0 4.0x0.80 1.88 45.0 2400.0 130 145
70 3.6 0.5 2.5 2.04 52.0 4000.0 4.0x0.80 1.88 48.0 2730.0 160 181

95 3.6 0.6 2.5 2.20 56.0 4660.0 4.0x0.80 2.04 52.0 3210.0 191 221
HIGH VOLTAGE CABLES

120 3.6 0.6 2.5 2.36 59.0 5200.0 4.0x0.80 2.20 56.0 3680.0 217 254

150 3.6 0.6 2.5 2.36 62.0 5640.0 4.0x0.80 2.20 59.0 4050.0 243 290
185 3.6 0.7 3.15 2.52 68.0 7130.0 4.0x0.80 2.36 63.0 4690.0 274 330

240 3.6 0.7 3.15 2.68 74.0 8160.0 4.0x0.80 2.52 69.0 5550.0 317 390
300 3.6 0.7 3.15 2.84 79.0 9300.0 4.0x0.80 2.68 74.0 6520.0 357 450

400 3.6 0.7 4.00 3.00 87.0 11990.0 4.0x0.80 2.84 80.0 7700.0 408 525

11 / 11 KV, THREE CORE, ALUMINIUM CONDUCTOR, XLPE INSULATED, ARMOURED,


AND PVC SHEATHED CABLES CONFORMING TO IS : 7098 ( PART - 2 ) TABLE - 28
ROUND GALVANISED STEEL WIRE ARMOURED FLAT GALVANISED STEEL STRIP ARMOURED CURRENT RATING
Nominal Nominal Nominal Minimum Approx Approx Nominal Minimum Approx Approx
Nominal Direct in
thickness thickness diameter thickness overall weight of dimensions thickness overall weight of In Air
area of ground
of of inner of round of outer diameter cable of flat of outer diameter cable 40°C
conductor 30°C
insulation sheath wire sheath of cable strip sheath of cable

Sq mm mm mm mm mm mm kg/km mm mm mm kg/km Amps Amps

25 5.5 0.5 2.50 2.04 52.0 3860.0 4.0x0.80 1.88 49.0 2570.0 94 110
35 5.5 0.5 2.50 2.20 55.0 4210.0 4.0x0.80 2.04 51.0 2820.0 112 133

50 5.5 0.6 2.50 2.20 58.0 4550.0 4.0x0.80 2.20 54.0 3130.0 131 158
70 5.5 0.6 2.50 2.36 61.0 5140.0 4.0x0.80 2.20 58.0 3560.0 160 197

95 5.5 0.6 3.15 2.52 67.0 6490.0 4.0x0.80 2.36 62.0 4100.0 191 237
120 5.5 0.7 3.15 2.52 70.0 7050.0 4.0x0.80 2.52 65.0 4620.0 217 257

150 5.5 0.7 3.15 2.68 73.0 7670.0 4.0x0.80 2.52 68.0 5030.0 243 292
185 5.5 0.7 3.15 2.84 78.0 8470.0 4.0x0.80 2.68 73.0 5740.0 273 331

240 5.5 0.7 3.15 3.00 83.0 9630.0 4.0x0.80 2.84 78.0 6630.0 316 390
300 5.5 0.7 4.00 3.00 89.0 11890.0 4.0x0.80 3.00 83.0 7600.0 357 448

400 5.5 0.7 4.00 3.00 96.0 13490.0 4.0x0.80 3.00 89.0 8890.0 408 523

34
12.7 / 22 KV, THREE CORE, ALUMINIUM CONDUCTOR, XLPE INSULATED, ARMOURED,
AND PVC SHEATHED CABLES CONFORMING TO IS : 7098 ( PART - 2 ) TABLE - 29
ROUND GALVANISED STEEL WIRE ARMOURED FLAT GALVANISED STEEL STRIP ARMOURED CURRENT RATING
Nominal Nominal Nominal Minimum Approx Approx Nominal Minimum Approx Approx
Nominal Direct in
thickness thickness diameter thickness overall weight of dimensions thickness overall weight of In Air
area of ground
of of inner of round of outer diameter cable of flat of outer diameter cable 40°C
conductor 30°C
insulation sheath wire sheath of cable strip sheath of cable

