PTES Sample IR Scan Report

This document provides a thermal scan report for a commercial building project. It includes: - A cover letter addressed to the client, summarizing the inspection and findings. - Sections on the infrared scan results, deficiencies found, and locations/equipment scanned. - Individual reports detailing abnormalities found with electrical equipment, including temperature readings and photos. - Deficiency reports with additional details on issues needing attention or repair.

Uploaded by

Akshay Gatkal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
705 views22 pages

PTES Sample IR Scan Report

This document provides a thermal scan report for a commercial building project. It includes: - A cover letter addressed to the client, summarizing the inspection and findings. - Sections on the infrared scan results, deficiencies found, and locations/equipment scanned. - Individual reports detailing abnormalities found with electrical equipment, including temperature readings and photos. - Deficiency reports with additional details on issues needing attention or repair.

Uploaded by

Akshay Gatkal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 22

Company Name

Address of Project
Thermal Scan Report

Submitted By: Power-Tek Electrical Services Inc.


February 2015

Power-Tek Electrical Services Inc.


155 Iber Road, Ottawa, Ontario K2S 1E7
Tel: (613) 836-4311 Fax: (613) 836-3601
Maintenance Service Construction Commercial Industrial Residential

TABLE OF CONTENTS

Title Section
Cover Letter

Thermographic Survey of Electrical Equipment 1

IR Scan Results 2

Report # 1
Report # 2

Deficiencies 3
Deficiency Report # 1
Deficiency Report # 2
Deficiency Report # 3

Locations/Equipment Scanned 4

Summary of Locations / Equipment Scanned


Photographs of Locations / Equipment

Power-Tek Electrical Services Inc.


155 Iber Road, Ottawa, On
Tel: (613) 836-4311 Fax: (613) 836-3601 [email protected]
Maintenance Service Construction Commercial Industrial Residential

April 30, 2013

Client Name
Address

Attention: Client Contact

Reference: Electrical Infrared Inspection of Project Address

Dear Client Name,

The following electrical infrared inspection was conducted by:

Clint Massey Certified Level 1 Thermographer # 061027-8


Journeyman Electrician OCOT # 13260147
Iain Algie Certified Level 1 Thermographer # CA111216-01
Apprentice Electrician # 309A-2322374

Please see included reports for the results of the Infrared Scanning.

Thank you for choosing Power-Tek Electrical Services Inc. for your infrared inspection requirements.
If you have any questions regarding this report or would like us to follow up on any deficiencies,
please feel free to contact us.

Yours truly,

Walter Pamic V.P.


Power-Tek Electrical Services Inc.

Tel: (613) 836-4311 Fax (613) 836-3601


155 Iber Road Ottawa, Ontario K2S 1E7
e-mail: [email protected]
www.power-tek.on.ca
THERMOGRAPHIC SURVEY OF ELECTRICAL EQUIPMENT

The intent of the Thermographic survey is to identify potential electrical and/or mechanical defects in
the equipment surveyed. Like vibration monitoring, oil analysis, and other forms of predictive
maintenance (PdM) Infrared (IR) thermographs often spare facilities from minor periods of downtime
at the least; catastrophic equipment failure at worst.

The thermal abnormalities identified during this inspection are presented on individual report pages
complete with the thermal and real life image. In order to determine the severity of the defects, the
temperature rise from normal components is recorded along with the measurement of load.

Electrical Thermographic inspections should be conducted during normal full load conditions. When
the devices are not under sufficient load at the time of inspection the client must take this into
consideration when assessing the urgency to response.

For example, if a device has a 10º C temperature at 1/3 load and the load increased to 3/4 load, the
temperature rise will be the square to the current increase. In this example the urgency would go from
a low priority to a high priority.

The following table will help in determining the urgency of response.

Prioritization Matrix 1 2 3 Multiplier Total

Will a failure injure people? 3


Is the component critical? 3
Will loads increase? 2
Will wind decrease? 2
Is the measuring reliable? 2
Is the thermal gradient large? 1

Repair Immediately 32-42


Repair at next opportunity 22-31
Schedule Repair 12-21
Monitor 1-12

Only the customer can determine the priority of response and the importance of the defective
equipment.

