Ceiling
STULZ CeilAiR
Ceiling Mounted Air Conditioners
3.5 − 35 kW
60Hz Data
EM Engineering Manual
Air Technology Systems, Inc.
STULZ CeilAiR Engineering Manual – 60Hz
STULZ
Our Mission:
Driving innovation in our industry, providing highest quality environmental control
products, superior technology, customer solutions and exceptional customer
service while being a socially and environmentally responsible and ethical company.
This commitment to excellence, along with a standard two year warranty, fast lead times, and outstanding customer service,
make STULZ the perfect choice for all your environmental control needs.
CeilAiR ceiling mounted air conditioning units provide temperature and/or humidity control for those hot spot areas in the
building which exceed the central system capacity. They are an economical solution to such demands which may, in fact, be
temporary until the next offices are carved out of an existing plant area, another laboratory added to a school or new medical
equipment installed at a hospital. No floor space is required by the CeilAiR ceiling mounted units. The units are designed
with a wide range of options to handle both comfort and precision cooling applications.
2
STULZ CeilAiR Engineering Manual – 60Hz
Table of Contents
CEILAIR MODELS...................................................................................................................................... 8
Self-Contained Air Cooled - with Integral Air Cooled Condenser............................................................. 8
Split Air Cooled - With Remote Outdoor Or Indoor Air Cooled Condenser............................................... 8
Split Air Cooled - Air Handling Unit W/ Indoor Or Outdoor Remote Condensing Unit.............................. 8
Self-Contained Water Cooled Systems.................................................................................................... 9
Self-Contained Glycol Cooled Systems.................................................................................................... 9
Chilled Water Systems............................................................................................................................. 9
CEILAIR® NOMENCLATURE.................................................................................................................... 10
GUIDE SPECIFICATIONS......................................................................................................................... 11
Models.................................................................................................................................................... 11
Air-Cooled, Self-Contained: Integral Self-Contained (Models OHS-012/040-AS)............................. 11
DX - Evaporator Sections: Air Cooled Remote Evaporator (Models OHS-( )-()AR).......................... 11
DX - Water Cooled Systems: Integral Self-Contained Models OHS-( )-W / DW).............................. 11
DX - Glycol-Cooled Systems: Integral Self-Contained (Models OHS-( )-G / DG).............................. 11
Chilled Water Air Handlers: Chilled Water System (Models OHS-( )-C)............................................ 12
Quality Assurance................................................................................................................................... 14
General Description................................................................................................................................ 14
Component Access................................................................................................................................. 14
Cabinet Construction.............................................................................................................................. 14
Electrical System.................................................................................................................................... 14
Overflow Safety Float Switch.................................................................................................................. 14
Remote Stop / Start................................................................................................................................ 14
Coils .....................................................................................................................................................15
DX- Refrigeration System....................................................................................................................... 15
Scroll Compressors................................................................................................................................ 15
Chilled Water Systems (Models OHS-()-C)............................................................................................ 15
Cooling Coil....................................................................................................................................... 15
Control Valve..................................................................................................................................... 15
Blowers/Motors....................................................................................................................................... 16
Direct Drive Systems......................................................................................................................... 16
Belt Driven Systems.......................................................................................................................... 16
Evaporator Air Patterns and Filtration................................................................................................ 16
Ducted Evaporator (Available on all model sizes)............................................................................. 16
DX - Heat Rejection................................................................................................................................ 17
Air Cooled..........................................................................................................................................17
Water/Glycol Cooled.......................................................................................................................... 17
CeilAiR 60Hz Options............................................................................................................................. 18
A-Tech-1.1 Controller......................................................................................................................... 19
A-Tech-1.2 Controller......................................................................................................................... 20
E2 Controller...................................................................................................................................... 21
Canister Steam Humidification ......................................................................................................... 23
3
STULZ CeilAiR Engineering Manual – 60Hz
Electric Reheat/Heat.......................................................................................................................... 24
Hot Gas Reheat................................................................................................................................. 25
Hot Water Reheat/Heat...................................................................................................................... 26
Steam Reheat/Heat........................................................................................................................... 27
SCR Fired Reheat/Heat (Requires E2 controller).............................................................................. 28
High Static Pressure Belt-Drive Blowers........................................................................................... 29
Filtration.............................................................................................................................................30
Head Pressure Control: Air-Cooled - Low Ambient, 0°F, Fan Cycling / Fan Speed.......................... 31
Head Pressure Control: Air-Cooled - Low Ambient, -20°F, Variable Speed Control......................... 32
Head Pressure Control: Air-Cooled - Low Ambient, -30°F, Flooded Control..................................... 33
Head Pressure Control: Air-Cooled - Low Ambient, head pressure regulating control valve............. 34
Head Pressure Control: Free-Cooling System.................................................................................. 35
DX - Capacity Modulation /Freeze-Protection: Full-Floating, Hot Gas Bypass.................................. 36
DX - Capacity Modulation /Freeze-Protection: Snap-Acting, Hot Gas Bypass.................................. 37
Chilled Water and AWS Control Valves............................................................................................. 38
Dual Compressor System.................................................................................................................. 39
Three Phase Power Supply............................................................................................................... 40
277/1/60 Power Supply...................................................................................................................... 41
Condensate Pump: Low Profile......................................................................................................... 42
Condensate Pump: All-Metal (optional)............................................................................................. 43
Condensate Pump: Low-profile Factory Installation.......................................................................... 44
Smoke Detector................................................................................................................................. 45
Firestat...............................................................................................................................................46
Water Detector: Single Spot-type Remote ........................................................................................ 47
Water Detector: Dual Spot-type Remote........................................................................................... 48
Water Detector: 20 Ft. - Strip/Cable Type.......................................................................................... 49
Compressor Sound Jacket................................................................................................................ 50
Low Entering Condenser Water Kit................................................................................................... 51
Main Power - Electric Non-Fused Service Switch............................................................................. 52
Free-Cooling Option.......................................................................................................................... 53
Alternate Water Source...................................................................................................................... 54
4
STULZ CeilAiR Engineering Manual – 60Hz
5
STULZ CeilAiR Engineering Manual – 60Hz
6
STULZ CeilAiR Engineering Manual – 60Hz
7
STULZ CeilAiR Engineering Manual – 60Hz
CEILAIR MODELS
Self-Contained Air Cooled - with Integral Air Cooled Condenser
OHS-012/040-AS OHS-012/040-AS
(Self-Contained, "Ductless" Spot Cooler) (Self-Contained, Ducted Evaporator)
Split Air Cooled - With Remote Outdoor Or Indoor Air Cooled Condenser
(compressor located with Evaporator Section) STULZ Remote Outdoor
Please refer to the Propeller Condenser
STULZ Heat Rejection
Engineering Manual for
specification and perfor-
mance data on STULZ STULZ Remote Outdoor
Remote Condensers & Propeller Condenser STULZ Remote Indoor
Condensing Units { Centrifugal Condenser
{
STULZ Remote Indoor
Centrifugal Condenser
OHS-012/040-HAR & OHS-048/060-AR
(Single Compressor - Split Evaporator)
(Ducted Only)
{
{
STULZ Remote Indoor
Centrifugal Condenser
Split Air Cooled - Air Handling Unit W/ Indoor Or Outdoor Remote Condensing Unit
(compressor located with Condensing Section)
STULZ Outdoor Propeller
Remote Condensing Unit
STULZ Outdoor Propeller
Remote Condensing Unit
{
{ STULZ Indoor Centrifugal
Remote Condensing Unit
{
{ STULZ Indoor Centrifugal
Remote Condensing Unit
8
STULZ CeilAiR Engineering Manual – 60Hz
OHS-012/032-W
OHS-012/040-W (Self-Contained, Ducted Evaporator)
(Self-Contained, "Ductless" Spot Cooler)
OHS-012/040-HG
&
OHS-048/060-G with
STULZ DRYCOOLER & PUMP PACKAGE
(Single Compressor, Self-Contained, Ducted Only with
OHS-012/040-G with Outdoor Propeller Drycooler & Pump Package)
STULZ DRYCOOLER & PUMP PACKAGE
(Self-Contained, "Ductless" Spot Cooler with
Outdoor Propeller Drycooler & Pump Package)
9
STULZ CeilAiR Engineering Manual – 60Hz
CEILAIR® NOMENCLATURE
OHS-040-G-FC
AWS = Alternate Water Source
FC = Free-Cooling
LP = Low Profile Configuration
OHS = CeilAiR Overhead System OA = Outside Air*
COS = CyberONE System SF = Same-Face" Air Pattern
MCS = Modular Cyber System SP = Special Configuration
FCS = Floor Console System
SCS = STULZ Condensing Section*
GPS = Glycol Pump System* AHU = Air Handling Unit
CFS = CyberAiR Floor-mounted System AR = Remote (Split) Air Cooled
AS = Self-Contained Air Cooled
C = Chilled Water System
CAA = Indoor Centrifugal Condenser*
Nominal Capacity in 1,000's of BTU/H
D( ) = Dual (Two) Circuit System
G = Glycol Cooled
H( ) = Horizontal Discharge, "H- Series"
Configuration (i.e., HAHU, HAR, HW, HG,
and HC)
( )AA = Outdoor Prop Fan Condenser for 0° F*
( )SA = Outdoor Prop Fan Condenser for -20° F*
( )AA = Outdoor Prop Fan Condenser for -30° F*
EC = Outdoor Prop Fan Condenser for -20° F*
w/ EC Fans
RCU-I = Indoor Centrifugal Remote Condensing
Unit*
RCU-O = Outdoor Remote Condensing Unit*
W = Water Cooled
10
STULZ CeilAiR Engineering Manual – 60Hz
GUIDE SPECIFICATIONS
Models
Air-Cooled, Self-Contained: Integral Self-Contained (Models OHS-012/040-AS)
The system shall be a self-contained, ceiling mounted air conditioner with factory mounted integral air
cooled condenser with centrifugal blower.
