Flowmeter 2051CF
Flowmeter 2051CF
Flowmeter 2051CF
June 2013
00813-0400-4485, Rev EC
2-year stability
Conventional bid spec compliance - optional reference accuracy and stability improvements
Ease-of-Use features, enhanced EDDL screens, optional external zero and span buttons
Rosemount DP Flow June 2013
(1) The enhanced 4-20 mA HART device can be ordered with Transmitter Output option code A plus any of
the following new option codes: M4, QT, DZ, CR, CS, CT, HR5, HR7.
Additional Information
Specifications: page 20
Product Certifications: page 25
Dimensional Drawings: page 37
Installation and Flowmeter Orientation: Click Here
Contents
Rosemount 2051CF Flowmeter Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2
Rosemount 2051CFA Annubar Flowmeter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3
Rosemount 2051CFC Compact Flowmeter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 9
Rosemount 2051CFP Integral Orifice Flowmeter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 14
2051CF specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 20
Rosemount 2051CF product certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 25
Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 37
Installation and Flowmeter Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Click Here
2 www.rosemount.com
June 2013 Rosemount DP Flow
Ideal for large line size installations when cost, size, and weight of the flowmeter are concerns
www.rosemount.com 3
Rosemount DP Flow June 2013
4 www.rosemount.com
June 2013 Rosemount DP Flow
www.rosemount.com 5
Rosemount DP Flow June 2013
www.rosemount.com 7
Rosemount DP Flow June 2013
(1) Provide the “A” dimension for Flanged (page 38) and Pak-Lok (page 37).
(2) HART Revision 5 is the default HART output. The Enhanced 3051 can be factory or field configured to HART Revision 7. To order HART Revision 7 factory configured,
add option code HR7.
(3) Material specified is cast as follows: CF-8M is the cast version of 316 SST, CF-3M is the cast version of 316L SST. For housing, material is aluminum with polyurethane
paint.
(6) Instrument Connections for Remote Mount Options and Isolation Valves for Flo-tap Models are not included in the Material Traceability Certification.
(7) Materials of Construction comply with metallurgical requirements within NACE MR0175/ISO for sour oil field production environments. Environmental limits apply
to certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments.
(10) Only available with 4-20 mA HART output (output Code A).
(11) The T1 option is not needed with FISCO Product Certifications, transient protection is included with the FISCO Product Certification code IA.
(12) Only available with 4-20 mA HART (output codes A and M).
(13) NAMUR-Compliant operation is pre-set at the factory and cannot be changed to standard operation in the field.
(14) The V5 option is not needed with the T1 option; external ground screw assembly is included with the T1 option.
(15) Configures the HART output to HART Revision 5. The device can be field configured to HART Revision 7 if needed.
8 (16) Configures the HART output to HART Revision 7. The device can be field configured to HART Revision 5 if needed. www.rosemount.com
June 2013 Rosemount DP Flow
www.rosemount.com 9
Rosemount DP Flow June 2013
12 www.rosemount.com
June 2013 Rosemount DP Flow
(2) For the 10-in. (250 mm) and 12-in. (300 mm) line size, the alignment ring must be ordered (Installation Accessories).
(3) 10-in. (250 mm) and 12-in. (300 mm) line sizes not available with Primary Element Technology A.
(4) For 2-in. (50 mm) line sizes the Primary Element Type is 0.6 for Primary Element Technology Code C.
(6) HART Revision 5 is the default HART output. The Enhanced 3051 can be factory or field configured to HART Revision 7. To order HART Revision 7 factory configured, add
option code HR7.
(7) Material specified is cast as follows: CF-8M is the cast version of 316 SST, CF-3M is the cast version of 316L SST. For housing, material is aluminum with polyurethane paint.
(11) For Annubar Option A, consult factory for pipe schedules other than Sch. 40.
(14) Select Configuration Buttons (option code D4 or DZ) or Local Operator Interface (option code M4) if local configuration buttons are required.
(15) Only available with 4-20 mA HART output (output Code A).