Sq mm mm mm mm mm mm kg/km mm mm mm kg/km Amps Amps

35 6.0 0.6 2.50 2.20 57.0 4480.0 4.0x0.80 2.04 54.0 3020.0 110 132

50 6.0 0.6 2.50 2.36 60.0 4910.0 4.0x0.80 2.20 56.0 3360.0 129 157

70 6.0 0.6 2.50 2.36 64.0 5430.0 4.0x0.80 2.36 60.0 3840.0 158 194

95 6.0 0.7 3.15 2.52 69.0 6870.0 4.0x0.80 2.36 64.0 4390.0 188 224
HIGH VOLTAGE CABLES

120 6.0 0.7 3.15 2.68 72.0 7410.0 4.0x0.80 2.52 67.0 4840.0 213 257

150 6.0 0.7 3.15 2.68 76.0 8040.0 4.0x0.80 2.68 71.0 5390.0 239 292

185 6.0 0.7 3.15 2.84 80.0 8870.0 4.0x0.80 2.68 75.0 6050.0 269 332

240 6.0 0.7 4.00 3.00 87.0 11150.0 4.0x0.80 2.84 80.0 6960.0 312 390

300 6.0 0.7 4.00 3.00 92.0 12390.0 4.0x0.80 3.00 85.0 7920.0 352 448

400 6.0 0.7 4.00 3.00 98.0 13910.0 4.0x0.80 3.00 92.0 9130.0 402 523

19 / 33 KV, THREE CORE, ALUMINIUM CONDUCTOR, XLPE INSULATED, ARMOURED,


AND PVC SHEATHED CABLES CONFORMING TO IS : 7098 ( PART - 2 ) TABLE - 30
ROUND GALVANISED STEEL WIRE ARMOURED FLAT GALVANISED STEEL STRIP ARMOURED CURRENT RATING
Nominal Nominal Nominal Minimum Approx Approx Nominal Minimum Approx Approx
Nominal Direct in
thickness thickness diameter thickness overall weight of dimensions thickness overall weight of In Air
area of ground
of of inner of round of outer diameter cable of flat of outer diameter cable 40°C
conductor 30°C
insulation sheath wire sheath of cable strip sheath of cable

Sq mm mm mm mm mm mm kg/km mm mm mm kg/km Amps Amps

50 8.8 0.7 3.15 2.68 75.0 7440.0 4.0x0.80 2.52 70.0 4780.0 130 158

70 8.8 0.7 3.15 2.84 79.0 8140.0 4.0x0.80 2.68 74.0 5360.0 158 198

95 8.8 0.7 3.15 3.00 83.0 8890.0 4.0x0.80 2.84 78.0 5890.0 188 236

120 8.8 0.7 4.00 3.00 87.0 10710.0 4.0x0.80 2.84 81.0 6410.0 214 270

150 8.8 0.7 4.00 3.00 90.0 11410.0 4.0x0.80 3.00 84.0 7020.0 239 293

185 8.8 0.7 4.00 3.00 95.0 12380.0 4.0x0.80 3.00 88.0 7750.0 270 348

240 8.8 0.7 4.00 3.00 99.0 13550.0 4.0x0.80 3.00 93.0 8690.0 312 408

300 8.8 0.7 4.00 3.00 104.0 14760.0 4.0x0.80 3.00 98.0 9670.0 352 449

400 8.8 0.7 4.00 3.00 111.0 16480.0 4.0x0.80 3.00 104.0 10970.0 402 522

35
CURRENT RATING FOR XLPE INSULATED COPPER CONDUCTOR 1.1 KV GRADE POWER CABLES TABLE - 31
CABLE IN GROUND CABLE IN AIR

Nominal size Three, Three,


Three Three
of conductor Two Core Three & Half Two Core Three & Half
Single Core Single Core
Cable & Four Core Cable & Four Core
Cable Cable
Cables Cables

Sq.mm Amp. Amp. Amp. Amp. Amp. Amp.

10 77 83 71 79 75 65
16 101 107 92 103 98 83
25 132 144 119 132 131 108
35 156 175 144 152 150 132

50 186 206 174 198 194 162


70 228 256 210 240 244 198
95 264 300 252 297 288 240

120 300 344 288 346 331 276


150 336 388 324 390 381 318
185 366 438 360 444 430 363

240 414 503 410 510 512 426


300 450 565 462 570 581 480
400 500 612 510 660 662 540

500 570 758 602 708 888 784


630 625 865 678 825 1170 906
800 670 - - 986 - -
1000 715 - - 1094 - -

SOLID / STRANDED CONDUCTOR FOR INSULATED CABLES CONFORMING TO IS:8130 TABLE - 32


SOLID CONDUCTOR CLASS-1 STRANDED CONDUCTOR CLASS - 2
Nominal
size of Minimum number of Wires in Conductors Maximum Resistance Conductor at 20°C
Minimum Resistance
conductor Conductor at 200C Circular Conductor Circular Conductor
(non-compacted) Shaped Conductor Plain Copper Aluminium
Sq.mm Plain Copper Aluminium
Copper Aluminium Copper Aluminium Ohm / km Ohm / km
Ohm / km Ohm / km

1.5 12.10 18.10 3 3 - - 12.10 18.10


2.5 7.41 12.10 3 3 - - 7.41 12.10
4 4.61 7.41 7 3 - - 4.61 7.41

6 3.08 4.61 7 3 - - 3.08 4.61


10 - 3.08 7 7 6 - 1.83 3.08
16 - - 7 7 6 6 1.15 1.91

25 - - 7 7 6 6 0.727 1.200
35 - - 7 7 6 6 0.524 0.868
50 - - 19 19 6 6 0.387 0.641

70 - - 19 19 12 12 0.268 0.443
95 - - 19 19 15 15 0.193 0.320
120 - - 37 37 18 15 0.153 0.253

150 - - 37 37 18 15 0.1240 0.206


185 - - 37 37 30 30 0.0991 0.164
240 - - 61 61 34 30 0.0754 0.125

300 - - 61 61 34 30 0.0601 0.1000


400 - - 61 61 53 53 0.0470 0.0778
500 - - 61 61 53 53 0.0366 0.0605
630 - - 91 91 53 53 0.0283 0.0469