The Infrared Camera used to conduct this Thermographic survey was a Fluke Ti25.

Power-Tek Electrical Services Inc.


155 Iber Road, Ottawa, On
Tel: (613) 836-4311 Fax: (613) 836-3601 [email protected]
Power-Tek Electrical Services Inc.
155 Iber Road, Ottawa, Ontario K2S 1E7
Tel: (613) 836-4311 Fax: (613) 836-3601
Power‐Tek Electrical Services Inc.

Report # 1

IR000534.IS2
12/17/2014 10:15:39 AM

Image Info
Background temperature 23.0°C
Emissivity 0.95
Average Temperature 40.9°C
Camera Model Ti25
IR Sensor Size 160 x 120
Camera Manufacturer Fluke Thermography
Lens description 20mm
Calibration Range -22.0°C to 125.0°C

Annotations
Client Client Name
Operator Name Clint Massey
Location Address
Equipment SQD Disc – NO ID – 30A 600V fused at 15A feeds lighting contactor
Findings Appears that there is an issue with the mechanical parts of the
Disconnect or a seating issue with the fuses
Recommended Action REPLACE IMMEDIATELY
Comments This is a new disconnect that has recently been installed to fix a previous
issue. Needs attention Immediately.
A phase has 14.2 amps – Over 80%
B phase has 12.5 amps – Over 80%
C phase has 11.8 amps
Wires feeding the Disconnect are not supported – add straps for support

Markers
Name Temperature Emissivity Background
Centerpoint 64.0°C 0.95 23.0°C
Hot 98.1°C 0.95 23.0°C
Cold 23.3°C 0.95 23.0°C

1
Power‐Tek Electrical Services Inc.

Report # 2

IR000535.IS2
12/17/2014 12:54:09 PM

Image Info
Background temperature 23.0°C
Emissivity 0.95
Average Temperature 28.5°C
Camera Model Ti25
IR Sensor Size 160 x 120
Camera Manufacturer Fluke Thermography
Lens description 20mm
Calibration Range -22.0°C to 125.0°C

Annotations
Client Client Name
Operator Name Clint Massey
Location Address
Equipment SQD Disc – 30A 600V – J06
Findings Over Loaded Fuses 30 Amp fuses in a lighting disconnect
Recommended Action None
Comments Same Issue as before. Report R2 from 2012/2014

Markers
Name Temperature Emissivity Background
Centerpoint 44.3°C 0.95 23.0°C
Hot 88.2°C 0.95 23.0°C
Cold 22.5°C 0.95 23.0°C

2
Power-Tek Electrical Services Inc.
155 Iber Road, Ottawa, Ontario K2S 1E7
Tel: (613) 836-4311 Fax: (613) 836-3601
Company Name
Deficiency 1

IR 535

Info:
Location Company Name – Project Address
Thermographer Clint Massey
Location Zone J
Device SQD Disc – 30A 600V – J06
Findings Over Loaded Fuses 30 Amp fuses in a lighting disconnect

Date Repaired
Repaired By
Comments:
Same Issue as before. Report R2 from 2012/2014
Company Name
Deficiency 2

IR 534

Info:
Location Company Name – Project Address
Thermographer Clint Massey
Location Zone B – Yellow Cabinet
Device SQD Disc – NO ID – 30A 600V fused at 15A feeds lighting contactor
Findings Appears that there is and issue with the mechanical parts of the Disconnect or a seating issue
with the fuses - REPLACE IMMEDIATELY

Date Repaired
Repaired By
Comments:

-This is a new disconnect that has recently been installed to fix a previous issue. needs attention Immediately.
- A phase has 14.2 amps – Over 80%
- B phase has 12.5 amps – Over 80%
- C phase has 11.8 amps
- Wires feeding the Disconnect are not supported – add straps for support
Company Name
Deficiency 3

IR 539

Info:
Location Company Name – Project Address
Thermographer Clint Massey
Location Shop
Device Siemens Disconnect 100A 600V panels a and b
Findings Appears that B phase needs to be tightened – loose connection

Date Repaired
Repaired By
Comments:

-torque b phase
- A phase 14.2A
- B phase 22.6A
- C phase 17.9A
Power-Tek Electrical Services Inc.
155 Iber Road, Ottawa, Ontario K2S 1E7
Tel: (613) 836-4311 Fax: (613) 836-3601
POWER-TEK ELECTRICAL SERVICES INC.
Maintenance Service Construction Commercial Industrial

Attention: Client Contact


Reference: Client Name - Infrared Thermal Imaging - Project Address.

