Series DS-1 Dry-Type Sprinklers Quick Response, Standard Coverage 5.6 K-Factor, 3/4 and 1-Inch NPT General Description

Download as pdf or txt
Download as pdf or txt
You are on page 1of 10

Technical Services 8

 00-381-9312 | +1-401-781-8220
www.tyco-fire.com

Series DS-1 Dry-Type Sprinklers


Quick Response, Standard Coverage
5.6 K-factor, 3/4 and 1-Inch NPT
General jurisdiction. Failure to do so may impair
the performance of these de­vices.
Description Owners are responsible for maintain­ing
their fire protection system and de­vices
The TYCO Series DS-1, 5.6 K-factor, in proper operating condition. The in-
3/4 and 1-Inch NPT, Quick Response, stalling contractor or sprinkler manu-
Standard Coverage, Dry-Type Sprink- facturer should be contacted with any
lers are decorative, 3-mm glass bulb questions.
automatic sprinklers de­signed for com-
mercial use. Dry-Type Sprinklers are The Series DS-1 Dry-Type Sprinklers
typically used where: must only be installed in fittings that
meet the requirements of the Design
• pendent sprinklers are re­quired on Criteria section.
dry pipe systems that are exposed to
freezing tempera­tures; for example,
sprinkler drops from un­heated por- Model/Sprinkler
tions of buildings.
• sprinklers and/or a portion of the con-
Identification
necting piping are exposed to freezing
temperatures; for example, sprinkler
Numbers (SINs)
drops from wet sys­tems into freezers, 3/4-Inch NPT:
sprinkler sprigs from wet systems into TY3935 - Pendent
unheated attics, or horizontal piping TY3735 - Horizontal Sidewall
extensions through a wall to protect an 1-Inch NPT:
unheated areas such as loading docks, TY3235 - Pendent
overhangs, and building exteriors. TY3135 - Upright
• sprinklers are used on sys­tems that are TY3335 - Horizontal Sidewall
seasonally drained to avoid freezing;
for example, vacation areas.

NOTICE
The Series DS-1 Dry-Type Sprinklers
described herein must be installed
and maintained in compliance with this
document, as well as with the applica­
ble standards of the National Fire
Protection Association, in addition to
the standards of any authorities hav­ing

IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and in-
stallation of sprinkler systems and
components. Improper handling and
installation can permanently dam-
age a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.

Page 1 of 10 OCTOBER 2010 TFP510


TFP510
Page 2 of 10

3/4-INCH NPT

TY3935 Pendent TY3935 Pendent TY3735 Horizontal Sidewall


with Top of Deflector-to-Ceiling
with Standard with Standard Escutcheon
Distance of 4 to 12 inches
Recessed Escutcheon (Figure 3)
(100 to 300 mm)
(Figure 4) with Deep Escutcheon
(Figure 5)
without Escutcheon with Standard Escutcheon
(Figure 6) (Figure 8)
with Deep Escutcheon
(Figure 9)
without Escutcheon
(Figure 10)

Finish
Temperature Bulb
Rating Color Code Natural Chrome White Natural Chrome White Natural Chrome White
Brass Plated Polyester Brass Plated Polyester Brass Plated Polyester

135°F (57°C) Orange 1, 2 1, 2 1*, 2*


155°F (68°C) Red 1, 2 1, 2 1*, 2*
175°F (79°C) Yellow 1, 2 1, 2 1*, 2*
200°F (93°C) Green 1, 2 1, 2 1*, 2*
286°F (141°C) Blue N/A 1, 2 1*, 2*
Notes:
1. Listed by Underwriters Laboratories, Inc. 2. Listed by Underwriters Laboratories for use in
(maximum order length of 48 inches). Canada (maximum order length of 48 inches).
* Light and Ordinary Hazard Occupancies Only / N/A - Not Available
TABLE A
3/4-INCH NPT, SERIES DS-1 QUICK RESPONSE, STANDARD COVERAGE DRY-TYPE SPRINKLERS
LABORATORY LISTINGS AND APPROVALS

