1kha000951 Uen Re 216
1kha000951 Uen Re 216
1kha000951 Uen Re 216
1st Edition
All rights with respect to this document, including applications for patent and
registration of other industrial property rights, are reserved. Unauthorized use, in
particular reproduction or making available to third parties without our explicit consent
in writing is prohibited.
The use is only allowed for the purpose laid down in the contract.
This document has been carefully prepared and reviewed. Should in spite of this the
reader find an error, he is requested to inform us at his earliest convenience.
The data contained herein purport solely to describe the product and are not a warranty
of performance or characteristic. It is with the best interest of our customers in mind
that we constantly strive to improve our products and keep them abreast of advances in
technology. This may, however, lead to discrepancies between a product and its
'Technical Description' or 'Operating Instructions'.
Version 6.4 and higher
1. Introduction
2. Description of hardware
5. Operation (CAP2/316)
8. Technical data
12. Appendices
RE.216 1KHA000951-UEN ABB Switzerland Ltd
August 05
1. INTRODUCTION
1-1
ABB Switzerland Ltd RE.216 1KHA000951-UEN
1. INTRODUCTION
These Operating Instructions apply to the digital generator protection
REG216 and to the numerical control unit REC216. In these
instructions, the designation RE.216 is used to refer to both types
mentioned above.
1-2
RE.216 1KHA000951-UEN ABB Switzerland Ltd
1-3
ABB Switzerland Ltd RE.216 1KHA000951-UEN
1-4
RE.216 1KHA000951-UEN ABB Switzerland Ltd
August 05
2. DESCRIPTION OF HARDWARE
2.6. I/P and O/P units for the classic version ..........................................2-54
2.6.1. O/P relay unit 216GA61 ...................................................................2-54
2.6.2. Tripping relay unit 216GA62 ............................................................2-56
2.6.3. I/P relay unit 216GE61.....................................................................2-59
2-1
ABB Switzerland Ltd RE.216 1KHA000951-UEN
2. DESCRIPTION OF HARDWARE
2.1. Complete system
An RE.216 protection system comprises at least an electronic
equipment rack Type 216MB62 or 216MB68 with the electronic
modules inserted (plug-in units) and a number of I/O units, which are
in effect the interface with the primary plant, resp. the process. The
protection system is available as a cubicle version or as a
standardized electronic equipment rack. The standardized electronic
equipment racks can either be installed in a base frame or in a
protection cubicle.
The cubicle version contains one or several 216MB66 or 216MB68
equipment racks built into the hinged frame of a protection cubicle.
The electronic modules mounted on the front are designed as plug-in
units. The B448C parallel bus for the communication between the
electronic units is fitted firmly to the rear of the rack. Also mounted at
the rear of the rack are the plug-in bases for the connections via
system cable to the I/O units. The I/O units are mounted on the rear
wall of the protection cubicle.
The number of electronic units installed, their locations in a rack, the
number of racks and the number and arrangement of I/O units varies
from plant to plant.
Refer to the corresponding set of diagrams for the execution of an
RE.216 system for a particular plant.
Fig. 2.1 shows the principle function and the mode of operation of the
individual units and module types within the entire system.
2-2
RE. 216 1KHA000951-UEN ABB Switzerland Ltd
Fig. 2.1 RE.216 protection system; principle of operation of the cubicle version (see next page for legend)
2-3
ABB Switzerland Ltd RE.216 1KHA000951-UEN
2-4
RE.216 1KHA000951-UEN ABB Switzerland Ltd
2-5
ABB Switzerland Ltd RE.216 1KHA000951-UEN
2-6
RE.216 1KHA000951-UEN ABB Switzerland Ltd
2-7
ABB Switzerland Ltd RE.216 1KHA000951-UEN
2-8
RE.216 1KHA000951-UEN ABB Switzerland Ltd
2-9
ABB Switzerland Ltd RE.216 1KHA000951-UEN
NOTE: Please observe the specific set of station diagrams for the
disposition of the electronic units in the electronic equipment rack
216MB66 of a given station.
2-10
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Table 2.1 gives the standard slot references for the various units in a
single system. For example, a maximum of two 216VC62a processing
units can be installed in an equipment rack and are always located in
slot 4 and 6.
The designations and numbering of the I/O signals for the I/P and O/P
units of a protection system are given in the column "I/O channel
definition". Note that the quantity of I/O channels given for each group
of the same type of units refers to the particular equipment rack and
not the entire system. The number of I/O units installed gives the total
quantity of I/O channels for the entire system.
2-11
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Rack Unit No. Unit Type 216 Capacity / Function I/O channel definition
1)
Rack division No. 9 for 216EA61, rack division No. 8 for 216EA62
2)
Rack division No. 11 for 216EA61, rack division No. 10 for 216EA62
2-12
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Rack Unit No. Unit Type 216 Capacity / Function I/O channel definition
1. Analog I/P’s
Quantity Quantity Max. capacity (channels)
Version 216EA61 / 216GW61 / Analog I/P signals
216EA62 216GW62
1.1 1 1 12
1.2 1 2 24
1.3 2 3 36
1.41) 2 4 48
2-13
ABB Switzerland Ltd RE.216 1KHA000951-UEN
2. Signals
Quantity Quantity Max. capacity (channels)
Version 216AB61 216GA61 Signals Alarms
2.1 1 1 14 2
2.2 1 2 30 2
2.3 2 3 46 2
2.4 2 4 62 2
2-14
RE.216 1KHA000951-UEN ABB Switzerland Ltd
216 216
GA62 GA62
216
GA61
216
GA62
216 216
GA61 GA61
216 216
GA62 GA62
System B System B
2-15
ABB Switzerland Ltd RE.216 1KHA000951-UEN
2-16
RE.216 1KHA000951-UEN ABB Switzerland Ltd
ESL2080E
2-17
ABB Switzerland Ltd RE.216 1KHA000951-UEN
2-18
RE.216 1KHA000951-UEN ABB Switzerland Ltd
2-19
ABB Switzerland Ltd RE.216 1KHA000951-UEN
2-20
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Design
Fig. 2.12 shows the front and rear views of the auxiliary DC supply
units. The units have a width of 3 divisions (3T). The operation and the
construction of the three types 216NG61, 62 and 63 are identical.
2-21
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Settings
The states of the plug-in jumpers A and B at the rear of the unit
determine whether one or both of the auxiliary DC supply lines USA
and USB are supplied. Fig. 2.13 shows the corresponding plug-in
jumper positions (see also Fig. 2.9).
2-22
RE.216 1KHA000951-UEN ABB Switzerland Ltd
c) In the event of an auxiliary supply failure, the first binary O/P unit
216AB61 energizes the SML "System defect" signal line on the
B448 parallel bus. This is signaled remotely via channel CHO01.
2-23
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Settings
No settings have to be made to the equipment rack.
Care should be taken that the standard cables go to the appropriate
connectors for the electronic units actually inserted. Refer also to
Sections 2.1., 2.2.1 and 2.2.2. and the set of specific plant diagrams.
2.4.2. Processing unit 216VC62a
All the available protection and logic functions described in Section 3
are stored as a software module library in the 216VC62a processing
unit. All the user settings for the activated functions and the
configuration of the protection, i.e. assignment of I/P and O/P signals
(channels) to the protection functions, are also stored in this unit. The
software is downloaded using the operator program.
The protection functions and their associated settings necessary for a
particular plant are selected and stored with the aid of the portable
user interface (PC). Every individually selected and activated function
requires a certain percentage of the total available computing capacity
in [%] of the processing unit (see Section 3).
The processing unit 216VC62a has a computing capacity of 425 %.
The 216VC62a is used both as a processor and as an interface to the
interbay bus (IBB) in the substation monitoring system (SMS) and the
substation automation system (SAS). The available communication
protocols are:
• SPA
• LON
• MVB
• IEC 60870-5-103
In addition an MVB process bus is available.
The LON and MVB protocols are transferred by PC cards.
2-24
RE.216 1KHA000951-UEN ABB Switzerland Ltd
2-25
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Fixing screw
Socket 'Passive'
LED (red) 'Alarm'
Socket 'Reset'
Fixing screw
2-26
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Settings
No (hardware) settings are necessary on the 216VC62a unit itself.
2-27
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Design
Fig. 2.15 shows the front view of the analog I/P unit, which is a plug-in
unit with a width of 2 standard divisions (2T). The internal auxiliary
supply voltage is 5 V and is derived inside the unit from the 24 V
auxiliary DC supply. The unit's main components are:
• 24 (measurement) channel analog (-40 V...+40 V)-to-digital
converter
• processor for pre-processing the measured variables
• bus interface
• program memory
• main memory
• electrically deletable and programmable data memory
Settings
No (hardware) settings are necessary on the 216EA61 resp. 216EA62
unit itself.
The measuring channels are assigned to the activated protection
functions (configuration) with the aid of the portable user interface (PC)
connected to the 216VC62a unit.
Refer to the set of specific plant diagrams for the configuration of the
particular plant.
2-28
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Fixing screw
Socket 'Passive'
Socket 'Reset'
Fixing screw
2-29
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Design
Fig. 2.16 shows the front view of the binary O/P unit, which is a plug-in
unit with a width of 1 standard division (1T). The internal auxiliary
supply voltage is 5 V and is derived inside the unit from the 24 V
auxiliary DC supply. The unit's main components are:
• bus interface
• O/P register and O/P monitor
• O/P driver stages
2-30
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Fixing screw
Socket 'Passive'
Fixing screw
2-31
ABB Switzerland Ltd RE.216 1KHA000951-UEN
2-32
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Position X4-X5: System defect and stand-by signal (CH001, 002 in operation)
Position X3-X4: System defect and stand-by signal (CH001, 002 out of operation)
2-33
ABB Switzerland Ltd RE.216 1KHA000951-UEN
2-34
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Design
Fig. 2.18 shows the front view of the binary I/P and tripping unit, which
is a plug-in unit with a width of 1 standard division (1T). The internal
auxiliary supply voltage is 5 V and is derived inside the unit from the
24 V auxiliary DC supply. The unit's main components are:
• bus interface
• I/P register
• O/P register and O/P monitor
• O/P driver stages
• fault detector
2-35
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Fixing screw
Fixing screw
2-36
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Blocking relay
(Blocking CH OUT at short circuit
or by BLOCK 1/2)
2-37
ABB Switzerland Ltd RE.216 1KHA000951-UEN
2-38
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Design
Fig. 2.20 shows the front view of the analog/binary O/P unit, which is a
plug-in unit with a width of 1 standard division (1T). The internal
auxiliary supply voltages are 5 V and ±15 V for the analog O/P circuits
and are derived inside the unit from the 24 V auxiliary DC supply. The
unit's main components are:
• bus interface
• O/P register and O/P monitor for binary signals
• O/P driver stages for binary signals
• O/P register for analog signals
• D/A converter
• O/P driver stages for analog O/P currents
2-39
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Fixing screw
Socket 'Passive'
Fixing screw
2-40
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Position X4-X5: System defect and stand-by signal (CH001, 002) in operation
Position X3-X4: System defect and stand-by signal (CH001, 002) out of
operation
2-41
ABB Switzerland Ltd RE.216 1KHA000951-UEN
2-42
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Design
Fig. 2.22 shows the front view of the binary I/P unit, which is a plug-in
unit with a width of 1 standard division (1T). The internal auxiliary
supply voltage of 5 V is derived inside the unit from the 24 V auxiliary
DC supply. The unit's main components are:
• bus interface (64 kByte DPM/RAM)
• I/P register
• microprocessor for pre-processing signals (80C188)
• program memory (128 kByte EPROM)
• main memory (64 kByte RAM).
2-43
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Fixing screw
Socket 'Passive'
LED (red) 'Alarm'
Socket 'Reset'
Fixing screw
2-44
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Settings
The 216GW62 unit does not have any settings.
2-45
ABB Switzerland Ltd RE.216 1KHA000951-UEN
2-46
RE.216 1KHA000951-UEN ABB Switzerland Ltd
2-47
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Channel RA RB Channel RA RB
1 R402 R403 9 R602 R603
2 R412 R413 10 R612 R613
3 R422 R423 11 R622 R623
4 R432 R433 12 R632 R633
5 R502 R503 13 R702 R703
6 R512 R513 14 R712 R713
7 R522 R523 15 R722 R723
8 R532 R533 16 R732 R733
• 8 tripping relays:
Controlled by the tripping unit 216DB61. In each case, one circuit
is connected to terminals, which is made by two contacts in series.
• 16 signaling relays:
Controlled by the binary O/P unit 216AB61. The N/O contact of all
the relays and the N/C contact of relays 1...4 are connected to
terminals.
The unit is supplied at 24 V DC and provision is made for redundant
supplies. The location of the 216GD61a unit and its wiring diagram can
be seen from Fig. 2.25.
2-48
RE.216 1KHA000951-UEN ABB Switzerland Ltd
2-49
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Output
I/O interface
Binary
216GD61a
Input
2-50
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Channel RA RB Channel RA RB
1 R133 R117 9 R141 R125
2 R134 R118 10 R142 R126
3 R135 R119 11 R143 R127
4 R136 R120 12 R144 R128
5 R137 R121 13 R145 R129
6 R138 R122 14 R146 R130
7 R139 R123 15 R147 R131
8 R140 R124 16 R148 R132
• 6 tripping relays:
Controlled by the tripping unit 216DB61. In each case, one circuit
is connected to terminals, which is made by two contacts in series.
• 14 signaling relays:
Controlled by the binary O/P unit 216AB61. The N/O contact of all
the relays and the N/C contact of relays 1...4 are connected to
terminals.
The unit is supplied at 24 V DC and provision is made for redundant
supplies. A fuse F101 (2 A fast, 5 x 20 mm) is fitted to protect the 24 V
supply against short-circuits on the unit. The location of the 216GD61
unit and its wiring diagram can be seen from Fig. 2.27.
2-51
ABB Switzerland Ltd RE.216 1KHA000951-UEN
2-52
RE.216 1KHA000951-UEN ABB Switzerland Ltd
2-53
ABB Switzerland Ltd RE.216 1KHA000951-UEN
2-54
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A1 A6 A2 A4 A5
X12
X12
3 3 3 X12
X .. X ..
X .. X .. 1 1 1 X12
K ..
K ..
K ..
K ..
X10
7 7 7
6 6 6 X10
Settings
The 216GA61 unit does not have any settings.
2-55
ABB Switzerland Ltd RE.216 1KHA000951-UEN
The auxiliary tripping relays K1…K8 are controlled by the binary I/P
and tripping unit 216DB61. Fig. 2.31 shows the basic control circuit for
the control of the tripping relays.
2-56
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Fig. 2.31 Basic control circuit for the auxiliary tripping relays
K1...K8
How the tripping relay contacts are wired varies from plant to plant.
The different ways of wiring the contacts of the relays K1...K8 can be
seen from Table 2.7.
The relationship between the tripping relays and the numbering of the
tripping channels is:
1st 216GA62 unit, K1...K8 correspond to CHO01...CHO08
2nd 216GA62 unit, K1...K8 correspond to CHO09...CHO16
3rd 216GA62 unit, K1...K8 correspond to CHO17...CHO24
4th 216GA62 unit, K1...K8 correspond to CHO25...CHO32
Refer also to section 2.4.5. and Table 2.1.
2-57
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Direct tripping
In addition to being controlled by 216DB61, the diode matrix tripping
logic on 216GA62 also permits tripping relays K1...K8 to be directly
controlled by the external input signals from the 216GE61 unit (see
Fig. 2.31 and Section 2.6.3).
The first 10 channels (K1...K10) of the 216GE61 input relay assembly
are wired to the diode matrix tripping logic to facilitate direct tripping.
Direct tripping is enabled by inserting diode pegs in the desired
channels.
Refer to the set of specific plant diagrams for execution, alternative
wiring of the tripping contacts, assignment of the tripping channels and
arrangement of the diode pegs.
Settings
• Insert the diode pegs to achieve the desired tripping logic.
• There are no other settings on the 216GA62 unit.
Checks
• Check that the correct auxiliary tripping relays with a rated coil
voltage of 12 V DC are inserted in positions K1...K8.
2-58
RE.216 1KHA000951-UEN ABB Switzerland Ltd
2-59
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Fig. 2.33 Basic control circuit for the external signal I/P relays
K1...K16
The auxiliary relay channels K1...K10 are also connected to the matrix
tripping logic to enable them to directly energize tripping relays.
A second contact on each of the relays K1...K16 is wired to terminals
to remotely signal that the corresponding channel is energized.
The relationship between the auxiliary relays and the numbering of the
I/P channels is:
1st 216GE62 unit, K1...K16 correspond to CHI01...CHI16
2nd 216GE62 unit, K1...K16 correspond to CHI17...CHI32
3rd 216GE62 unit, K1...K16 correspond to CHI33...CHI48
4th 216GE62 unit, K1...K16 correspond to CHI49...CHI64
Refer also to Section 2.4.5. and Table 2.1.
Settings
There are no settings on the 216GE61 unit.
Checks
Check that the auxiliary relays fitted for K1...K16 the correct rated coil
voltage (= external auxiliary supply voltage).
2-60
RE.216 1KHA000951-UEN ABB Switzerland Ltd
2-61
ABB Switzerland Ltd RE.216 1KHA000951-UEN
The protection circuit will not reset, if the fault that caused it to pick up
is still present. In such a case, switch off the supply and check the
external wiring for short-circuits and open-circuits.
• Opto-coupler input:
This has the same function as the reset button and can also be
used to disable injection. The latter occurs when the input is at
logical '1' and resumes when it is returned to logical '0'.
The input voltage, the injection frequency and the opto-coupler voltage
must be specified in the customer's order and are then set in the works
prior to delivery.
There are no controls inside the unit that have to be set by the user.
Supply failure
If the green LED 'READY' is not lit in the case of version U1 although
the correct auxiliary supply voltage is applied, check and if necessary
replace the fuse on the supply unit 316NE61. The MCB is located at
the rear next to the auxiliary supply terminals.
Fuse type: cartridge 5 x 20 mm
2 A slow
Faulty U0, U2 and U3 units must be returned to the nearest ABB agent
or directly to ABB, Baden, Switzerland.
2-62
RE.216 1KHA000951-UEN ABB Switzerland Ltd
2-63
ABB Switzerland Ltd RE.216 1KHA000951-UEN
2-64
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Ui 25 V
*) The winding for voltage Uir has a tapping at 30 V. This enables Uir to be stepped down to
30 V or 20 V where an injection voltage less than 50 V is necessary.
2-65
ABB Switzerland Ltd RE.216 1KHA000951-UEN
2.8.2. REX011-1, -2
These injection transformers bear the following identifications (see
also Table 2.9 and Table 2.10):
• HESG 323 888 M11, M12, M13 for REX011-1
• HESG 323 888 M21, M22, M23 for REX011-2.
The injection transformers used for secondary injection of the stator
circuit have four injection voltage windings that are connected in
parallel or series to adjust the power to suit the particular grounding
resistor.
The value of the parallel resistor R'Ps, respectively the maximum
injection voltage determine the permissible injection voltage
The rated values of the injection voltage Uis are valid for the version
REX010 U1 and a battery voltage UB = 110 V DC.
For the versions U0, U2 and U3 all voltages are smaller by the factor
96/110 = 0,8727.
2-66
RE.216 1KHA000951-UEN ABB Switzerland Ltd
The connections to the primary system are made via the two heavy-
duty terminals 10 and 15 of Type UHV that are designed for spade
terminals. There are four Type UK35 universal terminals 11 to 14
which are used for the internal wiring between the two heavy-duty
terminals.
Depending on the version, the four windings must be connected to the
corresponding universal or heavy current terminals.
Should the version supplied not be the correct one, the connections
from the windings to the terminals must be changed as shown in the
following diagrams.
In the case of versions M12, M22, M13 and M23, KB-15 shorting links
must be fitted to the universal terminals. How this is done can be seen
from the diagram marked "Shorting links" at the end of this Section.
Shorting links and 3 rating plates are enclosed with every transformer.
After modification the appropriate rating plate should be stuck over the
old one.
S3 S4 S5 S6
10 11 12 13 14 15 16 17
10 11 12 13 14 15
In the case of versions M11 (REX011-1) and M21 (REX011-2), the two
windings S3 and S4 are connected in parallel across the heavy-duty
terminals (10, 15). The other two windings are not used and are wired
to the universal terminals. There are no KB-15 shorting links.
2-67
ABB Switzerland Ltd RE.216 1KHA000951-UEN
S3 S4 S5 S6
10 11 12 13 14 15 16 17
10 11 12 13 14 15
S3 S4 S5 S6
10 11 12 13 14 15 16 17
10 11 12 13 14 15
In the case of versions M13 (REX011-1) and M23 (REX011-2), all the
windings S3...S6 are connected in series. Terminals 12 and 13 are
bridged by a shorting link type KB-15.
2-68
RE.216 1KHA000951-UEN ABB Switzerland Ltd
The diagram below shows the shorting links used for versions M12
and M22:
Shorting links
Terminal screws
Shorting links
Universal terminals
11 to 14
Fig. 2.39 Shorting links used for versions M12 and M22
4 terminal screws, 3 shorting links and 1 dummy link are enclosed with
every transformer.
The shorting links are inserted into the recesses provided on the
universal terminal block.
2-69
ABB Switzerland Ltd RE.216 1KHA000951-UEN
2.8.3. Figures
Fig. 2.40 Injection signal Uis
Fig. 2.41 Wiring diagram for REX011 for primary injection of the
stator
Fig. 2.42 Wiring diagram for REX011-1 for secondary injection of
the stator at the star-point
Fig. 2.43 Wiring diagram for REX011-2 for secondary injection of
the stator at the terminals
Fig. 2.44 Wiring diagram for REX011 for rotor ground fault
protection
Fig. 2.45 Wiring diagram for REX011-1, -2 for rotor ground fault
protection
Fig. 2.46 Wiring diagram for REX011 for testing without the
generator
Fig. 2.47 Wiring diagram for REX011-1, -2 for testing without the
generator
Fig. 2.48 Dimensioned drawing of the injection transformer block
Type REX011
[V]
110
-110
Injection Test
2-70
RE.216 1KHA000951-UEN ABB Switzerland Ltd
R S T
Generator
REG216
N12 N11
REX010 REX011 REs Us
T. T.
X1 X1
Ui1 5 6 Voltage
5
transformer
Reset+ 7
RPs
Reset- 6 216GW62
7
316 GW61
3
Ui2 3
10
Ui
Ui3 4
4 11
UBat+ +
1
Up8+ 1 P8nax
UBat- -
Up8- 2
2
Fig. 2.41 Wiring diagram for REX011 for primary injection of the
stator (see also Fig. 2.48)
2-71
ABB Switzerland Ltd RE.216 1KHA000951-UEN
R S T
Generator
REG216
Voltage transformer
N'12 N'11
N1 N2 Us
R'Es
Grounding
transformer
R'Ps
316
216GW62
GW61
REX010 REX011-1 X2
T. T. X1
5
Ui1 5 10
Reset+ 7 Uis
Reset- 6
15
Ui2 3
3
X1
8
Ui
Ui3 4 9
4
UBat+ +
Up8+ 1 P8nax
1
UBat- -
2
Up8- 2
2-72
RE.216 1KHA000951-UEN ABB Switzerland Ltd
R S T Grounding
transformer
REG216
N1 N2 Voltage
transfrormer
N'12 N'11
Us
R'Es
R'Ps
316
216GW62
GW61
Generator
REX010 REX011-2
T. T. X1 X2
Ui1 5 10
5
Reset+ 7 Uis
Reset- 6
15
Ui2 3
3
X1
8
Ui
Ui3 4 9
4
UBat+ +
Up8+ 1 P8nax
UBat- - 1
Up8- 2
2
2-73
ABB Switzerland Ltd RE.216 1KHA000951-UEN
+
Rotor
-
2 × 2 µF
2 × 2 µF
8 kV 2) 1) 8 kV
REG216
Ui1 5 8
5
Reset+ 7
RPr
316
216GW62
GW61
Reset- 6
9
3
Ui2 3
10
Ui
Ui3 4
4
UBat+ + 11
Up8+ 1
1 P8nax
UBat- -
Up8- 2
2
Fig. 2.44 Wiring diagram for REX011 for rotor ground fault
protection (see also Fig. 2.48)
2-74
RE.216 1KHA000951-UEN ABB Switzerland Ltd
+
Rotor
-
2 × 2 µF 2 × 2 µF
8 kV 2) 1) 8 kV
REG216
Ui1 5 6
5
Reset+ 7
RPr
316
216GW62
GW61
Reset- 6
7
3
Ui2 3
Ui
Ui3 4
4
UBat+ + 9
Up8+ 1
1 P8nax
UBat- -
Up8- 2
2
Fig. 2.45 Wiring diagram for REX011-1, -2 for rotor ground fault
protection (see also Fig. 2.48)
2-75
ABB Switzerland Ltd RE.216 1KHA000951-UEN
S1
Ck = 4 µF
Rf
S2 CE = 1 µF
REG216
1 k Ω 2,5 W
REX010 REX011 22 Ω Us
T. T. X1 X1
Ui1 5 8
5
150 Ω
7
50 V
>10 W
6 316
216GW62
GW61
9
3
Ui2 3
Ur
10
Ui3 4
4 11
UBat+ +
1
Up8+ 1 P8nax Ui
UBat- -
Up8- 2
2
Fig. 2.46 Wiring diagram for REX011 for testing without the
generator
2-76
RE.216 1KHA000951-UEN ABB Switzerland Ltd
S1
Ck = 4 µF
Rf
S2 CE = 1 µF
REG216
1 kΩ 2,5 W
REX010 REX011-1, -2
22 Ω Us
T. T. X1 X1
Ui1 5 6
5
150 Ω
7 50 V
>10 W
6 316
216GW62
GW61
7
3
Ui2 3
Ur
Ui3 4
4 9
UBAT+ +
1
Up8+ 1 P8nax Ui
UBat- -
2
Up8- 2
Fig. 2.47 Wiring diagram for REX011-1, -2 for testing without the
generator
2-77
ABB Switzerland Ltd RE.216 1KHA000951-UEN
2-78
RE.216 1KHA000951-UEN ABB Switzerland Ltd
2-79
RE.216 1KHA000951-UEN ABB Switzerland Ltd
August 05
3-1
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-2
RE.216 1KHA000951-UEN ABB Switzerland Ltd
3-3
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-4
RE.216 1KHA000951-UEN ABB Switzerland Ltd
3-5
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-6
RE.216 1KHA000951-UEN ABB Switzerland Ltd
3-7
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Diff-Gen 40 dito
Current-DT 2 3 1 4 2
DirCurrentDT 19 dito 4 2
DirCurrentInv 21 dito
Current-Inst 3 4 2 4 2
Imax/Umin 5 8 2 4 2
Current-Inv 4 7 3
NPS-DT - 6 1
Voltage-DT 2 3 1 4 2
Voltage-Inst 3 4 2 4 2
Voltage-Bal 4 9 dito 4 2
Underimped 6 17 4 11
MinReactance 6 17 4 11
Power 5 14 3 8 4 2
OLoad-Stator 4 7 3
OLoad-Rotor - 6 3
NPS-Inv - 8 3
Frequency 15 - 3 2
Overexcitat 15 - dito 2
Stator-EFP 40 dito
Rotor-EFP 40 dito
Pole-Slip 20 dito
SynchroCheck 16 dito 2
Delay 8 dito
Counter 8 dito
Logic 4 dito
Defluttering 4 dito
BreakerFailure 34 46 dito
UifPQ 5 dito
Check-I3ph - 5 dito 2
Check-U3ph - 5 dito 2
Distur. rec.
3-8
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Distance 50
Z<start 20
Meas Bward 5
VTSup NPS 3
Power swing 15
HV distance 70
Meas Bward 5
VTSup NPS 3
Power swing 15
EarthFaultIsol 5 dito 4 2
Autoreclosure 1 dito
EarthFltGnd2 10 dito 4 2
IO-Invers 4 3
MeasureModule
Voltage/CurrentInp 10 dito
Cnt 8 dito
(*) can only be set once (**) always 1 for delays ≥ 200 ms
(***) depends on repetition rate (low/medium/high)
Example:
Table 3.4 shows the computation requirement according to Table 3.3
for a simple protection scheme with four active functions. Since
functions 1 and 2 use the same analogue inputs, the amount of
computing capacity required for function 2 is reduced to that of a
second stage.
3-9
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-10
RE.216 1KHA000951-UEN ABB Switzerland Ltd
with a DC component
time const. up to 150 ms
t < 30 ms 30 IN
t < 100 ms 23 IN
t < 200 ms 16 IN
t > 200 ms 14 IN
3-11
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-12
RE.216 1KHA000951-UEN ABB Switzerland Ltd
3-13
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-14
RE.216 1KHA000951-UEN ABB Switzerland Ltd
3-15
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Channel Type
The channel type is provided by the built-in A/D converter. The details
have to be taken from the respective schematics.
In the following tables the configuration possibilities and their
significance are explained.
Sec.nom.val.
Enter the nominal values for the CTs and VTs in the input transformer
unit (1 A, 2 A, 5 A, 100 V or 200 V). 3 phase converters take the value
of the R phase.
In order that the resolution of the impedance setting for a rated current
of 5 A is meaningful, the impedance setting range for 5 A is
automatically reduced by a factor of 10.
3-16
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Prim/Sec ratio
This setting is utilized to correctly display the primary value in the
measurands display of the HMI, for the evaluation of the disturbance
records, and for the IEC60870-5-103-Protocol. Three-phase CT and
VT channels assume the same value as R phase.
Ref. value
The reference values of the CT / VT channels enable the device
ratings to by matched to those of the protected unit. They e a factor
that can be set in the range 0.5 to 2. Three-phase channels assume
the same value as R phase.
Example: Rated voltage = 110 V
110 V
Reference value of the voltage channel = = 1.100
100 V
Effects of changing the reference values:
With the exception of the impedance settings for the distance function,
the protection function settings (parameters expressed in relation to
'IN' and 'UN') are automatically adjusted to the new reference values.
In the case of the distance function, adjusting the nominal current will
change the impedance values. For this reason the reference values for
the current inputs should not be changed.
Comment
User comment can be entered for each analog channel, which is
displayed together with the channel type when the corresponding
CT/VT input parameter of a protection function is selected.
3.4.3. Entering comments for binary inputs and outputs and analog
outputs
(see Section 5.4.2.)
By clicking on the 'Edit' button for the resp. slot card in the window
'Relay Configuration RE.216' the user can enter comments for each of
the binary inputs, LED, signaling outputs and tripping outputs.
3-17
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-18
RE.216 1KHA000951-UEN ABB Switzerland Ltd
3-19
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-20
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Explanation of parameters:
Confirm Parameters
If this parameter is set to ON, then on saving the parameters to a
file or the device, a list of the difference between the last saved
values and the current values are created.
This parameter has been implemented only in Version 6.5c and
above. This is not functional for lower versions.
Time Synchronization By PC
switches ON/OFF the synchronization of the RE.216 clock by the
PC when the HMI is started.
General Trip
General tripping signal generated via an OR function of all tripping
signals assigned to the tripping logic.
General Start
Signal for 'General Start'.
This signal is the OR of all start signals configured as events.
General Trip Mem
Latched General tripping signal generated via the General Trip,
remains latched until it is reset by one of the two reset signals.
General Start Mem
Latched General tripping signal generated via the General Start,
remains latched until it is reset by one of the two reset signals.
Test active (see Section 5.5.3.)
Signal indicating that the device is in the test mode.
This signal remains set as long as the HMI menu 'Test Functions'
is open.
MMI is On
Signal indicating that the control PC is connected and serviceable.
Reset 1, Reset 2
Input for remote resetting the signaling latched LEDs and relays:
Block Signals
Input for blocking of all signals.
All outputs to the relays and output cards are blocked. But the
event is logged.
3-21
ABB Switzerland Ltd RE.216 1KHA000951-UEN
NOTE: When the jumper X3 on the card 216DB61 is activated for the
function 'Release and Blocking of the tripping circuit', the inputs Block
Trips 1, Block Trips 2, Enable Trips 1, Enable Trips 2 of the System
Parameters are still active. (see Section 2.4.5.).
Enable Test
Input for the release of the HMI controlled test function
Remote Setting (see Section 5.9.1.)
Input for switching between sets of parameters via the interbay
bus.
Always FALSE: Switching between sets of parameters only by the
binary inputs ‘ParSet2…4’
Always ON: Switching between sets of parameters only by the
station control system
ParSet 2 IN...ParSet 4 IN (see Section 5.9.1.)
Inputs for switching between different sets of parameters.
ParSet 1 OUT...ParSet 4 OUT (see Section 5.9.1.)
Signal indicating the active set of parameters.
MVB PB Warning, MVB PB Crash, Process Bus BA1 Ready... Process
Bus BA4 Ready, Process Bus LA faulty, Process Bus LB faulty
These messages are only generated when using an MVB process
bus (see Operating Instructions for the remote I/O system RIO580,
1MRB520192-Uen).
3-22
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
Differential protection of generators.
B. Features
• Non-linear current-dependent tripping characteristic
(see Fig. 3.1)
• High stability during through-faults and CT saturation
• Short operating times
• Three-phase measurement
• Optimized for the differential protection of generators, i.e.
• no inrush restraint
• no compensation of group of connection
• only two measuring inputs
• Suppression of DC off-set
• Suppression of harmonics
I. Analog inputs:
• Current (2 sets of 3 inputs)
IV. Measurements:
• R phase summation current
• S phase summation current
• T phase summation current
3-23
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Explanation of parameters:
Run On CPU
Defines on which CPU the function should operate.
Trip
defines the tripping channel activated by the tripping output of the
function (tripping logic).
g Setting
Basic setting (sensitivity) g of the operating characteristic.
v Setting
Pick-up ratio (slope) of the operating characteristic.
Current Inp. Chan.
defines the A/D input channels. The first channel (R phase) of the
two groups of three phases with the same reference values from
the same sampling group must be specified. I.e. the channels 1, 7,
13, 19, 25, 31, 37 or 43.
Blocking Inp Chan
Binary address used as blocking input.
Signaling Trip
Output for tripping signal
Note:
The differential protection function does not have a pick-up signal.
Every time it trips, the signal 'GenStart' is set together with 'Trip',
providing the tripping command is configured to be recorded as an
event.
The tripping measurands will be stored in the event list only if the
trip command is configured in the event list.
3-24
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Signaling Trip-R
signals that tripping was initiated by R phase.
Signaling Trip-S
signals that tripping was initiated by S phase.
Signaling Trip-T
signals that tripping was initiated by T phase.
3-25
ABB Switzerland Ltd RE.216 1KHA000951-UEN
E. Setting instructions
Basic setting g Setting
Pick-up ratio v Setting
Basic setting g
The basic setting g defines the pick-up of the differential protection for
internal faults. It is the section of the operating characteristic with a low
restraint current IH.
The lowest possible value should be chosen for 'g' (high sensitivity) to
enable it to detect the worst case faults, e.g. when excitation is low.
The protection cannot detect interturn faults on the same winding,
because they do not produce a differential current.
Since, however, a small differential current flows during normal
operation, false tripping could result if 'g' is set too low. The spurious
differential current is usually due to imbalances of CT errors and CT
burdens.
Allowing for an unwanted differential current, a typical setting is 0.1 IN.
Higher values have to be set for 'g' should, for example, the CTs on
opposite sides of the protected unit have different accuracy classes or
their burdens be too high.
The level of primary current at which the protection picks up depends
on the relay settings and the ratio of the CTs. Assuming that there is
no compensation of the A/D channels by reference value settings, it is
calculated as follows:
Relay setting g = 0.1 IN
(where IN is the relay rated current)
Generator rated current IGN = 4000 A
CT rated current IN1 = 5000 A
Calculated primary pick-up current
(referred to the generator rated current):
g I 5000
i= × N1 = 0.1 = 0.125
IN IGN 4000
3-26
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Pick-up ratio v
The pick-up ratio 'v' is decisive for the stability of the protection during
through-faults. This is the section of the operating characteristic with
restraint currents higher than 1.5 IN.
The value of 'v' defines the pick-up current ID for a restrain current IH in
the moderately sloped region of the operating characteristic. In the
case of generator differential protection, 'b' has a fixed setting of 1.5
(compare this with Fig. 3.3 and Fig. 3.4 for transformer differential
protection).
The 'v' setting should be low enough to make the protection sensitive
to faults when load current is flowing, but high enough to avoid false
tripping during through-faults. A typical setting is v = 0.25.
A higher setting (v = 0.5) is chosen in cases where the transient
behavior of the CTs during through-faults can cause large differential
currents. This is normally the result of under-sized CTs or widely
differing CT burdens.
Typical settings:
g Setting 0.1 IN
v Setting 0.25
3-27
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-28
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
Differential protection of two and three-winding power transformers
generator/transformer units.
B. Features
• Non-linear, current-dependent operating characteristic
(see Fig. 3.2)
• High stability during through-faults and in the presence of CT satu-
ration
• Short tripping times
• Three-phase measurement
• Inrush current restraint
• using the second harmonic
• detection of the highest phase current
• detection of the load current to determine whether the
transformer is energized or not
• Compensation of phase group
• Compensation of CT ratio
• Scheme for three-winding transformers
• phase-by-phase comparison of the highest winding current with
the sum of the currents of the other two windings
• DC current component filter
• harmonic filter
I. CT/VT inputs:
• Current (2 or 3 sets of 3 inputs)
IV. Measurements:
• R phase summation current
• S phase summation current
• T phase summation current
• R phase restraining current
• S phase restraining current
• T phase restraining current
3-29
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Explanation of Parameters:
Run On CPU
Defines on which CPU the function should operate.
3-30
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Trip
defines the tripping channel activated by the tripping output of the
function (matrix).
g - Setting
defines the basic setting g of the operating characteristic.
v - Setting
defines the pick-up ratio v of the operating characteristic.
b - Setting
defines the value b of the operating characteristic. This should be
set to approx. 1.5 times rated current.
g - High
High- Basic setting which replaces the normal basic setting when
activated by the 'HighSetInp' input.
It is used to prevent false tripping, for example, due to excessive
flux (overfluxing).
I - Inst
Differential current, above which tripping takes place regardless of
whether the inrush current is detected. The restraint current, the
pick-up ratio v and b remain active.
This enables the tripping time to be reduced for high internal fault
currents.
Inrush Ratio
Ratio of 2nd harmonic current content to fundamental current
above which an inrush condition is detected.
Inrush Time
Time during which the inrush detection function is active following
initial energization or an external fault.
a1
Amplitude compensation factor for winding 1.
s1
Connection of winding 1 (primary)
Settings provided:
• Y: star-connected
• D: delta-connected
Current Inp.Chan. 1
defines the CT input channel for winding 1.
The first channel (R phase) of the two groups of three phases must
be specified.
a2
Amplitude compensation factor for winding 2.
s2
Vector group for winding 2.
Settings provided: All usual groups of connection with
• designation of the circuit (y = star, d = delta, z = zigzag)
3-31
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-32
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Inrush Signal
Signal output for inrush current.
This signal is set, when the tripping conditions are fulfilled, even
though the tripping is disabled due to the inrush restraint.
Stabilizing Signal
Output for signaling IH > b during through-faults.
I∆
IN
3
Operation for
I'1
<b
Operation IN
2 or
I'2
<b
IN
1
v Restraint
g
1 b 2 3 IH
IN
Protected I2
I1 unit
I3 HEST 965 007 C
I∆ = I1 + I2 + I3 Operating (differential)
current
3-33
ABB Switzerland Ltd RE.216 1KHA000951-UEN
E. Setting instructions
Basic setting g
Pick-up ratio v
Operating characteristic switching point b
Increased basic setting g - High
Pick-up differential current
(uninfluenced by inrush detection) I - Inst
Pick-up ratio of the inrush detector Inrush Ratio
Inrush detection time Inrush Time
Amplitude compensation factors a1 a2 a3
Connection of winding 1 s1
Vector groups of windings 2 and 3 s2 s3
The purpose of the transformer differential protection is to detect
phase faults in the protected zone. It may also detect earth faults and
interturn faults. The protection is sensitive, fast and absolutely
discriminative.
Basic setting g
The basic setting 'g' defines the pick-up setting of the differential
protection for internal faults.
The lowest possible value should be chosen for 'g' (high sensitivity) to
enable it to detect transformer earth faults and interturn faults in
addition to phase faults.
The setting of 'g' must not be too low, however, to avoid the danger of
false tripping due to:
• CT errors
• the maximum off-load transformer current at the maximum short-
time system voltage
• tap-changer range
The off-load current (magnetizing current) of a modern power
transformer is very low, usually between 0.3 and 0.5 % of rated current
at rated voltage. During short-time voltage peaks, e.g. following load
shedding, the off-load current can reach as much as 10 % or more.
The tap-changer voltage range is usually between ±5 % and ±10 %,
but ranges of ±20 % and more occur. Its influence has to be taken into
account regardless of whether the tap-changer is manually operated or
controlled by a voltage regulator.
All three of these influences cause a differential current, which flows
during normal system conditions. The setting for 'g' must be chosen
above the level of this differential current. A typical setting is g = 0.3 IN
(i.e. 30 % IN).
3-34
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Pick-up ratio v
The pick-up ratio 'v' is decisive for the stability of the protection during
external phase and earth faults, i.e. in the presence of high through-
fault currents.
The value of 'v' defines the ratio of the operating current to restraint
current. The setting should be such that when operating under load
conditions, weak faults causing only a low differential current can still
be detected, but at the same time there is no risk of false tripping
during through-faults. A typical setting is v = 0.5.
Restraint current b
The restraint current b defines the point at which the characteristic is
switched.
The sloped section of the characteristic ensures that the relay remains
stable during through-faults with CT saturation.
The ability to switch between two different slopes enables the
characteristic to adapt to different conditions.
The recommended setting for 'b' is 1.5. This provides high stability
during high through-fault currents and sufficient sensitivity to detect
fault currents in the region of the operating current.
Factors a2 and a3
The full setting range for the factors a2 and a3 for compensating
current amplitude only applies, if the reference value for the CT input
channels is set to 1.000. At all other settings, the permissible upper limit
reduces in proportion to the ratio of the CT input channel reference values
(transformer winding 1/winding 2, respectively winding 3/winding 1).
Operating characteristic
The restrain current is either defined by the equation
or is zero
IH = 0 for 90° < α < 270°
The angle
α = ∠ (I1, − I2 )
3-35
ABB Switzerland Ltd RE.216 1KHA000951-UEN
I2 I1
α
I2
I2 I1
α = 0°
I I2
HEST 905 003b C
I2 α I1 I2
α = 180°
HEST 905003c C
3-36
RE.216 1KHA000951-UEN ABB Switzerland Ltd
I∆
IN
0,75
0,5
0,25
g b
IH
0 0,5 1 1,5 IN
HEST 905 003d C
I∆
IN
0,75
0,5
0,25
g b
IH
0 1 2 IN
HEST 905 003e C
3-37
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Example:
Internal fault and rated current flowing through the transformer:
I1 I
= 4 2 =1 α = 0
IN IN
-I 2
I1
I∆ = I1 + I2 = 4 IN − IN = 3 IN
IH = I1 × I2 × cos α = 4 IN × 1IN × 1 = 2 IN
I - Inst. = 12 IN
3-38
RE.216 1KHA000951-UEN ABB Switzerland Ltd
3-39
ABB Switzerland Ltd RE.216 1KHA000951-UEN
250/5 A
1
110 kV 131 A
25 MVA
20 kV 722 A
2
1000/5 A
HEST 905 004a C
ICT1 250
IB1 = ITN1 = 131 A a1 = = = 1.91
ITN1 131
ICT 2 1000
IB2 = ITN2 = 722 A a1 = = = 1.38
ITN2 722
A further difference lies in the fact that the 'a' factors only effect the
differential protection, whilst changing the reference values of the A/D
channels effects the currents for the entire protection system (all
functions and measured variables).
The windings of a three-winding transformer normally have different
power ratings and a reference power has to be chosen, which is used
for all three windings. All the settings of the protection are then
referred to the reference currents calculated from the reference power.
3-40
RE.216 1KHA000951-UEN ABB Switzerland Ltd
250/5 A
25 MVA 110 kV 131 A
1 500/5 A
3
2
SB 25 ICT 2 600
IB 2 = = 722 A a2 = = = 0.83
3 × U TN2 3 × 20 IB 2 722
SB 25 ICT 3 500
IB3 = = 2291 A a3 = = = 0.22
3 × UTN3 3 × 6.3 IB3 2291
The same results are obtained by applying the formulas with the
reference power SB:
UTN1 × ICT1 × 3 110 × 250 × 3
a1 = = = 1.905
SB 25000
3-41
ABB Switzerland Ltd RE.216 1KHA000951-UEN
The 'a' factors compensate the signals at the inputs of the differential
protection.
If the reference values of the A/D channels are changed, the changes
apply to the entire protection system (i.e. all functions and measured
variables).
This can be seen from the following example.
Reference values:
ITN1 131
Winding 1: Reference value = = = 0.524
ICT1 250
ITN2 577
Winding 2: Reference value = = = 0.962
ICT 2 600
ITN3 458
Winding 3: Reference value = = = 0.916
ICT 3 500
Factors a1, a2 and a3:
ITN1 131
a1 = = =1
IB1 131
ITN2 577
a2 = = = 0.799
IB2 722
ITN3 458
a3 = = = 0.200
IB3 2291
3-42
RE.216 1KHA000951-UEN ABB Switzerland Ltd
i F2
i F
G S GN
i F
A fault on the unit auxiliaries supply system causes a current iF (in p.u.)
to flow to the generator star-point.
Saux.sys.
iF = iF2
SGN
Example:
S aux.sys.
iF2 = 10; = 0.03
S GN
iF = 10 × 0.03 = 0.3
It follows from this that 'g' must be set higher than 0.3 to avoid the
possibility of a false trip.
Alternative No. 2: CTs installed in the unit transformer feeder on the
generator side of the unit transformer (Fig. 3.5). These CTs usually
have the same ratio as the generator CTs although the rating of the
unit transformer is much less. The reason is the high fault level on the
generator side of the unit transformer and the consequentially high
thermal and dynamic stress on the CTs.
The reference value of the CT channel of the protection is determined
by the rated current of the generator and not of the unit transformer.
Alternative No. 3: CTs installed in the unit transformer feeder on the
auxiliaries side of the unit transformer (Fig. 3.5). In this case, the CTs
are specified according to the rated current of the unit transformer.
Advantages:
• clearly defined zone of protection
• reduced performance required of the CTs, which are therefore
cheaper
3-43
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Disadvantages:
• Interposing CTs may be necessary
• reduced sensitivity of the protection for faults in the protected zone,
but on the auxiliaries side of the unit transformer
800/5 A
3000/5 A
300 MVA
GT 220/18 kV
30 MVA
0.8/10 kA 10/1 A
UT 18/6 kV
1/3 kA
10000/5 A
I>
300 MVA
G 18 kV
10 kA
10000/5 A
3-44
RE.216 1KHA000951-UEN ABB Switzerland Ltd
d11 d11
2 3
Note:
This setting for the vector group (s2 = d11, s3 = d11) assumes that in
relation to the protected unit, the star-point is symmetrically formed
and grounded on the secondary side of the main CTs.
Should this not be possible for some reason (e.g. plant requirements),
the group of connection has to be compensated.
3-45
ABB Switzerland Ltd RE.216 1KHA000951-UEN
I
R
1R
I 2R • Star-connected primary
I R
1S
S
I 1T
I 2S • Delta-connected secondary
S
T I 2T
T • Phase-angle between the currents of
I
1R the same phase on both sides
5 x 30° = 150°
150°
⎧⎪I1r (compensated) = 1 / 3 ( −I1R + I1S )
⎨
I
HEST 905 005 C
⎪⎩I2r (compensated) = I2R
Yy0 Yy6
1 2 I1R I2R 1 2 I
1R
R
R R R
S
S S S
T
T T T
I 2R
Yd1 Yd5
1 2 I 1 2 I
1R I 1R
2R
R R R
R
S S S
S
T T T
T
I 2R
Yd7 Yd11
1 2 I 1R 1 2 I
I 2R 1R
R
R R R
S
S S S
T
T T T
3-46
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Yz1 Yz5
1 2 I1R I 2R 1 2 I1R
R
R R R
S
S S S
T
T T T
I 2R
Yz7 Yz11
1 2 I 1R 1 2
R I2R I1R
R R R
S
S S S
T
T T T
I 2R
1R
Dy1 Dy5
I1R I 2R 1 2
1 2
R
R R R
S
S S S
T
T T T
I
2R
Dy7 Dy11
1 2 I 1 2
1R
R I2R I1R
R R
S R
S S
T S
T T T
I 2R
Dd0 Dd6
1 2 I 1R I 2R 1 2 I1R
R
R R R
S
S S S
T
T T T
I2R
Dz0 Dz2
1 2 I 1R I 2R 1 2 I1R
R R R I2R
R
S S S
S
T T T
T
Dz4 Dz6
1 2 I 1 2 I1R
R 1R
R R
S R
S S
T S
T T
T
I
2R
I2R
Dz8 Dz10
1 2 I1R 1 2 I
1R
R R R I2R
R
S S S
S
T T T
T I 2R
3-47
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-48
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Three-winding transformer:
Compensation matrix winding 1
X X X
s3 y0 y6 d1 d5 d7 d11 z1 z5 z7 z11
s2
y0 EEE EEF EEA CCB EEB CCA EEG CCH EEH CCG
y6 EFE EFF EFA CDB EFB CDA EFG CDH EFH CDG
d1 EAE EAF EAA COB EAB COA EAG COH EAH COG
d5 CBC CBD CBO CBB CBN CBA CBK CBH CBJ CBG
d7 EBE EBF EBA CNB EBB CNA EBG CNH EBH CNG
d11 CAC CAD CAO CAB CAN CAA CAK CAH CAJ CAG
z1 EGE EGF EGA CKB EGB CKA EGG CKH EGH CKG
z5 CHC HD CHO CHB CHN CHA CHK CHH CHJ CHG
z7 EHE EHF EHA CJB EHB CJA EHG CJH EHH CJG
z11 CGC CGD CGO CGB CGN CGA CGK CGH CGJ CGG
3-49
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Example:
The compensation for the currents of a three-winding transformer
Yd5y0 is as follows:
s1 = Y
s2 = d5 CBC results from Table 3.8, i.e. the
s3 = y0
compensation matrix
for winding 1 = C = (1 -1 0) (see Table 3.7)
with an amplitude factor of 1 / 3
⎛ Ir 1 ⎞ ⎛ 1 − 1 0 ⎞⎛ IR1 ⎞
⎜ ⎟ 1 ⎜ ⎟⎜ ⎟
Winding 1: ⎜ Is1 ⎟ = ⎜0 1 − 1⎟⎜ IS1 ⎟
⎜I ⎟ 3 ⎜−1 0
⎝ t1 ⎠ ⎝ 1 ⎟⎠⎜⎝ IT1 ⎟⎠
⎛ Ir 2 ⎞ ⎛ − 1 0 0 ⎞⎛ IR2 ⎞
⎜ ⎟ ⎜ ⎟⎜ ⎟
Winding 2: ⎜ Is2 ⎟ = 1 ⎜ 0 − 1 0 ⎟⎜ IS2 ⎟
⎜I ⎟ ⎜ 0 0 − 1⎟⎜ I ⎟
⎝ t2 ⎠ ⎝ ⎠⎝ T 2 ⎠
⎛ Ir 3 ⎞ ⎛ 1 − 1 0 ⎞⎛ IR3 ⎞
⎜ ⎟ 1 ⎜ ⎟⎜ ⎟
Winding 3: ⎜ Is3 ⎟ = ⎜0 1 − 1⎟⎜ IS3 ⎟
⎜I ⎟ 3 ⎜−1 0
⎝ t3 ⎠ ⎝ 1 ⎟⎠⎜⎝ IT3 ⎟⎠
3-50
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Typical values:
g 0.3 IN
v 0.5
b 1.5
g - High 0.75 IN
I - Inst 12 IN
Inrush Ratio 10 %
Inrush Time 5s
a1, a2, a3 have to be calculated
s1, s2, s3 depend on plant
3-51
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-52
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
General-purpose current function (over and under) for
• phase fault protection
• back-up protection
• ground fault protection
or for monitoring a current minimum.
B. Features
• Insensitive to DC component
• Insensitive to harmonics
• Single or three-phase measurement
• Maximum respectively minimum value detection in the three-phase
mode
• Detection of inrush currents
I. CT/VT inputs:
• Current
IV. Measurements:
• Current amplitude
3-53
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Explanation of parameters:
Run On CPU
Defines on which CPU the function should operate.
Trip
defines the tripping channel activated by the tripping O/P of the
function (matrix tripping logic).
Delay
Time between the function picking up and tripping.
I Setting
Pick-up current setting.
Forbidden settings:
• > 2.5 IN (when measured with metering CTs)
• < 0.2 IN (when measured with protection CTs)
3-54
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Max / Min
defines operation as overcurrent or undercurrent or with inrush
blocking. Settings:
• Min(1Ph): Undercurrent.
Three-phase functions detect the lowest
phase current.
• Max(1Ph): Overcurrent.
Three-phase functions detect the highest
phase current.
• Max-Inrush: Blocks during inrush currents if one phase
exceeds setting.
Number Of Phases
defines whether single or three-phase measurement.
Current Inp. Chan.
defines the CT input channel. All current I/Ps may be selected. In
the case of three-phase measurement, the first channel (R phase)
of the group of three selected must be specified.
Block Input
I/P for blocking the function.
Trip Signal
Tripping signal.
Start Signal
Pick-up signal.
3-55
ABB Switzerland Ltd RE.216 1KHA000951-UEN
E. Setting instructions
Settings:
Setting I Setting
Delay Delay
Over or undercurrent Max / Min
Number of phases Number Of Phases
The definite time current function protects transformers, primary
equipment of a captive network, and generators, which can cause an
overcurrent, such as an overload, short circuit and ground fault. The
filters at the measurement input damp the DC component of the
harmonics, thereby the protection reacts only on the fundamental
harmonics.
The protection can be used for sensitive current measurements e.g.
when the earth fault current is small.
Together with an external high impedance protection circuit, this
function can be used as a 'restricted earthfault protection (REF)'.
Setting I-Setting
The current setting 'I-Setting' must be sufficiently high on the one hand
to avoid any risk of false tripping or false signals under normal load
conditions, but should be low enough on the other to detect the lowest
fault current that can occur. The margin that has to be allowed
between the maximum short-time load current and the setting must
take account of:
• the tolerance on the current setting
• the reset ratio
The maximum short-time load current has to be determined according
to the power system conditions and must take switching operations
and load surges into account.
I-Setting
IN
Delay
3-56
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Delay
The delay is used to achieve discrimination of the overcurrent function.
It is set according to the grading table for all the overcurrent units on
the power system. The zone of protection of our overcurrent function
extends to the location of the next downstream overcurrent relay.
Should the downstream relay fail to clear a fault, the overcurrent
function trips slightly later as a back-up protection.
3-57
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-58
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
• General current monitoring with instantaneous response (over and
undercurrent)
• Current monitoring where insensitivity to frequency is required
(over and undercurrent)
B. Features
• Processes instantaneous values and is therefore fast and largely
independent of frequency
• Stores the peak value following pick-up
• No suppression of DC component
• No suppression of harmonics
• Single or three-phase measurement
• Maximum value detection in the three-phase mode
• Adjustable lower frequency limit fmin
I. CT/VT inputs:
• Current
IV. Measurements:
• Current amplitude (only available if function trips)
3-59
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Explanation of parameters:
Run On CPU
Defines on which CPU the function should operate.
Trip
defines the tripping channel activated by the tripping output of the
function (matrix).
Delay
Time between the function picking up and tripping.
I Setting
Pick-up current setting.
Setting restrictions:
• > 2.5 IN (when measured with metering CTs)
• < 0.2 IN (when measured with protection CTs)
Min. Frequency
defines the minimum frequency required for measurement.
Setting restriction:
• < 40 Hz when supplied from metering cores
Number Of Phases
defines whether single or three-phase measurement.
Current Inp. Chan.
defines the CT input channel.
All current inputs may be selected.
In the case of three-phase measurement, the first channel
(R phase) of the group of three selected must be specified.
Block Input
Binary address used as blocking input.
3-60
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Max / Min
defines operation as overcurrent or undercurrent. Settings:
• Max: overcurrent
• Min: undercurrent
Trip Signal
Output for signaling tripping.
Start Signal
Output for signaling pick-up.
3-61
ABB Switzerland Ltd RE.216 1KHA000951-UEN
E. Setting instructions
Settings:
Current pick-up I Setting
Delay Delay
Minimum frequency Min. Frequency
Over or undercurrent Max / Min
The instantaneous overcurrent function is a high-speed protection,
which operates in a wide frequency range. It is intended primarily for
two applications.
A protection measuring peak value is necessary for protecting units,
for which the influence of DC component and harmonics may not be
neglected. This is especially the case where rectifiers with semi-
conductors are involved.
The measuring principle of the function is relatively insensitive to fre-
quency and operates in a range extending from 4 to 120 % of rated
frequency. It is therefore able to protect units with synchronous starting
equipment during the starting sequence before reaching system
frequency (e.g. gas turbine sets with solid-state starters).
The function detects when the instantaneous value of the input current
exceeds the peak value corresponding to the setting. For example, for
a setting of 10 IN, it will pick up when the input current exceeds
10 2 IN = 14.14 IN (see Fig. 3.7).
A fault current of 6 × 1.8 2 IN = 15.27 IN could reach this level as a
consequence of a DC component.
The minimum frequency must be entered for every application, be-
cause it determines the reset time. A low minimum frequency means a
long reset delay and since a good protection is expected to have a
quick response, the reset time should be as short as possible, i.e. the
minimum frequency setting should not be lower than absolutely neces-
sary.
3-62
RE.216 1KHA000951-UEN ABB Switzerland Ltd
i 15
IN 14.14
10
Setting current
10 I N
0 t
Output signal
0 t
Typical settings:
a) Peak value phase fault protection
I Setting according to application
Delay 0.01 s
Min. Frequency 40 Hz
3-63
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-64
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
Overcurrent function with time delay inversely proportional to the
current and definite minimum tripping time (IDMT).
B. Features
• Operating characteristics (see Fig. 3.8) according to British
Standard 142:
c = 0.02 : normal inverse
c=1 : very inverse and long time earth fault
c=2 : extremely inverse
• RXIDG : logarithmic time characteristic
• Insensitive to DC component
• Insensitive to harmonics
• Single or three-phase measurement
• Detection of the highest phase value in the three-phase mode
• Wider setting range than specified in BS 142
I. CT/VT inputs:
• Current
IV. Measurements:
• Current amplitude
3-65
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Explanation of parameters:
Run On CPU
Defines on which CPU the function should operate.
Trip
defines the tripping channel activated by the tripping O/P of the
function (matrix tripping logic).
c -Setting
Setting for the exponential factor according to BS 142 resp. for
selecting the RXIDG characteristic.
k1 -Setting
Constant (multiplication factor) of the tripping characteristic.
I Start
Pick-up current at which the characteristic becomes effective.
Min. Tripping Time
Definite minimum tripping time.
Number Of Phases
Defines the number of phases measured.
Current Inp. Chan.
Defines the CT input channel. All current I/Ps may be selected. For
three-phase measurement, the first channel (R phase) of the group
of three selected must be specified.
IB - Setting
Base current for taking account of differences of rated current IN.
3-66
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Block Input
defines the input for an external blocking signal.
Trip Signal
Tripping signal.
Start Signal
Pick-up signal.
3-67
ABB Switzerland Ltd RE.216 1KHA000951-UEN
E. Setting instructions
Settings:
Base current IB - Setting
Characteristic enabling current I Start
Type of characteristic c -Setting
Multiplier k1 -Setting
The IDMT overcurrent function is used to protect transformers, feeders
and loads of the auxiliaries supply system against phase and earth
faults. The function responds largely only to the fundamental compo-
nent of the fault current.
Example:
Load current of protected unit IB1 = 800 A
CT rated current IN1 = 1000 A
IN2 = 5A
Relay rated current IN = 5A
Relay reference current 'IB-Setting':
I 5A
IB = IB1 N2 = 800 A =4A
IN1 1000 A
Setting:
IB 4 A
= = 0 .8
IN 5 A
3-68
RE.216 1KHA000951-UEN ABB Switzerland Ltd
3-69
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Multiplier 'k1-Setting'
The multiplier 'k1-Setting' enables the IDMT characteristic chosen by
the setting of parameter c to be shifted without changing its shape.
For example, in the case of the 'very inverse' characteristic, the
constant c = 1 and the factor k1 ≤ 13.5. The operating time t is given
by the equation
k1
t=
I
−1
IB
t [s] k1 [s]
0.5 2.5
1 5
1.5 7.5
2 10
2.5 12.5
Typical settings:
IB-Setting to be calculated
I-Start 1.1 IB
c-Setting plant-specific
k1-Setting to be calculated
t-min 0.00
3-70
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
Directional overcurrent function for
• detecting phase faults on ring lines
• detecting phase faults on double-circuit lines with an infeed at one end
• backup protection for a distance protection scheme
B. Features
• Directionally sensitive three-phase phase fault protection
• Insensitive to DC component
• Insensitive to harmonics
• Voltage memory feature for close faults
I. CT/VT inputs:
• Current
• Voltage
IV. Measurements:
• Current amplitude
of the three phase currents (IR, IS, IT)
• Active power
A positive measurement indicates the forwards direction
(IR * UST, IS * UTR, IT * URS)
• Voltage amplitude
Amplitudes of the phase-to-phase voltages
(UST, UTR, URS)
3-71
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Explanation of parameters:
Run On CPU
Defines on which CPU the function should operate.
