QUICK RESPONSE
AUTOMATIC SPRINKLER
MODEL GL5606
ONE INCH ADJUSTABLE
FLAT PLATE CONCEALED PENDENT
DESCRIPTION AND OPERATION
The Globe Quick Response GL5606 Adjustable Concealed Pendent Sprinkler has a low profile,
aesthetically pleasing design. It provides sprinkler operations approximately six times faster than
ordinary sprinklers and can be installed wherever standard concealed spray sprinklers are specified
when allowed by the applicable standards. This sprinkler offers the additional feature of greatly in-
creased safety to life and should be used advisedly and under the direction of approving authorities
having jurisdiction. The sprinkler is available with a nominal 1" of adjustment and a low profile cover
plate assembly. All that is seen at the ceiling is a 3 5/16" diameter ceiling plate or an optional 2 3/4"
diameter ceiling plate color finished to match the specifier's exact requirements. The GL Series
Concealed Sprinkler may be virtually invisible as it does not interrupt the "smooth flow" of the ceiling.
Globe's GL5606 Concealed Sprinkler utilizes a 3mm frangible glass ampule which is located above
the ceiling and concealed from view by the ceiling plate.
The provided protective cap needs to be removed in order to install the sprinkler with the proper
wrench. The protective cap must be replaced on the sprinkler until the time the cover plate is to be
installed. The "push on - screw off" designed cover plate is easily installed and with a nominal 1" of
adjustment makes it easier to get a proper fit at the ceiling.
Operation of the sprinkler occurs when heat build up causes the solder holding the cover plate
to the support shell to melt allowing the cover plate to fall clear. Continued heat build up causes the
3mm glass bulb to burst allowing the deflector to drop down and distribute water in an approved
pattern to extinguish or control the fire.
TECHNICAL DATA
See reverse side for Approvals and Specifications.
Temperature Ratings -
135°F (57°C) Sprinkler, 135°F (57°C) Cover Plate
155°F (68°C) Sprinkler, 135°F (57°C) Cover Plate
155°F (68°C) Sprinkler, 155°F (68°C) Cover Plate 3 5/16” diameter plate
175°F (79°C) Sprinkler, 155°F (68°C) Cover Plate
200°F (93°C) Sprinkler, 155°F (68°C) Cover Plate
Water Working Pressure Rating - 175 psi (12 Bars)
Factory tested hydrostatically to 500 psi (34 Bars)
Maximum low temperature glass bulb rating is -67°F (-55°C)
Frame - bronze Deflector - brass Screw - brass
Lodgement Wire - stainless steel Bulb seat - copper 2 3/4” diameter plate
Spring - nickel alloy Seal - teflon Drop Pin - stainless steel QUICK RESPONSE
Bulb - glass with alcohol based solution, 3mm size WHITE FLAT PLATE
Cover Plate - brass Upper Escutcheon Assembly - steel CONCEALED PENDENT
NOTE: Globe’s wrench P/N 332765 must be used to install this sprinkler.
SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
AVAILABLE SPRINKLER N.F.P.A. MAXIMUM CEILING
CLASSIFICATION BULB COLOR
TEMPERATURES TEMPERATURE
APPROVALS
135°F (57°C) Flat Cover Plate 155°F (68°C) Flat Cover Plate NYC-DOB
SIN
STYLE
MODEL HAZARD1 **135°F (57°C) 155°F (68°C) **155°F (68°C) 175°F (79°C) 200°F (93°C) cULus *FM MEA
Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler 101-92-E
Adjustable
Concealed GL5606 LH/OH X X X X X X X X
Pendent
1
SPRINKLERS SHALL BE LIMITED AS PER THE REQUIREMENTS OF NFPA13 AND ANY OTHER RELATED DOCUMENTS.
*FM APPROVED AS STANDARD RESPONSE
**NO FM APPROVALS
OH: ORDINARY HAZARD
LH: LIGHT HAZARD
CROSS SECTIONS
2 1/4" DIA. MIN. 2 1/4" DIA. MIN.
HOLE IN CEILING HOLE IN CEILING
1 7/8" DIA. 1 7/8" DIA.
CUP CUP
2 3/4" MAX. 2 3/4" MAX.
1 7/8" MIN. 1 7/8" MIN.
CEILING CEILING
2 3/4" DIA. 3 5/16" DIA. 1/8"
1/8"
FLAT COVER PLATE FLAT COVER PLATE