The condenser shall be sized to provide the total heat of rejection of the system at a 95°F DB ambient
temperature.
The system shall require only single point supply power connection and the system shall ship from the
STULZ factory with a full operating refrigerant charge.
11
STULZ CeilAiR Engineering Manual – 60Hz
The system shall require only single point supply power connection and shall ship from the STULZ fac-
tory with a full operating refrigerant charge.
Chilled Water Air Handlers: Chilled Water System (Models OHS-( )-C)
The system shall be a ceiling mounted chilled water air conditioner to include chilled water cooling
coil, evaporator blower and motor and chilled water control valve. Chilled water shall be provided by a
remote liquid chiller system.
12
STULZ CeilAiR Engineering Manual – 60Hz
13
STULZ CeilAiR Engineering Manual – 60Hz
Quality Assurance
(ISO-9001:2008 Registered)
STULZ operates in an ISO-9001:2008 registered quality control environment. Each STULZ employee
is committed to satisfying his or her customer expectations with the highest level of consistent, measur-
able and continuous quality improvement.
General Description
The system shall be a ceiling mounted supplemental air conditioner designed and built to the highest of
industry standards. The system shall be complete and factory
run-tested before shipment. The system shall be listed and labeled in
compliance with UL 1995 (# SATS-1995) by an approved Nationally
Recognized Testing Laboratory (NRTL). The system shall be MEA
NYC (MEA-163-88-E) and Chicago Code approved.
The system shall be manufactured by ISO-9001:2008 Quality Registered Stulz Air Technology Systems,
Inc. in Frederick, Maryland, USA.
Component Access
The air conditioner shall be fully accessible in-place through easily removable side access panels.
Cabinet Construction
The cabinet and access panels shall be fabricated from aluminum for corrosion protection and to mini-
mize the system’s weight. The panels shall be lined with 2 lb/ft2 high density sound and thermal insula-
tion and sealed with self-extinguishing gasketing conforming to NFPA 90A and 90B.
Electrical System
The system shall incorporate overcurrent and overload protection in accordance with UL 1995 require-
ments. Each blower motor, compressor, electric heater stage and humid-
ifier (if applicable) shall be provided with a factory mounted and wired
starter / contactor.
The control circuit shall be a 24 VAC Class 2 low voltage circuit including
a circuit breaker for protection. Low voltage, high voltage and grounding
wires shall be color coded and shall be individually numbered at each
end for ease of service tracing. All wiring shall be in accordance with the
National Electric Code (NEC).
14
STULZ CeilAiR Engineering Manual – 60Hz
Coils
Evaporator systems shall be configured for a draw-thru air pattern to provide uniform air distribution
over the evaporator coil face. The coils shall be seamless drawn copper tubes, mechanically bonded
to tempered aluminum fins with a raised-lanced fin design for maximum heat transfer. Coil end plates
shall be hot dipped galvanized.
The evaporator coil shall be mounted in an insulated stainless steel or polymer condensate pan.
Control Valve
Cooling capacity shall be controlled by a factory installed slowly opening and slowly closing 2-way
motorized control valve rated for a maximum 300 psig w.w.p.
Note: See "Chilled Water and AWS Control Valves" on page 38 for additional chilled
water valve options.
15
STULZ CeilAiR Engineering Manual – 60Hz
Blowers/Motors
Direct Drive Systems
The blower shall be direct driven with double width, double inlet housing and forward curved blades.
The blower shall be dynamically and statically balanced to minimize vibration
and operate in the Class I range.
The evaporator motor shall be factory wired for the correct speed to produce the
specified air quantity. The motor shall have internal overload protection.
The unit shall have slide out, 1" deep Class 2 (per U.L. Standard 900) filter(s) easily
AIR IN
accessed through a side access panel. The filter shall have a rating of at least 80%
average arrestance as measured by ASHRAE Standard 52-76 test method. EVAPORATOR
AIR OUT
EVAPORATOR
AIR IN
Note: Please refer to the cabinet specification pages beginning on page 105 for stan-
dard CeilAiR cabinet configurations. Consult your local STULZ sales representa-
tive for special applications.
EVAPORATOR
AIR OUT
16
STULZ CeilAiR Engineering Manual – 60Hz
DX - Heat Rejection
Air Cooled
Please refer to the STULZ Heat Rejection Engineering Manual for information about air cooled con-
densers and condensing units.
Water/Glycol Cooled
Coaxial Tube-In-Tube (Models OHS-012/120-()W/G)
Each evaporator refrigerant circuit shall be provided with a factory-installed single pass, counterflow
configured, tube-in-tube coaxial condenser designed and tested for a 450 psig.
w.w.p.
17
STULZ CeilAiR Engineering Manual – 60Hz
Note that many of the above options are specific to subsets of, or individual models of, the CeilAiR
series.
18
STULZ CeilAiR Engineering Manual – 60Hz
A-Tech-1.1 Controller
The CeilAiR ceiling air conditioner shall be provided with a STULZ slim-line, ultra-thin profile, 1-stage
cool / 1-stage heat, remote wall mounted programmable digital microprocessor based controller.
Notes:
• The A-Tech-1.1 thermostat is standard on all single stage DX and non-proportional chilled water
systems.
• The A-Tech-1.2 thermostat is standard on all dual stage DX systems.
• A remote sensor (wired) is available on request.
19
STULZ CeilAiR Engineering Manual – 60Hz
A-Tech-1.2 Controller
The CeilAiR ceiling air conditioner shall be provided with a STULZ slim-line, ultra-thin profile,
2-stage cool / 2-stage heat, remote wall mounted programmable digital microprocessor based control-
ler.
Notes:
• The A-Tech-1.2 thermostat is standard on all dual stage DX systems.
• The A-Tech-1.1 thermostat is standard on all single stage DX and non-proportional chilled water
systems.
• A remote sensor (wired) is available on request.
20
STULZ CeilAiR Engineering Manual – 60Hz
E2 Controller
The CeilAiR ceiling mounted air conditioner shall be provided with STULZ' E2 Microprocessor Control-
ler. The controller shall incorporate a "user-friendly" operating environment, to allow easy system setup
and operation.
E2 Controller Features
• Control Panel
Back-lit LCD alphanumeric display for visual indication
Operated via 6-key menus, in five different modes
Unit functions for cooling, heating, humidifying and dehumidifying
Three levels of restricted entry into the configuration
Remote-mountable
• Microprocessor
Sensor inputs control inputs/outputs
Additional I/O Sensors & Alarms
Psychrometric control provided as a user configurable temperature and humidity (relative humidity)
or dew point control
Optional UPS backup module
• Control Inputs
Outside Air Temperature and humidity (optional)
Return air temperature
BMS control (optional)
• Control Outputs
Outside Air Intake (optional)
STULZ DX or CW operation (if needed)
• Software
Cooling control sequence: return air temperature, humidity, supply air temperature, dew point
21
STULZ CeilAiR Engineering Manual – 60Hz
• Networking
Capable of BMS interface or private local area network (pLAN). Capable of networking up to
eight E² controllers with an independent LAN.
The E2 controller will communicate to BMS/BAS systems via the following protocols:
–– BACnet IP
–– BACnet over Ethernet
–– BACnet MS/TP
–– Modbus IP
–– Modbus RTU
–– HTTP
–– SNMP V1, V2c
CyberLAN Networking Options
Multi-Unit Sequencing:
Multiple CyberAiR air conditioners incorporating E2 Microprocessor Controller controls can be
configured in groups of up to 8 (eight) units to allow for "N+1" redundancy/backup critical application
operation.