Trip
defines the tripping channel activated by the function’s tripping
output (matrix tripping logic).
CurrentInp
defines the CT input channel. Only three-phase CTs can be set
and the first channel (R phase) of the group of three selected must
be specified.
VoltageInp
defines the VT input channel. Only three-phase VTs can be set
and the first channel (R phase) of the group of three selected must
be specified.
3-72
RE.216 1KHA000951-UEN ABB Switzerland Ltd
I-Setting
Pick-up setting for tripping.
Setting restrictions:
• > 2.5 IN when supplied from metering cores
• < 0.2 IN when supplied from protection cores
Angle
Characteristic angle.
Delay
Delay between pick-up and tripping.
tWait
Time allowed for the directional decision to be received from the
opposite end in a blocking scheme.
MemDirMode
determines the response of the protection after the time set for
memorizing power direction:
• trip
• block
MemDuration
Time during which the power direction last determined remains
valid.
Receive
Input for the signal from the opposite end of the line:
When not used set it to 'Always TRUE'
Ext Block
Input for blocking the function
Trip Signal
Tripping signal.
Start Signal
Pick-up signal.
Start R
R phase pick-up signal.
Start S
S phase pick-up signal.
Start T
T phase pick-up signal.
MeasFwd
signals measurement in the forwards direction.
MeasBwd
signals measurement in the backwards direction.
3-73
ABB Switzerland Ltd RE.216 1KHA000951-UEN
E. Setting instructions
Settings:
Pick-up current I-Setting
Characteristic angle Angle
Delay Delay
Time allowed for receipt of signal tWait
Response at the end of the
memorized power direction time MemDirMode
Time during which the memorized
direction is valid MemDuration
I-Setting
IN
Delay
3-74
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Where the rated CT current IN1 differs from the rated current IGN of the
protected unit, compensating the measurement to achieve a match is
recommended. This is done by correcting either the reference value of
the A/D input or the setting.
For example, assuming IGN = 800 A and IN1 = 1000 A, the setting to
pick up at 1.5 IGN = 1200 A would be
IGN 800 A
1.5 = 1.5 = 1 .2
IN1 1000 A
Characteristic angle
Determining the phase-angle of the current provides an additional
criterion for preserving discrimination compared with non-directional
overcurrent protection. The directional sensitivity is ±180° in relation to
the reference voltage. This is illustrated in the following diagrams. The
angles given apply for connection according to the connections in
Chapter 12.
y
IR vit
iti
ϕ L ns
ω
. se
UR IR ax
M
UTR URS
UT US
Restraint: α = 45°
cos (ϕ’- α) = neg. ϕ’
U ST U ST
Operation:
cos ( ϕ’- α) = pos.
a) b)
L
HEST 005 001 C
3-75
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Delay
The delay enables the protection to be graded with other time-
overcurrent relays to achieve discrimination. Its setting is thus chosen
in relation to the timer settings of upstream and downstream protective
devices. The zone of protection covered by this overcurrent protection
extends to the next overcurrent protection device.
Should in the event of a fault in the next downstream zone, the
protection for that zone fail, this protection function takes over after the
time set for 'Delay' and clears the fault as backup.
3-76
RE.216 1KHA000951-UEN ABB Switzerland Ltd
I
R Start R
I>
Meas Fwd
Forwards meas. R
U
ST ϕ &
≥1 & t Trip
≥1
Backwards meas. R
ϕ &
Receive
td
I
S Start S
I>
Forwards meas. S
U
TR ϕ &
I
T Start T
I>
Forwards meas. T
U
RS ϕ & Start
≥1
Backwards meas. T
ϕ &
3-77
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-78
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
Directional overcurrent function for
• detecting phase faults on ring lines
• detecting phase faults on double-circuit lines with an infeed at one end
• backup protection for a distance protection scheme
B. Features
• Directionally sensitive three-phase phase fault protection
• Operating characteristics (see Fig. 3.12) according to British
Standard BS142:
c = 0.02: normal inverse
c = 1: very inverse und long time earth fault
c = 2: extremely inverse
• Insensitive to DC component
• Insensitive to harmonics
• Voltage memory feature for close faults
I. CT/VT inputs:
• Current
• Voltage
3-79
ABB Switzerland Ltd RE.216 1KHA000951-UEN
IV. Measurements:
• Current amplitude
of the three phase currents (IR, IS, IT)
• Active power
A positive measurement indicates the forwards direction
(IR * UST, IS * UTR, IT * URS)
• Voltage amplitude
Amplitudes of the phase-to-phase voltages
(UST, UTR, URS)
3-80
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Explanation of parameters:
Run On CPU
Defines on which CPU the function should operate.
Trip
defines the tripping channel activated by the function’s tripping
output (matrix tripping logic).
CurrentInp
defines the CT input channel. Only three-phase CTs can be set
and the first channel (R phase) of the group of three selected must
be specified.
VoltageInp
defines the VT voltage input channel. Only three-phase VTs can be
set and the first channel (R phase) of the group of three selected
must be specified.
3-81
ABB Switzerland Ltd RE.216 1KHA000951-UEN
I-Start
Pick-up current at which the characteristic becomes effective.
Angle
Characteristic angle.
c-Setting
Setting for the exponential factor determining the operating
characteristic according to BS 142.
k1-Setting
Constant determining the parallel shift of the characteristic.
t-min
Definite minimum operating time, operating characteristic constant.
IB-Setting
Base current for taking account of differences of rated current IN.
tWait
Time allowed for the directional decision to be received.
MemDirMode
determines the response of the protection after the time set for
memorizing power direction:
• trip
• block
MemDuration
Time during which the power direction last determined remains
valid.
Receive
Input for the signal from the opposite end of the line:
When not used set it to 'Always TRUE'
Ext Block
Input for blocking the function
Trip Signal
Tripping signal.
Start Signal
Pick-up signal.
Start R
R phase pick-up signal.
Start S
S phase pick-up signal.
Start T
T phase pick-up signal.
MeasFwd
signals measurement in the forwards direction.
MeasBwd
signals measurement in the backwards direction.
3-82
RE.216 1KHA000951-UEN ABB Switzerland Ltd
E. Setting instructions
Settings:
Base current IB-Setting
Characteristic enabling current I-Start
Type of characteristic c-Setting
Multiplier k1-Setting
Characteristic angle Angle
Delay Delay
Time allowed for receipt of signal tWait
Response at the end of the
memorized power direction time MemDirMode
Time during which the memorized
direction is valid MemDuration
Example:
Load current of the protected unit IB1 = 800 A
CT rated current IN1 = 1000 A
IN2 = 5A
Protection rated current IN = 5A
Protection base current
IN2 5A
IB = IB1 = 800 A = 4A
IN1 1000 A
Setting
IB 4 A
= = 0 .8 A
IN 5 A
An alternative is to adjust the position of the IDMT characteristic to
match the rated load of the protected unit and set the base current to
its rated current instead of its load current.
3-83
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Multiplier 'k1-Setting'
The multiplier 'k1-Setting' enables the IDMT characteristic chosen by
the setting of parameter c to be shifted without changing its shape.
This is used for grading the operating times of a series of IDMT relays
along a line to achieve discrimination.
For example, in the case of the 'very inverse' characteristic, the
constant c = 1 and the factor k1 ≤ 13.5. The operating time t is given
by the equation
k1
t=
I
−1
IB
3-84
RE.216 1KHA000951-UEN ABB Switzerland Ltd
t [s] k1 [s]
0.5 2.5
1 5
1.5 7.5
2 10
2.5 12.5
3-85
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Characteristic angle
Determining the phase-angle of the current provides an additional
criterion for preserving discrimination compared with non-directional
overcurrent protection. The directional sensitivity is ±180° in relation to
the reference voltage. This is illustrated in the following diagrams. The
angles given apply for connection according to the connections in
Chapter 12.
y
IR vit
iti
ϕ L ens
ω
.s
UR IR ax
M
UTR URS
UT US
Restraint: α = 45°
cos (ϕ’- α) = neg. ϕ’
U ST U ST
Operation:
cos ( ϕ’- α) = pos.
a) b)
L
HEST 005 001 C
3-86
RE.216 1KHA000951-UEN ABB Switzerland Ltd
calculated for Y-connected VTs (VT type UTS), while the input volt-
ages are used directly for delta-connected VTs (VT type UTD).
Forwards meas. R
U
ST ϕ &
≥1 & t Trip
≥1
Backwards meas. R
ϕ &
Receive
td
I
S Start S
I>
Forwards meas. S
U
TR ϕ &
I
T Start T
I>
Forwards meas. T
U
RS ϕ & Start
≥1
Backwards meas. T
ϕ &
3-87
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-88
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
Phase fault protection of generators with rapidly decaying fault current
such that a normal time overcurrent function could reset before its
delay had expired.
B. Features
• Stores the maximum current value after pick-up
• Resets either after recovery of the system voltage or after tripping
• Processes the positive-sequence component of the voltage
• Insensitive to DC component and harmonics
• Single or three-phase measurement with detection of the highest
phase value in the three-phase mode
I. Analog inputs:
• Current
• Voltage
IV. Measurements:
• Current amplitude
• Positive-sequence voltage
3-89
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Explanation of parameters:
Run On CPU
Defines on which CPU the function should operate.
Trip
defines the tripping channel activated by the tripping output of the
function (tripping logic).
Delay
Time between the function picking up and tripping.
Current
Pick-up current setting.
Setting restrictions:
• > 2.5 IN when supplied from metering cores
Hold-Voltage
Voltage below which the pick-up status latches, even if the current
falls below the pick-up setting.
Hold-Time
defines how long the tripping signal latches when the voltage
condition is fulfilled.
Nr Of Phases
defines whether single or three-phase measurement.
3-90
RE.216 1KHA000951-UEN ABB Switzerland Ltd
3-91
ABB Switzerland Ltd RE.216 1KHA000951-UEN
E. Setting instructions
Settings:
Current pick-up Current
Delay Delay
Undervoltage Hold-Voltage
Reset delay Hold-Time
i
6
5
4
3
2
in
1
t
-1
-2
-3
-4
-5
-6
HEST 905 012 C
3-92
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Maximum short-time
“C urrent" load current
IN
"Delay"
Delay
The delay is used to achieve discrimination of the overcurrent function.
It is set according to the grading table for all the overcurrent units on
the power system. The zone of protection of the voltage-controlled
overcurrent function extends from the CTs supplying it in the generator
star-point to the location of the next downstream overcurrent relay.
3-93
ABB Switzerland Ltd RE.216 1KHA000951-UEN
UN Minimum short-time
load voltage
"Hold-Voltage"
setting for latching
Block diagram
I> ≥1 Start
tV Trip
U< & S
tH ≥1 R
tV = Time delay
tH = Hold-Time
3-94
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Typical settings:
Current 1.5 IN
Delay 3s
Hold-Voltage 0.7 UN
Hold-Time 0.5 s
Should the rated currents of generator and CTs differ appreciably,
compensation of the overcurrent setting is recommended, if this has
not already been done with the aid of the reference value of the A/D
channel.
Example:
Generator rated current IGN = 4 000 A
CT rated current IN1 = 5 000 A
Typical value 1.5
(referred to the rated
current of the protection)
Compensated setting:
IGN 4000
1.5 = 1.5 = 1 .2
IN1 5000
Since the rated voltages of generator and VTs are generally the same,
compensation of the undervoltage setting is seldom necessary.
Should they differ, the compensated setting would be:
UGN
0.7
UN1
3-95
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-96
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
Protection of generators against excessive heating of the rotor due to
asymmetrical load.
B. Features
• Definite time delay
• Insensitive to DC component
• Insensitive to harmonics
• Three-phase measurement
I. Analog inputs:
• Current
IV. Measurements:
• Proportion of negative-sequence current component
I2 = 1/3 (IR + a2 IS + a IT)
3-97
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Explanation of parameters:
Run On CPU
Defines on which CPU the function should operate.
Trip
defines the tripping channel activated by the tripping output of the
function (tripping logic).
Delay
time delay between pick-up and tripping.
I2 - Setting
NPS current setting for tripping.
Setting restriction:
< 0.05 IN when supplied from protection cores
Current Inp. Chan.
defines the A/D current input channel. All three-phase current
inputs may be selected. The first channel (R phase) of the group of
three selected must be specified.
Block Input
Binary address used as blocking input.
Trip Signal
Output for signaling tripping.
Start Signal
Output for signaling pick-up.
3-98
RE.216 1KHA000951-UEN ABB Switzerland Ltd
E. Setting instructions
Settings:
Negative-sequence component of stator current I2 - Setting
Delay Delay
The definite time NPS function is intended for systems where asym-
metries are of longer duration and do not change frequently. This
generally applies in the case of small to medium generators. Two NPS
stages are used, one for alarm and one for tripping.
The maximum continuous NPS current rating I2∞ is stated by the gene-
rator manufacturer, usually as a percentage of the generator rated
current IGN.
I2 - Setting = 15 % IGN
3-99
ABB Switzerland Ltd RE.216 1KHA000951-UEN
I2
Tripping stage
I2
Alarm stage
In cases where both stages are used for tripping, the one with the
higher setting must be faster.
Typical settings:
1st stage (alarm)
I2 - Setting 0.1 IN
Delay 5s
2nd stage (tripping)
I2 - Setting 0.15 IN
Delay 10 s
3-100
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
Negative phase sequence protection especially of large generators
subject to high thermal utilization against excessive heating of the rotor
due to an asymmetric load.
B. Features
• Inverse time delay according to level of NPS (see Fig. 3.19)
• Wide setting ranges for the parameters determining the operating
characteristic
• Adjustable rate of counting backwards when the overload
disappears (cooling rate of thermal image)
• Insensitive to DC components
• Insensitive to harmonics
• Three-phase measurement
I. Analog inputs:
• Current
IV. Measurements:
• Proportion of negative-sequence current component
I2 = 1/3 (IR + a2 IS + a IT)
3-101
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Explanation of parameters:
Run On CPU
Defines on which CPU the function should operate.
Trip
defines the tripping channel activated by the tripping output of the
function (tripping logic).
K1 - Setting
Multiplier. Operating characteristic constant.
K2 - Setting
Continuously permissible NPS (I2/IB) and operating characteristic
constant.
Setting restrictions:
< 0.05 IN/IB when supplied from protection cores.
Min. Operating Time
Definite minimum operating time.
Max. Delay Time
Maximum delay after being enabled regardless of inverse
characteristic.
Reset Time
Time taken to reset (from the operating limit). This corresponds to
the time taken for the generator to cool.
3-102
RE.216 1KHA000951-UEN ABB Switzerland Ltd
3-103
ABB Switzerland Ltd RE.216 1KHA000951-UEN
E. Setting instructions
Settings:
Reference current IB - Setting
Multiplier K1 - Setting
Continuously permissible NPS K2 - Setting
Minimum operating time Min. Operating Time
Maximum operating time Max. Delay Time
Resetting time Reset Time
The setting is the ratio IB/IN, where IN is the rated current of the pro-
tection, otherwise 'IB-Setting' would be 1.0 IN.
The following two parameters are required from the manufacturer of
the generator in order to set k1 and k2:
• the continuously permissible NPS component i2∞ [p.u.]
k1 = i22 t
Typical settings:
IB - Setting to be calculated
K1 - Setting 10.0 s
K2 - Setting to be defined
Min. Operating Time 10.0 s
Max. Delay Time 1000.0 s
Reset Time 10.0 s
3-104
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
Standard voltage applications (overvoltage and undervoltage function).
The function is also utilized for:
• Stator earth fault protection (95 %)
• Rotor Stator earth fault protection (with YWX 111)
• Interturn protection
• Network earth fault protection.
B. Features
• DC component filter
• Harmonic filter
• Single or three-phase voltage measurement
• Maximum value, respectively minimum value, detection for three-
phase measurement
I. Analog inputs:
• Voltage
IV. Measurements:
• Voltage amplitude
3-105
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Explanation of parameters:
Run On CPU
Defines on which CPU the function should operate.
Trip
Tripping circuit to which the O/P of the over/undervoltage function
is connected (matrix tripping logic).
Delay
Time delay between the function picking up and tripping.
V-Setting
Voltage setting for tripping.
Max / Min
Over or undervoltage mode selection:
• Min (1ph): Undervoltage.
Three-phase functions detect the lowest
phase voltage.
• Max (1ph): Overvoltage.
Three-phase functions detect the highest
phase voltage.
Number Of Phases
Number of phases included in the measurement.
Voltage Inp. Chan
Analog I/P channel.
All the voltage channels are available for selection.
For three-phase measurement, the first channel (R phase) of the
group of three must be selected.
3-106
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Block Input
I/P for blocking the function.
Trip Signal
Tripping signal.
Start Signal
Pick-up signal.
3-107
ABB Switzerland Ltd RE.216 1KHA000951-UEN
E. Setting instructions
Settings:
Setting V - Setting
Delay Delay
Over or undervoltage Max / Min
Number of phases measured Number Of Phases
The overvoltage protection protects the stator coils of the generator as
well s transformers from dangerous overvoltages. Simultaneously the
magnetic core is protected from overheating resulting from increased
iron losses. Long duration overvoltage are especially to be expected
on the failure of the voltage regulators. A definite delay prevents
spurious tripping by transient conditions. Often the protection is
executed in two steps, which affects the tripping.
U
V - setting
Stage 2
V - setting
Stage 1
UN
Delay Delay
0 t
HEST 905 055 C
3-108
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Typical settings:
1st stage
V - setting 1.15 UN
Delay 2s
Max / Min Max(1Ph)
2nd stage
V - setting 1.4 UN
Delay 0.1 s
Max / Min Max(1Ph)
3-109
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Settings:
Voltage V - Setting
Delay Delay
The definite time stator E/F scheme (95 %) is designed for the pro-
tection of generators or generator/transformer units.
Description
The standard zone of protection in the case of generator/transformer
units is 95 % of the length of the stator winding (see Fig. 3.21). It is
normal to limit the zone to 95 % to avoid any risk of false tripping. The
stator E/F function is connected either to the VT at the stator star-point
or to the VTs at the generator terminals. In either case, the function
monitors the displacement of the star-point caused by a stator E/F.
The corresponding off-set voltage becomes a maximum for an E/F at a
generator terminal and zero for an E/F at the star-point (see Fig. 3.21).
A
U
Generator
5%
U
95 ma
% x
3-110
RE.216 1KHA000951-UEN ABB Switzerland Ltd
As can be seen from Fig. 3.21, the relay setting for a zone of protec-
tion of 95 % is 5 % of Umax. The scheme detects E/Fs on the gene-
rator stator winding, the cables to the step-up transformer and the
delta-connected windings of the step-up transformer.
The capacitances between primary and secondary of the step-up
transformer conduct currents emanating from E/Fs on the HV side to
the LV side and can cause false tripping of the stator E/F protection.
The capacitive coupling of E/F currents on the HV side takes place
regardless of whether the HV star-point is grounded or not. The capa-
citance C12 between HV and LV windings of the step-up transformer and
the capacitance C of the generator circuit form a potential divider that
determines the potential of the generator star-point (see Fig. 3.22a).
The value of the capacitance C is usually too low to reliably hold the
star-point below the pick-up setting of the protection. For this reason,
the generator star-point is grounded via a resistor RE (see Fig. 3.23)
which ensures that the potential of the star-point remains below the
setting of the protection for an E/F on the HV power system.
Correspondingly, the value of the resistor RE is chosen such that for a
given C12 and an E/F at the HV terminals of the step-up transformer,
the offset of the generator star-point does not reach the pick-up setting
of the 95 % E/F protection.
3 C 12 3 C 12
U HV U HV
Star-point 3 3
U RE U
3C
IE IE
3-111
ABB Switzerland Ltd RE.216 1KHA000951-UEN
where:
C12 capacitance between primary and secondary of the step-up
transformer
C capacitance to ground of the stator windings, the cables
with protection capacitors and the LV step-up transformer
winding
U star-point offset
UHV rated voltage of the step-up transformer HV windings
IE E/F current
RE grounding resistor
The value of the grounding resistor RE determines the E/F current. In
view of the damage an E/F current can cause — especially to the
laminations of the stator core — the maximum E/F current should be
limited to 20 A for 10 s, i.e. the grounding resistor RE must not be too
small.
Tripping by the E/F protection is delayed by 0.5 s to avoid any risk of
false tripping during transient phenomena.
U GN U HV
IE
3 C 12
I Emax
IE
U1n /U 2n
3C RE U>
IE
3-112
RE.216 1KHA000951-UEN ABB Switzerland Ltd
where IEmax ≤ 20 A
The equation for determining the maximum value of the grounding
resistor REmax (95 % scheme) can be derived from the simplified
circuit diagram of Fig. 3.22b:
0.05 UGN
RE max ≤
6 ω C12 UOS
where:
0.05 - protection sensitivity 5 % (95 % scheme)
6 - factor corresponding to 3 phases times 2 for half the pick-
up setting
The value of the effective grounding resistor RE is chosen between
REmax and REmin and rated for 10 s.
Example 1
UGN = 12 kV; UHV = 110 kV; C12 = 3 x 10-9 F; ω = 314 1/s
IEmax ≤ 20 A
a) HV system ungrounded
12000
RE min ≥ = 346 Ω
3 × 20
0.05 × 12
RE max ≤ = 965 Ω
6 × 314 × 3 × 10 −9 × 110
3-113
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Chosen RE = 750 Ω
UGN 12000
IE max = = = 9.24 A
3 RE 3 × 750
Specification:
1 grounding resistor 750 Ω; 10 A; 10 s
12000
1 VT / 100 V; single-phase insulation
3
Specification:
1 grounding resistor 3000 Ω; 2.3 A; 10 s
12000
1 VT / 100 V; single-phase insulation
3
3-114
RE.216 1KHA000951-UEN ABB Switzerland Ltd
U1n
where Ie = IE max
U2n
UGN
or for U1n =
3
2
U2n
Re =
U1n IE max
Rated power of the grounding transformer:
Sn = U1n I1n
U GN U HV
IE
3 C 12
I
Em
ax
IE
U 1n /U 2n U3n /U 4n
3C Re U>
IE Ie
3-115
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Example 2
UGN = 12 kV; IC = 10 A
IEmax = IC = 10 A
12000
U1n = = 6930 V
3
I1n = 10 A
U2n = 200 V
6930
I2n = Ie = 10 = 346 A
200
200 2
Re = = 0.577 Ω
6930 × 10
Sn = U1n I1n = 6930 × 10 ⇒ 70 kVA
Specification:
1 grounding transformer 70 kVA; 10 s; 50 Hz
6930/200 V; 10/346 A
1 resistor 0.577 Ω; 346 A; 10 s
1 interposing VT 10 VA; 50 Hz; 200/100 V
(only necessary if U2n > 100 V)
Example 3
UGN = 12 kV; IC = 10 A; grounding transformer specified according to
the rated voltage of the generator.
U1n = UGN = 12 kV
U2n = 230 V
I1n = IEmax = IC = 10 A
U1n 12000
I2n = Ie = IEmax = 10 = 522 A
U2n 230
2
12000 ⎛ 230 ⎞
Re = ⎜ ⎟ = 0.254 Ω
3 × 10 ⎝ 12000 ⎠
Sn = 12000 × 10 ⇒ 120 kVA
Specification:
1 grounding transformer 120 kVA; 10 s; 50 Hz
12000/230 V; 10/522 A
1 resistor 0.254 Ω; 522 A; 10 s
1 interposing VT 10 VA; 50 Hz; 230/100 V
3-116
RE.216 1KHA000951-UEN ABB Switzerland Ltd
IE
U GN U HV
3 C 12
I1 I1 I1
IE = 3 I 1
I
E
U 1n /U 2n U 3n /U 4n
3C Ie Re Ie U>
3-117
ABB Switzerland Ltd RE.216 1KHA000951-UEN
and the voltage across the broken delta windings 3U2n. This voltage
must be approximately 30 % higher than the voltage Re Ie across the
resistor so that the design current IE can flow.
Example 4
UGN = 12 kV; UHV = 110 kV; C12 = 3 x 10-9 F; ω = 314 1/s
HV system ungrounded.
IEmax = 15 A
UGN 12000
U1n = = = 6930 V
3 3
2
12000 ⎛ 3U2n ⎞ −4 2
R e min ≥ ⎜ ⎟ × 0.7 = 0.60 × 10 × U2n
3 × 15 ⎝ 6930 ⎠
2
0.05 × 12 ⎛ 3U2n ⎞ −4 2
R e max ≤ ⎜ ⎟ = 1.81 × 10 × U2n
−9
6 × 314 × 3 × 10 × 110 ⎝ 6930 ⎠
Since from this calculation Remax is greater than Remin, the protection
is stable at the chosen current IEmax and the value of the resistor Re
can be determined in relation to Remin.
Ie = 200 A
15
U2n = 6930 = 173 V
3 × 200
3-118
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Neglecting load current, the maximum voltage across the broken delta
windings is:
U = 3 U2n = 3 × 173 ≈ 520 V
Specification:
1 resistor 1.80 Ω; 200 A; 10 s
12000
3 VTs / 173 V; single-phase insulated
3
1 interposing VT 10 VA; 50 Hz; 520 / 100 V
Note:
Because of the voltage drop of the VTs, the voltage does not reach
520 V at the full E/F current, but only 360 V. The setting of the pro-
tection must therefore be modified as follows:
Overvoltage setting
360
0.05 = 0.034 (3.4 % UN instead of 5 % UN)
520
Example 5
UGN = 27 kV; UHV = 400 kV; C12 = 3 x 10-9 F; x = 314 1/s
HV system solidly grounded
IE = 15 A
UGN 27000
U1n = = = 15600 V
3 3
2
27000 ⎛ 3U2n ⎞ −6 2
R e min ≥ ⎜ ⎟ = 27 × 10 × U2n
3 × 15 ⎝ 15600 ⎠
2
0.05 × 27 ⎛ 3 U2n ⎞ −6
Re max ≤ ⎜ ⎟ = 132 × 10 × U2n2
−9 400 ⎝ 15600⎠
6 × 314 × 3 × 10 ×
6
Ie = 250 A (chosen)
15
U2n = 15600 = 260 V
3 × 300
3-119
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Typical settings:
V-Setting 0.05 UN
Delay 0.5 s
Note:
If a generator circuit-breaker is installed between the generator and
the step-up transformer, a second E/F protection scheme is required
for the zone between the step-up transformer and the unit transformer.
The second scheme is connected to the broken delta secondary
windings of three VTs. This scheme must also remain stable for E/Fs
on the HV system and during ferroresonance phenomena and for this
reason there is a resistor across the broken delta as well. Frequently,
the E/F protection is only required to protect the cables and bar
conductors, because the transformers are protected by differential
schemes and Buchholz relays. In this case, the E/F protection setting
is determined by the voltage offset for an E/F at the lowest load
voltage. A typical setting for reliable E/F detection in an ungrounded
system is 60 % UN, i.e.
V - setting = 0.6 UN
The delay can remain the same at 0.5 s. The second E/F scheme
usually gives only an alarm. Since the plant remains in operation for an
E/F on the cables, the resistor across the broken delta must be
continuously rated.
3.5.11.2. Rotor E/F protection
Settings:
Overvoltage V - Setting
Delay Delay
Over/undervoltage Max / Min
The rotor E/F function in conjunction with the ancillary unit Type
YWX 111 and 2 coupling capacitors is suitable for protecting synchro-
nous generators regardless of the method of excitation. The scheme
operates according to the Wheatstone bridge principle and is
uninfluenced by frequency. The harmonics of the excitation system do
not therefore effect the rotor E/F protection.
3-120
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Typical settings:
V - Setting (for 1 kΩ) 1 to 3 V
Delay 1s
Max / Min Max
3-121
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Settings:
Overvoltage V - Setting
Delay Delay
Typical settings:
V - Setting 0.05 UN
Delay 0.5 s
R S T
Voltage transformer
Generator
U>
3-122
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
• General voltage monitoring with instantaneous response (over and
undervoltage)
• Voltage monitoring where insensitive to frequency is required (over
and undervoltage)
B. Features
• Processes instantaneous values and is therefore fast and largely
independent of frequency
• Stores the peak value following pick-up
• No suppression of DC component
• No suppression of harmonics
• Single and three-phase measurement
• Maximum value detection in the three-phase mode
• Adjustable lower frequency limit fmin
I. CT/VT inputs:
• Voltage
IV. Measurements:
• Voltage amplitude (only available if function trips)
3-123
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Explanation of parameters:
Run On CPU
Defines on which CPU the function should operate.
Trip
defines the tripping channel activated by the tripping O/P of the
function (matrix).
Delay
Time between the function picking up and tripping.
V- Setting
Pick-up voltage setting.
Min. Frequency
defines the minimum frequency for which measurement is
required.
Max / Min
defines operation as overvoltage or undervoltage. Settings:
• Max: overvoltage
• Min: undervoltage
Number Of Phases
defines whether single or three-phase measurement.
Voltage Inp. Chan.
defines the VT input channel.
All voltage inputs may be selected.
In the case of three-phase measurement, the first channel
(R phase) of the group of three selected must be specified.
3-124
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Block Input
Binary address used as blocking input.
Trip Signal
Output for signaling tripping.
Start Signal
Output for signaling pick-up.
3-125
ABB Switzerland Ltd RE.216 1KHA000951-UEN
E. Setting instructions
Settings:
Overvoltage V- Setting
Delay Delay
Minimum frequency Min. Frequency
Over or undervoltage Max / Min
The instantaneous overvoltage function is a high-speed protection,
which operates in a wide frequency range. It is intended primarily for
the following applications:
• where an overvoltage protection is required, which is largely
insensitive to frequency especially for f > fN.
The limited capacity of the VTs to transform low frequencies must
be taken into account for f < fN:
f
2.25 UN ×
fN
• where high-speed protection is required. The high speed is
achieved by measuring the instantaneous value of the voltage and
since DC components and harmonics are not suppressed, by
eliminating the inertia of the digital input filter.
Compared with the normal voltage function, the instantaneous function
has a larger tolerance on the pick-up setting. It should therefore only
be used in the above two cases.
The measuring principle is the same as that of the peak value current
function (see Section 3.5.4) and therefore reference should be made
to that Section for a description of the principle and the significance of
the minimum frequency setting f-min.
Typical settings:
V- Setting according to application
Delay according to application
Min. Frequency 40 Hz
3-126
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
Monitoring/comparison of two groups of single or three-phase voltage
inputs to detect voltage measurement errors.
B. Features
• Comparison of the amplitudes of two groups of voltage inputs
(e.g. line 1 and line 2)
• Single or three-phase voltage measurement
• Indication of group with the lower voltage
• Evaluation of voltage balance per phase in the three-phase mode
with selection by OR gate for tripping
• Adjustable delays for operation and reset
• Insensitive to DC components
• Insensitive to harmonics
I. Analog inputs:
• Voltage (2 sets of 1 or 3 inputs)
IV. Measurements:
Single-phase mode
• Difference between voltage amplitudes (U1 - U2)
Three-phase mode
• Voltage amplitude difference for R phase (U1R - U2R)
• Voltage amplitude difference for S phase (U1S - U2S)
• Voltage amplitude difference for T phase (U1T - U2T)
3-127
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Explanation of parameters:
Run On CPU
Defines on which CPU the function should operate.
Trip
defines the tripping channel activated by the tripping output of the
function (tripping logic).
V - Unbalance
Voltage difference setting for tripping.
Difference between the amplitudes of the two voltage input
channels which results in tripping. The setting applies to all three
phases in the three-phase mode.
Delay
time delay between pick-up and tripping.
t-Reset
Time required for the measurement to reset after the tripping
condition has disappeared (reset ratio: 0.90).
Number Of Phases
defines whether single or three-phase measurement.
Voltage Input Line1
defines the 1st analog voltage input channel U1 (line 1).
In the case of three-phase measurement, the first channel
(R phase) of the group of three selected must be specified.
3-128
RE.216 1KHA000951-UEN ABB Switzerland Ltd
U 2R
U1R:
1 x UN
R phase voltage amplitude of
Operates
Line 1 voltage channel 1 (line 1)
(U 1 < U 2 )
0,8 U2R:
Restrains R phase voltage amplitude of
voltage channel 2 (line 2)
3-129
ABB Switzerland Ltd RE.216 1KHA000951-UEN
E. Setting instructions
Settings:
Max. voltage difference V - Unbalance
Delay Delay
Reset delay t-Reset
3-130
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Notes:
• Only the voltages of similar sources that have coincident
amplitudes and phase-angles and are connected to the same
busbar should be compared.
• Wherever possible the voltages should be processed by
neighboring sampling groups and by the same input unit. The
purpose of this is to limit signal conditioning errors should the
power system frequency deviate from the rated frequency fN and
during transients.
• To prevent false tripping during extreme variations of frequency,
either the pick-up setting can be increased or the balanced voltage
function can be blocked by a frequency function.
• Differing primary rated voltages of the VTs can be compensated by
appropriately setting the reference values of the corresponding A/D
channels. The adjusted reference values then apply for all the
protection functions connected to the same channels.
Application example:
R S T V.t. 1
Line 1
U 1R
Protection/
U 1S instrumentation
U 1T equipment
1
Voltage input
channel (U1 )
Blocking
input
TRIP-Line 1
Voltage comparsion
Blocking
function TRIP
input
(three-phase)
TRIP-Line 2
Voltage input
Blocking
channel (U2 )
input
V.t. 2
U 2R
Protection/
U 2S instrumentation
U 2T equipment
2
Line 2
3-131
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Typical settings:
Max. voltage difference (V - Unbalance) 0.20 UN
Delay 0.04 s
Reset time (t-Reset) 0.50 s
3-132
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
Back-up phase fault protection for the generator feeder.
B. Features
• Circular operating characteristic (see Fig. 3.30)
• Adjustable time delay
• Insensitive to DC component in voltage and current
• Insensitive to harmonics in voltage and current
• Single or three-phase measurement
• Detection of the lowest impedance in the three-phase mode
• Underimpedance measurement enabled by undercurrent unit (0.1 IN)
I. Analog inputs:
• Current
• Voltage
IV. Measurements:
• Impedance (value)
3-133
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Explanation of parameters:
Run On CPU
Defines on which CPU the function should operate.
Trip
defines the tripping channel activated by the tripping output of the
function (tripping logic).
Delay
Time between the function picking up and tripping.
Z Setting
Pick-up impedance setting.
Number Of Phases
defines whether single or three-phase measurement.
Current Inp. Chan.
defines the analog current input channel. All current inputs may be
selected. For three-phase measurement, the first channel
(R phase) of the group of three selected must be specified.
Voltage Inp. Chan.
defines the analog voltage input channel. All voltage inputs may be
selected. For three-phase measurement, the first channel (e.g. the
phase-to-phase voltage R-S) of the group of three selected must
be specified.
Block Input
Binary address used as blocking input.
Signaling Trip
Output for signaling tripping.
Start Out
Output for signaling pick-up.
3-134
RE.216 1KHA000951-UEN ABB Switzerland Ltd
3-135
ABB Switzerland Ltd RE.216 1KHA000951-UEN
E. Setting instructions
Settings:
Impedance Z Setting
Delay Delay
3-136
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Step-up transformer
GT
Protection zone
I>
Z<
3-137
ABB Switzerland Ltd RE.216 1KHA000951-UEN
or
UTN IN1 UN2 I
Z-Setting = 0.7 xT × × × N [1; 1; V; A]
ITN IN2 UN1 UN
where:
z1 impedance of the protected zone
xT short-circuit reactance of the step-up transformer
Ki, Ku ratios of CTs and VTs
IN1, IN2 CT rated currents
UN1, UN2 VT rated voltages
UTN, ITN rated voltage and current of the step-up transformer
UN, IN rated voltage and current of the underimpedance
function
The factor of 0.7 avoids any risk of false tripping for a fault on the HV
system at the cost of a zone of protection that is shorter than differen-
tial protection zone.
Example:
Transformer: 500 MVA; 24 kV; 12 kA; xT = 0.1
Protection: 100 V; 5A
I 12000
K i = N1 = = 2400
I N2 5
U N1 24000
Ku = = = 240
U N2 100
3-138
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Settings:
UTN K i I
Z Setting = 0.7 x T × × N
ITN K u UN
24 2400 5
Z Setting = 0.7 × 0.1 × × = 0.07
12 240 100
Typical settings:
Z Setting 0.07
Delay 0.5 s
x
+0.07
0 r
Z-Setting
-0.07
HEST 935 003 C
3-139
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-140
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
• Detection of inadmissible operating conditions due to under-
excitation of a synchronous generator.
B. Features
• Circular operating characteristic (see Fig. 3.33)
• Selectable to operate inside or outside the circle
• Adjustable size and position of the operating characteristic
• Correction of phase errors caused by input circuit
• Adjustable time delay
• Insensitive to DC component in voltage and current
• Insensitive to harmonics in voltage and current
• Single or three-phase measurement
• Detection of the lowest impedance (distance from the centre of the
circle)
• Underreactance measurement enabled by undercurrent unit (0.1 IN)
I. Analog inputs:
• Current
• Voltage
IV. Measurements:
• Impedance (distance from the centre of the circle)
3-141
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Explanation of parameters:
Run On CPU
Defines on which CPU the function should operate.
Trip
defines the tripping channel activated by the tripping output of the
function (tripping logic).
Delay
Time between the function picking up and tripping.
XA-Setting
defines the first intersection of the impedance circle with the
reactance axis (assuming a phase correction setting of 0°).
Setting restriction: |XA| < |XB|.
XB-Setting
defines the second intersection of the impedance circle with the
reactance axis (assuming a phase correction setting of 0°).
Angle
For compensating phase errors of the analog input signals.
The setting can also be used to move the position of the im-
pedance circle.
Max / Min
defines whether over or underreactance function. Settings:
• Min: underreactance function with tripping inside the circle
• Max: overreactance function with tripping outside the circle
3-142
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Number Of Phases
defines whether single or three-phase measurement.
Current Inp. Chan.
defines the A/D input channel.
All current inputs may be selected.
For three-phase measurement, the first channel (R phase) of the
group of three selected must be specified.
Voltage Inp. Chan.
defines the A/D input channel.
All voltage inputs may be selected.
For three-phase measurement, the first channel (e.g. the phase-to-
phase voltage R-S) of the group of three selected must be
specified.
The VT should be from the same input card 216EA61 as the CT.
Block Input
Binary address used as blocking input.
Signaling Trip
Output for signaling tripping.
Start Out
Output for signaling pick-up.
3-143
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-144
RE.216 1KHA000951-UEN ABB Switzerland Ltd
E. Setting instructions
Settings:
Reactance XA XA-Setting
Reactance XB XB-Setting
Phase correction Angle
Delay Delay
3-145
ABB Switzerland Ltd RE.216 1KHA000951-UEN
e
ϕ - phase-angle
δ - load angle
u ϕ < u, I
δ < u, e
i
δ ϕ
xq i
xd i
δ ϕ
3-146
RE.216 1KHA000951-UEN ABB Switzerland Ltd
x ' U K
XB = d GN × i 3
2 3IGN K u
UN1
I
K u = 3 = N1
UN2 IN2
3
where:
xd, xd' unsaturated synchronous reactance and saturated
transient reactance of the generator in p.u.
xq synchronous reactance in p.u.
UGN, IGN rated generator voltage and current
Ki CT ratio
Ku VT ratio
UN1, UN2 VT rated voltages
IN1, IN2 CT rated currents
3-147
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Example:
Turboalternator 100 MVA; 24 kV; 12 kA
xd = 2.0; xd' = 0.25
U N1
3 24000
VTs Ku = = = 240
U N2 100
3
12000
CTs Ki = = 12000
1
U GN Ki 24000 12000
XA = xd × × 3 = 2.0 × 3 = 200.0 Ω
3 I GN Ku 3 × 12000 240
XA 200
XA − Wert = IN = − × 1 = − 2 .0
UN 100
XB 12.5
XB − Wert = IN = − × 1 = − 0.125 = 0.12
UN 100
3-148
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Phase correction
The scheme can include one to three independent measuring sys-
tems, each of which is connected to a phase-to-phase voltage and a
phase current. For example, there are three possible reference volt-
ages for the R phase measuring system, i.e. URS, UST and UTR.
Since, however, all the measuring systems need the angle of their own
phase, i.e. for R phase the angle of the voltage UR, the angle of the
voltage signal has to be corrected in any event.
Phase compensation
Reference voltage Vector diagram "Angle"
R U RS
RS +30°
T S
R
*)
ST -90°
T S
U ST
U TR R
*)
TR +150°
T S
HEST 905023 C
3-149
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Typical settings:
XA-Setting to be calculated
e.g. -2.0
XB-Setting to be calculated
e.g. -0.12
Phase-angle (delta-connected VTs) +30°
(star-connected VTs) 0°
Tripping delay timer:
Delay 2s
or separate integrator ('Delay' function):
Trip-Delay 6s
Reset-Delay 3s
Step-up
transformer
E
US
xd xT
Steady-state stability
x limit curve
xT
0
x' d r
XB-Setting
2
xd
Characteristic of the
underexcitation function XA-Setting
XA set
settings [UN / IN ]
XB set
HEST 905 021 C
3-150
RE.216 1KHA000951-UEN ABB Switzerland Ltd
tR tR tR tR
Pick-up
0
"TRIP-Delay" setting
t int
Integration
0
Trip
0
3-151
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Example:
xd = 2; Xd' = 0,2
1
z ≤ (2 − 0.1) = 0.95
2
x
U
I
z
r
X d' 0
xd
3-152
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
Power function for monitoring
• reverse power
• active power
• reactive power
• power direction
B. Features
• Definite time delay
• Over or underpower
• Adjustable characteristic angle
• Provision for correction of phase errors caused by the input circuit
• One, two or three-phase measurement (two-phase only with delta
connected VTs)
• Wide range of applications (see Fig. 3.39 and Fig. 3.40)
• Correction of CT and VT phase errors
• Insensitive to DC components in voltage and current
• Insensitive to harmonics in voltage and current
I. CT/VT inputs:
• Current
• Voltage
IV. Measurements:
• Power
3-153
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Explanation of parameters:
Run On CPU
Defines on which CPU the function should operate.
Trip
channel of the tripping logic (matrix) activated by the function’s
tripping O/P.
P - Setting
Power setting for tripping.
Forbidden settings:
• < 0.005 PN connected to metering cores
• < 0.020 PN connected to protection cores
• in addition n x 0,005 PN with different sampling circuits in the
A/D converters of the CT / VT inputs
(possible errors for f ≠ fN; n = 1...3 according to the offset of the
sampling groups).
3-154
RE.216 1KHA000951-UEN ABB Switzerland Ltd
3-155
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Delay
Time between the function picking up and tripping. The time the
function takes to reset is also influenced by the delay set for
operation, i.e.:
for t > 100 ms, the function resets after 50 ms, otherwise resetting
is instantaneous.
Max / Min
Defines the operating mode as:
• Max: overpower
• Min: underpower
Warning:
The number and its sign are relevant and not just the value, i.e.
'Min' must be set for reverse power, because tripping takes place
for a power less than zero (P Setting < 0).
Phi Compensation
Input of an angle to compensate CT and VT errors in the case of
highly accurate power measurements.
The setting is determined by the difference between CT and VT
errors.
Number Of Phases
Number of phases measured:
• 1: single-phase
• 2: two-phase, i.e. for a three-phase measurement with V
connected VTs
P = URS × IR × cos ϕ − UST × IT × cos ϕ
A two-phase power measurement is only possible when
connected to delta connected VTs.
• 3: three-phase
P = UR × IR × cos ϕ + US × IS × cos ϕ + UT × IT × cos ϕ
(for star connected VTs)
P = URS × IR × cos ϕ + UST × IS × cos ϕ + UTR × IT × cos ϕ
(for delta connected VTs),
the measurement is only correct with delta connected VTs if the
three phase voltages are symmetrical.)
Current Inp. Chan.
defines the CT input channel.
All current I/Ps may be selected.
In the case of multi-phase measurement, the first channel of the
group of three (R phase) must be selected.
Voltage Inp. Chan.
defines the VT input channel.
All voltage I/Ps may be selected.
In the case of multi-phase measurement, the first channel of the
group of three (R phase) must be selected.
The VT channel must be sampled by the same device 216EA61 as
the CT channel.
3-156
RE.216 1KHA000951-UEN ABB Switzerland Ltd
PN
Rated power as given by UN x IN. This enables the amplitude of
the power being measured to be compensated, e.g. to the rated
power factor of a generator.
Block Input
I/P for blocking the function.
Trip Signal
Tripping signal.
Start Signal
Pick-up signal.
1
Reset ratio 95%
Reset ratio
60%
0.5
3-157
ABB Switzerland Ltd RE.216 1KHA000951-UEN
E. Setting instructions
(function with two additional timers)
Settings:
Reference power PN
Setting P - Setting
Reset ratio Drop Ratio
Over/underpower Max / Min
Characteristic angle Angle
Phase error compensation Phi Compensation
tripping delay Delay
The power function can be used for many applications. Some
examples are given in Fig. 3.39 and Fig. 3.40. The angles given apply
for connection according to the connections in Fig. 12.4.
Q Q
0 P 0 P
3-158
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Q Q
Operates Restrains Operates
Restrains
0 P 0 P
Q
Restrains
0 60°
P
Operates
- P-Setting <0
- Max/Min MIN
- Drop-Ratio <100%
- Angle 60° (90° ) *)
HEST 965 018 C
3-159
ABB Switzerland Ltd RE.216 1KHA000951-UEN
where:
SGN, PGN, UGN, IGN, cos ϕGN: ratings of the protected unit
UN1, IN1: primary VT and CT ratings
PN, UN, IN: protection ratings
Example 1
Generator: 96 MVA, 13.8 kV, 4 kA, cosϕ = 0.8
14.4 100
VTs / CTs: kV / V; 5 kA / 5 A
3 3
Protection: 100 V; 5 A
Reverse power: 0.5 % PGN
Alternative 1: No modification of PN
Settings:
PN
Reference power = 1 .0
UN × IN
Reverse power:
P U ×I 13.8 × 4
= 0.005 GN GN cos ϕGN = 0.005 0.8 = 0.003
PN UN1 × IN1 14.4 × 5
3-160
RE.216 1KHA000951-UEN ABB Switzerland Ltd
P
xReverse power = 0.005
PN
Characteristic angle
The power function is connected to the phase currents and a phase-to-
neutral or phase-to-phase voltage. The purpose of the phase compen-
sation is twofold:
• to compensate the phase difference between the phase voltage
and the any measured phase-to-phase voltage
• to determine whether the function responds to active or reactive
power
The following table summarizes the most important operating modes
to simplify setting the corresponding parameters correctly. The
angles given apply for connection according to the connections in
Chapter 12.
The phase compensation also provides facility for changing the direc-
tion of measurement or to compensate incorrect VT or CT polarity.
3-161
Function "MaxMin" "Drop-Ratio" "P-Setting" "Angle" *)
P
U RS
3-162
max MAX < 100%
0
Fig. 3.41
Active power IR >0 +30°
P
min MIN > 100%
0
P
U RS 0
URS
ABB Switzerland Ltd
Phase compensation
Reverse power <0 +30°
P
IR 0
min MAX > 100%
*) Applicable for a single or three-phase measurement using phase-to-phase voltages (the setting is 30° HEST 965 019 C
This setting is for correcting the phase error between the VTs and
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Example 2
The active power error at rated current and a power factor of cosϕ = 0
for a total phase error δ of 10' is
∆P = 0.03 × δ = 0.03 × 10 = 0.3 % [%; 1; min]
This is an error which is not negligible at a setting of 0.5 %.
The total error corresponds to the difference between the VT and CT
errors. The case considered in this example of full reactive current
(100%) would scarcely occur in practice, but currents from about 80%
are possible.
3-163
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Block
t 1> Trip
U
P>
I Trip Trip
t 2>
Start
t 3>
Integrator
Typical settings:
PN determined by the generator cosϕGN
P - Setting (steam turbines of medium power) - 0.005
Max / Min Min
Drop Ratio 60 %
Angle connection to IR and UR 0°
connection to IR and URS +30°
connection to IR and UST -90°
connection to IR and UTR +150°
Phi Compensation 0.0
Stage 1:
Delay 0.5 s
Stage 2:
Delay 20 s
or
Integrator ('Delay' function) for delay on operation and reset
Trip time 20 s
Reset time 3s
Integration 1
3-164
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Note:
The following must be set for a 'Minimum forward power' scheme
according to Anglo-Saxon practice:
P - Setting >0
Max / Min Min
Drop Ratio 150 %
3-165
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-166
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
Overload protection for the stators of large generators.
B. Features
• Delay inversely proportional to overload (see Fig. 3.43)
• Operating characteristic according to ASA-C50.13 (American
Standard Requirements for Cylindrical-Rotor Synchronous
Generators) with extended setting range
• Adjustable rate of counting backwards when the overload
disappears (cooling rate of thermal image)
• Insensitive to DC components
• Insensitive to harmonics
• Single or three-phase measurement
• Detection of highest phase in the three-phase mode
I. Analog inputs:
• Current
IV. Measurements:
• Current amplitude
3-167
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Explanation of parameters:
Run On CPU
Defines on which CPU the function should operate.
Trip
defines the tripping channel activated by the tripping output of the
function (tripping logic).
K1 Setting
Multiplier. Operating characteristic constant.
I - Start
Enabling current for operating characteristic.
t - min
Minimum operating time. Operating characteristic constant.
tg
Time during which the inverse characteristic is active. Operating
characteristic constant.
This must not exceed the maximum delay time.
3-168
RE.216 1KHA000951-UEN ABB Switzerland Ltd
t - max
Maximum delay after being enabled regardless of inverse
characteristic. Operating characteristic constant.
t - Reset
Time taken to reset (from the operating limit). This corresponds to
the time taken by the generator to cool.
Number Of Phases
defines whether single or three-phase measurement.
Current Input Channel
defines the analog current input channel.
All current inputs may be selected. In the case of three-phase
measurement, the first channel of the group of three selected must
be specified.
IB - Setting
Reference (base) current for compensating a difference in relation
to IN.
Block Input
Binary address used as blocking input.
Trip Signal
Output for signaling tripping.
Start Signal
Output for signaling pick-up.
3-169
ABB Switzerland Ltd RE.216 1KHA000951-UEN
E. Setting instructions
Settings:
Reference current IB - Setting
Enabling current I - Start
Multiplier K1 Setting
Minimum operating time t - min
Time inverse characteristic effective tg
Maximum delay t - max
Resetting time t - Reset
where:
τ : thermal time constant of the stator
∆ϑm : maximum permissible temperature rise of the stator winding
∆ϑn : rated temperature rise of the stator winding
3-170
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Example:
τ = 5 min or 300 s
∆ϑm = 70 K
∆ϑn = 60 K
70−60
k1 = 300 = 50 s
60
Typical settings:
IB-Setting to be calculated
I-Start 1.1 IB
K1 - Setting 41.4 s
t - min 10.0 s
tg 120.0 s
t - max 300.0 s
t - Reset 120.0 s
3-171
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-172
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
Overload protection for the rotors of large generators.
B. Features
• Delay inversely proportional to overload (see Fig. 3.44)
• Operating characteristic according to ASA-C50.13 (American
Standard Requirements for Cylindrical-Rotor Synchronous
Generators) with extended setting range
• Adjustable rate of counting backwards when the overload
disappears (cooling rate of thermal image)
• Three-phase measurement
• Current measurement
• three-phases of AC excitation supply
• evaluation of the sum of the three phases (instantaneous
values without digital filtering)
I. Analog inputs:
• Current
IV. Measurements:
• Current amplitude
3-173
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Explanation of parameters:
Run On CPU
Defines on which CPU the function should operate.
Trip
defines the tripping channel activated by the tripping output of the
function (tripping logic).
K1 Setting
Multiplier. Operating characteristic constant.
I - Start
Enabling current for operating characteristic.
t - min
Minimum operating time. Operating characteristic constant.
tg
Time during which the inverse characteristic is active. Operating
characteristic constant.
This must not exceed the maximum delay time.
t - max
Maximum delay after being enabled regardless of inverse
characteristic. Operating characteristic constant.
t - Reset
Time taken to reset (from the operating limit). This corresponds to
the time taken by the machine to cool.
3-174
RE.216 1KHA000951-UEN ABB Switzerland Ltd
3-175
ABB Switzerland Ltd RE.216 1KHA000951-UEN
E. Setting instructions
Settings:
Reference current IB - Setting
Enabling current I - Start
Multiplier K1 Setting
Minimum operating time t - min
Time inverse characteristic effective tg
Maximum delay t - max
Resetting time t - Reset
∆ϑm − ∆ϑn
k1 = τ [s; s; K]
∆ϑn
where:
τ : thermal time constant of the rotor
∆ϑm : maximum permissible temperature rise of the rotor winding
∆ϑn : rated temperature rise of the rotor winding
3-176
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Typical settings:
IB - Setting to be calculated
I - Start 1.1 IB
K1 Setting 33.8 s
t - min 10.0 s
tg 120.0 s
t - max 300.0 s
t - Reset 120.0 s
3-177
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-178
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
Overtemperature protection with accurate thermal image.
B. Features
• selectable thermal image for:
• 1st. order model
• universal thermal image defined by the impulse response of the
thermal system (see Fig. 3.45)
• alarm and tripping stages
• adjustable initial temperature rise
• extended thermal time constant when stationary
• takes account of temperature coefficient of resistance
• insensitive to DC components
• insensitive to harmonics
• single or three-phase measurement
• highest phase value detection in the multi-phase mode
• independent scaling of the impulse response for the universal
thermal image (entry of a table)
• 40 temperature rise calculations per thermal time constant (for 1st.
order model) or 200 calculations per duration of the impulse
response.
I. CT/VT inputs:
• Current
IV. Measurements:
• Temperature rise
• Power dissipation
• Current
3-179
ABB Switzerland Ltd RE.216 1KHA000951-UEN
General Parameters
Run On CPU CPU1 (Select)
Trip ---
Theta Begin % 100 0 100 1
Theta Warning % 105 050 200 1
Theta Trip % 110 050 200 1
Temp Coeff 1/ThetaN 0 0 1 0.01
K - Setting 1 1 9 1
IB-Setting IN 1 0.5 2.5 0.01
Number Of Phases 1 Ph (Select) 2
Current Input Chan. CT/VT-Addr ---
Stillst. Input BinaryAddr Always
FALSE
Block Input BinaryAddr Always
FALSE
Warning Signal SignalAddr ER
Trip Signal SignalAddr ER
1. Order Model
Time Constant min 5 1 500 0.1
Universal Model
ResponseTime min 0 5 6000 1
h[1] 0 -0.2 2 0.01
h[2] 0 -0.2 2 0.01
h[3] 0 -0.2 2 0.01
.
.
.
h[40] 0 -0.2 2 0.01
Explanation of parameters:
GENERAL PARAMETERS
Run On CPU
Defines on which CPU the function should operate.
3-180
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Trip
Tripping logic (matrix) for this function.
Theta Begin
Initial temperature rise.
This temperature rise is set every time the function is initiated, e.g.
when the protection is switched on or settings are changed.
A setting of 100 % is recommended for a unit, which is already
warm; a setting of 0 % is recommended for a unit starting at room
temperature in order to obtain the maximum utilization during the
start-up period
Theta Warning
Temperature rise at which alarm is given.
Theta Trip
Temperature rise at which tripping takes place.
Temp Coeff
Temperature coefficient "a" for taking account of the increased
resistance of the conductor due to the temperature rise caused by
the flow of current.
The temperature rise is derived from the dissipated power, which is
proportional to the resistance R of the conductor:
R = R0 (1 + a × T).
where T is the temperature rise referred to the rated value and R0
is the resistance at zero temperature rise, i.e. at room temperature.
Normally, a setting of a = 0 models the thermal behavior
sufficiently well.
k-Setting
Factor for extending the time constant when the unit is stationary.
The unit is assumed to be at a standstill when binary standstill I/P
is a logical "1" and the measured current is low at the same time
(less than approx. 0.005 IN in the case of metering CT cores or
0.05 IN in the case of protection CT cores).
IB-Setting
Reference current: Normal operating current of the protected unit
referred to the rated current of the protection.
Number Of Phases
Nr. of phase currents measured.
Current Input Chan.
defines CT input channel.
All current channels are available for selection.
For three-phase measurement, the first channel (R phase) of the
group of three must be selected.
Stillst.-Inp
for detecting when the unit is at standstill and switching to a longer
time constant for taking account of the slower cooling.
Block Input
I/P for blocking the function
3-181
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Warning
Output for signaling an alarm
Trip
Output for signaling tripping
1. Order Model
Time Constant
Thermal time constant for calculating the temperature rise.
Settings:
>0→ 1st order thermal model for which the thermal time
constant has to be entered.
=0→ Thermal model according to table entered.
Universal Model
ResponseTime
Duration of the response impulse.
Only effective for a thermal model described by a table.
Setting restrictions:
not = 0 for a time constant setting = 0
not > 0 for a time constant setting > 0
h[1], h[2] . h[40]
define a value of the impulse response of the thermal system.
3-182
RE.216 1KHA000951-UEN ABB Switzerland Ltd
E. Setting instructions
Settings:
Reference current IB - Setting
Initial temperature rise Theta Begin
Temperature rise for alarm Theta Warning
Temperature rise for tripping Theta Trip
Temperature coefficient of resistance Temp Coeff
Extension factor K - Setting
Thermal time constant Time Constant
Duration of impulse response Response Time
Instantaneous value of the impulse response h[1] to h[40]
The overtemperature function guards against inadmissible tempera-
ture rise caused by overcurrents. The temperature rise is modeled on
the basis of the influence of the current flowing through the protected
unit on a thermal image of the protected unit. In contrast to the over-
load protection, this function can protect units of any power rating and
thermal capacity. It monitors the temperature rise and not the absolute
temperature. Thereby neither the ambient temperature nor the
effectiveness of the cooling system has an effect on the protection.
The operation of the overtemperature function is based on modelling
of the temperature rise of the winding. When the current changes, the
temperature rise changes from an initial value to a final value
according to one or more exponential functions. For a transformer,
these represent, for example, the thermal behavior of the cooling
water, the oil, the copper of the windings etc. In the case of a rotating
machine they concern the core, end windings, windings in the slots
etc. One of these functions is always more pronounced than the
others, e.g. the transformer oil or motor core. The overtemperature
function utilizes two models for modeling the transient temperature
rise. The first employs an exponential function and the second model a
universally applicable function (see Fig. 3.45). The first model is
suitable for the case where one exponential function is so
predominant, that the others may be either neglected, or approximated
by adjusting the thermal time constant. The second model is to be
preferred for more complex transient temperature rise functions.
This protection function does not monitor instantaneous values as do
most of the others. The temperature rise is determined by integration
over a given period, e.g. 1/40 of the thermal time constant.
The excursion of the temperature rise modeled by the protection is
determined by the following:
• the final steady-state temperature corresponding to the current
• the increased temperature rise due to the transfer functions.
3-183
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Step
Current 1
Step response
s(t)
1
∆t = t response
40
1
t response
Heating ∆ϑ
∆t
0 1 2 3... 37 38 39 40 t / ∆t
d
h(t) = s(t)
dt
t response
h(t) dt = 1
Impulse response
h(t)
h1 h(t)
h2
h3
hn
h38 h39
h40
0 1 2 3... 37 38 39 40 t / ∆t
3-184
RE.216 1KHA000951-UEN ABB Switzerland Ltd
The protection assumes that at the rated current IGN of the protected
unit, the temperature rise represents 100 %. Neglecting any compen-
sation of the A/D channel or the base current IB, the protection meas-
ures a current IR determined by the rated current of the CTs:
IN2
IR = IGN
IN1
where
IGN : rated current of the protected unit
IN1, IN2 : rated primary and secondary CT currents.
The current referred to the rated current IN of the protection is:
IR IGN IN2
IR = = ×
IN IN IN1
The steady-state temperature rise becomes:
2
⎛I I ⎞
∆ϑW = ⎜⎜ GN × N2 ⎟⎟ × 100 %
⎝ IN IN1 ⎠
At a constant current, the tripping time is:
⎛ 2
⎞
⎜ ϑ [%] − 100 × ⎛⎜ I ⎞⎟ ⎟
⎜ 0 ⎜I ⎟ ⎟
t = τ ln ⎜ ⎝ B⎠ ⎟
2
⎜ ⎛I⎞ ⎟
⎜⎜ ϑ [%] − 100 × ⎜⎜ ⎟⎟ ⎟⎟
⎝ ⎝ IB ⎠ ⎠
where
ϑ0 : initial temperature rise
ϑ : pick-up temperature rise
τ : thermal time constant
The variables in the submenu 'DISPLAY OPERATING VALUES' are
the calculated temperature rise, the power dissipation and the current.
The first two are mean values over the period of calculation (= τ / 40).
The values shown in the event list is the power dissipation at the
instant of tripping.
Example:
Rated current of the protected unit IGN = 8000 A
CT ratings IN1 = 10000 A
IN2 = 5A
Rated relay current IN = 5A
The temperature rise measured by the protection at a rated current of
IGN is:
2
⎛ 8000 5 ⎞
∆ϑW = ⎜ × ⎟ × 100% = 64 %
⎝ 5 10000 ⎠
3-185
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-186
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Example
Rated temperature rise ∆ϑN = 60 K; α = 4 × 10-3 K-1
a = α × ∆ϑN = 4 × 10-3 × 60 = 0.24
The following must therefore be set:
Temp.-Coeff. = 0.24
Transformers have two predominant exponential functions, one
determined by the oil, the other by the winding, with the following
typical values:
oil: ∆ϑoil = 50 K τoil = 120 min
winding: ∆ϑW - ∆ϑoil = 10 K τW = 10 min
total temperature rise of the winding: ∆ϑW = 60 K
The first model operates with a single exponential function and
therefore the composite temperature rise of the winding has to be
approximated as closely as possible by adjusting the single curve. This
can be seen in Fig. 3.46. The final temperature rise of the equivalent
curve is identical to that of the winding as a whole, i.e. ∆ϑW = 60 K in
the example above. The time constant, however, usually lies between
60 and 80 % of the time constant for the temperature rise of the oil
(see Fig. 3.47).