36
CALCULATED VALUE OF A.C. RESISTANCE / REACTANCE / CAPACITANCE OF XLPE CABLES TABLE - 33
AC resistance of
Aluminium Conductor. Reactance @ 50Hz (Ohm / Km) Capacitance (Micro Faradas / Km)
Nominal Maximum Operating
size of Temperature
conductor XLPE INSULATED CABLE XLPE INSULATED CABLE
(Ohm/Km) Maximum
Twin & Twin &
Conductor Temperature 90Co Single Core Cables Single Core Cables
Multicore Multicore
(Sq.mm) Ohm / km
Un-armoured Armoured Un-armoured Armoured
4 9.48 0.132 - 0.0927 0.29 - 0.22
6 5.90 0.123 - 0.0884 0.34 - 0.25
10 3.94 0.114 0.134 0.0837 0.43 0.32 0.31
16 2.44 0.108 0.125 0.8080 0.51 0.38 0.36

25 1.54 0.1030 0.120 0.0805 0.49 0.38 0.41


35 1.11 0.0986 0.114 0.0783 0.57 0.44 0.47
50 0.820 0.0937 0.108 0.0750 0.58 0.46 0.50
70 0.567 0.0900 0.102 0.0740 0.63 0.51 0.53

95 0.410 0.0865 0.1000 0.0724 0.73 0.59 0.61


120 0.325 0.0841 0.0968 0.0712 0.74 0.61 0.63
150 0.265 0.0839 0.0941 0.0716 0.73 0.61 0.60
185 0.211 0.0836 0.0932 0.0718 0.69 0.59 0.60

240 0.162 0.0813 0.0900 0.0710 0.74 0.64 0.63


300 0.1300 0.0795 0.0881 0.0705 0.80 0.69 0.67
400 0.1023 0.0787 0.0873 0.0704 0.83 0.70 0.67
500 0.0808 0.0779 0.0859 0.0702 0.83 0.71 0.69

630 0.0648 0.0765 0.0843 0.0698 0.87 0.75 0.73


800 0.0530 0.0750 0.0820 - 0.95 0.86 -
1000 0.0440 0.0690 0.0810 - 0.99 0.88 -

CURRENT RATING FOR XLPE INSULATED ALUMINIUM CONDUCTOR 1.1 KV GRADE POWER CABLES TABLE - 34

CABLE IN GROUND CABLE IN AIR


Nominal size
of conductor SINGLE CORE CABLES SINGLE CORE CABLES
Three, Three,
Two Core Cable Three & Half Two Core Cable Three & Half
Two Cables Three Cables & Four Core Two Cables Three Cables & Four Core

Sq.mm Amp. Amp. Amp. Amp. Amp. Amp. Amp. Amp.

4 42 36 43 34 34 31 39 31
6 52 44 55 43 43 39 50 40
10 69 59 71 57 60 53 67 53

16 90 76 91 73 82 73 88 70
25 116 96 120 94 108 98 117 96
35 139 114 143 113 136 121 145 117

50 162 135 167 133 163 150 176 142


70 199 166 204 164 208 187 221 179
95 241 198 245 196 258 230 271 221

120 273 225 276 223 303 268 316 257


150 305 253 315 249 348 309 362 292
185 347 286 356 262 407 360 420 337

240 407 332 407 326 488 433 497 399


300 458 376 463 367 569 501 578 455
400 518 431 523 418 669 596 678 530

500 592 490 592 470 786 693 786 612


630 666 557 676 529 922 814 913 707
800 737 625 - - 1060 940 - -
1000 814 690 - - 1220 1080 - -

37
CURRENT RATING (A.C.) FOR SHORT CIRCUIT RATING OF XLPE INSULATED
COPPER CONDUCTOR 1.1 KV XLPE INSULATED HEAVY DUTY CABLES
CONTROL CABLES CONF. TO IS:7098 (Part-1) (FOR ONE SECOND DURATION)
XLPE INSULATION TABLE - 36
TABLE - 35
Nominal
1.5 Sq. mm 2.5 Sq. mm size of ALUMINIUM COPPER
conductor CONDUCTOR CONDUCTOR
No. of Laid in Laid in
Laid in Air Laid in Air
Cores Ground Ground
Sq.mm K.Amp. K.Amp.
Amp. Amp. Amp. Amp.
1.5 - 0.210
2 33 29 43 39 2.5 - 0.360
3 25 22 34 30 4 0.380 0.570
4 25 22 34 30 6 0.570 0.860
5 24 21 31 28 10 0.940 1.430
6 22 19 29 26 16 1.500 2.290
7 21 18 27 25
25 2.350 3.580
8 20 18 26 24 35 3.290 5.010
9 19 17 25 22
10 18 16 24 21 50 4.700 7.150
70 6.580 10.010
12 17 15 22 20
14 16 14 21 19 95 8.930 13.590
16 16 14 20 18 120 11.280 17.160