1-INCH NPT

TY3235 Pendent TY3235 Pendent TY3335 Horizontal Sidewall

with Standard with Standard Escutcheon with Top of Deflector-to-Ceiling


Recessed Escutcheon (Figure 3) Distance of 4 to 12 inches
(Figure 4) with Deep Escutcheon (100 to 300 mm)
(Figure 5)
without Escutcheon with Standard Escutcheon
(Figure 6) (Figure 8)
with Deep Escutcheon
TY3135 Upright (Figure 9)
without Escutcheon without Escutcheon
(Figure 7) (Figure 10)
Finish
Temperature Bulb
Rating Color Code Natural Chrome White Natural Chrome White Natural Chrome White
Brass Plated Polyester Brass Plated Polyester Brass Plated Polyester

135°F (57°C) Orange 1, 2, 3 1, 2 1, 2, 3 1, 2 1*, 2*, 3** 1*, 2*


155°F (68°C) Red 1, 2, 3 1, 2 1, 2, 3 1, 2 1*, 2*, 3** 1*, 2*
175°F (79°C) Yellow 1, 2, 3 1, 2 1, 2, 3 1, 2 1*, 2*, 3** 1*, 2*
200°F (93°C) Green 1, 2, 3 1, 2 1, 2, 3 1, 2 1*, 2*, 3** 1*, 2*
286°F (141°C) Blue N/A 1, 2, 3 1, 2 1*, 2*, 3** 1*, 2*
Notes:
1. L
 isted by Underwriters Laboratories, Inc. 2. Listed by Underwriters Laboratories for use in Canada
(maximum order length of 48 inches). (maximum order length of 48 inches).
3. A
 pproved by Factory Mutual Research Corporation 4. The Upright Sprinkler without an Escutcheon (TY3135)
(maximum order length of 48 inches). is available in 1-Inch NPT only.
* Light and Ordinary Hazard Occupancies Only / ** Light Hazard Occupancies Only / N/A - Not Available

TABLE B
1-INCH NPT AND ISO 7-R1, SERIES DS-1 QUICK RESPONSE, STANDARD COVERAGE DRY-TYPE SPRINKLERS
LABORATORY LISTINGS AND APPROVALS
TFP510
Page 3 of 10

Technical
PLUG WITH
SEALING
INLET Data
ASSEMBLY
YOKE Approvals
UL and C-UL Listed
FM Approved
PLUG INLET
SPRING BAND Refer to Tables A and B.

Maximum Working Pressure


SPRING 175 psi (12,1 bar)
WATER
TUBE
CASING Inlet Thread Connection
3/4-Inch NPT
GUIDE INSERT 1-Inch NPT or ISO 7-R1
TUBE
Discharge Coefficient
BULB K = 5.6 GPM/psi1/2
SEAT (80,6 LPM/bar1/2)
FRAME

3 mm BULB Temperature Ratings


Refer to Tables A and B.
VENT HOLE
Finishes
COMPRESSION Sprinkler: Natural Brass, Chrome
DEFLECTOR SCREW Plated, White Polyester
Escutcheon: White Coated, Chrome
Plated, Brass Plated
FIGURE 1
SERIES DS-1, 3/4-INCH NPT, QUICK RESPONSE Physical Characteristics
DRY-TYPE SPRINKLER ASSEMBLY Inlet . . . . . . . . . . . . . . . . . . . . Copper
Plug . . . . . . . . . . . . . . . . . . . Copper
Yoke . . . . . . . . . . . . . . . Stainless Steel
Casing. . . . . Galvanized Carbon Steel
Insert . . . . . . . . . . . . . . . . . . . Bronze
Bulb Seat. . . . . . . . . . . Stainless Steel
Bulb. . . . . . . . . . . . . . . . . . . . . . . Glass
Compression Screw. . . . . . . . Bronze
PLUG WITH INLET
SEALING Deflector . . . . . . . . . . . . . . . . . Bronze
ASSEMBLY Frame . . . . . . . . . . . . . . . . . . . Bronze
YOKE Guide Tube . . . . . . . . . Stainless Steel
Water Tube . . . . . . . . . Stainless Steel
SPRING Spring . . . . . . . . . . . . . Stainless Steel
INLET Plug Spring*. . . . . . . . .Stainless Steel
BAND Sealing Assembly. . . . . . . . Beryllium
WATER Nickel w/Teflon**
TUBE Escutcheon . . . . . . . . . . Carbon Steel
CASING
Patents
U.S.A. Patent No. 5,188,185
GUIDE INSERT
*For 3/4-Inch NPT only
TUBE **Registered trademark of DuPont

