One Way Slab - Design
One Way Slab - Design
One Way Slab - Design
Question:
Note: Beam sizes mentioned here are designed in the coming steps.
Calculations:
Since, we have a symmetric slab system. So we have to design only two panels (one exterior and one
interior).
For this panel, one end is continuous and remaining three ends are discontinuous.
Minimum Thickness:
×
hmin = = = 7.5” (using table 13.1,from Nilson 13th edition)
Load calculations:
.
Weight of slab = × 150 = 93.75 psf
Factored Loads:
wu = 296.5 psf
For this case the design moments at critical sections may be found using the ACI moment coefficients
(Using table 12.1, from Nilson 13th edition)
Note:
wn = total factored load per unit length of beam or per area of slab
ln = clear span for +ive moment and shear & the average of the two adjacent clear spans for the –ive
moment.
Assuming the column dimensions: Each column of 18” x 18”, thus clear span = 13.5’
At interior support: -M = wuln2 = x (0.2965) x (13.5)2 = 5.04 k-ft
At mid span: +M = wuln2 = x (0.2965) x (13.5)2 = 3.859 k-ft
At exterior support: -M = wuln2 = x (0.2965) x (13.5)2 = 2.251 k-ft
If that maximum value of ρ was used actually, the minimum required effective depth, controlled by the
negative moment at the interior support, would be found from equation 3.38 (Nilson 13th edition):
ØMn = Øρfybd2(1 − 0.59 )
5.04×12
Or d2 = = = 5.38
Ø (
. ) 0.90×0.0214×60×12(1−0.590.0214×60
4
)
d = 2.319 in
This is less than the effective depth of 7.5 – 1.00 = 6.5 in. At the interior support, if the stress-block
depth a = 1.00 in., the area of steel required per foot of width in the top of the slab:
.
×
#$ = ' = *.++ = 0.186 in2
Ø(& )
.×)
(). )
( (
-.
./)×)
,= = = 0.273 in
./
./××
.
×
#$ = ' = +.(01 = 0.176 in2
Ø(& )
.×)
(). )
( (
.)
For which a = 0.273 × = 0.25 in. No further revision is necessary.
./)
At the other critical sections it will be satisfactory to use the same lever arm to determine steel areas
and,
At Mid span:
2./ ×
#$ = ' = +.(01 = 0.134 in2
Ø(& )
.×)
(). )
( (
At Exterior support:
. ×
#$ = ' = +.(01 = 0.08 in2
Ø(& )
.×)
(). )
( (
The minimum reinforcement is that required for control of shrinkage and temperature cracking. This is:
per 12 in. strip. This requires a small increase in the amount of steel used at the exterior support and at
mid span.
The factored shear force at a distance d from the face of the interior support is
56 7 8 296.5 13.5
34 = 1.15 × = 1.15 × = 2301 lb
2 2
Thus the design strength of the concrete slab, ØVc = 0.75 × 9866 = 7399 lb, is well above the required
strength on shear of Vu = 2301 lb
Figure:
The locations of bend and cutoff points shown in above figure were obtained using Figure 5.15 (From
Nilson 13th edition)
The required area of steel to be placed normal to the main reinforcement for the purpose of
temperature and shrinkage crack control is 0.162 in2. This will be provided by No. 3 bars at 8 in c/c
spacing (As = 0.17 in2), placed directly on the top of the main reinforcement in the positive moment
region and below the main steel in the negative-moment zone.
For this panel, two ends are continuous and remaining two ends are discontinuous.
Minimum Thickness:
×
hmin = = = 6.4” (using table 13.1,from Nilson 13th edition)
/ /
NOTE: Now as for interior panel we have calculated hmin = 6.5” but exterior panel has 7.5”.
So for sake of economy we must have to check for exterior panel by taking hmin = 6.5”, whether for such
condition all requirements are fulfilled or not. If all checks (like shear) satisfy then there is no need to
provide 7.5” thick slab throughout.
But here this time we will proceed by taking 7.5” slab thickness even for the interior panel.