The E2 Microprocessor Controller is programmed to automatically change from current primary unit
operation to secondary standby unit operation via three methods:
1. Manual Changeover
2. Automatic Timed (1-30 days)
3. Automatic Changeover on Unit Failure
(if applicable):
22
STULZ CeilAiR Engineering Manual – 60Hz
The humidifier shall be an electrode steam canister type and shall have an adjustable humidity output
setting from 25 to 100% of the full rated humidifier capacity, and an automatic flush cycle that senses
the current consumption of the humidifier and controls mineral concentration of the water. A “Change
Cylinder” light shall notify service personnel when the humidification output is below rated requirements
and when maintenance is due.
Dehumidification Cycle
The ceiling air conditioner shall be provided with a refrigeration based dehumidification mode. Moisture
shall be condensed on the cooling coil and discharged through the condensate drain.
Reheat (electric, hot gas, hot water or steam) shall be provided to offset sensible cooling during the
dehumidification cycle.
23
STULZ CeilAiR Engineering Manual – 60Hz
Electric Reheat/Heat
A factory mounted and wired electric resistance heater shall be included to provide automatic sensible
reheating mode during the dehumidification cycle and automatic heating mode as required. Electric
heaters shall be provided with thermal / magnetic circuit breakers which shall protect each conductor.
The heater elements shall be mounted with supports within a frame. Included shall be one automat-
ic resetting over-temperature safety device (pilot duty), and a non-resettable over-temperature safety
device (located in main power line).
Heaters shall use fast-reacting nichrome wire heater elements which cool quickly when turned off, elim-
inating residual heat problems.
24
STULZ CeilAiR Engineering Manual – 60Hz
Remote Air
Cooled Condenser
Equalizer
Line
Scroll
Compressor
Hot Gas Evaporator Hot Gas
Reheat Valve Cooling Coil Reheat Coil
Feeler
Equalizer
Bulb Air
Line
HP LP
Flooded Flow
Head Pressure
Control Valve
Solenoid
Relief Valve
Sight
Valve
Glass
Refrigerant Refrigerant
Reclaim Port Drier / Strainer
Thermal Expansion
Liquid Refrigerant Valve
Receiver
A factory installed copper tube, aluminum fin hot gas reheat coil and valve shall be provided for auto-
matic sensible reheating mode during dehumidification cycle. Hot compressor discharge gas shall be
diverted from the condenser to the hot gas reheat coil providing energy free sensible reheating.
25
STULZ CeilAiR Engineering Manual – 60Hz
26
STULZ CeilAiR Engineering Manual – 60Hz
Steam Reheat/Heat
A factory installed copper tube, aluminum fin heat/reheat coil and 2-way control valve shall be provided
to control the flow of steam for automatic sensible reheating mode during the dehumidification cycle
and automatic heating mode as required.
(Note: Steam trap and steam piping specialties shall be provided by others not STULZ.)
27
STULZ CeilAiR Engineering Manual – 60Hz
28
STULZ CeilAiR Engineering Manual – 60Hz
The CeilAiR ceiling air conditioner shall be provided with a high static pressure belt-driven evaporator
blower to provide standard unit CFM @ ____ in. e.s.p.
(Note: Due to the probable change in standard unit blower motor horsepower for the High Static Belt-
Drive Blower option, please consult your local STULZ sales representative for the following unit specifi-
cation changes:
• Blower Motor Horsepower
• Net Cooling Capacity
• Electrical Data
• Discharge Blower Data
29
STULZ CeilAiR Engineering Manual – 60Hz
Filtration
Filter ratings are based on dust spot efficiency ratings per ASHRAE Test Standard 52-76.
Note: F2, F3 & F4 optional filters create additional static pressure and may require the High Static
Pressure Belt-Drive Option. Please consult your local Sales Representative for details.
30
STULZ CeilAiR Engineering Manual – 60Hz
Head Pressure Control: Air-Cooled - Low Ambient, 0°F, Fan Cycling / Fan Speed
The air cooled system shall incorporate a low ambient fan cycling / fan speed head pressure control for
year-round air conditioning system operation down to 0°F DB minimum ambient air temperature.
Note: 0°F fan cycling head pressure control is a standard feature for all CeilAiR air cooled condensers
and condensing units incorporating direct drive condenser fans.
31
STULZ CeilAiR Engineering Manual – 60Hz
Head Pressure Control: Air-Cooled - Low Ambient, -20°F, Variable Speed Control
(Model SCS-( ) Condensers)
The air cooled system shall incorporate a low ambient variable speed fan head pressure control for
year-round system operation down to -20°F DB minimum ambient air temperature.
32
STULZ CeilAiR Engineering Manual – 60Hz
Remote Air
Cooled Condenser
(Optional)
Scroll
Compressor Evaporator
Cooling Coil
Equalizer
HP LP
Switch Switch
Line
Flooded Relief Liquid Line
Valve Sight
Head Pressure Solenoid Valve
Glass
Control Valve
Refrigerant
Refrigerant Drier / Strainer
Liquid Refrigerant Reclaim Port Thermal Expansion
Receiver Valve
The air cooled system shall incorporate a low ambient flooded head pressure control for year-round
system operation down to -30°F DB minimum ambient air temperature.
Note: This option shall include a factory-installed crankcase heater, cold-start relay, liquid refrigerant
receiver with liquid sight level glass, and head pressure regulating valve for flooded condenser
operation.
33
STULZ CeilAiR Engineering Manual – 60Hz
Head Pressure Control: Air-Cooled - Low Ambient, head pressure regulating control valve
DX Water Cooled and Glycol Cooled systems are available with following standard (V1) and optional
(V2-V6) head pressure regulating control valves:
* = OHS-018/040 only
34
STULZ CeilAiR Engineering Manual – 60Hz
Each refrigerant circuit’s head pressure shall be controlled by a field installed 3-way water / glycol
regulating valve rated for ____ psig w.w.p. Free-Cooling mode cooling shall be controlled by a factory
installed 3-way motorized (on/off) control valve rated for ____ psig. w.w.p.
Note: Modulating (0-10 Vdc) Free-Cooling mode cooling control is optionally available via E2 Micropro-
cessor Controller controls and modulating 3-way FC control valve.
DX Water/Glycol Cooled systems with Free-Cooling are available with the following standard and op-
tional DX head pressure and Free-Cooling valve combinations:
* = OHS-018/040 only
35
STULZ CeilAiR Engineering Manual – 60Hz
Equalizer Line
Interconnecting Field
Piping by Others
Solenoid Valve
Expansion Valve
Feeler Bulb
Quench Valve
Solenoid Valve
Evaporator Coil
Hot Gas
Equalizer Line
Equalizer Line
Expansion Valve
Regulator Optional Quick
Feeler Bulb
Disconnect Typ.
Condenser Coil
The CeilAiR ceiling A/C shall incorporate a full floating hot gas bypass system to provide modulation of
the unit’s cooling capacity and evaporator coil freeze protection under low load conditions.
36
STULZ CeilAiR Engineering Manual – 60Hz
Scroll
Compressor Evaporator
Cooling Coil
High Feeler
Pressure HP Bulb
Switch Low
Equalizer
Pressure
Line
LP
Switch
Flooded
Head Pressure
Control Valve
Hot Gas
Regulator Valve
(Optional)
Refrigerant
Refrigerant Drier / Strainer
Liquid Refrigerant Reclaim Port Thermal Expansion
Receiver Valve
The CeilAiR ceiling A/C shall incorporate a snap acting hot gas bypass system to provide modulation
of the unit’s cooling capacity and evaporator coil freeze protection under low load conditions.
37
STULZ CeilAiR Engineering Manual – 60Hz
A ____-way motorized (On/Off) CW or AWS cooling control valve rated for a maximum _____ psig w.w.p. shall
be factory unit installed. Precision cooling control shall be accomplished via a spring return slow open and close
valve design.
A ____-way modulating CW or AWS cooling control valve rated for a maximum _____ psig w.w.p. shall be factory
installed. Precision cooling control shall be accomplished via a 0-10 Vdc E2 Controller analog control signal to the
proportional actuating control valve.
Chilled Water and Alternate Water Source cooling shall be controlled by the following standard and optional con-
trol valves:
38
STULZ CeilAiR Engineering Manual – 60Hz
The air conditioner shall be a dual scroll compressor system with two independent refrigeration circuits
to provide 50% capacity unloading, as well as component redundancy.
The air conditioner shall be provided with a 2-Stage temperature controller with microprocessor based
control logic for automatic staging.
39
STULZ CeilAiR Engineering Manual – 60Hz
Compressor, (belt-drive blower motor and electric heat/reheat if applicable) shall be three phase in lieu
of standard single phase. All other components (5/10 lb humidifier and direct drive motor(s)) shall be
single phase, with each leg of power supply balanced as closely as possible.
(Note: Three phase power supply is a standard feature on models OHS-048 and larger units.)
40
STULZ CeilAiR Engineering Manual – 60Hz
277 Volt
Neutral
Main Power
Distribution Block
A main power distribution block shall be located in the air conditioner’s electric box for single point pow-
er connection to a 277/1/60 power supply source. All system components (motor, heater & humidifier, if
applicable) shall be rated for operation with a 277/1/60 power supply. 277V to 208V main power step-
down transformers shall not be required.