BULB
FRAME SEAT

3 mm BULB
VENT HOLE

COMPRESSION
DEFLECTOR SCREW

FIGURE 2
SERIES DS-1, 1-INCH NPT AND ISO 7-R1, QUICK RESPONSE
DRY-TYPE SPRINKLER ASSEMBLY
TFP510
Page 4 of 10

SPRINKLER FITTING SPRINKLER FITTING SPRINKLER FITTING


(REFER TO DESIGN (REFER TO DESIGN (REFER TO DESIGN
CRITERIA SECTION) CRITERIA SECTION) CRITERIA SECTION)
FACE OF FACE OF FACE OF
SPRINKLER SPRINKLER SPRINKLER
FITTING FITTING FITTING

ORDER LENGTHS: ORDER LENGTHS: ORDER LENGTHS: 3-1/2" DIA.


2-3/4" to 48" 3-3/4" to 48" 1/2" to 46" (88,9 mm)
1-3/4" DIA.
(69,9 to 1219,2 mm) (95,3 to 1219,2 mm) (12,7 to 1168,4 mm)
(44,5 mm) 2-1/2" DIA.
IN 1/4" (6,4 mm) IN 1/4" (6,4 mm) 2-1/4" DIA. IN 1/4" (6,4 mm)
(63,5 mm)
INCREMENTS INCREMENTS (57,2 mm) INCREMENTS

FACE OF
CEILING FACE OF
FACE OF CEILING
CEILING
4-1/4" ± 1/8"
(108,0 ± 3,2 mm)
2-3/16" ± 1/8" 3" DIA. 2-7/8" DIA.
(76,2 mm) 1-3/8" ± 1/8"
(55,6 ± 3,2 mm) (34,9 ± 3,2 mm) (73,0 mm)

FIGURE 3 FIGURE 4 FIGURE 5


TY3235 AND TY3935 PENDENT TY3235 AND TY3935 PENDENT TY3235 AND TY3935 PENDENT
WITH STANDARD ESCUTCHEON WITH STANDARD RECESSED WITH DEEP ESCUTCHEON
ESCUTCHEON

SPRINKLER FITTING
(REFER TO DESIGN TOP OF
CRITERIA SECTION) DEFLECTOR

FACE OF
SPRINKLER
FITTING
ORDER LENGTHS:
5" to 48"
(127,0 to 1219,2 mm)
IN 1/4" (6,4 mm)
ORDER LENGTHS:
5" to 48" INCREMENTS
(127,0 to 1219,2 mm)
IN 1/4" (6,4 mm)
INCREMENTS FACE OF
SPRINKLER
FITTING
MINIMUM
1-3/4" (44,5 mm)
DEFLECTOR
TO CEILING SPRINKLER FITTING
(REFER TO DESIGN
CRITERIA SECTION)

FIGURE 6 FIGURE 7
TY3235 AND TY3935 PENDENT TY3135 UPRIGHT
WITHOUT ESCUTCHEON WITHOUT ESCUTCHEON
— 1-INCH NPT ONLY —
TFP510
Page 5 of 10

ORDER LENGTHS:
2-3/4" to 48" (69,9 to 1219,2 mm)
Operation
IN 1/4" (6,4 mm) INCREMENTS When the TYCO Series DS-1 Dry-Type
4" ± 1/8" Sprinkler is in service, water is prevent-
(101,6 ± 3,2 mm) ed from entering the assembly by the
FACE OF FACE OF 1-3/4" DIA. Plug with Sealing Assembly in the Inlet
SPRINKLER MOUNTING (44,5 mm) of the Sprinkler. See Figures 1 and 2.
FITTING SURFACE
The glass Bulb contains a fluid that ex-
pands when ex­posed to heat. When the
3" DIA. rated tem­perature is reached, the fluid
(76,2 mm) expands sufficiently to shatter the glass
Bulb, and the Bulb Seat is released.
3.5°
The compressed Spring is then able
SPRINKLER FITTING to ex­pand and push the Water Tube as
(REFER TO DESIGN CENTERLINE 5/16" well as the Guide Tube outward. This
CRITERIA SECTION) OF WATERWAY (7,9 mm)
action simultaneously pulls inward on
FIGURE 8 the Yoke, withdrawing the Plug with
TY3335 AND TY3735 HORIZONAL SIDEWALL Sealing Assembly from the Inlet and
WITH STANDARD ESCUTCHEON allowing the sprin­kler to activate and
flow water.