Similar relationships prevail with regard to modeling the temperature
rise of generators and motors
3-187
ABB Switzerland Ltd RE.216 1KHA000951-UEN
1,5
0 t
ϑw ( t = ∞ )
ϑ [°C] 160
ϑ Öl ( t = ∞ ) ϑw
140
ϑ Öl
120
ϑ nw
100
ϑ Öl τ Öl
80
60
40
τw ∆ϑ Öl
20
ϑw ϑÖl
3-188
RE.216 1KHA000951-UEN ABB Switzerland Ltd
τ
ϑ =126,4°C
140
Wicklungstemperatur
simulierte Wicklungstemperatur
120
130
ϑ [°C] ∆ ϑ [%]
120
110
Überlast i = 1,2
Erwärmung bei Nennstrom ∆ϑ nw − ∆ϑnÖl = 10°C τ w = 10 min
110
∆ϑ nÖl = 50°C τ Öl = 120 min
Einstellwert der therm. Zeitkonstante τ = 90 min
100 100
0 100 200 300 400 500
t [min]
HEST 905 036 C
3-189
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Typical settings:
IB-Setting to be calculated
Theta-Begin 0%
Theta-Warn 105%
Theta-Trip 110%
Temp.-Coeff. 0
K - Setting 3 *) 3
Time Constant acc. to prot. unit 0
ResponseTime 0.
h[1] 0
h[2] 0
. acc. to prot. unit
.
.
h[40] 0
3-190
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
• Under and overfrequency
• Load-shedding
B. Features
• Measurement of one voltage
• Frequency calculation based on the complex voltage vector
• Insensitive to DC component
• Insensitive to harmonics
• Undervoltage blocking
I. CT/VT inputs:
• Voltage
IV. Measurements:
• Frequency
• Voltage
3-191
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Explanation of parameters:
Run On CPU
Defines on which CPU the function should operate.
Trip
defines the tripping relay activated by the tripping output of the
function (matrix).
Frequency
Operating value.
Setting restrictions:
• underfrequency not ≥ fN
• overfrequency not ≤ fN
Block Voltage
Peak value of the voltage for blocking.
(reset ratio approx. 1.05)
Delay
Time between the function picking up and tripping.
Max / Min
defines operation as overfrequency or underfrequency. Settings:
• Max: Overfrequency
• Min: Underfrequency
Voltage Inp. Chan.
defines the voltage input channel.
All voltage inputs may be selected.
3-192
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Block Input
Binary address used as blocking input.
Blocked (U<) Signal
defines the output for signaling blocking by undervoltage
(signal address).
Trip Signal
Output for signaling tripping.
Start Signal
Output for signaling pick-up.
3-193
ABB Switzerland Ltd RE.216 1KHA000951-UEN
E. Setting instructions
There are often several stages of frequency protection using several
single-stage relays.
Settings:
Frequency Frequency
Delay Delay
Undervoltage blocking Block Voltage
Under or over frequency Max / Min
Frequency protection is used either to protect synchronous machines
and prime-movers against the effects of operating at under or
overfrequency or for load-shedding in the event of an overload.
The adverse effects in the former case prevented by the frequency
protection are:
• excessive temperature rise and additional iron losses in the
generator
• damage to the generator and the prime-mover by vibration
Some synchronous machines are subject to severe vibration if they
are operated at speeds other than their rated speed.
Vibration occurs more usual at speeds below rated frequency, but can
occur both above and below. A complete scheme often comprises
therefore 4 stages, two for alarm and tripping for overfrequency and
two for alarm and tripping for underfrequency. Tripping is delayed to
avoid the risk of maloperation during transients.
Typical settings:
1. Protection of machines
3-194
RE.216 1KHA000951-UEN ABB Switzerland Ltd
2. Load-shedding
1st stage 2nd stage 3rd stage 4th stage 5th stage
Alarm Load-shed. Alarm Load-shed. Load-shed.
3-195
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-196
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
• Static, dynamic and adaptive load shedding in power utility and
industrial distribution systems
• Generator protection
B. Features
• One phase voltage as input variable
• Supervises the rate-of-change df/dt of the frequency
• Provision for enabling by absolute frequency
• Insensitive to DC component
• Insensitive to harmonics and other high-frequency signals
• Undervoltage blocking
I. CT/VT inputs:
• Voltage
IV. Measurements:
• Rate-of-change of frequency
• Absolute frequency
• Voltage amplitude
3-197
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Explanation of parameters:
Run On CPU
Defines on which CPU the function should operate.
Trip
defines the tripping channel activated by the tripping O/P of the
function (matrix tripping logic).
df/dt
Rate-of-change of frequency pick-up setting.
Inadmissible settings:
• df/dt = 0
• df/dt > 0 for absolute 'Frequency' settings < fN
• df/dt < 0 for absolute 'Frequency' settings > fN
Frequency
Setting of the absolute frequency enabling criterion.
Operation for overfrequency or underfrequency is determined by
the absolute frequency setting:
• Underfrequency for 'Frequency’ settings < fN
• Overfrequency for 'Frequency' settings > fN
The absolute frequency criterion is disabled for a setting of
'Frequency' = 0. In this case, tripping is dependent solely on the
rate-of-change setting df/dt.
Inadmissible settings:
• Frequency = fN
• Frequency < fN – 10 Hz
• Frequency > fN + 5 Hz
Block Voltage
Pick-up setting for undervoltage blocking
(reset ratio approx. 1.05, reset time approx. 0.1 s).
3-198
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Delay
Delay from the instant the function picks up to the generation of a
tripping command.
Voltage Inp. Chan.
defines the voltage input channel. All voltage inputs may be
selected with the exception of the special voltage inputs for the
100% ground stator fault protection.
Block Input
defines the input for an external blocking signal.
Blocked (U<) Signal
signals when the function is blocked by the undervoltage criterion.
Trip Signal
Output for signaling tripping.
3-199
ABB Switzerland Ltd RE.216 1KHA000951-UEN
E. Setting instructions
Several rate-of-change of frequency stages are often needed and the
additional stages are achieved by configuring the function as many
times as is necessary.
Settings:
Rate-of-change of frequency df/dt
Absolute frequency Frequency
Undervoltage Block Voltage
Delay Delay
The rate-of-change of frequency function only trips when the rate-of-
change is higher than setting, the absolute frequency criterion picks up
and the voltage is not lower than the undervoltage setting.
The additional absolute frequency criterion prevents unwanted opera-
tion of the rate-of-change function during power system transients.
Where it is desired that the rate-of-change function should operate
without regard to the absolute frequency, this is achieved by setting
the absolute frequency criterion to '0'.
3-200
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
Protection of generators and power transformers against excessive
flux.
B. Features
• Evaluation of the voltage/frequency ratio
• Single-phase measurement
• Definite time delay
• Determination of frequency from the complex voltage vector
• Insensitive to DC components
• Insensitive to harmonics
• Over or underexcitation mode
I. CT/VT inputs:
• Voltage
IV. Measurements:
• Voltage / frequency
• Frequency
3-201
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Explanation of parameters:
Run On CPU
Defines on which CPU the function should operate.
Trip
defines the tripping channel activated by the tripping output of the
function (tripping logic).
Delay
time delay between pick-up and tripping.
V/f - Setting
Setting of the voltage/frequency ratio for tripping.
Max / Min
defines operation as overfluxing or underfluxing. Settings:
Max: overfluxing
Min: underfluxing
Voltage Inp. Chan.
defines the VT input channel.
All voltage inputs may be selected.
Block Input
Binary address used as blocking input.
Trip Signal
Output for signaling tripping.
Start Signal
Output for signaling pick-up.
3-202
RE.216 1KHA000951-UEN ABB Switzerland Ltd
E. Setting instructions
Settings:
Magnetic flux V/f - Setting
Delay Delay
Over/underfluxing Max / Min
Typical settings:
V/f - Setting 1.1 UN/fN
Delay 5s
Max / Min Max
3-203
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-204
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
Protection of generators and power transformers against excessive
flux, especially in heavily loaded non-laminated metal parts, and the
associated excessive heating of the unit.
B. Features
• Evaluation of the voltage/frequency ratio
• Single-phase measurement
• Inverse time delay according to U/f ratio
• Determination of frequency from the complex voltage vector
• Insensitive to DC components
• Insensitive to harmonics
• Delay determined by integrating function response
• Input of delay table facilitates matching the operating characteristic
to a specific machine according to IEEE Guideline
C 37.91-1985
• Adjustable rate of counting backwards when the overfluxing
disappears
I. CT/VT inputs:
• Voltage
IV. Measurements:
• Voltage/frequency
• Frequency
3-205
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Explanation of parameters:
Run On CPU
Defines on which CPU the function should operate.
Trip
defines the tripping channel activated by the tripping output of the
function (matrix).
UB - Setting
Reference (base) voltage for compensating a difference between
the VT rating and the rating of the generator or transformer.
U/f Start
Voltage/frequency ratio setting referred to UB / fN.
3-206
RE.216 1KHA000951-UEN ABB Switzerland Ltd
t - Min
Minimum operating time after being enabled regardless of inverse
characteristic. Operating characteristic constant.
t - Max
Maximum operating time after being enabled regardless of inverse
characteristic. Operating characteristic constant.
t - Reset
Time taken to reset (from the operating point). This corresponds to
the time taken by the generator to cool.
t[U/f = 1.05] ... t[U/f = 1.50]
Table of 10 values (data input) for defining a specific inverse
operating characteristic.
Voltage Input Chan.
defines the VT input channel.
All voltage inputs may be selected.
Block Input
Binary address used as blocking input.
Trip Signal
Output for signaling tripping.
Start Signal
Output for signaling pick-up.
3-207
ABB Switzerland Ltd RE.216 1KHA000951-UEN
E. Setting instructions
Settings:
Magnetic flux for enabling char. U/f Start
Reference value UB - Setting
Minimum operating time t - Min
Maximum operating time t - Max
10 values defining the inverse t[U/f = 1.05] ... t[U/f = 1.50]
time operating characteristic
Reset time t - Reset
3-208
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Typical settings:
U/f Start 1.1 UB/fN
UB - Setting according to protected unit
t - Min 0.2 min
t - Max 60 min
t [U/f = 1.05...1.50] according to protected unit1)
t - Reset 60 min
A-Westinghouse-transformers
B-Westinghouse-generators
140
135
Permissible overfluxing [%]
130
125
A
120
B
115
110 110%
105 105%
100 continuous
.1 .2 .5 1.0 2 5 10 20 50 100 200
t [min]
HEST 935 004 FL
1)
Refer to Fig. 3.48 and Fig. 3.51 for typical settings for a Westinghouse unit.
3-209
ABB Switzerland Ltd RE.216 1KHA000951-UEN
300
t [min]
t-max
40
30
20
10
6
5
4
3
2
1
0.5 0.6
0.4
0.3
0.2
t-min
0.1
130
125
120
105
100
115
110
Overfluxing [%]
3-210
RE.216 1KHA000951-UEN ABB Switzerland Ltd
% 150
[VB/fN]
145
140
135
130
Permissible short-time
125
overfluxing
Approximation
120 according to table
115
V/f-Setting
110
105
.1 .2 .3 .4 .5 1.0 2 3 4 5 6 7 8 9 10 20 30 40 50 60
140
1
2
% 130
V
O
L
T 120
S
/
H
z 110
100
3-211
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-212
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
Ground fault protection function for detecting ground faults close to the
star-point of a generator. The scheme is based on the principle of
biasing the potential of the generator star-point by injecting a coded
low-frequency signal. The injection signal is generated by the injection
unit REX 010 and fed into the stator circuit by the injection transformer
block REX 011. In conjunction with the voltage function 'Voltage' that
covers 95 % of the winding, this protection completes detection of
ground faults over 100 % of the winding. Compensation is provided for
the influence of a second high-resistance grounded star-point in the
zone of protection.
Stator ground faults producing a current at the star-point > 5 A cause
the P8 contactor to reset which separates the injection unit Type
REX 010 from the injection transformer block REX 011 and interrupts
injection in both stator and rotor circuits. The 95 % stator ground fault
protection then clears the fault on its own.
B. Features
• Protects the star-point and a part of the stator winding depending
on the ground fault current. The entire winding is protected when
the generator is stationary.
• Biases the star-point in relation to ground by injecting a signal
generated in the REX 010 unit
• Computes the ground fault resistance
• Monitors the amplitude and frequency of the injection signal
• Monitors the measuring circuit with respect to open-circuit and
correct connection of the grounding resistor
I. CT/VT inputs:
• Voltage (2 inputs)
3-213
ABB Switzerland Ltd RE.216 1KHA000951-UEN
IV. Measurements:
• Ground fault resistance Rfs
• Measurement transformer ratio MTR
• Grounding resistor REs
Explanation of measurements:
Rfs:
Ground fault resistances between 0 and 29.8 kΩ can be deter-
mined and displayed. A display of 29.9 kΩ or 30 kΩ indicates a
ground fault resistance >29.8 kΩ. A value of 29.9 kΩ or 30 kΩ is
displayed when there is no ground fault.
A whole number fault code between 100 and 109 is displayed in
cases when it is not possible to compute the ground fault resis-
tance.
• 100.0 means no injection for more than 5 s.
• 101.0 means incorrect frequency. Either the injection frequency
on the REX 010 or the rated frequency on the REG316*4 is
incorrectly set.
• 102.0 means external open-circuit.
• 109.0 means that both the binary inputs 'Adjust REs Input' and
'AdjMTRInp' are enabled.
No other codes will normally be generated, but if they are, they are
a diagnostic aid for service people.
MTR:
The value measured for MTR is displayed when the input 'Adjust
MTR Input' is enabled.
During normal operation, the value entered for MTR via the HMI is
displayed.
3-214
RE.216 1KHA000951-UEN ABB Switzerland Ltd
REs:
When the input 'Adjust REs Input' is enabled, the error code 123.0
is displayed initially until the resistance has been calculated. It can
take up to 10 s before the value measured for REs is displayed.
During normal operation, the value entered for REs via the HMI is
displayed.
Normal operation:
Neither of the two inputs 'Adjust MTR Input' and 'Adjust REs Input'
is enabled and injection is taking place.
NOTE: Only one of the binary inputs may be enabled at any one
time, otherwise an error code is generated for the measurements
Rfs, MTR and REs (see table below).
3-215
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Explanation of parameters:
Run On CPU
Defines on which CPU the function should operate.
Trip
defines the tripping channel activated by the tripping output of the
function (tripping logic).
Alarm Delay
Time between pick-up of the alarm stage and an alarm.
3-216
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Trip Delay
Time between pick-up of the tripping stage and a trip.
RFs AlarmValue
Ground fault resistance setting for alarm.
RFs for alarm must be higher than RFs for tripping.
RFs Trip Value
Ground fault resistance setting for tripping.
REs
Grounding resistor REs for primary system grounding.
Where the grounding resistor is connected to the secondary of a
VT, its value related to the primary system R'Es has to be
calculated and entered.
REs 2. Star Point
The total grounding resistance of a 2nd star-point in the zone of
protection.
Rfs Adjust
Simulated ground fault resistance used as a reference value for
calculating REs in the 'REs-Adjust' mode.
Meas. Transf. Ratio
VT ratio for a directly grounded primary system.
Nr. Of Star Points
Number of star-points in the zone of protection.
Voltage Input Ui
defines the voltage input channel for the reference voltage.
Channel 8 must be used.
Voltage Input Us
defines the voltage input channel for the measured voltage.
Channel 9 must be used.
2. Star Point Input
Binary address used as status input. It determines whether the
second star-point is connected in parallel to the first.
Adjust MTR Input
switches the protection function to the MTR determination mode.
Adjust REs Input
switches the protection function to the REs determination mode.
Block Input
Binary address used as blocking input.
Trip Signal
Output for signaling tripping.
Start Signal
Output for signaling the pick-up of the tripping stage.
Alarm Signal
Output for signaling an alarm.
3-217
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-218
RE.216 1KHA000951-UEN ABB Switzerland Ltd
E. Setting instructions
The value of 'Rfs Alarm Value' for alarm must always be higher than
that of 'Rfs Trip Value' for tripping.
Both alarm and tripping stages have their own timers.
Typical delays used for the 100 % ground fault protection are in the
range of seconds.
Settings:
'Rfs Trip Value' for tripping
'Rfs Alarm Value' for alarm
Delay for tripping
Delay for alarm
Grounding resistor REs
Measuring transformer ratio (MTR).
Typical settings:
Alarm stage:
RFs-Setting 5 kΩ
Delay 5s
Tripping stage:
RFs-Setting 500 Ω
Delay 2s
Setting procedure:
The accuracy of the Rfs calculation depends on the values entered for
REs and MTR. Therefore check the settings and correct them if
necessary by connecting resistors between 100 Ω and 10 kΩ between
the star-point and ground while the generator is not running.
The protection function provides a convenient way of setting these two
parameters in the software by switching its mode using the input
'Adjust MTR Input' or 'Adjust REs Input'. This is the recommended
procedure. In this mode, the settings of the parameters 'MTR' and
'REs' are calculated with the aid of simulated ground fault resistances.
The two parameters are displayed continuously in the measured
values window.
Should the values of REs and MTR determined by the adjustment
modes differ from their nominal values, the calculated values are the
preferred values.
3-219
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Determination of 'MTR':
• Ground the star-point (Rf = 0 Ω).
• Set the input 'Adjust MTR Input' to 'Always TRUE'.
• Select menu 'Monitor', 'Measurement', 'Display Function
Measurements', '100% Stator Ground Fault' and click on 'Open
Function'. Note the value for 'Meas. Transf. Ratio'. Return to the
'Configuration' menu, then the submenu 'Protection Functions'. In
the window 'Select Protection Function' select the function '100%
Stator Ground Fault', now enter the value noted for the 'Meas.
Transf. Ratio' and download the set file into the relay.
• Remove the connection between the star-point and ground.
• Reset the binary input ‘Adjust MTR Input’.
Determination of ‘REs’.
• The selection of the menus and items is the same as for the
determination of 'MTR' above.
• Set the input 'Adjust REs Input' to 'Always TRUE'.
• Enter an approximate value for 'REs'.
• Simulate a ground fault Rf by connecting a resistor between the
star-point and ground: 8 kΩ < Rf < 12 kΩ
• In the window 'Select Protection Function', window '100% Stator
Ground Fault (Stator EFP)':
Enter the value for the setting 'Rfs Adjust'.
Enter the approximate value for 'REs'. If the grounding resistor is
on the secondary system side, the value entered must be referred
to the primary side (Refer also to the Sections concerning REs and
MTR in the case of secondary injection at the star-point, respec-
tively at the terminals.) and download the set file into the relay.
• Open the submenu 'Display Function Measurements' in the
'Monitor', 'Measurement', and note the value of 'REs'.
• Enter the value noted for the setting of 'REs' in the 'Configuration'
menu, then the submenu 'Protection Functions' and download the
set file into the relay.
• Remove the simulated ground fault.
• Reset the input 'Adjust REs Input'.
The protection function will only switch back from the
determination mode to the normal protection mode when both
binary Inputs have been reset.
Check the settings by connecting resistors of 100 Ω to 20 kΩ (P ≥ 5 W)
between the star-point and ground and compare their values with the
readings of the measured values on the screen.
NOTE: The tripping and alarm outputs are disabled as long as one of
the two binary Inputs 'Adjust MTR Input' or 'Adjust REs Input' is
enabled, i.e. the protection will not trip if the stator circuit is grounded.
The two signals 'Inj. Interrupt Signal' and 'Ext. Interrupt Signal',
however, are not disabled.
3-220
RE.216 1KHA000951-UEN ABB Switzerland Ltd
3.5.24.1. REs and MTR in the case of primary injection at the generator
star-point
An injection transformer block Type REX 011 is needed for this circuit.
R S T
Generator
N12 N11
REs Us
Voltage
transformer
Uis RPs
Injection voltage
The wiring diagram for primary injection is shown in Fig. 3.52 (peak
value of Uis 110 or 96 V DC) at the generator star-point. The star-point
is grounded via the resistor REs and the parallel resistor RPs. The
current at the star-point must not exceed 20 A. It is recommended,
however, to select the resistors such that the star-point current is ≤ 5 A
to protect as much of the winding as possible.
The total resistance is thus:
UGen
Condition 1: REs + RPs ≥
3 × IEmax
where: UGen phase-to-phase voltage at the generator
terminals
IEmax max. star-point current = 20 A
3-221
ABB Switzerland Ltd RE.216 1KHA000951-UEN
N12 UGen
A VT = will fulfill condition 4 in most cases.
N11 3 × 100 V
Design example:
UGen = 8 kV
Assumed: IEmax ≤ 5 A
Injection in Stator- und Rotor circuit
Determination of the grounding resistors:
8 kV
Condition 1: REs + RPs ≥ ≥ 924 Ω
3 ×5 A
924 Ω
Condition 2: RPs ≥ 87 Ω and RPs ≤ = 168 Ω
5.5
Assumed: RPs = 100 Ω
3-222
RE.216 1KHA000951-UEN ABB Switzerland Ltd
REs = 1'000 Ω
Design instructions:
The injection unit REX010 delivers a maximum output power of 150 W.
The peak injection voltage is ±96 V.
Taking into account the available power, typical resistance values for
most applications are REs = 1000 Ω and RPs = 100 Ω. Both RPs and
REs must be able to conduct the maximum star-point current for 10 s.
The resistor RPs must also be continuously rated for the injection
voltage (injected power < 150 W).
The maximum generator star-point current is determined by the
resistors REs and RPs. Using the above resistors, this current would
be, for example, 5.3 A for UGen = 10.5 kV or 13.5 A for UGen = 27 kV.
3-223
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3.5.24.2. REs and MTR in the case of secondary injection at the star-point
An injection transformer block Type REX011-1 is needed for this
circuit.
R S T
Generator
Voltage
transformer
N1 N2 N'12 N'11
R'Es Us
R'Ps Uis
Grounding
transformator
Injection voltage
The bias voltage can also be injected across part of the grounding
resistor connected to the secondary of a grounding VT (see Fig. 3.53).
The two resistors R'Es and R'Ps limit the maximum current at the star-
point which must not exceed 20 A. The total resistance is thus:
2
UGen ⎛N ⎞
Condition 1: R'Es +R'Ps ≥ × ⎜⎜ 2 ⎟⎟
3 × IEmax ⎝ N1 ⎠
where: UGen phase-to-phase voltage at the generator terminals
IEmax max. star-point current = 20 A
N1/N2 ratio of the grounding transformer
Uis Injection voltage, depending on the configuration is
0,85 V, 1,7 V or 3,4 V.
3-224
RE.216 1KHA000951-UEN ABB Switzerland Ltd
N'12 UGen N
A VT = × 2 will fulfill condition 4 in most cases.
N'11 3 × 100V N1
The settings for REs and MTR must be entered via the HMI, i.e. the
values of R'Es and MTR' reflected to the primary of the grounding
transformer:
2
⎛N ⎞
REs = R'Es × ⎜⎜ 1 ⎟⎟ ≥ 0.25 kΩ
⎝ N2 ⎠
110 V N'12 110 V
MTR = MTR' × = ×
Uis N'11 Uis
The injection voltage Uis depends on the value of the parallel
resistance R'Ps and can be either 0.85 V, 1.7 V or 3.4 V.
3-225
ABB Switzerland Ltd RE.216 1KHA000951-UEN
The two determination modes 'REs Adjust' and 'MTR Adjust' determine
and display the values for REs and MTR, i.e. they present the
secondary circuit reflected on the primary system side. Inaccuracies
due to contact resistance, grounding resistor tolerances etc., are thus
automatically compensated.
Determining the values for REs and MTR by means of the
determination modes 'REs Adjust' and 'MTR Adjust' during
commissioning is recommended in preference to calculating their
values.
As a check, calculate the values of R'Es and MTR' from the values
given for RE and MTR in the measured value window as follows:
2
⎛N ⎞
R'Es = REs × ⎜ 2 ⎟
⎝N⎠
Uis
MTR' = MTR ×
110 V
In most cases, the calculated and determined values will not agree.
Discrepancies of ±20 % are acceptable. Where the discrepancies -
especially in the case of REs - are large, check the actual values of the
grounding resistors and the grounding transformer.
Design example:
UGen = 16 kV
N1 14.4 kV
= = 60
N2 240 V
Assumed: IEmax ≤ 5 A
Injection only in Stator circuit
3-226
RE.216 1KHA000951-UEN ABB Switzerland Ltd
3 .4 V 2 513 mΩ
Condition 2: 1 .2 × ≤ R'Ps ≤ resp.
150 W 5 .5
92.5 mΩ ≤ R'Ps ≤ 93.3 mΩ
Assumed: R'Ps = 93 m Ω
Condition 3: R'Es ≥ 4.5 × 93 mΩ = 419 mΩ and
2
⎛ 1⎞
R'Es ≤ 5.0 kΩ × ⎜ ⎟ = 1.39kΩ
⎝ 60 ⎠
In order to fulfill Conditions 1, 2 and 3:
R'Es = 500 mΩ
Determination of the VT:
N'12 16 kV 1
Assumed: = × = 1.54
N'11 3 × 100 V 60
16 kV 1 500 mΩ
where n = × × = 1.30
3 × 100 V 60 500 mΩ + 93 mΩ
R'Es = 500 mΩ
3-227
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3.5.24.3. REs and MTR in the case of secondary injection at the generator
terminals
An injection transformer block Type REX011-2 is needed for this
circuit.
R S T Voltage
transformer
R'Ps Uis
Grounding
transformator
Injection voltage
Generator
The bias voltage can also be injected across part of the grounding
resistor connected to the broken-delta secondaries of a grounding VTs
at the generator terminals (see Fig. 3.54).
The two resistors R'Es and R'Ps limit the maximum current at the star-
point which must not exceed 20 A. The total resistance is thus :
2
UGen ⎛ 3 × N2 ⎞
Condition 1: R'Es + R'Ps ≥ × ⎜⎜ ⎟
3 × IEmax ⎝ N1 ⎟⎠
where: UGen phase-to-phase voltage at the generator
terminals
IEmax max. star-point current = 20 A
N1/N2 ratio of the grounding transformer
The grounding resistors R'Es and R'Ps must fulfill the following
conditions:
Condition 2a Injection in Stator and Rotor circuit:
2
Uis ⎛ R' + R'Es ⎞
R'Ps ≥ 1.2 × and R'Ps ≤ ⎜ Ps ⎟
130 W ⎝ 5.5 ⎠
Condition 2b Injection only in Stator circuit:
2
Uis ⎛ R' + R'Es ⎞
R'Ps ≥ 1.2 × and R'Ps ≤ ⎜ Ps ⎟
150 W ⎝ 5.5 ⎠
3-228
RE.216 1KHA000951-UEN ABB Switzerland Ltd
N'12 UGen 3 × N2
A VT = × will fulfill condition 4 in most cases.
N'11 3 × 100 V N1
The settings for REs and MTR must be entered via the HMI, i.e. the
values of R'Es and MTR' reflected to the primary of the grounding
transformer:
2
⎛ N1 ⎞
REs = R'Es ×⎜⎜ ⎟⎟ ≥ 0.725 kΩ
⎝ 3 × N2 ⎠
110 V N'12 110 V
MTR = MTR'× = ×
Uis N'11 Uis
The injection voltage Uis depends on the value of the parallel resistor
R'Ps and can be either 6.4 V, 12.8 V or 25.6 V.
The minimum value of the resistor R'Ps in relation to the corresponding
injection voltage Uis can be seen from the following table. The
maximum possible injection voltage should be chosen in each case.
Design example:
UGen = 12kV
12kV
N1 3
=
N2 600 V
3
Assumed: IEmax ≤ 5A
Injection for stator and rotor earthing protection
3-229
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-230
RE.216 1KHA000951-UEN ABB Switzerland Ltd
R S T
S1
REs-2.Starpt
Generator
Switch position to
binary input
N12 N11
REs
Us
Voltage
transformer
Uis RPs
Injection voltage
3-231
ABB Switzerland Ltd RE.216 1KHA000951-UEN
NOTE:
The stator ground fault protection scheme sees the grounding
resistor of the second star-point as a ground fault with the value
'REs 2.Star Point'.
Assuming a ground fault of resistance Rfs occurs, the total
resistance of the parallel resistors Rfs and 'REs 2. Star Point' is
calculated first. The value of Rfs can be simply determined from this,
providing the value of 'REs 2. Star Point' is known.
This procedure is subject, however, to certain restrictions. The
maximum ground fault resistance that can be detected is
approximately ten times the value of 'REs 2. Star Point'. Assuming the
grounding resistor of the second star-point to be 1 kΩ, ground faults
with a resistance less than 10 kΩ can be detected. For this reason,
choosing a grounding resistor 'REs 2. Star Point' ≥ 2 kΩ is
recommended wherever possible.
Design example:
R' = 4 Ω
N1 13.8 kV/ 3
=
N2 120 V
2
⎛ 13.8 kV / 3 ⎞
Rf = 4 Ω × ⎜ ⎟ = 1959 Ω
⎜ 3 × 120 V ⎟
⎝ ⎠
The system is loaded with a permanent earth fault resistance of
1'959 Ω which has to be compensated as a second star point.
3-232
RE.216 1KHA000951-UEN ABB Switzerland Ltd
R S T
N1 N2
R'
S1
Generator
Switch position
to binary I/P
N12 N11
REs
Us
Voltage
Uis transformer
RPs
Injection voltage
3-233
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-234
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
For the detection of ground faults on the rotor windings of generators.
Because of its low sensitivity to spurious signals, this scheme can be
used for all kinds of excitation systems.
B. Features
• Detection of ground faults on rotor windings
• Injection voltage applied via resistors and coupling capacitors to
both poles of the rotor
• Computes the resistance of the ground fault
• Monitors the amplitude and frequency of the injection signal
• Monitors the measuring circuit with respect to open-circuit and
correct connection of the grounding resistor
I. CT/VT inputs:
• Voltage (2 inputs)
IV. Measurements:
• Ground fault resistance RFr
• Coupling capacitor Ck"
• Grounding resistor REr"
3-235
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Explanation of measurements:
Rfr:
Ground fault resistances between 0 and 29.8 kΩ can be deter-
mined and displayed. A display of 29.9 kΩ or 30 kΩ indicates a
ground fault resistance >29.8 kΩ. A value of 29.9 kΩ or 30 kΩ is
displayed when there is no ground fault.
A whole number fault code between 100 and 111 is displayed in
cases when it is not possible to compute the ground fault resis-
tance.
• 100.0 means no injection for more than 5 s.
• 101.0 means incorrect frequency. Either the injection frequency
on the REX 010 or the rated frequency on the REG316*4 is
incorrectly set.
• 102.0 means external open-circuit.
• 109.0 means that both the binary inputs 'Adjust REr Input' and
'Adjust Capacitor Input' are enabled.
• 111.0 means that the binary input 'Adjust REr Input' is enabled.
No other codes will normally be generated, but if they are, they are
a diagnostic aid for the service people.
Ck":
When the input 'Adjust Capacitor Input' is enabled, 133.00 is
displayed initially until the coupling capacitor has been computed.
This can take a maximum of 10 s after which the value measured
for C is displayed.
During normal operation, the value entered for the coupling
capacitor C via the HMI is displayed.
REr":
When the input 'Adjust REr Input' is enabled, the error code 133.00
is displayed initially until the resistance has been calculated. It can
take up to 10 s before the value measured for REr is displayed.
The value measured for Rf is 97.0.
During normal operation, the value entered for REr on the HMI is
displayed.
3-236
RE.216 1KHA000951-UEN ABB Switzerland Ltd
NOTE: Only one of the binary inputs may be enabled at any one
time, otherwise an error code is generated for the measurements
Rfr, C and REr (see table below).
3-237
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Explanation of parameters:
Run On CPU
Defines on which CPU the function should operate.
Trip
defines the tripping channel activated by the tripping output of the
function (tripping logic).
Alarm Delay
Time between pick-up of the alarm stage and an alarm.
Trip Delay
Time between pick-up of the tripping stage and a trip.
3-238
RE.216 1KHA000951-UEN ABB Switzerland Ltd
3-239
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-240
RE.216 1KHA000951-UEN ABB Switzerland Ltd
E. Setting instructions
The value of 'RFr Setting' for alarm must always be higher than that of
'RFr Setting' for tripping. Both alarm and tripping stages have their own
timers. Typical delays used for the rotor ground fault protection are in
the range of seconds.
Recommended resistances:
REr = 1000 Ω
RPr = 100 Ω
Settings:
Grounding resistor REr
Coupling capacitor C
'RFr Alarm Value ' for alarm
'RFr Trip Value' for tripping
'Alarm Delay' for alarm
'Trip Delay' for tripping
Typical settings:
Alarm stage:
Rfr-Setting 5 kΩ
Delay 5s
Tripping stage:
Rfr-Setting 500 Ω
Delay 2s
Setting procedure:
How accurately Rfr is measured depends on the values entered for
REr and C. Therefore check the settings and correct them if necessary
by connecting resistors between 100 Ω and 10 kΩ between the rotor
and ground while the generator is not running.
The protection function provides a convenient way of setting these two
parameters in the software by switching its mode using the input
'Adjust REr Input' or 'Adjust Capacitor Input'. In this mode, the settings
of the parameters 'REr' and 'C' are calculated with the aid of simulated
ground fault resistances.
Determination of REr
• Set the input 'Adjust REr Input' to 'Always TRUE'
• Short-circuit the coupling capacitors.
• Simulate a ground fault Rf by connecting a resistor to the rotor:
8 kΩ < Rf < 12 kΩ
• Click on the 'Configuration' menu, then the submenu 'Protection
Functions', in the window 'Select Protection Function' select the
function '100% Rotor Ground Fault (Injection Principle)', and enter
the simulated ground fault value for 'Rfr Adjust' and the nominal
value for REr and download the set file into the relay.
3-241
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Design instructions:
The grounding resistors and coupling capacitors have to fulfill the
following conditions:
Rotor grounding resistor Rpr : 100 Ω ≤ Rpr ≤ 500 Ω
Rotor grounding resistor REr : 900 Ω ≤ REr ≤ 5 kΩ
Coupling capacitors
C = C1 + C2 : 2 µF ≤ C ≤10 µF
3-242
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Application examples:
Rpr = 200 Ω, P = 15 W
REr = 1 kΩ
C = 2 × 2 µF, 8 kV
τ = 4 ms
+
Rotor
-
C1 C2
C = C1 + C2
REr
Ur
Uir RPr
Injection voltage
3-243
ABB Switzerland Ltd RE.216 1KHA000951-UEN
+
Rotor
C1 C2
C = C1 + C2
REr Ur
Uir RPr
Injection voltage
3-244
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
The pole slipping function detects the condition of a generator that is
completely out-of-step with the power system.
B. Features
• Detection of slip frequencies in relation to the power system of 0.2
to 8 Hz
• Alarm before the first slip (rotor angle pick-up setting)
• Discriminates generating and motoring directions of rotor phase-
angle
• Discriminates an internal and an external power swing centre
• Trips after a set number of slips
• Trips within a set rotor angle
I. Analog inputs:
• Current
• Voltage
IV. Measurements:
• Slip impedance
• Slip frequency
3-245
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Explanation of parameters:
Run On CPU
Defines on which CPU the function should operate.
Trip 1
defines the tripping channel activated by the tripping output of
stage 1 of the function (tripping logic).
3-246
RE.216 1KHA000951-UEN ABB Switzerland Ltd
ZA
Forwards impedance 1). ZA marks the end of zone 2 and is also
used for determining phase-angle.
ZB
Reverse impedance 1). ZB marks the beginning of zone 1 and is
also used for determining phase-angle.
ZC
Impedance of the zone limit 1). ZC is the end of zone 1 between ZB
and ZC and the beginning of zone 2 between ZC and ZA.
phi
Angle of the slipping characteristic and of ZA, ZB and ZC. Phi also
determines the energy direction:
60°... 90° CT neutral on the line side
240°...270° CT neutral on the generator side
Warn Angle
Rotor angle above which alarm of potential slipping is given
(rotor angle > 'Warn Angle').
Trip Angle
Rotor angle below which first 'Trip 1 Signal' and the 'Trip 2 Signal'
are issued (rotor angle < 'Trip Angle').
Slip of Zone 1
Number of slips for zone 1, i.e. number of slips before 'Trip 1
Signal' is issued and signaled.
Slip of Zone 2
Number of slips for zone 2, i.e. number of slips before 'Trip 2
Signal' is signaled.
UN IN Impedance unit
100 V 1A 57.735 Ω/ph
100 V 2A 28.868 Ω/ph
100 V 5A 11.547 Ω/ph
200 V 1A 115.470 Ω/ph
200 V 2A 57.735 Ω/ph
200 V 5A 23.094 Ω/ph
3-247
ABB Switzerland Ltd RE.216 1KHA000951-UEN
t - Reset
The reset time 't - Reset' prevents the function from resetting
between two slips providing n1 or n2 is greater than 1.
Current Input Chan.
defines the A/D input channel.
Voltage Input Chan.
defines the A/D input channel.
Block Input Generator
Blocking input for detecting pole slip to the left, i.e. the generator is
faster than the power system.
Block Input Motor
Blocking input for detecting pole slip to the right, i.e. the generator
is slower than the power system.
(The power system drives the generator as if it were a motor.)
Block Input
Blocking input for the entire pole slipping function.
Enable Zone 1 Input
Zone 1 is enabled for slipping in zone 2 as well, i.e. independently
of ZC.
Warning Signal
Detection of variations of rotor angle (before the first slip occurs).
Generator Signal
Signals rotor movement to the left, i.e. the generator is faster than
the system.
Motor Signal
Signals rotor movement to the right, i.e. the generator is slower
than the system. (The power system drives the generator as if it
were a motor.)
Zone 1 Signal
First slip between ZB and ZC or between ZB and ZA, providing the
input 'Enable Zone 1 Input' is enabled.
Zone 2 Signal
First slip between ZC and ZA.
Trip 1 Signal
Tripping and signaling when the counter for zone 1 reaches the
value n1.
Trip 2 Signal
Signaling when the counter for zone 2 reaches the value n2. If
Trip2 is to control tripping, the signal Trip2 has to be assigned to a
tripping relay (see also Section 5.4.5.4.).
3-248
RE.216 1KHA000951-UEN ABB Switzerland Ltd
When the impedance crosses the slip line between ZB and ZC it counts
as being in zone 1 and between ZC and ZA in zone 2. The entire dis-
tance ZA-ZB becomes zone 1 when 'Enable Zone 1 Input' is enabled
(external device detects the direction of the centre of slipping).
After the first slip, the signals 'Zone 1 Signal' or 'Zone 2 Signal' and -
depending on the direction of slip - either 'Generator Signal' or 'Motor
Signal' are issued.
Every time pole slipping is detected, the impedance of the point where
the slip line is crossed and the instantaneous slip frequency are
displayed as measurements.
Further slips are only detected, if they are in the same direction and if
the change of the rotor angle detection has reset after the preceding
slip or the slip line is crossed in the opposite direction outside ZA-ZB.
A further slip in the opposite direction within ZA-ZB resets all the
signals and is then signaled itself as a first slip.
3-249
ABB Switzerland Ltd RE.216 1KHA000951-UEN
The 'Trip 1 Signal' tripping command and signal are generated after n1
slips in zone 1, providing the rotor angle is less than 'Trip Angle'.
The 'Trip 2 Signal' signal is generated after n2 slips in zone 2,
providing the rotor angle is less than 'Trip Angle'.
All signals are reset if:
• the direction of movement reverses,
• the rotor angle detector resets without a slip being counted or
• no rotor relative movement was detected during the time 't - Reset'.
3-250
RE.216 1KHA000951-UEN ABB Switzerland Ltd
3-251
ABB Switzerland Ltd RE.216 1KHA000951-UEN
F. Setting instructions
Setting: Phi
The angle Phi determines the angle of the slip line and is monitored to
detect slip. The impedances ZA, ZB and ZC lie on this line.
Phi is also used to check power direction, i.e. the polarity of the CTs:
60°... 90° CT neutral on the line side
i.e. connection according to Fig. 12.4
240°...270° CT neutral on the generator side
3-252
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Setting: ZA
ZA is the impedance of the slip line and marks the limit of zone 2. It is
also used for measuring phase-angle (see 'Warn Angle' and 'Trip
Angle').
ZA should be set to the impedance between the location of the
protection and the off-load voltage of the equivalent circuit for the
entire power system.
Setting: ZB
ZB is the impedance of the slip line in the reverse direction and marks
the limit of zone 1. It is also used for measuring phase-angle (see
'Warn Angle' and 'Trip Angle').
ZB should be set to the generator reactance Xd' in the reverse direction
(negative sign).
Setting: ZC
ZC divides the slip line into two zones. Zone 1 lies between ZB and ZC
and zone 2 between ZC and ZA.
ZC should be set to the impedance from the location of the protection
up to the first busbar.
Fig. 3.60 Determining the settings for ZA, ZB, ZC, and Phi
according to Xd', XT and ZS
3-253
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Example:
Zone 1 Zone 2
X'd XT ZS
~ ~
U cos ϕ
78
3-254
RE.216 1KHA000951-UEN ABB Switzerland Ltd
3-255
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Setting: TripAngle
Phi is evaluated in relation to 'Trip Angle' when one of the zones has
reached its number of slips, i.e. n ≥ n1 or n2.
For a setting of 'Trip Angle' = 180°, the tripping command 'Trip1' and
the signals 'Trip 1 Signal' and 'Trip 2 Signal' are issued immediately.
For a setting of 'Trip Angle' = 0°, these signals are only issued when
the slip detector has reset, i.e. when the generator is again close to
synchronism with the power system.
A setting of 'Trip Angle' between 180° and 0° (typically 90°) determines
the rotor angle at which tripping takes place and the signals are
generated.
The setting at which tripping should take place is determined accord-
ing to an operating point that
• occurs shortly after the last permissible slip
• is favorable for the circuit-breaker (least stress due to reignition)
Typical setting: 'Trip Angle' = 90°
3-256
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
The sensitive E/F protection (EarthFaultIsol) detects E/Fs on overhead
lines in radial systems. It is suitable for application in ungrounded
systems, systems with Petersen coils and in resistance grounded MV
and HV systems. The scheme monitors the neutral voltage and current
of the protected line. Depending on the characteristic angle chosen, it
responds to either the real or apparent value of the neutral power.
B. Features
• Adjustable characteristic angle
• Compensation of CT phase errors
• Suppression of DC component in voltage and current signals
• Suppression of harmonics in voltage and current signals
I. CT/VT inputs:
• Neutral current
• Neutral voltage
3-257
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-258
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Phi-Comp
Compensation of CT and VT phase errors. The setting concerns
only the difference between the two errors.
Current Inp Chan
Defines the CT input channel used for the neutral current. Only
single-phase CT inputs can be set.
Voltage Inp Chan
Defines the VT input channel used for the neutral voltage. Only
single-phase VT inputs can be set.
Block Inp
Input for blocking the sensitive E/F function.
Trip
Tripping signal.
Start Out
Starting signal.
3-259
ABB Switzerland Ltd RE.216 1KHA000951-UEN
E. Setting instructions
Settings:
Pick-up power P Setting
Characteristic angle Angle
Reset ratio Drop-Ratio
Delay Delay
Phase error compensation Phi-Comp
Rated power PN
The value entered for 'P Setting' is the power at which the function
picks up referred to rated power 'PN'. The parameter 'P Setting' has a
setting range of 0.005 to 0.100 in steps of 0.001.
The setting of the parameter 'Angle' determines the characteristic
angle of the measurement. Its implications are explained below under
'Real power' and 'Apparent power'.
The desired reset ratio is set as a percentage of the pick-up value
using the parameter 'Drop-Ratio'. To ensure that the reset ratio is
adequate for low values of 'P Setting', the following condition is
checked:
50
' Drop - Ratio' < 100 −
100 × ' P − Setting' + 1
An angle to compensate the relative phase errors of CTs and VTs can
be entered using parameter 'Phi-Comp'. The effective characteristic
angle is the sum of the parameters 'Angle' and 'Phi-Comp'.
The setting for the rated power is left at PN = 1.000. The corre-
sponding reference value in the 'ANALOGUE CT/VT CHANNELS-AD
CHANNEL REF VAL' menu must be adjusted for rated voltages other
than 100 V.
Real power
The real power component (real power component = proportion of real
power current x displacement voltage) of the zero-sequence power is
monitored to detect E/Fs in systems with Petersen coils and high-
resistance grounded systems. The neutral component of the current in
the healthy phases resulting from their capacitances to ground and the
inductive Petersen coil current unite at the fault location and return to
the source via the faulted phase.
A power relay is installed at both ends of every line with the exception
of stub lines, which only require a relay at the source end. If the E/F
current is too low and has to be artificially increased, an overvoltage
relay is fitted to detect the displacement voltage and connect a
grounding resistor temporarily to the star-point. To avoid any incorrect
response of the power relays while this is being done, they are
enabled after a short delay. The section of the line with the fault is
determined by comparison of the relay directions.
3-260
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Note:
The connections must be made in strict accordance with the ABB
wiring diagram.
3-261
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Apparent power
The apparent power component of the neutral power is monitored to
detect E/Fs in ungrounded systems. Every feeder is equipped with a
relay. During an E/F, the capacitive E/F current of the entire system
less that of the faulted line flows into the faulted line. Only the E/F relay
of the faulted line indicates power flowing into its line.
The minimum capacitive E/F current available to operate the relays is
the total capacitive E/F current of the whole system for the smallest
configuration to be expected less that of the faulted line. Of this
capacitive current, only the percentage corresponding to the assumed
minimum displacement voltage at which the protection is still required
to operate may be considered. If there are any double-circuit lines, the
division of current between the circuits must also be taken into
account.
To allow for the CT errors at such low current levels, the pick-up value
set on the relay must be less than the product of the minimum current
determined above and the minimum voltage.
The parameter 'Angle' must be set to -90° pick up for E/Fs in the
forwards direction and 90° for the reverse direction.
Note:
The connections must be made in strict accordance with the ABB
wiring diagram.
Time delay
The delay required between the picking up of the relay ('start') and
tripping ('Trip') is set by means of parameter 'Delay'. The setting range
provided is 0.05 to 60 s in steps of 0.01.
CT/VT inputs
The two CT and VT input channels 'CurrentInp' (current) and 'Voltage-
Inp' (voltage) have to be configured for the purpose. The current input
channel may only be allocated to a single-phase metering (core-
balance) CT and the voltage channel to a single-phase VT.
3-262
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
High-resistance earth faults, which cannot be detected by the distance
protection, can still cause appreciable problems in spite of the rela-
tively low fault currents involved.
The sensitive E/F protection function ((EarthFltGnd2)) has been
included to complement the main line protection function and cover the
low E/F current range. The protection processes the zero-sequence
components 3I0 and 3U0.
B. Features
• DC component filter
• Harmonic filter
• Directional measurement of zero-sequence components (derived
either internally or externally)
• Current pick-up enabling level
• Reference voltage enabling level
• Adjustable characteristic angle
• Permissive and blocking transfer tripping schemes
• Echo logic for weak infeed and open circuit-breaker
• Transient blocking logic for reversal of energy direction
I. CT/VT inputs:
• Voltage
• Current
IV. Measurements:
• Neutral voltage (3U0)
• Neutral current (3I0)
• Real power component of neutral power (3U0 x 3I0)
3-263
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-264
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Explanation of parameters:
Run On CPU
Defines on which CPU the function should operate.
Trip
Tripping logic (matrix).
3-265
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-266
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Echo Mode
Echo logic for weak infeed and open CB:
• Off echo logic disabled
• Weak echo only for weak infeed
• Brk. echo only when CB open
• Weak & Brk. echo for weak infeed or CB open
3-267
ABB Switzerland Ltd RE.216 1KHA000951-UEN
E. Setting instructions
3.5.28.1. Coordination with the distance protection
3-268
RE.216 1KHA000951-UEN ABB Switzerland Ltd
If this time is too short, there is a likelihood that the E/F protection will
issue a three-phase trip before the circuit-breaker has opened for
faults that have been correctly detected by the distance protection.
The basic time of the E/F protection must therefore be long enough to
ensure that the distance protection can trip phase-selectively.
No facility is provided for using the distance relay starters to achieve
phase-selective tripping by the directional E/F function.
An independent directional E/F function requires its own
communication channel, which must be entirely independent of the
distance protection.
3.5.28.2. Choice of operating mode
It is assumed that the E/F protection settings at both ends of the pro-
tected line are the same. This applies especially to the basic time, the
blocking time, the transfer tripping scheme in use and options.
3.5.28.3. Choice of transfer tripping scheme
In the case of a permissive directional comparison scheme, the
amount of fault resistance, which can be detected reduces towards the
remote end of the line, because the enabling current must be
exceeded at both ends. Without additional precautions, the use of a
permissive scheme would be limited on lines with a weak infeed at one
end.
It was possible to eliminate this disadvantage by providing the
directional E/F protection with its own echo logic for weak infeeds that
can be switched in and out as required.
3-269
ABB Switzerland Ltd RE.216 1KHA000951-UEN
& &
Rel. 1 Rel. 2
A1 A2
HEST 925 020 C
where:
Start : current higher than the enabling level 'I setting'
t Basic : basic time
MeasFwd : fault in forwards direction
3-270
RE.216 1KHA000951-UEN ABB Switzerland Ltd
I set
I dir
Iasymm
U set
U0
Basic operation mode
where:
<...> : optional function
Rx : receive
MeasFwd : fault in forwards direction
MeasBwd : fault in backwards direction including 'Transient
blocking'
MeasBwd' : fault in backwards direction
I dir : current enable for directional measurement
(= 0.7 I-Setting)
I-Setting : current enabling level
Iasymm : asymmetrical currents under normal load conditions
Tx : send
T : trip
TB : transient blocking
t TransBlk : blocking time
t Basic : basic time
t Wait : waiting time
U-Setting : reference voltage
3-271
ABB Switzerland Ltd RE.216 1KHA000951-UEN
tBasic tBasic
I-dir I-dir
I-Setting I-Setting
Send Send
MeasBwd MeasBwd
MeasFwd Receive Receive MeasFwd
& &
tWait tWait
Rel. 1 Rel. 2
A1 A2
HEST 925 021 FL
where:
I-Setting
: current enabling level
I-dir : current enable for directional measurement
(= 0,7 I-Setting)
t Basic : basic time
t Wait : waiting time
MeasFwd : fault in forwards direction
MeasBwd : fault in backwards direction
3-272
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Iasymm
U set
U0
Basic operation mode
3-273
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Iasymm
I - Setting = 2.0
IN
• The voltage pick-up must be set to 1.6 times the level of the
spurious voltages, which can occur due to asymmetries in the VT
secondary circuit.
Usec.asymm
U - Setting = 1.6
UN
where:
U-Setting : setting of the enabling voltage for the directional
measurement
Usec.asymm : voltage component 3 U0 caused by asymmetries in the
VT secondary circuit (e.g. VT errors)
UN : 100 V or 200 V according to VT unit in use
I-Setting : setting of the enabling current
Iasymm : current component 3I0 caused by asymmetrical load
currents
IN : primary CT rated current
3.5.28.5. Setting the characteristic angle 'Angle'
The line marking the reversal of direction lies at ± 90° in relation to the
reference voltage.
In order to achieve symmetrical operation of the directional element in
spite of this, the characteristic angle should equal that of the zero-
sequence impedance of the source.
3-274
RE.216 1KHA000951-UEN ABB Switzerland Ltd
3-275
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Ext. block
Exciting the 'Ext. block' I/P disables the entire protection function.
Receive
The signal transmitted by the protection in the opposite station is con-
nected to this I/P.
CB closed
The 'CB closed' I/P is intended for the position indicator signal from the
circuit-breaker and has a fixed pick-up delay of 50 ms. The protection
function is only enabled when this signal is received to confirm that the
CB is closed. The corresponding auxiliary contacts for the three
phases must be connected in series to ensure that the protection does
not operate during single-phase reclosure.
The echo logic is enabled 100 ms after the circuit-breaker is opened.
VT Supervision
The 'VT Superv' I/P is needed to block the echo logic. It can be excited
either by the 'VTSup' signal from the internal distance protection func-
tion or an auxiliary contact on the m.c.b. via a binary I/P.
If this I/P is not needed, it must be set to 'F'.
3-276
RE.216 1KHA000951-UEN ABB Switzerland Ltd
3.5.28.13. Outputs
Trip
There are two 'Trip' signals, one for energizing the tripping relay via
the tripping logic and the other for controlling LEDs and signaling
contacts.
Start
An active 'Start' O/P signals that the zero-sequence current has
exceeded the pick-up setting 'I-Setting'. This signal is only generated
providing the function is not blocked.
Meas Forward
'MeasFwd' is active when the measuring element detects a fault in the
forwards direction, i.e. the settings of 'I dir' and 'U setting' have been
exceeded.
Meas Backward
'MeasBwd' is active when the measuring element detects a fault in the
backwards direction, i.e. the settings of 'I dir' and 'U setting' have been
exceeded.
Send
The 'Send' O/P is the signal sent to the other end of the line.
Receive Inh.
The 'Recve Inh' signal prevents the distance function from receiving a
PLC signal (see Section 3.5.28.1.). It is only generated when the
parameter '1 Channel' is set, the basic time has expired or the E/F
protection picks up for a reverse fault.
The signal 'Receive Inh.' must be connected to the distance function
I/P 'ExtBlkHF'.
3-277
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-278
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
Overcurrent function with IDMT characteristic. A typical application is
as back-up for the E/F protection function, in which case it measures
3 I0 either supplied from an external source or internally derived.
B. Features
• Tripping characteristic according to British Standard 142
(see Fig. 3.66):
c = 0.02 : normal inverse
c=1 : very inverse and long time earth fault
c=2 : extremely inverse
• RXIDG : logarithmic time characteristic
• DC component filter
• Harmonic filter
• External 3 I0 signal or 3 I0 internally derived from the three phase
currents
• Wider setting range than specified in BS 142
I. CT/VT inputs:
• Current
IV. Measurements:
• Neutral current
3-279
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Explanation of parameters:
Run On CPU
Defines on which CPU the function should operate.
Trip
Tripping logic (matrix).
c - Setting
Setting for the exponential factor determining the shape of the
operating characteristic according to BS 142 or for selecting the
RXIDG characteristic.
K1 - Setting
Constant determining the tripping characteristic.
I - Start
Pick-up setting (initiates the tripping characteristic).
Min. Tripping Time
Definite minimum time of the tripping characteristic.
IB - Setting
Reference current to take account of discrepancies with respect to IN.
Number Of Phases
Number of phases evaluated for measurement:
1 Ph: neutral current direct from an CT input
3 Ph: neutral current derived internally from the three phases
3-280
RE.216 1KHA000951-UEN ABB Switzerland Ltd
3-281
ABB Switzerland Ltd RE.216 1KHA000951-UEN
E. Setting instructions
3-282
RE.216 1KHA000951-UEN ABB Switzerland Ltd
t [s] k1 [s]
0.5 2.5
1 5
1.5 7.5
2 10
2.5 12.5
3-283
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Typical settings:
IB to be calculated
I-Start 1.1 IB
c-Setting depends on the protected unit
k1-Setting to be calculated
t-min 0.00
3-284
RE.216 1KHA000951-UEN ABB Switzerland Ltd
3-285
ABB Switzerland Ltd RE.216 1KHA000951-UEN
The setting range for 'I Load' is 0...2 IN in steps of 0.01 IN (default
setting = 0.5 IN), where:
'I Load' = 0.01...1.99 IN: Characteristic switches as de-
scribed above.
'I Load' = 0 IN: Fixed slope of 14°
'I Load' = 2 IN: Fixed slope of 7°
3-286
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
Distance protection for the high-speed discriminative protection of long
or short overhead lines or cables, double-circuit lines, heavily loaded
lines, lines with weak infeeds and what are referred to as 'short-zone'
lines.
The protection is applicable to solidly or low-resistance grounded
systems, systems with Petersen coils or to ungrounded systems.
All kinds of faults are detected including close-in three-phase faults,
cross-country faults, evolving faults and high-resistance earth faults.
The protection remains stable in the presence of power swings and
reversal of energy direction. Switching onto an existing fault results in
instantaneous tripping of the circuit breaker.
The distance function can also act as back-up protection for the power
transformer and neighboring lines. Most of the logic described in this
Section (e.g. the transmission of signals) is not used for these
applications.
B. Features
• Overcurrent or underimpedance starters (polygon characteristic)
• 5 distance stages (independently set polygon characteristics)
• Definite time overcurrent back-up protection also applicable for
protecting short zones (teed section in 1½ breaker schemes
(see Section 4.8.4.))
• VT supervision
• Power-swing blocking
• Tripping logics for:
• switch-onto-fault protection
• overreaching zone
• permissive underreaching transfer tripping (also for weak
infeed and communications channel failure)
• permissive overreaching transfer tripping (also for weak infeed,
communications channel failure and reversal of energy
direction)
• blocking scheme (also for reversal of energy direction)
3-287
ABB Switzerland Ltd RE.216 1KHA000951-UEN
I. CT/VT inputs:
• Three-phase currents
• Three-phase voltages
• Neutral current
• Neutral current of the parallel circuit
3-288
RE.216 1KHA000951-UEN ABB Switzerland Ltd
IV. Measurements:
• Impedance loop RE
• Impedance loop SE
• Impedance loop TE
• Impedance loop RS
• Impedance loop ST
• Impedance loop TR
3-289
ABB Switzerland Ltd RE.216 1KHA000951-UEN
GENERAL
CT/VT INPUTS
MEASUREMENT
1)
Not available on HV distance function.
2)
Different settings for the HV distance function.
3-290
RE.216 1KHA000951-UEN ABB Switzerland Ltd
3-291
ABB Switzerland Ltd RE.216 1KHA000951-UEN
I O/C IN 0 0 10 0.01
Delay O/C s 5 0 10 0.1
VT SUPERVISION
TRIP SCHEMES
BINARY INPUTS
3-292
RE.216 1KHA000951-UEN ABB Switzerland Ltd
CB COMMANDS
SIGNAL OUTPUTS
3-293
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Delay 1 SignalAddr
Delay 2 SignalAddr ER
Delay 3 SignalAddr ER
Delay 4 SignalAddr ER
Delay Def SignalAddr ER
Meas Main SignalAddr
Meas Oreach SignalAddr
Meas Fward SignalAddr
Meas Bward SignalAddr
Weak Infeed SignalAddr
Dist Blocked SignalAddr
Del Dist Blocked SignalAddr ER
Power Swing SignalAddr ER
VT Sup SignalAddr
VT Sup Delay SignalAddr
Com Send SignalAddr ER
Com Boost SignalAddr
Freq Dev SignalAddr
1) Start OC SignalAddr ER
1) Start UZ SignalAddr
ADDITIONAL LOGIC
3-294
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Explanation of parameters:
GENERAL
Run On CPU
Defines on which CPU the function should operate.
Reference Length (see Section 3.5.31.1.)
Reactance (secondary value) to be used as reference length of the
line.
CT neutral (see Section 3.5.31.1.)
Side of the CTs on which the star-point is formed (current di-
rection):
busbar side (old BBC diagram)
line side (standard today,
see wiring diagram in the Chapter 12)
This parameter only influences the distance function and only the
display of the system variables. It does not influence the values of
the A/D channels.
Reset Events (see Page 3-306)
Determination of whether all the distance function events in the
event list which have been reset should be displayed:
All
Partly
Fupla directory
The sub directory for the distance protection logic is selectable.
The default directory name 'DISTSTD' is valid in case the standard
distance protection logic is utilized, which is situated in the HMI sub
directory.
A different configuration is necessary only if instead of the standard
distance logic a special distance protection logic is utilized. The
procedure in this case has to be obtained from the associated logic
description.
CT/VT INPUTS
U input
indicates the first of the VT inputs assigned to the three phase
voltages.
I input
indicates the first of the CT inputs assigned to the three phase
currents.
I0 input
indicates the CT input assigned to the neutral current (if fitted and
activated). This is used for the external acquisition of the neutral
current of the line. If the I0 input is not used, the neutral current is
derived from the phase currents.
3-295
ABB Switzerland Ltd RE.216 1KHA000951-UEN
I0P input
indicates the CT input assigned to the neutral current of the parallel
circuit (if fitted and activated). This is used for the neutral current of
the parallel circuit of a double-circuit line.
Note:
The CT input (I0P) should be wired in the same sense as the
neutral current input (I0) (e.g. terminals 9 and 10 correspond to
terminals 7 and 8 respectively).
1)
Not available on HV distance function.
2)
Different settings for the HV distance function.
3-296
RE.216 1KHA000951-UEN ABB Switzerland Ltd
3U0 Min
Voltage level of the neutral voltage (3U0) at which the E/F
measurement is enabled (ground fault detector).
XA
Reactive reach of the impedance characteristic in the tripping
direction.
XB
Reactive reach of the impedance characteristic in the restraint
direction.
RA
Resistive reach of the impedance characteristic in the tripping
direction.
RB
Resistive reach of the impedance characteristic in the restraint
direction.
RLoad
Resistive reach for avoiding load encroachment.
Angle Load
Limit phase-angle for avoiding load encroachment.
Uweak
(Phase) Voltage pick-up value for determining the 'weak infeed' or
'dead line' conditions for enabling manually energization of the line.
A setting of zero disables the function.