19 15 13 19 17 150 14.100 21.450


21 14 12 18 16 185 17.390 26.460
24 13 12 17 16 240 22.560 34.320

27 13 11 16 15 300 28.200 42.900


30 12 11 15 14 400 37.600 57.200
37 11 10 15 13 500 47.000 71.500

44 11 9 14 12 630 59.220 90.090


52 10 9 13 12 800 75.500 114.300
61 9 8 12 11 1000 94.000 143.000

ALUMINIUM CIRCULAR / COMPACTED CONDUCTORS CALCULATED VALUE OF REACTANCE FOR THREE CORE CABLES TABLE - 38
FOR INSULATED CABLES CONFORMING TO IS : 8130
TABLE - 37 Nominal
Reactance (ohms/km) (at 50Hz)
area
Circular
Minimum number
of wires
Conductor Max D C AC
Nominal 3.3 3.8/6.6 6.35/11 11/11 12.7/22 19/33
resistance resistance (Sq mm)
area Circular Compacted at 20 C 0
KV KV KV KV KV KV
at 900C
Conductor Conductors
25 0.098 0.120 0.125 0.140 - -
Sq mm mm mm (ohm/km) (ohm/km)
35 0.094 0.114 0.119 0.134 0.137 -
25 7 6 1.2000 1.5400
35 7 6 0.8680 1.1100
50 0.086 0.110 0.114 0.128 0.131 0.146
50 19 6 0.6410 0.8220
70 0.084 0.101 0.105 0.118 0.121 0.138
70 19 12 0.4430 0.5680

95 19 15 0.3200 0.4110
95 0.081 0.097 0.101 0.112 0.115 0.128
120 37 15 0.2530 0.3250
120 0.078 0.094 0.098 0.108 0.111 0.124
150 37 15 0.2060 0.2650
185 37 30 0.1640 0.2110
150 0.076 0.092 0.095 0.105 0.108 0.120
240 37 30 0.1250 0.1620
300 61 30 0.1000 0.1300 185 0.075 0.088 0.091 0.101 0.103 0.115

400 61 53 0.0778 0.1020


240 0.073 0.086 0.088 0.097 0.099 0.110
500 61 53 0.0605 0.0804
300 0.072 0.085 0.086 0.094 0.096 0.106
630 91 53 0.0469 0.0639
800 91 53 0.0367 0.0518
400 0.071 0.084 0.083 0.091 0.093 0.102
1000 91 53 0.0291 0.0432

38
CALCULATED VALUE OF REACTANCE FOR THREE SINGLE CORE CABLES
( CABLES IN TREFOIL TOUCHING ) TABLE - 39

Nominal
3.8/6.6 KV 6.35/11 KV 11/11 KV 12.7/22 KV 19/33 KV
area

(Sq mm) Un Arm Arm. Un Arm Arm. Un Arm Arm. Un Arm Arm. Un Arm Arm.

25 0.139 0.149 0.146 0.164 0.154 0.164 - - - -


35 0.132 0.142 0.137 0.156 0.146 0.156 0.149 0.158 - -

50 0.125 0.133 0.128 0.147 0.138 0.147 0.140 0.149 0.153 0.161
70 0.117 0.127 0.121 0.139 0.130 0.139 0.133 0.14 0.144 0.152

95 0.111 0.121 0.115 0.133 0.124 0.132 0.126 0.134 0.137 0.145
120 0.106 0.116 0.111 0.127 0.119 0.126 0.121 0.13 0.131 0.140

150 0.104 0.113 0.108 0.124 0.115 0.124 0.117 0.126 0.128 0.135
185 0.101 0.109 0.105 0.12 0.112 0.120 0.114 0.122 0.123 0.130

240 0.0977 0.105 0.101 0.117 0.108 0.116 0.11 0.118 0.119 0.126
300 0.0955 0.104 0.0976 0.113 0.104 0.112 0.106 0.113 0.115 0.122

400 0.094 0.102 0.0952 0.11 0.102 0.109 0.103 0.11 0.111 0.117
500 0.0928 0.0998 0.0931 0.107 0.0983 0.105 0.1 0.107 0.108 0.113

630 0.0899 0.0964 0.0901 0.104 0.0956 0.102 0.0969 0.103 0.104 0.111
800 0.0881 0.0938 0.0876 0.0998 0.0917 0.0971 0.0934 0.0997 0.0995 0.105

1000 0.0854 0.0918 0.0857 0.0983 0.0899 0.0959 0.0911 0.097 0.0967 0.102

CALCULATED VALUE OF STAR CAPACITANCE FOR THREE CORE CABLES ( AT 50 HZ) TABLE - 40

Nominal
Capacitance (mfd/km)
area

(Sq mm) 3.3 3.8/6.6 6.35/11 11/11 12.7/22 19/33


KV KV KV KV KV KV
25 0.260 0.237 0.198 0.149 - -
35 0.293 0.264 0.219 0.163 0.154 -

50 0.330 0.293 0.242 0.178 0.168 0.132


70 0.382 0.336 0.275 0.201 0.189 0.146

95 0.438 0.381 0.310 0.224 0.210 0.162


120 0.484 0.418 0.339 0.243 0.228 0.174

150 0.530 0.454 0.368 0.262 0.246 0.186


185 0.592 0.504 0.407 0.288 0.269 0.203

240 0.666 0.563 0.453 0.319 0.297 0.222


300 0.741 0.586 0.500 0.350 0.326 0.242

400 0.837 0.605 0.560 0.389 0.362 0.267

39
RATING FACTOR FOR VARIATION IN GROUND AND DUCT TEMPERATURE TABLE- 41
0
Temperature C 15 20 25 30 35 40 45 50 55
Rating Factor
(Maximum conductor
temperature 900C) 1.12 1.08 1.04 1.00 0.96 0.91 0.87 0.82 0.78