ORDER LENGTHS: FACE OF Design


Criteria
1/2" to 45-3/4" (12,7 to 1162,1 mm) MOUNTING
IN 1/4" (6,4 mm) INCREMENTS SURFACE
4-13/16" ± 1/8"
(122,2 ± 3,2 mm) The TYCO Series DS-1 Sprinklers are
2-1/2" DIA. intended for use in fire sprinkler sys-
FACE OF (63,5 mm)
SPRINKLER tems designed in accordance with the
FITTING standard installation rules recognized
by the applicable Listing or Approval
agency; for example, UL Listing is
3-1/2" DIA. based on NFPA 13 requirements.
(88,9 mm)
3.5° Sprinkler Fittings
Install the 3/4 or 1-inch NPT Series
SPRINKLER FITTING DS-1 Dry-Type Sprinklers in the 3/4 or
(REFER TO DESIGN CENTERLINE 5/16" 1-inch NPT outlet or run of the follow-
CRITERIA SECTION) OF WATERWAY (7,9 mm)
ing fittings:
FIGURE 9 • malleable or ductile iron threaded tee
TY3335 AND TY3735 HORIZONAL SIDEWALL fittings that meet the dimensional re-
WITH DEEP ESCUTCHEON quirements of ANSI B16.3 (Class 150)
• cast iron threaded tee fittings that
meet the dimensional requirements
ORDER LENGTHS: of ANSI B16.4 (Class 125).
5-1/2" to 48" (139,7 to 1219,2 mm)
Do not install the DS-1 Sprinklers into
IN 1/4" (6,4 mm) INCREMENTS MINIMUM an elbow fittings. The Inlet of the sprin-
2-1/4" (57,2 mm) kler can contact the interior of the el-
FACE OF DEFLECTOR TO bow, potentially damaging the Inlet
SPRINKLER MOUNTING seal.
FITTING SURFACE
The unused outlet of the threaded tee is
plugged as shown in Figures 12 and 13.
You can also install the Series DS-1
Dry-Type Sprinklers in the 3/4 or 1-inch
3.5° NPT outlet of a GRINNELL Figure 730
5/16"
(7,9 mm)
Mechanical Tee. However, the use of
SPRINKLER FITTING the Figure 730 Tee for this arrangement
(REFER TO DESIGN CENTERLINE is limited to wet pipe systems.
CRITERIA SECTION) OF WATERWAY
The configuration shown in Figure 12
FIGURE 10 is only applicable for wet pipe systems
TY3335 AND TY3735 HORIZONAL SIDEWALL where the sprinkler fitting and water-
filled pipe above the sprinkler fitting are
WITHOUT ESCUTCHEON
not subject to freezing and where the
length of the Dry-Type Sprinkler has the
minimum exposure length depicted in
Figure 11. Refer to the Exposure Length
section.
TFP510
Page 6 of 10

