Standalone three-phase UPS system

PowerScale
10–50 kVA
Maximize your availability
with PowerScale
PowerScale – premium power protection

PowerScale is a mid-size, three-phase UPS system and space for internal batteries. PowerScale is a complete
that delivers premium power protection for the increasing power protection system in one box and allows for
loads in today’s server rooms and data centers. simple installation.
PowerScale is available in seven power ratings:
10, 15, 20, 25, 30, 40 and 50 kVA. The standalone three-phase UPS system is the ideal
solution for server rooms, networks, small data centers,
This new generation of transformer-less UPS responds to all telecommunications and health care infrastructures, banking
major concerns of IT and facility managers. As saving costs and industrial applications.
and 100 percent uptime are their top priorities, PowerScale
offers the lowest cost of ownership of any UPS system The broad range of PowerScale has been designed to offer
by providing energy efficiency, scalable flexibility, highest the most important benefits to our customers and fulfil today’s
availability and easy serviceability. most demanding requirements in terms of:

The all-in-one solution includes a true online double –– System availability


conversion (VFI = Voltage Frequency Independent), –– Environmental impact
a power distribution unit, a manual maintenance bypass, –– Total cost of ownership
a static thyristor bypass, intelligent battery management –– Solution flexibility

High system availability Low environmental impact


Today’s critical applications require full redundancy in order The PowerScale range operates in the largest three-phase
to ensure the highest availability and 100 percent uptime. UPS market. Consequently it is even more important that
Up to 20 PowerScale units can be installed in parallel. Also, PowerScale offers best-in-class, environmentally friendly
PowerScale shows superior reliability as a result of being built features such as:
of the highest quality components.
– – High efficiency for energy saving
The high quality of components used, the advanced design, – – Small size for space saving
the highly efficient and lean production process and the – – Flexible battery block per string for minimal
exhaustive system test of each unit ensure the exceptional environmental impact
reliability of all PowerScale units. These specific measures – – Sustainable material for proper recycling
are confirmed by PowerScale industry-leading technical – – Efficient manufacturing
characteristics such as:
PowerScale fully embodies the fundamental values of ABB
– – Output power factor: 0.9 and allows IT facility managers to employ a sustainable power
– – High input voltage tolerance protection strategy.
(100 % load: –23 % / +15 %; 60 % load: –40 % / +15 %)
–– High input frequency tolerance (35–70 Hz)
– – AC–AC efficiency up to 95.5 % Up to 20 UPS units
– – Ripple-free battery charging Configuration N +1 can be installed in
parallel to achieve
increased redundancy
PowerScale

PowerScale

PowerScale

PowerScale

Parallel systems (n+x) substantially increase redundancy and


or more power.
therefore ensure continuous support of the load should any
unit shut down. The redundant system allows for maintenance
on all parallel cabinets without the need for an external
maintenance bypass and without having to remove the critical
Critical load
load from conditioned power.

02 PowerScale 10–50 kVA | ABB UPS Systems


Low total cost of ownership

Thanks to its broad range and simple parallel


configuration, each PowerScale system can be configured
and extended to function with the initial or future power
requirements of your infrastructure.

Initial right-sizing of the UPS system and gradual


extension according to effective load requirements will
optimize your investment.

PowerScale exhibits state-of-the-art energy efficiency of AC–AC efficiency


up to 95.5 percent, therefore helping you to further reduce
operating costs over the life of your UPS system. The flat 100

efficiency curve is typical for all ABB products, and hence the 95

fall in efficiency is marginal even at partial loads. 90


85
80
75
Linear load (cos phi = 1)
25% 50% 75% 100% load

This enables significant energy savings in every working Input power factor versus load
condition.The input power factor of PowerScale is near
unity. This is made possible by the advanced booster PFC 1.0
(Power Factor Correction) circuit of ABB’s transformer-less
technology. As a result there is no need for a filter for phase
compensation. When using PowerScale, the UPS system
respects the power grid regulations, and therefore achieves
important energy savings. 0.8

25% 50% 75% 100% load

The outstanding low input current total harmonic distortion Input current total harmonie distortion (THDi)
(THDi) helps to enhance the compatibility with generators.
Low THDi eliminates possible interference with other 6
equipment in the scheme, reduces the size of power cables, 5
fuses and breakers at the input and avoids excess heating of 4
power transformers. 3
2
1
0
25% 50% 75% 100% load
Technical specifications