3-297
ABB Switzerland Ltd RE.216 1KHA000951-UEN
k0 Angle (n)
Phase-angle of the zero-sequence compensation factor for E/Fs in
Zone (n); Arg [(Z 0 − Z1 ) / (3 × Z1 )] .
Delay (n)
Operating time for Zone (n).
X (BACK)
Pick-up line reactance for the reverse zone:
X = 0 zone disabled.
R (BACK)
Pick-up line resistance for the reverse zone.
RR (BACK)
Resistive reach for phase faults in the reverse zone.
RRE (BACK)
Resistive reach for E/Fs in the reverse zone.
Delay (Def) (see Section 3.5.31.4.)
Operating time for the final zone (starter reach).
k0m
Value of the zero-sequence compensation factor for a parallel
circuit (ratio of the mutual impedance to three times the positive-
sequence impedance); Zm0 / (3 × Z1) . The mutual impedance is
not taken into account for a setting of zero.
k0 Angle(m)
Phase-angle of the zero-sequence compensation factor for a
[ ]
parallel circuit Arg Zm0 / (3 x Z1) .
3-298
RE.216 1KHA000951-UEN ABB Switzerland Ltd
VT SUPERVISION
(see Section 3.5.31.6. / 4.8.3.)
VT Sup Mode
0 Off
1 ZeroSeq [U0 ⋅ I0]
2 NegSeq [U2 ⋅ I2]
3 Zero ⋅ NegSeq [(U0 ⋅ I0) + (U2 ⋅ I2)]
4 Special [U2 ⋅ (I0 + I2)]
VT Sup Blk Del
Delayed blocking of the distance function (12 s) for operation
of the VT supervision.
Off immediate blocking
On delayed blocking
VT Sup Deb Del
Delay (1 s) for resetting blocking by the VT supervision.
Off immediate reset
On delayed reset
U0 min VT Sup
Pick-up setting of the neutral voltage (U0) for VT supervision
referred to the rated VT voltage 100/ 3 or 200/ 3 .
I0 min VT Sup
Pick-up setting of the neutral current (I0) for VT supervision.
3-299
ABB Switzerland Ltd RE.216 1KHA000951-UEN
U2 min VT Sup
Pick-up setting of the negative sequence voltage (U2) for VT
supervision referred to the rated VT voltage 100/ 3 or 200/ 3 .
I2 min VT Sup
Pick-up setting of the NPS current (I2) for VT supervision.
3-300
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Unblock
Deblocking logic enable:
Off
On (only suitable for PLC)
Echo
'Echo' logic enable for the POTT transfer tripping mode:
Off
On
Trans Block
Enables 'Transient blocking' logic (stabilization for reversal of
power direction on double-circuit lines) for the POTT and BLOCK
OR (overreaching blocking scheme) transfer tripping modes:
Off
On
t1 Block
Time allowed for receiving a blocking signal in the BLOCK OR
(overreaching blocking scheme) mode.
t1 Trans Block
Time 1 for the TRANSBL (transient blocking) mode. Delay for
faults after a fault was detected in the reverse direction.
t2 Trans Block
Time 2 for the TRANSBL (transient blocking) mode. The logic
remains enabled for the time t2 after a fault was detected in the
reverse direction.
t1 Evol Faults
Time for discriminating evolving faults (three-phase trip for evolving
faults during this time setting).
1)
Not available on HV distance function.
3-301
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-302
RE.216 1KHA000951-UEN ABB Switzerland Ltd
CB COMMANDS
Trip CB R
Tripping logic for the R phase pole of the circuit-breaker. This
signal is not generated while a blocking signal is being applied with
the exception of a trip by the back-up overcurrent protection.
Trip CB S
Tripping relay for the S phase pole of the circuit-breaker. This
signal is not generated while a blocking signal is being applied with
the exception of a trip by the back-up overcurrent protection.
Trip CB T
Tripping relay for the T phase pole of the circuit-breaker. This
signal is not generated while a blocking signal is being applied with
the exception of a trip by the back-up overcurrent protection.
SIGNALING
Start R+S+T
General distance protection starting signal
(OR logic for all starting signals excluding 'weak infeed').
Start RST (StartRSTAux)
General distance protection starting signal
(OR logic for all starting signals including 'weak infeed').
Start R (Start R Aux)
Distance protection R phase starting signal
(including 'weak infeed').
Start S (Start S Aux)
Distance protection S phase starting signal
(including 'weak infeed').
Start T (Start T Aux)
Distance protection T phase starting signal
(including 'weak infeed').
Start E (Start E Aux)
Distance protection E/F starting signal (U0 or I0). Only generated
together with a phase starter.
Start I0
Neutral current starting signal (I0).
Start U0
Neutral voltage starting signal (U0).
Start O/C
Back-up overcurrent pick-up signal.
Start SOTF
Enabling signal for the switch-onto-fault protection.
Start 1ph
Indicates that the distance protection was started by a single
phase.
3-303
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Trip CB
General circuit-breaker tripping signal. This signal is disabled while
a blocking signal is being applied with the exception of a trip by the
back-up overcurrent protection.
Trip RST (trip RST Aux)
General tripping signal. This signal is not disabled while a blocking
signal is being applied.
Trip CB R
Circuit-breaker R phase trip signal.
This signal is disabled while a blocking signal is being applied with
the exception of a trip by the back-up overcurrent protection.
Trip CB S
Circuit-breaker S phase trip signal.
This signal is disabled while a blocking signal is being applied with
the exception of a trip by the back-up overcurrent protection.
Trip CB T
Circuit-breaker T phase trip signal.
This signal is disabled while a blocking signal is being applied with
the exception of a trip by the back-up overcurrent protection.
Trip CB 3ph
Three-phase trip signal. This signal is disabled while a blocking
signal is being applied with the exception of a trip by the back-up
overcurrent protection.
Trip CB 1ph
Single-phase trip signal. This signal is disabled while a blocking
signal is being applied with the exception of a trip by the back-up
overcurrent protection.
Trip O/C
Back-up overcurrent trip signal.
Trip SOTF
Switch-onto-fault trip signal.
Trip Com
Signal for tripping either enabled by the receipt of a permissive
signal or the non-receipt of a blocking signal. (This signal is
disabled while a blocking signal is being applied.)
Trip Stub
'Short-zone' protection trip signal.
Delay >= 2
Signal for starting in Zone 2 or higher.
Delay 1
Signal for starting in Zone 1.
3-304
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Delay 2
Signal for starting in Zone 2.
Delay 3
Signal for starting in Zone 3.
Delay 4
Signal for starting in Zone 4 (excepting when Zone 4 is being used
as an overreaching zone).
Delay Def
Signal for starting in the final zone.
Meas Main
Measurement by the distance function (Zones 1, 2, 3, 4 or the final
zone).
Meas Oreach
Measurement in the distance protection overreach zone.
Meas Fward
Measurement by the distance protection in the forwards direction.
Meas Bward
Measurement by the distance protection in the reverse direction
(reverse zone).
Weak Infeed
Tripping by the 'weak infeed' function.
Dist Blocked
Signal indicating that the distance protection is blocked.
Del Dis Blocked
Signal delayed by 12 s indicating that the distance protection is
blocked.
Power Swing
Power-swing blocking function picked up.
VT Sup
VT supervision picked up.
VT Sup Delay
Delayed operation of the VT supervision after 12 s.
Com Send
Signal generated when a transfer trip signal is transmitted.
Com Boost
Signal for boosting PLC transmitting power.
Freq Dev
Signal indicating a deviation of the memory voltage frequency.
3-305
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Start OC 1)
Overcurrent starting signal.
Start UZ 1)
Underimpedance starting signal.
ADDITIONAL LOGIC
The following settings are only of consequence when a special logic is
loaded instead of the standard distance protection logic. Refer to the
description of the corresponding logic for their significance.
BOOL_IN1, BOOL_IN2...BOOL_IN8
Additional binary inputs for the special distance protection logic.
TIMER_1, TIMER_2...TIMER_8
Additional timer settings for the special distance protection logic.
BOOL_OUT1, BOOL_OUT2...BOOL_OUT8
Additional signals for the special distance protection logic.
1)
Not available on HV distance function.
3-306
RE.216 1KHA000951-UEN ABB Switzerland Ltd
3-307
ABB Switzerland Ltd RE.216 1KHA000951-UEN
E. Setting instructions
3.5.31.1. General
The first parameter in the sub-menu 'General' is 'Ref length' which is
needed to indicate the distance to a fault in the event of a trip, but
otherwise bears no influence in the protection function. The parameter
gives the reactance of the reference length (in secondary Ω/ph per unit
length) and may be defined in km, miles, percent line length etc., i.e.
Xmeas.
distance =
ref. length
e.g.:
c) In km
Secondary reactance per km ≡ 0.2 Ω/ph
Ref. length = 0.2 Ω/ph
3-308
RE.216 1KHA000951-UEN ABB Switzerland Ltd
3.5.31.2. Starters
(see Section 4.8.1.)
The distance function provides for two methods of starting, i.e.
overcurrent or underimpedance. The desired method is selected by
appropriately setting the parameter 'Start Mode' in the 'Starting' sub-
menu.
Depending on the setting of the parameter 'Def Dir Mode', a starter
can also trip on its own after the time 'Delay (Def)'. (see
Section 3.5.31.4.)
IB max + IA
(Istart ) min > 1.25
0.95 × IN
The maximum setting (Istart)max is derived from the minimum fault
current IK for a fault at the end of the next section of line:
(Istart ) max < IK min / IN
Should the above relationships result in (Istart)max being lower than
(Istart)min, the underimpedance starters must be used instead.
3.5.31.2.2. Underimpedance starters
(see Section 4.8.1.3.)
Selecting ‘UZ’ as the ‘Start Mode’ parameter enables the
underimpedance starters. The following parameters then have to be
set:
3-309
ABB Switzerland Ltd RE.216 1KHA000951-UEN
XA
XB
RA
RB
RLoad
AngleLoad
The characteristic of the underimpedance starters and the correspond-
ing setting parameters can be seen from Fig. 3.67. The parameters
'RLoad' and 'AngleLoad' define the permissible load area.
X
XA
UNDERIMPEDANCE
CHARACTERISTIC
3-310
RE.216 1KHA000951-UEN ABB Switzerland Ltd
U
Z set ≤ Ω/ph
2 × (IB max + IA )
where:
Zset maximum value of the impedance, i.e. the maximum value of
the expression:
3-311
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-312
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Z3 = 0.85 (a + k · b2)
Z2 = 0.85 (a + k · b1)
b2
Z1 = 0.85 · a
b1
ZAZ = 1.2 · a
a b
A B C
HEST 935 050 C
Fig. 3.68 Typical settings for the reaches of distance relay zones
(grading table)
where:
Z1, Z2, Z3, Z4 impedance reach of the various zones
[Ω/ph]
ZOR impedance reach of the overreaching zone
[Ω/ph]
k≥1 factor to take into account -
the apparent increase of line impedance 'seen' by a
relay due to an intermediate infeed
a, b impedance of the corresponding section of line
[Ω]
3-313
ABB Switzerland Ltd RE.216 1KHA000951-UEN
A B I A'+ I C
1 2 B'
3 4
D
~ I A'
~
5
ZLP ZLp
ZLs = =
⎛ KU ⎞ KZ
⎜ ⎟
⎜K ⎟
⎝ I ⎠
where:
ZLp primary positive-sequence line impedance
ZLs secondary positive-sequence line impedance
KU main VT ratio
KI main CT ratio
KZ impedance ratio
The same applies to the conversion of the resistances and reactances.
The impedance characteristic is defined independently for each of the
four distance zones (Zone 4 is used alternatively for the overreaching
zone) by the following parameters (i = 1 to 4):
X (i)
R (i)
RR (i)
RRE (i)
k0 (i)
k0Ang (i)
Delay (i)
3-314
RE.216 1KHA000951-UEN ABB Switzerland Ltd
The reactance and resistance of the line or cable are set in the
proper units using the parameters 'R' and 'X' (see Fig. 3.70).
X
X
7°
Zone 1
(2, 3, 4, OR, BWD)
27°
-X/8 R RR RRE
27° R
-RR/2
-RRE/2
3-315
ABB Switzerland Ltd RE.216 1KHA000951-UEN
where:
d length of arc in m
I current in A
RB arc resistance in Ω
Since the unit is Ω/ph, the fault resistance appears differently in the
impedance plane according to the type of fault. Where the value of the
fault resistance RF is known in Ω (see Fig. 3.71), it has to be entered
in the R/X diagram as follows:
• E/F: R=RF/(1+k0)
• phase-to-phase fault: R=RF/2
RF
RF RF RF
RF
HEST 915 029 C
3-316
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Underimpedance
characteristic
Zone 3
Zone 2
Zone 1
RLoad
AngleLoad
R
REVERSE ZONE
Note that the load impedance area is only formed when the under-
impedance starter (UZ) is in operation. It does not exist when starting
is provided by the overcurrent starter (OC).
3-317
ABB Switzerland Ltd RE.216 1KHA000951-UEN
k 0 = 1 / 3 x (Z 0L − ZL ) / ZL )
3-318
RE.216 1KHA000951-UEN ABB Switzerland Ltd
jX
(2 × RL + R0L) / 3
∠k0
XL
k0 × ZL Ph-Ph
XL - k0 × XL
ZL 2 × ZL + Z0) / 3 Ph-E
RR RRE
3-319
ABB Switzerland Ltd RE.216 1KHA000951-UEN
NOTE: In order that this logic functions properly the reverse zone
must further than that of the overreach zone of the oppposite side.
This is also applicable for the reach in the ohmic direction.
To note:
• for underimpedance starting ('Z<'):
With the exception of the load discrimination defined by the
parameters 'RLoad' and 'Angle Load', the reverse zone operates
independently of the starters.
• for overcurrent starting ('I>'):
The reverse zone is only in operation when an overcurrent starter
('I Start') has picked up.
• the binary input ('Ext. UZ Block') blocks operation regardless of the
starter mode for the reverse zone.
• Signal output: 'Meas Bward'.
• Measurement of the reverse zone only takes place while the first
zone is active, i.e. the 'Meas Bward' signal resets, when 'Delay (2)'
has elapsed.
3-320
RE.216 1KHA000951-UEN ABB Switzerland Ltd
3-321
ABB Switzerland Ltd RE.216 1KHA000951-UEN
XA
Definitive Zone
27°
R
27°
Directional
(in tripping direction)
The parameter 'Def Dir Mode' determines the response at the end of
the definitive time. It can be set to be either directional (in tripping
direction) or non-directional (see Fig. 3.74).
3-322
RE.216 1KHA000951-UEN ABB Switzerland Ltd
The pick-up signal of the overcurrent unit is also used by the STUB
protection. If the function is being used for this purpose, i.e. the binary
I/P 'Isol open' is at logical '1', the tripping time is fixed at 25 ms.
The back-up overcurrent is always active. In case the STUB protection
is not utilized, and; the 'O/C BACK-UP PROTECTION' should only be
active when the distance protection is blocked, then connect the
inverted signaling output 'Dist Blocked' from the distance protection to
the blocking input 'Ext Blk OC' of the O/C backup protection.
3.5.31.6. VT supervision
(see Section 4.8.3.)
The parameters for setting the VT supervision function are located in
the sub-menu 'VT SUPERVISON'. One of four different operating
modes can be chosen using 'VTSupMode'. The function processes
zero and negative-sequence components, which are either used on
their own ('ZeroSeq' and 'NegSeq') or combined ('Zero*NegSeq' and
'Spec').
ZeroSeq [U0 ⋅ I0]
NegSeq [U2 ⋅ I2]
Zero ⋅ NegSeq [(U0 ⋅ I0) + (U2 ⋅ I2)]
Spec [U2 ⋅ (I0 + I2)]
The four pick-up values are the settings of the parameters
'U0min VTSup', 'U2min VTSup', 'I0min VTSup' and 'I2min VTSup'.
They can be set between 0 and 2 UN (or IN) in steps of 0.01. The basic
settings are 0.2 UN for the voltage and 0.07 IN for the current.
Only the 'NegSeq' or 'Spec' options are available in ungrounded
systems.
Upon operating, the VT supervision function is normally required to im-
mediately block the distance protection function (see Section 4.8.5.2.).
Provision is made, however, for blocking the distance function after a
delay of 12 s by setting the parameter 'VTSupBlkDel'. This parameter
is normally set in cases where only the overcurrent starters are in use.
If the VT supervision function remains picked up for longer than 12 s, it
resets only after a delay (1 s). Should a fault give rise to zero or
negative-sequence current components, it resets immediately.
The parameter 'VTSupDebDel' (deblocking) enables the reset delay to
be continuously enabled regardless of current.
3-323
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Recommended setting:
PUTT NONDIR
Permissive underreaching transfer tripping (non-directional)
'Weak' - enables the weak infeed logic.
PUTT FWD
Permissive underreaching transfer tripping (in line direction)
No other parameters.
PUTT OR2
Permissive underreaching transfer tripping (overreaching zone/Zone 2)
'Unblock' - selects the enabling logic for communications
channel failure.
POTT
Permissive overreaching transfer tripping
'Weak' - enables the weak infeed logic.
'Unblock' - selects the enabling logic for communications
channel failure.
'Echo' - enables the echo logic.
'Trans Block' - enables the logic for reversal of fault energy
't1 Trans Block' - min. holding time for the wrong energy direction
signal. This has to be set at least 50 ms longer than
the maximum reset time required by the communi-
cation channel.
3-324
RE.216 1KHA000951-UEN ABB Switzerland Ltd
BLOCK OR
Blocking scheme
'TransBlock' - enables the logic for reversal of fault energy
't1 Block' - time allowed for the receipt of a PLC signal
't1 Trans Block' - min. holding time for the wrong energy direction
signal. This has to be set at least 50 ms longer than
the maximum signal transmission time.
't2 Trans Block' - max. holding time for the wrong energy direction
signal. This has to be set at least 0.4 s longer than
the dead time setting to make sure that blocking is
still effective should an attempt be made to reclose
the faulted line.
TripMode
Depending on the setting of the parameter 'TripMode', tripping is either
phase-selective, controlled by the binary input '1PolAR' (for '1phTrip'),
always three-phase (for '3phTrip') or three-phase after the time 'Delay
(3)' (for '3phTripDel3').
SOTF Mode
Access is gained to the switch-onto-fault logic settings by selecting the
parameter 'SOTF Mode'. The alternatives presented are whether the
switch-onto-fault logic should trip on the basis of the non-directional
underimpedance starters or the overreaching zone.
This logic is enabled either by the undervoltage function delayed by
10 s or 200 ms (see Section 3.5.31.2.6.) or the binary inputs 'Deadline'
and 'Manual close'.
Two signaling outputs 'Start SOTF' and 'Trip SOTF' are associated
with the switch-onto-fault logic. 'Start SOTF' is intended for blocking
the auto-reclosure function and 'Trip SOTF' signals that tripping took
place as a result of the switch-onto-fault logic.
SOTF 10 sec
The parameter 'SOTF 10sec' determines whether the undervoltage
function and the binary input 'Deadline' are enabled after 10 s ('on') or
after just 200 ms ('Off'). 'Off' indicates switching onto a fault after fast
auto-reclosure (Fast OR). Tripping in this case is thus based on the
decisions of the starters alone.
3-325
ABB Switzerland Ltd RE.216 1KHA000951-UEN
t1EvolFaults
The setting of the parameter 't1 Evol Faults' determines the time
during which an evolving fault once detected results in a three-phase
trip.
Ext UZ Block
This input blocks the underimpedance starters, the neutral voltage
starter (U0), the measurement for 'Weak' and the reverse measure-
ment. The overcurrent starters (OC) remain in operation.
3-326
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Deadline
The signal applied to this input is needed by the switch-onto-fault logic
to indicate to the distance function that the line is without voltage be-
fore the circuit-breaker is closed. It is used for the switch-onto-fault
logic providing the VTs are on the busbars.
Manual Close
Prior to manually closing the circuit-breaker, this signal enables the
switch-onto-fault logic and blocks the VT supervision function.
Zextension, ZExtension AR
The overreaching logic permits instantaneous tripping within the over-
reaching zone. It is enabled via the binary input 'Zextension' or
'ZExtension AR'.
For this purpose, the output 'Zextension' of the auto-reclosure function
is connected to the input 'ZExtension AR'.
Isolator open
This input is required by the STUB protection to ascertain whether an
isolator is open or not (see Section 4.8.5.4.).
Com Rec
This input is needed for the external signal 'Com Rec' (signal received
by PLC, optical fibre link or point-to-point radio).
Com Fail
This input signals to the protection that the PLC channel has failed.
1 Pol AR
This input permits single-phase tripping to take place and is used in
conjunction with single or three-phase auto-reclosure schemes. Refer
to the Section 'Auto reclosure' for the connection to the auto-reclosure
function.
3-327
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Ext. Block HF
This input blocks the reception of an intertripping signal. It is used for
coordinating communication channel signals when in a solidly
grounded system, the distance protection and the E/F protection use
the same channel. It must be connected to the 'RecBlk' signal of the
E/F function.
Ext Block Z1
This input blocks measurement in zone 1.
3.5.31.11. Allocation of tripping commands
(see Section 5.5.6.1.)
The parameters for allocating tripping commands are grouped in the
'CB COMMANDS' sub-menu.
The allocation of the output signals depends on whether single or
three-phase tripping has been set (parameter 'TripMode'). In the case
of three-phase tripping, the three tripping outputs are allocated to the
same auxiliary tripping relay. Single-phase tripping ('TripMode' set to
'1PhTrip' or '3PhTripDel3') requires three separate auxiliary tripping
relays, i.e. the protection has to be equipped with at least two binary
I/O units Type 316DB61/62.
3.5.31.12. Signals
(see Section 5.5.3.2)
The parameters for allocating binary outputs to auxiliary signaling
relays are grouped in the 'SIGNALING' sub-menu.
Some signaling outputs latch until the entire distance protection func-
tion resets (i.e. until 'Start R+S+T' resets, see Section 3.5.31.).
3-328
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
The function can be configured for single or three-phase auto-reclosure.
The unit can operate in conjunction with any of the three protection
functions (distance, longitudinal differential and overcurrent protection)
and either an internal or external synchrocheck function.
However, an additional standard FUPLA logic T142 as detailed in the
document 1KHF600220 is necessary for single-phase reclosing in 1½
breaker applications.
B. Features
• Up to 4 fast or slow reclosure attempts
• First cycle with up to 4 individually configurable single and/or
three-phase reclosure attempts
• Independent operating indicators for each reclosure cycle
• Wide dead time setting range
• Provision to control bypassing of the synchrocheck unit and
extending the dead time for the first zone by external signals
• Clearly defined response to changing fault conditions during the
dead time (evolving faults)
• Logic for 1st and 2nd main protection (redundant), duplex and
master/follower schemes
I. CT/VT inputs:
• None
*) 2 and 3 denote the I/Ps of protection functions 2 and 3 or relays 2 and 3 in a redundant
protection scheme (see Fig. 3.78).
**) 2 denotes the I/O’s for CB2 in a duplex scheme (see Fig. 3.81).
3-329
ABB Switzerland Ltd RE.216 1KHA000951-UEN
• Synchrocheck (SynchroChck)
• Synchrocheck 2 (SynchroChck2) **)
IV. Measurements:
• None
**) 2 denotes the I/O’s for CB2 in a duplex scheme (see Fig. 3.81).
3-330
RE.216 1KHA000951-UEN ABB Switzerland Ltd
D. Autoreclosuresettings - Autoreclosure
Summary of parameters:
General Parameters
Run On CPU CPU 1 (Select)
1. AR Mode 1P3P-1P3P (Select)
2..4. AR Mode Off (Select)
Command Close Tripping chan. ---
Fupla Directory AURESTD
Timers
t Dead1 1P s 1.2 0.05 300 0.01
t Dead1 3P s 0.6 0.05 300 0.01
t Dead1 Ext. s 1 0.05 300 0.01
t Dead2 s 1.2 0.05 300 0.01
t Dead3 s 5 0.05 300 0.01
t Dead4 s 60 0.05 300 0.01
t Oper s 0.5 0.05 300 0.01
t Inhibit s 5 0.05 300 0.01
t Close s 0.25 0.05 300 0.01
t Discrim. 1P s 0.6 0.1 300 0.01
t Discrim. 3P s 0.3 0.1 300 0.01
t TimeOut s 1 0.05 300 0.01
t AR Block s 5 0.05 300 0.01
Binary Inputs
Start BinaryAddr Always FALSE
Trip CB 3P BinaryAddr Always FALSE
Trip CB BinaryAddr Always FALSE
Start 2 BinaryAddr Always FALSE
Trip CB2 3P BinaryAddr Always FALSE
Trip CB2 BinaryAddr Always FALSE
Start 3 BinaryAddr Always FALSE
Trip CB3 3P BinaryAddr Always FALSE
Trip CB3 BinaryAddr Always FALSE
CB Ready BinaryAddr Always FALSE
CO Ready BinaryAddr Always FALSE
CB Open BinaryAddr Always FALSE
Dead Line BinaryAddr Always FALSE
Ext. Block AR BinaryAddr Always FALSE
Cond. Block AR BinaryAddr Always FALSE
Manual Close BinaryAddr Always FALSE
Inhibit Close BinaryAddr Always FALSE
Extend t1 BinaryAddr Always FALSE
3-331
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-332
RE.216 1KHA000951-UEN ABB Switzerland Ltd
3-333
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Explanations of parameters:
GENERAL PARAMETER
Run On CPU
Defines on which CPU the function should operate.
1. AR Mode
Type of first reclosure
1. 1P-1P single-phase trip and reclosure for earth
faults (single-phase dead time), no reclosure
for phase faults
1. 1P-3P single-phase trip followed by three phase trip
after approx. 20 ms, three-phase reclosure
for earth faults (three-phase dead time
initiated by single-phase trip), no reclosure
for -phase faults
1. 1P3P-3P three-phase trip and reclosure for earth and
phase faults (three-phase dead time)
1. 1P3P-1P3P single-phase trip and reclosure for earth
faults (single-phase dead time), three-phase
trip and reclosure for phase faults (three-
phase dead time)
Ext. Selection External selection by the binary inputs
MD1_EXT_1P_1P, MD1_EXT_1P_3P,
MD1_EXT_1P3P_3P and
MD1_EX_1P3P_1P3P.
2..4. AR Mode
Maximum number of reclosure attempts (all three-phase)
Off no 2nd, 3rd or 4th reclosure
2 AR 2 reclosures
3 AR 3 reclosures
4 AR 4 reclosures
Command Close CB
Signal relay output for the command to close the circuit breaker.
FUPLA Directory
The sub directory for the auto reclose logic is selectable. The
default directory name 'AURESTD' is valid in case the standard
auto recluse protection logic is utilised, which is situated in the HMI
sub directory.
A different configuration is necessary only if instead of the standard
autoreclose logic a special autoreclose logic is utilised. The
procedure in this case has to be obtained from the associated logic
description.
3-334
RE.216 1KHA000951-UEN ABB Switzerland Ltd
TIMERS
t Dead1 1P
Dead time for first single-phase reclosure.
t Dead1 3P
Dead time for first three-phase reclosure.
t Dead1 Ext.
Extension of 1st dead time for single or three-phase reclosure
(effective as long as a logical '1' (pulse or continous) is applied to
the 'Extend t1' I/P before the dead time finishes (falling edge.)
t Dead2
2nd dead time.
t Dead3
3rd dead time.
t Dead4
4th dead time.
t Operation
Maximum duration of a fault for which a reclosure attempt is made.
t Inhibit
Period (CB recovery time) from the falling edge of the last
reclosure attempt during which the autoreclosure function is
blocked and after which the function is reset.
In the event of an evolving fault between discrimination and dead
times, the period commences at the instant of another trip
occurring between the two times.
The inhibit timer is also started if the protection trips after the fault
duration time 't Oper' has elapsed.
t Close
Duration of CB close signal.
t Discrim. 1P
Evolving fault discrimination time for single-phase reclosure.
t Discrim. 3P
Evolving fault discrimination time for three-phase reclosure.
t TimeOut
Period following the dead time during which the CB close signal
has to occur. If it does not, the 'Def. Trip' signal is generated.
t AR Block
Time during which reclosure is blocked. 't AR Block' is started by
every blocking signal ('Ext.Blk AR', 'Cond.Blk. AR', 'Manual Close',
'Inhibit Inp' and 'MasternoSucc').
3-335
ABB Switzerland Ltd RE.216 1KHA000951-UEN
BINARY INPUTS
Start *)
I/P for signaling the start of a reclosure cycle.
This I/P is connected to the 'General start' signal of a protection
function.
Trip CB 3P *)
I/P for the three-phase trip signal.
The three-phase trip from a protection function is connected to
this I/P.
Trip CB
I/P for the general trip signal
The general trip from a protection function is connected to this I/P.
Set to 'Always FALSE’, if not needed.
Start 2
I/P for the AR start signal.
In redundant protection schemes, the general start signal from the
2nd protection is connected to this I/P.
Set to 'Always FALSE’, if not needed.
Trip CB2 3P
I/P for the three-phase trip signal.
In redundant protection schemes, the three-phase tripping signal
from the 2nd protection is connected to this I/P.
Set to 'Always FALSE’, if not needed.
Trip CB2
I/P for the general trip signal.
In redundant protection schemes, the general start signal from the
2nd protection is connected to this I/P.
Set to 'Always FALSE’, if not needed.
Start 3
I/P for the AR start signal.
The general start signal from the 3rd protection can be connected
to this I/P.
Set to 'Always FALSE’, if not needed.
Trip CB3 3P
I/P for the three-phase trip signal.
The three-phase tripping signal from the 3rd protection can be
connected to this I/P.
Set to 'Always FALSE’, if not needed.
*)For the auto-reclosure function to operate correctly, at least the ‘Start’ and ‘Trip CB 3P’ inputs
must be connected to a protection function or via a binary system I/P to an external protection
relay.
3-336
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Trip CB3
I/P for the general trip signal.
The general start signal from the 3rd protection can be connected
to this I/P.
Set to 'Always FALSE’, if not needed.
CB Ready
I/P excited by a signal from the CB when it is ready
(open/close/open).
Set to '‘Always TRUE’, if not needed or not fitted.
I/P logic: 'CB ready' OR 'CB2 ready'
In a duplex scheme, either an active 'CB ready' or 'CB2 ready' I/P
enables an auto-reclosure cycle.
Resetting of this input is delayed internally by 100 ms.
CO Ready
I/P excited by a signal from the CB when it is ready for a
close/open cycle.
Set to '‘Always TRUE’ if not needed, not fitted and 'Dead line' or
'ExtSCBypas' not used.
I/P logic for enabling the closing command: [('synchrocheck' AND
'CO Ready') OR 'Dead line' OR 'ExtSCBypas'].
CB Open
I/P excited by a signal from the CB when it is open.
Set to 'Always FALSE’, if not needed.
To avoid the operation of fast circuit-breakers from being blocked
unintentionally, the effect of this input is delayed internally by
100 ms.
Dead Line
I/P indicating that the line is de-energised ('CB open' input if the
VTs are on the busbar side).
Set to 'Always FALSE’, if not needed.
An active I/P overrides the following logical relationship of the I/Ps:
'synchrocheck' AND 'CO Ready'.
Ext. Block AR
I/P for blocking the internal auto-reclosure function.
Even an autoreclosure cycle that is in progress is immediately
blocked by a signal applied to this input.
The output signals 'Trip 3 Pol' and 'Def Trip' are generated and a
three-phase definitive trip takes place.
Set to 'Always FALSE’, if not needed.
3-337
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Cond. Block AR
I/P for a conditional blocking signal.
Blocking only takes place providing an AR cycle is not in progress.
Set to 'Always FALSE’, if not needed.
When tripping is by the distance protection SOTF logic or a
directional E/F PLC signal, the corresponding signals can be
connected to this I/P to prevent auto-reclosure.
Manual Close
Blocking I/P excited by the manual CB close signal.
Even an autoreclosure cycle that is in progress is immediately
blocked by a signal applied to this input.
Set to 'Always FALSE’, if not needed.
Inhibit Close
I/P for blocking the follower reclosure function in a redundant
scheme. The follower is blocked from the end of the master closing
signal until the end of the reclaim time.
Set to 'Always FALSE’, if not needed.
Extend t1
Input for conditionally extending the dead time (single and three-
phase) for the first (fast) reclosure.
Set to 'Always FALSE’, if not needed.
MD1_EXT_1P_1P, MD1_EXT_1P_3P, MD1_EXT_1P3P_3P and
MD1_EX_1P3P_1P3P
Inputs for externally selecting the mode for the first reclosure. They
are only effective when the parameter '1. AR Mode' is set to 'Ext.
select'.
Unused inputs must be set to 'Always FALSE’. If a signal is applied
to more than one input, the next mode in the list is the one that is
active. The auto-reclosure function is blocked if none of the inputs
is used.
3-338
RE.216 1KHA000951-UEN ABB Switzerland Ltd
SIGNAL OUTPUTS
Close CB
Indication 'Close command CB'.
Trip 3-Pol
Signal to the distance function so that it can only carry out a three-
phase trip.
This signal is inverted and connected to the distance protection I/P
'1P AR'.
This signal is active in many situations, but particularly when the
AR function is blocked, the CB is not ready for AR, the CB is open,
the single-phase discrimination time 't 1P Discrim' finishes or the
output signal 'First AR 3P' is active.
It resets at the end of reclaim time.
Def. Trip
Signal initiating lock-out tripping of the CB.
This signal is normally active when the protection trips again after
the last programmed reclosing shot or trips while the AR function is
blocked. The signal resets after a fixed time of 500 ms.
Inhibit Output
Signal for blocking the follower AR function in a redundant scheme.
This signal is active from the end of the close command from the
master AR function to the end of the reclaim time.
AR Ready
Signal indicating that the AR function is ready for a reclosure cycle.
This signal is active when the AR function is ON and standing by
and also during the closing command.
AR Blocked
Signal indicating that the auto-reclosure relay is blocked.
AR in Progress
Signal indicating that a reclosure cycle is in progress.
This signal is active from the beginning of the dead time until the
end of the last reclosure attempt.
First AR 1P in Progress
Signal indicating that the 1st single-phase reclosure attempt is in
progress.
First AR 3P in Progress
Signal indicating that the 1st three-phase reclosure attempt is in
progress.
Second AR in Progress
Signal indicating that the 2nd reclosure attempt is in progress
(always three-phase).
3-339
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Third AR in Progress
Signal indicating that the 3rd reclosure attempt is in progress
(always three-phase).
Fourth AR in Progress
Signal indicating that the 4th reclosure attempt is in progress
(always three-phase).
First AR completed
Signal indicating that the 1st reclosure is completed.
2...4. AR completed
Signal indicating that the 2nd, 3rd and 4th reclosure is completed.
SYNCHROCHECK
SC ByPass 1P first AR
Bypass of the synchrocheck and close/open ready signals for the
first single-phase reclosure:
'on' First single-phase reclosure not enabled by
synchrocheck and close/open ready signals
(bypass always active).
'Off' First single-phase reclosure enabled by the
synchrocheck and close/open ready signals
(bypass inactive).
SC ByPass 1P3P first AR
Bypass of the synchrocheck and close/open ready signals for the
first single or three-phase reclosure:
'on' First reclosure not enabled by synchrocheck and
close/open ready signals
(bypass always active).
'Off' First reclosure enabled by synchrocheck and close/open
ready signals
(bypass inactive).
Ext. SC ByPass
Bypasses the 'synchroChck' and 'CO Ready' signals.
Set to 'Always FALSE’, if not needed.
I/P logic for enabling the close command: [('synchrocheck' AND
'CO Ready') OR 'Dead line' OR 'Ext.SCBypas'].
I/P logic for enabling the close command: [('synchroChk2' AND
'CO Ready 2') OR 'Dead line' OR 'Ext.SCBypas'].
Synchro Check blocked
I/P for a signal from a synchrocheck relay.
Set to '‘Always TRUE’, if not needed, not fitted and 'Dead line' or
'ExtSCBypas' not used.
I/P logic: [('synchrocheck' AND 'CO Ready') OR 'Dead line' OR
'Ext.SCBypas'].
3-340
RE.216 1KHA000951-UEN ABB Switzerland Ltd
ZONE EXTENSION
To achieve the functions described below, the 'ZExtension' signal must
be connected to the distance protection function (see Section
3.5.32.2.).
This signal can be used to initiate fast tripping in schemes including
overcurrent functions (see Section 3.5.32.3.).
ZE Prefault
Distance relay reach setting before the first fault:
'On' overreaching ('ZExtension' signal active)
'Off' underreaching ('ZExtension' signal inactive)
ZE 1. AR
Distance relay reach after the 1st reclosure attempt:
'On' overreaching ('ZExtension' signal active)
'Off' underreaching ('ZExtension' signal inactive)
ZE 2. AR
Distance relay’s reach after the 2nd reclosure attempt:
'On' overreaching ('ZExtension' signal active)
'Off' underreaching ('ZExtension' signal inactive)
ZE 3. AR
Distance relay’s reach after the 3rd reclosure attempt:
'On' overreaching ('ZExtension' signal active)
'Off' underreaching ('ZExtension' signal inactive)
ZE 4. AR
Distance relay’s reach after the 4th reclosure attempt:
'On' overreaching ('ZExtension' signal active)
'Off' underreaching ('ZExtension' signal inactive)
Z Extension
Signal to the distance function to switch it to overreach or enable
an overcurrent function with a short delay.
MASTER-FOLLOWER LOGIC
Master Mode
(for 1½ breaker and redundant schemes)
Selection of an auto-reclosure function to be 'Master':
'On' Master O/P signals transmitted
'Off' Master O/Ps blocked
Master Delay
I/P for a signal delaying the closing command from the follower
reclosure function.
This signal picks up when the dead time of the master reclosure
function starts and is reset either by a new trip after the last
reclosure of the cycle or at the end of the wait time following
successful reclosure by the master.
Set to 'Always FALSE’, if not needed.
3-341
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Mast. no Succ.
I/P for a blocking signal from the master CB.
This signal is triggered by the rising edge of the 'Def.Trip' output
from the master reclosure function and resets after a fixed time of
500 ms.
Set to 'Always FALSE’, if not needed.
Delay Flwr.
Signal to delay the follower CB for as long as the master circuit-
breaker has not completed its auto-reclosure cycle.
The signal picks up at the start of master AR dead time and is
reset either by the rising edge of the 'Def.Trip' output or the falling
edge of the 'Close CB' output after the time 'tClose'.
Block to Flwr.
Signal to block the follower CB as long as reclosure of the master
CB is unsuccessful.
The excursion of this signal is the same as for the 'Def.Trip' output.
DUPLEX LOGIC
CB2 Ready
I/P excited by a signal from CB2 when it is ready
(open/close/open).
Set to 'Always FALSE', if not needed or not fitted.
I/P logic: 'CB ready' OR 'CB2 ready'
In a duplex scheme, the auto-reclosure cycle is enabled either by
an active 'CB ready' or 'CB2 ready' I/P.
Resetting of this input is delayed internally by 100 ms.
CO Ready2
I/P excited by a signal from CB2 when it is ready for a close/open
operation.
Set to '‘Always TRUE', if not needed, not fitted and 'Dead line 2' is
not used.
I/P logic for enabling the close command: [('synchrocheck2' AND
'CO Ready 2') OR 'Dead line 2' OR 'ExtSCBypas'].
CB2 open
I/P excited by a signal from CB2 when it is open.
Set to 'Always TRUE', if not needed. Observe the information given
for the duplex logic in a duplex scheme (see Section 3.5.32.6.).
3-342
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Synchro Check 2
I/P for a signal from a synchrocheck function belonging to CB2.
Set to '‘Always TRUE’, if not needed, not fitted and 'Dead line 2' or
‘ExtSCBypas’ not used.
I/P logic for enabling the close command: [('synchrocheck2' AND
'CO Ready 2') OR 'Dead line 2' OR 'ExtSCBypas'].
Dead line 2
I/P indicating that line 2 is de-energised (CB2 open and VTs 2 on
the busbar side).
Set to 'Always FALSE’, if not needed.
An active I/P overrides the following logical relationship of the I/Ps:
'synchrocheck 2' AND 'CO Ready 2'.
Close CB2
Tripping relay O/P for the CB2 close command.
Close CB2
Auxiliary relay O/P for the CB2 close signal.
CB2 Priority
Input for determining the preferred circuit-breaker:
'Always FALSE’ CB1 is preferred circuit-breaker
'‘Always TRUE’ CB2 is preferred circuit-breaker
If both circuit-breakers are closed before a fault, only the preferred
circuit-breaker performs the entire auto-reclosure cycle. The other
circuit-breaker closes either after successful auto-reclosure or
when the close command to the preferred circuit-breaker is not
enabled (missing 'CO Ready' or 'Synchrocheck').
ADDITIONAL LOGIC
The following settings are only of consequence if a special auto-reclo-
sure logic is installed. In this case, consult the associated description
for the significance of the various settings.
P_INPUT1, P_INPUT2…P_INPUT16
Additional binary input for a special auto-reclosure logic.
TMSEC_Timer1, TMSEC_Timer2…TMSEC_Timer8
Additional timer settings for a special auto-reclosure logic.
P_OUTPUT1, P_OUTPUT2…P_OUTPUT8
Additional signals for a special auto-reclosure logic.
3-343
ABB Switzerland Ltd RE.216 1KHA000951-UEN
E. Setting instructions
3.5.32.1. General
The auto-reclosure function can perform from 1 to 4 auto-reclosure
attempts. The first attempt can be either single or three-phase while
the subsequent attempts are always three-phase. The type and num-
ber are determined by the parameters '1. AR Mode' (4 different modes
for the 1st reclosure cycle) and '2..4 AR Mode'.
The function can operate in conjunction with either an external dis-
tance protection relay or other internal protection functions.
It can also operate in a scheme comprising two or more protection
functions (see Sections 3.5.32.2. to 3.5.32.6.).
3.5.32.2. Connections between auto-reclosure and distance functions
The auto-reclosure function determines from the states of the input
signals 'start', 'Trip CB' and 'Trip CB 3P', whether the distance protec-
tion has picked up and whether it has performed a single or a three-
phase trip. Only the 'Trip CB' signal is generated for a single-phase
trip, whereas both the 'Trip CB' and 'Trip CB 3P' signals are generated
for a three-phase trip.
The external distance relay or internal distance function decides
whether single or three-phase tripping should take place.
The auto-reclosure function can send two signals to the distance pro-
tection. The 'Trip 3-Pol' signal informs the distance protection whether
it should perform a single or a three-phase trip. The 'ZExtension' signal
switches the distance protection’s overreaching zone on and off.
When setting the parameters, attention should be paid to the order of
the functions. For runtime reasons, the distance function should be
configured before the auto-reclosure function.
Where the SOTF logic is not required to operate during auto-reclosure,
connect the 'AR in progress' Signal to the 'Ext. Block SOTF' binary I/P
of the distance function. The 'SOTF 10 s' timer in the distance
function’s SOTF logic is normally activated for dead times <10 s and in
this case the above connection is not necessary.
If the SOTF logic initiates tripping, an auto-reclosure cycle can be
inhibited by connecting the 'start SOTF' from the distance function to
the 'Cond. Block AR' I/P of the auto-reclosure function.
The exchange of signals in the various schemes (one distance and
one auto-reclosure function, and several protection functions and one
reclosure function) can be seen from
Fig. 3.75, Fig. 3.76 and Fig. 3.79.
3-344
RE.216 1KHA000951-UEN ABB Switzerland Ltd
RE.216 / RE.316*4
Start RST Start Auto-reclosure
<Z Trip CB Trip CB function
Trip CB 3Ph Trip CB 3P
CO Ready
Start SOTF Cond. Block AR
CB Ready
Close CB
CB Open
1 Pol AR Trip 3-Pol
Z Extension AR Z Extension
HEST 045019 C
RE.216 / RE.316*4
Start Auto-reclosure
<Z Trip CB function
Trip CB 3P
CO Ready
CB Ready
Cond. Block AR
Close CB
CB Open
Trip 3-Pol
Z Extension
HEST 045020 C
3-345
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-346
RE.216 1KHA000951-UEN ABB Switzerland Ltd
RE.216 / RE.316*4
O/C Trip ≥ 1 *) Start Auto-reclosure
(I 1>, t 1)
Logic Trip CB 3P function
CO Ready
CB Ready
Close CB
CB Open
Z Extension
O/C Trip
(I 2>, t 2)
Block
HEST045021 C
where:
t1 standard delay (0.5 ... 1.5 s)
t2 short delay (0.02 ... 0.2 s)
I1>, I2> pick-up value 'I set' for 'Trip'
*) The ‘Trip’ signal from the second current function may be connected to the
inputs ‘Start 2’ and ‘Trip CB2 3P’ instead of to the logic function.
3-347
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-348
RE.216 1KHA000951-UEN ABB Switzerland Ltd
<Z <Z
RE.216 / RE.316*4
Z Extension AR
Trip CB 3Ph
Start SOTF
Start RST
1 Pol AR
Trip CB
Z Extension
Cond. Block AR
Cond. Block AR
Z Extension
Trip CB
Trip CB
Trip CB 3P
Trip CB 3P
Trip 3-Pol
Trip 3-Pol
Start
Start
Auto-reclosure
Auto-reclosure
Trip CB2 3P
function
function
CB Open CB Open
CB Ready CB Ready
CO Ready CO Ready
Close CB Close CB
HEST 045022 C
Fig. 3.78 Redundant scheme (first and second main < Z and
auto-reclosure functions) with master/follower logic
3-349
ABB Switzerland Ltd RE.216 1KHA000951-UEN
RE.216 / RE.316*4
< Z (1)
Start RST Start
Trip CB Trip CB
Trip CB 3Ph Trip CB 3P
Start SOTF Cond. Block AR
1 Pol AR Trip 3-Pol
Z Extension AR Z Extension
Z Extension
Auto-reclosure
function
Trip 3-Pol
Start 2
Trip CB2
CO Ready
CB Ready
Close CB
CB Open
Start
Trip CB 3P
Backup
HEST 045025 C
3-350
RE.216 1KHA000951-UEN ABB Switzerland Ltd
MAIN 1 MAIN 2
Trip CB R Trip CB R
<Z Trip CB S Trip CB S <Z
Trip CB T Trip CB T
Start RSTAux
Start RSTAux
Start SOTF
Start SOTF
Trip CB 3P
Trip CB 3P
Start RST
Start RST
1 Pol AR
1 Pol AR
Trip CB
Trip CB
Cond. Block
Trip CB 3P
Trip CB2 3P
Trip 3-Pol
AR
Trip CB
Trip CB 3P
Trip CB2 3P
Start 2
Trip CB 2
Start
Trip 3-Pol
Cond. Block
Trip CB
Start 2
Trip CB 2
Start
AR
Delay Flwr. Master Delay
RE.316*4 Block to Flwr. Mast. no Succ.
RE.316*4
Master AR Follower AR
CO Ready
CB Ready
CO Ready
CB Ready
Close CB
CB Open
Close CB
CB Open
LINE
HEST 045 023 C
3-351
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-352
Start Start RST
Fig. 3.81
CB Open
CB Ready Trip CB Trip CB
CB1
CO Ready Trip CB 3P Trip CB 3P
Start SOTF
< Z (1)
Z Extension Z Extension AR
RE.216 & RE.316*4
function
Auto-reclosure
CB2
CO Ready2 Start 2
Close CB2 Trip CB 2
Trip CB2 3P
3-353
ABB Switzerland Ltd
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3.5.32.7. Timers
The timers have setting ranges extending up to 300 s in steps of
10 ms.
The purpose of each of the timers is described below.
Example:
Time 'T Oper' < 'Delay(2)' of the distance function means that auto-
reclosure only takes place for faults in the first distance zone
('Delay(1)').
This function is not required for schemes that only use current func-
tions. The binary inputs 'Start' and 'Trip CB 3P' are connected together
(see Section 3.5.32.3.).
3-354
RE.216 1KHA000951-UEN ABB Switzerland Ltd
3-355
ABB Switzerland Ltd RE.216 1KHA000951-UEN
't TimeOut'
The parameter 't TimeOut' determines the period after the dead time
within which the close signal must be issued, otherwise a 'Def. Trip' is
generated and no further reclosure attempt is made. Before a close
command is issued at the end of every dead time, the logic
[('synchroChck' AND 'CO Ready') OR 'Dead Line' OR 'Ext. SC
ByPass')] is checked and the command only enabled providing all the
criteria are correct within the setting of 't TimeOut'.
*) 2 denotes the I/Os for CB2 in a duplex scheme (see Fig. 3.81.).
3-356
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A reclosure cycle remains blocked for the duration of the set blocking
time 't AR Block' after the last binary I/P has been enabled. Blocking
also takes place during initialisation of the protection relay when its
auxiliary supply is switched on or the parameter settings are being
loaded.
3-357
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-358
RE.216 1KHA000951-UEN ABB Switzerland Ltd
'Manual Close'
The reclosure function is immediately blocked (for the blocking time
't AR Block') by a 'Manual Close' signal. This signal is also needed for
the overreaching logic to switch the 'Z Extension' signal to 'On'.
3-359
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-360
RE.216 1KHA000951-UEN ABB Switzerland Ltd
logical '1' and the distance relay is switched to overreach either before
fault occurrence or for the following reclosure attempt, otherwise the
distance relay is set to underreach.
With the exception of its first change of state when providing
'ZE Prefault' is set to 'On' it resets together with the signal 'Trip CB' or
'Trip CB 3P', this signal picks up and resets together with the 'Close
CB' signal.
The distance relay is switched to overreaching for a 'Manual Close'.
It is switched to underreaching when the auto-reclosure function is
blocked.
Note also that the 'Z Extension' signal is connected to the binary input
'ZEMode AR' of the zone extension logic in the distance protection
function.
3-361
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Successful AR
time < t Operation
Trip CB
Trip CB 3P
Start
Def. Trip
t Close
Close CB
Z Extension
300 ms
First AR 1P
in Progress t Discrim. 1P
Trip 3-Pol
AR in Progress
AR Ready
AR Blocked
t Dead1 1P t Inhibit
Unsuccessful AR
time < t Operation
Trip CB
Trip CB 3P
Start
Def. Trip
Close CB
Z Extension
First AR 1P
in Progress
t Discrim. 1P
Trip 3-Pol
AR in Progress
AR Ready
AR Blocked
t Dead1 1P
3-362
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Trip CB 3P
Start
Def. Trip
t Close
Close CB
Z Extension
First AR 1P
in Progress
First AR 3P
in Progress
t Discrim. 1P
Trip 3-Pol
300 ms
AR in Progress
AR Ready
AR Blocked
t Dead1 1P t Inhibit
Trip CB 3P
Start
Def. Trip
Close CB
Z Extension
First AR 1P
in Progress
t Discrim. 1P
Trip 3-Pol
AR in Progress
AR Ready
AR Blocked
t Dead1 1P
3-363
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Successful AR
time < t Operation
Trip CB 3P
Trip CB
Start
Def. Trip
t Close
Close CB
Z Extension
First AR 3P
in Progress
Second AR
in Progress 300 ms
Third AR
in Progress
Trip 3-Pol
AR in Progress
AR Ready
AR Blocked
Unsuccessful AR
time < t Operation
Trip CB 3P
Trip CB
Start
Def. Trip
Close CB
Z Extension
First AR 3P
in Progress
Second AR
in Progress
Third AR
in Progress
Trip 3-Pol
AR in Progress
AR Ready
AR Blocked
3-364
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Trip CB 3P
Start
Def. Trip
t Close
Close CB
Z Extension
300 ms
First AR 1P
In Progress
t Discrim. 1P
Trip 3-Pol
Delay Flwr
Inhibit Output
AR in Progress
AR Ready
AR Blocked
t Dead1 1P t Inhibit
Trip CB 3P
Start
Def. Trip
Close CB
Z Extension
First AR 1P
in Progress t Discrim. 1P
Trip 3-Pol
Master Delay
Inhibit Close
AR in Progress
AR Ready
AR Blocked
t Dead1 1P t Inhibit
3-365
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Trip CB 3P
Start
Def. Trip
Close CB
Z Extension
First AR 1P
in Progress
t Discrim. 1P
Trip 3-Pol
Delay Flwr
Inhibit Output
AR in Progress
AR Ready
AR Blocked
t Dead1 1P t Inhibit
Trip CB 3P
Start
Def. Trip
Close CB
Z Extension
First AR 1P
in Progress
t Discrim. 1P
Trip 3-Pol
Master Delay
Inhibit Close
AR in Progress
AR Ready
AR Blocked
t Dead1 1P t Inhibit
3-366
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Unsuccessful AR
time < t Operation
Trip CB
Trip CB 3P
Start
Def. Trip
Close CB
Close CB2
Z Extension
First AR 3P
in Progress
Trip 3-Pol
AR in Progress
AR Ready
AR Blocked
t Dead1 3P
Successful AR
time < t Operation
Trip CB
Trip CB 3P
Start
Def. Trip
t Close
Close CB
300 ms
Close CB2
Z Extension
300 ms
First AR 3P
in Progress
Trip 3-Pol
AR in Progress
AR Ready
AR Blocked
t Dead1 3P t Inhibit
3-367
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Trip CB 3P
Start
Close CB
Z Extension
Def. Trip
First AR 1P
in Progress
t Discrim. 1P
Trip 3-Pol
Delay Flwr
Block to Flwr
AR in Progress
AR Ready
AR Blocked
t Dead1 1P
Trip CB 3P
Start
Close CB
Z Extension
Def. Trip
First AR 1P
in Progress t Discrim. 1P
Trip 3-Pol
Master Delay
Mast.no Succ
AR in Progress
AR Ready
AR Blocked
t Dead1 1P
3-368
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Trip CB
Trip CB 3P
Start
t Close
Close CB
Z Extension
Def. Trip
300 ms
First AR 1P
in Progress
t Discrim. 1P
Trip 3-Pol
Delay Flwr
Block to Flwr
AR in Progress
AR Ready
AR Blocked
t Dead1 1P t Inhibit
Trip CB 3P
Start
t Close
Close CB
Z Extension
Def. Trip
300 ms
First AR 1P
in Progress t Discrim. 1P
Trip 3-Pol
Master Delay
Mast.no Succ
AR in Progress
AR Ready
AR Blocked
t Dead1 1P t Inhibit
3-369
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Trip CB 3P
Trip CB
Start
Def. Trip
Block to Flwr
Delay Flwr
Close CB
Z Extension
First AR 3P
in Progress
Second AR
in Progress
Third AR
in Progress
Trip 3-Pol
AR in Progress
AR Ready
AR Blocked
t Dead1 3P t Dead2 t Dead3
Trip CB 3P
Trip CB
Start
Def. Trip
Close CB
Mast.no Succ
Master Delay
Z Extension
First AR 3P
in Progress
Trip 3-Pol
AR in Progress
AR Ready
AR Blocked
Settings:
'1. AR Mode' = '1P3P-1P3P', '2..4. AR Mode' = 'Off',
'ZE Prefault' = 'on', 'ZE 1. AR' = 'Off',
'ZE 2. AR' = 'on' and 'ZE 3. AR' = 'Off'.
3-370
RE.216 1KHA000951-UEN ABB Switzerland Ltd
3-371
ABB Switzerland Ltd RE.216 1KHA000951-UEN
A B
ts
tw
tp
0 1
C
6
2
A 5
3
4
O
t1 t2
t3 t4 t5
t6
t7
0 1
C 2
6
B 3 5
4
O
(t)
A: circuit-breaker 1 B: circuit-breaker 2
C: 'closed' position O: 'open' position
0: start 1: 'trip' signal
2: contacts part 3: current interrupted
4: 'close' signal 5: current flows again
6: contacts make
t1: tripping time t2: reclosing time t3: arc extinction time
t4: dead time t5: pre-ignition time t6: duration of interruption
t7: resulting dead time
tp: dead time ts: inhibit time tw: fault duration
3-372
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
• Redundant tripping schemes (RED 1))
• Repeated tripping attempts (BFP 2))
• Backup tripping (BFP)
• End fault protection (EFP 3))
• Unconditional tripping (UT 4))
• External trip initiation
B. Features
• Insensitive to DC component
• Insensitive to harmonics
• Single or three-phase operation
• Blocking
• Two independent timers (t1, t2)
• Transfer tripping
• Provision for disabling features (RED, BFP, EFP, UT)
• Unique ID for each binary input and output
I. CT/VT inputs
• Current
1)
Redundant
2)
Breaker failure protection
3)
End fault protection
4
) Unconditional trip
3-373
ABB Switzerland Ltd RE.216 1KHA000951-UEN
IV. Measurements
• Current amplitude L1
• Current amplitude L2
• Current amplitude L3
3-374
RE.216 1KHA000951-UEN ABB Switzerland Ltd
General Parameters
Run On CPU CPU 1 (Select)
Number Of Phases 3 (Select) 2
Current Input CT/VT-Addr 0
I Setting IN 1.2 0.2 5 0.01
Delay t1 s 0.15 0.02 60 0.01
Delay t2 s 0.15 0.02 60 0.01
Delay tEFP s 0.04 0.02 60 0.01
t Drop Retrip s 0.05 0.02 60 0.01
t Drop Butrip s 0.05 0.02 60 0.01
t Pulse RemTrip s 0.05 0.02 60 0.01
t1 active On (Select)
t2 active On (Select)
RemTrip active On (Select)
EFP active On (Select)
Red active On (Select)
Start Ext act. On (Select)
RemTrip after t1 (Select)
CB Commands
TRIP t1 ---
TRIP t1 L1 ---
TRIP t1 L2 ---
TRIP t1 L3 ---
TRIP t2 ---
REMOTE TRIP ---
RED TRIP L1 ---
RED TRIP L2 ---
RED TRIP L3 ---
EFP REM TRIP ---
EFP BUS TRIP ---
3-375
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Binary Inputs
Block BFP BinaryAddr Always FALSE
Start L1 BinaryAddr Always FALSE
Start L2 BinaryAddr Always FALSE
Start L3 BinaryAddr Always FALSE
Start L1L2L3 BinaryAddr Always FALSE
External Start BinaryAddr Always FALSE
CB-Off BinaryAddr Always FALSE
CB-On BinaryAddr Always FALSE
Ext Trip t2 BinaryAddr Always FALSE
Ext Trip EFP BinaryAddr Always FALSE
Signal Outputs
Trip t1 SignalAddr ER
Trip t1 L1 SignalAddr ER
Trip t1 L2 SignalAddr ER
Trip t1 L3 SignalAddr ER
Trip t2 SignalAddr ER
Remote Trip SignalAddr ER
Red Trip L1 SignalAddr ER
Red Trip L2 SignalAddr ER
Red Trip L3 SignalAddr ER
EFP Rem Trip SignalAddr ER
EFP Bus Trip SignalAddr ER
Retrip t1 SignalAddr ER
Uncon Trip t1 SignalAddr ER
Ext Trip t1 SignalAddr ER
Backup Trip t2 SignalAddr ER
Uncon Trip t2 SignalAddr ER
3-376
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Explanation of parameters:
General Parameters
Run On CPU
Defines on which CPU the function should operate.
Number of Phases
defines the number of phases supervised.
'1' single-phase operation
'3' three-phase operation
Current Input
defines the CT input channel. Single and three-phase CTs can be
set. The first channel (R phase) of the group of three selected must
be specified for three-phase CTs.
I Setting
Pick-up of the current criterion for the breaker failure protection
(BFP), end fault protection (EFP) and the redundant tripping logic
(RED).
Delay t1
'Retrip' tripping delay
Delay t2
Backup tripping delay.
Delay tEFP
End fault protection delay.
t Drop Retrip
Reset delay for 'Retrip', 'Redundant Trip' and 'External Trip Initiate'.
t Drop Butrip
Reset delay for backup tripping attempt.
t Puls RemTrip
Transfer tripping impulse width.
t1 active
defines whether timer t1 is enabled or disabled.
'on' Timer t1 enabled
'off' Timer t1 disabled
t2 active
defines whether timer t2 is enabled or disabled.
'on' Timer t2 enabled
'Off' Timer t2 disabled
RemTrip active
defines whether transfer tripping is enabled or disabled.
'on' Transfer tripping enabled
'Off' Transfer tripping disabled
3-377
ABB Switzerland Ltd RE.216 1KHA000951-UEN
EFP active
defines whether the end fault protection is enabled or disabled.
'on' End fault protection enabled
'Off' End fault protection disabled
Red active
defines whether the redundant logic is enabled or disabled.
'on' Redundant tripping logic enabled
'Off' Redundant tripping logic disabled
Start Ext active
defines whether the unconditional tripping logic is enabled or
disabled.
'on' Unconditional tripping logic enabled
'Off' Unconditional tripping logic disabled
RemTrip after
defines the delay for transfer tripping.
't1' after BFP time t1
't2' after BFP time t2
CB Commands
TRIP t1
defines the tripping channel activated by the function’s tripping
output TRIP t1 (matrix tripping logic). This output is activated for a
'Retrip', 'External Trip Initiate' or 'Unconditional Trip'.
TRIP t1 L1, L2 or L3
defines the tripping channel activated by the function’s tripping
outputs TRIP t1 L1, L2 or L3 (matrix tripping logic). This output is
activated for a phase segregated 'Retrip'.
TRIP t2
defines the tripping channel activated by the function’s tripping
output TRIP t2 (matrix tripping logic). This output is activated for a
'Backup Trip' or 'Unconditional Trip' the after second time step t2.
REMOTE TRIP
defines the tripping channel activated by the function’s tripping
output REMOTE TRIP (matrix tripping logic).
RED TRIP L1, L2 or L3
defines the tripping channel activated by the function’s tripping
outputs RED TRIP L1, L2 or L3 (matrix tripping logic).