For wet pipe system installations of NOTICE exposed barrel length to prevent water
the 1-inch NPT Series DS-1 Dry-Type Do not install the Series DS-1 Dry-Type from freezing in the connecting pipes
Sprinklers connected to CPVC piping, Sprinkler into any other type fitting due to conduction. The exposed bar-
use only the following TYCO CPVC without first consulting the Technical rel length measurement must be taken
fittings: Services Department. Failure to use the from the face of the sprinkler fitting to
appropriate fitting may result in one of the surface of the structure or insula-
• 1" x 1" NPT Female Adapter (P/N 80145) tion that is exposed to the heated area.
the following:
• 1" x 1" x 1" NPT Sprinkler Head Adapter Refer to Figure 11 for an example.
Tee (P/N 80249). • Failure of the sprinkler to operate prop-
erly due to formation of ice over the Clearance Space
For wet pipe system installations of inlet Plug or binding of the Inlet Plug. In accordance with Section 8.4.9.2
the the 3/4-inch NPT Series DS-1 of the 2010 edition of NFPA 13, when
Sprinklers connected to CPVC pip- • Insufficient engagement of the Inlet
pipe threads with consequent leakage. connecting an area subject to freez-
ing, use in the 3/4" x 3/4" NPT Female ing and an area containing a wet pipe
Adapter (P/N 80142). sprinkler system, the clearance space
Drainage
For dry pipe system installations, use In accordance with the minimum around the sprinkler barrel of Dry-Type
only the side outlet of maximum 2-1/2- requirements of the National Fire Sprinklers must be sealed. Due to tem-
inch reducing tee when locating the Protection Association for dry pipe perature differences between two ar-
Series DS-1 Sprinklers directly below sprinkler systems, branch, cross, and eas, the potential for the formation of
the branch line. Otherwise, use the con- feed-main piping connected to Dry condensation in the sprinkler and sub-
figuration shown in Figure 13 to assure Sprinklers and subject to freezing tem- sequent ice build-up is increased. If
complete water drainage from above peratures must be pitched for proper this condensation is not controlled, ice
the Series DS-1 Dry-Type Sprinklers drainage. build-up can occur that might damage
and the branch line. Failure to do so the dry-type sprinkler and/or prevent
may result in pipe freezing and water Exposure Length proper operation in a fire situation.
damage. When using Dry Sprinklers in wet pipe Use of the Model DSB-2 Dry Sprinkler
sprinkler systems to protect areas sub- Boot, described in technical data sheet
ject to freezing temperatures, use Table TFP591 and shown in Figures 14 and
C to determine a sprinkler’s appropriate 15, can provide the recommended seal.

Temperatures for Heated Area(a)


Ambient Temperature
Exposed to Discharge End of 40°F (4°C) 50°F (10°C) 60°F (16°C)
Sprinkler
Minimum Exposed Barrel Length, Inches (mm)(b)

40°F (4°C) 0 0 0
30°F (-1°C) 0 0 0
20°F (-7°C) 4 (100) 0 0
10°F (-12°C) 8 (200) 1 (25) 0
0°F (-18°C) 12 (305) 3 (75) 0
-10°F (-23°C) 14 (355) 4 (100) 1 (25)
-20°F (-29°C) 14 (355) 6 (150) 3 (75)
-30°F (-34°C) 16 (405) 8 (200) 4 (100)
-40°F (-40°C) 18 (455) 8 (200) 4 (100)
-50°F (-46°C) 20 (510) 10 (255) 6 (150)
-60°F (-51°C) 20 (510) 10 (255) 6 (150)
Notes:
(a) For protected area temperatures that occur between values listed above, use the next cooler temperature.
(b) These lengths are inclusive of wind velocities up to 30 mph (18,6 kph).

TABLE C
MINIMUM RECOMMENDED LENGTHS OF EXPOSED SPRINKLER BARRELS
IN WET PIPE SYSTEMS
TFP510
Page 7 of 10

RUN
FACE OF TO WET SIDE OUTLET
SPRINKLER SYSTEM OUTLET PLUGGED
FITTING PLUGGED
SPRINKLER
HEATED FITTING
HEATED EXPOSURE TO DRY (SEE DESIGN
AREA
AREA LENGTH SYSTEM
CRITERIA
(SEE DESIGN SECTION)
DSB-2 CRITERIA DSB-2 SPRINKLER
AREA
INTENDED SECTION) INTENDED FITTING DSB-2
(SEE DESIGN SUBJECT
FOR FREEZER FOR FREEZER TO INTENDED
STRUCTURES STRUCTURES CRITERIA FOR FREEZER
SECTION) FREEZING
STRUCTURES

FIGURE 11 FIGURE 12 FIGURE 13


EXPOSURE LENGTH SPRINKLER FITTING IN SPRINKLER FITTING IN
HEATED AREA UNHEATED AREA

STRAP TIES 1-3/4" DIA.


