Technical Information
Input Terminals: . . . . . . . . . . . . . . . . . . . . . . . . . 18 to 12 AWG
006145
Size: . . . . . . . . . . . . . . . . . . . . . . 4 3/4 in. x 4 3/4 in. x 2 3/4 in.
(102 mm x 102 mm x 76 mm)
Weight: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.9 lb. WIRING DIAGRAM
Color: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Red TO NEXT
FROM
Operating Temperature: . . . . . 32 °F to 120 °F (0 °C to 49 °C) PRECEDING
APPLIANCE
OR EOLR
APPLIANCE
Mounting – Surface: 4 in. x 4 in. x 1.5 in. OR FACP
(102 mm x 102 mm x 38 mm)
standard back box (2.5 in. (64 mm)
recommended)
Semi-flush: 4 in. x 4 in. x 1.5 in.
(102 mm x 102 mm x 38 mm)
006146
standard back box (2.5 in. (64 mm)
recommended) with mounting plate 3-1-01
(order separately) 3-36
Listings and Approvals* STROBE CANDELA SELECTION – BACK VIEW
UL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . S5391
Factory Mutual Research Corporation (FMRC). . . . . Pending
California State Fire Marshal (CSFM). . . . . . . 7125-0785:141
MEA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151-92-E
CANDELA
*Listings and Approvals are under Wheelock Inc. SELECTOR
Ordering Information
Shipping
Part Weight
No. Model Description lb. (kg)
429698 RSS-24MCW-FR Strobe, 2.0 (0.9)
Multi Candela
429701 SFP Semi-flush Plate, 0.5 (0.2)
Composite
429702 ISP Adapter 0.5 (0.2)
006170
ANSUL INCORPORATED, ONE STANTON STREET, MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2001123 2001 Ansul Incorporated Litho in U.S.A.
ANSUL
Detection and Control Components
Electronic Sounder
Description
MOUNTING WITH OPTIONAL SEMI-FLUSH PLATE
The electronic sounder is UL listed for primary or secondary
signaling in life safety systems. One of eight different warning STANDARD BACK BOX
Technical Information
Input Terminals: . . . . . . . . . . . . . . . . . . . . . . . . . 18 to 12 AWG
Size: . . . . . . . . . . . . . . . . . . . . 5.125 in. x 5.125 in. x 2.125 in.
(130 mm x 130 mm x 54 mm) 006149
3-1-01
3-37
Technical Information (Continued)
WIRING DIAGRAM
TO NEXT
FROM
APPLIANCE
PRECEDING
OR EOLR
APPLIANCE
OR FACP
006146
Ordering Information
Shipping
Weight
Part No. Model Description lb. (kg)
429697 MT-12/24-R Horn, 24 VDC, 2 (0.9)
Multiple Tone
429701 SFP Semi-Flush Plate, 0.5 (0.2)
Composite
429700 IOB Surface Mount 2 (0.9)
Back Box,
Weatherproof
ANSUL INCORPORATED, ONE STANTON STREET, MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2001124 2001 Ansul Incorporated Litho in U.S.A.
ANSUL
Detection and Control Components
3-37.1
ANSUL INCORPORATED, ONE STANTON STREET, MARINETTE, WI 54143-2542 715-735-7411 Form No. F-99037 1999 Ansul Incorporated Litho in U.S.A.
ANSUL
Detection and Control Components
Description DIMENSIONS
The electronic sounder with strobe provides either indepen- 5 1/2”
5 1/8”
dent or simultaneous audible and visual alarm indication. 3 1/4”
The electronic sounder is UL listed for primary or secondary
signaling and the strobe is suitable for primary signaling in
public mode for life safety applications.
5 1/8” 2 3/4”
The strobe complies with the Americans with Disabilities Act
(ADA) and the demanding requirements of the UL 1971
Standard for the Hearing Impaired. Both 15 and 75 candela
strobes are available to meet the light intensity requirements 006165
3-1-01
3-38
Technical Information (Continued)
dBA AND CURRENT RATINGS FOR MULTITONE SIGNALS WITH STROBES
Typical Anechoic1 Rated Reverberant dBA2
dBA at 10 Feet at 10 Feet Per UL 464
Input Current At Nominal At Minimum At Nominal
Tone AMPS @ 24 VDC Input Voltage Input Voltage Input Voltage
HI STD HI STD HI STD HI STD
Horn 0.040 0.023 99 93 85 79 88 82
Bell 0.014 0.012 92 87 79 75 82 75
March Time Horn 0.040 0.023 99 93 82 75 85 79
Code-3 Horn 0.040 0.023 99 93 79 75 82 75
Code-3 Tone 0.028 0.017 95 90 75 70* 79 73*
Slow Whoop 0.048 0.026 99 94 82 75 85 79
Siren 0.036 0.023 98 93 82 75 85 79
HI/LO 0.020 0.014 93 88 79 75 82 75
1 Anechoic dBA is measured on axis in a non-reflective (free field) test room using fast meter response.
2 Reverberant dBA is a minimum UL rating based on sound power measurements in a reverberant test room.
CAUTION: This setting is acceptable only for general signaling (non-fire alarm) use. Use the “high” dBA setting with this tone or use a different tone for public mode
* fire alarm service.