GENERAL DATA 10 kVA 15 kVA 20 kVA 25 kVA 30 kVA 40 kVA 50 kVA


Output power max. 9 kW 13.5 kW 18 kW 22.5 kW 27 kW 36 kW 45 kW
Output power factor 0.9
Topology True online double conversion
Parallel configuration Up to 20 units in parallel configuration
UPS type Standalone
Cable entry Rear accessible Rear accessible Rear accessible Rear accessible Front accessible Front accessible Front accessible
Inbuilt batteries Yes
INPUT
Nominal input voltage 3 × 380 V / 220 V + N, 3 × 400 V / 230 V + N, 3 × 415 V / 240 V + N
Voltage tolerance For loads < 100 % (–23 %, +15 %), < 80 % (–30 %, +15 %), < 60 % (–40 %, +15 %)
(Ref. to 3 × 400 V / 230 V)
Input distortion THDi ≤ 3 % at 100 % (sinewave)
Frequency 35–70 Hz
Power factor 0.99 at 100 % load
OUTPUT
Rated output voltage 3 × 380 V / 220 V + N, 3 × 400 V / 230 V + N, 3 × 415 V / 240 V + N
Voltage tolerance 1 % (static), 4 % (dynamic)
(Ref. to 3 × 400 V / 230 V)
Voltage distortion < 2 % linear load, < 4 % non-linear load (IEC / EN62040-3)
Frequency 50 or 60 Hz
Overload capability 10 min.: 125 % or 1 min.: 150 % (at cos phi 0.8); 10 min.: 110 % or 1 min.: 130 % (at cos phi 0.9)
Unbalanced load 100 % (all 3 phases regulated independently)
Crest factor 3:1
EFFICIENCY
Overall efficiency Up to 95.5 %
In eco-mode 98 %
configuration
ENVIRONMENT
Storage temperature –25–70 °C
Operating temperature 0–40 °C
Altitude 1000 m without derating
BATTERY
Battery type 7 Ah / 9 Ah / 28 Ah, sealed, lead-acid, maintenance-free
Battery replacement Field-replaceable
Battery voltage Flexible voltage for longer backup times
Battery capacity 48 or 48 or 48 or 96 or 144 × 7 / 9 Ah 144 × 7 / 9 Ah 144 × 7 / 9 Ah
96 × 7 / 9 Ah 96 × 7 / 9 Ah 96 × 7 / 9 Ah 144 × 7 / 9 Ah or 48 × 28 Ah or 48 × 28 Ah or 48 × 28 Ah
COMMUNICATIONS
LCD display Yes (per module)
LEDs LED for notification and alarm
Communication ports RS 232, SNMP slot (USB and potential free contacts optional)
STANDARDS
Safety IEC / EN 62040-1
Electromagnetic IEC / EN 62040-2
compatibility (EMC)
Performance IEC / EN 62040-3
Product certification CE
Protection rating IP 20
Manufacturing ISO 9001:2008, ISO 14001:2004
WEIGHT, DIMENSIONS
Cabinet type A or B A or B A or B B or C C C C
Weight 60 or 88 kg 62 or 90 kg 64 or 92 kg 94 or 135 kg 145 kg 150 kg 155 kg
Dimensions 345 × 720 × 710 or 345 × 720 × 710 or 345 × 720 × 710 or 345 × 1045 x 710 440 × 1400 × 910 440 × 1400 × 910 440 × 1400 × 910
W × H × D (mm) 345 × 1045 × 710 345 × 1045 × 710 345 × 1045 × 710 or 440 × 1400 × 910

ABB UPS Systems | PowerScale 10–50 kVA 04


Solution flexibility

GENERAL DATA 10 kVA 15 kVA 20 kVA 25 kVA 30 kVA 40 kVA 50 kVA


Cabinet type A B A B A B B C C C C
Maximum number of batteries 7 / 9 Ah 1 × 48 2 × 48 1 × 48 2 × 48 1 × 48 2 × 48 2 × 48 3 × 48 3 × 48 3 × 48 3 × 48
Maximum number of batteries 28 Ah n. a. n. a. n. a. n. a. n. a. n. a. n. a. 1 × 48 1 × 48 1 × 48 1 × 48
Maximum autonomy of internal batteries 15 35 10 20 6 15 12 20 15 10 8
in minutes at full load (cos phi 0.9)

Flexible battery configuration With the advanced booster technology of ABB’s transformer-
In each cabinet, the space available for internal batteries less UPS, the number of battery blocks per string can be
is designed to fulfil most of the run-time requirements. The adjusted to the exact run-time required. This unique flexibility
smaller units (10 to 25 kVA) are available in two cabinet sizes, allows an optimal sizing of the battery capacity and a minimal
and the larger units (30 to 50 kVA) can house different battery investment.
sizes (7 / 9 Ah or 28 Ah).

If extended autonomy is required, the complementary battery


cabinet of the PowerScale range can easily be connected to
any unit.

Compact design and simple serviceability


The compact design and small footprint of all PowerScale
models serve to minimize space requirements and save
valuable floor space. The units are available in three different
cabinet sizes: A / B / C (see technical specifications for
detailed dimensions).

Cabinet type C allows front access. The front panel is easily


removable and offers simple serviceability. Cabinet types A
and B are accessible from the rear.

Enhanced communication capabilities


PowerScale is equipped with a variety of standard and
optional communications features for network connectivity
and application management.

Standard features
– – RS 232 on Sub-D9 port
–– 4 input contacts
–– 12 VDC source
–– RJ 45 for multidrop

Optional features
– – SNMP card (slot)
–– Card including 5 potential free output contacts
and USB port The front panel of the type C cabinet is easily removable.

05 PowerScale 10–50 kVA | ABB UPS Systems