2727 Input Output Summary
2727 Input Output Summary
Sl.
Description Qty DI AI DO AO Filed devices
No
1 CHILLERS-4 4 4
a. Chiller On/Off Command 4 Relay Contact
b. Chiller Run Status 4 Potential free contact from the
Chiller DB panel
c. Chiller Auto/Manual Status 4 Potential free contact from the
Chiller DB panel
d Chiller trip/fault 4 Potential free contact from the
Chiller DB panel
e Individual Chiller Chilled water supply temp 8 Immersion type sensor
in (1) + out
f Ambient Temperature 1 Outside air temp & RH sensor
g Ambient RH 1
h Header Chill water supply & Return 2 Immersion type sensor
Temperature
i Chiller water flow switch 4 Water flow switch
k Butterfly Valve Open / Close Command 4 Relay Output from DDC to
Motorized Butterfly Valves
l Butterfly Valve Open / Close Status 4 Pot Free Contact From Motorized
Butterfly Valves
Sub Total 20 12 8 0
Condeuser Pumps 4
1 Pump start / stop 4 Volt Free Contact from BMS to
Pump panel
2 Pump run status 4 Differential Pressure Switch
3 Pump Auto / Manual switch status 4 Volt Free Contact to BMS from
Pump panel
Sub Total 8 0 4 0
CooLing Towerfans 3
1 Pump start / stop 3 Volt Free Contact from BMS to
Pump panel
2 Pump run status 3 Differential Pressure Switch
3 Pump Auto / Manual switch status 3 Volt Free Contact to BMS from
Pump panel
Sub Total 6 0 3 0
Chiller Plant 50 16 23 4
2 AHU(GENEARAL) 24
a AHU ON/OFF command 24 Relay output from DDC
b AHU run status 24 Differential pressure switch(Air)
5 Exhaust Fan 10
1 Fan ON/OFF command 10 Pot Free contact
2 Fan run status 10 Pot Free contact
3 Fan A/M status 10 Pot Free contact
Total Exhaust fan 20 0 10 0
8 MV PANEL - 1 No 1
a Breaker On/Off status 5 Voltfree terminal from Panel
b Earth Fault 2 Voltfree terminal from Panel
c Over Current Alarm 8 Voltfree terminal from Panel
Total MV Panel 15 0 0 0