Liebert GXT3™, 5kVA-10kVA UPS: Compact UPS Systems For High Power Network Rack Applications
Liebert GXT3™, 5kVA-10kVA UPS: Compact UPS Systems For High Power Network Rack Applications
Liebert GXT3™, 5kVA-10kVA UPS: Compact UPS Systems For High Power Network Rack Applications
2
UPS operation and display panel can rotate
90 degrees, which provides upright
viewing for users.
3
5 Or 6kVA Of True On-Line Power
In A Compact 4U Package
Adaptable Design
For installation flexibility, the
Liebert GXT3 5 & 6kVA models 5 & 6 kVA Model shown in rack mount position
allow you to choose from several
different wiring configurations
made possible by the use of
removable power distribution PD2-HDWR ships standard
boxes that simply plug into the with the unit and is hardwire
rear of the UPS. The standard input/output
box provides terminal blocks
for hardwired input and output
connections. An optional
hardwire version that includes
a maintenance bypass is also
available.
When the ease of plug-and-play
power connections is desired,
optional versions of the power
distribution box convert Liebert
GXT3 5 & 6kVA units to a cord- PD2-HDWR-MBS is an optional
type input with receptacles for hardwire input/output POD
output distribution, and also offers with maintenance bypass
maintenance bypass capability that
allows hot-swapping of the entire
UPS. The UPS has as adaptable
dual inverter design, capable of
providing simultaneous output
voltages of 240/120, 208/120,
230/115, 220/110, or 200/100 and
an output power factor of 0.8.
6 kVA Model shown in tower position with
optional battery cabinet
Pluggable input/output
PODs available with
maintenance bypass
4
8kVA And 10kVA Of Power The internal battery packs are
Adaptable Design
8 & 10 kVA Model shown in rack mount position
The UPS has a dual inverter
design, capable of providing
simultaneous output voltages
UPS is hardwire input/output of 240/120, 208/120, 230/115,
with maintenance bypass and 220/110, or 200/100 and an
includes no POD standard. output power factor of 0.9. The
new 6U cabinet is the smallest for
208/120 selectable voltage in the
8-10kVA size. The unit features
integrated internal manual and
automatic maintenance bypass,
power module, battery modules,
auto detection of extended battery
cabinets and optional plug-and-
play distribution plates.
The standard 8 & 10kVA models
include terminal blocks for
hardwired connections of both
input and output. Optional power
distribution modules are available
to add output receptacles to the
rear panel of the unit.
Hot-Swappable Operation
Liebert GXT3 8 & 10kVA units
feature three bays for one power
module and two battery modules.
10 k VA Model shown in tower position with The chassis contains a bypass
optional battery cabinet switch that allows all modules to be
removed without powering down
Optional PODs available
the connected load.
5
Product specifications
UPS specifications—5, 6, 8 and 10 kVA models
Model Number GXT3-5000RT208 GXT3-6000RT208 GXT3-8000RT208 GXT3-10000RT208 GXT3-6000RTL630
Model Rating 4000W/5000VA 4800W/6000VA 7200W/8000VA 9000W/10000VA 4200W/6000VA
Dimensions, Rack Mount, 16.9 x 26.1 x 6.8 16.9 x 26.5 x 10.3 16.9 x 22.6 x 8.5
W x D x H Unit in. (mm) (430 x 662 x 173) (430 x 672 x 261) (430 x 574 x 217)
Weight Unit, lb (kg) 56.2 (25.5) 78.3 (35.5) 51.8 (23.5)
Input AC Parameters
Nominal Operating Frequency 50 or 60Hz (Factory Default is 60Hz)
Factory Default VAC 120/208VAC 208 or 240VAC
Factory Default L1-N, L2-N VAC 120 VAC nominal N/A
Input Frequency w/o Battery Operation 40 - 70 Hz 40 - 70 Hz
Input Power Connection Hardwire Terminal Block 3W + G (L-L-N-G) L6-30P input plug (L-L-G)
L1-N, L2-N Maximum Allowable VAC 150VAC N/A
Output AC Parameters
Factory Default VAC 120/208V AC 208 or 240VAC
Factory Default L1-N, L2-N VAC 120VAC nominal N/A
User Configurable L1-N, L2-N VAC 100/110/115/120/127VAC, ±2% N/A
Overload Rating
105% to 130% 1 Minute
131% to 150% 10 seconds
151% to 200% 1 second
>200% (impact load) At least 5 cycles
Environmental
