Precast Pile Analysis & Design.400

The document discusses the design and analysis of precast driven piles used for a service road project near a railway overbridge. It includes checks for: [1] Driving stress on the concrete during installation, [2] Lifting and pitching stresses during transportation, [3] Axial stress capacity, and [4] Uplift capacity. The analyses show that the pile section meets the strength requirements for these loads based on relevant codes.

Uploaded by

civixx
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
462 views4 pages

Precast Pile Analysis & Design.400

The document discusses the design and analysis of precast driven piles used for a service road project near a railway overbridge. It includes checks for: [1] Driving stress on the concrete during installation, [2] Lifting and pitching stresses during transportation, [3] Axial stress capacity, and [4] Uplift capacity. The analyses show that the pile section meets the strength requirements for these loads based on relevant codes.

Uploaded by

civixx
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

BANGLADESH-INDIA FRIENDSHIP POWER

COMPANY (PVT.) LIMITED

2x660MW MAITREE SUPER THERMAL POWER


PROJECT RAMPAL, BANGLADESH

OWNER’S CONSULTANT:

M/s FICHTNER GmbH & Co KG.


STUTTGART, GERMANY

[MAITREE-00-UTX-ED-421607C004PEM]
DOC. NO.: AAA-BBBB
REV-0

BHARAT HEAVY ELECTRICALS LIMITED


PROJECT ENGINEERING MANAGEMENT
NOIDA-201301
DESIGN & ANALYSIS OF PRECAST DRIVEN PILE (400mm X 400mm SQ)
PROJECT TITLE: SERVICE ROAD BESIDE JURAIN RAILWAY OVERBRIDGE.

TABLE OF CONTENTS
1.0 CHECK FOR DRIVING STRESS ------------------------------------------------------------------------------------------- 2

2.0 CHECK FOR LIFTING & PITCHING STRESS --------------------------------------------------------------------------- 2

3.0 CHECK FOR AXIAL STRESS ----------------------------------------------------------------------------------------------- 3

4.0 CHECK FOR UPLIFT CAPACITY ---------------------------------------------------------------------------------------- 3

November 2, 2017 Page 1 of 3


DESIGN & ANALYSIS OF PRECAST DRIVEN PILE (400mm X 400mm SQ)
PROJECT TITLE: SERVICE ROAD BESIDE JURAIN RAILWAY OVERBRIDGE.

1.0 CHECK FOR DRIVING STRESS

Formula for use with Diesel Hammer:


Ru= [12efEn/ (s+0.5(C1+C2+C3)] x [(Wr+e Wp) / (Wr+Wp)] ---------(I)
Where,
 Ru = ultimate carrying capacity of pile  s = set value
(considered as ultimate resistance to  C1= temporary compression allowance
driving) for pile head and cap.
 Wr= weight of falling mass, lb  C2= temporary compression of pile, inch.
 En=Rated energy per blow, ft-lb = Ru L/ AE
 ef= hammer efficiency =100 percent for  C3= temporary compression allowance
diesel hammer. for quake of ground
 Wp= weight of pile  A= average cross section of pile, Sq.inch
 L = length of pile, inch.  E= modulus of elasticity for pile
 e = coefficient of restitution material=57000√ f’c
Using the above equation,
Developed Stress on Concrete during driving = = 20.61 Mpa < 40 Mpa
[FOR DETAIL CALCULATION: APPENDIX-A]
Hence Safe for Concrete Compressive Strength at Driving.

2.0 CHECK FOR LIFTING & PITCHING STRESS

Total dead weight of pile, W ' =[0.40x0.40x25x18] kN= 72 kN


Factored Dead Weight of Pile, W =1.4 x 72 = 100.80 kN [ACI-318-14: TABLE 5.3.1]
 2.0.1. LIFTING & PITCHING
For two point lifting and pitching at L/10, maximum developed moment = WL/40 …(II)*
=100.80 X 18/40 = 45.36 kN-m

[*Ref.: Pile Design & Construction Practices by M. Tomlinson & J. Woodward] [5th
Edition/Page No.: 376]
Maximum Developed Moment, Mu=45.36 kN-m
2.0.1.1 MOMENT CAPACITY OF REINFORCED CONCRETE SECTION
So Moment Capacity of the section, Mc = 81.21 kN-m
[REF.: APPENDIX-B –ANALYSIS ON SECTION CAPACITY.]

November 2, 2017 Page 2 of 3


DESIGN & ANALYSIS OF PRECAST DRIVEN PILE (400mm X 400mm SQ)
PROJECT TITLE: SERVICE ROAD BESIDE JURAIN RAILWAY OVERBRIDGE.

HENCE SAFE FOR TWO-POINT LIFTING (AT 0.2 L).

3.0 CHECK FOR AXIAL STRESS


According to ACI-318-14-10.3.6 & ACI-318-14-22.4.2,
Axial Capacity of Pile with Lateral Ties:

φPn = 0.80 φ [0.85 fC’(Ag-Ast) + fyAst]


φPn = 0.80 X 0.65 X [0.85 X30 X (160000-1608.50) +500 X 1608.50)]
= 2518.48 kN = 251.84 TON

4.0 CHECK FOR UPLIFT CAPACITY

According to ACI 543-R-4.3.3.1, the uplift capacity of the section can be determined from the
following equation,

Pup =0.5 x fy x Ast


Pup =0.5 x 500 x 1608.50 =402125 N =40.213 kN. =40.213Ton

November 2, 2017 Page 3 of 3