At interior support: -M = wuln2 = x (0.2965) x (13.5)2 = 5.40 k-ft
At mid span: +M = wuln2 = x (0.2965) x (13.5)2 = 3.37 k-ft
) )
If that maximum value of ρ was used actually, the minimum required effective depth, controlled by the
negative moment at the interior support, would be found from equation 3.38 (Nilson 13th edition):
ØMn = Øρfybd2(1 − 0.59 )
5.40×12
Or d2 = = = 5.76
Ø (
. ) 0.90×0.0214×60×12(1−0.590.0214×60
4
)
d = 2.4 in
This is less than the effective depth of 7.5 – 1.00 = 6.5 in.
At the interior support, if the stress-block depth a = 1.00 in., the area of steel required per foot of width
in the top of the slab:
.
×
#$ = ' = *.++ = 0.2 in2
Ø(& ( )
.×)
(). )
(
-.
.×)
,= = = 0.294 in
./
./××
.
×
#$ = ' = +.(?@ = 0.188 in2
Ø(& )
.×)
(). )
( (
.//
For which a = 0.294 × = 0.27 in. No further revision is necessary.
.
At the other critical sections it will be satisfactory to use the same lever arm to determine steel areas
and,
At Mid span:
2.2 ×
#$ = ' = +.(?@ = 0.117 in2
Ø(& )
.×)
(). )
( (
The minimum reinforcement is that required for control of shrinkage and temperature cracking. This is:
Use # 3 @ 8” c/c
per 12 in. strip. This requires a small increase in the amount of steel used at mid span.
The factored shear force at a distance d from the face of the interior support is
5 6 78 296.5 × 13.5
34 = 1.15 × = 1.15 × = 2301 lb
2 2
Thus the design strength of the concrete slab, ØVc = 0.75 × 9866 = 7399 lb, is well above the required
strength on shear of Vu = 2301 lb
Using the ACI moment coefficients, design a typical continuous beam. Consider the figure below:
Assumptions
Assume the width of beam as 8”. (Assumption will be on the basis of the column dimensions)
Minimum thickness of beam (from Mac Cormaic, table 3.1) = = = 9.729 in. Assume a total
/. /.
depth of 15 (So assumed d = 15 – 2.5 = 12.5”) in and the web depth of 15 – 7.5 = 7.5 in.
Load calculations:
Since; we are dealing with one way slab system. And in actual the load distribution on one way slab
system is same as for the two way slab system (i.e., Triangular & trapezoidal distribution). But in field,
there is a practice for one way slab that load distribution is taken as rectangular.
But here, for the sake of practice we will take the load distribution for continuous beam as per two way
slab system load distribution.
.
Volume of triangular portion of slab = [2 × ( × 7.5 × 7.5)] × = 35.156 cft
.
UDL on beam (A) due to slab = = 0.35 k/ft
= 100 × [2 × ( × 7.5 × 7.5)] = 5.625 k
.)
UDL on beam (A) due to live load = = 0.375 k/ft
= 20 × [2 × ( × 7.5 × 7.5)] = 1.125 k
.
UDL on beam (A) due to I.D.L = = 0.075 k/ft
Load due to self weight of beam (A) = (Volume of beam, exclusive of flange) × 150
/×.
=[( ) × 15] × 150 = 0.94 k
144
.
UDL on beam (A) due to Self-weight = = 0.062 k/ft
The beam is continuous on five spans and symmetrical about the centerline at D. therefore it is
sufficient to design half of the beam ABCD, because the other half has similar dimensions and
reinforcement.
Note: If the adjacent spans are not equal and their span ratio is less than 1.2 then ACI moment
coefficients can be applied to the beam. Moreover, the average of the adjacent clear span is used to
calculate the negative moments at the supports.
Mu = coefficient × wuln2
Location 1 2 3 4 5 6
Moment
- + - + - +
Coefficient
) )
Mu (K.ft) -8.96 +15.36 -21.51 +13.44 -19.55 +13.44
Maximum negative moment is -21.51 k-ft. using ρmax = 0.0214, Ru = 936.72 psi (Table A.14)
.×
d=A =A = 5.87 in ------- (A)
B
.2)×/
*Since calculate is less than assumed, so we will take the assumed value being on the safer side.
Otherwise we will end up with very small cross-section.
The section at the supports acts as rectangular sections with tension reinforcement placed in the flanges.
