Series DS-1 Dry-Type Sprinklers Quick Response, Standard Coverage 5.6 K-Factor, 3/4 and 1-Inch NPT General Description
Series DS-1 Dry-Type Sprinklers Quick Response, Standard Coverage 5.6 K-Factor, 3/4 and 1-Inch NPT General Description
Series DS-1 Dry-Type Sprinklers Quick Response, Standard Coverage 5.6 K-Factor, 3/4 and 1-Inch NPT General Description
00-381-9312 | +1-401-781-8220
www.tyco-fire.com
NOTICE
The Series DS-1 Dry-Type Sprinklers
described herein must be installed
and maintained in compliance with this
document, as well as with the applica
ble standards of the National Fire
Protection Association, in addition to
the standards of any authorities having
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and in-
stallation of sprinkler systems and
components. Improper handling and
installation can permanently dam-
age a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
3/4-INCH NPT
Finish
Temperature Bulb
Rating Color Code Natural Chrome White Natural Chrome White Natural Chrome White
Brass Plated Polyester Brass Plated Polyester Brass Plated Polyester
1-INCH NPT
TABLE B
1-INCH NPT AND ISO 7-R1, SERIES DS-1 QUICK RESPONSE, STANDARD COVERAGE DRY-TYPE SPRINKLERS
LABORATORY LISTINGS AND APPROVALS
TFP510
Page 3 of 10
Technical
PLUG WITH
SEALING
INLET Data
ASSEMBLY
YOKE Approvals
UL and C-UL Listed
FM Approved
PLUG INLET
SPRING BAND Refer to Tables A and B.
BULB
FRAME SEAT
3 mm BULB
VENT HOLE
COMPRESSION
DEFLECTOR SCREW
FIGURE 2
SERIES DS-1, 1-INCH NPT AND ISO 7-R1, QUICK RESPONSE
DRY-TYPE SPRINKLER ASSEMBLY
TFP510
Page 4 of 10
FACE OF
CEILING FACE OF
FACE OF CEILING
CEILING
4-1/4" ± 1/8"
(108,0 ± 3,2 mm)
2-3/16" ± 1/8" 3" DIA. 2-7/8" DIA.
(76,2 mm) 1-3/8" ± 1/8"
(55,6 ± 3,2 mm) (34,9 ± 3,2 mm) (73,0 mm)
SPRINKLER FITTING
(REFER TO DESIGN TOP OF
CRITERIA SECTION) DEFLECTOR
FACE OF
SPRINKLER
FITTING
ORDER LENGTHS:
5" to 48"
(127,0 to 1219,2 mm)
IN 1/4" (6,4 mm)
ORDER LENGTHS:
5" to 48" INCREMENTS
(127,0 to 1219,2 mm)
IN 1/4" (6,4 mm)
INCREMENTS FACE OF
SPRINKLER
FITTING
MINIMUM
1-3/4" (44,5 mm)
DEFLECTOR
TO CEILING SPRINKLER FITTING
(REFER TO DESIGN
CRITERIA SECTION)
FIGURE 6 FIGURE 7
TY3235 AND TY3935 PENDENT TY3135 UPRIGHT
WITHOUT ESCUTCHEON WITHOUT ESCUTCHEON
— 1-INCH NPT ONLY —
TFP510
Page 5 of 10
ORDER LENGTHS:
2-3/4" to 48" (69,9 to 1219,2 mm)
Operation
IN 1/4" (6,4 mm) INCREMENTS When the TYCO Series DS-1 Dry-Type
4" ± 1/8" Sprinkler is in service, water is prevent-
(101,6 ± 3,2 mm) ed from entering the assembly by the
FACE OF FACE OF 1-3/4" DIA. Plug with Sealing Assembly in the Inlet
SPRINKLER MOUNTING (44,5 mm) of the Sprinkler. See Figures 1 and 2.
FITTING SURFACE
The glass Bulb contains a fluid that ex-
pands when exposed to heat. When the
3" DIA. rated temperature is reached, the fluid
(76,2 mm) expands sufficiently to shatter the glass
Bulb, and the Bulb Seat is released.
3.5°
The compressed Spring is then able
SPRINKLER FITTING to expand and push the Water Tube as
(REFER TO DESIGN CENTERLINE 5/16" well as the Guide Tube outward. This
CRITERIA SECTION) OF WATERWAY (7,9 mm)
action simultaneously pulls inward on
FIGURE 8 the Yoke, withdrawing the Plug with
TY3335 AND TY3735 HORIZONAL SIDEWALL Sealing Assembly from the Inlet and
WITH STANDARD ESCUTCHEON allowing the sprinkler to activate and
flow water.