For 700C PVC 1.17 1.1 1.06 1.00 0.94 0.87 0.79 0.71 0.61

For 850C HRPVC


1.13 1.09 1.04 1.00 0.95 0.90 0.85 0.80 0.74

RATING FACTOR FOR VARIATION IN AMBIENT AIR TEMPERATURE FOR XLPE CABLES TABLE- 42
0
Temperature C 25 30 35 40 45 50 55 60
Rating Factor
(Maximum conductor
temperature 900C) 1.16 1.11 1.06 1.00 0.94 0.88 0.81 0.74

For 700C PVC 1.25 1.16 1.09 1.00 0.90 0.80 0.74 -

For 850C HRPVC 1.17 1.12 1.06 1.00 0.94 0.87 0.80 0.73

RATING FACTOR GROUP RATING FACTORS FOR CIRCUITS OF


FOR DEPTH OF LAYING THREE SINGLE - CORE CABLES,
(CABLES LAID DIRECT IN TREFOIL LAID 'DIRECT IN THE GROUND TABLE - 44
IN THE GROUND)
TABLE- 43 No. of
Spacing between Trefoil Group Centres (Cm)
Circuits
Depth of 1.1/11 KV
Laying XLPE Touching 20 40 60 80
Cm Cables 2 0.76 0.83 0.87 0.90 0.92

90 1.00 3 0.64 0.72 0.79 0.83 0.86

105 0.99 4 0.58 0.67 0.75 0.80 0.84

5 0.53 0.63 0.71 0.77 0.81


120 0.97
6 0.50 0.60 0.69 0.76 0.80
150 0.95
7 0.47 0.58 0.67 0.74 0.79

180 0.94
8 0.45 0.56 0.66 0.73 -
200 0.93
9 0.43 0.55 0.65 0.73 -
10 0.42 0.54 0.64 - -
250 0.91
300 0.90 11 0.41 0.53 0.64 - -
or more 12 0.40 0.52 0.63 - -

40
RATING FACTORS FOR CABLES LAID ON RACKS IN AIR RATING FACTORS FOR THREE SINGLE CORE CABLES
WITH CABLE TOUCHING, TRAYS ARE IN TIERS SPACED IN TREFOIL ON RACKS IN AIR
BY 30cm AND CLEARANCE BETWEEN THE WALL AND (WITH SPACING BETWEEN CABLES EQUAL TO
CABLE IS 25cm TWICE THE CABLE DIAMETER)
TABLE - 45 TABLE - 46

No. of Number of Cables per Rack No. of Number of Cables per Rack
Racks Racks
1 2 3 6 9 1 2 3
1 1.00 0.84 0.80 0.75 0.73 1 1.00 0.98 0.96
2 1.00 0.80 0.76 0.71 0.69 2 1.00 0.95 0.93
3 1.00 0.78 0.74 0.70 0.68 3 1.00 0.94 0.92
6 1.00 0.76 0.72 0.68 0.66 6 1.00 0.93 0.90

GROUP RATING FACTORS FOR MULTICORE CABLES IN RATING FACTORS FOR MULTICORE CABLES LAID ON RACKS IN AIR
GROUND HORIZONTAL FORMATION TABLE - 47 (WITH CABLE SPACING BETWEEN CABLES
EQUAL TO DIAMETER OF CABLE) TABLE - 48
Number of Spacing
Cables in group Number of Number of cables per rack
Touching 15 cm 30 cm 45 cm
racks
1 2 3 6 9
2 0.78 0.81 0.85 0.88
3 0.68 0.71 0.76 0.79 1 1.00 0.98 0.96 0.93 0.92
4 0.61 0.65 0.71 0.75 2 1.00 0.95 0.93 0.90 0.89
5 0.56 0.60 0.67 0.72
3 1.00 0.94 0.92 0.89 0.88
6 0.53 0.57 0.64 0.69 6 1.00 0.93 0.90 0.87 0.86
7 0.50 0.55 0.62 0.67
8 0.48 0.53 0.60 0.66
9 0.46 0.51 0.59 0.65
10 0.45 0.50 0.58 0.64

RATING FACTORS FOR VARIATION IN THERMAL RESISTIVITY OF SOIL FOR THREE


SINGLE - CORE CABLES AND THREE CORE XLPE CABLES LAID DIRECT IN THE GROUND TABLE - 49
Nominal Three single core cables Three core cables
size of
Thermal Resistivity of Soil in oC CM/W Thermal Resistivity of Soil in oC CM/W
conductor
Sq. mm 100 120 150 200 250 300 100 120 150 200 250 300
25 1.17 1.09 1.00 0.88 0.80 0.74 1.16 1.08 1.00 0.90 0.82 0.75
35 1.18 1.10 1.00 0.88 0.80 0.74 1.16 1.08 1.00 0.90 0.81 0.75

50 1.19 1.10 1.00 0.88 0.80 0.73 1.16 1.08 1.00 0.88 0.81 0.75
70 1.19 1.10 1.00 0.88 0.80 0.73 1.16 1.09 1.00 0.88 0.81 0.75
95 1.19 1.10 1.00 0.88 0.79 0.73 1.16 1.09 1.00 0.88 0.81 0.75