EFP REM TRIP
defines the tripping channel activated by the function’s tripping
output EFP REM TRIP (matrix tripping logic).
EFP BUS TRIP
defines the tripping channel activated by the function’s tripping
output EFP BUS TRIP (matrix tripping logic).
3-378
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Binary Inputs
Block BFP
Input for blocking the function.
Start L1, L2 or L3
BFP or RED Start in phase L1, L2 or L3
Start L1,L2 or L3
BFP or RED Start in all three phases
External Start
starts the unconditional trip.
CB-Off
signals that the circuit-breaker is fully open and also used to start
the end zone fault protection.
CB-On
signals that the circuit-breaker is fully closed.
Ext Trip t2
Input for signals from the other BFP units in the station.
Ext Trip EFP
Input for signals from the end zone fault outputs of the other BFP
units in the station.
Signal Outputs
Trip t1
signals a trip which is activated by one of the following logics:
• Repeat trip (see 'Retrip t1')
• External trip (see 'Ext Trip t1')
• Unconditional trip (see 'UnconTrip t1')
Trip t1 L1, L2 or L3
signals a repeat trip of phase L1, L2 or L3.
Trip t2
signals a backup trip. This signal is activated by the following
logics:
• Backup trip after t2 (see 'Backup Trip t2')
• Unconditional trip after t2 (see 'UnconTrip t2')
Remote Trip
signals a transfer trip.
Red Trip L1, L2 or L3
signals a redundant trip of phase L1, L2 or L3.
EFP Rem Trip
signals an end zone trip. This signal is an impulse of length
't Puls Rem Trip' generated when the EFP timer has timed out.
3-379
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-380
RE.216 1KHA000951-UEN ABB Switzerland Ltd
E. Setting instructions
Settings:
Pick-up current setting: I Setting
Tripping delay: Delay t1
Delay t2
Delay tEFP
3-381
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Fault CB Repeat
incidence (1) Start (2) open (3) trip (4)
CB Backup
open (5) trip (6)
Delay t1
Delay t2
3-382
RE.216 1KHA000951-UEN ABB Switzerland Ltd
(6) After a further reset delay tReset plus a safety margin tMargin , the
BFP either detects that the fault current has been interrupted and
the protection function resets, or the fault current continues to
flow and the BFP initiates backup tripping.
If the BFP is only required to carry out a single breaker failure step,
timer t1 can be disabled (see 't1 active'). The response of the BFP
corresponds once again to Fig. 3.92, but with timer t1 set to zero.
1)
see reset time of the current detector tReset
2)
see safety margin tMargin
3-383
ABB Switzerland Ltd RE.216 1KHA000951-UEN
CB CB EFP
tripping signal (1) open (3) tripping signal (4)
tCB open
tReset + tMargin
CB
tripped (2)
3)
see reset time of the current detector tReset
4) see Margin time t
Margin
3-384
RE.216 1KHA000951-UEN ABB Switzerland Ltd
't Drop Butrip' determines the reset delay for the following signals:
23310 Trip t2
23370 EFP Bus Trip
23335 Backup Trip t2
23365 Uncon Trip t2
3-385
ABB Switzerland Ltd RE.216 1KHA000951-UEN
t1 active
This setting provides facility for disabling the timer t1. When it is dis-
abled, none of the 'repeat trip' group of signals is generated.
t2 active
This setting provides facility for disabling the timer t2. When it is dis-
abled, none of the 'backup trip' group of signals is generated.
RemTrip active
This setting provides facility for disabling transfer tripping. When it is
disabled, none of the 'remote trip' group of signals is generated.
EFP active
This setting provides facility for disabling the end fault protection.
When it is disabled, none of the 'end fault' group of signals is gener-
ated.
Red active
This setting provides facility for disabling the redundant protection.
When it is disabled, none of the 'redundant' group of signals is gener-
ated.
3-386
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
General purpose timer for
• integration of pulsating binary signals to obtain a continuous signal,
e.g. output of the loss-of-excitation function (out-of-step protection)
or reverse power protection
• extension of short I/P signals (pulse prolongation)
• simple time delay
B. Features
• I/P channel and blocking input assignable to
• binary I/P signals
• protection function output signals
• I/P channel and blocking input can be inverted.
• Adjustable reset time
• 2 types of time delay
• Integration: Only the time during which the I/P signal is at
logical '1' counts at the end of the time delay.
• No integration: The total time from the instant the timer starts
until it is either reset or expires counts.
I. CT/VT inputs:
• None
IV. Measurements:
• Time from the instant the timer starts
3-387
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Explanation of parameters:
Run On CPU
Defines on which CPU the function should operate.
Trip
Definition of the tripping logic (matrix) excited by the function’s
output.
Trip Delay
Time delay between start signal and the tripping signal.
Reset Delay
Time required for the timer to reset after the input signal has
disappeared.
Integration
Determination of the response of the function in the presence of a
pulsating I/P signal:
0: The time delay continues to run, providing the I/P signal
does not disappear for longer than the reset time (see Fig.
3.94).
1: The time during which the I/P is at logical '1' is integrated,
i.e. tripping does not take place until the sum of logical '1'
time equals the set delay time (see Fig. 3.95).
Binary Input
Timer input.
Block Input
Input for blocking the function.
Trip Signal
Tripping signal.
Start Signal
Pick-up signal.
3-388
RE.216 1KHA000951-UEN ABB Switzerland Ltd
tR tR tR
Start
0 t 0 t
Impulse
prolongation
0 t 0 t
tA tA
(No (No
tripping) tripping)
Tripping
0 t 0 t
tR
tR tR
Start
0 t 0 t
Impulse
prolongation
0 t 0 t
tA tA
(No
tripping)
Tripping
0 t 0 t
Note: Tripping only takes place, if a start also occurs within the time tR.
tA tripping time ('Trip Delay')
tR reset time ('Reset Delay')
3-389
ABB Switzerland Ltd RE.216 1KHA000951-UEN
tR tR tR
Start
0 t 0 t
Setting
Setting
tint tint
Integration
0 t 0 t
(No (No
tripping) tripping)
Tripping
0 t 0 t
tR tR tR tR
Start
0 t 0 t
Setting
Setting
tint tint
Integration
0 t 0 t
Tripping
0 t 0 t
3-390
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
General counters, e.g. for
• counting the output impulses of the field failure or reverse power
protection functions
• prolongation of short input signals
B. Features
• Input channel and blocking input can be set by
• binary input signals
• output signal from a protection function
• Provision for inverting signals applied to the inputs
I. CT/VT inputs:
• None
IV. Measurements:
• Count reached
3-391
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Explanation of parameters:
Run On CPU
Defines on which CPU the function should operate.
Trip
defines the tripping channel activated by the tripping O/P of the
function (matrix tripping logic).
Set Count
Number of input impulses counted by the counter before it trips.
Drop Time
Time the counter output signal is maintained after the input signal
causing it has reset.
ResetTime
Time after the input signal has reset before the counter is reset to
zero if it did not trip.
Binary Input
Counter input
Block Input
defines the input for an external blocking signal.
Trip Signal
Tripping signal.
Start Signal
Pick-up signal.
3-392
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
Logical combination of binary input signals or of output signals from
the protection functions, e.g. for
• specific signals required by the application
• supplementary protection functions
B. Features
• Binary I/P channels assignable to
• binary I/P signals
• protection function O/P signals
• All I/P channels can be inverted
• Following logic functions available for selection:
• OR gate with 4 I/Ps
• AND gate with 4 I/Ps
• R/S flip-flop with 2 I/Ps for setting and 2 I/Ps for resetting:
• The O/P is '0', if at least one of the reset I/Ps is '1'.
• The O/P is '1', if at least one of the set I/Ps is '1' AND none
of the reset I/Ps is '1'.
• The O/P status is sustained when all the I/Ps are at '0'.
• Every logic has an additional blocking I/P, which when activated
switches the O/P to '0'.
I. CT/VT inputs:
• None
IV. Measurements:
• None
3-393
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Explanation of parameters:
Run On CPU
Defines on which CPU the function should operate.
Trip
Definition of the tripping circuit excited by the function’s O/P
(tripping matrix).
Logic Mode
Definition of the logic function to be performed by the 4 binary I/Ps.
Possible settings:
• OR: OR gate with all 4 binary I/Ps
• AND: AND gate with all 4 binary I/Ps
• R/S flip-flop: Flip-flop with 2 set I/Ps (S1 and S2) and 2 reset
I/Ps (R1 and R2). The O/P is set or reset when
at least one of the corresponding I/Ps is at
logical '1' (OR gate).
Reset I/Ps take priority over the set I/Ps.
Binary Output Signal
Output for signaling a trip.
Block Input
Input for blocking the function.
The O/P is always at logical '0' when the blocking I/P is at logical
'1'.
The blocking I/P acts as a reset I/P for the flip-flop function.
Binary Inputs 1 to 4 (AND or OR function)
Reset inputs 1 and 2 and set inputs 1 and 2 (RS flip-flop)
3-394
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
The control function is designed to perform data acquisition, monitor-
ing, and control functions in MV and HV substations.
The control logic of a switchgear bay can be configured for SF6 gas-
insulated switchgear (GIS), for indoor and outdoor switchgear and for
single, double or multiple busbar stations.
The control function registers and processes the switchgear position
signals, the measured variables and the alarms occurring in a switch-
gear bay. The corresponding data are then made available at the
communication interface (IBB).
The control function receives instructions from the station control
system (SCS) or from the local mimic, processes them in relation to
the bay control logic configuration and then executes them.
The interlocks included in the control function device prevent inadmis-
sible switching operations, which could cause damage to plant or en-
danger personnel.
B. Features
The control function depends on the particular application for which it
is specifically created using CAP 316. It includes essentially:
• Detection and plausibility check of switchgear position signals
• Switchgear control
• Interlocks
• Monitoring of switchgear commands
• Run-time supervision
• Integration of the local mimic
• Detection of alarms and alarm logic
• Processing of measured variables
Eight FUPLA functions can be configured. The total maximum size
of FUPLA code for all the functions is 128 kB. The FUPLA function
cannot be copied and not configured as 48th function. The function
plan programming language CAP 316 is described in the publication
1MRB520059-Uen.
3-395
ABB Switzerland Ltd RE.216 1KHA000951-UEN
I. CT/VT inputs:
• Constants, measured protection variables, IBB inputs and
sampled values
V. Measurements:
• Measured variable outputs
3-396
RE.216 1KHA000951-UEN ABB Switzerland Ltd
After clicking on the 'Browse' select the directory in which the files
'project1.bin' and 'project.cfg' are located and select 'project1.bin'. The
project name will be inserted from this file in the first line, alongwith the
time stamp in the second line and the file size in the third line.
3-397
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3.6.4.1.1. General
Summary of parameters:
Explanation of parameters:
RunOnCPU
Defines on which CPU the function should operate
RepetitionRate
Determines the number of FUPLA runs per cycle.
high: four FUPLA run per cycle
medium: two FUPLA run per cycle
low: one FUPLA runs per cycle
CycleTime
Determines the interval between FUPLA starts.
When for time critical applications the 'RepetitionRate' is set at
'medium' or 'high', then the 'CycleTime' must be set to 0ms
Otherwise for 'low' the 'CycleTime' must be set to the desired time
period between which the FUPLA should be processed.
BlockInput
(F → FALSE, T → TRUE, system binary input,
protection function binary output or input via the IBB).
This blocks FUPLA.
3-398
RE.216 1KHA000951-UEN ABB Switzerland Ltd
3.6.4.1.2. Timers
EXTIN signals of the time factor type and signals belonging to the
TMSEC group are displayed in this window.
The signals can be connected to the following sources:
• Measured variable constant
Setting range and resolution:
TMSEC signal group: 0...60 s, for TON
0...40 s, for TONS
TIMEFACTOR signal group: 0...4000 s, for TONL
• Protection function binary output (measured variable)
Observe the factors ms (TON), 10 ms (TONS), 1 s (TONL).
• Input from the SCS
Observe the factors ms (TON), 10 ms (TONS), 1 s (TONL).
• Input from AXM
Observe the factors ms (TON), 10 ms (TONS) 1 s (TONL).
3.6.4.1.3. Binary inputs
Binary inputs can be connected to the following sources:
• Always ON ('1')
• Always OFF ('0')
• Binary system inputs
• Protection function binary outputs
• Inputs from the SCS: 768 inputs in 24 groups of 32 signals each
• Inputs from the RIO (remote input / output system)
• Inputs from interlocking (64 groups of 48 signals each)
3.6.4.1.4. Binary outputs
Binary signals can be connected to the following sinks:
• Signaling relays
• Event processor (excluding 'BinExtOut' blocks)
• Tripping channels
• Outputs to the SCS: 768 inputs in 24 groups of 32 signals each
• Outputs from the RIO (remote input / output system)
• Outputs from interlocking (64 groups of 48 signals each)
3-399
ABB Switzerland Ltd RE.216 1KHA000951-UEN
FUPLA
1
O1 V1 function No.
Measurement
IBB IBB outputs
SCS output Measurement SCS input
CHAN. 4 CHAN. 9 inputs
O 64 V 64
64
IBB channel No. 4 is write-only and IBB channel No. 9 read-only. The
range of values for IBB channel No. 4 is -32768... +32767 which
corresponds to a 16 Bit integer.
3.6.4.2. Loading FUPLA
The FUPLA code has to be loaded again each time the FUPLA
configuration is changed. After making internal FUPLA changes and
copying the new versions of the files 'project1.bin' and 'project.cfg' to
the FUPLA directory, select 'Communication' from the main menu and
then 'Setfile Download to RE..16' to load the new FUPLA code.
3-400
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
Measurement of voltage, current, real and apparent power and fre-
quency, e.g. for display on the monitor of the control unit or for trans-
ferring to a high level station control system for further processing.
B. Features
• Single-phase measurement (1 voltage and 1 current I/P)
• Phase-to-ground or optionally phase-to-phase voltage meas-
urement (providing three-phase Y connected VTs are installed)
• Evaluation of the fundamental frequency components
• High accuracy in the frequency range (0.9 ... 1.1) fN
• Frequency of voltage measured unless voltage too low, in which
case current is measured; if both are too low, the result is set to
rated frequency
• At least 1 measurement per second
• Filters for voltage and current DC components
• Filters for voltage and current harmonics
• Provision for compensation of connection and measurement phase
errors.
I. CT/VT inputs:
• Voltage
• Current
IV. Measurements:
• Voltage (unit UN)
• Current (unit IN)
• Real power (unit PN (P))
• Apparent power (unit PN (Q))
• Frequency (unit Hz)
3-401
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Explanation of parameters
Run On CPU
Defines on which CPU the function should operate.
Angle
Characteristic angle for measuring real power. The phase-angle is
also taken into account when measuring apparent power.
The default setting of 0.0 degrees should not be changed, when
voltage and current I/Ps are in phase when measuring purely real
power, e.g. when measuring the phase-to-ground voltage and
current of the same conductor.
The setting may vary from 0.0 in the following cases:
• compensation of CT and VT phase errors
• compensation of the phase-shift between phase-to-ground and
phase-to-phase voltages
• compensation of the phase-shift between voltage and current in
general (e.g. when measuring S-T voltage and R current).
PN
Rated power corresponding to UN × IN.
This enables the amplitude of the measured power to be adjusted,
for example, to equal the rated power factor of a generator.
3-402
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Voltage Mode
Definition of the method of voltage measurement and therefore
also the calculation of power. Possible settings:
• Direct The voltage of the selected voltage I/P is
measured directly.
• Delta The phase-to-phase voltage formed by the
selected voltage I/P and the cyclically lagging
voltage channel is measured.
This setting is not permitted when only a single-
phase is connected or when phase-to-phase
voltages are connected.
Voltage Input Chan.
Defines the VT input channel.
All voltage I/Ps are available for selection.
Current Input Chan.
Defines the CT input channel.
All current inputs are available for selection.
3-403
ABB Switzerland Ltd RE.216 1KHA000951-UEN
E. Setting instructions
The measurement function must be carefully set to obtain the best
accuracy. The following must be observed:
• CT/VT input channel reference values
The reference values for the voltage and current input channels
must be set such that, when the rated values are applied to the
inputs, 1.000 UN and 1.000 IN are measured by the function.
3-404
RE.216 1KHA000951-UEN ABB Switzerland Ltd
3-405
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-406
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
Checking the plausibility of the three-phase current inputs for
• monitoring the symmetry of the three-phase system
• detection of a residual current
• supervision of the CT input channels
B. Features
• Evaluation of
• the sum of the three phase currents
• the sequence of the three phase currents
• Provision for comparing the sum of the three phase currents with a
residual current I/P
• Adjustment of residual current amplitude
• Blocking at high currents (higher than 2 × IN)
• Blocking of phase-sequence monitoring at low currents
(below 0.05 × IN)
• Insensitive to DC components
• Insensitive to harmonics
I. CT/VT inputs:
• Phase currents
• Neutral current (optional)
IV. Measurements:
• Difference between the vector sum of the three phase currents
and the neutral current
3-407
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Explanation of parameters:
Run On CPU
Defines on which CPU the function should operate.
Trip
Definition of the tripping logic (matrix) excited by the function’s O/P.
I-Setting
Current setting for tripping.
Delay
Time between start signal at the I/P and the tripping signal at the
O/P.
Forbidden settings:
≤ 1 s for current settings ≤ 0.2 IN
CT Compensation
Amplitude compensation factor for the residual current I/P,
enabling different transformation ratios of the main CTs for phase
and residual currents to be equalised.
The polarity of the residual current can be reversed by entering
negative values.
Current Input Channel
Defines the current input channel.
Any of the three-phase current I/Ps may be selected.
The first channel (R phase) of a three-phase group is entered.
Summation Current Input
Defines the neutral current input channel.
Any of the single-phase current I/Ps may be selected.
Block Input
Input for blocking the function.
3-408
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Trip Signal
Tripping signal.
Note:
If the phase sequence is incorrect, tripping takes place regardless of
setting (I-Setting).
3-409
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-410
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
Checking the plausibility of the three-phase voltage inputs for
• monitoring the sum of the phase voltages
• monitoring the asymmetry of the three-phase voltage system due
to the zero-sequence component
• supervision of the VT input channels
B. Features
• Evaluation of
• the sum of the three phase voltages
• the sequence of the three phase voltages
• Provision for comparing the sum of the three phase voltages with a
residual voltage I/P
• Adjustment of residual voltage amplitude
• Blocking at high voltages (higher than 1.2 × UN)
• Blocking of phase-sequence monitoring at low voltages
(below 0.4 × UN phase-to-phase)
• Insensitive to DC components
• Insensitive to harmonics
Evaluation of the phase voltages is only possible in the case of Y
connected input transformers, otherwise the residual component
cannot be detected.
I. CT/VT inputs:
• Phase voltages
• Neutral voltage (optional)
IV. Measurements:
• Difference between the vector sum of the three phase voltages
and the neutral voltage
3-411
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Explanation of parameters:
Run On CPU
Defines on which CPU the function should operate.
Trip
Definition of the tripping logic (matrix) output by the functions.
V-Setting
Voltage setting for tripping.
Delay
Time between start signal at the I/P and the tripping signal at the O/P.
Forbidden setting:
≤ 1 s for voltage settings ≤ 0.2 UN
VT Compensation
Amplitude compensation factor for the residual voltage I/P,
enabling different transformation ratios of the main VTs for phase
and residual voltages to be equalised.
The polarity of the residual voltage can be reversed by entering
negative values.
Voltage Input Channel
Defines the voltage input channel.
Any of the three-phase voltage inputs may be selected.
The first channel (R phase) of a three-phase group is entered.
Not applicable with delta connected VTs.
Summation Voltage Input
Defines the neutral voltage input channel.
Any of the single-phase voltage inputs may be selected.
Block Input
Input for blocking the function.
3-412
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Trip Signal
Tripping signal.
Note:
If the phase sequence is incorrect, tripping takes place regardless of
setting (U-Setting).
3-413
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-414
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
Recording current and voltage wave forms and the values of function
variables before, during and after operation of a protection function.
B. Features
• Records up to 12 CT and VT inputs
• Records up to 12 measured function variables
• Records up to 16 binary inputs
• Sampling rate of 12 samples per period (i.e. 600, respectively 720
Hz)
• 9 analog and 8 binary signals recorded in approx. 5 seconds
• Function initiated by the general pick-up or general trip signals, or
by any binary signal (binary I/P or O/P of a protection function).
• Data recorded in a ring shift register with provision for deleting the
oldest record to make room for a new one.
• Choice of procedure if memory full: either 'stop recording' or
'Overwrite oldest records'.
I. CT/VT inputs:
• All installed inputs available
V. Measurements:
• None
3-415
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-416
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Explanation of parameters:
Run On CPU
Defines on which CPU the function should operate
This function can only operate on CPU 1
Station Address
Number of the disturbance recorder for identifying records for
subsequent evaluation.
PreEvent
Definition of how long the recorder runs before a possible event.
Event
Definition of the maximum limit for the duration of an event
(recording mode A). In recording mode B, the same parameter sets
the duration of recording.
PostEvent
Definition of how long the recorder runs after an event (after
EventDur).
Recording Mode
Definition of how events should be recorded. Possible settings:
A: Recording only while the trigger signal is active. (minimum
time = 100 ms, maximum time = event duration setting).
B: Recording from the instant of the trigger signal for the event
duration setting.
Trigger Mode
Definition of the instant of triggering and how binary signals are
recorded. The configured CT and VT channels are always
recorded. Possible settings:
• TrigByStart: The disturbance recorder is triggered when a
protection function picks up (general pick-up).
Binary signals are not recorded.
• TrigByTrip: The disturbance recorder is triggered when a
protection function trips (general trip).
Binary signals are not recorded.
• TrigByBin1: The disturbance recorder is triggered by the binary
I/P 1. Binary signals are not recorded.
• TrigAnyBin: Defined binary signals are recorded and recording
is triggered by any of them via an OR gate.
• TrigStrt&Bin: Defined binary signals are recorded and recording
is triggered by any of them via an OR gate and also when a
protection function picks up (general pick-up).
• TrigTrip&Bin: Defined binary signals are recorded and
recording is triggered by any of them via an OR gate and also
when a protection function trips (general pick-up).
3-417
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Storage Mode
determines the procedure when the memory is full:
• StopOnFull: No further data are recorded when the memory is
full.
• Overwrite: The oldest records are overwritten and therefore
lost.
Binary Output
O/P signaling that recording is taking place.
Mem Full Signal
Warning that the memory is ¾ full. Normally, there remains
sufficient room for at least one more record after this signal is
generated.
Analog Input 1...Analog Input 12
Defines the CT and VT inputs to be recorded. The setting is the
number of the I/P.
The numbers of the CT and VT inputs do not necessarily have to
agree with the numbers of the CT and VT channels, however, no
gaps are permitted (setting zero).
3-418
RE.216 1KHA000951-UEN ABB Switzerland Ltd
3-419
ABB Switzerland Ltd RE.216 1KHA000951-UEN
E. Setting instructions
General:
3-420
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Application programs
Disturbance recorder data files are stored in a binary format and can
only be evaluated using the PSM E_wineve program (see Operating
Instructions 1MRB520372-Uen) or the REVAL program (see REVAL
Operating Instructions 1MDU10024-EN).
Disturbance recorder data (currents, voltages and measured variables)
can be transferred back to the RE.316*4 device using the conversion
program XSCON (in conjunction with the test set XS92b). To inject the
disturbance signals with other test equipment convert the disturbance
records with PSM / E_wineve to COMTRADE format.
Refer to Section 9.3. for the procedure for transferring disturbance
data via the IBB.
Measured functions may have values which cannot be entirely
reproduced by the evaluation software. Such variables can be reduced
using the scaling factors 'MeasScale'. The highest number the
evaluation software can reproduce faithfully is ±16535. The evaluation
software automatically takes account of the scaling factors.
'MeasScale' is calculated from:
Desired Range× Nominal value
16535
3-421
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Processor capacity:
The disturbance recorder function runs on the same central processing
unit (CPU) as the protection functions. The processor capacity
required by the disturbance recorder function as a percentage of the
total capacity and in relation to the number of signals is:
• 20 % for 9 analog and 0 binary signals
• 40 % for 9 analog and 16 binary signals
The disturbance recorder function will thus be generally confined to
recording the analog variables and be triggered by the general start or
general trip signals. Changes in the states of binary signals are
nevertheless registered by the event recorder.
Recording duration:
The time during which data are recorded can be determined from the
following relationship:
65535 − ((n + 1) × 22)
t rec = ×p
(2a + b) × 12
where trec: max. recording time
n: Number of events recorded
a: Number of CT and VT channels recorded
b: Number of Bytes required for binary channels
(one Byte per eight binary signals)
p: duration of one cycle at power system frequency
(e.g. 20 ms for 50 Hz)
3-422
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Example:
n = 10
a=9
b = 2 (i.e. 9 to 16 signals)
p = 20 ms
65535 − ((10 + 1) × 22)
t rec = × 20 ms = 5.44 s
( 2 × 9 + 2) × 12
It follows that for the given number of channels and power system
frequency, the capacity is sufficient for 10 events of 540 ms duration
each.
File PLOT.TXT
The programs PSM E_wineve, REVAL and XSCON need the file
PLOT.TXT to be able to process the disturbance recorder data.
Example PLOT.TXT
Hardware configuration: IN = 5 A
UN = 200 V)
N: 1
S: M216V6.6
D0 : f 0 GenStart /CO: 1
D1 : f 0 GenTrip /CO: 1
where:
N: station number: text
S: station name: text
Dnn binary channels: text (max. 8 char.)
Unn:, Inn: voltage channel, current channel: text (max. 8 char.)
/CO 1 to 15: number of the plot colour for PSM E_wineve
(In the case of REVAL the plotting colour is
determined by the particular layout)
/TR: conversion ratio for PSM E_wineve, REVAL
/UN: unit for PSM E_wineve, REVAL: text
3-423
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Ratio TR
Voltage channels for RE-216
Voltage channels for RE.216
15 V: TR = 5.082 in V
100 V: TR = 33.88 in V
200 V: TR = 67.76 in V
TR = 0.3388 times UN
Metering: 1 A: TR = 0.601 in A
2 A: TR = 1.202 in A
5 A: TR = 3.005 in A
TR = 0.601 times IN
3-424
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Example:
PLOT.TXT (existing file), plot020.txt (data for station No. 20) and
plot021.txt (data for station No. 21) can be combined using the DOS
command:
C:\REL316
C>copy PLOT.TXT+plot020.txt+plot021.txt PLOT.TXT
The file PLOT.TXT can be modified using an editor.
PSM / E_wineve
The data evaluation program must be installed in accordance with the
operating instructions 1MRB520372-Uen.
WINEVE
Copy the file 'PLOT.TXT' to the directory:
C:\I650\EVENTS
A disturbance should be recorded during the commissioning of every
relay and the record stored in the directory given above.
The procedure for installing the station parameter files is as follows:
• Start the WINEVE program.
• Open a fault record
The following error message appears:
C:\I650\STATION\ST0xx.PAR
Could not find file.
• Click on OK.
• Select the menu item 'Import station file' in the 'Parameter' menu.
• Select the file PLOT.TXT belonging to this disturbance recording.
• Select the menu item 'Save station' in the 'Parameter' menu.
This procedure must be repeated for all the relays. The configuration
file PLOT.TXT is no longer necessary and the error message
concerning the missing station file does not appear. WINEVE provides
facility for editing and resaving all the station parameters (texts,
colours etc.).
3-425
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Exception:
The ratios TR have to be changed in the file PLOT.TXT and the file re-
imported and saved again as described above.
REVAL
Copy the file 'PLOT.TXT' to the following directory:
C:\SMS\REVAL\EVENTS
REVAL rereads the file PLOT.TXT every time a disturbance record is
loaded, however, any colours specified in PLOT.TXT are ignored.
Instead, the colours are assigned by REVAL and can be edited after a
disturbance record has been loaded.
3-426
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
Checking the synchronisation criteria (amplitudes, phase-shift and
frequency difference) of two electrical systems and, providing the
corresponding limits are satisfied, enabling them to be connected in
parallel.
B. Features
• Monitoring synchronism:
Single-phase voltage measurement.
Comparison of the voltages (dU), phase-shift (dPh) and
frequencies (df) of two voltage vectors. Calculation of the
corresponding differences between the voltage vectors in the
complex plane.
Evaluation of the fundamental frequency components of the
voltage signals (after filtering of harmonic and DC components).
• Monitoring voltage:
Single or three-phase voltage measurement.
Evaluation of instantaneous values (non-digitally filtered analog
signals) resulting in a large permissible frequency range. Detection
of the largest and smallest of the three phase voltages in the case
of three-phase measurement.
No filtering of harmonics or DC component.
• Choice of phase for the voltage I/Ps on busbar and line sides (for
amplitude and phase-angle adjustment).
• Additional voltage I/P (for use in double busbar stations) with
provision for remote switchover.
• Provision for remote selecting the operating mode.
I. Analog inputs:
• Voltages (2 or 3 single or three-phase I/Ps for 'Voltage Busbar
Input 1', ' Voltage Busbar Input 2' and ' Voltage Line Input')
3-427
ABB Switzerland Ltd RE.216 1KHA000951-UEN
IV. Measurements:
Synchronism check (single-phase)
• 'Voltage amplitude difference'
(dU) = U bus - U line
• 'Maximum Phase Difference'
(dPh) = PhBusbar - PhLine
• 'Frequency Difference'
(⏐df⏐) = ⏐f bus - f line⏐
Voltage check (single or three-phase)
• Max. busbar voltage 'Maximum Busbar Voltage'
• Min. busbar voltage 'Mininimum Busbar Voltage'
• Max. line voltage 'Maximum Line Voltage'
• Min. line voltage 'Mininimum Line Voltage'
[Single-phase: max. voltage = min. voltage
Three-phase: max. voltage = max. phase-to-phase voltage
min. voltage = min. phase-to-phase voltage]
3-428
RE.216 1KHA000951-UEN ABB Switzerland Ltd
3-429
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Explanation of parameters:
GENERAL PARAMETERS
Run On CPU
Defines on which CPU the function should operate
PermitToClose
Logic (matrix) O/P channel at which the CB close signal is
available.
Max. Voltage Diff.
Max. permissible voltage difference ⏐dU⏐ between the phases
used for checking synchronism.
Max. Phase Diff.
Max. permissible phase-shift ⏐dPh⏐ between the voltages of the
phases used for checking synchronism.
Max. Frequency Diff.
Max. permissible difference of frequency ⏐df⏐ between the phases
used for checking synchronism.
Minimum Voltage
Voltage level for discriminating between busbar and line being live
(lowest phase voltage in the case of three-phase measurement).
Maximum Voltage
Voltage level for discriminating between busbar and line being
dead (highest phase voltage in the case of three-phase
measurement).
Operation Mode
Possible synchrocheck function operating modes:
• 'SynChk only': Synchrocheck
[Synchrocheck conditions fulfilled AND
(bus live AND line live)]
• 'dBus & lLine': Synchrocheck OR
(bus dead AND line live)
• 'lBus & dLine': Synchrocheck OR
(bus live AND line dead)
• 'dBus ⏐ dLine': Synchrocheck OR
(bus dead AND line live) OR
(bus live AND line dead)
• 'dBus & dLine': Synchrocheck OR
(bus live AND line dead)
Supervising Time
Period between the function picking up and it issuing the CB close
enable ('PermitToClos').
All the conditions for synchronism must remain fulfilled during this
time, otherwise the function is reset.
3-430
RE.216 1KHA000951-UEN ABB Switzerland Ltd
t-Reset
Reset time following the non-fulfilment of one or more synchronism
conditions.
ANALOG INPUT
Voltage Busbar Input Phase
Choice of phase I/P on the busbar side.
Possible settings:
1 ph RS, ST or TR; 1 ph RE, SE or TE; 3 ph Y; 3 ph ∆
The phase chosen must agree with the voltage I/P channel
selected (i.e. ' Voltage Busbar Input 1' and, if selected, ' Voltage
Busbar Input 2').
Voltage Busbar Input 1
1st voltage I/P channel on the busbar side. This must agree with
the phase chosen (' Voltage Busbar Input Phase'). In the case of a
three-phase connection (' Voltage Busbar Input Phase' = '3 ph Y' or
'3 ph ∆'), the first channel
(R phase) of a three-phase group must be chosen.
Voltage Busbar Input 2
2nd voltage I/P channel (if applicable) on the busbar side. This
must agree with the chosen phase (' Voltage Busbar Input Phase').
In the case of a three-phase connection (' Voltage Busbar Input
Phase' = '3 ph Y' or '3 ph ∆'), the first channel (R phase) of a three-
phase group must be chosen.
If a second I/P is not configured, the function only takes account of
the 1st voltage I/P channel (' Voltage Busbar Input 1').
Voltage Line Input Phase
Choice of phase I/P on the line side.
Possible settings:
1 ph RS, ST or TR; 1 ph RE, SE or TE; 3 ph Y; 3 ph ∆
The phase chosen must agree with the voltage I/P channel
selected (i.e. ' Voltage Line Input').
Voltage Line Input
Voltage I/P channel on the line side. This must agree with the
chosen phase (' Voltage Line Input Phase'). In the case of a three-
phase connection (' Voltage Line Input Phase' = '3 ph Y' or '3 ph
∆'), the first channel (R phase) of a three-phase group must be
chosen.
3-431
ABB Switzerland Ltd RE.216 1KHA000951-UEN
SIGNAL OUTPUTS
Permit To Close Signal
Signal to enable closure of the circuit-breaker.
This is generated at the end of the 'Supervising Time' and remains
active as long as the synchronism conditions are fulfilled, or until a
blocking signal is received, or the synchrocheck function resets.
Start Signal
Signal generated at the instant the conditions for synchronism are
fulfilled for the first time.
Sync. Blocked Signal
Signal indicating that the synchrocheck function is disabled, i.e.
both the I/Ps 'Interlock Synchrocheck Bus 1' and ' Interlock
Synchrocheck Bus 2' are set to 'FALSE' (F), and the synchrocheck
algorithm is not operative.
Trig. Blocked Signal
The CB close enabling O/Ps are blocked (one or more blocking
I/Ps are logical '1'), but the synchrocheck algorithm continues to
run.
Sync. Override Signal
Signal indicating that the synchrocheck function is bypassed
a signal output to releasee the CB close is generated is
instantaneously generated ('PermitToClos').
Ampl. Diff. OK Signal
Signal indicating that the voltage difference ⏐dU⏐ between the
phases used for synchrocheck has fallen below 'Max Voltage Diff.'.
Phase Diff. OK Signal
Signal indicating that the phase-shift ⏐dPh⏐ between the phases
has fallen below the value of 'Max. Phase Diff.'.
Freq. Diff. OK Signal
Signal indicating that the difference of frequency ⏐df⏐ has fallen
below 'Max. Frequency Diff.'.
Live Bus OK Signal
Signal indicating that the busbar is energised.
(U > 'Minimum Voltage')
Dead Bus OK Signal
Signal indicating that the busbar is de-energised.
(U < 'Maximum Voltage')
Live Line OK Signal
Signal indicating that the line is energised.
(U > ' Minimum Voltage')
Dead Line OK Signal
Signal indicating that the line is de-energised.
(U < ' Maximum Voltage')
3-432
RE.216 1KHA000951-UEN ABB Switzerland Ltd
BINARY INPUTS
Bus 1 Active, Bus 2 Active
Binary I/Ps for switching between voltage I/P channels by an
remote signal in the case of double busbars (mimic busbar). These
I/Ps are only active providing the second busbar I/P channel has
been configured ('Voltage Busbar Input 2').
• Assuming that only the first busbar I/P channel has been
configured, all the blocking I/Ps are active regardless of the
statuses of the binary I/Ps 'Bus 1 Active' and 'Bus 2 Active'.
The active blocking I/Ps are connected internally to an OR gate
and the CB close enabling O/Ps are blocked, if one of them is set
to 'TRUE' (T).
3-433
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Override Synchrocheck
Binary I/P for bypassing the synchrocheck function. This causes an
enabling signal to be issued regardless of whether the
synchronism conditions are fulfilled or not. It overrides the
function’s blocking and other enabling I/Ps.
Operation Mode Input 1, Operation Mode Input 2
I/Ps for remotely selecting the operating mode:
3-434
RE.216 1KHA000951-UEN ABB Switzerland Ltd
E. Setting instructions
3.6.9.1. General
It is only permissible to connect two energised parts of a power
system, if the difference between the amplitudes of their voltages and
the phase-shift between them are within acceptable limits.
The purpose of the synchrocheck function is to determine these
parameters and decide whether it is permissible to connect the sys-
tems in parallel.
The function thus issues an enable signal ('Permit To Close'),
providing the voltages of the two systems are higher than the set
minimum voltage ('Minimum Voltage') and
• the difference between the voltage amplitudes ⏐dU⏐
• the phase-shift ⏐dPh⏐
• the difference between the frequencies ⏐df⏐
do not exceed the limits set for the parameters 'Max. Voltage Diff.', 'Max.
Phase Diff.' and 'Max. Freq Diff' for the adjustable time 'Supervising
Time'.
According to the operating mode ('Operation Mode') selected, the
function also permits de-energised parts of a power system to be
coupled.
Provision is also made for switching between voltage I/Ps belonging to
the busbars of a double busbar station by appropriately controlling two
binary I/Ps ('Bus 1 Active' and 'Bus 2 Active'). Note that the function
can only check the synchronism of two voltages at any one time, that
of one of the busbars and that of the line.
The synchrocheck function is therefore used mainly
• to connect infeeds in parallel and to connect outgoing feeders to
the system
• to interconnect two synchronous or asynchronous parts of a power
system
• in auto-reclosure schemes
• as a safety check when carrying out manual switching operations
Note:
The expressions in brackets are the names of the corresponding
setting parameters. Refer also to Section D.
3-435
ABB Switzerland Ltd RE.216 1KHA000951-UEN
T1
CB
Line
VT Line
T2
Closing
command
Switching
unit
Permit to Close
uBus2Activ
uLine Input
uBus1Activ
VT SS2
uBusInput2 Synchrocheck BlckTrigLine
BlckTrigBus2
VT SS1
uBusInput1
BlckTrigBus1
where:
SS1, SS2: busbar 1, busbar 2
VT SS1, VT SS2, VT Line: VTs on busbar 1, busbar 2 and line
T1, T2: isolators on busbars 1 and 2
CB: circuit-breaker
Voltage Busbar Input 1,
Voltage Busbar Input 2: voltage I/P channels on the busbar side
Voltage Line Input: voltage I/P channel on the line side
Interlock Synchrocheck Bus 1,
Interlock Synchrocheck Bus 2,
Interlock Synchrocheck Line:
I/Ps for blocking the synchro-check
function by the VT fuse failure
equipment
Bus 1 Active, Bus 2 Active : Binary I/Ps for switching between the
analog busbar voltage I/Ps in
accordance with the configuration of the
isolators (mimic busbar)
3-436
RE.216 1KHA000951-UEN ABB Switzerland Ltd
3.6.9.2. Settings
Max. voltage difference ⏐dU⏐ Max. Voltage Diff.
Max. phase-shift ⏐dPh⏐ Max. Phase Diff.
Max. frequency difference ⏐df⏐ Max. Frequency Diff.
Minimum voltage level for monitoring Minimum Voltage
(determination of whether plant is energised)
Maximum voltage level for monitoring Maximum Voltage
(determination of whether plant is de-energised)
Choice of operating mode Operation Mode
Measuring period (delay before issuing Supervising Time
enable)
Reset delay t-Reset
Choice of phase for monitoring on the Voltage Busbar Input Phase
busbar side
Choice of phase for monitoring on the Voltage Line Input Phase
line side
The phase-shift dPh between the voltages and the difference between
their amplitudes dU are calculated from the corresponding vector
diagram in the complex plane.
Apparent
dÛ
Û bus, : complex vectors for Û line
ωL
U bus and U line
Û line ωB
Û bus ωB, ωL : angular velocities for
dPhi Û bus and Û line
PhiL
dÛ = Û bus − Û line
PhiB
dPhi = PhiB − PhiL
Real
3-437
ABB Switzerland Ltd RE.216 1KHA000951-UEN
The conditions for synchronism are fulfilled, providing the values of the
resulting variables are within the limits set for 'Max.Voltage Diff.', 'Max
Phase Diff.' and 'Max. Frequency Diff.'.
Typical values:
Max.Voltage Diff.: 0.2 UN
Max Phase Diff.: 10°
Max. Frequency Diff.:
50 mHz - for connecting largely synchronous parts of a stable
closely meshed system or where high demands
with regard to synchronism have to be fulfilled.
100 mHz - in auto-reclosure schemes with long dead times
(e.g. three-phase slow reclosure) or for auto-
reclosure of short transmission lines.
200 mHz - in auto-reclosure schemes with short dead times,
but where high slip frequencies are to be expected.
Note:
The setting of the synchronism measuring period ('Supervising
Time') must be chosen to correspond to the settings for the maximum
phase-shift and maximum frequency difference.
3-438
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Typical values:
Minimum Voltage 0.70 UN
Maximum Voltage 0.30 UN
3-439
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Choice of phase for the voltage I/P on the busbar and line sides
('Voltage Busbar Input Phase', 'Voltage Line Input Phase')
The phase voltage ('Voltage Busbar Input Phase', 'Voltage Line Input
Phase') to be used for determining synchronism can be entered
separately for busbar and line I/Ps (to facilitate individual adjustment of
phase-angle and amplitude).
All single and three-phase voltages are available for setting (1ph RS,
ST or TR; 1ph RE, SE or TE; 3ph Y; 3ph ∆), but the ones chosen must
agree with the setting for the corresponding I/P channels (see Section D.
'Synchrocheck function settings').
Where both busbar I/Ps are in use, the definition of the phase ('Voltage
Busbar Input Phase') applies to both busbars.
Notes:
• A phase-to-phase measurement is to be preferred for a single-
phase voltage measurement.
If a single-phase I/P has to be chosen on both sides, the same
phase should be used wherever possible.
• If a three-phase 'Y' connection is selected, phase-to-phase
voltages are formed internally. This reduces the harmonic content
and enables the function to continue to be used in ungrounded
systems, which are required to remain in service with a single earth
fault.
• According to the setting for 'Voltage Busbar Input Phase' and
'Voltage Line Input Phase', either a just one phase or all three
phases are monitored.
Whether or not the conditions for synchronism ('dU', 'dPh' and 'df')
are fulfilled is determined on the basis of a single phase, whereby
the following apply:
• Where three phases are monitored on busbar and line sides,
the phase-to-phase potential URS is the one extracted for
further processing.
• Should a three-phase measurement be defined on one side
and a single-phase on the other, Then the single-phase voltage
set for the single-phase I/P is used on both sides.
3-440
RE.216 1KHA000951-UEN ABB Switzerland Ltd
where:
ts: circuit-breaker operating time
Typical range: 0 ... 100 ms
tv: time required by the function to pick up
(response by the function to transient phenomena in the input
voltage and timer tolerances):
• typically 60... 80 ms for values of 'Supervising Time' < 200 ms
• typically 80... 100 ms for values of 'Supervising Time' ≥ 200 ms
The above setting for the measuring period ensures that for a constant
frequency difference df within the setting of 'Max. Frequency Diff.', the
phase-shift dPh will still be inside the set permissible angular range
(- 'Max. Phase Diff.' to + 'Max. Phase Diff.') at the end of the time
'Supervising Time'.
Typical values:
For a phase-shift setting ('Max. Phase Diff.') of 10°:
3-441
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Typical value:
t-Reset 50 ms
Note:
Where high slip frequencies df are to be expected, 't-Reset' must be
short enough to prevent the phase-shift from exceeding the set
permissible range of phase-angles (-'Max. Phase Diff.' to + 'Max.
Phase Diff.') during the reset time.
3-442
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Other combinations of the states of these two I/Ps do not result in any
switching of the AnalogAddr channels and the prevailing situation is
maintained.
Notes:
• The function (timer, all measuring elements and the associated
O/Ps) is automatically reinitialised when busbar I/Ps are switched.
This procedure takes about 60 ms (internal response times).
The function then begins to evaluate the new busbar voltage and
from this instant onwards the generation of an enable signal
('PermitToClos') relating to the new system configuration is
possible.
• The two binary I/Ps 'Bus 1 Active' and 'Bus 2 Active' are inactivated
in configurations in which only one busbar I/P ('Voltage Busbar
Input 1') is defined.
3-443
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-444
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Application example:
The scheme below shows a synchrocheck function in the same unit as
the distance protection and autoreclosure functions. The synchrocheck
function is only required during the dead times of the autoreclosure
function. This is achieved by connecting the inverted O/P signal
'AR Ready' generated by the autoreclosure function to the binary I/P
'Release Input 1' (or 'Release Input 2') of the synchrocheck unit.
Start
Distance Auto- AR ready Synchro-
function reclosure check
Trip CB function
ReleasInp1
Trip CB 3P Close CB
SynchroChck
PermitToClose
3-445
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-446
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
Suppresses the recording of multiple events for binary signals subject
to contact bounce.
B. Features
• Input channels can be set by
• binary input signals
• output signals (trips) from protection functions
• provision for inverting signals applied to the inputs
• adjustable supervision time and permissible signal change
• Two outputs assigned to each input:
• signal flutter detected (too many signal changes during the
supervision time)
• image of the status of the input signal
I. CT/VT inputs:
• None
IV. Measurements:
• None
3-447
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Explanation of parameters:
Run On CPU
Defines on which CPU the function should operate
Supervising Time
defines the time during which the flutter is supervised.
Nr of Signal Changes
defines the number of signal changes during the supervision time.
If a higher number of signal changes is greater than this value, the
signal is deemed to be fluttering.
Binary Input 1
Binary input No. 1
Binary Input 2
Binary input No. 2
Binary Input 3
Binary input No. 3
Binary Input 4
Binary input No. 4
State of Input 1
signals the status of input No. 1
3-448
RE.216 1KHA000951-UEN ABB Switzerland Ltd
State of Input 1
signals the status of input No. 1
State of Input 2
signals the status of input No. 2
State of Input 3
signals the status of input No. 3
State of Input 4
signals the status of input No. 4
Flutter State Input 1
signals that flutter detected on input No. 1
Flutter State Input 2
signals that flutter detected on input No. 2
Flutter State Input 3
signals that flutter detected on input No. 3
Flutter State Input 4
signals that flutter detected on input No. 4
3-449
ABB Switzerland Ltd RE.216 1KHA000951-UEN
E. Setting instructions
General:
If a signal at an input changes its state in a given period of time
(Supervising Time) more frequently than a given number of times (Nr of
Signal Changes), the input is deemed to be fluttering due, for example,
to contact bounce. As a result, no further signal changes at the input
are recorded as events. Its basic protective function, however, remains
intact. This condition is maintained until fewer signal changes are
counted than the number defined for the given period.
Settings:
Supervision time Supervising Time
Number of signal changes permissible Nr of Signal Changes
The function’s counters continuously count the signal changes at the
inputs selected. They are reset at the end of each supervision period.
Should the number of signal changes counted during the period
exceed the maximum permissible for the input, the input is tagged as
fluttering and the corresponding output set. The 'fluttering' condition is
maintained for as long as the number of signal changes is higher the
set limit and is only cancelled and the output reset when a smaller
number of changes is counted during the period.
To prevent the flutter function from fluttering itself (i.e. the number of
changes of an input is just about equal to the number of changes
setting), the number of changes for resetting to the non-fluttering state
must be less than the number of changes required for pick-up minus
ten percent, but at least one change less when the number of changes
for pick-up is set to less than ten.
Note that the start and finish of a supervision period is not signaled
externally. It can therefore occur that fluttering is not signaled although
the number of changes briefly exceeded the maximum permissible, but
the excess happened to straddle two supervision periods.
Typical settings:
Supervising Time 10 s
Nr of Signal Changes 20
3-450
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A. Application
Measurement of 3 phase voltages, 3 phase currents, active and
reactive power, power factor cos ϕ (cos phi) and frequency, e.g. for
display on an operating device or transmission to a station monitoring
system.
B. Features
• Measurement of 3 phase voltages (Y and delta), currents, active
and reactive power, power factor cos ϕ and frequency.
• Provision for using the 3 phase current inputs in combination with
either 3 phase-to-phase voltages or 3 phase-to-earth voltages.
• 2 independent impulse counter inputs for calculation of interval and
accumulated energy
• The three-phase measurement and impulse counters can be used
independently and may also be disabled.
• Up to 4 measurement module functions can be configured on one
RE..16 device.
• All inputs and outputs can be configured by the user.
I. CT / VT inputs:
• Voltage
• Current
3-451
ABB Switzerland Ltd RE.216 1KHA000951-UEN
3-452
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Explanation of parameters:
Run On CPU
Defines on which CPU the function should operate
CurrentInp
defines the current input channel. Only three-phase CTs can be set
and the first channel (R phase) of the group of three selected must
be specified.
Current and voltage input signals must come from the same CT/VT
input module.
VoltageInp
defines the voltage input channel. Only three-phase VTs can be
set and the first channel (R phase) of the group of three selected
must be specified.
Voltage and current inputs must be assigned before the three-
phase measurement part of the function can be activated. If only
the pulse counter part of the function is to be used, both CT and
VT inputs must be disabled.
PN
Reference value for measuring power. It enables the amplitude of
the power values to be adjusted to take account, for example, of
the rated power factor cos ϕ or to compensate the amplitude errors
of the input transformers.
3-453
ABB Switzerland Ltd RE.216 1KHA000951-UEN
AngleComp
Angular setting for compensating the phase error. It is set to obtain
the best possible power measuring accuracy. In many cases, the
default setting of 0.0 degrees will be acceptable, but a different
setting may be necessary to compensate the following:
c) CT and VT phase errors
→ typical setting: -5° ... +5°
d) correction of CT or VT polarity
→ typical setting: -180°or +180°
t1-Interval
Interval set for accumulating pulses assigned to E1 acc_interval and
Pulse1acc_interval.
The following settings are possible: 1 min, 2 min, 5 min,
10 min, 15 min, 20 min, 30 min, 60 min and 120 min.
PulseInp 1
Input for energy counter impulse.
Note: Minimum pulse-width is 10 ms.
Reset 1
Input to reset E1accumulate and Pulse1accumulate outputs.
ScaleFact 1
Factor for scaling E1 outputs in relation to pulse counter output:
E1acc_interval = Pulse1acc_interval × ScaleFact 1
E1accumulate = Pulse1accumulate × ScaleFact 1
Cnt 1 New
Output to indicate that new values are available at impulse counter
1 outputs and have been frozen. The binary output is cleared 30 s
after the interval starts.
t2-Interval
See t1-Interval.
PulseInp 2
See PulseInp 1.
Reset 2
See Reset 1.
ScaleFact 2
See ScaleFact 1.
Cnt 2 New
See Cnt 1 New.
3-454
RE.216 1KHA000951-UEN ABB Switzerland Ltd
E. Setting Instructions
To get the best performance from the measurement module, be sure
to set it properly. The following notes should help to decide the correct
settings:
• Reference values for the analog input channels
The settings in this case should be chosen such that the functions
measures 1.000 UN and 1.000 IN when rated voltage and current
are being applied. In many cases the default setting (1.000) will be
satisfactory.
• Phase compensation 'Angle comp'
This setting is important for correct measurement of active and
reactive power and the power factor cos ϕ. For most cases, it is
possible to accept the default value 0.0°.
A different setting may be necessary to compensate the following:
a) CT and VT phase errors
→ typical setting: between -5.0° and +5.0°
b) correction of direction of the measurement or CT or VT polarity
→ typical setting: -180.0° or +180.0°
Add multiple errors to obtain the correct compensation setting.
The angles given apply for connection according to the con-
nections in Chapter 12.
• Voltage measurement
The zero-sequence component in case of delta-connected VTs is
assumed to be zero, but with Y-connected VTs the zero-sequence
voltage does have an influence on the phase-to-ground
measurements. In an ungrounded power system, the phase-to-
ground voltages will float in relation to ground.
• Power and frequency measurements
A power measurement is obtained by summing the powers of the
three-phase system: 3 × S = UR × IR* + US × IS* + UT × IT*. The
measurement is largely insensitive to frequency in the range
(0.8...1.2) fN. The frequency measured is that of the positive
sequence voltage. Should the voltage be too low, the frequency is
not measured and a value of 0.0 Hz results.
• Where only the impulse counter is in use, both analog inputs
(current and voltage) must be disabled.
• Where only the measurement part of the function is in use, the
binary impulse and reset inputs of both impulse counters must be
disabled, i.e. 'always FALSE'.
3-455
ABB Switzerland Ltd RE.216 1KHA000951-UEN
tPulse tPause
3-456
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Intermediate Eaccumulate
buffer Scaling
accumulate
Pulseaccumulate
Signal response
tinterval tinterval tinterval Reset
tinterval t
Impulse counter
input t
Eacc_interval
Pulseacc_interval t
Counter values
to be transferred
Eaccumulate
Pulseaccumulate
Counter value t
to be transferred
Fig. 3.101 Block diagram for one impulse counter channel and
signal response
3-457
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Impulse counter values are stored in a RAM with a battery supply and
are not lost should the auxiliary supply fail. Impulses arriving at the
inputs while the software is being initialised, e.g. after settings have
been made, are lost.
• Capacity for Pulseaccumulate:
At the maximum impulse repetition rate, the total number of
impulses counted during a year is 25 pps × 3’600 s/h × 8’760
h/year = 788’400’000 impulses per year. The output is reset to zero
when a counter reaches 2’000’000’000, i.e. 2 × 109.
Unless special measures taken or a counter is reset, it can
overflow at the worst after approx. 2’537 years.
• Should an impulse counter overflow, the value of Pulseaccumulate is
recorded in the event list. No further measures have been
included, because
1. an overflow is hardly likely to occur.
2. should an overflow occur, it is obvious providing the counters
are checked regularly, for example, by an SCS.
If necessary, the total number of impulses counted since the last
reset can be determined even after an overflow.
3-458
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Reset
t
Measurement
event
Pulseaccumulate Internal only
CounterFrozen 30 s 30 s 30 s 30 s 30 s
3-459
RE.216 1KHA000951-UEN ABB Switzerland Ltd
August 05
4.1. Summary............................................................................................4-4
4-1
ABB Switzerland Ltd RE.216 1KHA000951-UEN
4.9. Auto-reclosure..................................................................................4-83
4.9.1. Logic segments................................................................................4-83
4.9.2. Signal designations..........................................................................4-91
4-2
RE.216 1KHA000951-UEN ABB Switzerland Ltd
4-3
ABB Switzerland Ltd RE.216 1KHA000951-UEN
4-4
RE.216 1KHA000951-UEN ABB Switzerland Ltd
4-5
ABB Switzerland Ltd RE.216 1KHA000951-UEN
4.286
HV system
4.286
4-6
RE.216 1KHA000951-UEN ABB Switzerland Ltd
95.8793
95.8793
4.1238
105.4672
2.0619
2.0619
5.4641
9.5879
T
G
Fig. 4.2 E/F on the HV system fed by the generator and the
network
4-7
ABB Switzerland Ltd RE.216 1KHA000951-UEN
IE
IE External E/F
R2
RS
Ui
I>
I2 I2
RS
VDR Shorting contact
I>
The knee-point voltage of the CTs is specified such that the they can
supply sufficient current during an internal fault to enable the
protection to trip. The knee-point voltage Uk of the CTs must therefore
be appreciably higher than the voltage drop ∆Ua.
4-8
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Symbols used:
IE primary star-point current (AC component) for a
through-fault
I2 secondary current of the non-saturated CTs
I2N CT secondary rated current
I1N CT primary rated current
IN protection rated current
R2 secondary resistance of the saturated CT at 75°C
RL lead resistance according to Fig. 4.3
∆Ua , ∆Ui voltage drop across the circulating current circuit for
external, respectively internal faults.
Uk knee-point voltages of the CTs
Û peak value of voltage
I current setting
RS stabilising resistor
IF highest primary fault current (AC component) for an
internal E/F.
Equations:
∆Ua = (R2 + 2 RL) I2
Uk ≥ 2 ∆Ua
I = 0.25 I2N (solidly grounded star-point)
I = 0.10 I2N (impedance grounded star-point)
∆U a
RS ≥
I
∆Ui = RS I2 (I2 is given by IF)
U max =2 2U k ( ∆U i − U k )
4-9
ABB Switzerland Ltd RE.216 1KHA000951-UEN
4.2.2.4. Example
Determination of the stabilising resistor:
CTs 1000/1 A
R2 = 5 Ω
100 m
RL = = 0.5 Ω
50 × 4 mm 2
(CT leads 100 m long, specific conductance of 50 Ω-1 m/mm2, gauge
of 4 mm2)
1
I2 = 100 000 = 100 A
1000
∆Ui = RS × I2 = 300 × 100 = 30 000 V
Umax = 2 2 Uk ( ∆Ui − Uk )
4-10
RE.216 1KHA000951-UEN ABB Switzerland Ltd
CT specification:
Rated currents 1000/1 A
Winding resistance R2 ≤ 5 Ω
Knee-point voltage Uk = 200 V
Magnetising current I2m ≤ 2 % I2N
i.e. I2m ≤ 0.02 A at U2 = 60 V
The CTs must conform to British Standard 3938, Class X.
The CTs should also:
• have evenly distributed secondary windings on a toroidal core (i.e.
to minimize the secondary leakage flux)
• not have any winding correction
4-11
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Shorting contacts:
The circulating current circuit must be short-circuited within the thermal
rating time of the two resistors, if an internal fault cannot be tripped in
a shorter time.
Setting value of the function 'Current':
I-setting 0.25 IN
Delay 0.02 s
u
2
Ui =
2 . 30 kV
Û=
u2 6905 V u2
i2
2 . 100 A
Î=
i2 23 A i2
4-12
1
9
8
7
6 METROSIL NON-LINEAR RESISTORS
Fig. 4.5
5
4 Typical Voltage - Current Characteristics (D.C.)
3 Type 600 A/S1/256 C = 900
Type 600 A/S1/793 C = 650 1088
2
Type 600 A/S1/1088 C = 450
1000 793
1
6
8
7 256
RE.216 1KHA000951-UEN
5
4
Voltage (volts)
1
100 9
8
7
10 1
1 2 3 4 5 6 7 8 91 2 3 4 5 6 7 8 91 2 3 4 5 6 7 8 91 2 3 4 5 6 7 8 91 2 3 4 5 6 7 8 9 1
4-13
ABB Switzerland Ltd
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Trip Trip
U U set = 0.85 UN TRIP time = 0.0 s
Delay = 1.00 s Reset time = 20.0 s
Block
4-14
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Design
The ancillary unit Type YWX111-11/-21 is in a casing for surface
mounting having dimensions of 183 x 113 x 81 mm.
4.4.2. Determining the settings
Since it is not possible to set the value of leakage resistance directly in
ohms, a voltage (U set) proportional to a given leakage resistance has
to be set on the RE.216 together with a time delay t [s]. A typical
setting range for the leakage resistance R would be 0 to 5000 Ω:
• U set = 0.5...3 V
• t = 0.5...5 s
4-15
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Recommended settings:
• Stage 2: 'Trip'
R < 2000 Ω
t > 1.5 s
• Stage 1: 'Alarm'
R < 5000 Ω
t > 1.5 s
Note that the voltage across the bridge is low for a high leakage
resistance and high for a low leakage resistance.
4-16
RE.216 1KHA000951-UEN ABB Switzerland Ltd
4-17
ABB Switzerland Ltd RE.216 1KHA000951-UEN
YWX 111-11/-21
• Standard: R 9 = 120 Ω
(normal sensitivity)
• Units with a shaft filter: R 9 = 1 kΩ
(increased sensitivity)
Refer to Fig. 4.13 for the location of the resistor R9.
4.4.5. Commissioning
The commissioning procedure is given in Sections 4.4.5.1 to 4.4.5.4.
The tripping circuits of the RE.216 must be interrupted while carrying
out commissioning.
4-18
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Procedure:
• Interrupt the tripping circuits from the RE.216.
• Connect and AC voltmeter to terminals 1 and 2 of
YWX111-11/-21.
• Connect a capacitor decade in place of CX.
• Close the field switch.
• Switch on the auxiliary supply USH.
• Vary the capacitor decade in place of CX until the output voltage at
terminals 1 and 2 of YWX111-11/-21 becomes a minimum;
normally < 50 mVr.m.s..
4-19
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Theoretical value of CX
a) Circuit according to Fig. 4.10 (or Fig. 4.7):
(CK1 +CK 2 ) × CR
CX =
CK1+CK 2 +CR
b) Circuit according to Fig. 4.11:
3CK × (3CS + CR )
CX =
3CK + 3CS + CR
4-20
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Procedure:
• Interrupt the tripping circuits from the RE.216.
• Connect resistors for RP = 5000 Ω, 2000 Ω and RP = 0 Ω to the
positive pole of the excitation circuit.
• Close the field switch.
• Switch on the auxiliary supply USH.
• Measure the voltage across the bridge corresponding to the
different values of resistance.
• Set the voltages measured at the two resistances of 2000 and
5000 Ω on the RE.216. They should lie between 0.5 and 3 V.
• Repeat the procedure with the resistors RP = 5000 Ω, 2000 Ω and
RP = 0 Ω connected to the negative pole of the excitation circuit.
4.4.5.4. Testing in operation
This test checks that the RE.216 and the ancillary unit function cor-
rectly with the generator in operation. Once again a rotor fault is simu-
lated by installing a leakage resistor. The protection must effectively
trip.