Abbreviations:
FD - Fused Disconnect
DP - Distribution Panel
LP - Lighting Panel
XFMR - Transformer
CON - Contactor
MTS - Manual Transfer Switch
ATS - Automatic Transfer Switch

Zone H
1.Siemens Panel 100A 120/240V - Securall Safety Storage Unit

Zone E

1. SQD Disconnect - 200A 600V - Flow Water Jet Machine Strap teck cable 35. FPE Disconnect - 30A 600V - E.D.39 - Belt Grinder
2. XFMR - Marcus - 600/480V 150KVA - Flow Water Jet Machine 36. Hydel Splitter - ESB 01 - 400A 600V
3. FPE Disconnect -30A 600V - E.D.16/E.D.17 37. SQD Disconnect - 30A 600V - E.D.04
4. FPE Disconnect -30A 600V - E.D.17/F.PA.01 38. SQD Disconnect - 30A 600V - E.D.09
5. AB Motor Starter - Oil Cooler - Flow Water Jet Machine 39. Commander Disconnect - 30A 600V - E.D.12
6. Control Panel - Flow Water Jet Machine 40. ITE Disconnect - 30A 600V - E.D.13
7. GE Disconnect - 30A 600V - D15 - Euromac Punch 41. Commander Disconnect - 30A 600V - E.D.08
8. GE Disconnect - 30A 600V - D19 - Sampson Rollers 42. Commander Disconnect - 30A 600V - E.D.06
9. Controller - Euromac Punch 43. SQD Disconnect - 30A 600V - D28 - Miller Welder
10. SQD Disconnect - 30A 600V - E.D.31/E.D.05 Miller Welder 44. GE Disconnect - 30A 600V - No I.D. - Miller Welder
11. FPE Disconnect - 30A 600V - E.D.33/B.D.415 Miller Welder 45. FPE Disconnect - 30A 600V - D29
12. ITE Disconnect - 30A 600V - E.D.31/B.D Miller Welder 46. SQD Disconnect - 30A 600V - No I.D. - Water Jet
13. GE Disconnect - 30A 600V - Forklift Charger 47. SQD Disconnect - 100A 600V - D47
14. FPE Disconnect - 30A 600V - E.D.34/ED23 Miller Welder 48. FPE Disconnect - 30A 600V - No I.D. - Press
15. FPE Disconnect - 30A 600V - E.D.35/ED23 Miller Welder 49. Amalgamated Disconnect - 30A 480V
16. Commander Disconnect - 100A 600V - E.D.20 - Splitter Feed 50. Disconnect E.D.01/E.SB.01 - 30A 600V
17. Siemens Disconnect - 30A 600V - E.D.21 51. Disconnect E.D.04/E.SB.01 - 30A 600V
18. FPE Disconnect - 30A 600V - E.D.22 52. Disconnect E.D.09/E.SB.01 - 30A 600V
19. FPE Disconnect - 30A 600V - E.D.23 53. Disconnect E.D.12/E.SB.01 - 30A 600V
20. FPE Disconnect - 30A 600V - E.D.24 54. Disconnect E.D.02/E.SB.01 - 30A 600V - Pipe bender
21. Splitter - Eurobex - 125A 600V - E.SB.02 55. Disconnect E.D.05/E.SB.01 - 30A 600V Dirrerent fuses
22. AB Contactor 56. Disconnect E.D.07/E.SB.01 - 30A 600V Dirrerent fuses
23.GE Disconnect - 30A 600V E.D.42 57. Disconnect E.D.10/E.SB.01 - 30A 600V
24. SQD Disconnect - 60A 600V E.D.26 58. Disconnect E.D.13/E.SB.01 - 60A 600V
25.GE Disconnect - 30A 600V - Bandsaw 59. Disconnect E.D.03/E.SB.01 - 30A 600V
26. FPE Disconnect - 30A 600V - E.D.36 60. Disconnect E.D.06/E.SB.01 - 30A 600V - Welder
27. FPE Disconnect - 30A 600V - E.D.37 - OFF 61. Disconnect E.D.08/E.SB.01 - 30A 600V - Welder
28. FPE Disconnect - 30A 600V - E.D.38 - Miller Welder 62. Disconnect E.D.11/E.SB.01 - 30A 600V - Welder
29. FPE Disconnect - 30A 600V - E.D.40 - Miller Welder 63. Disconnect E.D.01/E.SB.01 - 30A 600V - Drill Press
30. FPE Disconnect - 30A 600V - E.D.41 - Miller Welder - Removed 64. Waste Water Control Unit
31. FPE Disconnect - 30A 600V - E.D.30 - Miller Welder - Removed 65.Commander Disconnect 60A 600V - JD15/22
32. FPE Disconnect - 30A 600V - E.D.18/DB - Miller Welder 66. Amal Disconnect 30A 480/575V - Battery Charger
33. FPE Disconnect - 30A 600V - E.D.32 - Miller Welder 67.SQD Disconnect 200A 600V - Feeds XFMR - No I.D.
34. FPE Disconnect - 30A 600V - E.D.30 - Miller Welder 68.SQD Disconnect 200A 600V - Feeds into other Zone - No I.D.