Note: Fast-delivery orders sometimes require the OHS system be shipped from stock as 208/1/60. In
those cases, 277/1/60 applications are provided with a field-installed 277-to-208V step-down
transformer.
41
STULZ CeilAiR Engineering Manual – 60Hz
A Low-Profile condensate pump designed for limited height ceiling plenum installation shall be factory
provided for automatic removal of condensate and humidifier flush water (if applicable). The conden-
sate pump shall be field installed as a standard.
42
STULZ CeilAiR Engineering Manual – 60Hz
A heavy duty All-Metal condensate pump shall be provided for automatic removal of condensate and
humidifier flush water (if applicable).
The pump shall be constructed with a cast aluminum reservoir and impeller; aluminum reservoir cover
and impeller chamber cover; stainless steel fasteners and a stainless steel motor shaft. The conden-
sate pump meets most local codes for certification as a "plenum rated" pump. The condensate pump
shall be field installed only.
The condensate pump shall be specifically designed to operate with the higher condensate tempera-
tures caused by the flush and drain cycle of the electrode canister humidifiers.
43
STULZ CeilAiR Engineering Manual – 60Hz
The CeilAiR Low-Profile condensate pump can be factory installed as an option on models
OHS-012/040-AS, AHU, AR, W, G & C.
44
STULZ CeilAiR Engineering Manual – 60Hz
Smoke Detector
A photo-electric smoke detector shall be factory installed in the CeilAiR evaporator section on the suc-
tion side of the evaporator blower.
The smoke detector shall be rated for high air velocity applications, and shall shut down the air condi-
tioner upon sensing smoke in the return air stream.
Optional Auxiliary Contact:
An auxiliary dry-contact (n/o) terminal connection shall be provided for remote notification of a smoke
detection alarm.
45
STULZ CeilAiR Engineering Manual – 60Hz
Firestat
The air conditioner shall be provided with a factory wired and mounted firestat. The firestat shall shut
down the air conditioner upon sensing a high return air temperature.
46
STULZ CeilAiR Engineering Manual – 60Hz
Quantity 1(one) remote spot type water/leak detector per CeilAiR A/C unit shall be factory provided for
remote field installation. Upon sensing a water leak, the normally closed water detector control circuit
shall open, thereby shutting down the air conditioner’s water producing operations.
47
STULZ CeilAiR Engineering Manual – 60Hz
Quantity 2 (two) remote spot type water/leak detectors per CeilAiR A/C unit shall be factory provided for
remote field installation. Upon sensing a water leak, the normally closed water detector control circuit
shall open, thereby shutting down the air conditioner’s water producing operations..
48
STULZ CeilAiR Engineering Manual – 60Hz
A 20 ft. remote strip/cable type water/leak detector shall be factory provided for remote field installation.
In addition to the 20 ft. cable, a 24V power water detector power module shall require field mounting
and wiring to factory provided terminal connection. Upon sensing a water leak, the normally closed
water detector control circuit shall open, thereby shutting down the air conditioner’s water producing
operations.
49
STULZ CeilAiR Engineering Manual – 60Hz
Each compressor shall be provided with an acoustical sound jacket (shipped loose). Each sound jacket
shall have a snap closure system for ease of removing and re-installation during maintenance. Each
sound jacket shall have a Noise Reduction Coefficient NRC of 85 per ASTM C-423 and a Sound Trans-
mission Loss STC of 11 per ASTM E-90.
50
STULZ CeilAiR Engineering Manual – 60Hz
For Water/Glycol systems that require entering condenser water temperatures from 65°F to 45°F, the
system shall be provided with a factory installed in-line liquid refrigerant receiver to help reduce the
negative effect the low condenser source can have on the evaporator. A compressor crankcase heater
shall also be provided standard with this option. (Compressor Sound Jackets are not available with this
option due to the crankcase heater).
51
STULZ CeilAiR Engineering Manual – 60Hz
The main power service switch shall be the NEMA 3R or NEMA-12 non-fused type, depending on the
OHS model selected. The disconnect switch shall have a lockable handle.
Note: Field installed main power service switches shall be the standard option, however, switches
can be optionally factory mounted on select CeilAiR systems. Factory mounting of disconnect
switches is not available on models OHS-012, 018, 024 & 032-AS incorporating the “Ducted”
Evaporator Connection option.
52
STULZ CeilAiR Engineering Manual – 60Hz
Free-Cooling Option
(Water/Glycol Economizer Coil)
Remote Drycooler
(Optional)
Pump
(Optional)
3-Way
Valve Free-Cooling
Coil
Free-Cooling
Aqua-Stat
Equalizer
Line
Condenser Coil
Scroll
Compressor
Expansion
Valve
Refrigerant
Reclaim Coil
Sight Refrigerant
Glass Drier / Strainer
A Free-Cooling cycle shall be provided to take advantage of low ambient air temperature conditions to
provide compressor-less cooling.
When outdoor temperatures are sufficiently low (setpoint adjustable), source coolant shall be diverted
from the DX - Water or Glycol Cooled refrigerant condenser to a chilled water/glycol coil (free-cooling
coil & control valve). The drycooler capacity shall be increased by reversing the typical drycooler fan(s)
cycling sequence of operation to provide the maximum cooling effect for the coolant solution. The
free-cooling coil shall be closely sized to match the refrigerant cooling capacity to increase the number
of hours that the system can operate in the free-cooling mode, thereby increasing the operating savings
of the installation.
53
STULZ CeilAiR Engineering Manual – 60Hz
Pump
(by others)
Flow AWS
FS
Switch Control
Valve
Alternate Water
Source Aqua-Stat
Scroll
Compressor
DX - Cooling
Coil
Flooded
Feeler
Equalizer
Head Pressure
Bulb
Line
Control Valve HP LP
Relief
Valve
Sight Solenoid
Glass Valve
Refrigerant
Refrigerant
Drier / Strainer
Reclaim Port
Expansion
Receiver Valve
An Alternate Water Source cooling cycle shall be provided to utilize building chilled water supply when
available as the primary cooling cycle with DX - Air Cooled refrigerant cooling as a backup.
The air conditioner shall have two cooling systems:
1. A chilled water / glycol circuit (AWS coil & control valve)
2. A backup DX compressorized refrigerant circuit.
When chilled water is available, the system shall operate as a chilled water unit, without the compres-
sor operating. When the water temperature is too high, or the water flow rate is not sufficient, the air
conditioner shall automatically switch to the DX compressorized refrigerant operation.
54
STULZ CeilAiR Engineering Manual – 60Hz
55
STULZ CeilAiR Engineering Manual – 60Hz
Technical Specifications
DX - Self-Contained Air Cooled (AS) 3.5 - 10.5 kW / Split Air Cooled, 3.5-17.5 kW
OHS Model 012-AS/AR 018-AS/AR 024-AS/AR 032-AS/AR 040-AS/AR 048-AR 060-AR
Reheat/Heat - Performance Capacities Include Motor Heat, (Optional)
Electric Reheat / Heat - kW values are nominal
Standard Heater kW 5 5 5 5 5 10 10
Optional Heater kW N/A N/A N/A N/A N/A N/A N/A
Hot Gas Reheat:
kW (MBH) 3.3 (11.4) 5 (17) 6.2 (21.2) 7.5 (25.7) 9.1 (30.9) 14.5 (49.3) 15.9 (54.2)
Hot Water Reheat / Heat - Reheat rated @ 180°F Entering Water Temperature, EAT = 72°F DB
kW (MBH) 6.1 (20.7) 9.5 (32.4) 10.2 (34.9) 14.8 (50.4) 16.2 (55.3) 28.5 (97.1) 32.6 (111.2)
GPM 1 2 2 3 3 4 5
Coil pd. ft. 0.1 0.3 0.3 0.3 0.3 0.4 0.6
Control Motorized Motorized Motorized Motorized Motorized Motorized Motorized
Steam Reheat / Heat - nominally Reheat rated @ 5 psig Steam, EAT = 72°F DB
Nominal kW (MBH) 3.5 (12) 5.3 (18) 7 (24) 9.4 (32) 11.7 (40) 14.1 (48) 17.6 (60)
Condensate (lb/hr) 13 19 25 34 42 50 63
Control Motorized Motorized Motorized Motorized Motorized Motorized Motorized
Humidification - Electrode Steam Canister Humidifier with Adjustable Output, (Optional)
lb/hr 2-5 2-5 2-5 2-5 2-5 4-10 4-10
kW Input 1.7 1.7 1.7 1.7 1.7 3.4 3.4
Std Control Cycling Cycling Cycling Cycling Cycling Cycling Cycling
Evaporator Blower / Motor - DWDI Centrifugal
Horsepower 1/4 1/4 1/4 1/3 1/2 1 1 1/2
CFM @ e.s.p. (in. w.g.) 500 @ 0.3 750 @ 0.3 900 @ 0.3 1000 @ 0.3 1415 @ 0.3 2200 @ 0.5 2500 @ 0.5
Std. Drive Method Direct Direct Direct Direct Direct Belt Belt
Opt. Drive Method Belt Belt Belt Belt Belt N/A N/A
Evaporator Coil - Aluminum Fin, Copper Tube
Rows 3 3 3 3 3 4 4
Face Area (ft2) 2.1 2.1 2.1 2.8 2.8 5.0 5.0
Compressor - Heat pump duty rated, HCFC Ozone Safe R-407c
Type Recip. Scroll Scroll Scroll Scroll Scroll Scroll
Qty 1 1 1 1 1 1 1
kW Input 1.4 1.6 2.1 2.7 2.8 4.4 5
THR, kW (MBH) 5.2 (17.6) 7.1 (24.3) 9.2 (31.5) 11.9 (40.5) 12.8 (43.8) 20.5 (70.1) 22.7 (77.4)
Filters - 1" deep throwaway
Nominal Size (in.) 20x20 20x20 20x20 20x20 20x20 20x16 20x16
Qty 1 1 1 1 1 2 2
Connection Sizes - Copper, (Please refer to CeilAiR IOM Manual for proper interconnecting refrigerant line sizing.)