(16) Materials of Construction comply with metallurgical requirements within NACE MR0175/ISO for sour oil field production environments. Environmental limits apply to
certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments.
(18) The T1 option is not needed with FISCO Product Certifications, transient protection is included with the FISCO Product Certification code IA.
(20) NAMUR-Compliant operation is pre-set at the factory and cannot be changed to standard operation in the field.
(21) Only available with 4-20 mA HART (output codes A and M).
(22) The V5 option is not needed with the T1 option; external ground screw assembly is included with the T1 option.
(23) Configures the HART output to HART Revision 5. The device can be field configured to HART Revision 7 if needed.
(24) Configures the HART output to HART Revision 7. The device can be field configured to HART Revision 5 if needed.
www.rosemount.com 13
Rosemount DP Flow June 2013
Self-centering plate design prevents alignment errors that magnify measurement inaccuracies in small line
sizes
14 www.rosemount.com
June 2013 Rosemount DP Flow
16 www.rosemount.com
June 2013 Rosemount DP Flow
www.rosemount.com 17
Rosemount DP Flow June 2013
(1) To improve pipe perpendicularity for gasket sealing, socket diameter is smaller than standard pipe O.D.
(2) HART Revision 5 is the default HART output. The Enhanced 3051 can be factory or field configured to HART Revision 7. To order HART Revision 7 factory configured, add
option code HR7.
(3) Material specified is cast as follows: CF-8M is the cast version of 316 SST, CF-3M is the cast version of 316L SST. For housing, material is aluminum with polyurethane
paint.
(8) Not available for bore sizes 0010, 0014, 0020, 0034, 0066, or 0109.
(9) Not available with DIN Process Connection codes D1, D2, or D3.
(10) Materials of Construction comply with metallurgical requirements within NACE MR0175/ISO for sour oil field production environments. Environmental limits apply to
certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments.
18 www.rosemount.com
June 2013 Rosemount DP Flow
(12) Select Configuration Buttons (option code D4 or DZ) or Local Operator Interface (option code M4) if local configuration buttons are required.
(13) Only available with 4-20 mA HART output (output Code A).
(15) The T1 option is not needed with FISCO Product Certifications, transient protection is included with the FISCO Product Certification code IA.
(17) NAMUR-Compliant operation is pre-set at the factory and cannot be changed to standard operation in the field.
(18) Only available with 4-20 mA HART (output codes A and M).
(19) The V5 option is not needed with the T1 option; external ground screw assembly is included with the T1 option.
(20) Configures the HART output to HART Revision 5. The device can be field configured to HART Revision 7 if needed.
(21) Configures the HART output to HART Revision 7. The device can be field configured to HART Revision 5 if needed.
www.rosemount.com 19
Rosemount DP Flow June 2013
2051CF specifications
Rosemount 2051CF performance specifications
Performance assumptions include: measured pipe I.D, transmitter is trimmed for optimum flow accuracy, and performance is
dependent on application parameters.
(1) Range 1 flowmeters may experience an additional uncertainty up to 0.9%. Consult your Emerson Process
Management Representative for exact specifications.
20 www.rosemount.com
June 2013 Rosemount DP Flow
www.rosemount.com 21
Rosemount DP Flow June 2013
Power Consumption
3.0 mA, 27–84 mW
Output Load Pressure and Temperature Limits(1)
Direct Mount Transmitter
100 k or greater
Turn-On Time Up to 600# ANSI (1440 psig at 100 °F (99 bar at 38 °C))
Performance within specifications less than 2.0
seconds after power is applied to the transmitter. Integral temperature measurement is not available with
Flanged mounting type greater than class 600
Overpressure Limits
Remote Mount Transmitter
Transmitters withstand the following limits without damage:
Up to 2500# ANSI (6000 psig at 100 °F (416 bar at 38 °C)).
2051CF Flowmeters
(1) Static pressure selection may effect pressure limitations.