2/27/2015 Page 1 of 6
POWER-TEK ELECTRICAL SERVICES INC.
Maintenance Service Construction Commercial Industrial

Attention: Client Contact


Reference: Client Name - Infrared Thermal Imaging - Project Address.

Zone J
1. SQD Disconnect - 30A 600V - J D01 Add straps 9. FPE Disconnect - 30A 600V - J D07
2. SQD Disconnect - 30A 600V - J D02 Add straps 10. CEB Disconnect - 30A 600V - J D10
3. SQD Disconnect - 30A 600V - J D03 Add straps 11. XFMR - Anaconda 600/120/208V 45KVA J TR01
4. SQD Disconnect - 30A 600V - J D04 Add straps 12. SQD Panel 225A 120/208V - JP A 01
5. SQD Disconnect - 30A 600V - J D06 - See IR 535 13. Dip Tank Controller
6. SQD Disconnect - 30A 600V - J D08 Add Straps 14. Boiler Control Panel - Off - visual inspection
7. SQD Disconnect - 60A 600V - J D09 Add straps 15. Contactor - Outside Lights
8. SQD Disconnect - 30A 600V - J D11 Add straps 16. Jessup Control Units

Machine Shop
1. XFMR - Marcus 600/480V 75KVA
2. Control Panel - Cincinati Milling Machine
3. XFMR - Marcus - Unknown KVA - Gross Milling Machine
4. XFMR - Delta - 30KVA - Enshu Milling Machine
5. Control Panel - Gross Milling Machine

Zone D
1. GE Panel 225A 347/600V DPA 01 9. SQD Disconnect 30A 600V - Drill Press
2. XFMR - Rex - 30KVA 10. SQD Disconnect 30A 600V - Bandsaw
3. XFMR - JVC - 30KVA 11.GE Disconnect 100A 600V - feeds Bemag XFMR
4. XFMR - Bemag - 45KVA 600/120/208V 12. XFMR - Marcus - 600/120/208V 10KVA
5. SQD Disconnect - 30A 600V - No I.D. 13. SQD Disconnect - 30A 600V - DD 03
6. Siemens Disconnect - 600A 600V - TIG#4 14. Commander Panel - No I.D.
7. SQD Disconnect 100A 600V - No I.D. 15.Barnes Sump Pump Controller - Power pilot light required
8. SQD Disconnect 30A 600V - Welder 16. ITE Disconnect 30A 600V - GSD13

2/27/2015 Page 2 of 6
POWER-TEK ELECTRICAL SERVICES INC.
Maintenance Service Construction Commercial Industrial

Attention: Client Contact


Reference: Client Name - Infrared Thermal Imaging - Project Address.