WIRING DIAGRAM
Switch Settings
FROM PRECEDING TO NEXT
Tone POS POS POS
APPLIANCE OR RED APPLIANCE 2 3 4
FACP OR EOLR
BLACK Horn 1 1 1
Bell 1 0 1
March Time Horn 0 0 1
Code 3 Horn 1 1 0
006150
Code 3 Tone 0 1 1
STROBE AUDIBLE
Slow Whoop 0 1 0
Listings and Approvals* Siren 1 0 0
UL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E5496
HI/LO 0 0 0
Factory Mutual Research Corporation (FMRC):
15 cd . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0X1A0.AY
75 cd . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0Y8A1.AY
California State Fire Marshal (CSFM). . . . . . . 7135-0785:118
MEA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151-92-E
*Listings and Approvals are under Wheelock Inc.
Ordering Information
Shipping
Weight
Part No. Model Description lb. (kg)
429694 MT-24-LS-VFR Sounder/15 2 (0.9)
Candela Strobe
429695 MT-24-LS-VFR Sounder/75 2 (0.9)
Candela Strobe
429696 MT-24-WM-VFR Sounder/117 2 (0.9)
Candela Strobe
429701 SFP Semi-Flush Plate, 0.5 (0.2)
429700 IOB Surface Back Box 2 (0.9)
429702 ISP Adapter 0.5 (0.2)
ANSUL and AUTOPULSE are registered trademarks of Ansul Incorporated.
ANSUL INCORPORATED, ONE STANTON STREET, MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2001125 2001 Ansul Incorporated Litho in U.S.A.
ANSUL
Detection and Control Components
Description
Ansul alarm bells may be used to alert the occupant before 10 INCH BELL
10 IN.
and/or during actuation of the Ansul automatic fire suppres- (254 mm)
sion system and/or a general fire alert.
The Ansul motor driven alarm bell is designed to meet the
special requirements of fire alarm/release systems where
low power consumption and high sound output is essential.
Due to its low current drain, high level output sound can be
achieved with multiple units on a single 2-wire output circuit.
The bells are constructed of high quality materials to ensure
reliability and long life. The basic mechanism, gong and
accessories have a baked, red enamel finish. Holes are 3 3/8 IN.
located to mount to a standard 4 in. (102 mm) square outlet (86 mm)
box. A weatherproof back box is available for outdoor use.
Technical Information
Input Terminals: . . . . . . . . . . . . . . . . . . . . . . . . . 22 to 12 AWG 3 3/8 IN.
(86 mm)
Bell Sizes: . . . . . . . . . . . . 6 in. (152 mm) and 10 in. (254 mm)
Voltage Rating: . . . . . . . . . . . . . . . . . . . . . . . . . . 18 – 31 VDC 2 3/4 IN.
(70 mm)
Current Draw: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 mA
Decibel Level: . . . . . . . . . . . . . . . 92 dBA @ 10 ft. (3048 mm)
Operating Temperature: . . –31 °F to 150 °F (–35 °C to 66 °C)
@ 95% humidity (when used with WIRING FOR BELL
WBB, weatherproof back box)
TO NEXT FROM
DEVICE CONTROL
OR EOL UNIT
3-39
Listings and Approvals
UL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E71424
ULC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ML338
Factory Mutual Research Corporation (FMRC) . . . 0V1A5.KY
California State Fire Marshal (CSFM). . . . . . . 7135-0595:110
Ordering Information
Shipping
Weight
Part No. Description lb. (kg)
417805 Alarm Bell, 24 VDC, 6 in. (152 mm) 7 (3.2)
417806 Alarm Bell, 24 VDC, 10 in. (254 mm) 9 (4.1)
24747 WBB, Surface Mount Back Box, 2 (0.9)
Weatherproof
ANSUL and AUTOPULSE are registered trademarks.
ANSUL INCORPORATED, ONE STANTON STREET, MARINETTE, WI 54143-2542 715-735-7411 Form No. F-95116 1995 Ansul Incorporated Litho in U.S.A.