(ENDS ON (44,5 mm)
OPPOSING CLEARANCE INSULATED
SIDES OF HOLE FREEZER
BOOT) ADHESIVE STRUCTURE
DSB-2 BOOT
DSB-2
ADHESIVE BOOT
1-3/4" DIA.
(44,5 mm)
CLEARANCE
HOLE
INSULATED
FREEZER
STRUCTURE
STRAP TIES
(ENDS ON DS-1
DS-1 SHOWN WITH
SHOWN WITH OPPOSING
STANDARD
STANDARD SIDES OF
BOOT) ESCUTCHEON
ESCUTCHEON

FIGURE 14 FIGURE 15
MODEL DSB-2 SPRINKLER MODEL DSB-2 SPRINKLER
BOOT WITH PENDENT SERIES BOOT WITH SIDEWALL SERIES
DS-1 DRY SPRINKLER DS-1 DRY SPRINKLER
TFP510
Page 8 of 10

Installation Apply the Wrench Recess of the


W-Type 7 Sprinkler Wrench to the
Non-factory applied paint can adverse-
ly delay or prevent sprinkler operation
The TYCO Series DS-1 Dry-Type Wrench Flat. in the event of a fire.
Sprinklers must be installed in accor- Note: If sprinkler removal becomes Replace sprinklers that:
dance with the following instructions. necessary, remove the sprinkler • were damaged by dropping, striking,
using the same wrenching meth- wrench twisting, wrench slippage, or
NOTICE od noted above. Sprinkler remov- the like.
The Series DS-1 Dry-Type Sprinkler al is easier when a non-hardening
must only be installed in fittings that sealant was used and torque guide- • were modified or over-heated.
meet the requirements of the Design lines were followed. After removal, • have cracked bulbs or have lost liquid
Criteria section. Refer to the Design inspect the sprinkler for damage. from the bulbs. Refer to the Installation
Criteria section for other important re- 4. After installing the ceiling or wall and Section in this data sheet.
quirements regard­ing piping design applying a celing finish, slide on the • are leaking or exhibiting visible signs
and sealing of the clearance space outer piece of the Escutcheon until of corrosion.
around the Sprinkler Casing. it comes in contact with the ceiling
or wall. Do not lift the ceiling panel Responsibility lies with owners for the
Do not install any bulb type sprinkler in­spection, testing, and maintenance of
if the bulb is cracked or there is a loss out of its normal position.
their fire protection system and devices
of liquid from the bulb. With the sprin- When using the Deep Escutcheon, in compliance with this document, as
kler held horizontally, a small air bubble hold the outer piece in contact with well as with the applicable standards of
should be present. The diameter of the the mounting surface (ceiling or the National Fire Protec­tion Association
air bubble is approximately 1/16 inch wall). Then rotate the inner piece (for example, NFPA 25), in addition to
(1,6 mm) for the 135°F (57°C) rating to approximately 1/4 turn with respect the standards of any other authorities
1/8 inch (3,2 mm) for the 286°F (141°C) to the outer piece, to hold the Deep having jurisdiction. The installing con-
rating. Escutcheon firmly together. tractor or sprinkler manufacturer should
• Obtain a leak-tight 3/4-inch NPT sprin- be contacted relative to any questions.
kler joint by applying a minimum-to-
maximum torque of 10 to 20 ft. lbs.
Care and Automatic sprinkler systems are recom-
mended to be inspected, tested, and
(13,4 to 26,8 Nm). Maintenance maintained by a qualified Inspection
• Obtain a leak-tight 1 inch NPT sprin- Service in accordance with local re-
kler joint by applying a minimum-to- The TYCO Series DS-1 Dry-Type quirements and/or national codes.
maximum torque of 20 to 30 ft. lbs. Sprinklers must be maintained and ser-
(26,8 to 40,2 Nm). viced in accordance with the following
instructions.
Higher levels of torque can distort the
sprinkler Inlet with consequent leakage NOTICE
or impairment of the sprinkler.
Before closing a fire protection system WRENCH
Do not attempt to compensate for main control valve for maintenance RECESS
insufficient adjustment in an work on the fire protection system that
Escutcheon Plate by under or over- it controls, obtain permission to shut
tightening the Sprinkler. Re-adjust the down the affected fire protection sys-
position of the sprinkler fitting to suit. tems from the proper authorities and
1. Install pendent sprinklers only in the notify all personnel who may be affect- WRENCH
pendent position, and install upright ed by this action. FLAT
sprinklers only in the upright posi- Absence of the outer piece of an es­
tion. The deflector of a pendent or cutcheon, which is used to cover a
upright sprin­kler must be parallel to clearance hole, can delay the time to PUSH WRENCH
the ceiling. sprinkler operation in a fire situation. IN TO ENSURE
Install horizontal sidewall sprin- A Vent Hole is provided in the Bulb Seat ENGAGEMENT
klers in the horizontal position with (Figures 1 and 2) to indicate if the Dry- WITH SPRINKLER
their centerline of waterway perpen­ Type Sprinkler is remaining dry. Evi­ WRENCHING AREA
dicular to the back wall and paral- dence of leakage from the Vent Hole in-
lel to the ceiling. Ensure the word FIGURE 16
dicates potential leakage past the Inlet W-TYPE 7 SPRINKLER WRENCH
“TOP” on the De­flector faces the seal and the need to remove the sprin-
ceiling. kler to determine the cause of leakage;
2. With a non-hardening pipe-thread for example, an improper installation
sealant such as Teflon1 tape applied or an ice plug. Close the fire protec-
to the Inlet threads, hand-tighten the tion system control valve and drain the
sprinkler into the sprinkler fitting. system before removing the sprinkler.
3. Wrench-tighten the sprinkler using Exercise care to avoid dam­age before,
either: during, and after instal­lation. Never
paint, plate, coat, or otherwise alter
• a pipe wrench on the Inlet Band or automatic sprinklers after they leave
the Casing (Figures 1 and 2) the factory.
• the W-Type 7 Sprinkler Wrench on Never repaint factory-painted Cover
the Wrench Flat (Figure 16). Plates. When necessary, replace cov-
1 Registered trademark of DuPont
er plates with factory-painted units.
TFP510
Page 9 of 10