For wet pipe system installations of NOTICE exposed barrel length to prevent water
the 1-inch NPT Series DS-1 Dry-Type Do not install the Series DS-1 Dry-Type from freezing in the connecting pipes
Sprinklers connected to CPVC piping, Sprinkler into any other type fitting due to conduction. The exposed bar-
use only the following TYCO CPVC without first consulting the Technical rel length measurement must be taken
fittings: Services Department. Failure to use the from the face of the sprinkler fitting to
appropriate fitting may result in one of the surface of the structure or insula-
• 1" x 1" NPT Female Adapter (P/N 80145) tion that is exposed to the heated area.
the following:
• 1" x 1" x 1" NPT Sprinkler Head Adapter Refer to Figure 11 for an example.
Tee (P/N 80249). • Failure of the sprinkler to operate prop-
erly due to formation of ice over the Clearance Space
For wet pipe system installations of inlet Plug or binding of the Inlet Plug. In accordance with Section 8.4.9.2
the the 3/4-inch NPT Series DS-1 of the 2010 edition of NFPA 13, when
Sprinklers connected to CPVC pip- • Insufficient engagement of the Inlet
pipe threads with consequent leakage. connecting an area subject to freez-
ing, use in the 3/4" x 3/4" NPT Female ing and an area containing a wet pipe
Adapter (P/N 80142). sprinkler system, the clearance space
Drainage
For dry pipe system installations, use In accordance with the minimum around the sprinkler barrel of Dry-Type
only the side outlet of maximum 2-1/2- requirements of the National Fire Sprinklers must be sealed. Due to tem-
inch reducing tee when locating the Protection Association for dry pipe perature differences between two ar-
Series DS-1 Sprinklers directly below sprinkler systems, branch, cross, and eas, the potential for the formation of
the branch line. Otherwise, use the con- feed-main piping connected to Dry condensation in the sprinkler and sub-
figuration shown in Figure 13 to assure Sprinklers and subject to freezing tem- sequent ice build-up is increased. If
complete water drainage from above peratures must be pitched for proper this condensation is not controlled, ice
the Series DS-1 Dry-Type Sprinklers drainage. build-up can occur that might damage
and the branch line. Failure to do so the dry-type sprinkler and/or prevent
may result in pipe freezing and water Exposure Length proper operation in a fire situation.
damage. When using Dry Sprinklers in wet pipe Use of the Model DSB-2 Dry Sprinkler
sprinkler systems to protect areas sub- Boot, described in technical data sheet
ject to freezing temperatures, use Table TFP591 and shown in Figures 14 and
C to determine a sprinkler’s appropriate 15, can provide the recommended seal.
40°F (4°C) 0 0 0
30°F (-1°C) 0 0 0
20°F (-7°C) 4 (100) 0 0
10°F (-12°C) 8 (200) 1 (25) 0
0°F (-18°C) 12 (305) 3 (75) 0
-10°F (-23°C) 14 (355) 4 (100) 1 (25)
-20°F (-29°C) 14 (355) 6 (150) 3 (75)
-30°F (-34°C) 16 (405) 8 (200) 4 (100)
-40°F (-40°C) 18 (455) 8 (200) 4 (100)
-50°F (-46°C) 20 (510) 10 (255) 6 (150)
-60°F (-51°C) 20 (510) 10 (255) 6 (150)
Notes:
(a) For protected area temperatures that occur between values listed above, use the next cooler temperature.
(b) These lengths are inclusive of wind velocities up to 30 mph (18,6 kph).
TABLE C
MINIMUM RECOMMENDED LENGTHS OF EXPOSED SPRINKLER BARRELS
IN WET PIPE SYSTEMS
TFP510
Page 7 of 10
RUN
FACE OF TO WET SIDE OUTLET
SPRINKLER SYSTEM OUTLET PLUGGED
FITTING PLUGGED
SPRINKLER
HEATED FITTING
HEATED EXPOSURE TO DRY (SEE DESIGN
AREA
AREA LENGTH SYSTEM
CRITERIA
(SEE DESIGN SECTION)
DSB-2 CRITERIA DSB-2 SPRINKLER
AREA
INTENDED SECTION) INTENDED FITTING DSB-2
(SEE DESIGN SUBJECT
FOR FREEZER FOR FREEZER TO INTENDED
STRUCTURES STRUCTURES CRITERIA FOR FREEZER
SECTION) FREEZING
STRUCTURES
FIGURE 14 FIGURE 15
MODEL DSB-2 SPRINKLER MODEL DSB-2 SPRINKLER
BOOT WITH PENDENT SERIES BOOT WITH SIDEWALL SERIES
DS-1 DRY SPRINKLER DS-1 DRY SPRINKLER
TFP510
Page 8 of 10
Limited Ordering
Warranty Procedure
Products manufactured by Tyco Fire Contact your local distributor for avail-
Suppression & Building Products ability. When placing an order, indicate
(TFSBP) are warranted solely to the the full product name and Part Number
original Buyer for ten (10) years against (P/N).
