Fire Alarm Systems - FPC-500 Conventional Fire Panel

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

Fire Alarm Systems | FPC-500 Conventional Fire Panel

FPC-500 Conventional Fire Panel


www.boschsecurity.com

u High-value modern optics – suitable for public


access areas

u Plain text LCD

u Available for 2, 4 or 8 detector zones for up to 64,


128 or 256 detectors

u Optional use of EOL module (EN 54-13 requirement)

u Strong 3 A power supply

The FPC‑500‑x Conventional Fire Panel is the ideal Z1…Z8 Up to 8 zones


solution for small and medium-sized objects. Thanks to
the proven conventional line technology a cost-saving IN1, IN2 Up to 2 inputs (FPC‑500‑2 and FPC‑500 4 one input)
fire alarm system can be set up. Two NAC outputs (500 mA each)
Three types are available:
• FPC‑500‑2: 2 zones for up to 64 detectors ALARM RLY, Alarm and fault relay
FAULT RLY
• FPC‑500‑4: 4 zones for up to 128 detectors
• FPC‑500‑8: 8 zones for up to 256 detectors AUX AUX power supply (500 mA)
With the integrated LCD display, the panel can be
Emergency power supply, up to 2 x 7.2 Ah
programmed and operated.
The optional extensions such as relay modules, open
collector modules and key switches allow further
tailoring to user needs.

System Overview

1 LEDs
2 LCD display with zone numbers
2 | FPC-500 Conventional Fire Panel

3 Zone keys and zone status LEDs • For optimum battery life, the fire panel should only be
operated at permissible operating temperatures (0°C
4 Operating panel to +40°C).
• Country-specific standards and guidelines must be
Functions observed when planning.
• Note the requirements of your local authorities and
The fire panels of FPC-500 series have the following institutions (police, fire service).
features available: • For an operation of the fire detection system
• Alarm verification according to EN 54‑13, it is required to terminate
• Dual-detector dependency every zone with an EOL module.
• Dual-zone dependency
• Intermediate alarm storage Maintenance
• Programmable delays Have maintenance and inspection work carried out
• Switching between day and night mode (AV) regularly by trained, qualified personnel. Bosch
• Event and test history Sicherheitssysteme GmbH recommends a functional
• Alarm counter and visual inspection at least once a year.
Operating levels Specifications according to EN 54-4 chapter 7.1
The fire panels have three different operating levels. a) It is a power supply equipment, used in the fire
No access code is required for level 1. Access to level alarm system FPC‑500. It supplies the fire alarm
2 and 3 requires four-digit codes (level 2 also system and the connected peripherals, and charges
accessible with optional key switch). The access codes the two connectable batteries.
for level 2 and 3 can be changed. b) Technical specifications
Different test functions are available. On level 1 LED,
buzzer and LCD tests can be run. On level 2 and 3 1) Recommended load 61 W
additional tests for zones, outputs and NACs can be 2) Input voltage 230 VAC +10%/-15%, 50-60 Hz
run.
Operating voltage 26 VDC – 29 VDC
Programming
You can program the panel easily via the keypad and 3) Communication parameter none
LCD display. The zones can be configured
4) Fuse ratings 3.15A / 250 V
independently allowing for a perfect tailoring to
individual customer needs. The default programming 5) Batteries 2 x 7.0 – 7.2 Ah (max.) Lead-Acid
helps getting acquainted quickly with the system and Battery
must be modified slightly to fit many applications. 6) Current consumption, max 2.3 A
Certifications and Approvals 7) Battery, max. internal 800 mOhm
resistance
The provided options according to EN 54‑2:1997/
A1:2006 include: Imin 70 mA
• Alarm counter
• Test condition Imax, a 0.7 A
• Output to fire alarm devices Imax, b 2.3 A
• Delays to outputs
• Dependencies on more than one alarm signal 9) Line parameter
– Type A dependency
– Type B dependency Battery Cable comes standard

PCB power supply factory-made wiring


Region Certification
230 V power supply 1.5 mm2 standard cable (max.)
Europe CE FPC-500
c) The power supply equipment is a pre-assembled
Germany VdS VdS-G211100 FPC-500
part of the FPC‑500 Conventional Fire Panel. No
Europe CPD 0786-CPD-21105 FPC-500 additional installation information is required.
Croatia ELTEH 145-SF/12 FPC 500
1) For environmental conditions see technical
specifications beneath.
Installation/Configuration Notes 2) The power supply equipment is a pre-assembled
part of the FPC‑500 Conventional Fire Panel. No
• The fire panel must be mounted indoors in a dry, additional mounting instructions are required.
maintained place, note environmental conditions (see 3) Refer to installation guide FPC‑500 for connecting
Technical Data). instructions.
• Mount the fire panel to the wall with the LCD at eye
level.
3 | FPC-500 Conventional Fire Panel