120 1.19 1.10 1.00 0.88 0.79 0.73 1.16 1.09 1.00 0.88 0.81 0.75
150 1.19 1.10 1.00 0.88 0.79 0.73 1.16 1.09 1.00 0.88 0.81 0.75
185 1.19 1.10 1.00 0.88 0.79 0.72 1.16 1.09 1.00 0.88 0.81 0.75

240 1.20 1.11 1.00 0.88 0.79 0.72 1.17 1.09 1.00 0.88 0.81 0.75
300 1.20 1.11 1.00 0.87 0.79 0.72 1.17 1.09 1.00 0.88 0.81 0.75
400 1.20 1.11 1.00 0.87 0.79 0.72 1.17 1.09 1.00 0.88 0.81 0.75

500 1.20 1.11 1.00 0.87 0.79 0.72 1.17 1.09 1.00 0.88 0.81 0.74
630 1.21 1.11 1.00 0.87 0.78 0.72 - - - - - -

800 1.21 1.11 1.00 0.87 0.78 0.72 - - - - - -


1000 1.21 1.11 1.00 0.87 0.78 0.72 - - - - - -

41
Estimated Voltage Drops in XLPE Cables (Aluminium Conductor)
(Voltage drop unit: Volts/Km/Amps) TABLE- 50
Cable Sqmm.

Cores 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000

Single
18.98 11.80 7.88 4.90 3.08 2.23 1.65 1.15 0.83 0.66 0.55 0.44 0.35 0.30 0.24 0.23 0.21 0.20 0.18
Core
Multi
16.44 10.22 6.82 4.24 2.67 1.94 1.44 1.00 0.70 0.56 0.48 0.40 0.30 0.26 0.22 0.20 0.18 ---- ----
Core
* Above voltage drops (volts/km/amps) to be multiplied with rated current and length of cable in K.M. to calculate total voltage drop in particular length and size of Cables.

Estimated Voltage Drops in XLPE Cables 1100 Volts Armoured Control Cables (Copper Conductor)
(Voltage drop unit: Volts/Km) TABLE- 51
No. of Cores

Sqmm. 2 3 4 5 6 7 8 9 10 12 14 16 19 24 27 30 37 44 52 61

1.5 725 859 859 644 564 537 510 483 483 456 430 403 376 349 322 295 295 268 268 242

2.5 584 691 691 522 445 430 415 399 384 369 338 322 307 276 261 230 230 215 215 200

* Above voltage drops (volts/km/amps) to be multiplied with rated current and length of cable in K.M. to calculate total voltage drop in particular length and size of Cables.

"The above Data are approximate and subject to manufacturing tolerance"

GROUP RATING FACTORS FOR TWIN AND MULTI - CORE GROUP RATING FACTORS FOR TWIN AND MULTI - CORE
CABLES IN HORIZONTAL FORMATION, LAID DIRECT IN THE CABLES IN TIER FORMATION, LAID DIRECT IN THE
GROUND TABLE - 52 GROUND TABLE - 53
No. of No. of No. of
Spacing of Cables (Centre to Centre) Spacing of Cables (Centre to Centre)
Cables Cables Tiers

Touching 15 Cm 30 Cm 45 Cm 60 Cm Touching 15 Cm 30 Cm 45 Cm 60 Cm
2 0.80 0.84 0.87 0.90 0.91 2 1 0.88 0.84 0.87 0.90 0.91
3 0.68 0.74 0.79 0.83 0.86 3 1 0.68 0.74 0.79 0.83 0.86
4 0.62 0.69 0.75 0.80 0.83 4 2 0.60 0.66 0.73 0.77 0.79

5 0.58 0.65 0.72 0.77 0.80 5 2 0.55 0.61 0.68 0.71 0.73
6 0.55 0.62 0.69 0.75 0.78 6 2 0.51 0.57 0.63 0.67 0.69
7 0.52 0.59 0.67 0.73 0.77 7 3 0.48 0.54 0.59 0.63 0.64

8 0.50 0.57 0.66 0.72 0.75 8 3 0.46 0.51 0.56 0.60 0.61
9 0.48 0.55 0.65 0.71 0.75 9 3 0.44 0.48 0.53 0.57 0.58
10 0.46 0.54 0.64 0.70 0.74 10 4 0.42 0.47 0.52 0.55 0.56

11 0.45 0.53 0.63 0.70 0.74 11 4 0.41 0.46 0.50 0.54 0.55
12 0.44 0.52 0.62 0.69 0.73 12 4 0.40 0.45 0.49 0.53 0.54

42
1100 Volts Single Core and Three Core Armoured PVC Cables (Aluminium Conductor) TABLE- 54

Unit Sq.mm. 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000
Voltage Drop per
1000 meter length of Single
215 182 163 132 121 107 99 87 80 71 68 61 61 61 59
Cable Laid direct Core
in ground Volts
3.5 190 166 147 125 112 99 91 81 76 69 60 54 51 ---- ----
Core

1.5 Sqmm & 2.5 Sqmm 1100 Volts Armoured Control PVC Cables with Copper Conductor TABLE- 55

Unit Core 2 3 4 5 6 7 10 12 14 16 19 24 27 30 37
Voltage Drop per
1000 meter length of 1.5
Cable Laid direct Sqmm 666 608 608 463 434 405 376 348 318 318 290 261 261 261 232
in ground Volts
2.5
Sqmm 567 479 479 408 372 355 319 301 284 266 248 231 213 213 195

CURRENT RATING (A.C.) FOR MULTI CORE


650 / 1100 VOLTS ARMOURED OR UNARMOURED
ALUMINIUM / COPPER PVC CABLES CONFORMING
TO IS : 1554 (Part - 1) TABLE - 56
ALUMINIUM COPPER
Nominal
CONDUCTOR CONDUCTOR
size of
conductor G.P Insulation G.P Insulation

Sq.mm K.Amp. K.Amp.