Zone C
1. West. Disconnect - 30A 600V - CD29 - Garage Door 31. West. Disconnect 30A 600V - CD10
2. ITE Disconnect 30A 600V - CD30 different fuses 32. ITE Disconnect 30A 600V - CD09 different fuses
3. SQD Disconnect 30A 600V - CD31 33. West. Disconnect 60A 600V - CD11
4. ITE Disconnect 30A 600V - CD34 34. Siemens Disconnect 100A 600V - CD13
5. Commander Disconnect - 30A 600V - CD38 35. Siemens Disconnect 100A 600V - CD15
6. Siemens Disconnect - 30A 600V - CD39 - feeds welding plug CWP18 36. GE Disconnect 60A 600V - CD16
7. ITE Disconnect 30A 600V - CD33 37. Splitter - Bel - 125A 600V - CSB02
8. ITE Disconnect 30A 600V - CD35 38. SQD Disconnect 60A 600V - CD14
9. ITE Disconnect 30A 600V - CD37 39. GE Disconnect 60A 600V - Robotic Welder
10. Splitter - CEB - 100A 600V - CSB03 40. Control Panel - Robotic Welder
11. C/H Disconnect 30A 600V - CD41 41. Bulldog Disconnect - 30A 600V -CD44
12. FPE Disconnect - 30A 600V - GSD21 - Removed 42. ITE Disconnect 30A 600V - CD43
13. FPE Disconnect - 30A 600V - No I.D. 43. FPE Disconnect - 30A 600V - CD19
14. FPE Disconnect - 30A 600V - CD45 44. FPE Disconnect - 60A 600V - EWP09
15. FPE Disconnect - 30A 600V - CD46 45. Commander Panel 125A 120/240V - 'A' missing KO fillers
16. FPE Disconnect - 30A 600V - CD47 46. ITE Disconnect 100A 600V - CD20
17. Control Panel - Press 47. FPE Disconnect - 30A 600V - ED37
18. Siemens Disconnect - 30A 600V - CD48 48. West. Disconnect 30A 600V - CD21
19. West. Disconnect - 30A 600V - CD49 49. Siemens Disconnect 30A 600V - GSD03
20. FPE Disconnect - 30A 600V - Welder 50. Commander Disconnect - 30A 600V - CD24
21. SQD Panel - 225A 240V install proper tie bar 51. Motor Controller - No I.D.
22. Commander Disconnect - 60A 600V - CD01 52. ITE Disconnect 30A 600V - CD22
23. Commander Disconnect - 30A 600V - CD02 53. FPE Disconnect - 60A 600V - CD25
24. ITE Disconnect 60A 600V - CD04 54. SQD Disconnect 30A 600V - CD26
25. ITE Disconnect 30A 600V - CD06 54. GE Disconnect 30A 600V - CD27
26. ITE Disconnect 30A 600V - CD03 55. SQD Disconnect 30A 600V - D-32
27. ITE Disconnect 30A 600V - CD05 56. FPE Disconnect - 30A 600V - ED37
28. Splitter - Stelpro - 125A 600V - CSB01 57. FPE Disconnect - 60A 600V
29. ITE Disconnect 30A 600V - CD07 different fuses 58. ITE Disconnect 60A 600V - D-12
30. ITE Disconnect 30A 600V - CD08 different fuses 59. XFMR Marcus 45KVA 600/120/208V
60. GE Disconnect 30A 600V - D-19 missing KO fillers

