The Code of Practice For The Electricity (Wiring) Regulations 2015 Edition (Summary of Updates)

The document summarizes updates made to The Code of Practice for the Electricity (Wiring) Regulations 2015 Edition. It provides updated maximum earth fault loop impedance values for 0.4 second and 5 second disconnection times for circuits protected by general purpose and motor circuit fuses. It also includes an updated form for issuing electrical work permits in Chinese.

Uploaded by

Jack So
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
58 views1 page

The Code of Practice For The Electricity (Wiring) Regulations 2015 Edition (Summary of Updates)

The document summarizes updates made to The Code of Practice for the Electricity (Wiring) Regulations 2015 Edition. It provides updated maximum earth fault loop impedance values for 0.4 second and 5 second disconnection times for circuits protected by general purpose and motor circuit fuses. It also includes an updated form for issuing electrical work permits in Chinese.

Uploaded by

Jack So
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

The Code of Practice for the Electricity (Wiring) Regulations 2015 Edition (Summary of Updates)

Area of Pages Date of Content


Updates Updates
Table 11(8)
Maximum Earth Fault Loop Impedance for 0.4 Sec. Disconnection when
the Circuit is Protected by General Purpose (gG) Fuses and Motor Circuit
Application (gM) fuses to BS88-2 Fuse Suytem E (bolted)
and G (clip-in) with Nominal Voltage Uo 220V
Table 11(8) Page 89
Fuse Rating (Amp) 2 4 6 10 16 20 25 32
Zs (ohm) 33.3 15.7 7.85 4.68 2.44 1.69 1.29 1.00
Note: The table is based on nominal voltage to earth with nominal voltage Uo at 220V and for reference only. Please refer to
the manufacturer’s data

Table 11(11)
Maximum Earth Fault Loop Impedance for 5 Sec. Disconnection
when a Circuit is Protected by General Purpose (gG) Fuses and Motor
Circuit Application (gM) fuses to BS88-2 Fuse System E (bolted)
25 Feb 2016 and G (clip-in) with Nominal Voltage Uo 220V
Table 11(11) Page 90
Fuse Rating
2 4 6 10 16 20 25 32 40 50 63 80 100 125 160 200
(Amp)
Zs (ohm) 44.0 20.9 12.2 6.87 4.00 2.82 2.20 1.76 1.29 1.00 0.78 0.55 0.42 0.32 0.26 0.18

Note: The table is based on nominal voltage to earth with nominal voltage Uo at 220V and for reference only. Please refer to
the manufacturer’s data