Refrigerant: (OHS-012/060-()AR only):
Liquid Line O.D. (in.) 3/8 3/8 3/8 1/2 1/2 1/2 1/2
Qty 1 1 1 1 1 1 1
Hot Gas Line O.D. (in.) 1/2 1/2 5/8 5/8 7/8 7/8 7/8
Qty 1 1 1 1 1 1 1
Condensate Drain:
O.D. (in.) 7/8 7/8 7/8 7/8 7/8 N/A N/A
FPT (in.) N/A N/A N/A N/A N/A 3/4 3/4
Humidifier Inlet O.D. (in.) 1/4 1/4 1/4 1/4 1/4 1/4 1/4
Physical Size - (Please refer to Section 6 for detailed dimensional data.)
Approx. Wt. (OHS-()-AS) (lb) 210 215 220 255 265 N/A N/A
56
STULZ CeilAiR Engineering Manual – 60Hz
DX - Self-Contained Air Cooled (AS) 3.5 - 10.5 kW / Split Air Cooled, 3.5-17.5 kW
OHS Model 012-AS/AR 018-AS/AR 024-AS/AR 032-AS/AR 040-AS/AR 048-AR 060-AR
Approx. Wt. (OHS-()-AR) (lb) 160 165 170 205 215 370 380
Notes:
Please refer to the STULZ Heat Rejection Engineering Manual for specification and performance data on Remote Outdoor and Indoor Air
Cooled Condensers used with OHS-( )-()AR Split Systems.
57
STULZ CeilAiR Engineering Manual – 60Hz
58
STULZ CeilAiR Engineering Manual – 60Hz
Refer to the STULZ Heat Rejection Engineering Manual for specification and performance data on Remote Outdoor and Indoor Air Cooled Condensers
59
STULZ CeilAiR Engineering Manual – 60Hz
60
STULZ CeilAiR Engineering Manual – 60Hz
61
STULZ CeilAiR Engineering Manual – 60Hz
62
STULZ CeilAiR Engineering Manual – 60Hz
63
STULZ CeilAiR Engineering Manual – 60Hz
64
STULZ CeilAiR Engineering Manual – 60Hz
Glycol Pump Packages - Optional - Please refer to Glycol Pump / Drycooler Engineering Manual
65
STULZ CeilAiR Engineering Manual – 60Hz
66
STULZ CeilAiR Engineering Manual – 60Hz
67
STULZ CeilAiR Engineering Manual – 60Hz
68
STULZ CeilAiR Engineering Manual – 60Hz
69
STULZ CeilAiR Engineering Manual – 60Hz
70
STULZ CeilAiR Engineering Manual – 60Hz
71
STULZ CeilAiR Engineering Manual – 60Hz
72
STULZ CeilAiR Engineering Manual – 60Hz
73
STULZ CeilAiR Engineering Manual – 60Hz
74
STULZ CeilAiR Engineering Manual – 60Hz
75
STULZ CeilAiR Engineering Manual – 60Hz
76
STULZ CeilAiR Engineering Manual – 60Hz
77
STULZ CeilAiR Engineering Manual – 60Hz
78
STULZ CeilAiR Engineering Manual – 60Hz
79
STULZ CeilAiR Engineering Manual – 60Hz
80
STULZ CeilAiR Engineering Manual – 60Hz
81
STULZ CeilAiR Engineering Manual – 60Hz
82
STULZ CeilAiR Engineering Manual – 60Hz
83
STULZ CeilAiR Engineering Manual – 60Hz
84
STULZ CeilAiR Engineering Manual – 60Hz
Gross Cooling Capacities - kW (MBH) for 42°F Chilled Water Entering the Cooling Coil
80°FDB/67°FWB
High Flow (8°F ∆Tw)
Total, kW (MBH) 7.7 (26.3) 10.5 (35.7) 11.9 (40.6) 13.6 (46.5) 17.4 (59.3) 28.2 (96.3) 30.7 (104.8) 45 (153.4) 48.5 (165.4) 56.2 (191.9)
Sensible, kW (MBH) 4.9 (16.8) 6.9 (23.4) 7.9 (27.1) 9.2 (31.4) 12 (41) 19 (64.7) 20.8 (71.1) 29.1 (99.3) 31.6 (107.9) 37.7 (128.6)
GPM 6.6 8.9 10.1 11.6 14.8 24.0 26.2 38.3 41.3 42.0
Coil pd. ft. 25.0 43.9 55.8 29.8 47.2 24.2 28.4 59.6 68.6 24.2
Med Flow (10°F ∆Tw)
Total, kW (MBH) 7.2 (24.6) 9.8 (33.5) 11.2 (38.2) 12.8 (43.7) 16.3 (55.8) 26.3 (89.7) 28.7 (97.8) 42.4 (144.6) 45.6 (155.7) 52.3 (178.6)
Sensible, kW (MBH) 4.7 (16) 6.6 (22.5) 7.6 (26) 8.8 (30) 11.5 (39.3) 18.1 (61.7) 19.9 (67.9) 27.9 (95.3) 30.3 (103.5) 35.9 (122.6)
GPM 4.9 6.7 7.6 8.7 11.1 17.9 19.6 28.9 31.2 35.8
Coil pd. ft. 14.8 25.8 32.9 17.6 27.7 14.1 16.6 35.7 41.0 14.1
Total, kW (MBH) 6.6 (22.7) 9.1 (31.2) 10.5 (35.8) 11.8 (40.4) 15.3 (52.3) 23.8 (81.3) 17.5 (59.6) 39.7 (135.6) 42.9 (146.3) 47.5 (162)
Sensible, kW (MBH) 4.4 (15.2) 6.3 (21.4) 7.3 (24.9) 8.3 (28.5) 11 (37.6) 17 (57.9) 18.8 (64.2) 26.7 (91.3) 29.1 (99.3) 33.7 (115.2)
GPM 3.8 5.2 6.0 6.7 8.7 13.6 15.0 22.6 24.5 27.2
Coil pd. ft. 9.1 16.1 20.8 10.9 17.6 8.4 10.1 22.7 26.3 8.4
75°FDB/62.5°FWB
High Flow (8°F ∆Tw)
Total, kW (MBH) 5.7 (19.5) 7.8 (26.8) 9 (30.6) 10.3 (35.2) 13.2 (45.2) 21.1 (72.1) 23.2 (79.1) 33.9 (115.7) 36.5 (124.7) 42.1 (143.5)
Sensible, kW (MBH) 4.2 (14.4) 6 (20.3) 6.9 (23.6) 8 (27.1) 10.5 (35.8) 16.5 (56.2) 18.2 (62.1) 25.2 (86.1) 27.5 (93.7) 32.7 (111.7)
GPM 4.9 6.7 7.6 8.8 11.3 18.1 19.9 28.9 31.2 36.2
Coil pd. ft. 14.5 25.9 33.2 17.9 28.4 14.3 17.1 35.8 41.1 14.3
Total, kW (MBH) 5.2 (17.9) 7.3 (24.8) 8.4 (28.6) 9.5 (32.5) 12.4 (42.3) 19.1 (65.3) 21.1 (72) 31.9 (108.8) 34.3 (117.1) 38.1 (129.9)
85
STULZ CeilAiR Engineering Manual – 60Hz
Gross Cooling Capacities - kW (MBH) for 42°F Chilled Water Entering the Cooling Coil
Sensible, kW (MBH) 4 (13.6) 5.7 (19.4) 6.6 (22.5) 7.5 (25.7) 10 (34.2) 15.5 (52.8) 17.2 (58.6) 24.3 (82.8) 26.4 (90) 30.7 (104.9)
GPM 3.6 5.0 5.7 6.5 8.5 13.1 14.5 21.8 23.5 26.2
Coil pd. ft. 8.2 15.1 19.3 10.2 16.7 7.9 9.6 21.4 24.5 7.9
Total, kW (MBH) 4.8 (16.4) 6.7 (22.9) 7.8 (26.7) 8.8 (29.9) 11.4 (39.1) 17.3 (58.9) 19.1 (65.2) 29.7 (101.5) 32.3 (110.2) 34.3 (117.1)
Sensible, kW (MBH) 3.8 (12.9) 5.4 (18.4) 6.3 (21.4) 7.1 (24.4) 9.5 (32.5) 14.5 (49.4) 16.1 (55) 23.2 (79.2) 25.4 (86.6) 28.8 (98.2)