Zone A
1. ITE Disconnect 30A 600V - A19 3 different size fuses 15,30 14. SQD Disconnect 100A 240V - A7
2. Splitter - Stelpro - 125A 600V - A1 15. West. Disconnect 200A 240V - A6
3. ITE Disconnect 30A 600V - A18 16. West. Disconnect 200A 240V - A5
4. ITE Disconnect 30A 600V - A16 17. SQD Disconnect 60A 240V - A4
5. ITE Disconnect 30A 600V - A15 18. FPE Disconnect - 60A 600V - A3
6. ITE Disconnect 30A 600V - A14 19. XFMR - Polygon - 15KVA 600/120/208V
7. ITE Disconnect 30A 600V - A11 20. Splitter - Bel - 600A 120/240V
8. ITE Disconnect 30A 600V - A10 21. FPE Disconnect - 100A 600V - A2
9. Siemens Disconnect 60A 600V - A13 22. FPE Disconnect - 100A 600V - A1
10. SQD Disconnect 30A 600V - A12 23. XFMR - Polygon - 15 KVA 600/120/208V
11. SQD Panel 225A 120/208V Panel 'A' See diffeceny report a lot of issues 24. Splitter - Eurobec - 400A 600V
12. Commander Disconnect - 60A 240V - AD20 25. Siemens Distribution Panel 800A 347/600V
13. CEB Disconnect - 30A 600V - A8 26. GE SWGR 2000A 347/600V
27. ITE Disconnect 30A 600V - A17 Different fuses

2/27/2015 Page 3 of 6
POWER-TEK ELECTRICAL SERVICES INC.
Maintenance Service Construction Commercial Industrial

Attention: Client Contact


Reference: Client Name - Infrared Thermal Imaging - Project Address.

Mechanical/Compressor Room
1. Splitter - Bel - 225A 600V 4. FPE Disconnect 10A 600V - AD23
2. GE Disconnect 30A 600V - AD28 5. C/H Disconnect 100A 600V - AD24
3. C/H Disconnect 200A 600V - AD22 6. Siemens Disconnect 60A 600V - AD25
7. Atlas Copco Compressor 125Hp 575V

Zone B - Yellow Electrical Cabinet


1. Siemens Disconnect 30A 600V - B D14 10. ITE Disconnect 200A 600V - BD01
2. Splitter - 125A 600V - BSB02
3. ITE Disconnect 30A 600V - B17 12. Splitter - 400A 600V - Box B-1
4. ITE Panel 225A 120/208V 'BPA1'
5. Commander Disconnect - 30A 600V - BD11 14.Siemens Disconnect - 100A 600V - BD06/B5B01
15. Allen Bradley 'Zone B' - lighting contactor
7. SQD Disconnect 100A 600V - BD05 16. SQD Disconect no ID 30A 600V fused at 15A See IR image 534
8. ITE Disconnect 60A 600V - BD03
9. ITE Disconnect 100A 600V - BD02 Strap teck cable and KO fillers