Limited Ordering
Warranty Procedure
Products manufactured by Tyco Fire Contact your local distributor for avail-
Suppression & Building Products ability. When placing an order, indicate
(TFSBP) are war­ranted solely to the the full product name and Part Number
original Buyer for ten (10) years against (P/N).
defects in mate­rial and workman-
ship when paid for and properly in- Dry-Type Sprinklers
stalled and maintained under normal Specify this dry-type sprinkler as
use and service. This warranty will ex- follows:
pire ten (10) years from date of ship-
ment by TFSBP. No warranty is given • Model/SIN from Page 1
for products or com­ponents manu- • Quick Response, Standard Cover­age,
factured by companies not affiliated Dry-Type Sprinkler
by ownership with TFSBP or for prod-
ucts and components which have • Deflector Style
been subject to misuse, improper in- • 5.6 K-Factor
stallation, corrosion, or which have
not been installed, maintained, modi­ • Order Length
fied or repaired in accordance with ap­ Dry-Type Sprinklers are furnished
plicable Standards of the National Fire based upon Order Length as mea-
Protection Association, and/or the stan- sured per Figures 3 through 10. After
dards of any other Authorities Having taking the measurement, round it to
Jurisdiction. Materials found by TFSBP the nearest 1/4 inch increment.
to be defective shall be either repaired • Inlet Connection: 3/4-inch NPT,
or replaced, at TFSBP's sole option. 1-inch NPT, or ISO 7-R1
TFSBP neither assumes, nor authorizes
any person to assume for it, any other • Temperature Rating
obligation in connection with the sale of • Sprinkler Finish
products or parts of prod­ucts. TFSBP
shall not be responsible for sprinkler • Escutcheon Style and Finish, as
system design errors or inac­curate or applicable
incomplete information sup­plied by • Part Number (P/N) from Table C
Buyer or Buyer’s repre­sentatives.
The Upright Sprinkler without an
In no event shall TFSBP be liable, in Escutcheon (TY3135) is available in
contract, tort, strict liability or under 1-Inch NPT only.
any other legal theory, for incidental,
indirect, special or consequential dam­ Part Numbers are for 3/4-inch and
ages, including but not limited to labor 1-inch NPT stand­ard order sprin-
charges, regardless of whether TFSBP klers. Orders for all other sprinkler
was informed about the possibility of assemblies must be accompanied
such damages, and in no event shall by a complete description. Refer to
TFSBP's liability exceed an amount the Price List for a complete listing of
equal to the sales price. Part Numbers.
The foregoing warranty is made in lieu Sprinkler Wrench
of any and all other warranties, express Specify: W-Type 7 Sprinkler Wrench,
or implied, including warranties of mer- P/N 56-850-4-001.
chantability and fitness for a particular
purpose. Sprinkler Boot
This limited warranty sets forth the ex­ Specify: Model DSB-2 Dry Sprinkler
clusive remedy for claims based on fail- Boot, P/N 63-000-0-002.
ure of or defect in products, materi­als This Part Number includes one Boot,
or components, whether the claim is two Strap Ties, and 1/3 oz. of Adhesive.
made in contract, tort, strict liability or The quantity of adhesive is sufficient for
any other legal theory. installing one Boot.
This warranty will apply to the full ex­
tent permitted by law. The invalidity, in
whole or part, of any portion of thiswar-
ranty will not affect the remainder.
TFP510
Page 10 of 10