Ranges 2–5: 3626 psig (250 bar)
4500 psig (310,3 bar) for option code P9
For 2051CFC Temperature Limits-Process Temperature
Range 1: 2000 psig (137,9 bar) Limits
Direct Mount Transmitter
Static Pressure Limit
-40 to 450 °F (-40 to 232 °C)
Operates within specifications between static line pressures
Up to 400 °F (204 °C) when top mounted in steam service
of -14.2 psig (0.034 bar) and 3626 psig (250 bar)
Remote Mount Transmitter
Range 1: 0.5 psia to 2000 psig (34 mbar and 137,9 bar)
-148 to 850 °F (-100 to 454 °C) – Stainless Steel
Burst Pressure Limits
For 2051CFP Temperature Limits-Process Temperature
Limits
2051CF
Standard (direct/remote mount):
10000 psig (689,5 bar)
–40 to 450 °F (–40 to 232 °C)
Temperature Limits Extended (remote mount only with option code G):
For 2051CFA Temperature Limits-Process Temperature –148 to 850 °F (–100 to 454 °C)
Limits
Direct Mount Transmitter
Transmitter Temperature Limits:
500 °F (260 °C)
Ambient(1)
750 °F (398 °C) when used with a direct mount, high –40 to 185 °F (–40 to 85 °C)
temperature 5-valve manifold (Transmitter Connection With LCD display(2): –40 to 175 °F (–40 to 80 °C)
Platform code 6). Maximum temperature limit for steam
processes is 650 °F (343 °C). Storage(1)
–50 to 230 °F (–46 to 110 °C)
400 °F (204 °C) when top mounted in steam service With LCD display: –40 to 185 °F (–40 to 85 °C)
Remote Mount Transmitter
(1) Limits for silicone fill fluid only.
1250 °F (677 °C) – Alloy C-276 Sensor Material (For
superheated steam applications above 1000 °F (538 °C), it is (2) LCD display may not be readable and LCD updates will be slower at
temperatures below -4 °F (-20 °C).
recommended that the Rosemount 585 with Alloy 800H
sensor material is used.)
22 www.rosemount.com
June 2013 Rosemount DP Flow
Dynamic Performance
4-20 mA HART(1)
FOUNDATION Typical HART Transmitter Response
1-5 Vdc HART Low
fieldbus(3) Time
Power
Total Response Time (Td + Tc)(2):
Transmitter Output vs. Time
2051CF, Range 3-5: 115 milliseconds 152 milliseconds Pressure Released
Range 1: 270 milliseconds 307 milliseconds
Td = Dead Time
Range 2: 130 milliseconds 152 milliseconds Td Tc
Tc = Time Constant
100%
60 milliseconds Response Time = Td +Tc
Dead Time (Td) 97 milliseconds
(nominal)
63.2% of Total
Update Rate 22 times per second 22 times per second 36.8%
Step Change
0%
(1) Dead time and update rate apply to all models and ranges; analog output only Time
(2) Nominal total response time at 75 °F (24 °C) reference conditions.
(3) Transmitter fieldbus output only, segment macro-cycle not included.
(1) Stainless steel temperature housing is not recommended with primary element technology A in applications with mechanical vibration.
www.rosemount.com 23
Rosemount DP Flow June 2013
316/316L SST ASTM A193 Gr B8M Class 2 body studs provided for high
temperature option code G
50 micro-inch Ra surface finish
Transmitter Connection Studs
Manifold Head/Valves
ASTM A193 Gr B8M studs
316 SST
Gaskets/O-rings
Flange Studs and Nuts
Glass filled PTFE
Customer supplied
Inconel® X-750 provided for high temperature option code G
Available as a spare part
Transmitter Connection Studs and Nuts Gaskets and O-rings must be replaced each time the 3051SFP
is disassembled for installation or maintenance.
Studs– A193 Grade B8M.
Process Isolating Diaphragms
Nuts– A194 Grade 8M. 316L SST, Alloy C-276, or Tantalum
Gasket and O-rings
Non-Wetted Parts for 2051CF
Gaskets are customer supplied.