Zone B
1. SQD Disconnect 60A 600V - CD23 31. SQD Disconnect 30A 600V - BD21
2. Siemens Disconnect 30A 600V - BD53 - 5 Ton Crane 32. ITE Disconnect 30A 600V - BD20
3. SQD Disconnect 60A 600V - BD56 33. ITE Disconnect 100A 600V - BD19 Different fuses
4. Starter SQD 30A 600V - BD56 34. Amal. Disconnect 30A 600V - BD22
5. SQD Disconnect 30A 600V - B26 Dust Collector 35. SQD Disconnect 60A 600V - BD24
6. Contactor - Telemechanique - 30A 600V - Dust Collector 36. GE Disconnect 30A 600V - BD23
7. Control Panel - 30A 600V - Plasma Cutter 37. SQD Disconnect 60A 600V - BD25
8. Commander Disconnect - 30A 600V - Plasma Cutter 38. SQD Disconnect 30A 600V - BD26
9. ITE Panel 125A 120/240V - Sub Panel B4 39. SQD Disconnect 30A 600V - BD27
10. CEB Disconnect 30A 600V - B28B 40. CEB Disconnect 30A 600V - BD28
11. Contactor - Telemechanique - 30A 600V - Compressor 41. ITE Disconnect 60A 600V - BD29
12. FPE Disconnect 60A 600V - B36B 42. SQD Disconnect 30A 600V - BD30
13. ITE Disconnect 30A 600V - B21B 43. Splitter - 125A 600V - BSB03
14. Siemens Disconnect 30A 600V - BD58 44. Splitter - 125A 600V - BD03
15. FPE Disconnect 100A 600V - BD48 45. ITE Disconnect 30A 600V - BD31 Different fuses
16. Commander Panel 225A 120/208V - BPA03 add cover screws 46. ITE Disconnect 30A 600V - BD32
17. ITE Disconnect 30A 600V - BD47 47. ITE Disconnect 30A 600V - BD33
18. ITE Disconnect 30A 600V -BD45 48. ITE Disconnect 30A 600V - BD34 Different fuses
19. ITE Disconnect 60A 600V - BD44 49. SQD Disconnect 30A 600V - BD35
20. ITE Disconnect 60A 600V - BD43 50. FPE Disconnect 60A 600V - BD36
21. ITE Disconnect 30A 600V - BD40 51. SQD Disconnect 200A 600V - Mazak Laser Cutter
22. ITE Disconnect 30A 600V - BD46 52. XFMR - JVC - 112.5KVA 600/460V - Mazak Laser Cutter
23. ITE Disconnect 30A 600V - BD41 53. XFMR - Bemag - 30KVA 600/120/208V
24. ITE Disconnect 60A 600V - Splitter B-3 54. SQD Disconnect 60A 600V - 'All Steel Unit'
25. Commander Disconnect 100A 600V - BD38 55. ITE Disconnect 30A 600V - BD.52 - Demag Crane
26. Splitter - Stelpro - 125A 600V - B4 56. Splitter Box '05' 400A 600V
27. XFMR - Marcus - 75KVA 600/230V 57. SQD Disconnect 60A 600V - No I.D.
28. Siemens Panel 125A 120/208V - BPA02 58. SQD Disconnect 200A 600V - No I.D.
29.Siemens Disconnect 30A 600V - BD37 59. WWTS -Crane Interlock Box
30. XFMR - Bemag - 30KVA - 600/120/208V 60. SQD Disconnect 30A 600V - No I.D.

Zone F
1. Commander Panel 225A 120/208V - FPA2 add cover screws and KO 8. SQD Disconnect 30A 600V - Advance Cure Unit Different fuses
2. Lighting Contactors 9. GE Disconnect 30A 600V - Exh. Fans
3. Commander Panel 225A 120/208V - FPA1 add cover screws 10. Hayden Contol Panel
4. Twin Flow Control Panel 11. Twin Flow Control Panel
5. Schnieder VFD - Paint Booth #3 12. Air Exchange Unit
6. SQD Disconnect 30A 600V 13. Paint Booth #2 - Lighting Contactors
7. GE Panel 60A 120/208V - Zone F 14. Marcus XFMR - 30KVA

2/27/2015 Page 4 of 6
POWER-TEK ELECTRICAL SERVICES INC.
Maintenance Service Construction Commercial Industrial

Attention: Client Contact


Reference: Client Name - Infrared Thermal Imaging - Project Address.

Zone G
1. Siemens Panel 225A 120/208V - GPA02 12.Siemens Disconnect 30A 600V - GSD-17
2. Siemens Panel 250A 120/208V - GPA01 13.Siemens Disconnect 30A 600V - GSD-16
3. A/B Starter 14.Siemens Disconnect 30A 600V - GSD-14
4. SQD Disconnect 30A 600V - GSD27 15.Siemens Disconnect 30A 600V - GSD-15
5. Splitter - Bel - 400A 600V - GSB01 16.Siemens Disconnect 30A 600V - GSD-11
6. XFMR - Siemens 75KVA 600/120/208V - No I.D. 17.Siemens Disconnect 30A 600V - GSD-12
7. GE Disconnect 30A 600V - TIG#1 18.Siemens Disconnect 30A 600V - GSD-10
8. Westinghouse Lighting Relays 19.Siemens Disconnect 30A 600V - GSD-04
9.Siemens Disconnect 30A 600V - GSD-26 20.Siemens Disconnect 30A 600V - GSD-20
10.Siemens Disconnect 30A 600V - GSD-24 21.Siemens Disconnect 30A 600V - GSD-18
11.Siemens Disconnect 30A 600V - GSD-17 22.ITE Disconnect 30A 600V - GSD-01
23.Simens Disconnect 30A 600V -GSD-25 KO and inner guard has fallen off
Compressor Room # 2 (Mezzanine)
1. FPE Disconnect 100A 600V - No I.D. 6. FPE Disconnect 100A 600V - No I.D.
2. GE Disconnect 30A 600V - No I.D. 7. Splitter - Hydel - 225A 600V
3. GE Disconnect 30A 600V - TIG#3 - 8. XFMR - Bemag - 75KVA 600/120/208V
4. FPE Disconnect 200A 600V - No I.D. 9. Starter - 30A 600V - Dust Extractor
5. FPE Disconnect 30A 600V - No I.D. 10. Cyclon Air Comp. Control Panel