4-21
ABB Switzerland Ltd RE.216 1KHA000951-UEN
4-22
RE.216 1KHA000951-UEN ABB Switzerland Ltd
4-23
ABB Switzerland Ltd RE.216 1KHA000951-UEN
4.4.10. Appendices
Fig. 4.10 Wiring diagram of the relay RE.216 and ancillary unit
Type YWX111-11/-21
Connection to the d.c. part of the excitation circuit
Fig. 4.11 Wiring diagram of the relay RE.216 and ancillary unit
Type YWX111-11/-21
Connection to the a.c. part of the excitation circuit
4-24
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Fig. 4.12 Block diagram and terminals of the ancillary unit Type
YWX111-11/-21
Fig. 4.13 Component side of the PCB in the ancillary unit Type
YWX111-11/-21(derived from HESG 437 807)
4-25
ABB Switzerland Ltd RE.216 1KHA000951-UEN
4-26
RE.216 1KHA000951-UEN ABB Switzerland Ltd
instable
stable
instable
stable
instable
generator/transformer set
generator connected to busbar
Tripping
area
Tripping
area
4-27
ABB Switzerland Ltd RE.216 1KHA000951-UEN
4-28
RE.216 1KHA000951-UEN ABB Switzerland Ltd
4-29
ABB Switzerland Ltd RE.216 1KHA000951-UEN
4-30
RE.216 1KHA000951-UEN ABB Switzerland Ltd
4-31
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Short-time
Voltage transformer
sec. rating
U1N [V] U2N [V] S [kVA] [A] for 10 s
10500 167 70 240
3
4-32
RE.216 1KHA000951-UEN ABB Switzerland Ltd
UN Ubroken ∆ Rp Re I2
[V] [V] [Ω] [A] VT [A] 10 s
10500 500 250 2 1.7 Ω 240
4.6.7. Contactor
The contactor switches both ends of the grounding resistor Re.
4.6.8. Residual current CT
Alternative I:
1 core-balance CT 100/1 A, rated burden 2.5 Ω.
Alternative II:
3 bushing CTs, .../5 A - 33/1 A, rated burden 1.5 Ω.
The above burdens apply for CT leads of 2 x 100 m with a gauge of
4 mm2.
4-33
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Block
Generator ground fault signal
4-34
RE.216 1KHA000951-UEN ABB Switzerland Ltd
4-35
ABB Switzerland Ltd RE.216 1KHA000951-UEN
1
3
U> 2
5
P> 6 7 8
U> 9
UR
UTR USR U TR
U
UT US
HEST 965039 FL
U SR
where:
1 VT at the generator neutral
2 start-up protection voltage relay
3 3 neutral CTs for measuring the ground fault current
4 power relay for the generator ground fault protection scheme
5 grounding transformer
6 ground resistor Re for the generator ground fault protection scheme
7 transient voltage damping resistor Rp
8 intermediate VT
9 voltage relay for the busbar ground fault protection
4-36
RE.216 1KHA000951-UEN ABB Switzerland Ltd
4-37
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Injection
transformer
unit REX011
Injection
unit
REX010 RE.216
4-38
RE.216 1KHA000951-UEN ABB Switzerland Ltd
4-39
ABB Switzerland Ltd RE.216 1KHA000951-UEN
4-40
RE.216 1KHA000951-UEN ABB Switzerland Ltd
START
I max = highest
value of
IR, IS, IT
N
I max > I start
set log.
signal "ph" (R, S, T)
N all
phase currents
IR, IS, IT
set log.
signal "E"
END
HEST 955038 FL
4-41
ABB Switzerland Ltd RE.216 1KHA000951-UEN
START
[(IE ≥ 3I0min) N
AND (IE ≥ 0.25 Imax)]
AND/OR
(UE ≥ 3U0 min)
Y
(Iph1 ≥ Imin) N
N
Iph ≥ Imin AND
(Iph2 ≥ Imin)
Y
Y
U ph Uph1 - Uph2
Z= Z=
2 x Iph Iph1 - Iph2
N N
Z < Z Start Z < Z Start
Y Y
N all N all
ph-0 loops ph-ph loops
Y Y
Loop = Selectivity
phase selection conditions
N
Z < Z Start
log. signals =
temp. signals
END
HEST 955037 C
4-42
RE.216 1KHA000951-UEN ABB Switzerland Ltd
UPh − Ph UR − US
ZPh − Ph = e.g. ZRS =
IPh − Ph IR − IS
If the impedance (Z) calculated for the loop determined by the phase
selection logic lies within the underimpedance starting characteristic
(Zstart), the loop is used for measurement.
4-43
ABB Switzerland Ltd RE.216 1KHA000951-UEN
UT − UR
Z TR =
IT − IR
Comparison of the three starting impedances eliminates the healthy
loops (discrimination condition).
If just one of the loop impedances lies within the underimpedance
starting characteristic (Zstart), only the signals (R and S), or (S and T),
or (T and R) would be set to logical '1'.
If more than one of the loop impedances lie within the under-
impedance starting characteristic, the signals R and S and T are set to
logical '1'.
The kind of fault is thus determined, whereby the information is
needed for
• phase selection (determination of the loop to be measured)
• signalling the kind of fault (remote signalling relays, frontplate
LEDs etc.)
• enabling signals for single or three-phase tripping
• starting the timers for the measuring zones
4-44
RE.216 1KHA000951-UEN ABB Switzerland Ltd
XA
UNDERIMPEDANCE
CHARACTERISTIC
4-45
ABB Switzerland Ltd RE.216 1KHA000951-UEN
4-46
RE.216 1KHA000951-UEN ABB Switzerland Ltd
This is achieved by arranging for all the distance relays on the system
to measure the same E/F loop and this is the purpose of the phase
selection function.
The logic of the phase selection function provides a choice of the
following sequences:
4-47
ABB Switzerland Ltd RE.216 1KHA000951-UEN
period of the system frequency. The input variables are the sampled
analog and digitally filtered values converted to their vector
componentsof the phase currents IR, IS, IT, the residual current IE
(3I0), the residual current of any parallel circuit IEm (3I0m), the neutral
current IEm of any double-circuit line (3I0m) and the three phase
voltages UR, US and UT.
If the overcurrent starters are in operation and have picked up, the
phase selection function is performed and the loop to be measured
determined. Should this not be the case, the loop determined by the
underimpedance starters is measured.
The impedance of a phase-to-ground loop, e.g. R-E is calculated
using the equation:
UR
ZR = (compensated)
IR + k 0 × IE + k 0m × IEm
k0 zero-sequence compensation factor for Z0
k 0 = (Z0 − Z1 ) 3Z1
k0m zero-sequence compensation factor for the mutual impedance
Z0m of double-circuit line
k 0m = Z0m 3Z1
4-48
RE.216 1KHA000951-UEN ABB Switzerland Ltd
START
Overcurrent
starter
Overcurrent N
starter
Loop =
phase selection
Z calculation
(ph-0 compensated)
Z Start , Z 1-4 , (Z OR ),
Z Back , direction
N
Trip
Signalling,
fault location,
Z(loop)
N
t > 1 periode
Stoping
the timers
Y
Change to
processing
Change to periode II
processing
periode II
END
HEST 955035 FL
4-49
ABB Switzerland Ltd RE.216 1KHA000951-UEN
4-50
RE.216 1KHA000951-UEN ABB Switzerland Ltd
START
solidly grounded N
network
Phase selection
AND (I> starting
active)
Y
6 Z calculations N
(ph-0 compensated) ph-E
Y
Selectivity
conditions
ph-0 Z-calculation 3 ph-ph Z-calculation
Y
Fallback
conditions
Reset-
Signalling
signalling
N
Trip
Signalling
fault location
Z(loop)
Stoping the
timers
END
HEST 955036 C
4-51
ABB Switzerland Ltd RE.216 1KHA000951-UEN
4-52
RE.216 1KHA000951-UEN ABB Switzerland Ltd
The reference voltage Uref is derived from the phase voltages not
involved in the fault. In the case of a phase-to-phase loop, the
reference voltage also includes a proportion of the memory voltage
Umem. The duration of the memory voltage is limited to between 5 and
15 periods of the power system frequency, depending on the
discrepancy between the measured frequency and the rated power
system frequency, i.e. the memory voltage is used for 15 periods at
rated system frequency and for a proportionally reduced number of
periods as the frequency deviates from rated power system frequency.
As long as the reference voltage Uref is greater than 0.5% of rated
voltage, it is used to determine fault direction:
In this case, a 'forwards fault' satisfies the condition:
-90° < arg Zref < +90°
A 'reverse fault' satisfies the condition:
+90° < arg Zref < -90°
Zref is the impedance measured by the protection, which contains a
component of the source impedance ZS in addition to the line
impedance ZL. The operating characteristic has to be mathematically
transformed in order to make the influence of the source impedance
visible (see following Section 4.8.2.5).
If the reference voltage is less than 0.5% of rated voltage, direction is
not taken into account for the phase-to-ground loop and tripping is
blocked. In the case of the phase-to-phase loops, tripping is either
enabled or blocked, depending on the setting of the parameter
'MemDirMode'.
4-53
ABB Switzerland Ltd RE.216 1KHA000951-UEN
X
7° / 14°
27°
-X/8 R RR RRE
27° R
-RR/2
-RRE/2
7° / 14°
R RR RRE
-X/8
R
ZS'
-RR/2
-RRE/2
α
4-54
RE.216 1KHA000951-UEN ABB Switzerland Ltd
RRE/2
RR/2
R
ZS'
7° / 14°
-X
4-55
ABB Switzerland Ltd RE.216 1KHA000951-UEN
4.8.3. VT supervision
The purpose of the VT supervision function is to monitor the VT leads
with respect to asymmetrical short-circuits and open-circuits. An m.c.b.
can be included for three-phase VT short-circuits and arranged to
block the protection via a separate opto-coupler I/P.
The I/P variables monitored by the VT supervision function are the
three voltages UR, US, and UT and the three currents IR, IS, IT. The
zero-sequence (U0, I0) and negative-sequence (U2, I2) components
are calculated for both the three-phase voltage and three-phase
current systems.
3U0 = UR + US + UT
3
3U2 = UR + US . a2 + UT . a a = −0.5 + j = 1 / 120°
2
3I0 = IR + IS + IT
3I2 = IR + IS . a2 + IT . a
R R
S S
T T
4-56
RE.216 1KHA000951-UEN ABB Switzerland Ltd
4-57
ABB Switzerland Ltd RE.216 1KHA000951-UEN
P_U2_VTSUP
INP30C4
2
TONB
I 4
5 T TOFFB
Q I
14 T
Q BIT_VTSUP1_1
P_U0_VTSUP
INP30C2
6
TONB
I 8
5 T TOFFB
Q I
14 T
Q BIT_VTSUP1_2
1
P_DRST >=1
OUT3072
P_MANCL_DIST
INP3105
P_HFREC 2
INP3102 TOFF
P_EXTBL_DIST I
INP3100 12000 T 5
Q >=1
3
P_I2_VTSUP >=1 4
INP30C5 TOFFB
P_I0_VTSUP I
INP30C3 22 T 7
Q >=1
6
BIT_VTSUP1_1 & 8
o &
<
P_VTFAIL_IU2
9 10 OUT3076
BIT_VTSUP1_2 & >=1 11
o &
<
P_VTFAIL_IU0
12 OUT3075
>=1
BIT_VTSUP2_1
4-58
RE.216 1KHA000951-UEN ABB Switzerland Ltd
3
BIT_VTSUP2_1 &
P_VTSUP_BLKDEL o
INP3A15 1
TON
I 2
12000 T TOFF
Q I
1000 T
4 Q P_VTFAIL_DLY
P_I0_VTSUP >=1 6 7 OUT30B5
INP30C3 5 & >=1
P_I2_VTSUP o >=1
INP30C5
P_VTSUP_DEBDEL P_VTFAIL
INP3A16 OUT3091
4-59
ABB Switzerland Ltd RE.216 1KHA000951-UEN
VTSUP
SUPBL
Binary input data of the distance protection function and the Input/Output unit
SOTF
STUB
TRANSBL
UNBLOCK
PUTTREC
PUTSEND
POTTREC
POTSEND
BLOCREC
BLOSEND
HFSEND
TRIP
The O/Ps of the system logic are binary signals for controlling a fault
recorder, LED signals and auxiliary tripping and signalling relays.
4.8.5.2. Enabling and blocking logic (SUPBL)
The logic of the VT supervision function (segment VTSUP) has already
been described in the relevant section. The segment SUPBL
coordinates all the external blocking signals distance protection
[EXTBL_DIST] (opto-coupler I/Ps), the power swing blocking function
[PS_BLOCK] and the VT supervision function [VT_BLOCK] and blocks
all the distance protection functions [DISTBL] with the exception of the
back-up overcurrent function.
4-60
RE.216 1KHA000951-UEN ABB Switzerland Ltd
1
TOFFB
P_EXTBL_DIST I
INP3100 100 T 2
Q >=1
P_PSBLOCK
INP3056
P_VTFAIL P_DISTBL
OUT3091 3
TON
I
12000 T
Q P_DISTBL_DEL
4-61
ABB Switzerland Ltd RE.216 1KHA000951-UEN
2
P_UWEAK_R >=1
INP3034
P_UWEAK_S 3
INP3035 TON
P_UWEAK_T I
INP3036 1 5000 T
& Q BIT_UWEAK_5000
P_CREL_R o
INP3030
P_CREL_S o
INP3031 4
P_CREL_T o >=1
INP3032 5
P_DEADLINE1 & 6
INP3107 TON
P_SOTF_10S I
INP3A13 10000 T 9
Q >=1
7 8
& TONB
o I
200 T
Q 10
TOFF
P_MANCL_DIST I
INP3105 1000 T
Q P_START_SOTF
11 OUT30B7
&
P_SOTF_INIT P_SOTF
INP3053 OUT3073
4-62
RE.216 1KHA000951-UEN ABB Switzerland Ltd
1
P_ZE_FOR_DIST >=1
INP3111 2
P_AR_ZE & 4
OUT3094 RSFF
P_MEAS_OR2 S
INP3052
3
P_START_ALL 1 :B R
INP3050 Q BIT_TRIP_ZE
4-63
ABB Switzerland Ltd RE.216 1KHA000951-UEN
A1 B1
t=0 s:
Relays A1, B1 and B2
detect the fault
in the OR zone
and send a signal
to the opposite station.
Relay A2 detects
a backward fault.
A2 B2
A1 B1
t = sign.rec.: Relays A1, B1 and A2
receive a signal from
the opposite station.
A2 B2
A1 B1
t = CB open : CB A1 opens
before CB B1 opens.
Relay A2 detects the
fault in the OR zone,
but still receives
a signal from
the opposite station,
e.g. it trips and opens
A2 B2
the “healthy” line.
4-64
RE.216 1KHA000951-UEN ABB Switzerland Ltd
A1 B1 TBA T1
T2 100ms
A2 B2
A1 B1 TBA T1
T2 100ms
A2 B2
A1 B1 TBA T1
T2 100ms
A2 B2
4-65
ABB Switzerland Ltd RE.216 1KHA000951-UEN
1
P_TBA_BLOCK >=1 2
OUT3720 TONB
P_TBA_POTT I
OUT3707
PAR_B_T1_TRANSBL T 7
PAR3860 Q o &
3
>=1
P_MEAS_BWD
INP3067 4
TON
I
PAR_W_T2_TRANSBL T 5
PAR3880 Q >=1 6
TOFF
P_D I
OUT3071 100 T 8
Q o &
<
FL_TRANSBL BIT_TBE
INP3832
1
FL_UNBLOCK &
INP3833
P_HFREC o 2
INP3102 TONB
P_HFFAIL I
INP3103 20 T 4
Q &
3
TONB
I
100 T
Q o BIT_UNBL
4-66
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Delay (Def)
Meas Main
Delay (3)
Meas Main
Delay (2)
Com Rec
E A B C D
4-67
ABB Switzerland Ltd RE.216 1KHA000951-UEN
1
FL_PUTT_NONDIR &
INP3810 4
P_START_ALL >=1
INP3050 2
FL_PUTT_FWD &
INP3811
P_UZ_FORWARD
INP30C1
3
FL_PUTT_OR2 &
INP3812 7
P_MEAS_OR2 &
INP3052
5
P_TH2 >=1
INP3061
P_M_OWN o
OUT3084 6
BIT_UNBL >=1
P_HFREC
INP3102 8
& 11
FL_WEAK &
INP3813
9
TOFFB
I
100 T
Q o
10
TOFFB
I
20 T
Q
P_UWEAK_R
INP3034 o
BIT_UWEAK_5000 o P_UWEAKR_PUTT
OUT3700
12
&
o
P_UWEAK_S
INP3035 o
o P_UWEAKS_PUTT
OUT3701
13
&
o
P_UWEAK_T
INP3036 o
o P_UWEAKT_PUTT
14 OUT3702
>=1
P_UWEAK_PUTT
15 OUT3703
>=1
P_TRIP_PUTT
OUT3704
1
FL_PUTT_NONDIR >=1
INP3810
FL_PUTT_FWD
INP3811
FL_PUTT_OR2 P_PUTT_ON
INP3812 2 OUT3721
&
P_TH3 o
INP3062
P_MEAS_MAIN
INP3051
P_START_ALL P_SEND_PUTT
INP3050 OUT3722
4-68
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Delay (Def)
Meas Main
Delay (3)
Meas Main
Delay (2)
Com Rec
E A B C D
4-69
ABB Switzerland Ltd RE.216 1KHA000951-UEN
2
P_MEAS_OR2 &
INP3052 1
BIT_UNBL >=1
P_HFREC P_TBA_POTT
INP3102 8 OUT3707
&
BIT_TBE o
4
P_TH2 >=1
INP3061
P_M_OWN
OUT3084 3
FL_ONE_CHL &
INP3824
P_EF_BLKHF o
INP31A3
5
TOFFB
P_MEAS_BWD I
INP3067 200 T 9
Q o &
P_UWEAK_R
INP3034 6
TOFFB
I
20 T
Q
7
TOFFB
I
200 T
Q o
o
FL_WEAK
INP3813
BIT_UWEAK_5000 o P_UWEAKR_POTT
OUT3710
10
o &
P_UWEAK_S
INP3035
o
o
o P_UWEAKS_POTT
OUT3711
11
o &
P_UWEAK_T
INP3036
o
o
o P_UWEAKT_POTT
12 OUT3712
>=1
P_UWEAK_POTT
13 OUT3713
>=1
P_TRIP_POTT
OUT3714
4-70
RE.216 1KHA000951-UEN ABB Switzerland Ltd
1
FL_POTT 1 :B P_POTT_ON
INP3820 2 OUT3705
&
P_MEAS_OR2
INP3052
BIT_TBE o
11
P_TH2 o >=1
INP3061
10
3 o &
& o
FL_ECHO
INP3821 4
>=1
P_MEAS_BWD 5
INP3067 TOFFB
P_M_OWN I
OUT3084 100 T
Q o
P_HFREC
INP3102 6
&
P_EF_BLKHF
INP31A3
FL_ONE_CHL o
INP3824 7
& 8
TONB
I
150 T 9
Q o &
P_SEND_POTT
OUT3706
4-71
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Delay (Def)
Meas Main
Delay (3)
Meas Main
Delay (2)
Com Rec
E A B C D
1
FL_BLOCK_OR &
INP3830
P_HFFAIL o 2
INP3103 TONB
P_MEAS_OR2 I
INP3052
PAR_B_T1_BLOCK T 4
PAR3840 Q &
P_HFREC o
INP3102 3
P_TH2 >=1
INP3061
P_M_OWN o
OUT3084
BIT_TBE o P_TRIP_BLOCK
OUT3717
5
o &
P_TBA_BLOCK
OUT3720
4-72
RE.216 1KHA000951-UEN ABB Switzerland Ltd
1
FL_BLOCK_OR &
INP3830
P_HFFAIL o P_BLOCK_ON
INP3103 3 OUT3715
&
P_TH2 o
INP3061
P_MEAS_OR2 o
INP3052 2
TOFFB
P_MEAS_BWD I
INP3067 100 T 5
Q >=1
4
&
BIT_TBE P_SEND_BLOCK
OUT3716
1
P_PUTT_ON >=1
OUT3721
P_POTT_ON
OUT3705
P_BLOCK_ON BIT_HF_ON
OUT3715 3
2 &
P_SEND_PUTT >=1
OUT3722
P_SEND_POTT
OUT3706
P_SEND_BLOCK
OUT3716
P_DISTBL o P_HFSEND
OUT3077 4 OUT3081
P_UWEAK_R >=1 8
INP3034 &
P_UWEAK_S
INP3035 6
P_UWEAK_T &
INP3036 5
TON
I
2000 T 7
Q o >=1
P_START_ALL P_HFBOOST
INP3050 OUT3080
4-73
ABB Switzerland Ltd RE.216 1KHA000951-UEN
4-74
RE.216 1KHA000951-UEN ABB Switzerland Ltd
1
P_START_R >=1
INP3000
P_UWEAKR_PUTT
OUT3700
P_UWEAKR_POTT BIT_R
OUT3710
2
P_START_S >=1
INP3001
P_UWEAKS_PUTT
OUT3701
P_UWEAKS_POTT BIT_S
OUT3711 4
3 &
P_START_T >=1
INP3002
P_UWEAKT_PUTT
OUT3702
P_UWEAKT_POTT BIT_T
OUT3712 5 7
& >=1
6
&
BIT_TRIP1_345
8
>=1
P_OC_RST P_RST
INP3054 9 OUT3070
& 15
P_DRST &
OUT3072 10
TOFF
I
PAR_W_T1_TRIP T 11
PAR38C0 Q & 12
TONB
o I
4 T 14
Q >=1
13
&
BIT_TRIP1_12
3
BIT_TRIP1_345 >=1
P_THREE_PH_TRIP
INP3A11
P_AR_1POL_INP o
INP3112 1
P_TH3 &
INP3062 2
P_TH3P >=1
INP3A10
P_OC_D
INP3055
P_SOTF
OUT3073
P_TRIP_STUB
OUT30B6
BIT_TRIP1_12 BIT_THREE_P
4
P_UWEAK_PUTT >=1
OUT3703
P_UWEAK_POTT P_WI
OUT3713 OUT30B4
4-75
ABB Switzerland Ltd RE.216 1KHA000951-UEN
6
P_SOTF >=1
OUT3073 2
P_ZE_FOR_DIST >=1
INP3111 1
P_AR_ZE &
OUT3094 3
P_ZE_EN & 5
INP3814 RSFF
P_MEAS_OR2 S
INP3052
4
P_START_ALL 1 :B R
INP3050 Q
P_TRIP_STUB
OUT30B6
P_OC_D 7
INP3055 TOFFB
P_MEAS_MAIN I
INP3051 8 10 100 T
P_TRIP_PUTT >=1 >=1 Q P_M_OWN
OUT3704 OUT3084
P_TRIP_POTT
OUT3714 9
P_TRIP_BLOCK &
OUT3717 14
P_HF_OFF o &
INP30C7
11
BIT_THREE_P >=1
18
BIT_R >=1
12 15
>=1 &
BIT_S
13 16
>=1 &
BIT_T P_D
OUT3071
17
o & 19
o
P_DISTBL I01 O01 P_DRST
OUT3077 I02 OUT3072
I03 O02 P_D3PH
I04 OUT3085
I05 O03 P_D1PH
P_EF_ENABLE I06 OUT3083
INP3DC5 O04 P_DH
P_EF_TRIP_OUT I07 OUT3087
INP31A1 O05 P_DR
OUT30B0
O06 P_DS
OUT30B1
O07 P_DT
OUT30B2
1
P_DR >=1
OUT30B0
P_DS
OUT30B1
P_DT P_DRST
OUT30B2 2 OUT3072
&
P_D3PH
OUT3085
3
&
o 6
o >=1
4
o &
5
o & 7
o TONB
I
8 T
Q P_D1PH
OUT3083
8
&
BIT_TRIP3_1 P_DH
OUT3087
4-76
RE.216 1KHA000951-UEN ABB Switzerland Ltd
E1 U E2
U×cosϕ
U )U×cosϕ
ϕ I
E1 E2
4-77
ABB Switzerland Ltd RE.216 1KHA000951-UEN
4-78
RE.216 1KHA000951-UEN ABB Switzerland Ltd
FUPLA name HMI name Signal description INT PAR CPU OPT OUT
AR_ZE ZExtensionAR Sig. from recl. function to switch distance function to overreach x
D Trip RST General trip signal before blocking gate from R, S or T phases x
DEADLINE1 Dead line Line isolator open; used when VTs on the busbars. x
EXTBL_PSB Ext blk PSB Power swing blocking blocked by external signal x
HFBOOST Com boost Signal to boost PLC power ready for transmission x
HFREC_EF (unused) x
ISOL_OPEN Isol open Line isolator open (only in conjunction with short-zone logic) x
MEAS_MAIN Meas main Fault in zone 1, 2, 3, 4 or <Z (dir./non-dir.) acc. to sig. delay x x
4-79
ABB Switzerland Ltd RE.216 1KHA000951-UEN
FUPLA name HMI name Signal description INT PAR CPU OPT OUT
4-80
RE.216 1KHA000951-UEN ABB Switzerland Ltd
FUPLA name HMI name Signal description INT PAR CPU OPT OUT
4-81
ABB Switzerland Ltd RE.216 1KHA000951-UEN
FUPLA name HMI name Signal description INT PAR CPU OPT OUT
4-82
RE.216 1KHA000951-UEN ABB Switzerland Ltd
4.9. Auto-reclosure
4.9.1. Logic segments
The auto-reclosure logic comprises the several FUPLA segments, the
block diagrams of which are shown below.
The relationship between the inputs and outputs and the designations
used for the HMI is given in Section 4.9.2.
1
P_MD1_EXT &
P_MD1_EXT_1P_1P
P_MD1_EXT_1P_3P o
P_MD1_EXT_1P3P_3P o
2
P_MD1_EX_1P3P_1P3P o >=1
P_MD1_1P_1PAR BIT_MD_1P_1P
3
&
o 4
o >=1
P_MD1_1P_3PAR BIT_MD_1P_3P
5
&
6
o >=1
P_MD1_1P3P_3PAR BIT_MD_1P3P_3P
7
& 8
>=1
P_MD1_1P3P_1P3P BIT_MD_1P3P_1P3P
4-83
ABB Switzerland Ltd RE.216 1KHA000951-UEN
1
P_AR_START >=1
P_AR_START_2
P_AR_START_3 BIT_AR_START
2
P_TRIP &
5
P_TRIP_3P o >=1
3
P_TRIP_2 &
P_TRIP_3P_2 o
4
P_TRIP_3 &
9
P_TRIP_3P_3 o >=1
6
>=1
11
P_AR_RUN o &
10
BIT_MD_1P_3P >=1
BIT_MD_1P_1P
13
>=1
12
&
BIT_DISCRT
P_1AR_1P BIT_AR1_DEFTR
8 15
o & >=1
7
>=1
BIT_MD_1P3P_3P
14
NPLS
In
Out
17
RSFF
P_AR_BLCKD S
18 20
>=1 & 16
BIT_MD_1P3P_1P3P NPLS
In
19 21 23 Out R
>=1 >=1 RSFF Q P_AR_3POL_OUT
o S
22
>=1
P_CL_CB
P_CL_CB2 R
Q BIT_AR1_3P_EN
25 27
o & o &
24 26
>=1 RSFF
S
R
Q BIT_AR1_1P_EN
28 29 30
NPLS & &
In
Out
BIT_AR1 o
P_MAST_DEL o BIT_AR_TRIP
31
&
32
o PPLS
BIT_DEADT o In
Out BIT_ST_DEAD_T
33
o & 34
TON
o I
TMSEC_OPERT Tim
Q BIT_BLK_OPT_FIN
4-84
RE.216 1KHA000951-UEN ABB Switzerland Ltd
1
TON
P_CB_OP I
100 Tim 3
Q >=1
2
TOFF
P_RDY_OCO I
100 Tim 4
Q o &
10
P_AR_RUN o &
5
TON
P_CB2_OP I
100 Tim 7
Q >=1
6
TOFF
P_RDY_OCO2 I
100 Tim 9
Q o & 16
o >=1
8
P_CL_CB >=1 11
TOFF
P_CL_CB2 I
50 Tim 12
Q o &
P_MANCL_AR
13
BIT_AR_START o &
o
BIT_AR_TRIP
14
o &
P_COND_BLCK
P_EXTBL_AR
P_TST_AROFF
BIT_BLK_OPT_FIN
15
P_MD1_EXT &
P_MD1_EXT_1P_1P o
P_MD1_EXT_1P_3P o
P_MD1_EXT_1P3P_3P o 17
TOFF
P_MD1_EX_1P3P_1P3P o I
TMSEC_BLCK_T Tim 18
Q >=1
BIT_INHIB_OUT
P_INH_IN P_AR_BLCKD
19
o & 20
o >=1
P_AR_RDY
21
P_AR1_ZE &
25
BIT_AR1 >=1
22
P_AR2_ZE &
P_2AR
23
P_AR3_ZE &
P_3AR
24
P_AR4_ZE &
26
P_4AR &
28
>=1
27
o &
o
P_AR_ZEMD P_AR_ZEOUT
29 30
& RSFF
S
R
Q BIT_CB1_DISABLED
31 32
& RSFF
S
R
Q BIT_CB2_DISABLED
4-85
ABB Switzerland Ltd RE.216 1KHA000951-UEN
1 2
BIT_ST_DEAD_T & COUNTX
o C Q0 BIT_ARINI
R
Q1 BIT_AR1
Q2 P_2AR
Q3 P_3AR
Q4 P_4AR
Q5 BIT_AR_FIN
Q6 P_AR_RUN
4
&
3
P_AR_MD2 >=1
P_AR_MD3
8
P_AR_MD4 o >=1
5
&
6
&
7
&
BIT_LAST_AR
<
9
P_AR_BLCKD ASSB
<
10
&
BIT_AR1_1P_EN P_1AR_1P
11
TON
I
TMSEC_DEADT1_1P Tim 13
Q o &
17
>=1
12
RSFF
S
R 14
Q o &
16
BIT_AR1_3P_EN &
15
TON
I
TMSEC_DEADT1_3P Tim 20
Q o >=1
18
TOFF
I
TMSEC_DEADT1_EXT Tim 19
Q &
27
P_EXT_T1_EN >=1
21
TON
I
TMSEC_DEADT2 Tim 22
Q o &
23
TON
I
TMSEC_DEADT3 Tim 24
Q o &
25
TON
I
TMSEC_DEADT4 Tim 26
Q o &
28
TON BIT_DEADT
I
TMSEC_DISCRT_1P Tim 31
Q o &
36
>=1
29
RSFF
S
R 30
Q o & 32
PPLS
In 34
Out >=1
33 35
o & TOFF
I
TMSEC_DISCRT_3P Tim
37 Q BIT_DISCRT
o &
o P_1AR_3P
4-86
RE.216 1KHA000951-UEN ABB Switzerland Ltd
1
P_MAST_DEL &
2
P_AR_RUN >=1
BIT_CB1_WAIT
3
BIT_DEADT & 4
TOFF
BIT_CB1_DISABLED o I
TMSEC_TIME_OUT Tim
Q BIT_T_OUT1
5 6
& PPLS
o In 7
Out &
BIT_AR_TRIP BIT_TOUT_TRIP1
8 13
P_MDSCBYPS_1P & & 17
o &
BIT_AR1_1P_EN
10
BIT_AR1 >=1
9
&
P_MDSCBYPS_1P3P
12
P_EXTSC_BYP >=1
11
P_SYN_CK &
P_CO_RDY 15
RSFF
P_DEADL S
14
>=1 16
P_AR_BLCKD R TON
Q I
TMSEC_CL_T Tim
Q o
P_CL_CB
18
PPLS
1 In
Out BIT_INIT_BLOCK
20
o &
o
o
19
NPLS
In
Out
o BIT_CB1_DEFTRIP
4-87
ABB Switzerland Ltd RE.216 1KHA000951-UEN
1
P_MAST_DEL &
2
P_AR_RUN >=1
BIT_CB2_WAIT
3
BIT_DEADT & 4
TOFF
BIT_CB2_DISABLED o I
TMSEC_TIME_OUT Tim
Q BIT_T_OUT2
5 6
& PPLS
o In 7
Out &
BIT_AR_TRIP BIT_TOUT_TRIP2
8 13
P_MDSCBYPS_1P & & 17
o &
BIT_AR1_1P_EN
10
BIT_AR1 >=1
9
&
P_MDSCBYPS_1P3P
12
P_EXTSC_BYP >=1
11
P_SYN_CK2 &
P_CO_RDY2 15
RSFF
P_DEADL2 S
14
>=1 16
P_AR_BLCKD R TON
Q I
TMSEC_CL_T Tim
Q o
P_CL_CB2
19
o &
o
18
NPLS
In
Out
o
BIT_INIT_BLOCK o BIT_CB2_DEFTRIP
4-88
RE.216 1KHA000951-UEN ABB Switzerland Ltd
1
TOFF
P_CL_CB I
300 Tim 2
Q & 5
RSFF
BIT_AR_TRIP S
3
BIT_DEADT >=1
P_AR_BLCKD R
Q BIT_CL_AND_TR1
4 7
NPLS o &
In 6
Out &
P_AR_RUN
P_CB_OP
o BIT_CL1_UNS
8
o & 9
RSFF
o S
R
10 Q BIT_CL1_SUC
RSFF
S 11
R TON
Q I
40 Tim 12
Q &
P_MAST_MDE P_DEL_FLW
1
TOFF
P_CL_CB2 I
300 Tim 2
Q & 5
RSFF
BIT_AR_TRIP S
3
BIT_DEADT >=1
P_AR_BLCKD R
Q BIT_CL_AND_TR2
4 7
NPLS o &
In 6
Out &
P_AR_RUN
P_CB2_OP
o BIT_CL2_UNS
8
o & 9
RSFF
o S
R
Q BIT_CL2_SUC
4-89
ABB Switzerland Ltd RE.216 1KHA000951-UEN
16
P_MAST_MDE &
13
BIT_TOUT_TRIP1 >=1
BIT_TOUT_TRIP2
1
BIT_CB1_DEFTRIP >=1 2
RSFF
BIT_CL1_UNS S
P_AR_BLCKD R 7
Q &
3
BIT_CB2_DEFTRIP >=1 4
RSFF
BIT_CL2_UNS S
R 5
Q >=1
BIT_CB2_DISABLED
BIT_CL2_SUC
o
6
>=1
BIT_CB1_DISABLED
8
BIT_CL1_SUC &
o
9
BIT_AR_TRIP &
BIT_DISCRT o
BIT_DEADT
BIT_AR1_DEFTR
10
BIT_CL_AND_TR1 >=1
11
BIT_CL_AND_TR2 &
BIT_LAST_AR
12 15
& TMOC
I
500 Tim
Q P_BLCK_TO_FLW
17
>=1
P_MAST_NOSUC
14 18
& TMOC
I
22 500 Tim
19 o & 23 Q P_DEF_TRP
& 21 >=1
>=1
20 24
& TOFF
I
TMSEC_INHIB_T Tim
Q BIT_INHIB_OUT
25
&
P_INH_OUT
26
o &
P_CB2_PRIORITY
BIT_T_OUT2
o BIT_CB1_WAIT
27
o &
o
BIT_T_OUT1
o BIT_CB2_WAIT
4-90
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Timer settings
Binary inputs
4-91
ABB Switzerland Ltd RE.216 1KHA000951-UEN
4-92
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Signal outputs
4-93
ABB Switzerland Ltd RE.216 1KHA000951-UEN
4-94
RE.216 1KHA000951-UEN ABB Switzerland Ltd
The block diagram below shows the basic functions, which are
explained in the following sections.
I Current
detectors
Redundant Red Trip Lx
Start Lx logic
Trip t1 Lx
Retrip
logic Retrip t1
Remote Trip
Remote logic
Backup Trip t2
Back up logic
CB On Uncon Trip t2
Unconditional
Start Ext logic Uncon Trip t1
Trip t1
≥1
Trip t2
≥1
4-95
ABB Switzerland Ltd RE.216 1KHA000951-UEN
4.10.4. Retrip
The unit protection issues a trip command and simultaneously starts
individual phases or all three phases of the breaker fail function.
A second attempt is made to trip the corresponding phase or phases
after the first time step (t1), providing the current detectors have not
reset.
The ‘Retrip’ logic can be disabled if not required.
Separate timers for each phase ensure correct operation during
evolving faults.
4.10.5. Backup trip
A second time step (t2) follows the first time step (t1) and initiates
backup tripping which is always of all three phases. If the first time
step is disabled, the second time step is started immediately, providing
the current detectors have activated by the starting signal from the
protection.
The backup trip logic trips all surrounding breakers feeding the fault.
4.10.6. Remote trip
The ‘Remote Trip’ logic trips the breaker at the remote end of the line.
Remote tripping can take place concurrently with the ‘Retrip’ or
‘Backup’ functions or not at all as desired.
In contrast to the other tripping commands which remain activate for a
given period after the initiating signal has reset, the remote tripping
signal is an impulse with a width which is adjustable irrespective of
when the starting signal from the protection resets.
4.10.7. Unconditional trip
This feature was introduced to respond to low-level faults with currents
too low for the current detectors to pick up or do not initially cause any
fault current at all such as mechanical protection devices like
Buchholz, etc.
The start input bypasses the current detectors and activates the time
steps if the breaker is in the closed position. In all other respects, this
logic is similar to the ‘Retrip’ and ‘Backup’ logics.
4.10.8. End Fault trip
While in the case of a fault between a circuit-breaker and a single set
of CTs, the circuit-breaker may not fail, the affect on the power system
and the action that has to be taken are the same as if the circuit-
breaker had failed.
Where there is only a single set of CTs on the busbar side of a circuit-
breaker, the zones of protection do not overlap and a fault between the
circuit-breaker and the CTs is seen as a line fault, although it belongs
to the busbar zone and persists after the circuit-breaker has been
4-96
RE.216 1KHA000951-UEN ABB Switzerland Ltd
tripped. The breaker failure protection’s ‘End Fault Trip’ logic ultimately
clears such faults at the end of the second time step.
This logic is enabled if the breaker is open and the current detectors
are still picked up, indicating a fault between the breaker and the CTs.
The speed of tripping is determined by the time delay setting.
Depending on whether the single set of CTs is on the line side or bus
side of the circuit-breaker, either the section of busbar or the circuit-
breaker at the remote end of the line is tripped.
4.10.9. External trip
This function has been included to make the breaker fail protection
more user-friendly and reduce the amount of systems engineering
required. It generates an instantaneous trip when either of the
following inputs is activated:
• The input connected to the second time steps of other breaker fail
protection devices in the station.
• The input connected to the end fault outputs of other breaker fail
protection devices in the station.
4-97
RE.216 1KHA000951-UEN ABB Switzerland Ltd
August 05
5. OPERATION (CAP2/316)
5.1. Summary............................................................................................5-4
5-1
ABB Switzerland Ltd RE.216 1KHA000951-UEN
5-2
RE.216 1KHA000951-UEN ABB Switzerland Ltd
5-3
ABB Switzerland Ltd RE.216 1KHA000951-UEN
5. OPERATION (CAP2/316)
5.1. Summary
The HMI program CAP2/316 has been designed to be largely self-
sufficient and requires a minimum of reference to the manual. This
approach achieves a number of advantages:
• The same program can be utilized for both the RE.216 and the
RE.316*4 devices.
• Functions can be selected from extremely user-friendly menus with
full screen displays and windows.
• “Pop-up” prompts wherever practical to guide the user and avoid
errors, see Section 6.4.
• Provision for creating, editing and checking parameter sets off-line,
i.e. without being connected to the protection device.
• Provision for reading or writing parameter sets from and to files.
• Self-explanatory texts using a minimum of mnemonic codes.
• Provision for the user to enter customized descriptions for
functions, inputs and outputs.
• The possibility to view and analyze event lists offline or online.
• Copy – Paste Windows functionality for configuration of comments.
• Call up of HELP with the “F1” key, for clarifications or aid to
problems - from help files stored in PDF format.
5-4
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Start menu
Install the complete software packet on one disk.
Stop all other application programs and insert the installation CD into
the CD-ROM drive. The following start-up menu will pop up.
5-5
ABB Switzerland Ltd RE.216 1KHA000951-UEN
5-6
RE.216 1KHA000951-UEN ABB Switzerland Ltd
5-7
ABB Switzerland Ltd RE.216 1KHA000951-UEN
5-8
RE.216 1KHA000951-UEN ABB Switzerland Ltd
5-9
ABB Switzerland Ltd RE.216 1KHA000951-UEN
5-10
RE.216 1KHA000951-UEN ABB Switzerland Ltd
5-11
ABB Switzerland Ltd RE.216 1KHA000951-UEN
5.3. Operation
5.3.1. General
The HMI can be in one of four modes:
• Menu: User can select a sub-menu item.
• Operation: User can enter data, e.g. parameter settings,
confirmation of prompts, password etc.
• Output: Display of measured variables, event lists etc.
• Wait: This can occur in any one of the above states, while
a function is being executed (menu is blocked, other
programs can still execute, Multitasking feature of
Windows).
If a selection is made in the main menu or in the icon bar, a new
Window is opened. In this Window it is possible to select further sub-
menus. In order that a modification becomes effective, click on the
'OK' or 'Save to file' button. To discard changes click on the 'Cancel'
button.
5-12
RE.216 1KHA000951-UEN ABB Switzerland Ltd
1) 2) 3) 4) 5) 6) 7) 8) 9)
Fig. 5.9 Status Display
1) Help:
Information regarding the active menu item.
2) Software version of the CAP2/316
It is mandatory that this value corresponds to the version number
(x) in front of the dot and with the sub-version number (y) after the
dot. See item 3. below in the status line. (Example: x.yz; the
revision index is represented as a character (z)).
3) Software version of the device (CPU Firmware):
Provides information of the firmware-version of the device. To
guarantee an accurate communication between the device and the
PC, the firmware number of the device must correspond to the SW
version number of the CAP2/316 as described under point 2).
4) Provides information of the utilized communication protocol to the
substation automation system (SCS) resp. which type of firmware
is stored in the device:
'SPA', 'IEC870-5-103', 'LON' or 'MVB'.
5) Displays whether the configuration program is in the:
'Online', 'Offline', 'Demo' or 'Remote-HMI' mode of operation.
6) Displays the active parameter set:
'Parset (1…4) '.
7) Displays the configured communication port 'COM (1…4) '.
8) Displays the active interface to the device:
The data displays which port is connected to the PC:
'TC57' = Communication is via the Frontend
'SPA' = Communication is via the interface at the rear.
9) Displays the relay type:
’REC216’, ’REG216’, 'REC316*4', 'REG316*4', 'REL316*4', or
'RET316*4'.
5-13
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Main menu
Icon header
Main menu:
File: • Open and save the settings,
open the event list
• Import MBA and RIO parameters,
Export from SIGTool and RIO parameters
• Printer configuration
• End the configuration (HMI) program
5-14
RE.216 1KHA000951-UEN ABB Switzerland Ltd
The above is valid for the 'Online' mode. In the 'Offline' mode it is
possible to use the following menu items i.e. 'File', 'View',
'Configuration', 'Help' and some of the sub-menus in 'Options' and
'Monitor'.
Icon list
The icon bar is activated in the 'View' menu by selection 'Toolbar'. This
facilitates a fast selection of the configuration menus.
Create a new set file. If the currently open set file is not
saved, it will be lost!.
Save the current set file. If the set file in the PC memory has
to be saved under a different file name, use the 'Save as'
sub-menu in the menu 'File'.
5-15
ABB Switzerland Ltd RE.216 1KHA000951-UEN
5-16
RE.216 1KHA000951-UEN ABB Switzerland Ltd
5-17
ABB Switzerland Ltd RE.216 1KHA000951-UEN
The SW Vers should always be set to the value of 999 .i.e. all
protection functions from the library are available for configuration.
A few other parameters and comments have to be configured as
described in the Section 5.4.2.1 upto 5.4.2.7.
5.4.2.1. Binary input card 216DB61
Each binary input has a LED indication on the front of the card.
Depending on the system configuration, not all inputs have galvanic or
opto-coupler isolation.
On clicking on the 'Edit' button the following 216DB61 configuration
screen is displayed.
5-18
RE.216 1KHA000951-UEN ABB Switzerland Ltd
The comments for the binary inputs can be configured in this window,
to be displayed in the event list. A check in the box next to the
comments suppresses display in the event list.
5-19
ABB Switzerland Ltd RE.216 1KHA000951-UEN
NOTE: With the jumper BR1 on the card 216BD61 the function
"ENABLE und BLOCK CH OUT", i.e. release and blocking of the
tripping outputs CHO01... CHO08 should be in operation or not can
be selected. The release and blocking is valid only for the 216DB61
card (see Section 2.4.5.).
In most cases the blocking functionality is not utilized, i.e. the jumper
is plugged into position X4 and in the 'Block Enable' folder 'X4
inactive' should be selected. The binary inputs 13,14, 15 and 16 are
used as normal inputs.
5-20
RE.216 1KHA000951-UEN ABB Switzerland Ltd
5-21
ABB Switzerland Ltd RE.216 1KHA000951-UEN
The comments for the binary inputs can be configured in this window,
to be displayed in the event list. A check in the box next to the
comments suppresses display in the event list.
5-22
RE.216 1KHA000951-UEN ABB Switzerland Ltd
5-23
ABB Switzerland Ltd RE.216 1KHA000951-UEN
If a contact bounces the filter time prevents repeated on and off inputs
of the contact.
5-24
RE.216 1KHA000951-UEN ABB Switzerland Ltd
5-25
ABB Switzerland Ltd RE.216 1KHA000951-UEN
NOTE: In case in the system there are no 216AB61 cards then the
first channel is automatically reserved for the signal 'Relay Ready' and
the Channel 2 for the signal 'No Error' (see Section 2.4.6.).
5-26
RE.216 1KHA000951-UEN ABB Switzerland Ltd
5-27
ABB Switzerland Ltd RE.216 1KHA000951-UEN
• Prim/Sec ratio:
This value is required for the IEC60870-5-103-protocol, for the
display of the measurand values in the sub-menu 'Monitor' of the
'Main menu', and for the signal display in the evaluation program
'E_Wineve'. For three phase A/D converters this value is valid for
all three phases simultaneously.
• Sec.nom.val:
Configure the nominal rated value of the current and voltage
transformer. For three phase A/D converters this value is valid for
all three phases simultaneously.
• Ref. value:
With the reference value the relay nominal rated value can be
adapted to the primary equipment nominal value. For three phase
A / D converters this value is valid for all three phases
simultaneously.
• Comments:
Comments up to 25 characters can be configured for each
channel.
5-28
RE.216 1KHA000951-UEN ABB Switzerland Ltd
5-29
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Sink Nr. 2
NOTE: Use the trip matrix if more than two sinks are required.
Normally the trip matrix is utilized for trip signals. (see
Section 5.4.7.5).
5-30
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Comment text if defined for the inputs and outputs are displayed. A
check in the box enables the selection of the text. Select the second
slot to configure the signaling relays in this slot.
An allocated channel is shown as a grey block, and cannot be reused.
If the allocation is made for an output and confirmed with 'OK', then in
the box next to the 'Edit' button the following text will be displayed:
Sxyy: S = Signal relay
xx = Slot number (4 ... 21)
yy = Channel number (01 ... 32)
Example: S1203, (signal relay on 216AB61 in slot 12, channel 03)
5-31
ABB Switzerland Ltd RE.216 1KHA000951-UEN
NOTE: The first and second channel of the first 216AB61 in the
system cannot be selected. Both these channels are automatically
reserved for the system messages 'Relay Ready' (Channel 1) and the
signal 'No Error' (Channel 2)
If a channel is already utilized, it is displayed in grey, and cannot be
selected
If the event recording is activated with 'On' and 'OK', then an 'ER' is
displayed in the field next to the 'Edit' button.
5-32
RE.216 1KHA000951-UEN ABB Switzerland Ltd
5-33
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Once the allocation is confirmed with 'OK', then the field next to the
'Edit' button will have the following text:
Cxyy: C = Trip relay
x = Slot number (4 ... 21)
yy = Channel number (01 ... 08)
Example: C1401, (trip channel 216DB61 in Slot 14, Channel 01)
NOTE: Trip Relays can also be utilized for Indication. In general the
Trip Relay is used for the Trip Matrix to activate the protection function
(see Fig. 5.44). It is possible to use an OR function for the trip and the
trip relay indication. Thereby the trip relay can be activated by an
indication output or from the tripping matrix.
Select the group from which the signal is to sent to the SCS (Station
Control System = Substation automation system). The SCS groups
1c … 24c are used for transmitting short signals to the MVB
interbaybus (signal capturing).
5-34
RE.216 1KHA000951-UEN ABB Switzerland Ltd
5-35
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Once the allocation is confirmed with 'OK', then the field next to the
'Edit' button will have the following text:
RBOxxyy: RBO = RBO signal
xx = module address (1 ... 80)
yy = output relay within a module (01 ... 16)
Example:
RBO102, (output module with the address 1, output relay 02)
5-36
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Each binary input can be allocated to many sinks. However one sink
can have only one source.
Typical sources are:
• Signal from SCS (Substation Automation System), RBI (Remote
Binary Input), ITL (Interlocking data)
• Output from a system parameter e.g. 'General Trip',
'General Start' etc. (similar to a protection function)
• Output of a protection function (e.g. 'Start Overcurrent')
• Predefined values (Always ON, Always OFF)
• Binary inputs acquired via Opto-coupler inputs
Sink Nr. 2
Sink Nr. xx
5-37
ABB Switzerland Ltd RE.216 1KHA000951-UEN
NOTE: The default value for all inputs is 'Always OFF'. If a particular
input is no longer used it should be set to 'Always OFF'.
5-38
RE.216 1KHA000951-UEN ABB Switzerland Ltd
5-39
ABB Switzerland Ltd RE.216 1KHA000951-UEN
5-40
RE.216 1KHA000951-UEN ABB Switzerland Ltd
5-41
ABB Switzerland Ltd RE.216 1KHA000951-UEN
5-42
RE.216 1KHA000951-UEN ABB Switzerland Ltd
5-43
ABB Switzerland Ltd RE.216 1KHA000951-UEN
4)
6)
7)
9) 2) 3) 1) 8)
Function library
All the functions available in the RE.216 is displayed in the function
library.
If some functions are not displayed, then check if the Software key as
described in Section 5.4.2, is set to 999 in the Relay Configuration.
Legend
1) Configured functions with the ANSI code and the corresponding
symbol.
2) A green button next to the right of the ANSI code indicates that the
minimal requirements of the function have been configured. If the
button is red, then the function is not correctly configured and
therefore cannot be activated.
5-44
RE.216 1KHA000951-UEN ABB Switzerland Ltd
3) The number between the button and the function is the function
number. This is utilized for the allocation of the output from the
function (see Section 5.4.6.3.).
4) For each of the functions a short description of the function is
provided. The ANSI code of the function is provided before the
description. The ANSI code represents the exact meaning and
functionality of the protection function, and overrides the text
description / clarification.
5) This provides an overview of the function configured for the various
parameter sets, which can be defined by item 6) below.
6) Configuring the function in different parameter sets (see
Section 5.9.2.1.).
7) Displays from which function this particular function has been
copied. The A/D converter, the trip signal card and the signal
outputs cannot be changed (see Section 5.9.2.2.).
8) The bar display and the numeric value provide information of the
capacity utilization of the CPU by the currently configured
protection functions in the device.
In systems with two CPU’s the load of each CPU is displayed
separately.
9) Protection functions in the device can be added from the function
library with the 'drag and drop' method (see Section 5.4.7.2.).
5-45
ABB Switzerland Ltd RE.216 1KHA000951-UEN
5-46
RE.216 1KHA000951-UEN ABB Switzerland Ltd
7)
1)
2)
3)
4)
5)
6)
5-47
ABB Switzerland Ltd RE.216 1KHA000951-UEN
NOTE : ABB recommends that the trip channels are configured via
the trip channel matrix. This facilitates the simultaneous activation of
the trip channel from different protection functions.
5-48
RE.216 1KHA000951-UEN ABB Switzerland Ltd
5-49
ABB Switzerland Ltd RE.216 1KHA000951-UEN
5-50
RE.216 1KHA000951-UEN ABB Switzerland Ltd
5-51
ABB Switzerland Ltd RE.216 1KHA000951-UEN
5-52
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Online
In the Online state of the CAP2/316 the configuration can be uploaded
from the device into the working memory of the CAP2/316 by selecting
'Communication' and then the sub-menu 'Setfile Upload from RE..16'.
Offline
If the PC is connected to the device as described above and if the
CAP2/316 is in the off-line mode, then establish communication with
the device by selecting 'Communication' in the main menu and then
the sub-menu 'Connect'. Now the active configuration in the device will
be automatically uploaded to the CAP2/316.
5-53
ABB Switzerland Ltd RE.216 1KHA000951-UEN
long as the device identification and the time stamp in the file is
identical to that stored in the device.
5-54
RE.216 1KHA000951-UEN ABB Switzerland Ltd
If the 'Confirm Parameters' is set to 'On' then when storing the settings
to a file or the device a list of differences between the last saved
settings and the latest changes are displayed:
5-55
ABB Switzerland Ltd RE.216 1KHA000951-UEN
NOTE: If in Fig. 5.56 the file is stored always with the same
filename, then all the changes made are stored sequentially in a list
with date and time data. Thereby one can track all the changes that
have been made.
The file saved as shown in Fig. 5.56 can be opened with the Word
program:
NOTE: If the parameter are confirmed while saving, then the when
downloading to the device the differences are no longer displayed.
5-56
RE.216 1KHA000951-UEN ABB Switzerland Ltd
5-57
ABB Switzerland Ltd RE.216 1KHA000951-UEN
In this display mode the PC acquires the latest events from the device.
All existent events are displayed with absolute time, and in the
sequence in which they are created. The events are displayed once,
i.e. when the display is closed and reopened, the display is empty and
remains empty until new events are created.
The event list can be printed on the installed printer, by clicking on
'Print'. If the events have to saved as an ASCII file (*.evt), then click on
the 'Save as ASCII' button. Detailed information is provided in
Section 5.5.1.2
Exit
Time Function Signal comment, Scrollbar
number I/O
Fig. 5.61 Listing of the events in the device event list buffer
In this display mode the entire event storage buffer is displayed (255
events).
If the signal 'General Start Signal' is received, then the subsequent
events are displayed with relative time to this signal, otherwise an
absolute time is displayed. The display can be called up repeatedly,
until it is deleted.
5-58
RE.216 1KHA000951-UEN ABB Switzerland Ltd
With the keys '↑', '↓', 'PgUp', 'PgDn' and the 'Scrollbar' one can move
one line up / down or a complete page. Hitting the 'Home' or 'End' key
moves the cursor to the start or end of the event list.
To display the relative time of events subsequent to a particular event,
double click with the mouse on that particular event line.
In both types of display an invalid time stamp is marked with a 'T'
between the time stamp and the function number. An invalid time
stamp occurs due to loss of the time synchronization signal on the
Inter Bay Bus. If a device is not connected to an IBB then on loss of
power supply all events are marked as invalid, until the device is
connected to a PC running the CAP2/316. The device is then
synchronized with the PC system time.
The event list can be saved as files for further analysis in the Offline
mode. The files can be saved in two formats:
a) Save as ASCII file (.evt-file extension)
If the events are saved as an ASCII file, it can be opened and edited
with any word processor. It is also possible to open the file with the
CAP2/316 in the off-line mode and if necessary printed. The *.evt file
can be opened from the main menu 'File', 'Open', 'Event ASCII File'.
b) Save as binary file (.ebn-file extension)
If the event list is stored as a binary file *.ebn then it can only be
opened in the off-line mode with the CAP2/316 program. To open the
file, select in the main menu 'Monitor', 'Event Handling' and then 'List
Event List'. It is possible to save the events in ASCII format to facilitate
processing with a word processor program as described above.
5.5.1.3. Clearing the event list
5-59
ABB Switzerland Ltd RE.216 1KHA000951-UEN
5-60
RE.216 1KHA000951-UEN ABB Switzerland Ltd
5-61
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Process value
5-62
RE.216 1KHA000951-UEN ABB Switzerland Ltd
The status display of the in-/outputs is possible with the above shown
displays. The legend at the bottom of the display indicates the
meaning of the color of the lamps for ON / OFF state. The slot number
and the card number are displayed in the top respectively bottom lines.
The status display of the in-/outputs can also be seen with the LEDs
on the front of the plug-in cards.
5.5.2.4. Displaying remote analog or binary in-/outputs
Display of the measurement Select module address
5-63
ABB Switzerland Ltd RE.216 1KHA000951-UEN
5-64
RE.216 1KHA000951-UEN ABB Switzerland Ltd
5-65
ABB Switzerland Ltd RE.216 1KHA000951-UEN
With a double click on the signal the 'Input List' resp. 'Output List' or
'Segment List' will display the respective signals in the display
window.
To check the status of the FUPLA signals select 'Display Signals'. The
status of the signals will be displayed online.
Fig. 5.73 Display of FUPLA in-/outputs, cycle time and signals
5-66
RE.216 1KHA000951-UEN ABB Switzerland Ltd
The test functions can only be opened with a password, because they
can stop the normal operation of the device. The functionality is meant
specifically for commissioning, and should be used only when the
station is out of operation, or, in operation, if the trip and signaling
relays are isolated.
On closing the menu 'Test Functions' the device will be restarted with
the last active parameter set.
The operation of the test function is illustrated below.
5.5.3.1. 5.5.3.5. 5.5.3.2. 5.5.3.6.
5-67
ABB Switzerland Ltd RE.216 1KHA000951-UEN
5-68
RE.216 1KHA000951-UEN ABB Switzerland Ltd
5-69
ABB Switzerland Ltd RE.216 1KHA000951-UEN
5-70
RE.216 1KHA000951-UEN ABB Switzerland Ltd
5-71
ABB Switzerland Ltd RE.216 1KHA000951-UEN
As long as the 'Toggle Binary Output' window is open, all remote I/Os
are decoupled from the process signals. These are transmitted only
when the test function menu is closed.
See the following logic:
Selected window ≥1
'Toggle Binary Output'
closed Binary output
Simulated signal
5-72
RE.216 1KHA000951-UEN ABB Switzerland Ltd
5.5.4. Diagnostics
5-73
ABB Switzerland Ltd RE.216 1KHA000951-UEN
The diagnostic menu in 'Monitor' in the main menu provides the following
possibilities:
• 'List Diagnostic Info'
The result of the self-monitoring of the complete device, the main
processor, the analog inputs card 216EA61 or 216EA62, the
analog output card 216AB61 and the binary input and output card
216 DB61 are displayed. It also comprises the time of the last
changes in the configuration.
5-74
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Close window
Transfer the selected
recording to a file
Delete the first recording
Transfer to File:
A recording can be saved to a file by first selecting the record with the
mouse and then clicking on the button 'Transfer to file'.
After selection of the directory, the recording is stored to the file. It is
important that the file name which contains the Station- (xxx) and
record (yyy) the (RExxx.yyy) is not modified. These are created by the
CAP2/316.
Delete first Record:
The oldest – i.e. the first– recording is deleted. This action cannot be
undone!
b) Reset Disturbance Recorder
The disturbance recorder is reset. All recorded disturbances are
deleted. This process cannot be reversed! The disturbance records
are also deleted if the disturbance recorder configuration is modified.
5-75
ABB Switzerland Ltd RE.216 1KHA000951-UEN
5-76
RE.216 1KHA000951-UEN ABB Switzerland Ltd
5-77
ABB Switzerland Ltd RE.216 1KHA000951-UEN
5-78
RE.216 1KHA000951-UEN ABB Switzerland Ltd
The following menu items are meaningful only if the manuals have
been installed along with the main operation program - the CAP2/316.
Otherwise the manuals will not be displayed (see also Section 5.2.2.),
instead an error message.
5.7.1. User Manual
This menu item will call up the latest operating instructions of the
device.
The SPA commands and the respective SPA address list are clarified
in Chapter 9 of the operating instructions.
5.7.2. RIO580 / LON / MVB / IEC60870-5-103 User Manual
With this menu item all the operating instructions of the various
communication protocols can be called up.
5.7.3. About CAP2/316
This sub-menu provides information about the actual software version
and license information.
5-79
ABB Switzerland Ltd RE.216 1KHA000951-UEN
5-80
RE.216 1KHA000951-UEN ABB Switzerland Ltd
5-81
ABB Switzerland Ltd RE.216 1KHA000951-UEN
If when configuring the inputs using the CAP2/316 they are left at their
default setting of 'Always FALSE' the protection can only operate with
parameter set 1.
“Remote sel.” : If this I/P is activated, a signal from the station
control system (SCS) is necessary to switch between sets of
parameters, otherwise the I/P’s “ParSet2 IN”, “ParSet3 IN” and
“ParSet4 IN” determine which set of parameters is active.
“ParSet2 IN”, “ParSet3 IN” and “ParSet4 IN”:
These three I/P’s enable one of the four sets of parameters to be
selected.
ParSet2 IN ParSet3 IN ParSet4 Active set of
IN para.
F F F 1
T F F 2
F T F 3
T T F no change
F F T 4
T F T no change
F T T no change
T T T no change
As can be seen from the table, the current set of parameters remains
effective, if a signal is applied to more than one of the I/P’s at the same
time.
5-82
RE.216 1KHA000951-UEN ABB Switzerland Ltd
The assignment is done with a check in the box 'P1'…'P4'. Select the
folder 'ParSet1...4' for this purpose.
To view the active functions of a parameter set and the respective
CPU usage select one of the folders ParSet x. From which parameter
set a protection function has been copied, is displayed in the column
'Copy of' (see Section 5.9.2.2).
The copied function must not be active in the same set of parameters
as the original and the parameter set number of the original function
must be lower:
5-83
ABB Switzerland Ltd RE.216 1KHA000951-UEN
RULE: P1 ≤ pO ≤ P4 ↔ pO < pK ≤ P4
pO = parameter set number of the original function
pK = parameter set number of the copied function.