Electronics Housing
Durlon 8500 fiber gaskets are recommended. Consult an Low-copper aluminum or CF-8M (Cast version of 316 SST).
Emerson Process Management representative for use with Enclosure Type 4X, IP 65, IP 66, IP68
other gaskets.
Coplanar Sensor Module Housing
Available as a spare part CF-3M (Cast version of 316L SST)
Note Bolts
Gaskets and O-rings should be replaced when the 405 is ASTM A449, Type 1 (zinc-cobalt plated carbon steel)
disassembled. ASTM F593G, Condition CW1 (Austenitic 316 SST)
ASTM A193, Grade B7M (zinc plated alloy steel)
For 2051CFP Wetted Parts-Material of Construction
Sensor Module Fill Fluid
Orifice Plate Silicone oil (D.C. 200) or Fluorocarbon oil (Halocarbon or
Fluorinert® FC-43 for 2051T)
316/316L SST
Paint
Alloy C-276
Polyurethane
Alloy 400
Cover O-rings
Nitirile Butadiene (NBR)
24 www.rosemount.com
June 2013 Rosemount DP Flow
www.rosemount.com 25
Rosemount DP Flow June 2013
Special Conditions for Safe Use (X): Markings: II 1 D Ex t IIIC T50 °C T500 60 °C Da
IP66 IP68
When the optional transient protection terminal block is Ui = 42.4 Vdc
installed, the apparatus is not capable of withstanding the 1180
500 V insulation test required by EN60079-11. This must
be taken into account when installing the apparatus. Special Conditions for Safe Use (X):
When the optional transient protection terminal block is 4. During installation, use and maintenance of the
installed, the apparatus is not capable of withstanding a product, observe the warning “Don’t open the cover when
500 V r.m.s. test to case. This must be taken into account the circuit is alive”.
on any installation in which it is used, for example by
5. During installation, there should be no present mixture
assuring that the supply to the apparatus is galvanically
harmful to the flameproof housing.
isolated.
6. Cable entry and conduit, certified by NEPSI with type of
Inmetro Certifications
protection Ex d IIC and appropriate thread form, should be
E2 Flame-Proof applied when installed in hazardous locations. Blanking
Certificate No: CEPEL 09.1767X elements should be used on the redundant cable entries.
Ex d IIC T* Ga/Gb IP66 7. End users are not permitted to change any internal
T6 = -50 °C Tamb 65 °C components, but to settle the problem in conjunction with
T5 = -50 °C Tamb 80 °C the manufacturer to avoid damage to the product.
I2 Intrinsic Safety 8. Maintenance should be done in non-hazardous
Certificate No: CEPEL 09.1768X locations.
Ex ia IIC T4 Ga (–60 °C Tamb +70 °C)
IP66 9. During installation, use and maintenance of this
product, observe the following standards:
China (NEPSI) Certifications
GB3836.13-1997 “Electrical apparatus for explosive gas
E3 Flameproof atmospheres Part 13: Repair and overhaul for apparatus
NEPSI Certificate No.: GYJ101321X used in explosive gas atmospheres”
Applicable Standards: GB3836.1-2000, GB3836.2-2000
Markings: Ex d II C T5/T6, GB3836.15-2000 “Electrical apparatus for explosive gas
T5: -50 °C Ta +80 °C atmospheres Part 15: Electrical installations in hazardous
T6: -50 °C Ta +65 °C area (other than mines)”
Specific Conditions for Safe Use (X): GB3836.16-2006 “Electrical apparatus for explosive gas
atmospheres Part 16: Inspection and maintenance of
1. Symbol “X” is used to denote specific conditions of use: electrical installation (other than mines)”
a. The Ex d blanking elements, cable glands and wiring GB50257-1996 “Code for construction and acceptance of
shall be suitable for a temperature of 90°C. electric device for explosion atmospheres and fire hazard
electrical equipment installation engineering”.