Outside Compressor Room # 2 (Mezzanine)


1. SQD Disconnect 100A 600V - Hoist Panel Different fuses
2. SQD Disconnect 30A 600V - Boiler Panel
3. Hoffman splitter 225A 600V

Offices (Top Floor)


1. SQD Panel 100A 120/208V - No I.D.
2. SQD Panel 100A 120/208V - 'H'

Telephone Room (Top Floor)


1. SQD Panel 225A 120/208V

Storage Room (Top Floor)


1. SQD Panel 8 Cir. 120/208V 1 meter rule

Offices (1st Floor)


1. ITE Panel 225A 120/208V - Panel 03/A.D.06

Main Building Server Room (1st Floor)


1. RTS Generac Power Systems
2. Siemens Panel 120/208V HPA02/HPA01

Armour Testing (1st Floor)


1. Commander Panel 100A 120/208V - No I.D. 5. Splitter - Hoffman - 125A 600V - No I.D.
2. Siemens Disconnect 60A 600V - No I.D. 6. Siemens Disconnect 60A 600V - Air Compressor
3. FPE Disconnect 30A 600V - No I.D. 7.Commander Panel 100A 120/240V - Panel #1 Walkway
4. SQD Manual Motor Starter - No I.D.

2/27/2015 Page 5 of 6
POWER-TEK ELECTRICAL SERVICES INC.
Maintenance Service Construction Commercial Industrial

Attention: Client Contact


Reference: Client Name - Infrared Thermal Imaging - Project Address.

Dewbridge Office Building (1st Floor Server Room)


1. Siemens Panel 400A 120/208V - 'A' 3.Anaconda XFMR 75KVA 600/208Y/120V
2. Siemens Panel 400A 120/208V - 'B'

Dewbridge Shop
1. ASCO Transfer Switch 9. Siemens Disconnect 30A 600V - Rooftop Unit 2nd Floor
2. Starter - Siemens - 30A 600V - No I.D. 10. Siemens Disconnect 30A 600V - Rooftop Unit Warehouse
3. Siemens Panel 250A 347/600V 'D' 11. SQD Disconnect 60A 600V - No I.D.
4. Siemens Panel 400A 120/208V 'C' 12. Splitter - Hydel - 400A 600V - No I.D.
5. Siemens Disconnect 100A 600V - Panels A + B See IR 539 13. XFMR - Anaconda - 75KVA 600/120/208V - No I.D.
6. Siemens Disconnect 100A 600V - Panel D See IR 538 14. West. Disconnect 60A 600V - Smoke Hood
7. Siemens Disconnect 100A 600V - Panel C 15. FPE Disconnect 30A 600V - Welder
8. Siemens Disconnect 30A 600V - Rooftop Unit 1st floor 16. GE Disconnect 30A 600V - Steam Cleaner
17. Siemens Disconnect 400A 600V 'Main' - No access

2/27/2015 Page 6 of 6
Infrared Report
Project Address
Client Name Report Date

Location of Equipment

1.SQD DP 'Panel PL' 225A 120/208V 42 Cir.


2.Relay Panel 'PR' - Douglas Relays
Infrared Report
Project Address
Client Name Report Date

Location of Equipment

1.SQD DP 'Panel PM' 225A 120/208V 42 Cir.


Infrared Report
Project Address
Client Name Report Date

Location of Equipment

2.SQD DP 'Panel C' 100A 120/208V 24 Cir.


Infrared Report
Project Address
Client Name Report Date

Location of Equipment

3.SQD Main Breaker 300A 600V Rated