6290-A Power Transformers
6290-A Power Transformers
6290-A Power Transformers
GENERAL SPECIFICATIONS
TABLE OF CONTENTS
1.0 SCOPE
3.0 DEFINITIONS
4.0 DESIGN
5.0 MATERIALS
5.1 OIL
5.2 EXPOSED METAL
5.3 VALVES
5.4 CONDUCTORS
6.0 FABRICATION/CONSTRUCTION
6.1 GENERAL
6.2 ACCESSORIES
7.1 TESTS
7.2 VARIANCE
7.3 NOTICE
GENERAL SPECIFICATIONS
1.0 SCOPE
This specification covers the minimum requirements for three-phase oil filled
transformers rated over 500 kVA.
2.1 Vendor shall meet or exceed the requirements of the latest edition of the following
codes, regulations and standards, except as superseded herein. In cases where
more than one code, regulation or standard apply to the same condition, the most
stringent shall be followed. In the event of a conflict between this specification and
other specifications or correspondence, the OWNER shall be consulted and a
ruling, in writing, shall be obtained before any work is started.
2.3 Any deviation from this specification must be approved, in writing, by OWNER.
Such written approval must be obtained prior to the commencement of any work
which would constitute such a deviation.
GENERAL SPECIFICATIONS
3.0 DEFINITIONS
OWNER shall mean the OWNER as set out in the Request for Quotation (RFQ) or
any other person, firm or corporation engaged by OWNER, to perform services to
which this specification is applicable.
Vendor shall mean the person(s) or company(ies) selling the product specified in
this specification to the OWNER.
Standard means that the feature, accessory or test is provided in accordance with
the applicable IEC Standard, without additional specification by the OWNER.
Provision for Cooling means that the transformer shall have, as a minimum,
adequate capacity in all current-carrying parts, plus fan support bracket(s) and
thermowell.
4.0 DESIGN
Transformers shall be built in accordance with and contain all the standard
features specified in IEC 71, plus this Specification.
5.0 MATERIALS
5.1 Oil
The Vendor shall use "Mineral Based" transformer oil. Oils containing PCB's are
not acceptable.
The oil shall contain oxidation inhibitors and shall have a breakdown voltage of 30
kV minimum when tested according to ASTM D 877.
5.3 Valves
Revision - August 25, 1997 Page 2
File - 6290-a_Power Transformers
MUGLAD BASIN OIL DEVELOPMENT PROJECT
GENERAL SPECIFICATIONS
5.4 Conductors
6.0 FABRICATION/CONSTRUCTION
6.1 General
6.1.1 The wye-connected windings of transformers shall have the neutral point
connected to a neutral terminal suitable for grounding.
6.1.2 High-voltage windings shall have four (4) 2.5% full capacity taps, two above and
two below rated voltage; tap changing shall be "off-load".
6.1.3 Dial gauges, valves, tap changer handle and nameplate shall all be on one side of
the transformer.
6.1.4 Alarm and control wiring shall be clearly labelled using heat shrink tubing, and be
terminated in a weatherproof junction box with a wiring diagram enclosed.
6.1.5 Piping and fittings shall be screwed or socket welded. Backwelding of screwed
fittings shall not be done.
6.1.10 Average winding temperature rise at Full Load shall be 55°C, however, insulation
shall be rated for 65°C rise.
6.2 Accessories
Unless otherwise specified on the Data Sheet, the following accessories are
required:
GENERAL SPECIFICATIONS
• Liquid-level gauge.
• Vacuum/pressure gauge.
• Provision for High Side lightning arrestor (Vendor to specify rating and type).
• Taps, with a lockable off-load tap changer handle and position indicator (also
see sub-section 6.1.3)
• Explosion relief device.
• Provision for fan cooling.
• Tank capable of withstanding pressures of +50 kPa and vacuum of 50 mm
mercury.
• Automatic pressure relief.
7.1 Tests
Transformers shall be tested as specified in IEC 79 for the tests listed below:
7.2. Variance
Where tests show the efficiency of the transformer is less than the guaranteed
value quoted, the Vendor shall incur a cost penalty. The amount of this penalty
shall equal the value of excess losses (in kilowatts), that are above the quoted
value, times an efficiency cost factor (in dollars per kilowatt). This factor is
specified on the Data Sheet. Losses at Full Load will be used for comparison.
7.3 Notice
The Vendor shall give a minimum of ten (10) days notice prior to transformer
testing to allow the OWNER the option of observing the tests.
GENERAL SPECIFICATIONS
The Vendor shall supply a minimum of one reproducible copy of all drawings and
data unless otherwise specified on the Purchase Order.
The following lists the drawings and data required for the proposal, drawing
approval and certified (final) drawing stage (after manufacturing):
Outline Dimensions X X X
Control Schematics X X X
Wiring Diagrams X X
Nameplate Data X X
Installation/Operation/Maintenance Data X
Bills of Material X
GENERAL SPECIFICATIONS
APPENDIX A
POWER TRANSFORMER
DATA SHEET