b. This device contains a thin wall diaphragm. Installation,
maintenance and use shall take into account the I3 Intrinsic Safety
environmental conditions to which the diaphragm will be NEPSI Certificate No.: GYJ101320X
subjected. Applicable Standards: GB3836.1-2000, GB3836.4-2000
Markings: Ex ia IIC T4
2. The relation between T code and ambient temperature
T4: -60°C Ta +70°C
range is:
Specific Conditions for Safe Use (X):
www.rosemount.com 27
Rosemount DP Flow June 2013
a. If the apparatus is fitted with an optional 90V transient 6. The cables between this product and associated
suppressor, it is not capable of withstanding the 500V apparatus should be shielded cables (the cables must have
insulation test for 1 minute. This must be taken into insulated shields). The shield has to be grounded reliably in
account when installing the apparatus. a non-hazardous area.
2. The relation between T code and ambient temperature 7. End users are not permitted to change any internal
range is: components, but to settle the problem in conjunction with
Temperature the manufacturer to avoid damage to the product.
Transmitter Model T Code
Range
8. During installation, use and maintenance of this
Using 644 temperature product, observe the following standards:
T4 -40 °C Ta +60 °C
transmitter
No 644 No FISCO GB3836.13-1997 “Electrical apparatus for explosive gas
T4 -60 °C Ta +70 °C atmospheres Part 13: Repair and overhaul for apparatus
temperature Version
transmitter FISCO Version T4 -60 °C Ta +60 °C used in explosive gas atmospheres”
28 www.rosemount.com
June 2013 Rosemount DP Flow
All CSA hazardous approved transmitters are certified per IA ATEX FISCO Intrinsic Safety
ANSI/ISA 12.27.01-2003. Certificate No: Baseefa08ATEX0129X
Applicable Standards: EN60079-0:2012,
E6 Explosion-Proof, Dust Ignition Proof EN60079-11:2012
Certificate No: 2041384 Markings: II 1 G Ex ia IIC T4 Ga(–60 °C Ta +60 °C)
Applicable Standards: CSA Std. C22.2 No. 142 - M1987, IP66 IP68
CSA Std. C22.2 No. 30 - M1986, CSA Std. C22.2 No. 213 - 1180
M1987, CAN/CSA-E60079-0:07,
CAN/CSA-E60079-1:07 Table 12. Input Parameters
Markings: Explosion-Proof for Class I, Division 1, Groups B, Ui = 30 V
C, and D. Dust-Ignitions Proof for Class II and Class III, Ii = 200 mA
Division 1, Groups E, F, and G. Suitable for Class I, Division Pi = 1.0 W
2, Groups A, B, C, and D for indoor and outdoor hazardous Ci = 0.012 μF
locations. Class I Zone 1 Ex d IIC T5. Enclosure type 4X,
factory sealed. Single Seal.
www.rosemount.com 29
Rosemount DP Flow June 2013
30 www.rosemount.com
June 2013 Rosemount DP Flow
www.rosemount.com 31
Rosemount DP Flow June 2013
32 www.rosemount.com
June 2013 Rosemount DP Flow
Combinations of Certifications
K5 E5 and I5 combination
K6 I6 and E6 combination
www.rosemount.com 33
Rosemount DP Flow June 2013
34 www.rosemount.com
June 2013 Rosemount DP Flow
www.rosemount.com 35
Rosemount DP Flow June 2013
36 www.rosemount.com
June 2013 Rosemount DP Flow
Dimensional drawings
Rosemount 2051CFA Pak-Lok Annubar Flowmeter(1)
Front View Side View Top View
B
C
(1) The Pak-Lok Annubar model is available up to 600# ANSI (1440 psig at 100 °F (99 bar at 38 °C)).
www.rosemount.com 37
Rosemount DP Flow June 2013
D
B
38 www.rosemount.com
June 2013 Rosemount DP Flow
www.rosemount.com 39
Rosemount DP Flow June 2013
40 www.rosemount.com
June 2013 Rosemount DP Flow
(1) Downstream length shown here includes plate thickness of 0.162-in. (4.11 mm).
www.rosemount.com 41
Rosemount DP Flow Product Data Sheet
00813-0100-4485 Rev EC June 2013