GPM 2.8 3.8 4.4 5.0 6.5 9.9 11.0 17.0 18.5 19.8
Coil pd. ft. 5.0 9.2 11.9 6.3 10.2 4.7 5.7 13.6 15.8 4.7
72°FDB/60°FWB
High Flow (8°F ∆Tw)
Total, kW (MBH) 4.7 (16.1) 6.6 (22.4) 7.5 (25.8) 8.7 (29.6) 11.2 (38.4) 17.6 (59.9) 19.3 (65.9) 28.7 (97.8) 30.9 (105.3) 34.9 (119.2)
Sensible, kW (MBH) 3.8 (13) 5.4 (18.5) 6.3 (21.5) 7.2 (24.6) 9.6 (32.7) 14.9 (50.8) 16.5 (56.3) 23 (78.6) 25.1 (85.5) 29.6 (101)
GPM 4.1 5.7 6.4 7.4 9.6 15.1 16.6 24.5 26.4 30.2
Coil pd. ft. 10.4 19.0 24.0 13.0 21.0 10.2 12.3 26.4 30.3 10.2
Total, kW (MBH) 4.3 (14.8) 6.1 (20.7) 7 (23.9) 7.9 (27.1) 10.4 (35.4) 15.8 (53.9) 17.4 (59.5) 27 (92) 29.1 (99.2) 31.4 (107.1)
Sensible, kW (MBH) 3.6 (12.3) 5.1 (17.5) 6 (20.4) 6.8 (23.2) 9.1 (31) 13.9 (47.5) 15.4 (52.7) 22.2 (75.6) 24.1 (82.4) 27.6 (94.3)
GPM 3.0 4.2 4.8 5.4 7.1 10.8 12.0 18.5 20.0 21.6
Coil pd. ft. 5.9 10.8 14.0 7.4 12.1 5.6 6.8 15.8 18.2 5.6
Total, kW (MBH) 4 (13.5) 5.6 (19) 6.4 (22) 7.3 (24.9) 9.5 (32.5) 13.9 (47.4) 15.3 (52.2) 24.9 (84.9) 27 (92.2) 27.6 (94.1)
Sensible, kW (MBH) 3.4 (11.6) 4.8 (16.5) 5.7 (19.3) 6.4 (21.9) 8.5 (29.1) 12.8 (43.5) 14.1 (48.2) 21.1 (71.9) 23 (78.5) 25.3 (86.3)
GPM 2.3 3.2 3.7 4.2 5.4 8.0 8.8 14.2 15.5 16.0
Coil pd. ft. 3.4 6.6 8.6 4.5 7.3 3.2 3.8 9.9 11.4 3.2
Gross Cooling Capacities - kW (MBH) for 50°F Chilled Water Entering the Cooling Coil
80°FDB/67°FWB
High Flow (8°F ∆Tw)
Total, kW (MBH) 5.1 (17.3) 7 (23.7) 7.9 (27.1) 9.2 (31.6) 11.8 (40.3) 18.8 (64.2) 20.5 (69.8) 30.1 (102.6) 32.5 (110.9) 37.4 (127.6)
Sensible, kW (MBH) 3.8 (13) 5.4 (18.4) 6.3 (21.4) 7.2 (24.7) 9.5 (32.6) 15 (51.2) 16.5 (56.4) 22.8 (77.6) 24.8 (84.8) 29.8 (101.6)
GPM 4.4 6.0 6.8 7.9 10.1 16.1 17.6 25.7 27.9 32.2
Coil pd. ft. 11.6 20.6 26.0 14.5 22.7 11.4 13.4 28.3 32.7 11.4
Total, kW (MBH) 4.7 (15.9) 6.5 (22.1) 7.4 (25.4) 8.5 (29.1) 10.8 (36.8) 17.2 (58.7) 19 (64.8) 28.3 (96.4) 30.5 (104) 34.2 (116.7)
Sensible, kW (MBH) 3.6 (12.3) 5.2 (17.6) 6 (20.5) 6.9 (23.5) 9.2 (31.3) 14.2 (48.5) 15.8 (53.9) 22 (74.9) 23.9 (81.7) 28.2 (96.4)
GPM 3.2 4.5 5.1 5.8 7.6 11.8 13.1 19.4 21.0 23.6
Coil pd. ft. 6.5 12.0 15.3 8.2 13.4 6.4 7.8 16.9 19.5 6.4
Total, kW (MBH) 4.3 (14.6) 6 (20.4) 6.9 (23.7) 7.8 (26.8) 10.3 (35.1) 15.5 (52.9) 17.1 (58.5) 26.7 (91) 28.7 (97.9) 30.8 (105)
Sensible, kW (MBH) 3.4 (11.7) 4.9 (16.8) 5.8 (19.6) 6.5 (22.3) 8.7 (29.8) 13.3 (45.5) 14.8 (50.5) 21.2 (72.4) 23.1 (78.8) 26.5 (90.3)
GPM 2.5 3.4 4.0 4.5 5.9 8.9 9.9 15.3 16.4 17.8
Coil pd. ft. 4.0 7.4 9.7 5.1 8.3 3.8 4.6 10.9 12.5 3.8
86
STULZ CeilAiR Engineering Manual – 60Hz
Gross Cooling Capacities - kW (MBH) for 50°F Chilled Water Entering the Cooling Coil
75°FDB/62.5°FWB
High Flow (8°F ∆Tw)
Total, kW (MBH) 3.5 (12.1) 4.9 (16.7) 5.6 (19.2) 6.6 (22.4) 8.4 (28.8) 12.8 (43.6) 13.3 (45.4) 22.1 (75.5) 23.7 (80.9) 25.3 (86.5)
Sensible, kW (MBH) 3.2 (11) 4.6 (15.6) 5.3 (18.2) 6.1 (20.9) 8.1 (27.6) 12.4 (42.4) 13.3 (45.4) 19.9 (67.8) 21.6 (73.6) 24.7 (84.2)
GPM 3.1 4.2 4.8 5.7 7.2 11.0 11.5 19.0 20.4 22.0
Coil pd. ft. 6.1 10.9 14.0 7.8 12.3 5.6 6.1 16.3 18.6 5.6
Total, kW (MBH) 3.2 (10.9) 4.4 (14.9) 5 (17) 5.8 (19.9) 6.9 (23.4) 10.6 (36.1) 11.7 (40) 21 (71.7) 22.3 (76.3) 20.9 (71.4)
Sensible, kW (MBH) 3 (10.3) 4.2 (14.4) 4.9 (16.7) 5.7 (19.3) 6.9 (23.4) 10.6 (36.1) 11.7 (40) 19.2 (65.4) 20.7 (70.6) 20.9 (71.4)
GPM 2.2 3.0 3.4 4.0 4.8 7.3 8.2 14.4 15.4 14.6
Coil pd. ft. 3.3 5.8 7.4 4.2 5.7 2.7 3.3 9.9 11.2 2.7
Sensible, kW (MBH) 2.6 (8.7) 3.6 (12.4) 4.2 (14.4) 4.5 (15.4) 6 (20.4) 8.8 (30) 9.8 (33.4) 15.9 (54.3) 17.4 (59.3) 17.4 (59.3)
GPM 1.5 2.1 2.4 2.6 3.5 5.1 5.7 9.2 10.0 10.2
Coil pd. ft. 1.3 2.9 3.9 1.7 3.1 1.2 1.6 4.4 5.1 1.2
72°FDB/60°FWB
High Flow (8°F ∆Tw)
Total, kW (MBH) 2.6 (9) 3.7 (12.7) 4.3 (14.8) 4.8 (16.2) 6.3 (21.5) 9.8 (33.6) 10.9 (37.2) 16.3 (55.6) 17.7 (60.5) 19.5 (66.4)
Sensible, kW (MBH) 2.6 (9) 3.7 (12.7) 4.3 (14.8) 4.8 (16.2) 6.3 (21.5) 9.8 (33.6) 10.9 (37.2) 16.3 (55.6) 17.7 (60.5) 19.5 (66.4)
GPM 2.3 3.2 3.7 4.1 5.5 8.5 9.5 14.1 15.4 17.0
Coil pd. ft. 3.5 6.6 8.7 4.3 7.3 3.5 4.3 9.5 11.1 3.5
Total, kW (MBH) 2.3 (7.9) 3.3 (11.3) 3.8 (13.1) 4.1 (14.1) 5.5 (18.6) 8.2 (27.9) 9.1 (30.9) 14.5 (49.3) 15.8 (53.8) 16.1 (55.1)
Sensible, kW (MBH) 2.3 (7.9) 3.3 (11.3) 3.8 (13.1) 4.1 (14.1) 5.5 (18.6) 8.2 (27.9) 9.1 (30.9) 14.5 (49.3) 15.8 (53.8) 16.1 (55.1)
GPM 1.6 2.3 2.7 2.9 3.8 5.7 6.4 10.0 11.0 11.4
Coil pd. ft. 1.6 3.5 4.6 2.1 3.7 1.6 2.0 5.1 6.0 1.6
Total, kW (MBH) 2 (6.7) 2.8 (9.6) 3.3 (11.1) 3.4 (11.5) 4.5 (15.3) 6.1 (20.9) 6.8 (23.4) 12.1 (41.4) 13.3 (45.3) 12 (41.1)
Sensible, kW (MBH) 2 (6.7) 2.8 (9.6) 3.3 (11.1) 3.4 (11.5) 4.5 (15.3) 6.1 (20.9) 6.8 (23.4) 12.1 (41.4) 13.3 (45.3) 12 (41.1)
GPM 1.1 1.6 1.9 2.0 2.6 3.6 4.1 7.0 7.7 7.2
Coil pd. ft. 0.7 1.6 2.3 0.8 1.7 0.5 0.7 2.7 3.2 0.5
(Note: The above Cooling capacities @ standard CFM/e.s.p. as shown on page 79, Evaporator Blower/Motor.)
