This document provides an input-output summary of a building management system for a chiller plant. It lists various field devices and their associated quantities of digital inputs, analog inputs, digital outputs, and analog outputs. These include devices for chillers, primary and secondary chilled water pumps, cooling towers, air handling units, fan coil units, exhaust fans, a water treatment plant, drinking water pumps, and a medium voltage panel. The total number of input-output points for the entire plant management system are listed at the bottom.

Uploaded by

Minh Nhut Luu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
429 views4 pages

2727 Input Output Summary

This document provides an input-output summary of a building management system for a chiller plant. It lists various field devices and their associated quantities of digital inputs, analog inputs, digital outputs, and analog outputs. These include devices for chillers, primary and secondary chilled water pumps, cooling towers, air handling units, fan coil units, exhaust fans, a water treatment plant, drinking water pumps, and a medium voltage panel. The total number of input-output points for the entire plant management system are listed at the bottom.

Uploaded by

Minh Nhut Luu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

BMS I-O (Input - Output) Summary

Sl.
Description Qty DI AI DO AO Filed devices
No
1 CHILLERS-4 4 4
a. Chiller On/Off Command 4 Relay Contact
b. Chiller Run Status 4 Potential free contact from the
Chiller DB panel
c. Chiller Auto/Manual Status 4 Potential free contact from the
Chiller DB panel
d Chiller trip/fault 4 Potential free contact from the
Chiller DB panel
e Individual Chiller Chilled water supply temp 8 Immersion type sensor
in (1) + out
f Ambient Temperature 1 Outside air temp & RH sensor
g Ambient RH 1
h Header Chill water supply & Return 2 Immersion type sensor
Temperature
i Chiller water flow switch 4 Water flow switch
k Butterfly Valve Open / Close Command 4 Relay Output from DDC to
Motorized Butterfly Valves
l Butterfly Valve Open / Close Status 4 Pot Free Contact From Motorized
Butterfly Valves

Sub Total 20 12 8 0

Primary Chilled Water Pumps 4


1 Pump start / stop 4 Volt Free Contact from BMS to
Pump panel
2 Pump run status 4 Differential Pressure Switch
3 Pump Auto / Manual switch status 4 Volt Free Contact to BMS from
Pump panel
Sub Total 8 0 4 0

Secondary Chilled Water Pumps 4


1 Pump start / stop 4 Volt Free Contact from BMS to
Pump panel
2 Pump run status 4 Differential Pressure Switch
3 Pump Auto / Manual switch status 4 Volt Free Contact to BMS from
Pump panel
4 VFD Speed Control 4 BMS Vender to provide VFD
5 VFD Speed Feedback 4 BMS Vender to provide VFD
Sub Total 8 4 4 4

Condeuser Pumps 4
1 Pump start / stop 4 Volt Free Contact from BMS to
Pump panel
2 Pump run status 4 Differential Pressure Switch
3 Pump Auto / Manual switch status 4 Volt Free Contact to BMS from
Pump panel
Sub Total 8 0 4 0

CooLing Towerfans 3
1 Pump start / stop 3 Volt Free Contact from BMS to
Pump panel
2 Pump run status 3 Differential Pressure Switch
3 Pump Auto / Manual switch status 3 Volt Free Contact to BMS from
Pump panel
Sub Total 6 0 3 0

Chiller Plant 50 16 23 4

2 AHU(GENEARAL) 24
a AHU ON/OFF command 24 Relay output from DDC
b AHU run status 24 Differential pressure switch(Air)

c AHU A/M status 24 Potential free contact from the AHU


DB panel
d AHU filter status 24 Differential pressure switch(filter)

e Return Air Temperature sensor 24 Duct Temp. Sensor


g 2 Way Modulating CHW Valve with Actuator 24 2 way modulating valve + Actuator

3 AHU- -( Opeation theatre) 12


1 AHU VFD ENABLE 12 AT AHU LOCAL PANEL
2 AHU VFD SPEED CONTROL 12 AT AHU LOCAL PANEL
3 AHU BLOWER STATUS 12 AIR DP SWITCH
4 AHU AUTO MANUAL STATUS 12 AT AHU LOCAL PANEL
5 AHU SUPPLY AIR TEMP 12 DUCT TEMP. SENSOR
6 AHU RETURN AIR TEMP 12 DUCT TEMP. SENSOR
AHU FRESH AIR TEMP 12 DUCT TEMP. SENSOR
7 AHU RETURN AIR HUMIDITY 12 DUCT HUMIDITY SENSOR
8 AHU CHW MODULATING VALVE 12 MODULATING VALVE
Command
9 AHU CHW MODULATING VALVE STATUS 12 MODULATING VALVE

10 RETURN AIR FAN STATUS 12 AT AHU LOCAL PANEL


11 FILTER STATUS 12 AIR DP TRANSMITTER
12 ROOM TEMPERATURE 12 ROOM TEMP. SENSOR
13 FRESH AIR DAMPER STATUS 12 AT DAMPER
14 FRESH AIR DAMPER CONTROL 12 AT DAMPER
15 PRE-FILTER STATUS 12 AIR DP SWITCH
16 MICROVEE FILTER STATUS 12 AIR DP TRANSMITTER
AHU SUB TOTAL 144 120 48 36
4 FCUs 24
1 Start/Stop 24 Potential Free Contact from BMS to
FCU panel
2 Room Air Temp 24 Temp. Sensor inbuilt with display
and set poinit adjustment

3 Modulate Chilled Water Valve 24 2 Way Control Valve


4 3 speed fan control 24 Potential Free Contact from BMS to
FCU panel

Sub Total for FCU 0 24 48 24

5 Exhaust Fan 10
1 Fan ON/OFF command 10 Pot Free contact
2 Fan run status 10 Pot Free contact
3 Fan A/M status 10 Pot Free contact
Total Exhaust fan 20 0 10 0

6 Water Treatment Plant - 1


a Pump On/Off Control 2 Relay output from DDC
b Pump Flow Monitoring 2 Differential Pressure Switch
c Pump A/M status 2 Potential free contact
d Pump trip status 2 Potential free contact
e Treated Water Sump Level Monitoring 2 Level Switch
TOATAL FOR WATER TREATMENT 8 0 2 0
PLANT

DRINKING WATER PUMP (2 Nos) 2


a Pump On/Off Control 2 Relay output from DDC
c Pump A/M status 2 Potential free contact
e Treated Water Sump Level Monitoring 2 Level Switch
Total for DRINKING WATER PUMP 4 0 2 0

Water Management System 12 0 4 0

8 MV PANEL - 1 No 1
a Breaker On/Off status 5 Voltfree terminal from Panel
b Earth Fault 2 Voltfree terminal from Panel
c Over Current Alarm 8 Voltfree terminal from Panel
Total MV Panel 15 0 0 0

TOTAL PLANT IO's 444 304 247 124


9 INTEGRATION
Third Party Integration on
BACNET/Modbus
a VRVInterface -Bacnet/Modbus 3 Through Software Integration
communication
b VFD for Secondary Pump 4 Through Software Integration
c Energy Meter Communication 12 Through Software Integration
d Lift 6 Through Software Integration