Fire Alarm Systems - FPC-500 Conventional Fire Panel
Fire Alarm Systems - FPC-500 Conventional Fire Panel
Fire Alarm Systems - FPC-500 Conventional Fire Panel
System Overview
1 LEDs
2 LCD display with zone numbers
2 | FPC-500 Conventional Fire Panel
3 Zone keys and zone status LEDs • For optimum battery life, the fire panel should only be
operated at permissible operating temperatures (0°C
4 Operating panel to +40°C).
• Country-specific standards and guidelines must be
Functions observed when planning.
• Note the requirements of your local authorities and
The fire panels of FPC-500 series have the following institutions (police, fire service).
features available: • For an operation of the fire detection system
• Alarm verification according to EN 54‑13, it is required to terminate
• Dual-detector dependency every zone with an EOL module.
• Dual-zone dependency
• Intermediate alarm storage Maintenance
• Programmable delays Have maintenance and inspection work carried out
• Switching between day and night mode (AV) regularly by trained, qualified personnel. Bosch
• Event and test history Sicherheitssysteme GmbH recommends a functional
• Alarm counter and visual inspection at least once a year.
Operating levels Specifications according to EN 54-4 chapter 7.1
The fire panels have three different operating levels. a) It is a power supply equipment, used in the fire
No access code is required for level 1. Access to level alarm system FPC‑500. It supplies the fire alarm
2 and 3 requires four-digit codes (level 2 also system and the connected peripherals, and charges
accessible with optional key switch). The access codes the two connectable batteries.
for level 2 and 3 can be changed. b) Technical specifications
Different test functions are available. On level 1 LED,
buzzer and LCD tests can be run. On level 2 and 3 1) Recommended load 61 W
additional tests for zones, outputs and NACs can be 2) Input voltage 230 VAC +10%/-15%, 50-60 Hz
run.
Operating voltage 26 VDC – 29 VDC
Programming
You can program the panel easily via the keypad and 3) Communication parameter none
LCD display. The zones can be configured
4) Fuse ratings 3.15A / 250 V
independently allowing for a perfect tailoring to
individual customer needs. The default programming 5) Batteries 2 x 7.0 – 7.2 Ah (max.) Lead-Acid
helps getting acquainted quickly with the system and Battery
must be modified slightly to fit many applications. 6) Current consumption, max 2.3 A
Certifications and Approvals 7) Battery, max. internal 800 mOhm
resistance
The provided options according to EN 54‑2:1997/
A1:2006 include: Imin 70 mA
• Alarm counter
• Test condition Imax, a 0.7 A
• Output to fire alarm devices Imax, b 2.3 A
• Delays to outputs
• Dependencies on more than one alarm signal 9) Line parameter
– Type A dependency
– Type B dependency Battery Cable comes standard
Housing material
• Front ABS+PC
• Back ABS-FR
Housing color
Environmental conditions
Protection class as IP 30
per IEC 60529
Protection class as II
per EN 60950
5 | FPC-500 Conventional Fire Panel
Represented by:
© Bosch Security Systems 2012 | Data subject to change without notice
1252291339 | en, V3, 21. May 2012