87
STULZ CeilAiR Engineering Manual – 60Hz
88
STULZ CeilAiR Engineering Manual – 60Hz
89
STULZ CeilAiR Engineering Manual – 60Hz
90
STULZ CeilAiR Engineering Manual – 60Hz
91
STULZ CeilAiR Engineering Manual – 60Hz
Notes
1. Electrical Data is based on standard performance and component selection per Section 4 of this
brochure. Please consult your local Sales Representative for "special" equipment electrical data.
2. Electrical data is the same for horizontal and standard discharge cabinets.
3. High Static Pressure Belt-Drive Option - Electrical Data in the pages to follow are based on Stan-
dard CFMs and External Static Pressures. Please Consult your local Sales Representative for
component and electrical rating data for this Option.
4. Current Draws in the following tables are specified as:
FLA = Full Load Amps
MCA = Minimum Circuit Amps (wire size amps)
MFS = Maximum Fuse Size
5. The A-Tech-1.2 and E2 Microprocessor Controller controls provide two compressor stages of Cool-
ing and one compressor stage of Dehumidification. Therefore, electrical data for dual compressor
systems with dehumidification mode (reheat) is controller dependent as shown above.
92
STULZ CeilAiR Engineering Manual – 60Hz
93
STULZ CeilAiR Engineering Manual – 60Hz
94
STULZ CeilAiR Engineering Manual – 60Hz
95
STULZ CeilAiR Engineering Manual – 60Hz
96
STULZ CeilAiR Engineering Manual – 60Hz
97
STULZ CeilAiR Engineering Manual – 60Hz
98
STULZ CeilAiR Engineering Manual – 60Hz
99
STULZ CeilAiR Engineering Manual – 60Hz
COOLING AND CONDENSATE PUMP only, with or without Hot Gas, Hot Water or Steam Reheat
208/1/60 18.6 15.9 19.4 27.7 40 18.6 15.9 19.4 27.7 40 N/A N/A
277/1/60 15.8 13.5 16.5 23.1 35 15.8 13.5 16.5 23.1 35 N/A N/A
208/3/60 13.4 12 13.8 20.1 30 13.4 12 13.8 20.1 30 19.3 16.8 20.1 27.7 40 25.7 22.4 26.7 32.3 50
460/3/60 6.8 6.1 7 10.6 15 6.8 6.1 7 10.6 15 9.9 8.7 10.3 13.3 20 11.4 10 11.8 15.3 20
COOLING, CONDENSATE PUMP, and ELECTRIC REHEAT/HEAT only, (No Humidifier)
208/1/60 40 37.3 40.8 54.4 60 40 37.3 40.8 54.4 60 N/A N/A
277/1/60 33.9 31.6 34.6 45.7 50 33.9 31.6 34.6 45.7 50 N/A N/A
208/3/60 25.8 24.4 26.2 35.6 40 25.8 24.4 26.2 35.6 40 44 41.5 44.8 58.6 60 50.4 47.1 51.4 63.2 70
460/3/60 13.1 12.4 13.3 18.5 20 13.1 12.4 13.3 18.5 20 22.5 21.3 22.9 29.1 30 24 22.6 24.4 31.1 35
COOLING, CONDENSATE PUMP, and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat)
208/1/60 26.8 24.1 27.6 35.9 50 26.8 24.1 27.6 35.9 50 N/A N/A
277/1/60 21.9 19.6 22.6 29.2 40 21.9 19.6 22.6 29.2 40 N/A N/A
208/3/60 21.6 20.2 22 28.3 40 21.6 20.2 22 28.3 40 35.6 33.1 36.4 44 60 42 38.7 43 48.6 60
460/3/60 10.5 9.8 10.7 14.3 20 10.5 9.8 10.7 14.3 20 17.3 16.1 17.7 20.7 25 18.8 17.4 19.2 22.7 30
COOLING, CONDENSATE PUMP, ELECTRIC REHEAT/HEAT and HUMIDIFIER
208/1/60 40 37.3 40.8 54.4 60 40 37.3 40.8 54.4 60 N/A N/A
277/1/60 33.9 31.6 34.6 45.7 50 33.9 31.6 34.6 45.7 50 N/A N/A
208/3/60 25.8 24.4 26.2 35.6 40 25.8 24.4 26.2 35.6 40 44 41.5 44.8 58.6 60 50.4 47.1 51.4 63.2 70
460/3/60 13.1 12.4 13.3 18.5 20 13.1 12.4 13.3 18.5 20 22.5 21.3 22.9 29.1 30 24 22.6 24.4 31.1 35
100
STULZ CeilAiR Engineering Manual – 60Hz
101
STULZ CeilAiR Engineering Manual – 60Hz
102
STULZ CeilAiR Engineering Manual – 60Hz
Chilled Water
With Condensate Pump (OHS-012 − OHS-040)
OHS-012-C OHS-018-C OHS-024-C OHS-032-C OHS-040-C
Model
FLA MCA MFS FLA MCA MFS FLA MCA MFS FLA MCA MFS FLA MCA MFS
COOLING AND CONDENSATE PUMP only, with or without Hot Gas, Hot Water or Steam Reheat
208/1/60 3.9 4.9 15 3.9 4.9 15 3.9 4.9 15 4.6 5.8 15 5.9 7.4 15
277/1/60 3 3.8 15 3 3.8 15 3 3.8 15 3.5 4.4 15 4.6 5.8 15
208/3/60 3.9 4.9 15 3.9 4.9 15 3.9 4.9 15 4.6 5.8 15 5.9 7.4 15
460/3/60 2 2.6 15 2 2.6 15 2 2.6 15 2 2.6 15 2.7 3.4 15
COOLING, CONDENSATE PUMP, and ELECTRIC REHEAT/HEAT only, (No Humidifier)
208/1/60 25.3 31.6 35 25.3 31.6 35 25.3 31.6 35 26 32.5 35 27.3 34.1 35
277/1/60 21.1 36.4 30 21.1 36.4 30 21.1 36.4 30 21.6 27 30 22.7 28.4 30
208/3/60 16.3 20.4 25 16.3 20.4 25 16.3 20.4 25 17 21.3 25 18.3 22.9 25
460/3/60 8.3 10.4 15 8.3 10.4 15 8.3 10.4 15 8.3 10.4 15 9 11.3 15
COOLING, CONDENSATE PUMP, and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric
Reheat/Heat)
208/1/60 12.1 15.1 20 12.1 15.1 20 12.1 15.1 20 12.8 16 20 14.1 17.6 20
277/1/60 9.1 11.4 15 9.1 11.4 15 9.1 11.4 15 9.6 12 15 10.7 13.4 15
208/3/60 12.1 15.1 20 12.1 15.1 20 12.1 15.1 20 12.8 16 20 14.1 17.6 20
460/3/60 5.7 7.2 15 5.7 7.2 15 5.7 7.2 15 5.7 7.2 15 6.4 8.1 15
COOLING, CONDENSATE PUMP, ELECTRIC REHEAT/HEAT and HUMIDIFIER
208/1/60 33.5 41.9 45 33.5 41.9 45 33.5 41.9 45 34.2 42.8 45 35.5 44.4 45
277/1/60 27.2 34 35 27.2 34 35 27.2 34 35 27.7 34.6 35 28.8 36 40
208/3/60 24.5 30.6 35 24.5 30.6 35 24.5 30.6 35 25.2 31.5 35 26.5 33.1 35
460/3/60 12 15.1 20 12 15.1 20 12 15.1 20 12 15.1 20 12.7 15.9 20
103
STULZ CeilAiR Engineering Manual – 60Hz
104
STULZ CeilAiR Engineering Manual – 60Hz
105
STULZ CeilAiR Engineering Manual – 60Hz
106
STULZ CeilAiR Engineering Manual – 60Hz
"A" = Suction Line, inches OD Copper Note-1: ----- means connection type not applicable to this unit configu-
"B" = Liquid Line, inches OD Copper ration.