The reinforcement required at the supports is as follows:
Figure:
Location 1 3 5
Mu (K.ft) -8.96 -21.51 -19.55
Ru = ( (psi) 86.02 206.49 187.680
&
ρ (%) 0.18 0.4 0.36
As (in2) 0.18 0.4 0.36
No. 4 bars 2 3 2
Note:
For the Mid span T-section, Mu = +15.36 k-ff. For a = 1.00 in. and flange width = 15”
.2) ×
#$ = ' = * = 0.28 in2
Ø(& )
.×)
(. ()
(
-.
./ × )
Check a; ,= = = 0.329 in
./
./××
Revised ‘a’ gives As = 0.276 in2. Therefore use 2 # 4 bars (As = 0.39 in2) for all mid span sections.
(a) T-Beam
Note: First of all we will assume the cross section of the T-beam and then considering that section, we’ll
calculate the Mu and on the behalf of Mu we will calculated the d, now using that calculated d again
calculation of load on the beam would be our next step. Finally on this selected cross section design will
be done.
Load Calculations:
)
Self load of beam (only web portion) = Web depth × 150 × -------------- (i)
Web depth = [(d + cover) – hf]/12 = [(20.5 + 3.5) – 7.5]/12 = 1.375 ft --------------- (ii)
)
Self load of beam = 1.375 × 150 × = 0.275 k/ft
Now:
wu = 1.2 (1.40 + 0.3 + 0.275) + 1.6 (1.5) = 4.77 k/ft ---------- (iii)
C ( (.)× (2)( th
Mu = = = 486.93 k-ft ------- (iv)
(From Hibbler 6 edition, Table FEMs)
We have relation:
/).2×
d=A =A = 19.7 in
B
.2)×)
&
Now check ratio, it should be between 1.5 -2.0:
.
= = 1.28 < 1.5 So need to revise the ‘d’
)
Assume d= 24.5 in, and re-solving the equ. (ii), (iii) & (iv) we get:
wu = 4.848 k/ft
Mu = 494.9 k-ft So, Mn = = 549.88 k-ft
.
&
d = 20 in, less than the assumed & check is also OK
DE
Assume lever arm z Equal to the Larger of 0.9d or (d - )
F
.
z = 24.5 – = 20.75 in
Asfyz = Mn
×/.//
As = = 4.97 in2
)
×.
0.85 fc’ Ac = As fy
0.85 × 4 × Ac = 4.97 × 60
Ac = 87.85 in2
/./
a= = 0.836 in
./2)
z = 24.5 – = 24.08”
×/.//
As = = 4.5 in2
)
×.
/
0.85 fc’ Ac = As fy
0.85 × 4 × Ac = 4.5 × 60
Ac = 79.41 in2
.
a= = 0.756 in
.)
z = 24.5 – = 24.12”
×/.//
As = = 4.55 in2 OK, close enough to previous value.
)
×.
) .
As min = = = 1.239 in2
)
,
G &
) .
Or As min = = = 1.30 in2.
)
,
Figure:
C ( (.)× (2)(
Mu = = = 243.46 k-ft
Mn = = 270.5 k-ft
.
×
.
As = = 2.45 in2s
)
×.
0.85 fc’ Ac = As fy
0.85 × 4 × Ac = 2.45 × 60
Ac = 43.23 in2
2.2
a= = 0.411 in
.
z = 24.5 – = 24.29”
×
.
As = = 2.23 in2
)
×.
0.85 fc’ Ac = As fy
0.85 × 4 × Ac = 2.23 × 60
Ac = 39.35 in2
2.2
a= = 0.37 in
.2
z = 24.5 – = 24.31”
.
As = = 2.22 in2 OK, close enough to previous value.
)
.2
So use 3 # 8 (As = 2.35 in2) bars, at –ive moment zone i.e, at supports
(b) L-Beam
The values of bw and d will be same as assumed for the T-beam. So bw = 10” and d = 15.5”
Load Calculations:
Self load of beam (only web portion) = Web depth × 150 × -------------- (i-a)
Web depth = [(d + cover) – hf]/12 = [(15.5 + 2.5) – 7.5]/12 = 0.875 ft --------------- (ii-a)
Now:
wu = 1.2 (0.7 + 0.15 + 0.109) + 1.6 (0.75) = 2.35 k/ft ---------- (iii-a)
C ( (.2)× (2)( th
Mu = = = 239.89 k-ft ------- (iv-a)
(From Hibbler 6 edition, Table FEMs)
We have relation:
2./×
d=A =A = 17.6 in
B
.2)×
Since calculated‘d’ is more than assumed, so now take d = 17.6” and repeat the above steps, then equ
.(iii-a) and (iv-a) gives:
wu = 2.40 k/ft
C ( (.