1.5 0.114 0.173


2.5 0.190 0.288
4 0.304 0.460
6 0.456 0.690

10 0.760 1.150
16 1.216 1.840
25 1.900 2.875

35 2.660 4.025
50 3.800 5.750
70 5.320 8.050

95 7.220 10.925
120 9.120 13.800
150 11.400 17.250

185 14.060 21.275


240 18.240 27.600
300 22.800 34.500

400 30.400 46.000


500 38.000 57.500
630 47.880 72.450

800 60.800 92.000


1000 76.000 115.000

43
PACKING, HANDLING AND STORAGE
PACKING HANDLING
On receipt of cable drums visual inspection of drums
Cables are generally received wound on wooden
should be made ensuring drum packing is original.
drums, both the ends of the cable being easily accessible
When unloading the cables, certain precautions are to
for inspection and testing. However short length may be
be taken to ensure the safety of the cables.
transported in coils without drums with prior intimation
to customer. a) The cable drums should not be dropped or thrown
from railway wagons or trucks during unloading
In case of paper-insulated lead-sheathed cables, both the
operations as the shock may cause serious damage to
ends of cables should be protected form moisture by
cable layers. A crane should be used for unloading
means of plumbed lead caps. In case of PVC and XLPE
cable drums. When lifting drums with the crane, it is
cables sealed plastic caps or heat shrinkable caps should
recommended that the lagging should be kept in
be used. The cable shall be wound on drums and packed.
place to prevent the flanges from crushing on to the
cable. If the crane is not available, a ramp should be
The cable drums shall carry the following information
prepared with approximate inclination of 1:3 or 1:4.
either stenciled or contained in a label attached to it.
The cable drum should be rolled over the ramp by
• Reference of Indian standard, means of ropes and winches. Additionally, a sand bed
• Manufacture's name or trade-mark; at the foot of the ramp may be prepared to brake the
• Type of cable and voltage grade; rolling of the cable drum.
• Number of cores;
b) Cable should not be dragged along the earth surface.
• Nominal cross sectional area of conductor;
• Cable code;
c) The arrows painted on the flange of the drum
• Length of cable on the drum;
indicate the direction in which the drum should be
• Number of length on the drum (if more than one);
rolled. The cable will unwind and become loose if
• Direction of rotation of drum (by arrow);
the drum is rolled in the opposite direction. Improper
• Gross mass;
handling or uncoiling of cable from reels or coils often
• Country of manufacture;
results in the “springing” of armour of the cable and
• Year of manufacture
kinking of the cable both of which are very difficult to
• The cable drums or label may also be marked with
be corrected. It reduces effective cable life
ISI Standard mark.
considerably. To avoid this, the following steps are to
be followed:

44
i) If the cable is supplied on a reel, it should be All drums should be stored in such a manner as to leave
mounted on a shaft and cable paid off from the sufficient space between them for air circulation. It is
reel while it rotates. Suitable brakes should be desirable for drums to stand on battens placed directly
applied on the flanges of the reel. under the flanges. During storage the drum should be
rolled to an angle of 90 º once every 3 months, This will
ii) If the cable is supplied in large coils these should
avoid collapsing of barrel of drum due to weight
be mounted on a turn table with suitable brakes
pressure continuously in one direction for longer period.
and cable paid off while the turn table rotates.
In no case, should the drum be stored “on the flat” that
is, with flange horizontal.
iii) Small coils of cables can be made to roll along the
ground for uncoiling.
If it is necessary to rewind a cable on to another drum,
the barrel of the drum should have a diameter not less
iv) Cable should be neither pulled straight from the
than that of the original drum.
coil while the coil rests on the ground nor taken
off turn from reel while it is lying on its flange on
the ground. LAYING
The selection of the route should first be decided
v) Also never allow the reel to rotate at high speed
keeping in view the intermediate and ultimate use of
during payoff.
the cable as an intermediate part of the transmission

STORAGE and distribution system.

The site chosen for storage of cables should be will


For transporting the cable drum to site, it is necessary to
drained. Cable should be stored in a dry covered place
check the road condition, whether it has loose soil, is
to prevent exposure to climatic conditions and wear and
marshy, water logged etc.
tear of wooden drums and it should preferably on a
concrete surface/firm surface, which will not cause the If possible, cables should be laid along the footpath
drums to sink and thus lead to flange rot and extreme rather than the carriageway. Plans for future building
difficulty in moving the drums. projects should be considered. The route should be
away from parallel running gas, water pipes and
However cable drum can be stored in uncovered area,
telephone cables. Also suitable locations for cable
but the area should be free from corrosive agents such as
joints and end termination should be selected as
chemicals and fumes etc. Also the lagging should be
required.
kept in place to avoid cable surface from direct sunrays.
The cables stored in hot condition at higher temperature On receipt of the drum at site, the plank should be
may cause oxidation of outer sheath jacket, whenever a removed and the cable is examined for exterior
cable length is cut, it should be recapped to avoid ingress damage, if any. To avoid damage to the protective
of water in the cable.