The originals of existing copied functions cannot be deleted.
5.9.2.3. Logics
Where several protection functions are related by a common logic,
they must all be active in the same set of parameters.
5-84
RE.216 1KHA000951-UEN ABB Switzerland Ltd
August 05
6-1
ABB Switzerland Ltd RE.216 1KHA000951-UEN
A defect is also signalled to the other units connected to the bus by the
'SML' or 'CK' bus lines and on the frontplate of the unit concerned by
the alarm LED 'AL'.
A defective unit sets the general alarm bus line 'SML' (i.e. applies a
logical '1'). In normal operation, the bus line 'CK' oscillates at the clock
frequency of the B448C bus. A defective unit disables this signal (i.e.
connects the line to logical '0').
6-2
RE.216 1KHA000951-UEN ABB Switzerland Ltd
6-3
ABB Switzerland Ltd RE.216 1KHA000951-UEN
6-4
RE.216 1KHA000951-UEN ABB Switzerland Ltd
6-5
ABB Switzerland Ltd RE.216 1KHA000951-UEN
UP supply failure UP - 0 - -
‘PASSIVE’ - Connector in- GNB - 1 0 0
serted
Device not initialised GNB 1 1 0 0
6-6
RE.216 1KHA000951-UEN ABB Switzerland Ltd
6.1.2. Self-diagnosis
In addition to continuous hardware self-monitoring, a diagnostics
routine runs on the 216VC62a processing unit which performs the
following functions:
• cyclic testing of its own memories (RAM, EPROM, EEPROM).
• monitoring the correct running of the program (watchdog).
The operation of the microprocessor is monitored by a
watchdog, which is basically a timer. The program must reset
the watchdog at least once every 50 ms. If the program does
not run correctly (run-time error) the timer goes the full time
and resets the processor. The diagnostic system reports a
warm start.
• initialisation and checking that the actual configuration of all the
devices connected to the B448C bus agrees with the set hardware
configuration.
• evaluation of all the disturbance signals from all the units, setting
the status of the protection system and blocking of the protection
functions if necessary.
• entry in the event list.
The status of the protection system can be determined with the aid of
the control unit's (PC) diagnostic function (see Section 5.5.4.) and can
assume one of the four following states:
No error: Normal operation
Every change in the status of the device gives rise to an entry in the
event list. The same list can also be viewed and printed using the HMI
(PC).
6-7
ABB Switzerland Ltd RE.216 1KHA000951-UEN
The diagnostic function can make the following entries in the event list:
Signal Significance
Cold system start Signal generated upon switching on the
auxiliary supply.
Warm system start The system has been reinitialised due to a
software or hardware error (watchdog).
Diagnostics:
System status ... The status of the system has changed as
indicated by the message.
Diagnostics:
Device ... An error has been detected in the device
indicated. Refer to Section 6.1.1. for the
significance.
A/D error A 216EA61 analogue I/P unit has detected and
error and initiated a warm system start.
Software error A software (run-time) error has reinitialised the
system. Further information can be obtained via
the control unit (menus: ‘Display‘ →
‘Diagnostics’ → ‘Read run-time error data’).
Refer also to Section 6.3.1.
Bus error A data transfer error was detected on the
B448C parallel bus and a warm system start
initiated.
Program stop The protection program was stopped, for
example, for changing parameter settings or
because a fatal error was discovered.
Program start The protection program was initialised, for
example, after switching the system on or after
parameters have been reset.
6-8
RE.216 1KHA000951-UEN ABB Switzerland Ltd
The date and time are only added and synchronised after the
control unit (PC) has been connected.
b) Entries following connection of the control unit (PC) and after
binary I/P No. 1 has been switched on and then off again:
14 1990-07-29 05:28:28.758 BinI/P No. 1 ON
15 1990-07-29 05:28:29.111 BinI/P No. 1 OFF
6-9
ABB Switzerland Ltd RE.216 1KHA000951-UEN
The number in brackets at the end of the status line indicates the
contents of the device status register for the unit concerned. It can
be decoded with the aid of the weighting data (see Section 6.1.1.).
For example, entry No. 22: Unit 216NG61 No.4: SSS (8020H)
8000H : SML SML bus line active
+ 0020H : SSS General system alarm
---------
8020H
=====
6-10
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Event messages Nos. 11..13 indicate the device status SSS (0024H).
This means:
0004H : STG Incorrect device configuration
+ 0020H : SSS General system alarm
---------
0024H
=====
6-11
ABB Switzerland Ltd RE.216 1KHA000951-UEN
6-12
RE.216 1KHA000951-UEN ABB Switzerland Ltd
6-13
ABB Switzerland Ltd RE.216 1KHA000951-UEN
6-14
RE.216 1KHA000951-UEN ABB Switzerland Ltd
If a program run-time error was the reason for the warm start, this
information enables the source code instruction to be located at which
the error occurred.
After viewing the information, the list can be deleted in the protection
by selecting ‘Delete HEX dump’ from the ‘Display‘→ ‘Diagnostics’
menu .
The list is deleted when a new set of settings is saved.
6-15
ABB Switzerland Ltd RE.216 1KHA000951-UEN
IBB – Information
Depending on the firmware installed and therefore the choice of the
interbay bus, various data on the status of the bus in relation to the
station control system and the PC card can be obtained via this menu
item.
Details for the respective bus protocols are in the specific operating
instructions.
RIO – Information
Information is displayed on the status of the process bus, the
distributed input/output system and the PC card. A detailed description
of the data is given in publication 1MRB520192-Uen.
6-16
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Example:
Gen. diff.
0.52 IN (spill current in the relay circuit,
IN = transformer rated current)
• binary I/P’s and O/P’s
• O/P signals.
6-17
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Example:
xd = 2; x'd = 0.2
1
z≤ ( 2 − 0.1) = 0.95
2
x
U
I
z
r
X d' 0
xd
6-18
RE.216 1KHA000951-UEN ABB Switzerland Ltd
6-19
ABB Switzerland Ltd RE.216 1KHA000951-UEN
6-20
RE.216 1KHA000951-UEN ABB Switzerland Ltd
August 05
7.1. Summary............................................................................................7-3
7.4. Installation..........................................................................................7-7
7.4.1. Grounding guidelines .........................................................................7-7
7.4.1.1. Cubicle grounding ..............................................................................7-7
7.4.1.2. Grounding for relays mounted in an open frame .............................7-11
7.4.1.3. Additional grounding points along cables ........................................7-12
7.4.2. Wiring...............................................................................................7-12
7.4.2.1. External wiring .................................................................................7-12
7.4.2.2. Internal wiring...................................................................................7-13
7.4.3. Screening.........................................................................................7-13
7.4.3.1. Cable screens ..................................................................................7-13
7.4.3.2. Terminating cable screens...............................................................7-13
7.4.4. Communication cables.....................................................................7-15
7.4.4.1. Laying optical fiber cables................................................................7-16
7.4.5. Guidelines for wiring rack assemblies..............................................7-16
7.4.6. Checking the CT connections ..........................................................7-18
7.4.7. Checking the VT connections ..........................................................7-19
7.4.8. Checking the auxiliary supply connections ......................................7-19
7.4.9. Checking the duty of the tripping and signaling contacts.................7-19
7.4.10. Checking the opto-coupler inputs ....................................................7-19
7.4.11. Inserting the units in the equipment rack .........................................7-20
7.7. Spares..............................................................................................7-26
7-1
ABB Switzerland Ltd RE.216 1KHA000951-UEN
7-2
RE.216 1KHA000951-UEN ABB Switzerland Ltd
7-3
ABB Switzerland Ltd RE.216 1KHA000951-UEN
7-4
RE.216 1KHA000951-UEN ABB Switzerland Ltd
7-5
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Leave sufficient space in front to avoid damage when the hinged frame
is opened. There must generally be enough room for carrying out
maintenance and for using the associated instruments.
Do not install equipment cubicles in corners, which would hinder
opening the hinged frame and working on the cubicle.
Free access is especially important in the case of cubicles not
equipped with a hinged frame. Cubicles are normally erected on a
pedestal or as a suite of cubicles on a platform to facilitate cleaning the
floor and routing of cables.
Fig. 7.1 Example of a front view and view with the hinged
equipment frame swung out of a cubicle
7-6
RE.216 1KHA000951-UEN ABB Switzerland Ltd
7.4. Installation
Mechanical design
The RF (radio frequency) impedance from the location of the various
relays in the cubicle to the cubicle ground must be low.
There must therefore be a good electrical contact between the metal
parts of the cubicle such as side plates, blanking plates etc., and the
frame and base of the cubicle. The contact surfaces must not only be
good electrical conductors, they must also be corrosion-proof so that
long-term good electrical conductivity is preserved.
Non-observance of these conditions can result in the cubicle or parts
of it resonating at certain frequencies, which increase the interference
transmitted by the relays in the cubicle and can lower their immunity to
electrical interference from outside.
7-7
ABB Switzerland Ltd RE.216 1KHA000951-UEN
2
1
1 Copper braid
2 Cable lug
3 Ground bolt
4 Steel flat washer
5 Contact surface
7-8
RE.216 1KHA000951-UEN ABB Switzerland Ltd
7-9
ABB Switzerland Ltd RE.216 1KHA000951-UEN
1 Cubicle
2 Cubicle ground rail
3 Station ground
Fig. 7.4 Grounding principles for two adjacent cubicles
(schematic view)
The ground rails in the two cubicles are connected together and each
one individually connected to the station ground. The ground rails of
cubicles that are more than 1 m apart do not have to be connected.
The cubicles of a suite of several cubicles are also connected together
and each one individually connected to the station ground.
7-10
RE.216 1KHA000951-UEN ABB Switzerland Ltd
RE.216
} non-insulated connection
* braided copper (at least 3 cm wide)
** Station ground
7-11
ABB Switzerland Ltd RE.216 1KHA000951-UEN
7.4.2. Wiring
7.4.2.1. External wiring
The external wiring includes all the connections between the primary
system plant and the cubicle, rack or relay terminals.
The corresponding cables should be run in metal cable ducts that are
connected at several points to the station ground.
The external wiring comprises of the following groups:
• instrument transformer leads
• auxiliary supply connections
• binary inputs and outputs
7-12
RE.216 1KHA000951-UEN ABB Switzerland Ltd
7.4.3. Screening
The screens of cables can be grounded best if the cables enter cubi-
cles via cable glands. Where this is not possible, proceed as illustrated
in Fig. 7.6, taking care that that the cable screens are grounded inside
the cubicle as closely as possible to the entrance.
In order to connect the screen to ground, remove a suitable length of
the insulation, push the exposed screen back over end of the remain-
ing insulation and clamp it to a metal surface. Both the clamp and the
metal surface must be electrically conducting and corrosion-proof.
7-13
ABB Switzerland Ltd RE.216 1KHA000951-UEN
1 3
2 4
1 Cable insulation
2 Screen pushed back over end of insulation
3 Cable clamp
4 Cores
Fig. 7.6 Cable screen termination
It is important that the screen be pushed back over the end of the
insulation as otherwise it frays with time and the quality of the ground
connection diminishes. The risk of the screen and cores being pinched
is also reduced.
Screens in the case of open frames are also secured by a clamp to the
mounting plate close to the relay as shown in Fig. 7.7.
1 Equipment frame
2 Bare mounting plate with relay
3 Cable screen terminations
4 Station ground
5 Screened cables
Fig. 7.7 Cable screen terminations in open equipment frames
(rear view for semi-flush mounting, front view for surface
mounting)
The unscreened ends of the cores going to the relay terminals must be
kept as short as possible and the groups of cables should be run sepa-
rately as explained in Section 7.4.2.2. 'Internal wiring'.
7-14
RE.216 1KHA000951-UEN ABB Switzerland Ltd
1 2 3
5 4
7-15
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Device
Terminals
7-16
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Screened leads must be used for the CT and VT wiring from the
terminals to the equipment.
Recommendation
It is also recommended to use screened leads for the binary inputs
and outputs (BIOs) and the auxiliary supply.
The following applies if the equipment is not installed in a
cubicle:
The terminals should be as close as possible to the equipment
terminals so that the unscreened lengths of cables are very short!
Screened CT, VT, binary input and output and auxiliary supply cables
can be secured in one of the following ways:
Assemblies fitted into panels
CT and VT leads to the terminals can be secured, for example, to a
surface (steel rail) using cable clamps. The surface must be in direct
contact with the plant ground and the cable screens must make good
contact with the cable clamps all the way round.
This, however, is not always the case and the screen is frequently not
in contact at the sides which impairs the screening effect. To over-
come this drawback, a tinned copper braid tape can be wound on top
of the cable screen in the region of the clamps. This then ensures
maximum screening efficiency.
Assemblies fitted into cubicles
(2 alternatives)
a) The CT and VT cables going to the terminals can pass through
cable glands. Again the cable screens must be in good contact
with the gland all the way round and the gland with the station
ground (e.g. via the panel or strip material in which the gland is
fitted).
CT and VT leads to the terminals can be secured, for example, to a
surface (steel or copper) using conduit clamps. The surface (e.g. floor
plate) must be in direct contact with the station ground and the cable
screens must make good contact with the conduit clamps all the way
round.
b) This, however, is not always the case and the screen is frequently
not in contact at the sides which impairs the screening effect. To
overcome this drawback, a tinned copper braid tape can be wound
on top of the cable screen in the region of the clamps. This then
ensures maximum screening efficiency.
To prevent corrosion, a cupal disc (copper plated aluminium) must be
inserted between aluminium and copper parts.
7-17
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Core-balance CTs
If the residual current is obtained from a core-balance CT, the ground
for the cable screen must first be taken back through the core-balance
CT before connecting it to ground. The purpose of this is to ensure that
any spurious E/F current flowing along the screen of the cable cancels
itself and is not measured falsely as an E/F on the relay’s own feeder.
7-18
RE.216 1KHA000951-UEN ABB Switzerland Ltd
T S T US S
7-19
ABB Switzerland Ltd RE.216 1KHA000951-UEN
7-20
RE.216 1KHA000951-UEN ABB Switzerland Ltd
7.5. Commissioning
Prior to commissioning, i.e. before energizing the plant, carry out the
checks in Section 7.4.4.
7.5.1. PC connection
7.5.1.1. Minimum PC requirements
The PC used for commissioning and setting must satisfy at least the
following:
• Windows 2000 or Windows XP operating system
• 128 MByte RAM
• 1 CD drive and a hard disc drive with at least 700 MByte of free
space (depend on the chosen installation options)
• 1 serial interface (RS-232).
7.5.1.2. Interfaces
The 216VC62a has a 25 pin connector on the frontplate for the serial
interface RS-423A, CCIT V.10. Data transfer takes place vie a
unbalanced cable at a data transfer rate between 1200 and
19200 Baud. The signal level for the 216VC62a is approx. ± 4.5 V.
The PC interface (RS-232C) is initialised and appropriately set to
communicate with the RE. 216 by the software.
7-21
ABB Switzerland Ltd RE.216 1KHA000951-UEN
25 pin 9 pin
Screen Screen
Send 2 2 Receive
Receive 3 3 Send
GND 7 5 GND.
7-22
RE.216 1KHA000951-UEN ABB Switzerland Ltd
7-23
ABB Switzerland Ltd RE.216 1KHA000951-UEN
7-24
RE.216 1KHA000951-UEN ABB Switzerland Ltd
7.6. Maintenance
Because of the self-testing and monitoring features included, RE. 216
requires neither special maintenance nor periodic testing.
The wet electrolytic capacitors have a life of >20 years. This assumes
a mean ambient temperature around the casing of 40° C. The life is
doubled, respectively halved for each 10° C of difference.
7.6.1. Fault-finding
The diagnostic function on the control unit (PC) is a valuable tool for
finding faults on the RE. 216 protection system.
Where an error message points to an internal defect, the corre-
sponding unit must be replaced.
7-25
ABB Switzerland Ltd RE.216 1KHA000951-UEN
7.7. Spares
When ordering spares, state the name, type designation and the
function in the protection system for which it is intended. Stocking
spare units is recommended, if there are several units of the same
type in a plant.
The remarks in Section 7.2.2. also apply to storing spares. Testing the
spares at the same time as carrying out routine testing of units in
operation is recommended. This should include connecting them to the
auxiliary supply and allowing them to run for a quarter of an hour.
7-26
RE.216 1KHA000951-UEN ABB Switzerland Ltd
7.8.2. Deleting the old settings and program and downloading the new
program
NOTE: During this procedure only one processing unit 216VC62 may
be installed.
If there are two processing units, the firmware update must be carried
out separately for each processing unit.
The following files needed to update the firmware are in the HMI
directory after installation:
7-27
ABB Switzerland Ltd RE.216 1KHA000951-UEN
7-28
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Fig. 7.11 Main processor unit 216VC62a with the jumpers X602 and
X603 (originated from HESG 324 442
7-29
ABB Switzerland Ltd RE.216 1KHA000951-UEN
NOTE: It follows from the purpose for which the devices and
equipment are used that if they are not correctly handled, mal-
operation or damage can result (either to the devices themselves or to
items of plant)
Examples of damages:
• false tripping of primary system plant
• destruction of modules etc.
The following precautions should be taken to avoid electrostatic
discharge:
• Before touching the modules, discharge your body by touching the
station ground (cubicle).
• Only hold the modules at the edges and do not touch contacts or
components.
• Only store or transport modules in their original packing.
Tools required
Philips screwdriver No. 0 (for older version screwdriver No. 1)
Procedure
Follow the check list when replacing hardware units (PCB’s) (see
Section 7.9.1).
The checklist is primarily intended for replacing defective units by one
of the same type. In the event that another relay configuration is
desired or necessary, a plug-in unit must possibly be exchanged. This
may also entail an exchange of the firmware. In case of uncertainties
please contact ABB.
Where changing a module involves updating the software, check with
ABB Switzerland Ltd., to confirm compatibility etc.
7-30
RE.216 1KHA000951-UEN ABB Switzerland Ltd
7-31
ABB Switzerland Ltd RE.216 1KHA000951-UEN
7-32
RE.216 1KHA000951-UEN ABB Switzerland Ltd
This display indicates that the relay is measuring in the forwards direc-
tion, because the real component of the phase-to-phase impedance is
positive, i.e. providing the scheme is wired according to the standard
ABB diagram in the Appendices (Chapter 12.), the CTs are grounded
on the line side and power flows from the busbars into the line. If the
real component is negative, power is flowing from the line towards the
busbars.
The settings 'CT Neutral' on line and busbar sides and the binary input
'Chg Measurement Dir' on the distance protection function influence
this display.
The first four lines (fault distance and phase-to-ground loop im-
pedances) do not influence the direction of measurement.
The last three lines (phase-to-phase loop impedances) are displayed
providing the load current exceeds
U ⎡V⎤
0,5 × Ph −0 ⎢ ⎥ and 0,5 Imin .
XA ⎣ Ω ⎦
where:
XA reactance in the tripping direction (see Section 3.5.31.2.2.)
Imin pick-up setting of the low-current enabling function
Example:
For a purely resistive load with power flowing from the busbar into
the line and the CT neutral on the line side, the angle between R
phase voltage and current (or US-IS, UT-IT) is zero degrees.
This method of checking the direction of measurement, however, does
not disclose whether the setting of the parameter 'CT neutral'
('Bus side/Line side') is correct.
7-33
ABB Switzerland Ltd RE.216 1KHA000951-UEN
7-34
RE.216 1KHA000951-UEN ABB Switzerland Ltd
R R
S S
T T
6 4 6 4
1 1
3 3
n e n e
K K K K K K
2 k k k 5 2 k k k 5
l l l l l l
L L L L L L
7-35
ABB Switzerland Ltd RE.216 1KHA000951-UEN
7-36
RE.216 1KHA000951-UEN ABB Switzerland Ltd
R R
S S
T T
8 4 8 4
1 1
3 3
6 7 n e 6 7 n e
2 k 5 2 k 5
l I
7-37
ABB Switzerland Ltd RE.216 1KHA000951-UEN
7-38
RE.216 1KHA000951-UEN ABB Switzerland Ltd
R R
S S
T T
6 4 6 4
1 1
3 3
n e n e
K K K K K K
2 k k k 5 2 k k k 5
l l l l l l
L L L L L L
7-39
ABB Switzerland Ltd RE.216 1KHA000951-UEN
The 'Pick-up' and 'Trip' signals must operate, if the conductor passing
through the CT is connected to terminal v on the busbar side and
terminal u on the line side.
7-40
RE.216 1KHA000951-UEN ABB Switzerland Ltd
R R
S S
T T
8 4 8 4
1 1
3 3
u v w u v w
6 7 6 7
n e n e
2 2
k 5 k 5
l l
7-41
ABB Switzerland Ltd RE.216 1KHA000951-UEN
metering wind-
ings where
u v w
fitted
HEST 945017 C
Legend:
R, S, T = three-phase primary system
U, V, W = VT primary terminals
u, v, w = VT metering terminals
n, e = broken delta terminals for E/F protection
R R
S S
T T
U V W U V W
u v w u v w
e n
U0
e n
U0 HEST 945019 FL
HEST 945018 FL
7-42
RE.216 1KHA000951-UEN ABB Switzerland Ltd
R S T RST
K K K
k k k
l l l
L L L
l
HEST 945020 FL
HEST 945021 FL
R S T
K K K
k
L L L
HEST 945022 FL
7-43
RE.216 1KHA000951-UEN ABB Switzerland Ltd
August 05
8. TECHNICAL DATA
8-1
Numerical Generator Protection REG216 /
REG216 Classic
1MRB520004-Ben
Page 1
Issued: May 2005
Changed since: January 2005
Application The REG216 is intended for the protection of tion can be chosen to suit the application by
generators and block transformers. duplicating e.g. auxiliary supply units of the
whole system.
The modular hardware and software design
allows an extremely flexible installation. Standard interfaces make REG216 compati-
Simplicity of adaption to the size of the pri- ble with different process control systems.
mary system and the desired protection Data exchange with higher process control
schemes are achieved through the combi- levels are possible, e.g. one-way reporting of
nation of a software library and hardware digital states and events, measured values and
modules. Economic solutions can thus be protection parameters.
achieved in the full range of applications for
which it is intended. REG216 and REG216 Classic differ with
regard to the binary process connection:
The REG216 software system offers a library
- REG216 uses the E/A-module 216GD61a.
of protective functions. Functions suitable for
generator and transformer protection are lis- - The REG216 Classic uses the modules
ted in the table below. 216GE61 / 216GA61 and 216GA62.
Different degrees of redundancy can be selec-
ted. Availability and reliability of the protec-
ABB Switzerland Ltd Numerical Generator Protection REG216 / REG216
Power Technology Systems
Classic
1MRB520004-Ben
Page 2
Application (cont´d)
ANSI
Protection functions: Description
code
Generator differential 87G three-phase
Power transformer differential 87T three-phase for 2- and 3-winding transformers
Definite time overcurrent (undercurrent) 51 definite time delay, for phase and earth-fault, over-
and undercurrent
Overcurrent or undercurrent with peak value 50 instantaneous operation or with definite time delay,
evaluation value evaluation wide frequency range, over- and undercurrent
Restricted earth fault 87N overcurrent operation with definite time delay*
Voltage-controlled overcurrent 51/27 operation restrained by undervoltage
Inverse time overcurrent 51 inverse current dependent time delay, for phase and
earth fault (51N)
Directional definite time overcurrent 67 definite time tripping
Directional inverse time overcurrent 67 inverse time tripping
Negative phase sequence current 46 negative phase sequence current with definite time delay or
inverse time delay with thermal replica
Definite time overvoltage (undervoltage) 59 definite time delay, over- and undervoltage
27 Applicable also for
64 - stator E/F (95%) (59 G/N)
- rotor E/F (64 R) **
- intertum fault protection
100% stator and rotor earth fault 64 S based on the displacement principle calculation of the
protection 64 R earth fault resistance.
in addition the units REX010 and REX011 are required
Dead machine protection 50AE
Underimpedance 21 circular characteristics centered at origin of impedance plane
Minimum reactance 40 circular characteristics for loss of excitation protection
Pole slip protection 78 detecting loss of synchronism of a generator as against the net-
work
High-voltage distance protection 21Z<HV 6-system high-voltage protection
Distance protection 21Z< distance protection with overcurrent or underimpedance starting
Power 32 any characteristic angle, over and underpower for:
- active power
- reactive power
- reverse power protection
37 - minimum forward power
Overload 49 thermal replica with operating characteristic
according to ASA-C50.13*** for:
- standard stator current (49 S)
- rotor current (49 R)
Negative phase sequence current 46 evaluation of negative phase sequence of currents
inverse time delay;
with terminal replica
Overtemperature 49 thermal protection with precise thermal replica
Frequency 81 evaluation of voltage input
Rate-of-change of frequency 81 df/dt
Overexcitation 24 voltage/frequency protection (81/27)
definite time delay or inverse time delay (81/27)
Voltage balance 60 monitoring/comparing two groups of single- or three-phase volt-
age
Voltage peak value evaluation 59/27 instantaneous operation with definite time delay
Synchro check 25 supervision of phase angle frequency and voltage level of two
systems
Breaker failure protection 50BF
Logical functions AND, OR, flip-flop, time delay, counter
Aside from these typical generator protection functions the entire library of the RE.316*4 platform is also available (e.g. distance
protection, autoreclosure, I0 inverse, etc.). For more details see the Operating Instructions of REG216
ABB Switzerland Ltd Numerical Generator Protection REG216 / REG216
Power Technology Systems
Classic
1MRB520004-Ben
Page 3
Construction (cont´d)
Facilities for different trip circuit supervision • Connection to the station control with
arrangements in conjunction with the output transmission of messages
unit 216DB61and the input auxiliary relay • Time clock synchronizing for time-tagging
assembly 216GE61 can be provided. of events
• Non-volatile event and disturbance mem-
Parallel bus and electronic units ory (gold capacitor buffered)
The electronic units are of plug-in design and
accommodated in an equipment rack with the • Space requirement: two rack divisions.
standard dimension 19", 6U (1U = 44,45
mm). An equipment rack of this kind is di- Analog Input unit 216EA62
vided into 21 standard divisions. The ex- • 24 inputs sampled simultaneously in
change of data via the parallel bus B448C is groups of six
controlled and monitored by all units avail- • Sampling frequency 600 (720) Hz for a
able. power frequency of 50 (60) Hz
The protection system is based on a data bus • Space requirement: two rack divisions.
with digital signal processing for most func-
tions; signal conditioning, analog and digital Digital output unit 216AB61
inputs, A/D conversion, processing and signal • 32 outputs for controlling the relays of the
output. output auxiliary relay assembly
• Short-circuit proof
The components of the system are:
• Front plate LEDs for indication of acti-
• Static plug-in units, which exchange data vated relays
via a powerful parallel bus
• Space requirement: one rack division.
• Interfaces to the process (primary system,
station equipment), which are isolated Tripping output and binary input unit
from the digital processing unit. 216DB61
• 8 outputs for two-pole control of auxiliary
Equipment rack 216MB66/216MB68 and tripping relays
parallel bus B448C
• Monitored output amplifiers
The main features of the parallel bus B448C
are: • 16 digital inputs for the signals from the
input auxiliary relay assembly (two each
• Specification based on IEEE P 896 (future can be used to externally enable and block
bus) tripping respectively)
• Time multiplexing of addresses and data • Activated outputs and inputs indicated by
(16 bit) LEDs
• Asynchronous data transmission with • Front space requirements: one rack divi-
handshake sion.
• Integrity checking of each data exchange.
Auxiliary DC supply unit 216NG61,
• Up to 32 master units having equal status, 216NG62 and 216NG63
actively accessing the bus • Versions for 36 to 312 V DC input
• Common internal 24 V auxiliary supply • Outputs 24V DC, 150 W
for all electronic units; redundant 24 V are
possible. • Short-circuit and overload-proof outputs
• Parallel connection to increase rating
Processing unit 216VC62a
• 32 bit processor type 80486DX-2 • Parallel connection for redundancy
(2 outputs)
• Application software on Flash EPROM
• Space requirement: 3 rack divisions.
• Operating data on RAM
• Settings on non-volatile Flash EPROM All the REG216 protection functions operate
with sampled primary system voltages and
• Potential-free RS-423 interface for PC currents. The sampling rate of the analog
operation
ABB Switzerland Ltd Numerical Generator Protection REG216 / REG216
Power Technology Systems
Classic
1MRB520004-Ben
Page 6
Construction (cont´d) input units is 12 times per period at rated For each protection function a visible tripping
power system frequency with a dynamic characteristic is displayed depending on the
range of 15 bits. setting values, e.g. the underimpedance func-
tion shown below.
All further signal processing takes place digi-
tally. The protection functions are therefore
universally applicable, highly accurate and
have excellent long-time stability.
Windows HMI
A new Windows-based setting tool CAP2/
316 is available since the Firmware version
V5.2. This Software runs only under the fol-
lowing operating systems:
• WINDOWS NT 4.0 Self-monitoring and testing
facilities
• WINDOWS 2000 The self-monitoring and testing routine philo-
• WINDOWS XP ≥6.0 sophy of the REG216 can be divided into fol-
lowing sections:
The perfect tool for engineering, testing, • Self-monitoring
commissioning and maintenance personnel
can be used for ON-LINE or OFF-LINE pro- • Parameter viewing facilities
gramming. • Injection testing with separate test equip-
ment.
Self-monitoring
The self-monitoring and testing routine philo-
sophy is quite different from conventional
testing techniques. Whilst the previous prac-
tice in protection was to maintain availability
through comprehensive periodic testing.
REG216 does this continuously by taking full
advantage of digital and data bus technology.
3
Operation for
I'1
<b
Operation IN
2 or
I∆ = I1+ I2 + I3
I'2
<b
IN
I ' × I ' × cos α for cos α ≥ 0
IH = 1 2 1
0 for cos α < 0
v Restraint
α = arg (I'1 ; - I'2) g
1 b 2 3 IH
2-winding: I'1 = I1, I'2 = I2
IN
3-winding: I'1 = MAX (I1, I2, I3)
I'2 = I1 + I2 + I3 - I'1 Fig. 2 Differential protection characteristic
Table 12: Instantaneous overvoltage protection function (59, 27) with peak value
evaluation
Features:
• Evaluation of instantaneous values, therefore extremely fast and frequency-independent on a wide scale
• Storing of the highest instantaneous value after start
• No suppression of DC components
• No suppression of harmonics
• Single- or three-phase
• Maximum value detection for multi-phase functions
• Variable lower limiting frequency fmin
Settings:
Voltage 0.01 to 2.0 UN in steps of 0.01 UN
Delay 0.00 to 60 s in steps of 0.01 s
Limiting fmin 25 to 50 Hz in steps of 1 Hz
Accuracy of pick-up value (at 0.08 to 1.1 fN) ±3% or 0.005 UN
Reset ratio >90% (for max. function)
<110% (for min. function)
Max. trip time at no delay (at fN) <30 ms (for max. function)
<50 ms (for min. function)
Technical data (cont´d) Table 24: Overexcitation function with inverse time delay (24)
Features:
• Single-phase measurement
• inverse time delay
• According to IEEE Guide C37.91-1985, setting made by help of table settings
Settings:
Table settings U/f values: (1.05; 1.10 to 1.50) UN/fN
Start value U/f 1.05 to 1.20 UN/fN in steps of 0.01 UN/fN
tmin 0.01 to 2 min in steps of 0.01 min
tmax 5 to 100 min in steps of 0.1 min
Reset time 0.2 to 100 min in steps of 0.1 min
Reference voltage 0.8 to 1.2 UN in steps of 0.01 UN
Accuracy of pick-up value ±3% UN/fN (at fN)
Frequency range 0.5 to 1.2 fN
Reset ratio 100%
Starting time <120 ms
ABB Switzerland Ltd Numerical Generator Protection REG216 / REG216
Power Technology Systems
Classic
1MRB520004-Ben
Page 19
Fig. 7 Tripping characteristic Voltage comparison (shown for the phases R and the setting value volt.
diff. = 0.2 • UN)
Settings:
Voltage difference 0.1 to 0.5 UN in steps of 0.05 UN
Trip delay 0.00 to 1.0 s in steps of 0.01 s
Reset delay 0.1 to 2.0 s in steps of 0.01 s
Numbers of phases 1 or 3
Maximum tripping time without delay ≤50 ms
U1R: phase R voltage amplitude voltage channel 1 (line 1)
U2R: phase R voltage amplitude voltage channel 2 (line 2)
For 3-phase function: the characteristic is valid accordingly for the phases S and T
ABB Switzerland Ltd Numerical Generator Protection REG216 / REG216
Power Technology Systems
Classic
1MRB520004-Ben
Page 20
Technical data (cont´d) Table 26: Dead machine protection (51, 27)
Features:
• Quick separation from network at accidental energization of generator (e.g. at standstill or on turning
gear)
• Instant overcurrent measurement
• Voltage-controlled overcurrent function e.g. blocked at voltage values >0.85 UN
This function does not exist in the library, it must be combined from the voltage current and time function
Settings:
Voltage 0.01 to 2 UN in steps of 0.002 UN
Reset delay 0 to 60 s in steps of 0.01 s
Current 0.02 to 20 IN in steps of 0.02 IN
Delay 0.02 to 60 s in steps of 0.01 s
Table 33: Accuracy of the metering function UIfPQ and three-phase measuring module
(including input voltage and input current CT)
Input variable Accuracy Conditions
Core balance CTs Protection CTs
with error compensation without error com-
pensation
Voltage ±0.5% UN ±1% UN 0.2 to 1.2 UN
f = fN
Current ±0.5% IN ±2% IN 0.2 to 1.2 IN
f = fN
Real power ±0.5% SN ±3% SN 0.2 to 1.2 SN
0.2 to 1.2 UN
0.2 to 1.2 IN
f = fN
Apparent power ±0.5% SN ±3% SN
Power factor ±0.01 ±0.03 S = SN, f = fN
Frequency ±0.1% fN ±0.1% fN 0.9 to 1.1 fN
0.8 to 1.2 UN
SN = √3 • UN • IN (three-phase)
SN = 1/3 • √3 • UN • IN (single-phase)
ABB Switzerland Ltd Numerical Generator Protection REG216 / REG216
Power Technology Systems
Classic
1MRB520004-Ben
Page 24
Ordering In order to configure the generator protection 1) 216GW62 Input transformer assembly
system type REG216 the ABB-Engineering 2) 216GD61a Interface unit consisting of:
group needs the information from the Ques- 8 tripping relays
tionnaire 1MRB520026-Ken.
16 signalling relays
When ordering the REG216 version the fol- 16 optocouplers
lowing has to be stated: 3 cables 216IK61.
• Rated current
• Rated voltage NOTE:
For customizing the REG216 version, please
• Optocoupler voltage contact an ABB sales representative.
• Quantity of different units (electronic part)
and interfaces.
1*GW62 Code K-
1*GD61a Code I-
M- M2 Single system 1*rack 216MB66 consisting of 1*NG6x, 1*EA62, 1*AB61, 2*DB61, 1*VC62a
1*GW62 Code K-
2*GD61a Code I-
M- M5 Single system 1*rack 216MB66 consisting of 1*NG6x, 2*EA62, 1*AB61, 2*DB61, 1*VC62a
M- M11 Redundant system 1*rack 216MB68 consisting of 1*NG6x, 1*EA62, 1*AB61, 1*DB61, 1*VC62a per system
M- M21 Double system 2*racks 216MB66 consisting of 1*NG6x, 1*EA62, 1*AB61, 2*DB61, 1*VC62a per rack
Ordering (cont´d)
Subcodes Explanation Description Remarks for ordering
K-/L- K16 2 VTs (special) 100% Stator earth fault protection
N-/O- L16 1 CT (1ph Code A-)
P-/Q- N16 9 CT (3ph Code A-)
O16
P16
Q16
K-/L- K18 6 CTs (3ph Code A-)
N-/O- L18 1 CT (1ph Code A-)
P-/Q- N18 1 MT (1ph Code B-)
O18 1 CT (1ph Code A-)
P18 3 VTs (3ph delta Code U-)
Q18
K-/L- K19 3 VTs (3pn delta Code U-)
N-/O- L19 3 VTs (3ph delta Code U-)
P-/Q- N19 1 CT (1ph Code A-)
O19 1 MT (1ph Code B-)
P19 1 CT (1ph Code A-)
Q19 1 VT (1ph 95% Stator earth fault protection
2 VTs (special) 100% Stator earth fault protection
Ordering (cont´d)
Configuration:
- 1*216NG6x Code G
- 1*216VC62a
- 1*216EA62
- 1*216AB61
- 1*216DB61
- 12 Input transformers (1*216GW62) Code K
- 8 Tripping relays
}
- 16 Signaling relays (1*216GD61a) Code I
- 16 Binary inputs
Options:
- Additional CPU type 216VC62a Code W5
- Redundant power supply 216NG6x Code H
216NG62
ABB Switzerland Ltd Numerical Generator Protection REG216 / REG216
Power Technology Systems
Classic
1MRB520004-Ben
Page 36
Configuration:
- 1*216NG6x Code G
- 1*216VC62a
- 1*216EA62
- 1*216AB61
- 2*216DB61
- 24 input transformers (2*216GW62) Code K/L
- 16 tripping relays
- 32 signaling relays
- 32 binary inputs
} (2*216GD61a) Code I
Options:
- Additional CPU type 216VC62a Code W5
- Redundant power supply 216NG6x Code H
K- L-
216NG62
ABB Switzerland Ltd Numerical Generator Protection REG216 / REG216
Power Technology Systems
Classic
1MRB520004-Ben
Page 37
Configuration:
- 1*216NG6x Code G
- 1*216VC62a
- 1*216EA62
- 1*216AB61
- 1*216DB61
- 24 input transformers (2*216GW62) Code K/L
}
- 8 tripping relays
- 16 signaling relays (1*216GD61a) Code I
- 16 binary inputs
Options:
- Additional CPU type 216VC62a Code W5
- Redundant power supply 216NG6x Code H
K- L-
216NG62
ABB Switzerland Ltd Numerical Generator Protection REG216 / REG216
Power Technology Systems
Classic
1MRB520004-Ben
Page 38
Configuration:
- 1*216NG6x Code G
- 1*216VC62a
- 1*216EA62
- 1*216AB61
- 2*216DB61
- 12 input transformers (1*216GW62) Code K
}
- 16 tripping relays
- 32 signaling relays (2*216GD61a) Code I
- 32 binary inputs
Options:
- Additional CPU type 216VC62a Code W5
- Redundant power supply 216NG6x Code H
K-
216NG62
ABB Switzerland Ltd Numerical Generator Protection REG216 / REG216
Power Technology Systems
Classic
1MRB520004-Ben
Page 39
Configuration:
- 1*216NG6x Code G
- 1*216VC62a
- 2*216EA62
- 1*216AB61
- 2*216DB61
- 36 input transformers (3*216GW62) Code K/L/N
}
- 16 tripping relays
- 32 signaling relays (2*216GD61a) Code I
- 32 binary inputs
Options:
- Additional CPU type 216VC62a Code W5
- Redundant power supply 216NG6x Code H
K- L- N-
216NG62
ABB Switzerland Ltd Numerical Generator Protection REG216 / REG216
Power Technology Systems
Classic
1MRB520004-Ben
Page 40
Configuration:
- 1*216NG6x Code G
- 1*216VC62a
- 2*216EA62
- 1*216AB61
- 2*216DB61
- 48 input transformers (4*216GW62) Code K/L/N/O
}
- 16 tripping relays
- 32 signaling relays (2*216GD61a) Code I
- 32 binary inputs
Options:
- Additional CPU type 216VC62a Code W5
- Redundant power supply 216NG6x Code H
K- L- N- O-
216NG62
ABB Switzerland Ltd Numerical Generator Protection REG216 / REG216
Power Technology Systems
Classic
1MRB520004-Ben
Page 41
}
- 8 tripping relays
- 16 signaling relays (1*216GD61a) Code I
- 16 binary inputs
Common use for both systems:
- 24 input transformers (2*216GW62) Code K/L
Options:
- none
K- L-
216NG62
ABB Switzerland Ltd Numerical Generator Protection REG216 / REG216
Power Technology Systems
Classic
1MRB520004-Ben
Page 42
}
- 16 tripping relays
- 32 signaling relays (2*216GD61a) Code I
- 32 binary inputs
Common use for both systems:
- 24 input transformers (2*216GW62) Code K/L
Options:
- none
K- L-
ABB Switzerland Ltd Numerical Generator Protection REG216 / REG216
Power Technology Systems
Classic
1MRB520004-Ben
Page 43
}
- 8 tripping relays
- 16 signaling relays (1*216GD61a) Code I
- 16 binary inputs
- 12 input transformers (1*216GW62) Code K/N
Common use for both systems:
- 12 input transformers (1*216GW62) Code L
Options:
- none
K- L- N-
216NG62
ABB Switzerland Ltd Numerical Generator Protection REG216 / REG216
Power Technology Systems
Classic
1MRB520004-Ben
Page 44
}
- 16 tripping relays
- 32 signaling relays (2*216GD61a) Code I
- 32 binary inputs
- 12 input transformers (1*216GW62) Code K/N
Common use for both systems:
- 12 input transformers (1*216GW62) Code L
Options:
- none
K- L- N-
ABB Switzerland Ltd Numerical Generator Protection REG216 / REG216
Power Technology Systems
Classic
1MRB520004-Ben
Page 45
}
- 8 tripping relays
- 16 signaling relays (1*216GD61a) Code I
- 16 binary inputs
- 24 input transformers (2*216GW62) Code K/L/N/O
Common use for both systems:
- none
Options:
- none
K- L- N- O-
216NG62
ABB Switzerland Ltd Numerical Generator Protection REG216 / REG216
Power Technology Systems
Classic
1MRB520004-Ben
Page 46
}
- 16 tripping relays
- 32 signaling relays (2*216GD61a) Code I
- 32 binary inputs
- 24 input transformers (2*216GW62) Code K/L/N/O
Common use for both systems:
- none
Options:
- none
K- L- N- O-
ABB Switzerland Ltd Numerical Generator Protection REG216 / REG216
Power Technology Systems
Classic
1MRB520004-Ben
Page 47
}
- 16 tripping relays
- 32 signaling relays (2*216GD61a) Code I
- 32 binary inputs
- 12 input transformers (1*216GW62) Code K/N
Common use for both systems:
- 12 input transformers (1*216GW62) Code L
Options:
- Additional CPU board per system Code W
- 2nd power supply (A) Code H
- 2nd power supply (B) Code F
K- L- N-
216NG62 216NG62
ABB Switzerland Ltd Numerical Generator Protection REG216 / REG216
Power Technology Systems
Classic
1MRB520004-Ben
Page 48
}
- 16 tripping relays
- 32 signaling relays (2*216GD61a) Code I
- 32 binary inputs
- 12 input transformers (1*216GW62) Code K/O
Common use for both systems:
- 24 input transformers (2*216GW62) Code L/N
Options:
- Additional CPU board per system Code W
- 2nd power supply (A) Code H
- 2nd power supply (B) Code F
K- L- N- O-
216NG62 216NG62
ABB Switzerland Ltd Numerical Generator Protection REG216 / REG216
Power Technology Systems
Classic
1MRB520004-Ben
Page 49
Options:
- Additional CPU board per system Code W
- 2nd power supply (A) Code H
- 2nd power supply (B) Code F
K- L- N- O-
216NG62 216NG62
ABB Switzerland Ltd Numerical Generator Protection REG216 / REG216
Power Technology Systems
Classic
1MRB520004-Ben
Page 50
}
- 16 tripping relays
- 32 signaling relays (2*216GD61a) Code I
- 32 binary inputs
- 12 input transformers (1*216GW62) Code K/P
Common use for both systems:
- 36 input transformers (3*216GW62) Code L/N/O
Options:
- Additional CPU board per system Code W
- 2nd power supply (A) Code H
- 2nd power supply (B) Code F
K- L- N- O- P-
216NG62 216NG62
ABB Switzerland Ltd Numerical Generator Protection REG216 / REG216
Power Technology Systems
Classic
1MRB520004-Ben
Page 51
}
- 16 tripping relays
- 32 signaling relays (2*216GD61a) Code I
- 32 binary inputs
- 24 input transformers (2*216GW62) Code K/L/P/Q
Common use for both systems:
- 24 input transformers (2*216GW62) Code N/O
Options:
- Additional CPU board per system Code W
- 2nd power supply (A) Code H
- 2nd power supply (B) Code F
K- L- N- O- P- Q-
216NG62 216NG62
ABB Switzerland Ltd Numerical Generator Protection REG216 / REG216
Power Technology Systems
Classic
1MRB520004-Ben
Page 52
Sample Numerical protection equipment used for • duplicating power supply unit
specification generator and block transformer protection.
• duplicating the whole system.
It will be a stand-alone system but closely
Additional benefits considered are wide set-
involved in the process. Parameters, signals, ting ranges, excellent long-term stability and
measured values as well as remote parameter few setting steps. The numerical system
regulation commands will be exchanged via
should offer a library of the available protec-
appropriate interfaces and a serial communi- tive functions. These functions will then be
cations channel to central process control selected by the user by the simple assign-
equipment.
ment of parameters.
The system will be supported by a software All protection functions should operate from
library of diverse protection functions. A
sampled primary system voltages and cur-
menu-driven HMI (human machine interface) rents. The sampling rate of the analog input
will allow users to activate functions which units should be 12 times per period at rated
are provided in the protection function
power system frequency with a dynamic
library. range of 15 bit.
The entire protective system will consist of a
The man-machine communication should be
relatively small number of hardware compo- performed easily using only a few push but-
nents. This applies not only to the electronic ton commands on a personal computer (PC)
units, but also to the process interfaces, such
via a serial RS 232 interface. No prior knowl-
as current and voltage inputs as well as the edge of programming should be necessary.
numbers of signal and tripping relays. For all functions the user is guided with the
aid of screen menus and windows. All differ-
This flexibility resulting from the modular ent languages for texts could be supplied.
hardware will enable the equipment configu- Any text change is accommodated easily.
ration to be easily adapted for installations of
different sizes and the desired scope of pro- All the hardware components should be pack-
tection. aged in a single cabinet. This cubicle can also
accommodate other protection relays with
The system will permit various degrees of external functions, for example 100% stator
redundancy. The user can specify the desired earth fault protection, Buchholz relay or some
configuration:
thermal sensors.
www.abb.com/substationautomation
Application The unit is applied for the protection of gen- former REX011 are required. This injection
erators in block configuration for earth faults equipment can be applied to all common
on the generator side. For the implementation generator earthing- and excitation-systems.
of the 100% stator and rotor earth fault The protection is active during all states of
protection using a REG216/316*4, an injec- the machine, standstill as well as run-up and
tion unit REX010 and the injection trans- run-down.
ABB Switzerland Ltd Auxiliary unit for REG216/316*4 for 100% REX010/011
Utility Automation Systems
stator and rotor earth fault protection 1MRB520123-Ben
Page 2
Overlap
Winding
Neutral point Terminal
Running machine
Fig. 1
The coding is achieved by alternating the type P8. In the case that the earth fault current
transmission of the square wave with a quies- exceeds 5 A the contactor will open the input
cent period, as seen in Fig. 3. circuit to the injection unit to protect it
against high voltages during earth faults near
the generator terminals. The 95% function is
always active and will detect any earth faults.
Software Three protection functions are available in the the protected zone by including the monitor-
REG216/316*4 library: ing of the generator circuit breaker status.
- 100% Stator earth fault The function is capable of measuring the ef-
protection Stator EFP fective value of RES and of the transformation
- Rotor earth fault protection Rotor EFP ratio of the voltage transformer while the ma-
- 95% Stator earth fault chine is at standstill. This allows optimizing
the function with the actual parameters of the
protection Overvoltage U>
protected machine.
During the transmitting period, the digital fil-
Alarm and trip levels are entered and read out
ter algorithms are calculating the instanta-
in kΩ.
neous earth fault resistance from the input
signal pairs Uis, Ui and Uir, Ui respectively. Settings:
Alarm level 100 Ω to 20 kΩ
During the quiescent period the filtered sig-
Delay 0.2 s to 60s
nals Uis and Uir are examined for interfer-
Trip level 100 Ω to 20 kΩ
ence from the protected object or the
Delay 0.2 s to 60 s
connected network. This examination is used
RES 250 Ω to 5 kΩ
to validate the previous calculation of the
earth fault resistance. Number of neutral points 2
RES-2. neutral point 900 Ω to 30 kΩ
The reference signal Ui is continuously Reset ratio 110% (with
supervised with respect to amplitude and fre- settings of <10 kΩ)
quency. This ensures that the injection signal 120% (with
is correct and that it has the correct frequency. settings of >10 kΩ)
Accuracy 100 Ω to 10 kΩ:
The primary earth connection of the protected
<±10%
machine is checked through evaluation of the
0 to 100 Ω, 10 kΩ
capacitive component of the earth fault cur-
to 20 kΩ: <±20%
rent during the transmitting period.
Operating time 1.5 s
100% Stator earth fault protection function
Machine and system parameters:
This function consists of an alarm level and a
- Max. earth fault
trip level with corresponding signalling and
current l0 <20 A (recom-
tripping outputs.
mended l0 ≤5 A)
It is possible to compensate for a second - Stator earth
high-resistance earth to neutral point within capacitance 0.5 µF to 6 µF
ABB Switzerland Ltd Auxiliary unit for REG216/316*4 for 100% REX010/011
Utility Automation Systems
stator and rotor earth fault protection 1MRB520123-Ben
Page 4
Diagrams
Fig. 4 Stator earth fault protection, star point Fig. 5 Stator earth fault protection with earthing
transformer on generator terminals
Fig. 6 Stator earth fault protection with Fig. 7 Single pole rotor connection earthing with
earthing transformer on star point resistors
ABB Switzerland Ltd Auxiliary unit for REG216/316*4 for 100% REX010/011
Utility Automation Systems
stator and rotor earth fault protection 1MRB520123-Ben
Page 6
Diagrams (cont’d)
www.abb.com/substationautomation
Introduction
The operation of any generator differential protection is influenced by distortion in
the measuring quantities. The current to the protection will be heavily distorted
when the current transformer is saturated.In most cases it is not possible to avoid
current transformer saturation for all fault conditions, therefore measures are taken
in the generator differential protections to allow for current transformer saturation
with maintained proper operation. REG316 / REG316*4 / REG216 can allow for
heavy current transformer saturation but not an unlimited one.
For transformer differential protection see document
CH-ES 30-32.10 E for RET316 / RET316*4.
Requirements on current transformers
Choice of current transformers
The current transformer should be to type TPS,TPX or TPY with accuracy class
5P20 or better. The use of the linearized current transformer type TPZ leads only
to a small phase angle shift and they can be used without problems, if the same
type is on both sides of the generator. Possibly ABB Switzerland Ltd, Utility Auto-
mation can be contacted for confirmation that the actual type can be used.
The current transformer ratio should be selected so, that the current to the
protection is larger than the minimum operating value for all faults that shall be
detected. Minimum operating current for the generator differential protection in
REG316 / REG316*4 / REG216 is 10 % of nominal current.
Conditions for the CT requirements
The requirements for REG316 / REG316*4 / REG216 are a result of investigations
performed in our network simulation program. The tests have been performed with
a digital current transformer model.
The setting of the current transformer model was representative for current trans-
formers type TPX and TPY.
The performance of the generator differential protection was checked for internal
and external both symmetrical and fully asymmetrical fault currents. A source with
a time constant from 40 up to 300 milliseconds was used at the tests. The current
requirements below are thus applicable both for symmetrical and asymmetrical fault
currents.
Both phase to ground, and three phase faults were tested.
UTAST
1/3
CH-ES 30-32.20 E
The protection was checked with regard to security to block. All testing was made
with and without remanence flux in the current transformer core. It is difficult to
give general recommendations for additional margins for remanence flux. It de-
pends on the demands of reliability and economy.
When current transformers of type TPY are used, practically no additional margin
is needed due to the anti remanence air gap. For current transformer of Type TPX,
the small probability of a fully asymmetrical fault together with maximum
remanence flux in the same direction as the flux generated by the fault has to be
kept in mind at the decision of an additional margin. Fully asymmetrical fault cur-
rent will be achieved when the fault occurs at zero voltage (0°). Investigations
have proved that 95 % of the faults in the network will occur when the voltage is
between 40° and 90°.
Fault current
The current transformer requirements are based on the maximum fault current for
faults in different positions. Maximum fault current will occur for three phase faults
or single phase to ground faults. The current for a single phase to ground fault will
exceed the current for a three phase fault when the zero sequence impedance in
the total fault loop is less than the positive sequence impedance.
When calculating the current transformer requirements, the maximum fault current
should be used and therefore both fault types have to be considered.
Cable resistance and additional load
The current transformer saturation is directly affected by the voltage at the current
transformer secondary terminals. This voltage, for a ground fault, is developed in a
loop containing the phase and neutral conductor and additional load in this loop.
For three phase faults, the neutral current is zero, and only the phase conductor
and additional phase load have to be considered.
In the calculation, the loop resistance should be used for phase to ground faults
and the phase resistance for three phase faults.
REG316 / REG316*4 / REG216 current transformer requirements
The current transformer effective overcurrent factor should meet the two require-
ment below. The requirement assume 40 to 300 msec maximum dc time constant
for the network.
2/3
CH-ES 30-32.20 E
Pr + PE IN of CT
1. n' ≤ n × ×
PB + PE IN
and 2.
the dependence of the curves of Figure 1, where:
for fault currents ≤ 3 * IN the CT's should not saturate, respectively
the exact boundary is at b*√3 (b = setting value of the characteristic).
n'
10
9
8
7
6
5
4
3
2
1
0
0 3 4 6 8 10 12 14
IK/ IN
with 50% remanence without remanence
3/3
CH-ES 30-32.10 E
The current transformer ratio should be selected so that the current to the protec-
tion is larger than the minimum operating value for all faults that shall be detected.
Minimum operating current for the transformer protection in RET316 / RET316*4 is
10 % of nominal current.
The performance of the transformer protection was checked for internal and ex-
ternal both symmetrical and fully asymmetrical fault currents. A source with a time
constant from 40 up to 300 milliseconds was used at the tests. The current require-
ments below are thus applicable both for symmetrical and asymmetrical fault
currents.
Both phase to ground, and three phase faults were tested.
UTAST
1/3
CH-ES 30-32.10 E
The protection was checked with regard to security to block. All testing was made
with and without remanence flux in the current transformer core. It is difficult to
give general recommendations for additional margins for remanence flux. It
depends on the demands of reliability and economy.
When current transformers of type TPY are used, practically no additional margin
is needed due to the anti remanence air gap. For current transformer of Type TPX,
the small probability of a fully asymmetrical fault together with maximum
remanence flux in the same direction as the flux generated by the fault has to be
kept in mind at the decision of an additional margin. Fully asymmetrical fault
current will be achieved when the fault occurs at zero voltage (0°). Investigations
have proved that 95 % of the faults in the network will occur when the voltage is
between 40° and 90°.
Fault current
The current transformer requirements are based on the maximum fault current for
faults in different positions. Maximum fault current will occur for three phase faults
or single phase to ground faults. The current for a single phase to ground fault will
exceed the current for a three phase fault when the zero sequence impedance in
the total fault loop is less than the positive sequence impedance.
When calculating the current transformer requirements, the maximum fault current
should be used and therefore both fault types have to be considered.
In the calculation, the loop resistance should be used for phase to ground faults
and the phase resistance for three phase faults.
Pr + PE IN of ct.
1. n' ≤ n × ×
PB + PE IN
2/3
CH-ES 30-32.10-E
and 2.
the dependence of the curves of Figure 1 and 2, where:
for fault currents ≤ 3 * IN the CT's should not saturate
n'
16
14
12
10
8
6
4
2
0
0 3 4 6 8 10 12 14 16 18 20
IK/IN
with 50% remanence without remanence
n'
35
30
25
20
15
10
5
0
0 3 4 6 8 10 12 14 16 18 20
IK/IN
with 50% remanence without remanence
August 05
9-1
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9-2
RE.216 1KHA000951-UEN ABB Switzerland Ltd
g448308
Pin 2: Rx
Pin 3: Tx
Pin 4: +12V
Pin 5: 0V
Pin 9: -12V
9-3
ABB Switzerland Ltd RE.216 1KHA000951-UEN
NOTE:
The settings are to be found in the publication:
• the LON interbay bus 1MRB520225-Uen,
• for the MVB interbay bus 1MRB520270-Uen,
• for the IEC60870-5-103 interbaybus
1MRB520226-Uen to
1MRB520229-Uen
• for the MVB process bus 1MRB520192-Uen.
Slave/NodeAddr
Range 2- 255: Must be set to the correct SPA bus address.
9-4
RE.216 1KHA000951-UEN ABB Switzerland Ltd
TouchScreen/SMS
Setting determines whether the touch screen or an SMS has to be
controlled:
• Inactive Connection not in operation (default)
• Active Connection in operation
Note that this parameter has no influence for the versions with the
SPA and IEC60870-5-103 Bus.
The versions for the LON or MVB bus has a fully functional SPA
interface in parallel with the LON/MVB interbay bus for connecting
either a touch screen or an SMS. The parameter 'TouchScreen/SMS'
should only be set to 'active', when the second interface is in use,
while in this case the response time of the LON or MVB bus is more.
Note that this parameter has no relevance in the versions with the SPA
or IEC60870-5-103 bus protocol.
Timesynchr.
Defines the time for synchronization via the IBB when the summer
time bit is set:
• Standard time Only the summer time bit is set and standard
time is used for synchronization (preferred
setting).
• Summer time Summer time is used for synchronization in spite
of the fact that the summer time bit is also set.
'Standard time' has to be selected when the summer time bit is not set
(e.g. as in the case of the SPA bus).
Baud rate
Default 9600 for SPA bus. Do not change.
9-5
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Master mask
• Bit mask
The bit masks set for every function via the SPA bus apply for all
binary events. No masks are used for analog events.
• Q events off
As above, but all analog events are blocked. This is the default
setting and must always be used when the device is connected to
an SCS100.
• Event off
All events are masked (not recorded).
This setting is intended for testing and during commissioning when
it is not wanted that events be transmitted to the control room.
Receiving
Indicates that valid SPA telegrams have been received.
Initiating
Indicates that the device is being initialised.
The following parameters determine the access rights of the remote
HMI and can only be configured on the local HMI:
• Remote CAP2/316 On / Off
Enables or disables the remote HMI.
• TestFunctions On/Off
Enables or disables the test function on the remote HMI.
• TimeSynchronization On / Off
Enables or disables synchronization by the remote HMI.
• Downloading On / Off
Enables or disables the downloading of a 'setfile' from the remote
HMI.
9-6
RE.216 1KHA000951-UEN ABB Switzerland Ltd
V20:
Write: WV20:1 starts the transmission of a telegram.
Read: RV20 returns the number of disturbance recorder
records available.
V17:
Write: WV17:1...5 determines the compression factor, i.e.
1 %...5 %.
Read: RV17 returns the compression factor.
Compression reduces the number of periods that have to be
transferred per channel. Assuming the 12 points of a period deviate by
less than the specified compression factor from the corresponding
points of the preceding period, the points themselves are not
transferred, but simply the number of repeats in relation to the
preceding period. For example, if a record consists of 100 periods all
the same, then only the 12 points of one period and the number of
repeats are transferred. Compression is applied independently for
each individual channel.
M28:
Write: WM28:n selects a disturbance recorder record for
transfer. n has a value between 1 and the number of
records that that can be read using RV20. The
conversion of the record to the EVE format starts and
the first response is NAK. WM28:n has to be repeated
until the response is ACK. (From firmware V4.0.)
Read: RM28 returns the directory information, time stamp and
record number.
1995-05-10 12.34;23.423 RE001.001
9-7
ABB Switzerland Ltd RE.216 1KHA000951-UEN
M29:
Write: NAK
Read: returns the number of lines in a record (0...1023). A line
contains 26 Byte of data. 0 is returned if a record has
not been selected (M28).
M30:
Write: WM30:n moves the pointer to the line to be transferred.
The pointer is automatically incremented by one every
time a line is transferred until there are no lines left. The
pointer is set to 1 at the commencement of data transfer
(WM28:n).
Read: RM30 returns the number of the line that was
transferred last.
M31:
Write: NAK
Read: RM31 transfers the line indicated by the pointer.
V16:
Write: WV16:1, WV16:0, deletes the oldest record.
Read: RV16 returns the status of the disturbance recorder.
0: Disturbance recorder not full.
1: Disturbance recorder full.
V20:
Write: WV20:0 terminates data transfer.
9-8
RE.216 1KHA000951-UEN ABB Switzerland Ltd
9-9
ABB Switzerland Ltd RE.216 1KHA000951-UEN
The table below shows the channel number mapping for a typical
configuration:
9-10
RE.216 1KHA000951-UEN ABB Switzerland Ltd
9-11
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9-12
RE.216 1KHA000951-UEN ABB Switzerland Ltd
9-13
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9-14
RE.216 1KHA000951-UEN ABB Switzerland Ltd
9-15
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9-16
RE.216 1KHA000951-UEN ABB Switzerland Ltd
9-17
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9-18
RE.216 1KHA000951-UEN ABB Switzerland Ltd
9-19
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9-20
RE.216 1KHA000951-UEN ABB Switzerland Ltd
9-21
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9.6.13. Hardware 35
RE.216 unit addresses and codes
9-22
RE.216 1KHA000951-UEN ABB Switzerland Ltd
9-23
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Measured variables
Function 9 (IBB I/O) makes measured variables available the number
and significance of which depend on the device configuration. The
number of measured variables is limited to 64.
