Leaflet ESI 48 120V 1000VA en

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

The ESI series

Inverter ESI 48 / 120 V - 1000 VA


ESI48N102AB A
Features
• Standard 19”, 23”and 25” rack

• 1KVA/800W

• Selectable 100V/110V/115V/120V system output

• High efficiency

• Pure sine wave output

• Compact, lightweight modular design

• Bypass function

• RS-232 communication

• User friendly LED and LCD display

Applications
• Indoor and outdoor

• Modular UPS configurations

• Telecom, wireless, datacom

Description
The inverter ESI 48 / 120 V inverters are single phase, fan-cooled inverters. They convert all direct voltages from
48 V battery systems to an uninterruptible, stabilized AC voltage. The outstanding dynamic performance matches
the supply requirements for state-of-the-art telecom equipment. This performance as well as the advanced
technology is the key factors of the success of this inverter and it offers a cost effective and reliable solution.

The typical applications for this inverter are both in indoor and outdoor environments, which is a perfect solution for
wireless base stations, core network components, telecommunications networks and data networks.

Leaflet_ESI48_120_1000/rev. 1.0/Aug.08.2007/Chad Tseng


Delta Electronics, Inc. Tel:+886-3-4526107; Fax:+886-3-4527314;http://www.deltaww.com
ESI 48 / 120 V - 1k VA: Technical specifications
General Mechanics
Efficiency, at 120Vrms 83 % Width, overall 17.3” / 440 mm
Safety UL 60950 Depth, overall 11.8” / 300 mm
CAN/CSA-C22.2 No. 60950 Height, overall 3.5” / 88.0 mm
EMI, radiated FCC Part 15, class A Weight 15.4 lb / 7 kg (1k VA)
Cooling Fan cooled
Acoustic noise 46 dB(A) Environment
On/Off Switch Yes Operating temperature 0 ... + 50 °C
MTBF 450K Hours Relative humidity 20 ~ 90 %, non condensing
Altitude - 500 ~ 10000 feet
DC Input
Input voltage 40 … 60 Vdc *Specifications are subject to change due to technical progress
Rated current 25 A (1k VA) /
Inrush current 90 A
Protection Fuse and DC breaker

AC Input ( Bypass)
Input voltage 100 / 110 / 115 / 120 Vrms ±
20 Vrms
Frequency 50 / 60 Hz ± 5 Hz
EMI, conducted FCC Part 15, class A
Mains connector Rear side
Input protection AC circuit breaker
Connection Terminal block (3 P)

Output
Output voltage 100 / 110 / 115 / 120 Vrms
Voltage regulation ±3%
Frequency 50 / 60 Hz ± 0.2 Hz
THD 3 %: 100% liner load
5 %: 100% SPS load
Current, nominal 10 Arms (1kVA)

Crest factor 3:1


Power, nominal 1000 VA / 800 W

Receptacles NEMA 5-15R x 2 (1kVA)

User Interface
Status display LCD display
Status indication LED «Inverter ON»
LED «Overload»
LED «DC abnormal»
LED «Fault»
Communication RS 232
Dry contact

Leaflet_ESI48_120_1000/rev. 1.0/Aug.08.2007/Chad Tseng


Delta Electronics, Inc. Tel:+886-3-4526107; Fax:+886-3-4527314;http://www.deltaww.com

You might also like