Operating Temp, °F (°C) 32 to 104 (0 to 40)
Storage Temp, °F (°C) 5 to 122 (-15 to 50)
Audible Noise Less than 55dBA at 3.2ft. (1m) rear; less than 50dBA at 3.2ft. (1m) front and sides
Operating Elevation Up to 10,000 ft. (3000m) at 104°F (40°C) without derating
Relative Humidity 0% to 95%, non-condensing
Agency
Safety UL 1778, c-UL Listed
RFI/EMI FCC Part 15, Subpart B, Class A, FCC Class A
Surge Immunity IEEE/ANSI C62.41 Category A & B
Transportation ISTA Procedure 1A
ENERGY STAR qualified
®
YES
Battery Parameters
Type Valve-regulated, non-spillable, lead acid
Kit Quantity x Battery Quantity 2 x 6 x 12V x 9.0 AH 2 x 12 x 12V x 9.0 AH 2 x 10 x 12V x 4.5AH
x V x Rating
Recharge Time 6 hours to 90% capacity after full discharge into 100% load
Environmental Operating Temp, Storage Temp, Operating Elevation, and Relative Humidity: Same as UPS
6
External battery cabinet specifications
Model Number GXT3-144VBATT GXT3-240VBATTUL GXT3-288RTVBATT
Used w/UPS Model GXT3-5000 & GXT3-6000RT208 GXT3-6000RTL630 GXT3-8000 & GXT3 10000RT208
Dimensions, W x D x H, 16.9 x 26.1 x 3.3 16.9 x 22.6 x 5.1 16.9 x 26.5 x 6.8
Unit (with bezel) in. (mm) (430 x 662 x 85) (430 x 574 x 130) (430 x 672 x 173)
Weight, Unit lb (kg) 99.9 (45.3) 94.8 (43) 29.8 (13.5)
Battery Parameters
Type Valve-regulated, non-spillable, lead acid
Kit Quantity x Battery Quantity x Rating 2 x 6 x 12V x 9.0 AH 2 x 10 x 12V x 9.0 AH 2 x 12 x 12V x 9.0 AH
Environmental Operating Temp, Storage Temp, Operating Elevation, and Relative Humidity: Same as UPS
Electrical Specifications
Amp Rating 30A 2-pole input breaker for UPS input power
Input Power Hardwire Terminal Block
Connections [1] L14-30P on a 3.2m cord (1) L6-30P
3W + G (L-L-N-G)
(4) 5-20R
Output Power Hardwire Terminal Block (2) 5-20R (4) 5-20R (4) L5-20R (4) L5-20R (2) L6-20R
Connection (1) L14-30R (4) L6-20R
3W + G (L-L-N-G) (2) L6-20R (2) L6-30 (2) L5-30R (2) L6-30R (2) L6-30R
(1) L6-30R
Electrical Specifications
Amp Rating 2-pole 60A Input Breaker
Input Power Hardwire Terminal Block 3W + G (L-L-N-G) to Chassis
Connections
(4) 5-20R (4) 5-20R
Output Power (2) L6-30 (4) L6-20R (4) 5-20R (4) L6-20R
Connection (2) L6-30R (2) L5-30R
(8) 5-20R (4) 5-20R (4) L6-30R (4) L5-20R
(2) L6-20R (2) L5-20R
30% 30 23 40 34 26
40% 22 17 27 25 18
50% 16 12 21 18 13.5
Internal
Battery 60% 12 10 16 14 11
70% 10 7 13 12 8
80% 8 5.5 11 9 7
90% 6 4.5 9 8 6
100% 5 4 8 7 4.5
7
Emerson Network Power, a business of Emerson (NYSE:EMR), delivers software, hardware and Emerson Network Power
Global Headquarters
services that maximize availability, capacity and efficiency for data centers, healthcare and 1050 Dearborn Drive
P.O. Box 29186
industrial facilities. A trusted industry leader in smart infrastructure technologies, Emerson Columbus, Ohio 43229
800 877 9222 Phone (U.S. & Canada Only)
Network Power provides innovative data center infrastructure management solutions that 614 888 0246 Phone (Outside U.S.)
[email protected]
bridge the gap between IT and facility management and deliver efficiency and uncompromised
availability regardless of capacity demands. Our solutions are supported globally by local Emerson Network Power
Emerson Network Power service technicians. Learn more about Emerson Network Power Caribbean and Latin America
Office – United States of America
products and services at www.EmersonNetworkPower.com +1-954-984-3452 Phone
[email protected]
liebert.com
24 x 7 Tech Support
800 222 5877 Phone
614 841 6755 (outside U.S.)
EmersonNetworkPower.com
While every precaution has been taken to ensure accuracy and completeness in this literature, Liebert Corporation assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or
omissions. © 2013 Liebert Corporation. All rights reserved throughout the world. Specifications subject to change without notice. All names referred to are trademarks or registered trademarks of their respective owners. ® Liebert is a registered
trademark of the Liebert Corporation.
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2013 Emerson Electric Co.