Automatic Transfer Switch (ATS) : I. History and Background
Automatic Transfer Switch (ATS) : I. History and Background
Automatic Transfer Switch (ATS) : I. History and Background
1
Automatic Transfer Switch (ATS)
In its most basic form, a transfer switch for a 120/240V single-phase service is simply a double-
pole, double-throw switch of proper ampere rating with a middle off position. By design, it is a physical
impossibility for both power sources to supply the load simultaneously, unless, of course, that is the
intent. It's also impossible for the two sources to mix — or for one source to backfeed into the other.
An automatic transfer switch having two sets of phase switches, one set for connection between a
normal source of power and a load, and the other set for connection between an emergency power source
and the load. The transfer switch includes two pairs of neutral switches, one pair for connection in parallel
between the normal source neutral and the load neutral, and the other pair for connection in parallel
between the emergency source neutral and the load neutral. The phase switches can operate to provide an
"open transition" transfer, wherein the phase switches connecting the load to one source open before
closing of the phase switches which connect the load to the other source, or a "closed transition" transfer,
wherein the phase switches connecting the load to one source open after closing of the phase switches
which connect the load to the other source. Prior to transfer operation, the pair of neutral switches
corresponding to the closed set of phase switches are closed and the pair of neutral switches
corresponding to the open set of phase switches are open. During transfer of the load, whether by open or
closed transition transfer, one neutral switch of each pair are closed before the open set of phase switches
close and those neutral switches remain closed until after the closed set of phase switches opens.
Thereafter, the pair of neutral switches which had originally been open are both closed, and the pair of
neutral switches which had originally been closed are both opened.
IV. Application
An ATS is a device that interfaces with a generator and the building's electrical system. It monitors
the utility power and signals the generator to start if the utility power goes out of spec or drops out entirely
(blackout). Backup power is now fed to the main utility panel or an emergency panel via the ATS.
V. Circuit Diagram
An ATS, typically, has two inputs and one output. The inputs are a standby generator and utility
power. The ATS will automatically turn on the generator in the event of a power failure or it can be
manually turned on due to an approaching storm or for UPS maintenance. Most critical facilities consider
their generators to be a more reliable and cleaner source of power than the utility.
VI. Conclusion
In some facilities, it is vitally important to have uninterrupted power. To achieve this goal, the
systems in the power path must be properly maintained and tested. To ensure reliability in the event of a
power outage, the importance of installation of the ATS is a must. As embodiment, an ATS or Automatic
Transfer Switch is a device that interfaces with a generator and the building's electrical system. It monitors
the utility power and signals the generator to start if the utility power goes out of spec or drops out entirely
(blackout). Backup power is now fed to the main utility panel or an emergency panel via the ATS.
VII. Reference
www.mcgsurge.com
www.searchdatacenter.techtarget.com