P/N 60 – XXX – X – XXX

SPRINKLER ESCUTCHEON
MODEL/SIN FINISH FINISH (1)

Pendent with Standard TY3935 1 NATURAL BRASS WHITE


01
Escutcheon (3/4" NPT) (Figure 3)
4 WHITE POLYESTER WHITE
Pendent with Deep TY3935
02
Escutcheon (3/4" NPT) (Figure 5) 9 CHROME PLATED CHROME

Pendent with Standard Recessed TY3935 0 CHROME PLATED WHITE


03
Escutcheon (3/4" NPT) (Figure 4)
2 NATURAL BRASS BRASS PLATED
Pendent without TY3935
04
Escutcheon (3/4" NPT) (Figure 6)

Sidewall with Standard TY3735


05
Escutcheon (3/4" NPT) (Figure 8)

Sidewall with Deep TY3735 TEMPERATURE


06 SAMPLE ORDER
Escutcheon (3/4" NPT) (Figure 9) RATINGS (2) LENGTHS (3)

Sidewall without TY3735 0 135°F (57°C)


07
Escutcheon (3/4" NPT) (Figure 10) 055 5.50”
1 155°F (68°C)
082 8.25”

Pendent with Standard TY3235 2 175°F (79°C)


36 180 18.00”
Escutcheon (1" NPT) (Figure 3)
3 200°F (93°C)
187 18.75”
Pendent with Deep TY3235
33 4 286°F (141°C)
Escutcheon (1" NPT) (Figure 5)
372 37.25”

Pendent with Standard Recessed TY3235


37 480 48.00”
Escutcheon (1" NPT) (Figure 4)

Pendent without TY3235


32
Escutcheon (1" NPT) (Figure 6)

NOTES
(1). Escutcheon Finish applies to sprinklers provided with
Sidewall with Standard TY3335
34 escutcheons.
Escutcheon (1" NPT) (Figure 8)
(2). 286°F (141°C) temperature rating applies to non-recessed
Sidewall with Deep TY3335 sprinkler assemblies.
43
Escutcheon (1" NPT) (Figure 9) (3). Dry-Type Sprinklers are furnished based upon “Order Length”
as measured per Figures 3 through 10, as applicable, and
44
Sidewall without TY3335 for each individual sprinkler where it is to be installed. After
Escutcheon (1" NPT) (Figure 10) the measurement is taken, round it to the nearest 1/4 inch
increment.

Upright without TY3135


38
Escutcheon (1" NPT) (Figure 7)

TABLE C
PART NUMBER SELECTION
SERIES DS-1, 3/4 AND 1-INCH NPT, QUICK RESPONSE, STANDARD COVERAGE, DRY-TYPE SPRINKLERS
(Use Prefix “I” for ISO 7-R1 Connection; for example, I-60-361-1-180)

Copyright © 2009 - 2010 Tyco Fire Suppression & Building Products. All rights reserved.

You might also like