9-24
RE.216 1KHA000951-UEN ABB Switzerland Ltd
9.6.16. Current-DT 2
Basic channel No.: 14
Summary of parameters:
Measured variables
Tripping levels
Event list
9-25
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9.6.17. Current 3
Basic channel No.: 14
Summary of parameters:
Measured variables
Tripping levels
Event list
9-26
RE.216 1KHA000951-UEN ABB Switzerland Ltd
9.6.18. Diff-Transf 4
Basic channel No.: 14
Summary of parameters:
9-27
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9-28
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Measured variables
Tripping levels
Event list
9-29
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9.6.19. Underimped 5
Basic channel No.: 14
Summary of parameters:
Measured variables
Tripping levels
9-30
RE.216 1KHA000951-UEN ABB Switzerland Ltd
9.6.20. MinReactance 6
Basic channel No.: 14
Summary of parameters:
Measured variables
Tripping levels
Event list
9-31
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9.6.21. NPS-DT 7
Basic channel No.: 14
Summary of parameters:
Measured variables
Tripping levels
Event list
9-32
RE.216 1KHA000951-UEN ABB Switzerland Ltd
9.6.22. NPS-Inv 11
Basic channel No.: 14
Summary of parameters:
Measured variables
Tripping levels
Event list
9-33
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9.6.23. Voltage 12
Basic channel No.: 14
Summary of parameters:
Measured variables
Tripping levels
Event list
9-34
RE.216 1KHA000951-UEN ABB Switzerland Ltd
9.6.24. Current-Inv 13
Basic channel No.: 14
Summary of parameters:
Measured variables
Tripping levels
9-35
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Event list
9-36
RE.216 1KHA000951-UEN ABB Switzerland Ltd
9.6.25. OLoad-Stator 14
Basic channel No.: 14
Summary of parameters:
9-37
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9.6.26. OLoad-Rotor 15
Basic channel No.: 14
Summary of parameters:
Measured variables
Tripping levels
Event list
9-38
RE.216 1KHA000951-UEN ABB Switzerland Ltd
9.6.27. Power 18
Basic channel No.: 14
Summary of parameters:
Measured variables
Address Access Text Dec.
14V1 R PN 3
Tripping levels
Address Access Text Dec.
14Q1 R PN 3
9-39
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Event list
Event No. Cause Event mask Enable code Status
14E1 Trip Set V155 1 14I1
14E2 Dito Reset V155 2
14E3 Start Set V155 4 14I2
14E4 Dito Reset V155 8
9-40
RE.216 1KHA000951-UEN ABB Switzerland Ltd
9.6.28. Imax-Umin 20
Basic channel No.: 14
Summary of parameters:
Measured variables
Tripping levels
Event list
Event No. Cause Event mask Enable code Status
14E1 Trip Set V155 1 14I1
14E2 Dito Reset V155 2
14E3 Start Set V155 4 14I2
14E4 Dito Reset V155 8
9-41
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9.6.29. Delay 22
Basic channel No.: 14
Summary of parameters:
Measured variables
Tripping levels
Event list
C E
14E1 Trip Set V155 1 14I1
14E2 Dito Reset V155 2
14E3 Start Set V155 4 14I2
14E4 Dito Reset V155 8
9-42
RE.216 1KHA000951-UEN ABB Switzerland Ltd
9.6.30. Diff-Gen 23
Basic channel No.: 14
Summary of parameters:
Measured variables
Address Access Text Dec.
14V1 R IN (Id-R) 2
14V2 R IN (Id-S) 2
14V3 R IN (Id-T) 2
Tripping levels
Address Access Text Dec.
14Q1 R IN (Id-R) 2
14Q2 R IN (Id-S) 2
14Q3 R IN (Id-T) 2
Event list
Event No. Cause Event mask Enable code Status
14E1 Trip-R Set V155 1 14I1
14E2 Dito Reset V155 2
14E3 Trip-S Set V155 4 14I2
14E4 Dito Reset V155 8
14E5 Trip-T Set V155 16 14I3
14E6 Dito Reset V155 32
14E7 Trip Set V155 64 14I4
14E8 Dito Reset V155 128
9-43
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9.6.31. Distance 24
Basic channel No.: 14
Summary of parameters:
The starter and measurement settings (in columns Min., Max. and
Step) with the unit 'ohms/phase' have to be divided by 10 for relays
with a rated current of 5 A.
9-44
RE.216 1KHA000951-UEN ABB Switzerland Ltd
9-45
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9-46
RE.216 1KHA000951-UEN ABB Switzerland Ltd
9-47
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9-48
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Measured variables
Tripping levels
9-49
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Note:
A tripping value will only be overwritten (e.g. Z(RS)) if the same loop
(RS) trips again.
The Real and Imaginary values of the loop impedance are transmitted
on successive addresses.
The 'distance to the fault' is as derived from the last trip signal.
The correct distance to fault value is furnished only if the parameter
'Ref Length' is correctly configured.
Event list
9-50
RE.216 1KHA000951-UEN ABB Switzerland Ltd
9-51
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9-52
RE.216 1KHA000951-UEN ABB Switzerland Ltd
9-53
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9.6.32. Frequency 25
Basic channel No.: 14
Summary of parameters:
Measured variables
Tripping levels
Event list
9-54
RE.216 1KHA000951-UEN ABB Switzerland Ltd
9.6.33. Overexcitat 26
Basic channel No.: 14
Summary of parameters:
Measured variables
Tripping levels
Event list
9-55
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9.6.34. Count 27
Basic channel No.: 14
Summary of parameters:
Measured variables
Tripping levels
Event list
9-56
RE.216 1KHA000951-UEN ABB Switzerland Ltd
9.6.35. Overtemp. 28
Basic channel No.: 14
Summary of parameters:
9-57
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Measured variables
9-58
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Tripping levels
Event list
9-59
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9.6.36. Check-I3ph 29
Basic channel No.: 14
Summary of parameters:
Measured variables
Tripping levels
Event list
9-60
RE.216 1KHA000951-UEN ABB Switzerland Ltd
9.6.37. Check-U3ph 30
Basic channel No.: 14
Summary of parameters:
Measured variables
Tripping levels
Event list
9-61
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9.6.38. Logic 31
Basic channel No.: 14
Summary of parameters:
Event list
9-62
RE.216 1KHA000951-UEN ABB Switzerland Ltd
9-63
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9-64
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Event list
9-65
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9.6.40. Voltage-Inst 36
Basic channel No.: 14
Summary of parameters:
Measured variables
Tripping levels
Event list
9-66
RE.216 1KHA000951-UEN ABB Switzerland Ltd
9.6.41. Autoreclosure 38
Basic channel No.: 14
Summary of parameters:
9-67
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9-68
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Event list
9-69
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9-70
RE.216 1KHA000951-UEN ABB Switzerland Ltd
9.6.42. EarthFaultIsol 40
Basic channel No.: 14
Summary of parameters:
Measured variables
Tripping levels
Event list
9-71
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9.6.43. Voltage-Bal 41
Basic channel No.: 14
Summary of parameters:
Measured variables
Tripping levels
9-72
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Event list
9-73
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9.6.44. U/f-Inv 47
Basic channel No.: 14
Summary of parameters:
Measured variables
9-74
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Tripping levels
Event list
9-75
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9.6.45. UIfPQ 48
Basic channel No.: 14
Summary of parameters:
Measured variables
9-76
RE.216 1KHA000951-UEN ABB Switzerland Ltd
9.6.46. SynchroCheck 49
Basic channel No.: 14
Summary of parameters:
9-77
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Measured variables
Tripping levels
9-78
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Event list
9-79
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9.6.47. Rotor-EFP 51
Basic channel No.: 14
Summary of parameters:
Measured variables
Tripping levels
9-80
RE.216 1KHA000951-UEN ABB Switzerland Ltd
9-81
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9.6.48. Stator-EFP 52
Basic channel No.: 14
Summary of parameters:
Measured variables
Tripping levels
9-82
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Event list
9-83
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9.6.49. I0-Invers 53
Basic channel No.: 14
Summary of parameters:
Measured variables
Tripping levels
9-84
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Event list
9-85
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9.6.50. Pole-Slip 55
Basic channel No.: 14
Summary of parameters:
Measured variables
Tripping levels
9-86
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Event list
9-87
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9.6.51. EarthFltGnd2 58
Basic channel No.: 14
Summary of parameters:
9-88
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Measured variables
Event list
9-89
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9.6.52. FUPLA 59
Basic channel No.: 14
Summary of parameters:
Measured variables
The number of FUPLA measured variables depends on the con-
figuration. Within this total configured, the order of the FUPLA
measured variables measured variable numbers can be determined by
assigning numbers to them.
Events
FUPLA events can only be configured as IBB events. Events are not
recorded under the FUPLA function number. Because of the variable
number of signals/events, FUPLA would require a variable number of
channels.
IBB events
FUPLA ‘Extout’ to IBB channel and ER:
Events are recorded under their SPA address, IBB group and event
number,
Addr 121 E1 .
Binary signals are assigned to IBB channels using the HMI. It is not
possible to mask IBB events.
9-90
RE.216 1KHA000951-UEN ABB Switzerland Ltd
9.6.53. Defluttering 60
Basic channel No.: 14
Summary of parameters:
Event list
9-91
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9.6.54. HV distance 63
Basic channel No.: 14
Summary of parameters:
The starter and measurement settings (in columns Min., Max. and
Step) with the unit 'ohms/phase' have to be divided by 10 for relays
with a rated current of 5 A.
9-92
RE.216 1KHA000951-UEN ABB Switzerland Ltd
9-93
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9-94
RE.216 1KHA000951-UEN ABB Switzerland Ltd
9-95
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9-96
RE.216 1KHA000951-UEN ABB Switzerland Ltd
Measured variables
Tripping levels
Note:
A tripping value will only be overwritten (e.g. Z(RS)) if the same loop
(RS) trips again.
The real and imaginary values of the loop impedance are transmitted
on successive addresses.
The 'distance to the fault' is as derived from the last trip signal.
The correct distance to fault value is furnished only if the parameter
'Ref Length' is correctly configured.
9-97
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Event list
9-98
RE.216 1KHA000951-UEN ABB Switzerland Ltd
9-99
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9-100
RE.216 1KHA000951-UEN ABB Switzerland Ltd
9-101
ABB Switzerland Ltd RE.216 1KHA000951-UEN
9.6.55. df/dt 69
Basic channel No.: 14
Summary of parameters:
Measured variables
Tripping levels
Event list
9-102
RE.216 1KHA000951-UEN ABB Switzerland Ltd
9.6.56. DirCurrentDT 70
Basic channel No.: 14
Summery of parameters:
Measured variables
9-103
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Tripping levels
Event list
9-104
RE.216 1KHA000951-UEN ABB Switzerland Ltd
9.6.57. DirCurrentInv 71
Basic channel No.: 14
Summery of parameters:
Measured variables
9-105
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Tripping levels
Event list
9-106
RE.216 1KHA000951-UEN ABB Switzerland Ltd
9.6.58. BreakerFailure 72
Basic channel No.: 14
Summery of parameters:
CPU 1 1
CPU 2 2
9-107
ABB Switzerland Ltd RE.216 1KHA000951-UEN
off 0
on 1
off 0
on 1
off 0
on 1
off 0
on 1
9-108
RE.216 1KHA000951-UEN ABB Switzerland Ltd
off 0
on 1
off 0
on 1
t2
t1 1
9-109
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Event list
9-110
RE.216 1KHA000951-UEN ABB Switzerland Ltd
9.6.59. MeasureModule 74
Parameter summary:
9-111
ABB Switzerland Ltd RE.216 1KHA000951-UEN
Measured variables
Tripping levels
Event list
9-112
RE.216 1KHA000951-UEN ABB Switzerland Ltd
August 05
10-1
ABB Switzerland Ltd RE.216 1KHA000951-UEN
10-2
RE.216 1KHA000951-UEN ABB Switzerland Ltd
10-3
ABB Switzerland Ltd RE.216 1KHA000951-UEN
10-4
RE.216 1KHA000951-UEN ABB Switzerland Ltd
August 05
12. APPENDIX
12-1
ABB Switzerland Ltd RE.216 1KHA000951-UEN
12-2
RE.216 1KHA000951-UEN ABB Switzerland Ltd
12-3
ABB Switzerland Ltd RE.216 1KHA000951-UEN
12-4
RE.216 1KHA000951-UEN ABB Switzerland Ltd
12-5
ABB Switzerland Ltd RE.216 1KHA000951-UEN
12-6
RE.216 1KHA000951-UEN ABB Switzerland Ltd
12-7
CHECKLIST GENERATOR PROTECTION
STATION: UNIT:
94-04
Type of protection
Cubicle/relay number
Check of signalisation/alarms
Primary tests
Final check
Client
Date: Signature: Date: Signature:
TEST SHEET
STATION: UNIT:
96-09
Generator protection type REG216
Generator datas:
Settings: According to separate print out Software version of the relay ...............
Remark: If the AD channel reference value is not 1.0 it is advisable to inject rated value * ref. value to get on
the display 1.000 UN/IN.
Example: Rated current generator = 540 A, CT ratio = 600/5 ---> Ref. value = 0.9
Injected current = 5 * 0.9 A = 4.5 A ---> Display = 1.000 IN
Client
Date: Signature: Date: Signature:
1 2 3 4 5 6 7 8
B B
D D
E E
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Cover page Ref. des.
F
Approved 05-10-25 Winterhalder Title page DCC
Print: 25.10.2005
Red.
ZP
ZP
UB+
01 Power supply ok
01z04
01z08
01z12
01z16
01z20
01z24
01z28
01z32
-X20
02
B B
01d06
01d10
01d14
01d18
01d22
01d26
01d30
ZB
03
UP
UP
216GW62
Code K-
04
05
06
07
08 08a 08b
C C
09 09a 09b
10 10a 10b
11 11a 11b
12 12a 12b
13 13a 13b
14 14a 14b
D 15 15a 15b D
16 16a 16b
17 17a 17b
18 18a 18b
-X1 -
01
Red.
+
ZP
ZP
UB+
19 -X2 02
19z04
19z08
19z12
19z16
19z20
19z24
19z28
19z32
216GD61a 03 -
-X3 Code I- +
20 04
19d06
19d10
19d14
19d18
19d22
19d26
19d30
21
UP
UP
+
Redundant power supply ok
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Connection diagram of devices DCC
Print: 25.10.2005
Project Var. M1 (single system, 1 rack) Resp. dept. PTUSE Rev. ind. Language en
Sheet C11
Rev. Revision note Date Name ABB ABB Switzerland Ltd.
Doc. no. 1KHF309592 n. sheet C21
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Red.
ZP
ZP
UB+
01 Power supply ok
01z04
01z08
01z12
01z16
01z20
01z24
01z28
01z32
-X20
02
B B
01d06
01d10
01d14
01d18
01d22
01d26
01d30
ZB
03
UP
UP
216GW62
Code K-
04 -X20
05
216GW62
Code L-
06
07
08 08a 08b
C C
09 09a 09b
10 10a 10b
11 11a 11b
12 12a 12b
13 13a 13b
14 14a 14b
D 15 15a 15b D
+
ZP
ZP
UB+
19 -X2 02
19z04
19z08
19z12
19z16
19z20
19z24
19z28
19z32
216GD61a 03 -
-X3 Code I +
20 04
19d06
19d10
19d14
19d18
19d22
19d26
19d30
21
UP
UP
+
Redundant power supply ok
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Connection diagram of devices DCC
Print: 25.10.2005
Project Var. M2 (single system, 1 rack) Resp. dept. PTUSE Rev. ind. Language en
Sheet C21
Rev. Revision note Date Name ABB ABB Switzerland Ltd.
Doc. no. 1KHF309592 n. sheet C31
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Red.
ZP
ZP
UB+
01 Power supply ok
01z04
01z08
01z12
01z16
01z20
01z24
01z28
01z32
-X20
02
B B
01d06
01d10
01d14
01d18
01d22
01d26
01d30
ZB
03
UP
UP
216GW62
Code: K
04 -X20
05
216GW62
Code: L-
06
07
08 08a 08b
C C
09 09a 09b
10 10a 10b
11 11a 11b
12 12a 12b
13 13a 13b
14 14a 14b
D 15 15a 15b D
16 16a 16b
17 17a 17b
18 18a 18b
-X1 -
01
Red.
+
ZP
ZP
UB+
19 -X2 02
19z04
19z08
19z12
19z16
19z20
19z24
19z28
19z32
216GD61a 03 -
-X3 Code I +
20 04
19d06
19d10
19d14
19d18
19d22
19d26
19d30
21
UP
UP
+
Redundant power supply ok
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Connection diagram of devices DCC
Print: 25.10.2005
Project Var. M3 (single system, 1 rack) Resp. dept. PTUSE Rev. ind. Language en
Sheet C31
Rev. Revision note Date Name ABB ABB Switzerland Ltd.
Doc. no. 1KHF309592 n. sheet C41
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Red.
ZP
ZP
UB+
01 Power supply ok
01z04
01z08
01z12
01z16
01z20
01z24
01z28
01z32
-X20
02
B B
01d06
01d10
01d14
01d18
01d22
01d26
01d30
ZB
03
UP
UP
216GW62
Code: K-
04
05
06
07
08 08a 08b
C C
09 09a 09b
10 10a 10b
11 11a 11b
12 12a 12b
13 13a 13b
14 14a 14b
D 15 15a 15b D
+
ZP
ZP
UB+
19 -X2 02
19z04
19z08
19z12
19z16
19z20
19z24
19z28
19z32
216GD61a 03 -
-X3 Code I +
20 04
19d06
19d10
19d14
19d18
19d22
19d26
19d30
21
UP
UP
+
Redundant power supply ok
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Connection diagram of devices DCC
Print: 25.10.2005
Project Var. M4 (single system, 1 rack) Resp. dept. PTUSE Rev. ind. Language en
Sheet C41
Rev. Revision note Date Name ABB ABB Switzerland Ltd.
Doc. no. 1KHF309592 n. sheet C51
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Red.
ZP
ZP
UB+
01 Power supply ok
01z04
01z08
01z12
01z16
01z20
01z24
01z28
01z32
-X20
02
B B
01d06
01d10
01d14
01d18
01d22
01d26
01d30
ZB
03
UP
UP
216GW62
Code: K-
04 -X20
05
216GW62
Code: L-
06
-X20
07
216GW62
08 08a 08b Code: N-
C C
09 09a 09b
10 10a 10b
11 11a 11b
12 12a 12b
13 13a 13b
14 14a 14b
D 15 15a 15b D
+
ZP
ZP
UB+
19 -X2 02
19z04
19z08
19z12
19z16
19z20
19z24
19z28
19z32
216GD61a 03 -
-X3 Code I +
20 04
19d06
19d10
19d14
19d18
19d22
19d26
19d30
21
UP
UP
+
Redundant power supply ok
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Connection diagram of devices DCC
Print: 25.10.2005
Project Var. M5 (single system, 1 rack) Resp. dept. PTUSE Rev. ind. Language en
Sheet C51
Rev. Revision note Date Name ABB ABB Switzerland Ltd.
Doc. no. 1KHF309592 n. sheet C61
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Red.
ZP
ZP
UB+
01 Power supply ok
01z04
01z08
01z12
01z16
01z20
01z24
01z28
01z32
-X20
02
B B
01d06
01d10
01d14
01d18
01d22
01d26
01d30
ZB
03
UP
UP
216GW62
Code: K-
04 -X20
05
216GW62
Code: L-
06
-X20
07
216GW62
08 08a 08b Code: N-
C -X20 C
09 09a 09b
216GW62
10 10a 10b Code: O-
11 11a 11b
12 12a 12b
13 13a 13b
14 14a 14b
D 15 15a 15b D
+
ZP
ZP
UB+
19 -X2 02
19z04
19z08
19z12
19z16
19z20
19z24
19z28
19z32
216GD61a 03 -
-X3 Code I +
20 04
19d06
19d10
19d14
19d18
19d22
19d26
19d30
21
UP
UP
+
Redundant power supply ok
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Connection diagram of devices DCC
Print: 25.10.2005
Project Var. M6 (single system, 1 rack) Resp. dept. PTUSE Rev. ind. Language en
Sheet C61
Rev. Revision note Date Name ABB ABB Switzerland Ltd.
Doc. no. 1KHF309592 n. sheet C111
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Red.
ZP
ZP
UB+
01 Power supply ok
01z04
01z08
01z12
01z16
01z20
01z24
01z28
01z32
-X20
02
B B
01d06
01d10
01d14
01d18
01d22
01d26
01d30
ZB
03
UP
UP
216GW62
-X21 Code: K-
04 -X20
05
216GW62
-X21 Code: L-
06 06a 06b
07 07a 07b
08 08a 08b
C C
09 09a 09b
10 10a 10b
11 11a 11b
12
13
14 14a 14b
D 15 15a 15b D
+
ZP
ZP
UB+
19 -X2 02
19z04
19z08
19z12
19z16
19z20
19z24
19z28
19z32
216GD61a 03 -
-X3 Code I +
20 04
19d06
19d10
19d14
19d18
19d22
19d26
19d30
21
UP
UP
+
Power supply ok
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
+ Power supply
- Code E-
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Connection diagram of devices DCC
Print: 25.10.2005
Project Var. M11 (red. system, 1 rack) A&B Resp. dept. PTUSE Rev. ind. Language en
Sheet C111
Rev. Revision note Date Name ABB ABB Switzerland Ltd.
Doc. no. 1KHF309592 n. sheet C121
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Red.
ZP
ZP
UB+
01 Power supply ok
01z04
01z08
01z12
01z16
01z20
01z24
01z28
01z32
-X20
02
B B
01d06
01d10
01d14
01d18
01d22
01d26
01d30
ZB
03
UP
UP
216GW62
-X21 Code: K-
04 -X20
05
216GW62
-X21 Code: L-
06 06a 06b
07 07a 07b
08 08a 08b
C C
09 09a 09b
10 10a 10b
11 11a 11b
-X1 -
01
12 +
-X2 02
216GD61a 03 -
13 -X3 Code I +
04
-X1 -
14 14a 14b 01
-X2 02 +
D 15 15a 15b 216GD61a 03 - D
-X3 Code I +
04
16 16a 16b -X1 -
01
-X2 02 +
17 17a 17b -
216GD61a 03
-X3 Code I +
04
18 18a 18b
-X1 -
01
Red.
+
ZP
ZP
UB+
19 -X2 02
19z04
19z08
19z12
19z16
19z20
19z24
19z28
19z32
216GD61a 03 -
-X3 Code I +
20 04
19d06
19d10
19d14
19d18
19d22
19d26
19d30
21
UP
UP
+
Power supply ok
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
+ Power supply
- Code E-
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Connection diagram of devices DCC
Print: 25.10.2005
Project Var. M12 (red. system, 1 rack) A&B Resp. dept. PTUSE Rev. ind. Language en
Sheet C121
Rev. Revision note Date Name ABB ABB Switzerland Ltd.
Doc. no. 1KHF309592 n. sheet C131
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Red.
ZP
ZP
UB+
01 Power supply ok
01z04
01z08
01z12
01z16
01z20
01z24
01z28
01z32
-X20
02
B B
01d06
01d10
01d14
01d18
01d22
01d26
01d30
ZB
03
UP
UP
216GW62
Code: K-
04 -X20
05
216GW62
-X21 Code: L-
06 06a 06b
-X20
07 07a 07b
216GW62
08 08a 08b Code: N-
C C
09 09a 09b
10 10a 10b
11 11a 11b
12
13
14 14a 14b
D 15 15a 15b D
+
ZP
ZP
UB+
19 -X2 02
19z04
19z08
19z12
19z16
19z20
19z24
19z28
19z32
216GD61a 03 -
-X3 Code I +
20 04
19d06
19d10
19d14
19d18
19d22
19d26
19d30
21
UP
UP
+
Power supply ok
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
+ Power supply
- Code E-
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Connection diagram of devices DCC
Print: 25.10.2005
Project Var. M13 (red. system, 1 rack) A&B Resp. dept. PTUSE Rev. ind. Language en
Sheet C131
Rev. Revision note Date Name ABB ABB Switzerland Ltd.
Doc. no. 1KHF309592 n. sheet C141
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Red.
ZP
ZP
UB+
01 Power supply ok
01z04
01z08
01z12
01z16
01z20
01z24
01z28
01z32
-X20
02
B B
01d06
01d10
01d14
01d18
01d22
01d26
01d30
ZB
03
UP
UP
216GW62
Code: K-
04 -X20
05
216GW62
-X21 Code: L-
06 06a 06b
-X20
07 07a 07b
216GW62
08 08a 08b Code: N-
C C
09 09a 09b
10 10a 10b
11 11a 11b
-X1 -
01
12 +
-X2 02
216GD61a 03 -
13 -X3 Code I +
04
-X1 -
14 14a 14b 01
-X2 02 +
D 15 15a 15b 216GD61a 03 - D
-X3 Code I +
04
16 16a 16b -X1 -
01
-X2 02 +
17 17a 17b -
216GD61a 03
-X3 Code I +
04
18 18a 18b
-X1 -
01
Red.
+
ZP
ZP
UB+
19 -X2 02
19z04
19z08
19z12
19z16
19z20
19z24
19z28
19z32
216GD61a 03 -
-X3 Code I +
20 04
19d06
19d10
19d14
19d18
19d22
19d26
19d30
21
UP
UP
+
Power supply ok
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
+ Power supply
- Code E-
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Connection diagram of devices DCC
Print: 25.10.2005
Project Var. M14 (red. system, 1 rack) A&B Resp. dept. PTUSE Rev. ind. Language en
Sheet C141
Rev. Revision note Date Name ABB ABB Switzerland Ltd.
Doc. no. 1KHF309592 n. sheet C151
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Red.
ZP
ZP
UB+
01 Power supply ok
01z04
01z08
01z12
01z16
01z20
01z24
01z28
01z32
-X20
02
B B
01d06
01d10
01d14
01d18
01d22
01d26
01d30
ZB
03
UP
UP
216GW62
Code: K-
04 -X20
05
216GW62
Code: L-
06 06a 06b
-X20
07 07a 07b
216GW62
08 08a 08b Code: N-
C -X20 C
09 09a 09b
216GW62
10 10a 10b Code: O-
11 11a 11b
12
13
14 14a 14b
D 15 15a 15b D
+
ZP
ZP
UB+
19 -X2 02
19z04
19z08
19z12
19z16
19z20
19z24
19z28
19z32
216GD61a 03 -
-X3 Code I +
20 04
19d06
19d10
19d14
19d18
19d22
19d26
19d30
21
UP
UP
+
Power supply ok
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
+ Power supply
- Code E-
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Connection diagram of devices DCC
Print: 25.10.2005
Project Var. M15 (red. system, 1 rack) A&B Resp. dept. PTUSE Rev. ind. Language en
Sheet C151
Rev. Revision note Date Name ABB ABB Switzerland Ltd.
Doc. no. 1KHF309592 n. sheet C161
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Red.
ZP
ZP
UB+
01 Power supply ok
01z04
01z08
01z12
01z16
01z20
01z24
01z28
01z32
-X20
02
B B
01d06
01d10
01d14
01d18
01d22
01d26
01d30
ZB
03
UP
UP
216GW62
Code: K-
04 -X20
05
216GW62
Code: L-
06 06a 06b
-X20
07 07a 07b
216GW62
08 08a 08b Code: N-
C -X20 C
09 09a 09b
216GW62
10 10a 10b Code: O-
11 11a 11b
-X1 -
01
12 +
-X2 02
216GD61a 03 -
13 -X3 Code I +
04
-X1 -
14 14a 14b 01
-X2 02 +
D 15 15a 15b 216GD61a 03 - D
-X3 Code I +
04
16 16a 16b -X1 -
01
-X2 02 +
17 17a 17b -
216GD61a 03
-X3 Code I +
04
18 18a 18b
-X1 -
01
Red.
+
ZP
ZP
UB+
19 -X2 02
19z04
19z08
19z12
19z16
19z20
19z24
19z28
19z32
216GD61a 03 -
-X3 Code I +
20 04
19d06
19d10
19d14
19d18
19d22
19d26
19d30
21
UP
UP
+
Power supply ok
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
+ Power supply
- Code E-
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Connection diagram of devices DCC
Print: 25.10.2005
Project Var. M16 (red. system, 1 rack) A&B Resp. dept. PTUSE Rev. ind. Language en
Sheet C161
Rev. Revision note Date Name ABB ABB Switzerland Ltd.
Doc. no. 1KHF309592 n. sheet C211
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Red.
ZP
ZP
UB+
01 Power supply ok
01z04
01z08
01z12
01z16
01z20
01z24
01z28
01z32
-X20
02
B B
01d06
01d10
01d14
01d18
01d22
01d26
01d30
ZB
03
UP
UP
216GW62
Code: K-
04 -X20
05
216GW62
I31 -X21 Code: L-
/C212.B5
06
07
08 08a 08b
C C
09 09a 09b
10 10a 10b
11 11a 11b
12 12a 12b
13 13a 13b
14 14a 14b
D 15 15a 15b D
+
ZP
ZP
UB+
19 -X2 02
19z04
19z08
19z12
19z16
19z20
19z24
19z28
19z32
216GD61a 03 -
-X3 Code I +
20 04
19d06
19d10
19d14
19d18
19d22
19d26
19d30
21
UP
UP
+
Redundant power supply ok
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Connection diagram of devices DCC
Print: 25.10.2005
Project Var. M21 (double system, 2 racks) A Resp. dept. PTUSE Rev. ind. Language en
Sheet C211
Rev. Revision note Date Name ABB ABB Switzerland Ltd.
Doc. no. 1KHF309592 n. sheet C212
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Red.
ZP
ZP
UB+
01 Power supply ok
01z04
01z08
01z12
01z16
01z20
01z24
01z28
01z32
-X20
02
B B
01d06
01d10
01d14
01d18
01d22
01d26
01d30
ZB
03
UP
UP
216GW62
Code: N-
04 I31
/C211.C5
05
06
07
08 08a 08b
C C
09 09a 09b
10 10a 10b
11 11a 11b
12 12a 12b
13 13a 13b
14 14a 14b
D 15 15a 15b D
+
ZP
ZP
UB+
19 -X2 02
19z04
19z08
19z12
19z16
19z20
19z24
19z28
19z32
216GD61a 03 -
-X3 Code I +
20 04
19d06
19d10
19d14
19d18
19d22
19d26
19d30
21
UP
UP
+
Redundant power supply ok
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Connection diagram of devices DCC
Print: 25.10.2005
Project Var. M21 (double system, 2 racks) B Resp. dept. PTUSE Rev. ind. Language en
Sheet C212
Rev. Revision note Date Name ABB ABB Switzerland Ltd.
Doc. no. 1KHF309592 n. sheet C221
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Red.
ZP
ZP
UB+
01 Power supply ok
01z04
01z08
01z12
01z16
01z20
01z24
01z28
01z32
-X20
02
B B
01d06
01d10
01d14
01d18
01d22
01d26
01d30
ZB
03
UP
UP
216GW62
Code: K-
04 -X20
05
216GW62
I31 -X21 Code: L-
/C222.B5
06
-X20
07
216GW62
I32 -X21 Code: N-
08 08a 08b /C222.C5
C C
09 09a 09b
10 10a 10b
11 11a 11b
12 12a 12b
13 13a 13b
14 14a 14b
D 15 15a 15b D
+
ZP
ZP
UB+
19 -X2 02
19z04
19z08
19z12
19z16
19z20
19z24
19z28
19z32
216GD61a 03 -
-X3 Code I +
20 04
19d06
19d10
19d14
19d18
19d22
19d26
19d30
21
UP
UP
+
Redundant power supply ok
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Connection diagram of devices DCC
Print: 25.10.2005
Project Var. M22 (double system, 2 racks) A Resp. dept. PTUSE Rev. ind. Language en
Sheet C221
Rev. Revision note Date Name ABB ABB Switzerland Ltd.
Doc. no. 1KHF309592 n. sheet C222
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Red.
ZP
ZP
UB+
01 Power supply ok
01z04
01z08
01z12
01z16
01z20
01z24
01z28
01z32
-X20
02
B B
01d06
01d10
01d14
01d18
01d22
01d26
01d30
ZB
03
UP
UP
216GW62
Code: O-
04 I31
/C221.C5
05
06
I32
/C221.C5
07
08 08a 08b
C C
09 09a 09b
10 10a 10b
11 11a 11b
12 12a 12b
13 13a 13b
14 14a 14b
D 15 15a 15b D
+
ZP
ZP
UB+
19 -X2 02
19z04
19z08
19z12
19z16
19z20
19z24
19z28
19z32
216GD61a 03 -
-X3 Code I +
20 04
19d06
19d10
19d14
19d18
19d22
19d26
19d30
21
UP
UP
+
Redundant power supply ok
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Connection diagram of devices DCC
Print: 25.10.2005
Project Var. M22 (double system, 2 racks) B Resp. dept. PTUSE Rev. ind. Language en
Sheet C222
Rev. Revision note Date Name ABB ABB Switzerland Ltd.
Doc. no. 1KHF309592 n. sheet C231
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Red.
ZP
ZP
UB+
01 Power supply ok
01z04
01z08
01z12
01z16
01z20
01z24
01z28
01z32
-X20
02
B B
01d06
01d10
01d14
01d18
01d22
01d26
01d30
ZB
03
UP
UP
216GW62
I31 -X21 Code: K-
/C232.B5
04 -X20
05
216GW62
I32 -X21 Code: L-
/C232.B5
06
-X20
07
216GW62
I33 -X21 Code: N-
08 08a 08b /C232.C5
C -X20 C
09 09a 09b
216GW62
10 10a 10b I34 -X21 Code: O-
/C232.C5
11 11a 11b
12 12a 12b
13 13a 13b
14 14a 14b
D 15 15a 15b D
+
ZP
ZP
UB+
19 -X2 02
19z04
19z08
19z12
19z16
19z20
19z24
19z28
19z32
216GD61a 03 -
-X3 Code I +
20 04
19d06
19d10
19d14
19d18
19d22
19d26
19d30
21
UP
UP
+
Redundant power supply ok
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Connection diagram of devices DCC
Print: 25.10.2005
Project Var. M23 (double system, 2 racks) A Resp. dept. PTUSE Rev. ind. Language en
Sheet C231
Rev. Revision note Date Name ABB ABB Switzerland Ltd.
Doc. no. 1KHF309592 n. sheet C232
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Red.
ZP
ZP
UB+
01 Power supply ok
01z04
01z08
01z12
01z16
01z20
01z24
01z28
01z32
I31
02 /C231.B5
B B
01d06
01d10
01d14
01d18
01d22
01d26
01d30
ZB
03
UP
UP
04 I32
/C231.C5
05
06
I33
/C231.C5
07
08 08a 08b
C I34
/C231.C5 C
09 09a 09b
10 10a 10b
11 11a 11b
12 12a 12b
13 13a 13b
14 14a 14b
D 15 15a 15b D
+
ZP
ZP
UB+
19 -X2 02
19z04
19z08
19z12
19z16
19z20
19z24
19z28
19z32
216GD61a 03 -
-X3 Code I +
20 04
19d06
19d10
19d14
19d18
19d22
19d26
19d30
21
UP
UP
+
Redundant power supply ok
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Connection diagram of devices DCC
Print: 25.10.2005
Project Var. M23 (double system, 2 racks) B Resp. dept. PTUSE Rev. ind. Language en
Sheet C232
Rev. Revision note Date Name ABB ABB Switzerland Ltd.
Doc. no. 1KHF309592 n. sheet C241
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Red.
ZP
ZP
UB+
01 Power supply ok
01z04
01z08
01z12
01z16
01z20
01z24
01z28
01z32
-X20
02
B B
01d06
01d10
01d14
01d18
01d22
01d26
01d30
ZB
03
UP
UP
216GW62
Code: K-
04 -X20
05
216GW62
I31 -X21 Code: L-
/C242.B5
06
-X20
07
216GW62
I32 -X21 Code: N-
08 08a 08b /C242.C5
C -X20 C
09 09a 09b
216GW62
10 10a 10b I33 -X21 Code: O-
/C242.C5
11 11a 11b
12 12a 12b
13 13a 13b
14 14a 14b
D 15 15a 15b D
+
ZP
ZP
UB+
19 -X2 02
19z04
19z08
19z12
19z16
19z20
19z24
19z28
19z32
216GD61a 03 -
-X3 Code I +
20 04
19d06
19d10
19d14
19d18
19d22
19d26
19d30
21
UP
UP
+
Redundant power supply ok
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Connection diagram of devices DCC
Print: 25.10.2005
Project Var. M24 (double system, 2 racks) A Resp. dept. PTUSE Rev. ind. Language en
Sheet C241
Rev. Revision note Date Name ABB ABB Switzerland Ltd.
Doc. no. 1KHF309592 n. sheet C242
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Red.
ZP
ZP
UB+
01 Power supply ok
01z04
01z08
01z12
01z16
01z20
01z24
01z28
01z32
-X20
02
B B
01d06
01d10
01d14
01d18
01d22
01d26
01d30
ZB
03
UP
UP
216GW62
Code: P-
04 I31
/C241.C5
05
06
I32
/C241.C5
07
08 08a 08b
C I33
/C241.C5 C
09 09a 09b
10 10a 10b
11 11a 11b
12 12a 12b
13 13a 13b
14 14a 14b
D 15 15a 15b D
+
ZP
ZP
UB+
19 -X2 02
19z04
19z08
19z12
19z16
19z20
19z24
19z28
19z32
216GD61a 03 -
-X3 Code I +
20 04
19d06
19d10
19d14
19d18
19d22
19d26
19d30
21
UP
UP
+
Redundant power supply ok
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Connection diagram of devices DCC
Print: 25.10.2005
Project Var. M24 (double system, 2 racks) B Resp. dept. PTUSE Rev. ind. Language en
Sheet C242
Rev. Revision note Date Name ABB ABB Switzerland Ltd.
Doc. no. 1KHF309592 n. sheet C251
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Red.
ZP
ZP
UB+
01 Power supply ok
01z04
01z08
01z12
01z16
01z20
01z24
01z28
01z32
-X20
02
B B
01d06
01d10
01d14
01d18
01d22
01d26
01d30
ZB
03
UP
UP
216GW62
Code: K-
04 -X20
05
216GW62
Code: L-
06
-X20
07
216GW62
I31 -X21 Code: N-
08 08a 08b /C252.C5
C -X20 C
09 09a 09b
216GW62
10 10a 10b I32 -X21 Code: O-
/C252.C5
11 11a 11b
12 12a 12b
13 13a 13b
14 14a 14b
D 15 15a 15b D
+
ZP
ZP
UB+
19 -X2 02
19z04
19z08
19z12
19z16
19z20
19z24
19z28
19z32
216GD61a 03 -
-X3 Code I +
20 04
19d06
19d10
19d14
19d18
19d22
19d26
19d30
21
UP
UP
+
Redundant power supply ok
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Connection diagram of devices DCC
Print: 25.10.2005
Project Var. M25 (double system, 2 racks) A Resp. dept. PTUSE Rev. ind. Language en
Sheet C251
Rev. Revision note Date Name ABB ABB Switzerland Ltd.
Doc. no. 1KHF309592 n. sheet C252
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Red.
ZP
ZP
UB+
01 Power supply ok
01z04
01z08
01z12
01z16
01z20
01z24
01z28
01z32
-X20
02
B B
01d06
01d10
01d14
01d18
01d22
01d26
01d30
ZB
03
UP
UP
216GW62
Code: P-
04 -X20
05
216GW62
Code: Q-
06
I31
/C251.C5
07
08 08a 08b
C I32
/C251.C5 C
09 09a 09b
10 10a 10b
11 11a 11b
12 12a 12b
13 13a 13b
14 14a 14b
D 15 15a 15b D
+
ZP
ZP
UB+
19 -X2 02
19z04
19z08
19z12
19z16
19z20
19z24
19z28
19z32
216GD61a 03 -
-X3 Code I +
20 04
19d06
19d10
19d14
19d18
19d22
19d26
19d30
21
UP
UP
+
Redundant power supply ok
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Connection diagram of devices DCC
Print: 25.10.2005
Project Var. M25 (double system, 2 racks) B Resp. dept. PTUSE Rev. ind. Language en
Sheet C252
Rev. Revision note Date Name ABB ABB Switzerland Ltd.
Doc. no. 1KHF309592 n. sheet E11
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
C C
CH OUT CH IN
CHA CHA
ENABLE
D BLOCK D
CH OUT
E E
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Configuration rack DCC
Print: 25.10.2005
Project Var. M1; 3 (single system, 1 rack) Resp. dept. PTUSE Rev. ind. Language en
Sheet E11
Rev. Revision note Date Name ABB ABB Switzerland Ltd.
Doc. no. 1KHF309592 n. sheet E21
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
C C
ENABLE ENABLE
D BLOCK BLOCK D
CH OUT CH OUT
E E
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Configuration rack DCC
Print: 25.10.2005
Project Var. M2; 4 (single system, 1 rack) Resp. dept. PTUSE Rev. ind. Language en
Sheet E21
Rev. Revision note Date Name ABB ABB Switzerland Ltd.
Doc. no. 1KHF309592 n. sheet E31
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
C C
ENABLE ENABLE
D BLOCK BLOCK D
CH OUT CH OUT
E E
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Configuration rack DCC
Print: 25.10.2005
Project Var. M5; 6 (single system, 1 rack) Resp. dept. PTUSE Rev. ind. Language en
Sheet E31
Rev. Revision note Date Name ABB ABB Switzerland Ltd.
Doc. no. 1KHF309592 n. sheet E111
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Code G- Code E-
B B
ABB ABB ABB
ABB ABB ABB ABB ABB ABB ABB ABB
PSV Passiv PSV PSV Passiv PSV
AL Alarm AL AL AL Alarm AL AL
C C
ENABLE ENABLE
D BLOCK BLOCK D
CH OUT CH OUT
216NG6.a 216VC62a 216EA62 216AB61 216DB61 216VC62a 216EA62 216AB61 216DB61 216NG6.a
REG216
MB68 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
E E
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Configuration rack DCC
Print: 25.10.2005
Project Var. M11; 13; 15 (red. system, 1 rack) A&B Resp. dept. PTUSE Rev. ind. Language en
Sheet E111
Rev. Revision note Date Name ABB ABB Switzerland Ltd.
Doc. no. 1KHF309592 n. sheet E121
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Code G- Code E-
B B
ABB ABB ABB
ABB ABB ABB ABB ABB ABB ABB ABB ABB ABB
PSV Passiv PSV PSV Passiv PSV
AL Alarm AL AL AL AL Alarm AL AL AL
C C
216NG6.a 216VC62a 216EA62 216AB61 216DB61 216DB61 216VC62a 216EA62 216AB61 216DB61 216DB61 216NG6.a
REG216
MB68 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
E E
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Configuration rack DCC
Print: 25.10.2005
Project Var. M12; 14; 16 (red. system, 1 rack) A&B Resp. dept. PTUSE Rev. ind. Language en
Sheet E121
Rev. Revision note Date Name ABB ABB Switzerland Ltd.
Doc. no. 1KHF309592 n. sheet E211
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
C C
ENABLE ENABLE
D BLOCK BLOCK D
CH OUT CH OUT
E E
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Configuration rack DCC
Print: 25.10.2005
Project Var. M21 (double system, 2 racks) A&B Resp. dept. PTUSE Rev. ind. Language en
Sheet E211
Rev. Revision note Date Name ABB ABB Switzerland Ltd.
Doc. no. 1KHF309592 n. sheet E222
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
C C
ENABLE ENABLE
D BLOCK BLOCK D
CH OUT CH OUT
E E
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Configuration rack DCC
Print: 25.10.2005
Project Var. M22; 23; 24; 25 (double system, 2 racks) A&B Resp. dept. PTUSE Rev. ind. Language en
Sheet E222
Rev. Revision note Date Name ABB ABB Switzerland Ltd.
Doc. no. 1KHF309592 n. sheet F11
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
IR1 12 URS W 42
A 13 S 43
IS1 14 UST W 44
15 45
B A S B
IT1 16 UTR W 46
17 47
Io 18 48
19 49
W04-W06 21
A
IR2 22
C C
A 23
IS2 24
A 25
IT2 26
27
Io 28
D D
29
W07 31
A
IM 32
33
W08 34
S
U1 W 35
E 36 E
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
W09 37
S
U2 38
We reserve all rights in this document and in the
39
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Measuring circuits DCC
Print: 25.10.2005
IR1 12 URS W 42
A 13 S 43
IS1 14 UST W 44
15 45
B A S B
IT1 16 UTR W 46
17 47
Io 18 48
19 49
W04-W06 21
A
IR2 22
C C
A 23
IS2 24
A 25
IT2 26
27
Io 28
D D
29
W07-W09 31
A
IRM 32
A 33
ISM 34
A 35
E ITM 36 E
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
37
Io 38
We reserve all rights in this document and in the
39
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Measuring circuits DCC
Print: 25.10.2005
IR1 12 URS2 W 42
A 13 S 43
IS1 14 UST2 W 44
15 45
B A S B
IT1 16 UTR2 W 46
17 47
Io 18 48
19 49
W04-W06 21
A
IR2 22
C C
A 23
IS2 24
A 25
IT2 26
27
Io 28
D D
29
W07-W09 31
S
URS1 W 32
S 33
UST1 W 34
S 35
E UTR1 36 E
W
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
37
38
We reserve all rights in this document and in the
39
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Measuring circuits DCC
Print: 25.10.2005
IR1 12 URS W 42
A 13 S 43
IS1 14 UST W 44
15 45
B A S B
IT1 16 UTR W 46
17 47
Io 18 48
19 49
W04-W06 21
A
IR2 22
C C
A 23
IS2 24
A 25
IT2 26
27
Io 28
D D
29
W07 31
A
I 32
33
W08 34
A
IM 35
E 36 E
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
W09 37
S
U 38
We reserve all rights in this document and in the
39
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Measuring circuits DCC
Print: 25.10.2005
IR1 12 IM 42
A 13 43
IS1 14 W11 44
S
15 U1 45
B A W B
IT1 16 46
17 W12 47
S
Io 18 U2 W 48
19 49
W04-W06 21
A
IR2 22
C C
A 23
IS2 24
A 25
IT2 26
27
Io 28
D D
29
W07-W09 31
A
IR3 32
A 33
IS3 34
A 35
E IT3 36 E
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
37
38
We reserve all rights in this document and in the
39
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Measuring circuits DCC
Print: 25.10.2005
IR1 12 URS W 42
A 13 S 43
IS1 14 UST W 44
15 45
B A S B
IT1 16 UTR W 46
17 47
Io 18 48
19 49
W04-W06 21
A
IR2 22
C C
A 23
IS2 24
A 25
IT2 26
27
Io 28
D D
29
W07-W09 31
A
IR3 32
A 33
IS3 34
A 35
E IT3 36 E
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
37
Io 38
We reserve all rights in this document and in the
39
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Measuring circuits DCC
Print: 25.10.2005
IR1 12 IR4 42
A 13 A 43
IS1 14 IS4 44
15 45
B A A B
IT1 16 IT4 46
17 47
Io 18 Io 48
19 49
W04-W06 21
A
IR2 22
C C
A 23
IS2 24
A 25
IT2 26
27
Io 28
D D
29
W07-W09 31
A
IR3 32
A 33
IS3 34
A 35
E IT3 36 E
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
37
Io 38
We reserve all rights in this document and in the
39
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Measuring circuits DCC
Print: 25.10.2005
IR1 12 IRM 42
A 13 A 43
IS1 14 ISM 44
15 45
B A A B
IT1 16 ITM 46
17 47
Io 18 Io 48
19 49
W04-W06 21
A
IR2 22
C C
A 23
IS2 24
A 25
IT2 26
27
Io 28
D D
29
W07-W09 31
A
IR3 32
A 33
IS3 34
A 35
E IT3 36 E
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
37
Io 38
We reserve all rights in this document and in the
39
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Measuring circuits DCC
Print: 25.10.2005
IR1 12 U1 W 42
A 13 43
IS1 14 W11 44
S
15 U2 45
B A W B
IT1 16 46
17 W12 47
A
Io 18 IM 48
19 49
W04-W06 21
A
IRM 22
C C
A 23
ISM 24
A 25
ITM 26
27
Io 28
D D
29
W07-W09 31
S
URS W 32
S 33
UST W 34
S 35
E UTR 36 E
W
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
37
38
We reserve all rights in this document and in the
39
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Measuring circuits DCC
Print: 25.10.2005
IR1 12 U1 W 42
A 13 43
IS1 14 S 44
15 U2 45
B A W B
IT1 16 46
17 W12 47
S
Io 18 U3 W 48
19 49
W04-W06 21
A
IR2 22
C C
A 23
IS2 24
A 25
IT2 26
27
Io 28
D D
29
W07-W09 31
S
URS W 32
S 33
UST W 34
S 35
E UTR 36 E
W
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
37
38
We reserve all rights in this document and in the
39
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Measuring circuits DCC
Print: 25.10.2005
IR1 12 UR W 42
A 13 S 43
IS1 14 US W 44
15 45
B A S B
IT1 16 UT W 46
17 47
Io 18 48
19 49
W04-W06 21
A
IR2 22
C C
A 23
IS2 24
A 25
IT2 26
27
Io 28
D D
29
W07-W09 31
A
IR3 32
A 33
IS3 34
A 35
E IT3 36 E
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
37
Io 38
We reserve all rights in this document and in the
39
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Measuring circuits DCC
Print: 25.10.2005
IR 12
A 13
IS 14
15
B A B
IT 16
17
Io 18
19
W04-W06 21
S
URS W 22
C C
S 23
UST W 24
S 25
UTR W 26
27
28
D D
29
W07 31
S
U W 32
33
W08 34
A
IM 35
E 36 E
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Measuring circuits DCC
Print: 25.10.2005
Ui(100%)
W 45
46
REX010 REX011
Code U-/F-/I- 1 1 Variant M1
UP8+
B P8 B
2 2
UP8-
4 4 11
Ui3
Ui
10
9
3 3
Ui2 Uir Rpr
8
DC supply
+ 7
- Uis
C 5 5 6 Rps C
Ui1
W10 41 Rer
100V spez. S
Urot(100%)
W 42
v V
43 u U Res
W12 47
15V S
C1 C2
Ustat(100%)
48
D W D
-
49
G~
+
W09 37 Rotor
100V S
U(95%)
W 38
39
L1 L2 L3
E E
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Measuring circuits DCC
Print: 25.10.2005
Ui(100%)
W 45
46
REX010 REX011-1
Code U-/F-/I- 1 1 Variant M11
UP8+ Rps > 8mOhm
B P8 B
2 2
UP8-
4 4 9
Ui3
Ui
8
7
3 3
Ui2 Uir Rpr
6
DC supply
+ 15
- Uis
C 5 5 10 Rps C
Ui1
W10 41 Rer
100V spez. S
Urot(100%)
W 42
v V
43 u U Res
W12 47
15V S
C1 C2
Ustat(100%)
48
D W D
-
49
G~
+
W09 37 Rotor
100V S
U(95%)
W 38
39
L1 L2 L3
E E
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Measuring circuits DCC
Print: 25.10.2005
Ui(100%)
W 45
46
REX010 REX011-2
Code U-/F-/I- 1 1 Variant M21
UP8+ Rps > 0.45Ohm
B P8 B
2 2
UP8-
4 4 9
Ui3
Ui
8
7
3 3
Ui2 Uir Rpr
6
DC supply
+ 15
- Uis
C 5 5 10 C
Ui1
W10 41 Rer
100V spez. S
Urot(100%)
W 42
C1 C2
43
-
G~
+
Rotor
D D
Rps
W12 47
15V S
Ustat(100%) v V
W 48 u U Res
49
W09 37
100V S L1 L2 L3
E U(95%) E
W 38
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
39
We reserve all rights in this document and in the
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Measuring circuits DCC
Print: 25.10.2005
IR1 12
A 13
IS1 14
15
B A B
IT1 16
17
Io 18
19
W04-W06 21
A
IR2 22
C C
A 23
IS2 24
A 25
IT2 26
27
Io 28
D D
29
W07-W09 31
S
URS W 32
S 33
UST W 34
S 35
E UTR 36 E
W
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
37
38
We reserve all rights in this document and in the
39
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Measuring circuits DCC
Print: 25.10.2005
Ui(100%)
W 45
46
REX010 REX011
Code U-/F-/I- 1 1 Variant M1
UP8+
B P8 B
2 2
UP8-
4 4 11
Ui3
Ui
10
9
3 3
Ui2 Uir
8
DC supply
+ 7
- Uis
C 5 5 6 Rps C
Ui1
W12 47
15V S
Ustat(100%) v V
W 48 u U Res
49
W10 41
D 100V S D
U(95%)
W 42
G~
43
L1 L2 L3
E E
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Measuring circuits DCC
Print: 25.10.2005
Ui(100%)
W 45
46
REX010 REX011-1
Code U-/F-/I- 1 1 Variant M11
UP8+ Rps > 8mOhm
B P8 B
2 2
UP8-
4 4 9
Ui3
Ui
8
7
3 3
Ui2 Uir
6
DC supply
+ 15
- Uis
C 5 5 10 Rps C
Ui1
W12 47
15V S
Ustat(100%) v V
W 48 u U Res
49
W10 41
D 100V S D
U(95%)
W 42
G~
39
L1 L2 L3
E E
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Measuring circuits DCC
Print: 25.10.2005
Ui(100%)
W 45
46
REX010 REX011-2
Code U-/F-/I- 1 1 Variant M21
UP8+ Rps > 0.45Ohm
B P8 B
2 2
UP8-
4 4 9
Ui3
Ui
8
7
3 3
Ui2 Uir
6
DC supply
+ 15
- Uis
C 5 5 10 C
Ui1
G~
D D
Rps
W12 47
15V S
Ustat(100%) v V
W 48 u U Res
49
W10 41
100V S L1 L2 L3
E U(95%) E
W 42
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
43
We reserve all rights in this document and in the
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Measuring circuits DCC
Print: 25.10.2005
IR 12 URS2 W 42
A 13 S 43
IS 14 UST2 W 44
15 45
B A S B
IT 16 UTR2 W 46
17 47
Io 18 48
19 49
W04-W06 21
S
URS1 W 22
C C
S 23
UST1 W 24
S 25
UTR1 W 26
27
28
D D
29
W07 31
A
IM1 32
33
W08 34
A
I 35
E 36 E
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
W09 37
A
IM2 38
We reserve all rights in this document and in the
39
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Measuring circuits DCC
Print: 25.10.2005
U1 W 12 IR3 42
13 A 43
W02 14 IS3 44
S
U2 15 45
B W A B
16 IT3 46
W03 17 47
A
I 18 Io 48
19 49
W04-W06 21
A
IR1 22
C C
A 23
IS1 24
A 25
IT1 26
27
Io 28
D D
29
W07-W09 31
A
IR2 32
A 33
IS2 34
A 35
E IT2 36 E
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
37
Io 38
We reserve all rights in this document and in the
39
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Measuring circuits DCC
Print: 25.10.2005
I 18 IR3 42
19 A 43
W04-W06 21 IS3 44
A
IR1 22 45
B A B
A 23 IT3 46
IS1 24 47
A 25 Io 48
IT1 26 49
27
Io 28
C C
29
W07-W09 31
A
IR2 32
A 33
IS2 34
A 35
D D
IT2 36
37
Io 38
39
E E
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Measuring circuits DCC
Print: 25.10.2005
Ui(100%)
W 12
13
REX010 REX011
Code U-/F-/I- 1 1 Variant M1
UP8+
B P8 B
2 2
UP8-
4 4 11
Ui3
Ui
10
9
3 3
Ui2 Uir
8
DC supply
+ 7
- Uis
C 5 5 6 Rps C
Ui1
W02 14
15V S
Ustat(100%) v V
W 15 u U Res
16
D D
G~
L1 L2 L3
E E
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Measuring circuits DCC
Print: 25.10.2005
Ui(100%)
W 12
13
REX010 REX011-1
Code U-/F-/I- 1 1 Variant M11
UP8+ Rps > 8mOhm
B P8 B
2 2
UP8-
4 4 9
Ui3
Ui
8
7
3 3
Ui2 Uir
6
DC supply
+ 15
- Uis
C 5 5 10 Rps C
Ui1
W02 14
15V S
Ustat(100%) v V
W 15 u U Res
16
D D
G~
L1 L2 L3
E E
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Measuring circuits DCC
Print: 25.10.2005
Ui(100%)
W 12
13
REX010 REX011-2
Code U-/F-/I- 1 1 Variant M21
UP8+ Rps > 0.45Ohm
B P8 B
2 2
UP8-
4 4 9
Ui3
Ui
8
7
3 3
Ui2 Uir
6
DC supply
+ 15
- Uis
C 5 5 10 C
Ui1
G~
D D
Rps
W02 14
15V S
Ustat(100%) v V
W 15 u U Res
16
L1 L2 L3
E E
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Measuring circuits DCC
Print: 25.10.2005
IR1 12 URS W 42
A 13 S 43
IS1 14 UST W 44
15 45
B A S B
IT1 16 UTR W 46
17 47
Io 18 48
19 49
W04-W06 21
A
IR2 22
C C
A 23
IS2 24
A 25
IT2 26
27
Io 28
D D
29
W07 31
A
I1 32
33
W08 34
A
IM 35
E 36 E
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
W09 37
A
I2 38
We reserve all rights in this document and in the
39
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Measuring circuits DCC
Print: 25.10.2005
URS1 W 12
S 13
UST1 W 14
15
B S B
UTR1 W 16
17
18
19
W04-W06 21
S
URS2 W 22
C C
S 23
UST2 W 24
S 25
UTR2 W 26
27
28
D D
29
W07 31
A
I1 32
33
W08 34
A
IM 35
E 36 E
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
W09 37
A
I2 38
We reserve all rights in this document and in the
39
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Measuring circuits DCC
Print: 25.10.2005
Ui(100%)
W 45
46
REX010 REX011
Code U-/F-/I- 1 1 Variant M1
UP8+
B P8 B
2 2
UP8-
4 4 11
Ui3
Ui
10
9
3 3
Ui2 Uir
8
DC supply
+ 7
- Uis
C 5 5 6 Rps C
Ui1
W12 47
15V S
Ustat(100%) v V
W 48 u U Res
49
W10 41
D 100V S D
U(95%)
W 42
G~
43
L1 L2 L3
E E
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Measuring circuits DCC
Print: 25.10.2005
Ui(100%)
W 45
46
REX010 REX011-1
Code U-/F-/I- 1 1 Variant M11
UP8+ Rps > 8mOhm
B P8 B
2 2
UP8-
4 4 9
Ui3
Ui
8
7
3 3
Ui2 Uir
6
DC supply
+ 15
- Uis
C 5 5 10 Rps C
Ui1
W12 47
15V S
Ustat(100%) v V
W 48 u U Res
49
W10 41
D 100V S D
U(95%)
W 42
G~
43
L1 L2 L3
E E
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
We reserve all rights in this document and in the
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Measuring circuits DCC
Print: 25.10.2005
Ui(100%)
W 45
46
REX010 REX011-2
Code U-/F-/I- 1 1 Variant M21
UP8+ Rps > 0.45Ohm
B P8 B
2 2
UP8-
4 4 9
Ui3
Ui
8
7
3 3
Ui2 Uir
6
DC supply
+ 15
- Uis
C 5 5 10 C
Ui1
G~
D D
Rps
W10 47
15V S
Ustat(100%) v V
W 48 u U Res
49
W10 41
100V S L1 L2 L3
E U(95%) E
W 42
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
43
We reserve all rights in this document and in the
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Measuring circuits DCC
Print: 25.10.2005
CHT05 CHI05
52 83 13
CHO04
53 84 14
54
CHT06 CHI06
41 15
CHO05
55 42 16
56
CHT07 CHI07
39 17
CHO06
57 40 18
58
CHT08 CHI08
37 19
C CHO07 C
59 38 20
60
CHI09
21
CHO08
61 22
62
CHI10
23
CHO09
63 24
64
CHI11
25
CHO10
65 26
66
CHI12
27
CHO11
D 67 28 D
CHI13
29
CHO12
68 30
69
CHI14
31
CHO13
70 32
CHI15
33
CHO14
71 34
CHI16
35
CHO15
72 36
E E
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
CHO16
73
74
We reserve all rights in this document and in the
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Signalling relays; Tripping relays; Binary inputs DCC
Print: 25.10.2005
CHT13 CHI21
52 83 13
CHO20
53 84 14
54
CHT14 CHI22
41 15
CHO21
55 42 16
56
CHT15 CHI23
39 17
CHO22
57 40 18
58
CHT16 CHI24
37 19
C CHO23 C
59 38 20
60
CHI25
21
CHO24
61 22
62
CHI26
23
CHO25
63 24
64
CHI27
25
CHO26
65 26
66
CHI28
27
CHO27
D 67 28 D
CHI29
29
CHO28
68 30
69
CHI30
31
CHO29
70 32
CHI31
33
CHO30
71 34
CHI32
35
CHO31
72 36
E E
I:\AS\Projects\P\REG216\drawing\1KHF309592Rev-0.e3s
CHO32
73
74
We reserve all rights in this document and in the
07:26
F
Based on Prepared 05-10-24 Schraner Title Numerical generator protection REG216 Doc. kind. Schema Ref. des.
F
Approved 05-10-25 Winterhalder Signalling relays; Tripping relays; Binary inputs DCC
Print: 25.10.2005
Do you find the publication readily understandable and logically structured? Can you make
any suggestions to improve it?
Is the information sufficient for the purpose of the publication? If not, what is missing and
where should it be included?
Name: Date:
Company
Equipment data:
Unit type:
Serial No.: ……….....................................
In operation since:
Remarks/Description of fault:
Customer: Date:
Address:
Description of problem:
Customer: Date:
Address:
www.abb.com/substationautomation