Fiamm Fit Battery Range
Fiamm Fit Battery Range
Fiamm Fit Battery Range
Applicable Standards
Applications and Key Benefits
- IEC 60896 Part 21 - VRLA methods of testing
Designed for high energy density front terminal - IEC 60896 Part 22 - VRLA requirements
Telecom installations - BS 6290 Part 4 - specifications for VRLA classification
Ideal for: - UL Recognized
- Telecom BTS - wireless application - Eurobat “Long Life” - 12 years and longer
- Outdoor wireline cabinets
- Broadband, microwave repeater and
fiber optic regeneration sites FIAMM Manufacturing
- Use in areas with stable on-grid power supply
- ISO 9001 Quality Management System
Suitable for discharge 30 min up to 10 hours - ISO 14001 Environmental Management System
Front terminal design for reduced headspace,
higher energy density and compact battery layout
Front terminal design reduces installation time
- Technical Features
and facilitates maintenance
19 or 23 inch and ETSI power racks / cabinets - Pasted plates and grids of high quality
lead-tin-calcium alloy
AGM gas recombination technology
- Electrolyte fully absorbed in glass mat AGM separators with
Minimal gassing and fit for remote venting
extremely high porosity
Non-spillable
- ABS IEC 707 FV0 and UL 94 V0 (LOI greater than 28%)
Maintenance free without topping-up flame retardant plastics
Non-hazardous for air/sea/rail/road transportation - Container and lid designed for unsurpassed mechanical
100% Recyclable strength made of thick walled plastics
- Thermally welded case-to-cover sealing avoids leakage
- Threaded terminal posts with brass inserts guarantee
highest conductivity, maximum torque retention and
easy installation
- High integrity post seal design to prevent electrolyte
leakage over a wide temperature range
- Flame arrestors prevent sparks or flames from
entering the battery
- Heavy-duty internal straps and through-the-partition cell
connections minimize internal resistance
- Front terminals for reduced headspace, higher energy
density and compact battery layout
- Fully insulated removable terminal covers with probe hole
for safe and easy voltage measurement
- Robust connectors for use also in high rate application
- Design allows connections to the top, the front or the side
- Lids have space for end-battery connection cables
- All models have removable rope handles
- Cells equipped with one-way safety valves to allow
excess gas to escape when overcharging
- Remote venting system available for applications which
require limited gassing to be vented externally
- < 2% self-discharge per month at 20°C allows
6 months shelf life
FIT
FIAMM reserves the right to change or revise without notice any information or detail given in this publication
Electrical Characteristics
FLOAT VOLTAGE CHARGE FOR STANDBY USE AT 20°C: 13.62 V/bloc (2.27 V/cell)
BOOST CHARGE: 14.4 V/bloc (2.40 V/cell)
FLOAT VOLTAGE TEMPERATURE COMPENSATION: -15 mV/°C/bloc
Dimensions
W L W L
W L
H
H
H
FIT_EMEA_2013_10_25
FIAMM S.p.A.
Industrial Batteries
www.fiamm.com
email:[email protected]