d) The power supply equipment is a pre-assembled Electrical


part of the FPC‑500 Conventional Fire Panel. No
FPC‑500‑2 FPC‑500‑4 FPC‑500‑8
additional commissioning instructions are required.
e) The power supply equipment is a pre-assembled Input voltage 230 VAC +10%/-15%, 50-60 Hz
part of the FPC‑500 Conventional Fire Panel. No
additional operating instructions are required. Max. current 275 mA 312 mA 375 mA
consumption AC
f) Have maintenance and inspection work carried out
regularly by trained, qualified personnel. Bosch Power consumption 80 W
Sicherheitssysteme GmbH recommends a functional
Operating voltage 21.4 VDC to 29 VDC
and visual inspection at least once a year.
Change the batteries regularly. Country-specific Imin 70 mA
standards and guidelines must be considered.
Imax, a 0.7 A
Parts Included
Imax, b 2.3 A
Qty. Components
Zones
1 Fire panel FPC-500-2/FPC-500-4/FPC-500-8
• voltage 20 VDC ±1VDC
1 Labeling strips for zones
• current max. 100 mA ±5 mA
1 Labeling strips for LEDs
• max. cable 22.5 Ω
1 Quick Installation Guide resistance
1 Quick Operation Guide AUX
1 CD with Installation and User Guide, battery calculator and • voltage 21 VDC to 29 VDC
software flashing tool
• current 500 mA ±10%
1 EOL resistors for zones and inputs
• max. cable 22.5 Ω
1 Battery cable set resistance
1 Cable ties for strain relief on power supply feeder • fuse 0.75 A @ 60 V
2 Rubber pads to fix batteries
NAC

Technical Specifications • voltage 21 VDC to 29 VDC

• current 500 mA ±10% each


FPC‑500‑2 FPC‑500‑4 FPC‑500‑8
• fuse 0.75 A @ 60 V
Detector zones 2 4 8
• max. cable 22.5 Ω
Max. number of 64 128 256
resistance
detectors in
accordance with Relay outputs
EN 54‑2
• contact rating 1 A @ 30 VDC
Max. number of 32
detectors per zone in • max. cable 22.5 Ω
accordance with resistance
EN 54‑2
OC outputs No inductive load.
Max. extension 0 1 2
modules • contact rating 20 mA @ 24 VDC

Prog. inputs 1 2 • max. cable 22.5 Ω


resistance
AUX output 1
recommended cable Unshielded cable, 0.8 mm cable diameter to
NAC output 2 type 1.5 mm² cable cross section
Relays 2 Batteries 2 x 7.2 Ah (max.)
Alarm counter 999 alarms • max. internal 800 mΩ
resistance
Event history 1000 events
• current 2.3 A
Test history 1000 test events consumption
4 | FPC-500 Conventional Fire Panel

• fuse 5 A @ 60 V EMC emmission EN 61000-6-3

Discharge voltage 21.4 V EMC immunity EN 50130-4


threshold
Vibrations EN 60068-2-6
Communication parameters
Permissible operating 0°C to +40°C
NAC temperature

Normal Permissible storage -10°C to +55°C


temperature
• A- 10 – 15 V
Permitted relative 95% non-condensing
• B+ 0 – 0,5 V humidity

Alarm Ordering Information


• A- 0–1V
FPC-500-2 Conventional Fire Panel
• B+ 21 – 29 V Order number FPC-500-2

Inputs FPC-500-4 Conventional Fire Panel


Order number FPC-500-4
• Alarm resistor 820 Ω ±5%
FPC-500-8 Conventional Fire Panel
• End of line resistor 3.9 kΩ ±1% Order number FPC-500-8
Zone (with resistors) Accessories
• Alarm resistor 820 Ω ±5% Relay Extension Module
910 Ω ±5% Order number FPC-500-RLYEXT
No dual-detector dependency:
680 Ω ±5% OC Extension Module
Order number FPC-500-OCEXT
• End of line resistor 3.9 kΩ ±1%
Access Key
Zone (with EOL-Module) Order number FPC-500-KEY
• Alarm resistor 820 Ω ±5%
FLM-320-EOL2W Conventional EOL Module 2-Wire
910 Ω ±5%
No dual-detector dependency: for EN 54‑13 compliant termination of conventional
680 Ω ±5% lines
Order number FLM-320-EOL2W
Mechanics
FLM-320-EOL4W-S Conventional EOL Module 4-Wire
FPC‑500‑2 FPC‑500‑4 FPC‑500‑8 for EN 54‑13 compliant termination of conventional
lines
Dimensions ( H x W x 351 x 351 x 90 mm Order number FLM-320-EOL4W-S
D)

Weight 2200 g, without batteries

Housing material

• Front ABS+PC

• Back ABS-FR

Housing color

• Front RAL 9003 (signal white)

• Back PANTONE 10 C (cool grey)

Environmental conditions

FPC‑500‑2 FPC‑500‑4 FPC‑500‑8

Protection class as IP 30
per IEC 60529

Protection class as II
per EN 60950
5 | FPC-500 Conventional Fire Panel

Represented by:
© Bosch Security Systems 2012 | Data subject to change without notice
1252291339 | en, V3, 21. May 2012