defects in material and workman-
ship when paid for and properly in- Dry-Type Sprinklers
stalled and maintained under normal Specify this dry-type sprinkler as
use and service. This warranty will ex- follows:
pire ten (10) years from date of ship-
ment by TFSBP. No warranty is given • Model/SIN from Page 1
for products or components manu- • Quick Response, Standard Coverage,
factured by companies not affiliated Dry-Type Sprinkler
by ownership with TFSBP or for prod-
ucts and components which have • Deflector Style
been subject to misuse, improper in- • 5.6 K-Factor
stallation, corrosion, or which have
not been installed, maintained, modi • Order Length
fied or repaired in accordance with ap Dry-Type Sprinklers are furnished
plicable Standards of the National Fire based upon Order Length as mea-
Protection Association, and/or the stan- sured per Figures 3 through 10. After
dards of any other Authorities Having taking the measurement, round it to
Jurisdiction. Materials found by TFSBP the nearest 1/4 inch increment.
to be defective shall be either repaired • Inlet Connection: 3/4-inch NPT,
or replaced, at TFSBP's sole option. 1-inch NPT, or ISO 7-R1
TFSBP neither assumes, nor authorizes
any person to assume for it, any other • Temperature Rating
obligation in connection with the sale of • Sprinkler Finish
products or parts of products. TFSBP
shall not be responsible for sprinkler • Escutcheon Style and Finish, as
system design errors or inaccurate or applicable
incomplete information supplied by • Part Number (P/N) from Table C
Buyer or Buyer’s representatives.
The Upright Sprinkler without an
In no event shall TFSBP be liable, in Escutcheon (TY3135) is available in
contract, tort, strict liability or under 1-Inch NPT only.
any other legal theory, for incidental,
indirect, special or consequential dam Part Numbers are for 3/4-inch and
ages, including but not limited to labor 1-inch NPT standard order sprin-
charges, regardless of whether TFSBP klers. Orders for all other sprinkler
was informed about the possibility of assemblies must be accompanied
such damages, and in no event shall by a complete description. Refer to
TFSBP's liability exceed an amount the Price List for a complete listing of
equal to the sales price. Part Numbers.
The foregoing warranty is made in lieu Sprinkler Wrench
of any and all other warranties, express Specify: W-Type 7 Sprinkler Wrench,
or implied, including warranties of mer- P/N 56-850-4-001.
chantability and fitness for a particular
purpose. Sprinkler Boot
This limited warranty sets forth the ex Specify: Model DSB-2 Dry Sprinkler
clusive remedy for claims based on fail- Boot, P/N 63-000-0-002.
ure of or defect in products, materials This Part Number includes one Boot,
or components, whether the claim is two Strap Ties, and 1/3 oz. of Adhesive.
made in contract, tort, strict liability or The quantity of adhesive is sufficient for
any other legal theory. installing one Boot.
This warranty will apply to the full ex
tent permitted by law. The invalidity, in
whole or part, of any portion of thiswar-
ranty will not affect the remainder.
TFP510
Page 10 of 10
SPRINKLER ESCUTCHEON
MODEL/SIN FINISH FINISH (1)
NOTES
(1). Escutcheon Finish applies to sprinklers provided with
Sidewall with Standard TY3335
34 escutcheons.
Escutcheon (1" NPT) (Figure 8)
(2). 286°F (141°C) temperature rating applies to non-recessed
Sidewall with Deep TY3335 sprinkler assemblies.
43
Escutcheon (1" NPT) (Figure 9) (3). Dry-Type Sprinklers are furnished based upon “Order Length”
as measured per Figures 3 through 10, as applicable, and
44
Sidewall without TY3335 for each individual sprinkler where it is to be installed. After
Escutcheon (1" NPT) (Figure 10) the measurement is taken, round it to the nearest 1/4 inch
increment.
TABLE C
PART NUMBER SELECTION
SERIES DS-1, 3/4 AND 1-INCH NPT, QUICK RESPONSE, STANDARD COVERAGE, DRY-TYPE SPRINKLERS
(Use Prefix “I” for ISO 7-R1 Connection; for example, I-60-361-1-180)