45
covering and the insulation the cable must not be Provision should be made to break the drum to avoid
pulled across hard and sharp objects. further rolling & buckling of cable during sudden stop.
A simple wooden plank can serve this purpose
For laying of cables special cares to be taken to prevent
sharp bending, kinking, twisting. Cable should be
unwound from drum by proper mounting the cable
drum on a cable wheel making sure the spindle is
strong enough to carry the weight without bending and
that it is lying horizontally in the bearings so as to
prevent the drum creeping to one side or the other
while it is rotating.

This is incorrect way of pulling the cable & will cause


kinks & twist in cable. Shall be avoided at all.
Cable must be pulled
from the top

Cable must not be pulled across hard & sharp object to


avoid the damage to the covering & insulation.

Cable must be laid in ducts or trenches as showing


in Fig.

46
However, following salient points are to be considered 4 a) If the cable are buried directly in ground.

during laying procedure of cables laid in racks and in I.S. 1255 is to be followed for code of practice.

build-in trenches. However generally cables are laid 1000 mm. below

finished ground level at any point of cable run


1 For laying of cables, power cables are to be placed
and 75 mm. of sand cushioning to be provided.
at the bottom most layer and control cables at top

most layer. b) In loose soil concrete pillar should be provided

for as support and hence pipes are


2 Single core power cable for use on a.c system shall
recommended to the used for cable path
be laid in delta formation supported by non-

magnetic material. Trefoil clamps of suitable size 5 If there is a possibility of mechanical damage, cable

are to be placed at regular intervals but preferably should be protected by means of mild steel covers

not more than 800 mm. Axial spacing of two placed on racks.

circuits in delta formation shall not be less than 4


6 Method of Installation:
times the cable dia. In case of multicore power

cables, cables shall be laid side by side, with spacing • Three Core Cables: Installed independently

not less than one cable diameter. However derating


• Single Core Cables: Three cables in a trefoil
factors for cables laid on trenches are to be referred.
touching each other

Multicore power cables and single core d.c circuits


7 Maximum safe pulling force (when pulled by
may be clamped by means of galvanized mild steel
pulling eye)
saddles. The saddles shall not be placed at intervals

more than 1500 mm. for horizontal and 1200 mm. Aluminum conductor cables: 3.0 kg/mm²

for vertical runs. Copper conductor cables: 5.0 kg/mm²

Proper method of pulling of cable should be


3 Multicore control cables can be laid touching each
used. Refer I.S. 1255-1983, code of practice for
other on cable racks and wherever required may be
installation and maintenance of power cables.
taken in two layers. They should be clamped by

means of PVC straps both for horizontal and vertical

runs, (alternatively, fabricated aluminum clamps

may be used) at regular intervals.

47
BENDING RADIUS:
While Installing 'GLOSTER' Cables, the following minimum bending radius should be observed such that
the cables, and especially the insulation, are not damaged. Wherever possible, larger bending radii should be used.

VOLTAGE GRADE OF CABLES RECOMMENDED MINIMUM BENDING RADII

Upto 1.1KV (12 X D) For Multi Core Cables


Upto 1.1KV (15 X D) For Single Core Cables
3.3 KV upto 11KV (15 X D) For Single and Multi Core Cables
Above 11 KV (15 X D) For Multi Core Cables
(20 X D) For Single Core Cables

Where 'D' is the overall diameter of Cables.

TESTING INSULATION RESISTANCE MEASUREMENT OF CABLE

The voltage rating of I R Tester (Megger) should be chosen as following table:

VOLTAGE GRADE RATING OF IR VOLTAGE GRADE RATING OF IR


OF CABLES TESTER (MEGGER) OF CABLE TESTER (MEGGER)

1.1 KV 500 V 11 KV 1000 V


3.3 KV 1000 V 22 KV 2500 V
6.6 KV 1000 V 33 KV 2500 V

TESTING DURING LAYING: under all service conditions. The joint should further be
resistant to corrosion and other chemical effects.
All new cables shall be megger-tested before
Termination and jointing of power and control cables
jointing. After jointing is completed all cables shall be
shall be done by means of compression methods using
megger-tested.
solder less tinned copper/Aluminum terminal lugs.

JOINTING OF CABLE:
HIGH VOLTAGE TEST:

The emphasis should be laid on quality and selection of


Cables after jointing and terminations are subjected to
proper cable accessories, proper jointing techniques
dc high voltage test. The recommended test voltage are
and skill and workmanship of the working personnel.
given in I.S. 1255 - 1983.
The quality of joint should be such that it does not add
any resistance to the circuit. The materials and The cable cores must be discharge after completion of
techniques employed should give adequate dc high voltage test.
mechanical and electrical protection to the joints
11/2008

48