SEMCO’s Velocity™ gasketed joint system will save you time and money when installing a duct system. SEMCO
manufactures this product to very close tolerances to make sure the gasket blade seals securely. In order to maintain
these tolerances and achieve the desired integrity of the joint, please follow these installation instructions carefully.
Carefully inspect to make sure that all ends are round (See Figure 1)
and have not been damaged in shipment or handling.
Some minor deformation can occur during the shipping and handling
process (See Figure 2). This minor deformation can be corrected in the
field. It is important that the round shape of both spiral duct and fitting
ends be maintained to ensure the proper sealing of the gasket ring.
Check the spiral duct ends and remove any burrs and/or other sharp
edges to avoid cutting the gasket ring. FIGURE 2. Straighten edges
3. Installation:
4. Velocity Gasket:
Just slide the joint together and the “T” shaped gasket will lay back in
place (See Figure 4), sealing the fitting.
Once the gasket is completely inserted into the duct Once the piece is in place, fasten the joint by placing
end, slide the pieces together until the duct end tek screws or pop-rivets .5” to .75” from the bead
contacts the fitting bead. (figure 6). This distance should be maintained to avoid
placing a fastener through the gasket.
SINGLE WALL
SPIRAL DUCT
SECTION A-A
VELOCITY DUCT
GASKET CONNECTION
FIGURE 6.
Cutaway image illustrates the gasket in its final Mechanically fasten
position, sealing the fitting
SMACNA recommends that screws be placed at uniform intervals (15” maximum) along the circumference of
the duct joint. Minimum of 3 screws per joint.