"C" = Hot Gas, inches OD Copper
Note-2: Dimensions shown represent the "pipe connection size" only.
For information detailing the sizing of the interconnecting refrigerant
and water lines, please refer to the CeilAiR Installation, Operation and
Maintenance Manual.
Legend:
107
STULZ CeilAiR Engineering Manual – 60Hz
DIMENSIONAL DATA
MODEL "A" "B" "C" "D" "E" "F" OHS-012 thru 032-AS Self-Con-
OHS-012, 018,& 024-AS 20.38" 15.5" 5.75" 18.0" 19.75" 16.13" tained, Air Cooled ("Ducted"
OHS-032-AS 26.38" 21.5" 10.88" 23.0" 15.63" 19.75" Evap - Direct Driven)
OHS-040-AS Self-Contained,
Air Cooled ("Ductless" Spot
Cooler)
108
STULZ CeilAiR Engineering Manual – 60Hz
OHS-040-HAS Self-Contained,
Air Cooled ("Ducted" Version -
Direct Driven)
DIMENSIONAL DATA
OHS-012 thru 032-AR Remote
MODEL "A"
OHS-012, 018,& 024-AR 20.38"
Air Cooled, Evaporator ("Duct-
OHS-032-AR 26.38" less" Spot Cooler)
DIMENSIONAL DATA
OHS-012 thru 032-AR Remote
MODEL "A" "B" "E" "F"
Air Cooled, Evaporator ("Ducted" OHS-012, 018,& 024-AR 20.38" 15.5" 19.75" 16.13"
Version - Direct Driven) OHS-032-AR 26.38" 21.5" 15.63" 19.75"
109
STULZ CeilAiR Engineering Manual – 60Hz
DIMENSIONAL DATA
MODEL "A" "B" "C" "L" "M"
OHS-012 thru 040-HAR Remote Air
OHS-012, 018, & 024- see see see Cooled, Evaporator "H-Series Ducted
20.0" 16.0"
HAR note note note Version" (040 - Direct Driven) & (012/040
see see see
OHS-032- & 040-HAR 24.0" 20.0"
note note note
- Belt Driven)
OHS-040-HAR @ 0.3"
24.0" 20.0" 6.62" 11.38" 10.5"
esp (direct drive blower)
DIMENSIONAL DATA
OHS-048 thru 060-AR Remote MODEL "C" "L" "M"
Air Cooled, Evaporator (Ducted OHS-040 & 060-AR 6.62" 11.38" 13.12"
Only)
110
STULZ CeilAiR Engineering Manual – 60Hz
DIMENSIONAL DATA
OHS-120-DAR Remote Air
MODEL "C" "L" "M"
Cooled, Evaporator (DUAL Com-
OHS-120-DAR 7.25" 13.44" 15.62" pressors)
111
STULZ CeilAiR Engineering Manual – 60Hz
DIMENSIONAL DATA
MODEL "A"
OHS-012, 018, &
20.7"
024-AHU
OHS-032 & 040-AR 26.7"
DIMENSIONAL DATA
OHS-012 thru 040-HAHU DX - MODEL "A" "E" "F" "C" "L" "M"
"H-Series", Air Handling Unit ("Duct- OHS-012, 018, &
20.0" 19.75" 15.63"
see see see
024-AHU note note note
ed Version" - Belt Driven)
see see see
OHS-032 & 040-AHU 24.0" 19.75" 19.75"
note note note
112
STULZ CeilAiR Engineering Manual – 60Hz
DIMENSIONAL DATA
OHS-048 thru 060-AHU DX - Air Std CFM @ 0.5" esp
MODEL
Handling Unit (Ducted Only) "C" "L" "M"
OHS-048 & 060-AHU 6.62" 11.38" 13.12"
DIMENSIONAL DATA
OHS-120-DAHU DUAL Circuit, DX Std CFM @ 0.5" esp
MODEL
- Air Handling Unit (Ducted Only) "C" "L" "M"
OHS-120-DAHU 7.38" 13.5" 15.69"
113
STULZ CeilAiR Engineering Manual – 60Hz
Water/Glycol Systems
OHS-012 thru 032-W / G DIMENSIONAL DATA
Self-Contained, Water/Glycol MODEL "A"
OHS-012, 018, & 024 W/G 20.4"
Cooled ("Ductless" Spot Cooler) OHS-032-W/G 26.4"
DIMENSIONAL DATA
MODEL "A" "B" "E" "F"
OHS-012 thru 032-W / G Self-Con-
OHS-012, 018, & 024-W/G 20.4" 15.5" 19.75" 16.13" tained, Water/Glycol Cooled
OHS-032-W/G 26.4" 21.5" 15.63" 19.75" ("Ducted Version" - Direct Drive)
OHS-040-W / G Self-Contained,
Water/Glycol Cooled ("Ductless"
Spot Cooler)
114
STULZ CeilAiR Engineering Manual – 60Hz
DIMENSIONAL DATA
OHS-012 thru 040-HW / HG & optional MODEL "A" "B" "C" "L" "M"
OHS-012 thru 040-HW/HG-FC "H-Series OHS-012, 018, & 024-
20.0" 16.0"
see see see
HW/HG (& HW/HG-FC) note note note
Ducted Version" (040 - Direct Driven) & OHS-032, & 040-HW/
see see see
(012/040 - Belt Driven) HG 24.0" 20.0"
note note note
(& HW/HG-FC)
OHS-040-HW/G @
0.3" esp (Direct-Drive 24.0" 20.0" 6.62" 11.38" 10.5"
Blower)
DIMENSIONAL DATA
Std CFS @ 0.5" esp
OHS-048 thru 060-W / G & op-
MODEL
"C" "L" "M" tional OHS-048 thru 060-W/G-FC
OHS-048, & 060-W/G 6.62" 11.38" 13.12" Self-Contained, Water/Glycol
OHS-048, & 060-W/G-FC
see see see Cooled (Ducted Only)
note note note
115
STULZ CeilAiR Engineering Manual – 60Hz
DIMENSIONAL DATA
Std CFS @ 0.5" esp
OHS-048 thru 084-DW / DG & optional MODEL
"C" "L" "M"
W/DG-FC Self-Contained, Water/Gly- OHS-048-DW/DG 6.62" 11.38" 13.19"
col Cooled (DUAL Compressors) OHS-072-084-DW/DG 7.62" 13.5" 15.69"
OHS-048/084-DW/ see see see
DG-FC note note note
116
STULZ CeilAiR Engineering Manual – 60Hz
117
STULZ CeilAiR Engineering Manual – 60Hz
DIMENSIONAL DATA
MODEL "A" "B" "E" "F" OHS-012 thru 040-C Chilled
OHS-012, 018, & 024-C 20.4" 15.5" 19.75" 15.63" Water System ("Ducted Version"
OHS-032, & 040-C 26.4" 21.5" 15.63" 19.75" - Direct Driven)
DIMENSIONAL DATA
OHS-012 thru 040-HC "H-Se- MODEL "A" "E" "F" "C" "L" "M"
ries", Chilled Water System OHS-012, 018, & 024-HC 20.0" 19.75" 15.63"
SEE
NOTE
SEE
NOTE
SEE
NOTE
("Ducted Version" - Belt Driven) SEE SEE SEE
OHS-032, & 040-HC 24.0" 19.75" 19.75"
NOTE NOTE NOTE
118
STULZ CeilAiR Engineering Manual – 60Hz
DIMENSIONAL DATA
Std CFS @ 0.5" esp
MODEL
"C" "L" "M"
OHS-048 & 060-C 6.62" 11.38" 13.12"
DIMENSIONAL DATA
Std CFS @ 0.5" esp
OHS-072 thru 084-C Chilled
MODEL
"C" "L" "M" Water System ("Ducted" - Belt
OHS-072 & 084-C 7.62" 13.5" 15.69" Driven)
DIMENSIONAL DATA
OHS-120-C Chilled Water Sys- MODEL
Std CFS @ 0.5" esp
"C" "L" "M"
tem ("Ducted" - Belt Driven) OHS-120-C 7.38" 13.5" 15.7"
119
STULZ CeilAiR Engineering Manual – 60Hz