)× (2)(
Mu = = = 245.85 k-ft
We have relation:
./×
d=A =A = 17.7 in
B
.2)×
So depth = 17.7 + 2.5 = 20.2 in, using 21” thus actual d = 18.5”
Mn = = 273.166 k-ft
.
DE
Assume lever arm z Equal to the Larger of 0.9d or (d - )
F
.
z = 18.5 – = 14.75 in
Asfyz = Mn
×2.))
As = = 3.28 in2
)
×).)
0.85 fc’ Ac = As fy
0.85 × 4 × Ac = 3.28 × 60
Ac = 58.00 in2
/.
a= = 1.73 in
22.
.2
z = 18.5 – = 17.63”
×2.))
As = = 3.10 in2
)
×.)2
0.85 fc’ Ac = As fy
0.85 × 4 × Ac = 3.1 × 60
Ac = 54.70 in2
.
a= = 1.63 in
22.
.)2
z = 18.5 – = 17.68”
×2.))
As = = 3.09 in2 OK, close enough to previous value.
)
.)/
/.
As min = = = 0.58 in2
)
,
G &
/.
Or As min = = = 0.616 in2.
)
,
The values of bw and d will be same as assumed for the T-beam. So bw = 10” and d = 18.5” (same, as
selected in above steps while designing L-beam for negative moment zone)
From Equ. (iii-a) wu = 1.2 (0.7 + 0.15 + 0.109) + 1.6 (0.75) = 2.35 k/ft
C ( (.2 2(
Mu = = = 119.94 k-ft
Mn = = 133.26 k-ft
.
DE
Assume lever arm z Equal to the Larger of 0.9d or (d - )
F
.
z = 18.5 – = 14.75 in
Asfyz = Mn
×22.)
As = = 1.60 in2
)
×).)
0.85 fc’ Ac = As fy
0.85 × 4 × Ac = 1.60 × 60
Ac = 28.23 in2
/.2
a= = 0.84 in
22.
./
z = 18.5 – = 18.0”
×22.)
As = = 1.48 in2
)
×/.
0.85 fc’ Ac = As fy
0.85 × 4 × Ac = 1.48 × 60
Ac = 26.129 in2
).
a= = 0.77 in
22.
.
z = 18.5 – = 18.11”
×22.)
As = = 1.47 in2 OK, close enough to previous value.
)
×/.
/.
As min = = = 0.58 in2
)
,
G &
/.
Or As min = = = 0.616 in2.
)
,
T-beam:
Thus;
(. .
Vu at a distance d from the support = I J × 59.10
= 53.89 k
M .
= = 9.42 ft from right
2./ .
For ØVc :
M .
= = 4.71 ft from right
. .
&
The max spacing should neither exceed, =9.25” nor 24”
-N
Also; Smax= = 19.88” (Av = 2 × 0.11 for # 3 stirrups)
.: G
-N
Smax ≤ = 18.86”
G
∅-N &
For Max Shear S = = 8.29” > 4” (Because stirrup spacing should not be less than 4”, according to code)
P ∅P
As we have max spacing 9.25” but at same time we have max shear S = 8.29”, this happened so because
in our case the loading is very small, so we don’t need to place shear reinforcement at different
locations in different ratio.
So in general we will place the shear reinforcement at a spacing of 9” c/c, up to ØVc
Figure:
L-beam:
Thus;
(. .
Vu at a distance d from the support = I J × 49.7 = 43.90 k
M .
= = 10.29 ft from right
. .
For ØVc :
M .
= = 5.14 ft from right
.) .
&
The max spacing should neither exceed, = 12.25” nor 24”
-N
Also; Smax= = 19.88” (Av = 2 × 0.11 for # 3 stirups)
.: G
-N
Smax ≤ = 18.86”
G
∅-N &
For Max Shear S = = 16.5” > 4” (Because stirrup spacing should not be less than 4”, according to code)
P ∅P
As we have max spacing 12.25” but at same time we have max shear S = 16.5”, this happened so
because in our case the loading is very small, so we don’t need to place shear reinforcement at different
locations in different ratio.
So in general we will place the shear reinforcement at a spacing of 12” c/c, up to ØVc
Figure: