INPUTS PAGE 0 OF 114 FIRST PAGE - COVER OUTPUTS

DMH Ltd - Exploration & Production Division - LNBR/NCDI


Raventown District

"BONNIE & CLYDE" NATURAL GAS PLATFORMS FIELD

"MARTHA CLUSTER" PLATFORM

FIRE&GAS ESD PES REPLACEMENT

HIMA PES H41q - HS FAMILY

APPLICATION PROGRAM

G.D.C. of GIOVANNI DE CESARE


Tax code: DCSGNN64E31F205K
VAT code: _
Registered office: 31/A Romagna Avenue - I-20092 Cinisello Balsamo (MI), Italy
Offices and operations unit: 76 Asiago Street - I-20128 Milano, Italy
Tel./Fax. +39.0266594742
Mob. +39.3281708850
E-mail: [email protected]
Project developed by: GDC
3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/0
1 check Martha Cluster MARTHA PLATF PES page 1
revision date name status: LZ based replaced replaced FIRST PAGE - COVER
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 1 OF 114 SECOND PAGE - INDEX (PAGE 1 OF 3) OUTPUTS

PAGE 0 OF 114 FIRST PAGE - COVER


PAGE 1 OF 114 SECOND PAGE - INDEX (PAGE 1 OF 3)
PAGE 2 OF 114 THIRD PAGE - INDEX (PAGE 2 OF 3)
PAGE 3 OF 114 FOURTH PAGE - INDEX (PAGE 3 OF 3)
PAGE 4 OF 114 FIFTH PAGE - NOTES AND DESCRIPTIONS
PAGE 5 OF 114 SIXTH PAGE - REVISIONS INDEX AND DESCRIPTIONS
PAGE 6 OF 114 UTILITIES FUNCTIONS
PAGE 7 OF 114 SYSTEM DIAGNOSTIC (PAGE 1 OF 4)
PAGE 8 OF 114 SYSTEM DIAGNOSTIC (PAGE 2 OF 4)
PAGE 9 OF 114 SYSTEM DIAGNOSTIC (PAGE 3 OF 4)
PAGE 10 OF 114 SYSTEM DIAGNOSTIC (PAGE 4 OF 4)
PAGE 11 OF 114 DIGITAL INPUTS/OUTPUTS MODULES DIAGNOSTIC (PAGE 1 OF 2)
PAGE 12 OF 114 DIGITAL INPUTS/OUTPUTS MODULES DIAGNOSTIC (PAGE 2 OF 2)
PAGE 13 OF 114 DIGITAL OUTPUTS MODULES CHANNELS DIAGNOSTIC (PAGE 1 OF 9)
PAGE 14 OF 114 DIGITAL OUTPUTS MODULES CHANNELS DIAGNOSTIC (PAGE 2 OF 9)
PAGE 15 OF 114 DIGITAL OUTPUTS MODULES CHANNELS DIAGNOSTIC (PAGE 3 OF 9)
PAGE 16 OF 114 DIGITAL OUTPUTS MODULES CHANNELS DIAGNOSTIC (PAGE 4 OF 9)
PAGE 17 OF 114 DIGITAL OUTPUTS MODULES CHANNELS DIAGNOSTIC (PAGE 5 OF 9)
PAGE 18 OF 114 DIGITAL OUTPUTS MODULES CHANNELS DIAGNOSTIC (PAGE 6 OF 9)
PAGE 19 OF 114 DIGITAL OUTPUTS MODULES CHANNELS DIAGNOSTIC (PAGE 7 OF 9)
PAGE 20 OF 114 DIGITAL OUTPUTS MODULES CHANNELS DIAGNOSTIC (PAGE 8 OF 9)
PAGE 21 OF 114 DIGITAL OUTPUTS MODULES CHANNELS DIAGNOSTIC (PAGE 9 OF 9)
PAGE 22 OF 114 HARDWIRED DIGITAL INPUTS ELABORATION (PAGE 1 OF 7)
PAGE 23 OF 114 HARDWIRED DIGITAL INPUTS ELABORATION (PAGE 2 OF 7)
PAGE 24 OF 114 HARDWIRED DIGITAL INPUTS ELABORATION (PAGE 3 OF 7)
PAGE 25 OF 114 HARDWIRED DIGITAL INPUTS ELABORATION (PAGE 4 OF 7)
PAGE 26 OF 114 HARDWIRED DIGITAL INPUTS ELABORATION (PAGE 5 OF 7)
PAGE 27 OF 114 HARDWIRED DIGITAL INPUTS ELABORATION (PAGE 6 OF 7)
PAGE 28 OF 114 HARDWIRED DIGITAL INPUTS ELABORATION (PAGE 7 OF 7)
PAGE 29 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL INPUTS ELABORATION (PAGE 1 OF 3)
PAGE 30 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL INPUTS ELABORATION (PAGE 2 OF 3)
PAGE 31 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL INPUTS ELABORATION (PAGE 3 OF 3)
PAGE 32 OF 114 SOFTWARE - MODBUS SERIAL LINK - ANALOG INPUTS ELABORATION
PAGE 33 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL INPUTS ELABORATION (COILS)
PAGE 34 OF 114 PES SYSTEM CLOCK MANAGEMENT
PAGE 35 OF 114 PES SYSTEM GENERAL DIAGNOSTIC
PAGE 36 OF 114 TRIP LOGICS PROC. (PAGE 1 OF 34) - SMOKE DET. CTRL UNIT POWER-ON MANAG. (PAGE 1 OF 2)
PAGE 37 OF 114 TRIP LOGICS PROC. (PAGE 2 OF 34) - SMOKE DET. CTRL UNIT POWER-ON MANAG. (PAGE 2 OF 2)
PAGE 38 OF 114 TRIP LOGICS PROC. (PAGE 3 OF 34) - SMOKE DETEC. TRIP AND INERGEN RELEASE MANAG.
PAGE 39 OF 114 TRIP LOGICS PROC. (PAGE 4 OF 34) - STAU ROOM TRIP MANAGEMENT
PAGE 40 OF 114 TRIP LOGICS PROC. (PAGE 5 OF 34) - G1 COMPARTMENT TRIP MANAGEMENT
PAGE 41 OF 114 TRIP LOGICS PROC. (PAGE 6 OF 34) - SWITCHBOARDS COMPARTMENT TRIP MANAGEMENT
PAGE 42 OF 114 TRIP LOGICS PROC. (PAGE 7 OF 34) - TRANSFORMER COMPARTMENT TRIP MANAGEMENT
PAGE 43 OF 114 TRIP LOGICS PROC. (PAGE 8 OF 34) - STAU ROOM AIR DAMPERS CLOSING MANAGEMENT
Project developed by: GDC
3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/1
1 check Martha Cluster MARTHA PLATF PES page 2
revision date name status: LZ based replaced replaced SECOND PAGE - INDEX (PAGE 1 OF 3)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 2 OF 114 THIRD PAGE - INDEX (PAGE 2 OF 3) OUTPUTS

PAGE 44 OF 114 TRIP LOGICS PROC. (PAGE 9 OF 34) - G1 COMPARTMENT AIR DAMPERS CLOSING MANAGEMENT
PAGE 45 OF 114 TRIP LOGICS PROC. (PAGE 10 OF 34) - SWITCHBOARDS COMPART. AIR DAMP. CLOSING MANAG.
PAGE 46 OF 114 TRIP LOGICS PROC. (PAGE 11 OF 34) - TRANSFORMER COMPART. AIR DAMP. CLOSING MANAG.
PAGE 47 OF 114 TRIP LOGICS PROC. (PAGE 12 OF 34) - MAIN ENTRANCE AIR DAMPERS CLOSING MANAGEMENT
PAGE 48 OF 114 TRIP LOGICS PROC. (PAGE 13 OF 34) - PLATFORM GENERAL TRIP MANAGEMENT
PAGE 49 OF 114 TRIP LOGICS PROC. (PAGE 14 OF 34) - PURGING AIR PANEL TRIP MANAGEMENT
PAGE 50 OF 114 TRIP LOGICS PROC. (PAGE 15 OF 34) - PRESSURIZATION GENERAL TRIP MANAGEMENT
PAGE 51 OF 114 TRIP LOGICS PROC. (PAGE 16 OF 34) - AVAILABLE EMPTY PAGE
PAGE 52 OF 114 TRIP LOGICS PROC. (PAGE 17 OF 34) - STAU ROOM INERGEN RELEASE COMMAND MANAGEMENT
PAGE 53 OF 114 TRIP LOGICS PROC. (PAGE 18 OF 34) - G1 COMPART. INERGEN RELEASE COMMAND MANAG.
PAGE 54 OF 114 TRIP LOGICS PROC. (PAGE 19 OF 34) - SWTCHBRDS COMPART. INERGEN REL. CMD MANAG.
PAGE 55 OF 114 TRIP LOGICS PROC. (PAGE 20 OF 34) - TRANSF. COMPART. INERGEN REL. COMMAND MANAG.
PAGE 56 OF 114 TRIP LOGICS PROC. (PAGE 21 OF 34) - AT LEAST ONE TRIP PRESENT SIGNALING
PAGE 57 OF 114 TRIP LOGICS PROC. (PAGE 22 OF 34) - PURGING AIR PANEL PERMISSIVE MANAGEMENT
PAGE 58 OF 114 TRIP LOGICS PROC. (PAGE 23 OF 34) - AVAILABLE EMPTY PAGE
PAGE 59 OF 114 TRIP LOGICS PROC. (PAGE 24 OF 34) - TONE #1 ACTIVATION MANAGEMENT
PAGE 60 OF 114 TRIP LOGICS PROC. (PAGE 25 OF 34) - TONE #2 ACTIVATION MANAGEMENT
PAGE 61 OF 114 TRIP LOGICS PROC. (PAGE 26 OF 34) - TONE #3 GAS PRES. ACTIVATION MANAG. (PAGE 1 OF 4)
PAGE 62 OF 114 TRIP LOGICS PROC. (PAGE 27 OF 34) - TONE #3 GAS PRES. ACTIVATION MANAG. (PAGE 2 OF 4)
PAGE 63 OF 114 TRIP LOGICS PROC. (PAGE 28 OF 34) - TONE #3 GAS PRES. ACTIVATION MANAG. (PAGE 3 OF 4)
PAGE 64 OF 114 TRIP LOGICS PROC. (PAGE 29 OF 34) - TONE #3 GAS PRES. ACTIVATION MANAG. (PAGE 4 OF 4)
PAGE 65 OF 114 TRIP LOGICS PROC. (PAGE 30 OF 34) - TONE #4 SMOKE/FLAME PRES. ACT. MANAG. (PAGE 1 OF 4)
PAGE 66 OF 114 TRIP LOGICS PROC. (PAGE 31 OF 34) - TONE #4 SMOKE/FLAME PRES. ACT. MANAG. (PAGE 2 OF 4)
PAGE 67 OF 114 TRIP LOGICS PROC. (PAGE 32 OF 34) - TONE #4 SMOKE/FLAME PRES. ACT. MANAG. (PAGE 3 OF 4)
PAGE 68 OF 114 TRIP LOGICS PROC. (PAGE 33 OF 34) - TONE #4 SMOKE/FLAME PRES. ACT. MANAG. (PAGE 4 OF 4)
PAGE 69 OF 114 TRIP LOGICS PROC. (PAGE 34 OF 34) - AVAILABLE EMPTY PAGE
PAGE 70 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL OUTPUTS ELABORATION (PAGE 1 OF 19)
PAGE 71 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL OUTPUTS ELABORATION (PAGE 2 OF 19)
PAGE 72 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL OUTPUTS ELABORATION (PAGE 3 OF 19)
PAGE 73 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL OUTPUTS ELABORATION (PAGE 4 OF 19)
PAGE 74 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL OUTPUTS ELABORATION (PAGE 5 OF 19)
PAGE 75 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL OUTPUTS ELABORATION (PAGE 6 OF 19)
PAGE 76 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL OUTPUTS ELABORATION (PAGE 7 OF 19)
PAGE 77 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL OUTPUTS ELABORATION (PAGE 8 OF 19)
PAGE 78 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL OUTPUTS ELABORATION (PAGE 9 OF 19)
PAGE 79 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL OUTPUTS ELABORATION (PAGE 10 OF 19)
PAGE 80 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL OUTPUTS ELABORATION (PAGE 11 OF 19)
PAGE 81 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL OUTPUTS ELABORATION (PAGE 12 OF 19)
PAGE 82 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL OUTPUTS ELABORATION (PAGE 13 OF 19)
PAGE 83 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL OUTPUTS ELABORATION (PAGE 14 OF 19)
PAGE 84 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL OUTPUTS ELABORATION (PAGE 15 OF 19)
PAGE 85 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL OUTPUTS ELABORATION (PAGE 16 OF 19)
PAGE 86 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL OUTPUTS ELABORATION (PAGE 17 OF 19)
PAGE 87 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL OUTPUTS ELABORATION (PAGE 18 OF 19)
Project developed by: GDC
3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/2
1 check Martha Cluster MARTHA PLATF PES page 3
revision date name status: LZ based replaced replaced THIRD PAGE - INDEX (PAGE 2 OF 3)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 3 OF 114 FOURTH PAGE - INDEX (PAGE 3 OF 3) OUTPUTS

PAGE 88 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL OUTPUTS ELABORATION (PAGE 19 OF 19)
PAGE 89 OF 114 HARDWIRED DIGITAL OUTPUTS ELABORATION (PAGE 1 OF 4)
PAGE 90 OF 114 HARDWIRED DIGITAL OUTPUTS ELABORATION (PAGE 2 OF 4)
PAGE 91 OF 114 HARDWIRED DIGITAL OUTPUTS ELABORATION (PAGE 3 OF 4)
PAGE 92 OF 114 HARDWIRED DIGITAL OUTPUTS ELABORATION (PAGE 4 OF 4)
PAGE 93 OF 114 TRIP LOGICS VISUAL. (PAGE 1 OF 22) - AT LEAST ONE TRIP PRESENT SIGNALING
PAGE 94 OF 114 TRIP LOGICS VISUAL. (PAGE 2 OF 22) - STAU ROOM TRIP CAUSES/EFFECT
PAGE 95 OF 114 TRIP LOGICS VISUAL. (PAGE 3 OF 22) - G1 COMPARTMENT TRIP CAUSES/EFFECT
PAGE 96 OF 114 TRIP LOGICS VISUAL. (PAGE 4 OF 22) - SWITCHBOARDS COMPARTMENT TRIP CAUSES/EFFECT
PAGE 97 OF 114 TRIP LOGICS VISUAL. (PAGE 5 OF 22) - TRANSFORMER COMPARTMENT TRIP CAUSES/EFFECT
PAGE 98 OF 114 TRIP LOGICS VISUAL. (PAGE 6 OF 22) - STAU ROOM AIR DAMPERS CLOSING CAUSES/EFFECT
PAGE 99 OF 114 TRIP LOGICS VISUAL. (PAGE 7 OF 22) - G1 COMPART. AIR DAMPERS CLOSING CAUSES/EFFECT
PAGE 100 OF 114 TRIP LOGICS VISUAL. (PAGE 8 OF 22) - SWITCHBRDS COMP. AIR DAMP. CLOS. CAUSES/EFFECT
PAGE 101 OF 114 TRIP LOGICS VISUAL. (PAGE 9 OF 22) - TRANSF. COMPART. AIR DAMP. CLOS. CAUSES/EFFECT
PAGE 102 OF 114 TRIP LOGICS VISUAL. (PAGE 10 OF 22) - MAIN ENTRANCE AIR DAMP. CLOSING CAUSES/EFFECT
PAGE 103 OF 114 TRIP LOGICS VISUAL. (PAGE 11 OF 22) - GENERAL PLATFORM TRIP CAUSES/EFFECT
PAGE 104 OF 114 TRIP LOGICS VISUAL. (PAGE 12 OF 22) - PURGING AIR PANEL TRIP CAUSES/EFFECT
PAGE 105 OF 114 TRIP LOGICS VISUAL. (PAGE 13 OF 22) - PRESSURIZATION GENERAL TRIP CAUSES/EFFECT
PAGE 106 OF 114 TRIP LOGICS VISUAL. (PAGE 14 OF 22) - STAU ROOM INERGEN RELEASE CMD CAUSES/EFFECT
PAGE 107 OF 114 TRIP LOGICS VISUAL. (PAGE 15 OF 22) - G1 COMPART. INERGEN RELEASE CMD CAUSES/EFFECT
PAGE 108 OF 114 TRIP LOGICS VISUAL. (PAGE 16 OF 22) - SWITCHBRD COMP. INERGEN REL. CMD CAUSES/EFFECT
PAGE 109 OF 114 TRIP LOGICS VISUAL. (PAGE 17 OF 22 - TRANSF. COMP. INERGEN REL. CMD CAUSES/EFFECT
PAGE 110 OF 114 TRIP LOGICS VISUAL. (PAGE 18 OF 22) - TONE #1 ACTIVATION CAUSES/EFFECT
PAGE 111 OF 114 TRIP LOGICS VISUAL. (PAGE 19 OF 22) - TONE #2 ACTIVATION CAUSES/EFFECT
PAGE 112 OF 114 TRIP LOGICS VISUAL. (PAGE 20 OF 22) - TONE #3 ACTIVATION CAUSES/EFFECT
PAGE 113 OF 114 TRIP LOGICS VISUAL. (PAGE 21 OF 22) - TONE #4 ACTIVATION CAUSES/EFFECT
PAGE 114 OF 114 TRIP LOGICS VISUAL. (PAGE 22 OF 22) - AVAILABLE EMPTY PAGE

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/3
1 check Martha Cluster MARTHA PLATF PES page 4
revision date name status: LZ based replaced replaced FOURTH PAGE - INDEX (PAGE 3 OF 3)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 4 OF 114 FIFTH PAGE - NOTES AND DESCRIPTIONS OUTPUTS

ELOP II V 5.1 B710.20644 F8652X - Central Unit Modules (CU) PADT (PC) serial communication Serial communication with Master
S1 Dip Switches Setting: parameters setting values for Elop II V 5.1: ModBus - parameters setting values:

CU Operating system version: 81 from S1-1 to S1-7 Speed: 57600bps (bits per second) Mode: RTU - ModBus Slave
No. of operating system: 3 S1-1: Off Data bits: 8 Slave Address: 1
CU Operating system release: BS41q/51q V7.0-8 (07.14) S1-2: On Parity: None Speed: 57600bps (bits per second)
S1-3: On Stop bits: 1 Data bits: 8
S1-4: On Parity: None
Code version (hex.): F3A4 - Program version: 38739 S1-5: On Stop bits: 1
Data version (hex.): 6D00 - Area version (hex.): 033C S1-6: On Data transmission: Asynchronous
Run version (hex.): 0998 S1-7: On
corresponding to: Bus Station no.1

S1-8: Off
corresponding to: 57600bps serial
communication ports baud rate for
Elop II V 5.1

THIS APPLICATION PROGRAM HAS BEEN DEVELOPED ON THE BASIS OF DOCUMENT NO. 0266/IS/283395/2D, NAMED: "MARTHA PLATFORM SAFETY AUTOMATION DIAGRAM (CAUSES-EFFECTS)",
REV. 0 OF 30 NOVEMBER 2009, PREPARED BY: "SOVVI WEST Ltd".

EVERY DIGITAL SIGNAL DESCRIPTION, UNLESS OTHERWISE INDICATED, IT'S REFERRED TO LOGICAL LEVEL "ONE" (1, TRUE, HIGH) OF THE SAME SIGNAL.

IN ONLINE-Test MODE (APPLICATION PROGRAM ONLINE MONITORING) GRAPHIC CONNECTIONS OF BOOLEAN (DIGITAL) VARIABLES ARE "BLUE" COLOR, IF THE VARIABLE HAS "ZERO" VALUE
(0, FALSE, LOW), OR "RED" COLOR, IF THE VARIABLE HAS "ONE" VALUE (1, TRUE, HIGH).

ALL DIGITAL COMMAND SIGNALS RECEIVED BY MODBUS SERIAL LINE MUST BE IMPULSIVE.

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/4
1 check Martha Cluster MARTHA PLATF PES page 5
revision date name status: LZ based replaced replaced FIFTH PAGE - NOTES AND DESCRIPTIONS
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 5 OF 114 SIXTH PAGE - REVISIONS INDEX AND DESCRIPTIONS OUTPUTS

Revision: 001 - Code version (hex.): F3A4


FIRST EMISSION

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/5
1 check Martha Cluster MARTHA PLATF PES page 6
revision date name status: LZ based replaced replaced SIXTH PAGE - REVISIONS INDEX AND DESCR.
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 6 OF 114 UTILITIES FUNCTIONS OUTPUTS

TRUE CLK RTRIG 6000


Q FPC
APPLICATION PROGRAM FIRST CYCLE EXECUTION

CYCTM ms CYCLE_TIME
PRGCYC 6003 APPLICATION PROGRAM EXECUTION CYCLE TIME (msec)
CYCFR Hz

CYCLE_FREQ
APPLICATION PROGRAM EXECUTION FREQUENCY (Hz)

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/6
1 check Martha Cluster MARTHA PLATF PES page 7
revision date name status: LZ based replaced replaced UTILITIES FUNCTIONS
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 7 OF 114 SYSTEM DIAGNOSTIC (PAGE 1 OF 4) OUTPUTS

SYSFLTMSK1 >BOOL
7000 SYSFLTMSK1NOFLT
SYSTEM FAULTS MASK #1 NO FAULTS IN SYSTEM FAULTS MASK #1
IN OT01 CUERROR
OT02 CU MODULE ERROR
OT03 HWCLKDISTSUP
OT04 HARDWARE CLOCK DISTURB. DURING START-UP
OT05 HWWDGERROR
OT06 HARDWARE WATCHDOG ERROR
OT07 MEMERROR
OT08 MEMORY ERROR
WORDto16BOOL OT09 PROGRCRASHERROR
OT10 PROGRAM CRASH ERROR
OT11 TIMEOUTERROR
OT12 TIMEOUT ERROR
OT13 HWCLKDEVH
OT14 DEVIATION HARDWARE CLOCK NOT TOLERABLE
OT15 HWCLKDISTOP
OT16
7003 HARDWARE CLOCK DISTURB. DURING OPERATION
I/OCONNERROR
CONNECTION TO I/O LEVEL ERROR
PSMONERROR
POWER SUPPLY MONITORING ERROR
ADDRTSTI/OERROR
ADDRESS TEST I/O SUBRACK ERROR
TDELCUERROR
TIME DELAY OTHER CU ERROR
OUTNOZSUP
OUTPUTS NOT SET TO 0 DURING START-UP
HWCLKDEVT
DEVIATION HARDWARE CLOCK TOLERABLE
SYSFLTMSK1_BIT15
SYSTEM FAULTS MASK #1 - BIT15 not used
MEMDIFFERROR
MEMORY NOT IDENTICAL ERROR

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/7
1 check Martha Cluster MARTHA PLATF PES page 8
revision date name status: LZ based replaced replaced SYSTEM DIAGNOSTIC (PAGE 1 OF 4)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 8 OF 114 SYSTEM DIAGNOSTIC (PAGE 2 OF 4) OUTPUTS

SYSFLTMSK2 >BOOL
8000 SYSFLTMSK2NOFLT
SYSTEM FAULTS MASK #2 NO FAULTS IN SYSTEM FAULTS MASK #2
IN OT01 VMON3.3VCU1ERROR
OT02 VOLTAGE MONITORING 3.3V CU1 ERROR
OT03 VMON3.3VCU2ERROR
OT04 VOLTAGE MONITORING 3.3V CU2 ERROR
OT05 PS1ERROR
OT06 POWER SUPPLY PS1 ERROR
OT07 PS2ERROR
OT08 POWER SUPPLY PS2 ERROR
WORDto16BOOL
OT09 PS3ERROR
OT10 POWER SUPPLY PS3 ERROR
OT11 NOISEBLANKACT
OT12 NOISE BLANKING IS ACTIVE
OT13 CU1ERROR
OT14 ERROR IN CENTRAL MODULE 1
OT15 CU2ERROR
OT16
8003 ERROR IN CENTRAL MODULE 2
COPR1CU1ERROR
COPROCESSOR MODULE 1 NEXT TO CU 1
COPR2CU1ERROR
COPROCESSOR MODULE 2 NEXT TO CU 1
COPR3CU1ERROR
COPROCESSOR MODULE 3 NEXT TO CU 1
COPR1CU2ERROR
COPROCESSOR MODULE 1 NEXT TO CU 2
COPR2CU2ERROR
COPROCESSOR MODULE 2 NEXT TO CU 2
COPR3CU2ERROR
COPROCESSOR MODULE 3 NEXT TO CU 2
BATTCU1ERROR
BACKUP BATTERY ON CENTRAL MODULE 1
BATTCU2ERROR
BACKUP BATTERY ON CENTRAL MODULE 2

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/8
1 check Martha Cluster MARTHA PLATF PES page 9
revision date name status: LZ based replaced replaced SYSTEM DIAGNOSTIC (PAGE 2 OF 4)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 9 OF 114 SYSTEM DIAGNOSTIC (PAGE 3 OF 4) OUTPUTS

SYSRAMEPROM IN OT01 CU1RUNRAM


CU MODULES RAM/EPROM STATUS OT02 CU1 MOD. IN SERVICE - PARAM. IN RAM MEM.
OT03
CU1RUNEPROM
OT04
CU1 MOD. IN SERVICE - PARAM. IN EPROM MEM.
OT05
OT06
OT07
OT08
WORDto16BOOL
OT09 CU2RUNRAM
OT10 CU2 MOD. IN SERVICE - PARAM. IN RAM MEM.
OT11
CU2RUNEPROM
OT12
CU2 MOD. IN SERVICE - PARAM. IN EPROM MEM.
OT13
OT14
OT15
OT16
9000

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/9
1 check Martha Cluster MARTHA PLATF PES page 10
revision date name status: LZ based replaced replaced SYSTEM DIAGNOSTIC (PAGE 3 OF 4)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 10 OF 114 SYSTEM DIAGNOSTIC (PAGE 4 OF 4) OUTPUTS

SYSERRCODE SYSERRCODENOERR
=
SYSTEM ERRORS CODE 0 10000 PES SYSTEM NO ERROR PRESENT

SYSERRCODECHGPLS
<>
MOVE
10006 10003 SYSTEM ERRORS CODE VALUE
PREVIOUS CYCLE SYSTEM CHANGED (PULSE)
ERROR CODE VALUE

SYSIOERR NOT
10009 SYSIONOERR
AT LEAST ONE I/O ERROR PRESENT PES I/O MODULES NO ERROR PRESENT

ERR_ACK_ENAB IN Q CLK RTRIG 10018


Q SYSIOACKCMD
TON
I/O ERRORS AUTOMATIC ACKNOWLEDGE ENABLE & T#10S PT 10015
ET SYSTEM I/O FAULTS ACKNOWLEDGMENT COMMAND
10012
SYSFORBACC
ATTEMPTED TO PERFORM A FORBIDDEN FUNCTION
I/O MODULES ERRORS AUTOMATIC ACKNOWLEDGMENT:
SYSNUMFORBACC IF AT LEAST ONE I/O ERROR PERSISTS FOR MORE THAN
10 SECONDS, AN IMPULSIVE ACKNOWLEDGMENT COMMAND
NUMB. OF ATTEMP. TO PERFORM A FORBID. FUNC. IS GENERATED THAT, IF THE I/O ERROR PERSISTS, IT IS
REPEATED EVERY 10 SECONDS
SYSFORSWIN
AT LEAST ONE INPUT VARIABLE FORCED
SYSFORSWOT
AT LEAST ONE OUTPUT VARIABLE FORCED FALSE SYSLOGEMEROFF
PES SYSTEM LOGIC EMERGENCY
SYSMSTFORSWIN SHUT DOWN COMMAND
INPUTS FORCE MAIN SWITCH ACTIVATED
SYSMSTFORSWOT
OUTPUTS FORCE MAIN SWITCH ACTIVATED

SYSNORMAL
PES SYSTEM NORMAL FUNCTIONING

SYSSINGCH
REDUNDANT PES SYSTEM WITH ONLY ONE CU IN SERVICE

SYSCODEVER
PES RESOURCE CURRENT CODE VERSION

SYSRUNVER
PES RESOURCE CURRENT RUN VERSION

SYSIOACKACT
SYSTEM I/O ERRORS ACKNOWLEDGMENT COMMAND ACTIVATED

INPUTS_ENABLED
READING INPUTS VALUES ENABLED
OUTPUTS_ENABLED
WRITING OUTPUTS VALUES ENABLED

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/10
1 check Martha Cluster MARTHA PLATF PES page 11
revision date name status: LZ based replaced replaced SYSTEM DIAGNOSTIC (PAGE 4 OF 4)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 11 OF 114 DIGITAL INPUTS/OUTPUTS MODULES DIAGNOSTIC (PAGE 1 OF 2) OUTPUTS

HZ-FAN-3 Error Display Test. IO Modules


1101 Bus-No.Rack Pos.(e.g. 1306) Error Code
BUS1 RACK1 SLOT01 - F3236 - DI1 Error ERR-SLOT01
1102 Bus-No.Rack Pos. Error Code ERROR MODULE I/O SLOT01 - F3236 - DI1
BUS1 RACK1 SLOT02 - F3236 - DI2 Error ERR-SLOT02
1103 Bus-No.Rack Pos. Error Code ERROR MODULE I/O SLOT02 - F3236 - DI2
BUS1 RACK1 SLOT03 - F3236 - DI3 Error ERR-SLOT03
1104 Bus-No.Rack Pos. Error Code ERROR MODULE I/O SLOT03 - F3236 - DI3
BUS1 RACK1 SLOT04 - F3236 - DI4 Error ERR-SLOT04
HZ-FAN-3
1105 Bus-No.Rack Pos. Error Code ERROR MODULE I/O SLOT04 - F3236 - DI4
BUS1 RACK1 SLOT05 - F3236 - DI5 Error ERR-SLOT05
1106 Bus-No.Rack Pos. Error Code ERROR MODULE I/O SLOT05 - F3236 - DI5
BUS1 RACK1 SLOT06 - empty Error ERR-SLOT06
1107 Bus-No.Rack Pos. Error Code ERROR MODULE I/O SLOT06 - empty
BUS1 RACK1 SLOT07 - empty Error ERR-SLOT07
1108 Bus-No.Rack Pos. Error Code ERROR MODULE I/O SLOT07 - empty
BUS1 RACK1 SLOT08 - F3331 - DO1 11000
Error ERR-SLOT08
ERROR MODULE I/O SLOT08 - F3331 - DO1
HZ-FAN-3 Error Display Test. IO Modules1
1109 Bus-No.Rack Pos.(e.g. 1306) Error Code
BUS1 RACK1 SLOT09 - F3331 - DO2 Error ERR-SLOT09
1110 Bus-No.Rack Pos. Error Code ERROR MODULE I/O SLOT09 - F3331 - DO2
BUS1 RACK1 SLOT10 - F3331 - DO3 Error ERR-SLOT10
1111 Bus-No.Rack Pos. Error Code ERROR MODULE I/O SLOT10 - F3331 - DO3
BUS1 RACK1 SLOT11 - F3331 - DO4 Error ERR-SLOT11
1112 Bus-No.Rack Pos. Error Code ERROR MODULE I/O SLOT11 - F3331 - DO4
BUS1 RACK1 SLOT12 - F3331 - DO5 Error ERR-SLOT12
HZ-FAN-3
1113 Bus-No.Rack Pos. Error Code ERROR MODULE I/O SLOT12 - F3331 - DO5
BUS1 RACK1 SLOT13 - F3331 - DO6 Error ERR-SLOT13
Bus-No.Rack Pos. Error Code ERROR MODULE I/O SLOT13 - F3331 - DO6
Error
Bus-No.Rack Pos. Error Code
Error
Bus-No.Rack Pos. Error Code
11003
Error

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/11
1 check Martha Cluster MARTHA PLATF PES page 12
revision date name status: LZ based replaced replaced DIG. INP./OUT. MOD. DIAGN. (PAG. 1 OF 2)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 12 OF 114 DIGITAL INPUTS/OUTPUTS MODULES DIAGNOSTIC (PAGE 2 OF 2) OUTPUTS

ERR-SLOT01 CUM-IOMOD-OK
ERROR MODULE I/O SLOT01 - F3236 - DI1 ALL PES I/O MODULES FUNCTIONING

ERR-SLOT02
ERROR MODULE I/O SLOT02 - F3236 - DI2

ERR-SLOT03 FALSE
ERROR MODULE I/O SLOT03 - F3236 - DI3 FALSE >=1

ERR-SLOT04
ERROR MODULE I/O SLOT04 - F3236 - DI4

ERR-SLOT05
ERROR MODULE I/O SLOT05 - F3236 - DI5
12000
ERR-SLOT06
ERROR MODULE I/O SLOT06 - empty

ERR-SLOT07
ERROR MODULE I/O SLOT07 - empty

ERR-SLOT08
ERROR MODULE I/O SLOT08 - F3331 - DO1

ERR-SLOT09
ERROR MODULE I/O SLOT09 - F3331 - DO2

ERR-SLOT10
ERROR MODULE I/O SLOT10 - F3331 - DO3

ERR-SLOT11
ERROR MODULE I/O SLOT11 - F3331 - DO4

ERR-SLOT12
ERROR MODULE I/O SLOT12 - F3331 - DO5

ERR-SLOT13
ERROR MODULE I/O SLOT13 - F3331 - DO6

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/12
1 check Martha Cluster MARTHA PLATF PES page 13
revision date name status: LZ based replaced replaced DIG. INP./OUT. MOD. DIAGN. (PAG. 2 OF 2)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 13 OF 114 DIGITAL OUTPUTS MODULES CHANNELS DIAGNOSTIC (PAGE 1 OF 9) OUTPUTS

BUS1 RACK1 SLOT08 - F3331 - DO1 HB-BLD-3 Testable Outp.Module with Line Diagnostic FAULTS MASK MODULE I/O SLOT08 - F3331 - DO1
1108 Bus-No. Rack Pos. (e.g. 1305) Channel Fault Mask ERRMSK-SLOT08
MODE-SLOT08-CH1 Mode Channel 1 (0/1/2) Error Channel 1 ERR-SLOT08-CH1
MODE-SLOT08-CH2 Mode Channel 2 (0/1/2) Error Channel 2 ERR-SLOT08-CH2
MODE-SLOT08-CH3 Mode Channel 3 (0/1/2) Error Channel 3 ERR-SLOT08-CH3
MODE-SLOT08-CH4 Mode Channel 4 (0/1/2) Error Channel 4 ERR-SLOT08-CH4
MODE-SLOT08-CH5 Mode Channel 5 (0/1/2) Error Channel 5 ERR-SLOT08-CH5
MODE-SLOT08-CH6 Mode Channel 6 (0/1/2) Error Channel 6 ERR-SLOT08-CH6
HB-BLD-3
MODE-SLOT08-CH7 Mode Channel 7 (0/1/2) Error Channel 7 ERR-SLOT08-CH7
MODE-SLOT08-CH8 Mode Channel 8 (0/1/2) Error Channel 8 ERR-SLOT08-CH8
ALMDEL-SLOT08 Max. Time Inrush Current in ms Pulse on Error
ALARM DELAY I/O MODULE SLOT08 - F3331 - DO1 Pulse on Error
alarm delay (0...50ms) Error ERRCUM-SLOT08
CUMUL. ERR. MODULE I/O SLOT08 - F3331 - DO1
channel mode:
0 non used, free Error13000
Code ERRCODE-SLOT08
1 normal ERRORS CODE MODULE I/O SLOT08 - F3331 - DO1
2 inverse

BUS1 RACK1 SLOT09 - F3331 - DO2 HB-BLD-3 Testable Outp.Module with Line Diagnostic1 FAULTS MASK MODULE I/O SLOT09 - F3331 - DO2
1109 Bus-No. Rack Pos. (e.g. 1305) Channel Fault Mask ERRMSK-SLOT09
MODE-SLOT09-CH1 Mode Channel 1 (0/1/2) Error Channel 1 ERR-SLOT09-CH1
MODE-SLOT09-CH2 Mode Channel 2 (0/1/2) Error Channel 2 ERR-SLOT09-CH2
MODE-SLOT09-CH3 Mode Channel 3 (0/1/2) Error Channel 3 ERR-SLOT09-CH3
MODE-SLOT09-CH4 Mode Channel 4 (0/1/2) Error Channel 4 ERR-SLOT09-CH4
MODE-SLOT09-CH5 Mode Channel 5 (0/1/2) Error Channel 5 ERR-SLOT09-CH5
MODE-SLOT09-CH6 Mode Channel 6 (0/1/2) Error Channel 6 ERR-SLOT09-CH6
HB-BLD-3
MODE-SLOT09-CH7 Mode Channel 7 (0/1/2) Error Channel 7 ERR-SLOT09-CH7
MODE-SLOT09-CH8 Mode Channel 8 (0/1/2) Error Channel 8 ERR-SLOT09-CH8
ALMDEL-SLOT09 Max. Time Inrush Current in ms Pulse on Error
ALARM DELAY I/O MODULE SLOT09 - F3331 - DO2 Pulse on Error
alarm delay (0...50ms) Error ERRCUM-SLOT09
CUMUL. ERR. MODULE I/O SLOT09 - F3331 - DO2
channel mode:
Error13003
Code ERRCODE-SLOT09
0 non used, free
1 normal ERRORS CODE MODULE I/O SLOT09 - F3331 - DO2
2 inverse

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/13
1 check Martha Cluster MARTHA PLATF PES page 14
revision date name status: LZ based replaced replaced DIG.OUT. MOD.CHANN. DIAGN. (PAGE 1 OF 9)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 14 OF 114 DIGITAL OUTPUTS MODULES CHANNELS DIAGNOSTIC (PAGE 2 OF 9) OUTPUTS

BUS1 RACK1 SLOT10 - F3331 - DO3 HB-BLD-3 Testable Outp.Module with Line Diagnostic2 FAULTS MASK MODULE I/O SLOT10 - F3331 - DO3
1110 Bus-No. Rack Pos. (e.g. 1305) Channel Fault Mask ERRMSK-SLOT10
MODE-SLOT10-CH1 Mode Channel 1 (0/1/2) Error Channel 1 ERR-SLOT10-CH1
MODE-SLOT10-CH2 Mode Channel 2 (0/1/2) Error Channel 2 ERR-SLOT10-CH2
MODE-SLOT10-CH3 Mode Channel 3 (0/1/2) Error Channel 3 ERR-SLOT10-CH3
MODE-SLOT10-CH4 Mode Channel 4 (0/1/2) Error Channel 4 ERR-SLOT10-CH4
MODE-SLOT10-CH5 Mode Channel 5 (0/1/2) Error Channel 5 ERR-SLOT10-CH5
MODE-SLOT10-CH6 Mode Channel 6 (0/1/2) Error Channel 6 ERR-SLOT10-CH6
HB-BLD-3
MODE-SLOT10-CH7 Mode Channel 7 (0/1/2) Error Channel 7 ERR-SLOT10-CH7
MODE-SLOT10-CH8 Mode Channel 8 (0/1/2) Error Channel 8 ERR-SLOT10-CH8
ALMDEL-SLOT10 Max. Time Inrush Current in ms Pulse on Error
ALARM DELAY I/O MODULE SLOT10 - F3331 - DO3 Pulse on Error
alarm delay (0...50ms) Error ERRCUM-SLOT10
CUMUL. ERR. MODULE I/O SLOT10 - F3331 - DO3
channel mode:
Error14000
Code ERRCODE-SLOT10
0 non used, free
1 normal ERRORS CODE MODULE I/O SLOT10 - F3331 - DO3
2 inverse

BUS1 RACK1 SLOT11 - F3331 - DO4 HB-BLD-3 Testable Outp.Module with Line Diagnostic3 FAULTS MASK MODULE I/O SLOT11 - F3331 - DO4
1111 Bus-No. Rack Pos. (e.g. 1305) Channel Fault Mask ERRMSK-SLOT11
MODE-SLOT11-CH1 Mode Channel 1 (0/1/2) Error Channel 1 ERR-SLOT11-CH1
MODE-SLOT11-CH2 Mode Channel 2 (0/1/2) Error Channel 2 ERR-SLOT11-CH2
MODE-SLOT11-CH3 Mode Channel 3 (0/1/2) Error Channel 3 ERR-SLOT11-CH3
MODE-SLOT11-CH4 Mode Channel 4 (0/1/2) Error Channel 4 ERR-SLOT11-CH4
MODE-SLOT11-CH5 Mode Channel 5 (0/1/2) Error Channel 5 ERR-SLOT11-CH5
MODE-SLOT11-CH6 Mode Channel 6 (0/1/2) Error Channel 6 ERR-SLOT11-CH6
HB-BLD-3
MODE-SLOT11-CH7 Mode Channel 7 (0/1/2) Error Channel 7 ERR-SLOT11-CH7
MODE-SLOT11-CH8 Mode Channel 8 (0/1/2) Error Channel 8 ERR-SLOT11-CH8
ALMDEL-SLOT11 Max. Time Inrush Current in ms Pulse on Error
ALARM DELAY I/O MODULE SLOT11 - F3331 - DO4 Pulse on Error
alarm delay (0...50ms) Error ERRCUM-SLOT11
CUMUL. ERR. MODULE I/O SLOT11 - F3331 - DO4
channel mode:
Error14003
Code ERRCODE-SLOT11
0 non used, free
1 normal ERRORS CODE MODULE I/O SLOT11 - F3331 - DO4
2 inverse

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/14
1 check Martha Cluster MARTHA PLATF PES page 15
revision date name status: LZ based replaced replaced DIG.OUT. MOD.CHANN. DIAGN. (PAGE 2 OF 9)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 15 OF 114 DIGITAL OUTPUTS MODULES CHANNELS DIAGNOSTIC (PAGE 3 OF 9) OUTPUTS

BUS1 RACK1 SLOT12 - F3331 - DO5 HB-BLD-3 Testable Outp.Module with Line Diagnostic4 FAULTS MASK MODULE I/O SLOT12 - F3331 - DO5
1112 Bus-No. Rack Pos. (e.g. 1305) Channel Fault Mask ERRMSK-SLOT12
MODE-SLOT12-CH1 Mode Channel 1 (0/1/2) Error Channel 1 ERR-SLOT12-CH1
MODE-SLOT12-CH2 Mode Channel 2 (0/1/2) Error Channel 2 ERR-SLOT12-CH2
MODE-SLOT12-CH3 Mode Channel 3 (0/1/2) Error Channel 3 ERR-SLOT12-CH3
MODE-SLOT12-CH4 Mode Channel 4 (0/1/2) Error Channel 4 ERR-SLOT12-CH4
MODE-SLOT12-CH5 Mode Channel 5 (0/1/2) Error Channel 5 ERR-SLOT12-CH5
MODE-SLOT12-CH6 Mode Channel 6 (0/1/2) Error Channel 6 ERR-SLOT12-CH6
HB-BLD-3
MODE-SLOT12-CH7 Mode Channel 7 (0/1/2) Error Channel 7 ERR-SLOT12-CH7
MODE-SLOT12-CH8 Mode Channel 8 (0/1/2) Error Channel 8 ERR-SLOT12-CH8
ALMDEL-SLOT12 Max. Time Inrush Current in ms Pulse on Error
ALARM DELAY I/O MODULE SLOT12 - F3331 - DO5 Pulse on Error
alarm delay (0...50ms) Error ERRCUM-SLOT12
CUMUL. ERR. MODULE I/O SLOT12 - F3331 - DO5
channel mode:
Error15000
Code ERRCODE-SLOT12
0 non used, free
1 normal ERRORS CODE MODULE I/O SLOT12 - F3331 - DO5
2 inverse

BUS1 RACK1 SLOT13 - F3331 - DO6 HB-BLD-3 Testable Outp.Module with Line Diagnostic5 FAULTS MASK MODULE I/O SLOT13 - F3331 - DO6
1113 Bus-No. Rack Pos. (e.g. 1305) Channel Fault Mask ERRMSK-SLOT13
MODE-SLOT13-CH1 Mode Channel 1 (0/1/2) Error Channel 1 ERR-SLOT13-CH1
MODE-SLOT13-CH2 Mode Channel 2 (0/1/2) Error Channel 2 ERR-SLOT13-CH2
MODE-SLOT13-CH3 Mode Channel 3 (0/1/2) Error Channel 3 ERR-SLOT13-CH3
MODE-SLOT13-CH4 Mode Channel 4 (0/1/2) Error Channel 4 ERR-SLOT13-CH4
MODE-SLOT13-CH5 Mode Channel 5 (0/1/2) Error Channel 5 ERR-SLOT13-CH5
MODE-SLOT13-CH6 Mode Channel 6 (0/1/2) Error Channel 6 ERR-SLOT13-CH6
HB-BLD-3
MODE-SLOT13-CH7 Mode Channel 7 (0/1/2) Error Channel 7 ERR-SLOT13-CH7
MODE-SLOT13-CH8 Mode Channel 8 (0/1/2) Error Channel 8 ERR-SLOT13-CH8
ALMDEL-SLOT13 Max. Time Inrush Current in ms Pulse on Error
ALARM DELAY I/O MODULE SLOT13 - F3331 - DO6 Pulse on Error
alarm delay (0...50ms) Error ERRCUM-SLOT13
CUMUL. ERR. MODULE I/O SLOT13 - F3331 - DO6
channel mode:
Error15003
Code ERRCODE-SLOT13
0 non used, free
1 normal ERRORS CODE MODULE I/O SLOT13 - F3331 - DO6
2 inverse

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/15
1 check Martha Cluster MARTHA PLATF PES page 16
revision date name status: LZ based replaced replaced DIG.OUT. MOD.CHANN. DIAGN. (PAGE 3 OF 9)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 16 OF 114 DIGITAL OUTPUTS MODULES CHANNELS DIAGNOSTIC (PAGE 4 OF 9) OUTPUTS
AVAILABLE EMPTY PAGE

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/16
1 check Martha Cluster MARTHA PLATF PES page 17
revision date name status: LZ based replaced replaced DIG.OUT. MOD.CHANN. DIAGN. (PAGE 4 OF 9)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 17 OF 114 DIGITAL OUTPUTS MODULES CHANNELS DIAGNOSTIC (PAGE 5 OF 9) OUTPUTS

ERR-SLOT08-CH1 CHERR-SLOT08
ERROR CH.1 MOD. I/O SLOT08 - F3331 - DO1 AT LEAST ONE ERROR CHAN. MOD. I/O SLOT08 - F3331 - DO1

ERR-SLOT08-CH2
ERROR CH.2 MOD. I/O SLOT08 - F3331 - DO1 >=1

ERR-SLOT08-CH3
ERROR CH.3 MOD. I/O SLOT08 - F3331 - DO1
17000
ERR-SLOT08-CH4
ERROR CH.4 MOD. I/O SLOT08 - F3331 - DO1

ERR-SLOT08-CH5
ERROR CH.5 MOD. I/O SLOT08 - F3331 - DO1

ERR-SLOT08-CH6
ERROR CH.6 MOD. I/O SLOT08 - F3331 - DO1

ERR-SLOT08-CH7
ERROR CH.7 MOD. I/O SLOT08 - F3331 - DO1

ERR-SLOT08-CH8
ERROR CH.8 MOD. I/O SLOT08 - F3331 - DO1

ERR-SLOT09-CH1 CHERR-SLOT09
ERROR CH.1 MOD. I/O SLOT09 - F3331 - DO2 AT LEAST ONE ERROR CHAN. MOD. I/O SLOT09 - F3331 - DO2

ERR-SLOT09-CH2
ERROR CH.2 MOD. I/O SLOT09 - F3331 - DO2 >=1

ERR-SLOT09-CH3
ERROR CH.3 MOD. I/O SLOT09 - F3331 - DO2
17003
ERR-SLOT09-CH4
ERROR CH.4 MOD. I/O SLOT09 - F3331 - DO2

ERR-SLOT09-CH5
ERROR CH.5 MOD. I/O SLOT09 - F3331 - DO2

ERR-SLOT09-CH6
ERROR CH.6 MOD. I/O SLOT09 - F3331 - DO2

ERR-SLOT09-CH7
ERROR CH.7 MOD. I/O SLOT09 - F3331 - DO2

ERR-SLOT09-CH8
ERROR CH.8 MOD. I/O SLOT09 - F3331 - DO2

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/17
1 check Martha Cluster MARTHA PLATF PES page 18
revision date name status: LZ based replaced replaced DIG.OUT. MOD.CHANN. DIAGN. (PAGE 5 OF 9)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 18 OF 114 DIGITAL OUTPUTS MODULES CHANNELS DIAGNOSTIC (PAGE 6 OF 9) OUTPUTS

ERR-SLOT10-CH1 CHERR-SLOT10
ERROR CH.1 MOD. I/O SLOT10 - F3331 - DO3 AT LEAST ONE ERROR CHAN. MOD. I/O SLOT10 - F3331 - DO3

ERR-SLOT10-CH2
ERROR CH.2 MOD. I/O SLOT10 - F3331 - DO3 >=1

ERR-SLOT10-CH3
ERROR CH.3 MOD. I/O SLOT10 - F3331 - DO3
18000
ERR-SLOT10-CH4
ERROR CH.4 MOD. I/O SLOT10 - F3331 - DO3

ERR-SLOT10-CH5
ERROR CH.5 MOD. I/O SLOT10 - F3331 - DO3

ERR-SLOT10-CH6
ERROR CH.6 MOD. I/O SLOT10 - F3331 - DO3

ERR-SLOT10-CH7
ERROR CH.7 MOD. I/O SLOT10 - F3331 - DO3

ERR-SLOT10-CH8
ERROR CH.8 MOD. I/O SLOT10 - F3331 - DO3

ERR-SLOT11-CH1 CHERR-SLOT11
ERROR CH.1 MOD. I/O SLOT11 - F3331 - DO4 AT LEAST ONE ERROR CHAN. MOD. I/O SLOT11 - F3331 - DO4

ERR-SLOT11-CH2
ERROR CH.2 MOD. I/O SLOT11 - F3331 - DO4 >=1

ERR-SLOT11-CH3
ERROR CH.3 MOD. I/O SLOT11 - F3331 - DO4
18003
ERR-SLOT11-CH4
ERROR CH.4 MOD. I/O SLOT11 - F3331 - DO4

ERR-SLOT11-CH5
ERROR CH.5 MOD. I/O SLOT11 - F3331 - DO4

ERR-SLOT11-CH6
ERROR CH.6 MOD. I/O SLOT11 - F3331 - DO4

ERR-SLOT11-CH7
ERROR CH.7 MOD. I/O SLOT11 - F3331 - DO4

ERR-SLOT11-CH8
ERROR CH.8 MOD. I/O SLOT11 - F3331 - DO4

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/18
1 check Martha Cluster MARTHA PLATF PES page 19
revision date name status: LZ based replaced replaced DIG.OUT. MOD.CHANN. DIAGN. (PAGE 6 OF 9)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 19 OF 114 DIGITAL OUTPUTS MODULES CHANNELS DIAGNOSTIC (PAGE 7 OF 9) OUTPUTS

ERR-SLOT12-CH1 CHERR-SLOT12
ERROR CH.1 MOD. I/O SLOT12 - F3331 - DO5 AT LEAST ONE ERROR CHAN. MOD. I/O SLOT12 - F3331 - DO5

ERR-SLOT12-CH2
ERROR CH.2 MOD. I/O SLOT12 - F3331 - DO5 >=1

ERR-SLOT12-CH3
ERROR CH.3 MOD. I/O SLOT12 - F3331 - DO5
19000
ERR-SLOT12-CH4
ERROR CH.4 MOD. I/O SLOT12 - F3331 - DO5

ERR-SLOT12-CH5
ERROR CH.5 MOD. I/O SLOT12 - F3331 - DO5

ERR-SLOT12-CH6
ERROR CH.6 MOD. I/O SLOT12 - F3331 - DO5

ERR-SLOT12-CH7
ERROR CH.7 MOD. I/O SLOT12 - F3331 - DO5

ERR-SLOT12-CH8
ERROR CH.8 MOD. I/O SLOT12 - F3331 - DO5

ERR-SLOT13-CH1 CHERR-SLOT13
ERROR CH.1 MOD. I/O SLOT13 - F3331 - DO6 AT LEAST ONE ERROR CHAN. MOD. I/O SLOT13 - F3331 - DO6

ERR-SLOT13-CH2
ERROR CH.2 MOD. I/O SLOT13 - F3331 - DO6 >=1

ERR-SLOT13-CH3
ERROR CH.3 MOD. I/O SLOT13 - F3331 - DO6
19003
ERR-SLOT13-CH4
ERROR CH.4 MOD. I/O SLOT13 - F3331 - DO6

ERR-SLOT13-CH5
ERROR CH.5 MOD. I/O SLOT13 - F3331 - DO6

ERR-SLOT13-CH6
ERROR CH.6 MOD. I/O SLOT13 - F3331 - DO6

ERR-SLOT13-CH7
ERROR CH.7 MOD. I/O SLOT13 - F3331 - DO6

ERR-SLOT13-CH8
ERROR CH.8 MOD. I/O SLOT13 - F3331 - DO6

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/19
1 check Martha Cluster MARTHA PLATF PES page 20
revision date name status: LZ based replaced replaced DIG.OUT. MOD.CHANN. DIAGN. (PAGE 7 OF 9)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 20 OF 114 DIGITAL OUTPUTS MODULES CHANNELS DIAGNOSTIC (PAGE 8 OF 9) OUTPUTS
AVAILABLE EMPTY PAGE

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/20
1 check Martha Cluster MARTHA PLATF PES page 21
revision date name status: LZ based replaced replaced DIG.OUT. MOD.CHANN. DIAGN. (PAGE 8 OF 9)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 21 OF 114 DIGITAL OUTPUTS MODULES CHANNELS DIAGNOSTIC (PAGE 9 OF 9) OUTPUTS

CHERR-SLOT08 CUM-CHMODIO-OK
AT LEAST ONE ERROR CHAN. MOD. I/O SLOT08 - F3331 - DO1 I/O DO MODULES ALL CHANNELS WORKING

CHERR-SLOT09
AT LEAST ONE ERROR CHAN. MOD. I/O SLOT09 - F3331 - DO2 >=1

CHERR-SLOT10
AT LEAST ONE ERROR CHAN. MOD. I/O SLOT10 - F3331 - DO3 FALSE
FALSE 21000
CHERR-SLOT11
AT LEAST ONE ERROR CHAN. MOD. I/O SLOT11 - F3331 - DO4

CHERR-SLOT12
AT LEAST ONE ERROR CHAN. MOD. I/O SLOT12 - F3331 - DO5

CHERR-SLOT13
AT LEAST ONE ERROR CHAN. MOD. I/O SLOT13 - F3331 - DO6

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/21
1 check Martha Cluster MARTHA PLATF PES page 22
revision date name status: LZ based replaced replaced DIG.OUT. MOD.CHANN. DIAGN. (PAGE 9 OF 9)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 22 OF 114 HARDWIRED DIGITAL INPUTS ELABORATION (PAGE 1 OF 7) OUTPUTS

INPUTS_ENABLED
READING INPUTS VALUES ENABLED EN
MOVE
22000 003F.2 FLAME_FAIL
00.01.01
EN FLAME DETECT. SYST. FAIL. NOT PRESENT
Terminal strip: TB-DI-01 Terminals: 1(+24Vcc), 2(Ch01 - d2) MOVE
22003 003E.2 EXPG_FAIL
00.01.02 EN EXPL. GAS DETECT. SYST. FAIL. NOT PRESENT
MOVE
Terminal strip: TB-DI-01 Terminals: 3(+24Vcc), 4(Ch02 - d4) 22006 RPA.2 PLT_ABD
EN PLATF. ABAND. PUSH-BUTTONS NOT ACTIV.
00.01.03 MOVE
22009 RPS1.2 UNM_MAN
Terminal strip: TB-DI-01 Terminals: 5(+24Vcc), 6(Ch03 - d6)
EN UNMANNED POSIT. SELECT. SIGNALIZ.
MOVE
00.01.04 22012 RET2.3 ELETRP_INC
Terminal strip: TB-DI-01 Terminals: 7(+24Vcc), 8(Ch04 - d8) EN ELECT. TRIPS SELECT. INCLUDED POSIT.
MOVE
22015 RMOB.2 MOB_PB
00.01.05
EN MAN OVERBOARD PUSH-BUTTONS NOT ACTIVATED
Terminal strip: TB-DI-01 Terminals: 9(+24Vcc), 10(Ch05 - d10) MOVE
22018 003S.2 SMOKE_FAIL
00.01.06 EN SMOKE DETECT. SYST. FAIL. NOT PRESENT
MOVE
Terminal strip: TB-DI-01 Terminals: 11(+24Vcc), 12(Ch06 - d12) 22021 DMP5.2 DMP_GEN
EN MAIN ENTRANCE AIR DAMPERS CLOSED
00.01.07 MOVE
22024 012F.2 FLAME_PALM
Terminal strip: TB-DI-01 Terminals: 13(+24Vcc), 14(Ch07 - d14)
EN FLAME PREALARM STAU ROOM NOT PRESENT
MOVE
00.01.08 22027 022F.2 FLAME_PALM
Terminal strip: TB-DI-01 Terminals: 15(+24Vcc), 16(Ch08 - d16) EN FLAME PREALARM G1 COMPART. NOT PRESENT
MOVE
22030 032F.2 FLAME_PALM
00.01.09
EN FLAME PREALARM SWTCHBRDS COMP. NOT PRESENT
Terminal strip: TB-DI-01 Terminals: 17(+24Vcc), 18(Ch09 - d18) MOVE
22033 042F.2 FLAME_PALM
00.01.10 EN FLAME PREALARM TRANSF. COMPART. NOT PRESENT
MOVE
Terminal strip: TB-DI-01 Terminals: 19(+24Vcc), 20(Ch10 - d20) 22036 011F.2 FLAME_ALM
EN FLAME ALARM STAU ROOM NOT PRESENT
00.01.11 MOVE
22039 012F.2 FLAME_ALM
Terminal strip: TB-DI-01 Terminals: 21(+24Vcc), 22(Ch11 - d22)
EN FLAME ALARM G1 COMPART. NOT PRESENT
MOVE
00.01.12 22042 013F.2 FLAME_ALM
Terminal strip: TB-DI-01 Terminals: 23(+24Vcc), 24(Ch12 - d24) EN FLAME ALARM SWTCHBRDS COMP. NOT PRESENT
MOVE
22045 014F.2 FLAME_ALM
00.01.13
FLAME ALARM TRANSF. COMPART. NOT PRESENT
Terminal strip: TB-DI-01 Terminals: 25(+24Vcc), 26(Ch13 - d26) Module: Digital Inputs
Model: F3236
00.01.14 Cable: Z7116
Terminal strip: TB-DI-01 Terminals: 27(+24Vcc), 28(Ch14 - d28) Rack: Rack00
Position: Slot01
00.01.15
Terminal strip: TB-DI-01 Terminals: 29(+24Vcc), 30(Ch15 - d30)

00.01.16
Terminal strip: TB-DI-01 Terminals: 31(+24Vcc), 32(Ch08 - d32)

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/22
1 check Martha Cluster MARTHA PLATF PES page 23
revision date name status: LZ based replaced replaced HARDWIRED DIG. INP. ELAB. (PAGE 1 OF 7)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 23 OF 114 HARDWIRED DIGITAL INPUTS ELABORATION (PAGE 2 OF 7) OUTPUTS

INPUTS_ENABLED
READING INPUTS VALUES ENABLED EN
MOVE
23000 011E.2 EXPG_PALM
00.02.01
EN EXPL. GAS PREALARM ZONE #1 WELL HEADS NOT PRES.
Terminal strip: TB-DI-02 Terminals: 1(+24Vcc), 2(Ch01 - d2) MOVE
23003 012E.2 EXPG_ALM
00.02.02 EN EXPL. GAS ALARM ZONE #1 WELL HEADS NOT PRES.
MOVE
Terminal strip: TB-DI-02 Terminals: 3(+24Vcc), 4(Ch02 - d4) 23006 021E.2 EXPG_PALM
EN EXPL. GAS PREALARM ZONE #2 WELL HEADS NOT PRES.
00.02.03 MOVE
23009 022E.2 EXPG_ALM
Terminal strip: TB-DI-02 Terminals: 5(+24Vcc), 6(Ch03 - d6)
EN EXPL. GAS ALARM ZONE #2 WELL HEADS NOT PRES.
MOVE
00.02.04 23012 031E.2 EXPG_PALM
Terminal strip: TB-DI-02 Terminals: 7(+24Vcc), 8(Ch04 - d8) EN EXPL. GAS PREALARM ZONE #3 WELL HEADS NOT PRES.
MOVE
23015 032E.2 EXPG_ALM
00.02.05
EN EXPL. GAS ALARM ZONE #3 WELL HEADS NOT PRES.
Terminal strip: TB-DI-02 Terminals: 9(+24Vcc), 10(Ch05 - d10) MOVE
23018 041E.2 EXPG_PALM
00.02.06 EN EXPL. GAS PREALARM ZONE #4 WELL HEADS NOT PRES.
MOVE
Terminal strip: TB-DI-02 Terminals: 11(+24Vcc), 12(Ch06 - d12) 23021 042E.2 EXPG_ALM
EN EXPL. GAS ALARM ZONE #4 WELL HEADS NOT PRES.
00.02.07 MOVE
23024 051E.2 EXPG_PALM
Terminal strip: TB-DI-02 Terminals: 13(+24Vcc), 14(Ch07 - d14)
EN EXPL. GAS PREALARM ZONE #5 PROC. MOD. NOT PRES.
MOVE
00.02.08 23027 052E.2 EXPG_ALM
Terminal strip: TB-DI-02 Terminals: 15(+24Vcc), 16(Ch08 - d16) EN EXPL. GAS ALARM ZONE #5 PROC. MOD. NOT PRES.
MOVE
23030 061E.2 EXPG_PALM
00.02.09
EN EXPL. GAS PREALARM ZONE #6 PROC. MOD. NOT PRES.
Terminal strip: TB-DI-02 Terminals: 17(+24Vcc), 18(Ch09 - d18) MOVE
23033 062E.2 EXPG_ALM
00.02.10 EN EXPL. GAS ALARM ZONE #6 PROC. MOD. NOT PRES.
MOVE
Terminal strip: TB-DI-02 Terminals: 19(+24Vcc), 20(Ch10 - d20) 23036 071E.2 EXPG_PALM
EN EXPL. GAS PREALARM ZONE #7 PROC. MOD. NOT PRES.
00.02.11 MOVE
23039 072E.2 EXPG_ALM
Terminal strip: TB-DI-02 Terminals: 21(+24Vcc), 22(Ch11 - d22)
EN EXPL. GAS ALARM ZONE #7 PROC. MOD. NOT PRES.
MOVE
00.02.12 23042 081E.2 EXPG_PALM
Terminal strip: TB-DI-02 Terminals: 23(+24Vcc), 24(Ch12 - d24) EN EXPL. GAS PREALARM ZONE #8 PROC. MOD. NOT PRES.
MOVE
23045 082E.2 EXPG_ALM
00.02.13
EXPL. GAS ALARM ZONE #8 PROC. MOD. NOT PRES.
Terminal strip: TB-DI-02 Terminals: 25(+24Vcc), 26(Ch13 - d26) Module: Digital Inputs
Model: F3236
00.02.14 Cable: Z7116
Terminal strip: TB-DI-02 Terminals: 27(+24Vcc), 28(Ch14 - d28) Rack: Rack00
Position: Slot02
00.02.15
Terminal strip: TB-DI-02 Terminals: 29(+24Vcc), 30(Ch15 - d30)

00.02.16
Terminal strip: TB-DI-02 Terminals: 31(+24Vcc), 32(Ch08 - d32)

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/23
1 check Martha Cluster MARTHA PLATF PES page 24
revision date name status: LZ based replaced replaced HARDWIRED DIG. INP. ELAB. (PAGE 2 OF 7)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 24 OF 114 HARDWIRED DIGITAL INPUTS ELABORATION (PAGE 3 OF 7) OUTPUTS

INPUTS_ENABLED
READING INPUTS VALUES ENABLED EN
MOVE
24000 091E.2 EXPG_PALM
00.03.01
EN EXPL. GAS PREALARM ZONE #9 PROC. MOD. NOT PRES.
Terminal strip: TB-DI-03 Terminals: 1(+24Vcc), 2(Ch01 - d2) MOVE
24003 092E.2 EXPG_ALM
00.03.02 EN EXPL. GAS ALARM ZONE #9 PROC. MOD. NOT PRES.
MOVE
Terminal strip: TB-DI-03 Terminals: 3(+24Vcc), 4(Ch02 - d4) 24006 101E.2 EXPG_PALM
EN EXPL. GAS PREALARM STAU ROOM NOT PRES.
00.03.03 MOVE
24009 102E.2 EXPG_ALM
Terminal strip: TB-DI-03 Terminals: 5(+24Vcc), 6(Ch03 - d6)
EN EXPL. GAS ALARM STAU ROOM NOT PRES.
MOVE
00.03.04 24012 111E.2 EXPG_PALM
Terminal strip: TB-DI-03 Terminals: 7(+24Vcc), 8(Ch04 - d8) EN EXPL. GAS PREALARM G1 COMPART. NOT PRES.
MOVE
24015 112E.2 EXPG_ALM
00.03.05
EN EXPL. GAS ALARM G1 COMPART. NOT PRES.
Terminal strip: TB-DI-03 Terminals: 9(+24Vcc), 10(Ch05 - d10) MOVE
24018 121E.2 EXPG_PALM
00.03.06 EN EXPL. GAS PREALARM SWTCHBRDS COMP. NOT PRESENT
MOVE
Terminal strip: TB-DI-03 Terminals: 11(+24Vcc), 12(Ch06 - d12) 24021 122E.2 EXPG_ALM
EN EXPL. GAS ALARM SWTCHBRDS COMP. NOT PRESENT
00.03.07 MOVE
24024 131E.2 EXPG_PALM
Terminal strip: TB-DI-03 Terminals: 13(+24Vcc), 14(Ch07 - d14)
EN EXPL. GAS PREALARM TRANSF. COMP. NOT PRESENT
MOVE
00.03.08 24027 132E.2 EXPG_ALM
Terminal strip: TB-DI-03 Terminals: 15(+24Vcc), 16(Ch08 - d16) EN EXPL. GAS ALARM TRANSF. COMP. NOT PRESENT
MOVE
24030 141E.2 EXPG_PALM
00.03.09
EN EXPL. GAS PREALARM PRESS. ASPIR. NOT PRESENT
Terminal strip: TB-DI-03 Terminals: 17(+24Vcc), 18(Ch09 - d18) MOVE
24033 142E.2 EXPG_ALM
00.03.10 EN EXPL. GAS ALARM PRESS. ASPIR. NOT PRESENT
MOVE
Terminal strip: TB-DI-03 Terminals: 19(+24Vcc), 20(Ch10 - d20) 24036 RP1.2 PSL_ST
EN STAU ROOM PRESSURIZATION PRESENT
00.03.11 MOVE
24039 RP2.2 PSL_G1
Terminal strip: TB-DI-03 Terminals: 21(+24Vcc), 22(Ch11 - d22)
EN G1 COMPARTMENT PRESSURIZATION PRESENT
MOVE
00.03.12 24042 RP3.2 PSL_EP
Terminal strip: TB-DI-03 Terminals: 23(+24Vcc), 24(Ch12 - d24) EN SWITCHBOARDS COMPART. PRESSURIZ. PRESENT
MOVE
24045 RP4.2 PSL_TR
00.03.13
TRASFORMER COMPART. PRESSURIZ. PRESENT
Terminal strip: TB-DI-03 Terminals: 25(+24Vcc), 26(Ch13 - d26) Module: Digital Inputs
Model: F3236
00.03.14 Cable: Z7116
Terminal strip: TB-DI-03 Terminals: 27(+24Vcc), 28(Ch14 - d28) Rack: Rack00
Position: Slot03
00.03.15
Terminal strip: TB-DI-03 Terminals: 29(+24Vcc), 30(Ch15 - d30)

00.03.16
Terminal strip: TB-DI-03 Terminals: 31(+24Vcc), 32(Ch08 - d32)

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/24
1 check Martha Cluster MARTHA PLATF PES page 25
revision date name status: LZ based replaced replaced HARDWIRED DIG. INP. ELAB. (PAGE 3 OF 7)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 25 OF 114 HARDWIRED DIGITAL INPUTS ELABORATION (PAGE 4 OF 7) OUTPUTS

INPUTS_ENABLED
READING INPUTS VALUES ENABLED EN
MOVE
25000 011S.2 SMOKE_ALM
00.04.01
EN SMOKE ALARM STAU ROOM NOT PRESENT
Terminal strip: TB-DI-04 Terminals: 1(+24Vcc), 2(Ch01 - d2) MOVE
25003 021S.2 SMOKE_ALM
00.04.02 EN SMOKE ALARM G1 COMPART. NOT PRESENT
MOVE
Terminal strip: TB-DI-04 Terminals: 3(+24Vcc), 4(Ch02 - d4) 25006 031S.2 SMOKE_ALM
EN SMOKE ALARM SWTCHBRDS COMP. NOT PRESENT
00.04.03 MOVE
25009 041S.2 SMOKE_ALM
Terminal strip: TB-DI-04 Terminals: 5(+24Vcc), 6(Ch03 - d6)
EN SMOKE ALARM TRANSF. COMPART. NOT PRESENT
MOVE
00.04.04 25012 012S.2 SMOKE_FAIL
Terminal strip: TB-DI-04 Terminals: 7(+24Vcc), 8(Ch04 - d8) EN SMOKE FAIL. STAU ROOM NOT PRESENT
MOVE
25015 022S.2 SMOKE_FAIL
00.04.05
EN SMOKE FAIL. G1 COMPART. NOT PRESENT
Terminal strip: TB-DI-04 Terminals: 9(+24Vcc), 10(Ch05 - d10) MOVE
25018 032S.2 SMOKE_FAIL
00.04.06 EN SMOKE FAIL. SWTCHBRDS COMP. NOT PRESENT
MOVE
Terminal strip: TB-DI-04 Terminals: 11(+24Vcc), 12(Ch06 - d12) 25021 042S.2 SMOKE_FAIL
EN SMOKE FAIL. TRANSF. COMPART. NOT PRESENT
00.04.07 MOVE
25024 DMP1.2 DMP_ST
Terminal strip: TB-DI-04 Terminals: 13(+24Vcc), 14(Ch07 - d14)
EN STAU ROOM AIR DAMPERS CLOSED
MOVE
00.04.08 25027 DMP2.2 DMP_G1
Terminal strip: TB-DI-04 Terminals: 15(+24Vcc), 16(Ch08 - d16) EN G1 COMPART. AIR DAMPERS CLOSED
MOVE
25030 DMP3.2 DMP_EP
00.04.09
EN SWTCHBRDS COMPART. AIR DAMPERS CLOSED
Terminal strip: TB-DI-04 Terminals: 17(+24Vcc), 18(Ch09 - d18) MOVE
25033 DMP4.2 DMP_TR
00.04.10 EN TRANSF. COMPART. AIR DAMPERS CLOSED
MOVE
Terminal strip: TB-DI-04 Terminals: 19(+24Vcc), 20(Ch10 - d20) 25036 R13.2 INR_REL_ST
EN INERGEN RELEASE STAU ROOM NOT OCCURR.
00.04.11 MOVE
25039 R23.2 INR_REL_G1
Terminal strip: TB-DI-04 Terminals: 21(+24Vcc), 22(Ch11 - d22)
EN INERGEN RELEASE G1 COMPART. NOT OCCURR.
MOVE
00.04.12 25042 R33.2 INR_REL_EP
Terminal strip: TB-DI-04 Terminals: 23(+24Vcc), 24(Ch12 - d24) EN INERGEN RELEASE SWTCHBRDS COMPART. NOT OCCURR.
MOVE
25045 R43.2 INR_REL_TR
00.04.13
INERGEN RELEASE TRANSF. COMPART. NOT OCCURR.
Terminal strip: TB-DI-04 Terminals: 25(+24Vcc), 26(Ch13 - d26) Module: Digital Inputs
Model: F3236
00.04.14 Cable: Z7116
Terminal strip: TB-DI-04 Terminals: 27(+24Vcc), 28(Ch14 - d28) Rack: Rack00
Position: Slot04
00.04.15
Terminal strip: TB-DI-04 Terminals: 29(+24Vcc), 30(Ch15 - d30)

00.04.16
Terminal strip: TB-DI-04 Terminals: 31(+24Vcc), 32(Ch08 - d32)

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/25
1 check Martha Cluster MARTHA PLATF PES page 26
revision date name status: LZ based replaced replaced HARDWIRED DIG. INP. ELAB. (PAGE 4 OF 7)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 26 OF 114 HARDWIRED DIGITAL INPUTS ELABORATION (PAGE 5 OF 7) OUTPUTS

INPUTS_ENABLED
READING INPUTS VALUES ENABLED EN
MOVE
26000 052S.1 SMOKE_FAIL
00.05.01
EN SMOKE FAIL. COMMON LINE NOT PRESENT
Terminal strip: TB-DI-05 Terminals: 1(+24Vcc), 2(Ch01 - d2) MOVE
26003 051S.1 SMOKE_ALM
00.05.02 EN SMOKE ALARM COMMON LINE NOT PRESENT
MOVE
Terminal strip: TB-DI-05 Terminals: 3(+24Vcc), 4(Ch02 - d4) 26006 TONES_SILENCER
EN TONES CTRL UNIT SILENCER PUSH-BUTTON ACTIV.
00.05.03 MOVE
26009 RB_A/B_REM_TRP
Terminal strip: TB-DI-05 Terminals: 5(+24Vcc), 6(Ch03 - d6)
EN PLATFORM EMERGENCY TRIP REMOTE COMMAND
MOVE
00.05.04 26012 FUPLGNET
Terminal strip: TB-DI-05 Terminals: 7(+24Vcc), 8(Ch04 - d8) EN PROD. EMERG. TRIP FROM FUSIB. PLUGS NOT ACTIV.
MOVE
26015 TRIPS_RES_PB
00.05.05
EN TRIPS RESET PUSH BUTTON ACTIV.
Terminal strip: TB-DI-05 Terminals: 9(+24Vcc), 10(Ch05 - d10) MOVE
26018 SPARE_DI5_CH07
00.05.06 EN AVAILABLE DIGITAL INPUT (NOT USED)
MOVE
Terminal strip: TB-DI-05 Terminals: 11(+24Vcc), 12(Ch06 - d12) 26021 SPARE_DI5_CH08
EN AVAILABLE DIGITAL INPUT (NOT USED)
00.05.07 MOVE
26024 SPARE_DI5_CH09
Terminal strip: TB-DI-05 Terminals: 13(+24Vcc), 14(Ch07 - d14)
EN AVAILABLE DIGITAL INPUT (NOT USED)
MOVE
00.05.08 26027 SPARE_DI5_CH10
Terminal strip: TB-DI-05 Terminals: 15(+24Vcc), 16(Ch08 - d16) EN AVAILABLE DIGITAL INPUT (NOT USED)
MOVE
26030 SPARE_DI5_CH11
00.05.09
EN AVAILABLE DIGITAL INPUT (NOT USED)
Terminal strip: TB-DI-05 Terminals: 17(+24Vcc), 18(Ch09 - d18) MOVE
26033 SPARE_DI5_CH12
00.05.10 EN AVAILABLE DIGITAL INPUT (NOT USED)
MOVE
Terminal strip: TB-DI-05 Terminals: 19(+24Vcc), 20(Ch10 - d20) 26036 SPARE_DI5_CH13
EN AVAILABLE DIGITAL INPUT (NOT USED)
00.05.11 MOVE
26039 SPARE_DI5_CH14
Terminal strip: TB-DI-05 Terminals: 21(+24Vcc), 22(Ch11 - d22)
EN AVAILABLE DIGITAL INPUT (NOT USED)
MOVE
00.05.12 26042 POWSUPP_24V_OK
Terminal strip: TB-DI-05 Terminals: 23(+24Vcc), 24(Ch12 - d24) EN 24VDC PS1 & PS2 POW. SUPP. IN SERVICE
MOVE
26045 RACK_PES_OK
00.05.13
HIMA PES RACK FUNCTIONING
Terminal strip: TB-DI-05 Terminals: 25(+24Vcc), 26(Ch13 - d26) Module: Digital Inputs
Model: F3236
00.05.14 Cable: Z7116
Terminal strip: TB-DI-05 Terminals: 27(+24Vcc), 28(Ch14 - d28) Rack: Rack00
Position: Slot05
00.05.15
Terminal strip: TB-DI-05 Terminals: 29(+24Vcc), 30(Ch15 - d30)

00.05.16
Terminal strip: TB-DI-05 Terminals: 31(+24Vcc), 32(Ch08 - d32)

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/26
1 check Martha Cluster MARTHA PLATF PES page 27
revision date name status: LZ based replaced replaced HARDWIRED DIG. INP. ELAB. (PAGE 5 OF 7)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 27 OF 114 HARDWIRED DIGITAL INPUTS ELABORATION (PAGE 6 OF 7) OUTPUTS


AVAILABLE EMPTY PAGE

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/27
1 check Martha Cluster MARTHA PLATF PES page 28
revision date name status: LZ based replaced replaced HARDWIRED DIG. INP. ELAB. (PAGE 6 OF 7)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 28 OF 114 HARDWIRED DIGITAL INPUTS ELABORATION (PAGE 7 OF 7) OUTPUTS


AVAILABLE EMPTY PAGE

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/28
1 check Martha Cluster MARTHA PLATF PES page 29
revision date name status: LZ based replaced replaced HARDWIRED DIG. INP. ELAB. (PAGE 7 OF 7)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 29 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL INPUTS ELABORATION (PAGE 1 OF 3) OUTPUTS
MODBUS FUNCTION CODE 06: WRITE (PRESET) SINGLE HOLDING (OUTPUT) REGISTER - MODBUS FUNCTION CODE 16: WRITE (PRESET) MULTIPLE HOLDING (OUTPUT) REGISTERS

MODB-IMP-WORD-0 G MODB-IMP-WORD-0
<>
MODBUS WORD REGISTER RECEIVED: 0 MOVE
29003 29000 0 IN0 SEL MODBUS WORD REGISTER RECEIVED: 0
IN1 29006
IF THERE ARE NO VARIATIONS OF THE RECEIVED MODBUS WORD
REGISTER VALUE, THE MODBUS WORD REGISTER VALUE USED IN
THE FOLLOWING OF THE APPLICATION PROGRAM IT IS ZEROED.

INPUTS_ENABLED
READING INPUTS VALUES ENABLED EN
MOVE
MODB-IMP-WORD-0 IN OT01 29012 SYSIOACKCMD_MODB
MODBUS WORD REGISTER RECEIVED: 0 OT02 EN SYSTEM I/O FAULTS ACKNOWLEDGMENT MODBUS COMMAND
MOVE
OT03 29015 TRIP_RES_MODB
OT04 EN TRIPS RESET MODBUS COMMAND
MOVE
OT05 29018 ELE_TRPS_SEL_MODB
OT06 EN ELECT. TRIPS INC./EXC. SEL. MODBUS COMMAND
MOVE
OT07 29021 SEL_UNM_MAN_MODB
OT08 EN MANN./UNMAN. SIGNALIZ. SEL. MODBUS COMMAND
WORDto16BOOL MOVE
OT09 29024 TONE_SIL_MODB
OT10 EN TONE CTRL UNIT SILENCING MODBUS COMMAND
MOVE
OT11 29027 ST_TRP_SEL_MODB
OT12 EN STAU ROOM TRIP INC./EXC. SEL. MODBUS COMMAND
MOVE
OT13 29030 G1_TRP_SEL_MODB
OT14 EN G1 COMPART. TRIP INC./EXC. SEL. MODBUS COMMAND
MOVE
OT15 29033 EP_TRP_SEL_MODB
29009
OT16 EN SWTCHBRDS COMPART. TRIP INC./EXC. SEL. MODBUS COMMAND
MOVE
29036 TR_TRP_SEL_MODB
Software Digital Inputs via ModBus serial link
Managed as a block of 16 values (=1 word, =1 ModBus register) EN TRANSF. COMPART. TRIP INC./EXC. SEL. MODBUS COMMAND
MOVE
Output OUT01 correspond to bit 0 of the ModBus register 29039 ST_CLDP_SEL_MODB
Output OUT16 correspond to bit15 of the ModBus register EN STAU ROOM AIR DAMP. CL. INC./EXC. SEL. MODBUS COMMAND
Holding Register: 0 MOVE
29042 G1_CLDP_SEL_MODB
EN G1 COMPART. AIR DAMP. CL. INC./EXC. SEL. MODBUS COMMAND
MOVE
29045 EP_CLDP_SEL_MODB
EN SWTCHBRDS COMPART. AIR DAMP. CL. INC./EXC. SEL. MODBUS COMMAND
MOVE
29048 TR_CLDP_SEL_MODB
EN TRANSF. COMPART. AIR DAMP. CL. INC./EXC. SEL. MODBUS COMMAND
MOVE
29051 ME_CLDP_SEL_MODB
EN MAIN ENTRANCE AIR DAMP. CL. INC./EXC. SEL. MODBUS COMMAND
MOVE
29054 PTF_TRP_SEL_MODB
EN PLATFORM GENERAL TRIP INC./EXC. SEL. MODBUS COMMAND
MOVE
29057 PRG_TRP_SEL_MODB
PURGING PANEL TRIP INC./EXC. SEL. MODBUS COMMAND

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/29
1 check Martha Cluster MARTHA PLATF PES page 30
revision date name status: LZ based replaced replaced SOFTWARE DIG. INP. ELAB. (PAGE 1 OF 3)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 30 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL INPUTS ELABORATION (PAGE 2 OF 3) OUTPUTS
MODBUS FUNCTION CODE 06: WRITE (PRESET) SINGLE HOLDING (OUTPUT) REGISTER - MODBUS FUNCTION CODE 16: WRITE (PRESET) MULTIPLE HOLDING (OUTPUT) REGISTERS

MODB-IMP-WORD-1 G MODB-IMP-WORD-1
<>
MODBUS WORD REGISTER RECEIVED: 1 MOVE
30003 30000 0 IN0 SEL MODBUS WORD REGISTER RECEIVED: 1
IN1 30006
IF THERE ARE NO VARIATIONS OF THE RECEIVED MODBUS WORD
REGISTER VALUE, THE MODBUS WORD REGISTER VALUE USED IN
THE FOLLOWING OF THE APPLICATION PROGRAM IT IS ZEROED.

INPUTS_ENABLED
READING INPUTS VALUES ENABLED EN
MOVE
MODB-IMP-WORD-1 IN OT01 30012 PRS_TRP_SEL_MODB
MODBUS WORD REGISTER RECEIVED: 1 OT02 EN PRESSUR. GEN. TRIP INC./EXC. SEL. MODBUS COMMAND
MOVE
OT03 30015 IN_ST_SEL_MODB
OT04 EN STAU ROOM INER. DISCH. INC./EXC. SEL. MODBUS COMMAND
MOVE
OT05 30018 IN_G1_SEL_MODB
OT06 EN G1 COMPART. INER. DISCH. INC./EXC. SEL. MODBUS COMMAND
MOVE
OT07 30021 IN_EP_SEL_MODB
OT08 EN SWTCHBRDS COMPART. INER. DISCH. INC./EXC. SEL. MODBUS COMMAND
WORDto16BOOL MOVE
OT09 30024 IN_TR_SEL_MODB
OT10 EN TRANSF. COMPART. INER. DISCH. INC./EXC. SEL. MODBUS COMMAND
MOVE
OT11 30027 DATE_READ_PULSE
OT12 EN DATE (YEAR, MONTH, DAY) READING PULSE
MOVE
OT13 30030 TIME_READ_PULSE
OT14 EN TIME (HOURS, MINUTES, SECONDS) READING PULSE
MOVE
OT15 30033 MIN_SYNCH_PULSE
30009
OT16 EN MINUTES SYNCHRONIZATION PULSE
MOVE
30036 HOUR_SYNCH_PULSE
Software Digital Inputs via ModBus serial link
Managed as a block of 16 values (=1 word, =1 ModBus register) EN HOURS SYNCHRONIZATION PULSE
MOVE
Output OUT01 correspond to bit 0 of the ModBus register 30039 DAY_SYNCH_PULSE
Output OUT16 correspond to bit15 of the ModBus register EN DAY SYNCHRONIZATION PULSE
Holding Register: 1 MOVE
30042 MODB-HR1-BIT10
EN AVAILABLE SPARE DIGITAL INPUT (NOT USED)
MOVE
30045 MODB-HR1-BIT11
EN AVAILABLE SPARE DIGITAL INPUT (NOT USED)
MOVE
30048 MODB-HR1-BIT12
EN AVAILABLE SPARE DIGITAL INPUT (NOT USED)
MOVE
30051 MODB-HR1-BIT13
EN AVAILABLE SPARE DIGITAL INPUT (NOT USED)
MOVE
30054 MODB-HR1-BIT14
EN AVAILABLE SPARE DIGITAL INPUT (NOT USED)
MOVE
30057 MODB-HR1-BIT15
AVAILABLE SPARE DIGITAL INPUT (NOT USED)

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/30
1 check Martha Cluster MARTHA PLATF PES page 31
revision date name status: LZ based replaced replaced SOFTWARE DIG. INP. ELAB. (PAGE 2 OF 3)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 31 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL INPUTS ELABORATION (PAGE 3 OF 3) OUTPUTS
MODBUS FUNCTION CODE 06: WRITE (PRESET) SINGLE HOLDING (OUTPUT) REGISTER - MODBUS FUNCTION CODE 16: WRITE (PRESET) MULTIPLE HOLDING (OUTPUT) REGISTERS

MODB-IMP-WORD-2 G MODB-IMP-WORD-2
<>
MODBUS WORD REGISTER RECEIVED: 2 MOVE
31003 31000 0 IN0 SEL MDBUS WORD REGISTER RECEIVED: 2
IN1 31006
IF THERE ARE NO VARIATIONS OF THE RECEIVED MODBUS WORD
REGISTER VALUE, THE MODBUS WORD REGISTER VALUE USED IN
THE FOLLOWING OF THE APPLICATION PROGRAM IT IS ZEROED.

INPUTS_ENABLED
READING INPUTS VALUES ENABLED EN
MOVE
MODB-IMP-WORD-2 IN OT01 31012 MODB-HR2-BIT0
MDBUS WORD REGISTER RECEIVED: 2 OT02 EN AVAILABLE SPARE DIGITAL INPUT (NOT USED)
MOVE
OT03 31015 MODB-HR2-BIT1
OT04 EN AVAILABLE SPARE DIGITAL INPUT (NOT USED)
MOVE
OT05 31018 MODB-HR2-BIT2
OT06 EN AVAILABLE SPARE DIGITAL INPUT (NOT USED)
MOVE
OT07 31021 MODB-HR2-BIT3
OT08 EN AVAILABLE SPARE DIGITAL INPUT (NOT USED)
WORDto16BOOL MOVE
OT09 31024 MODB-HR2-BIT4
OT10 EN AVAILABLE SPARE DIGITAL INPUT (NOT USED)
MOVE
OT11 31027 MODB-HR2-BIT5
OT12 EN AVAILABLE SPARE DIGITAL INPUT (NOT USED)
MOVE
OT13 31030 MODB-HR2-BIT6
OT14 EN AVAILABLE SPARE DIGITAL INPUT (NOT USED)
MOVE
OT15 31033 MODB-HR2-BIT7
31009
OT16 EN AVAILABLE SPARE DIGITAL INPUT (NOT USED)
MOVE
31036 MODB-HR2-BIT8
Software Digital Inputs via ModBus serial link
Managed as a block of 16 values (=1 word, =1 ModBus register) EN AVAILABLE SPARE DIGITAL INPUT (NOT USED)
MOVE
Output OUT01 correspond to bit 0 of the ModBus register 31039 MODB-HR2-BIT9
Output OUT16 correspond to bit15 of the ModBus register EN AVAILABLE SPARE DIGITAL INPUT (NOT USED)
Holding Register: 2 MOVE
31042 MODB-HR2-BIT10
EN AVAILABLE SPARE DIGITAL INPUT (NOT USED)
MOVE
31045 MODB-HR2-BIT11
EN AVAILABLE SPARE DIGITAL INPUT (NOT USED)
MOVE
31048 MODB-HR2-BIT12
EN AVAILABLE SPARE DIGITAL INPUT (NOT USED)
MOVE
31051 MODB-HR2-BIT13
EN AVAILABLE SPARE DIGITAL INPUT (NOT USED)
MOVE
31054 MODB-HR2-BIT14
EN AVAILABLE SPARE DIGITAL INPUT (NOT USED)
MOVE
31057 MODB-HR2-BIT15
AVAILABLE SPARE DIGITAL INPUT (NOT USED)

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/31
1 check Martha Cluster MARTHA PLATF PES page 32
revision date name status: LZ based replaced replaced SOFTWARE DIG. INP. ELAB. (PAGE 3 OF 3)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 32 OF 114 SOFTWARE - MODBUS SERIAL LINK - ANALOG INPUTS ELABORATION OUTPUTS
MODBUS FUNCTION CODE 06: WRITE (PRESET) SINGLE HOLDING (OUTPUT) REGISTER - MODBUS FUNCTION CODE 16: WRITE (PRESET) MULTIPLE HOLDING (OUTPUT) REGISTERS

INPUTS_ENABLED
READING INPUTS VALUES ENABLED EN
>UINT
MODB-IMP-WORD-3 32000 YEAR_IN
MODBUS WORD REGISTER RECEIVED: 3 EN YEAR VALUE TO BE READ (0...99)
>UINT
MODB-IMP-WORD-4 32003 MONTH_IN
MODBUS WORD REGISTER RECEIVED: 4 EN MONTH VALUE TO BE READ (1...12)
>UINT
MODB-IMP-WORD-5 32006 DAY_IN
MODBUS WORD REGISTER RECEIVED: 5 EN DAY VALUE TO BE READ (1...31)
>UINT
MODB-IMP-WORD-6 32009 HOURS_IN
MODBUS WORD REGISTER RECEIVED: 6 EN HOURS VALUE TO BE READ (0...23)
>UINT
MODB-IMP-WORD-7 32012 MINUTES_IN
MODBUS WORD REGISTER RECEIVED: 7 EN MINUTES VALUE TO BE READ (0...59)
>UINT
MODB-IMP-WORD-8 32015 SECONDS_IN
MODBUS WORD REGISTER RECEIVED: 8 SECONDS VALUE TO BE READ (0...59)

MODB-IMP-WORD-LIM
MODBUS ANAL. SIGN. REC. MEM. AREA LIMIT (0...499)
MODB-IMP/EXP-WORD-LIM
MODBUS ANAL. SIGN. REC./SENT MEM. AREA LIMIT (1000...1499)

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/32
1 check Martha Cluster MARTHA PLATF PES page 33
revision date name status: LZ based replaced replaced SOFTWARE ANALOG INPUTS ELABORATION
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 33 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL INPUTS ELABORATION (COILS) OUTPUTS
AVAILABLE EMPTY PAGE
MODBUS FUNCTION CODE 05: WRITE (FORCE) SINGLE COIL (OUTPUT) - MODBUS FUNCTION CODE 15: WRITE (FORCE) MULTIPLE COILS (OUTPUTS)

MODB-IMP-BOOL-0
MODBUS DIG. SIGN. REC.: 0 - AVAILAB. (NOT USED)
MODB-IMP-BOOL-LIM
MODBUS DIG. SIGN. REC. MEM. AREA LIMIT (0...499)
MODB-IMP/EXP-BOOL-LIM
MODBUS DIG. SIGN. REC./SENT MEM. AREA LIMIT (1000...1499)

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/33
1 check Martha Cluster MARTHA PLATF PES page 34
revision date name status: LZ based replaced replaced SOFTWARE DIGITAL INPUTS ELABOR. (COILS)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 34 OF 114 PES SYSTEM CLOCK MANAGEMENT OUTPUTS

H8-UHR-3 Date and Time


YEAR_IN Year Year YEAR_OUT
YEAR VALUE TO BE READ (0...99) Month Month ACTUAL YEAR VALUE (0...99)
MONTH_IN Day Day MONTH_OUT
MONTH VALUE TO BE READ (1...12) >Read in Date ACTUAL MONTH VALUE (1...12)
DAY_IN Hours Hours DAY_OUT
DAY VALUE TO BE READ (1...31) Minutes H8-UHR-3 Minutes ACTUAL DAY VALUE (1...31)
DATE_READ_PULSE Seconds Seconds
DATE (YEAR, MONTH, DAY) READING PULSE >Read in Time Milliseconds HOURS_OUT
>Full Min.Pulse Full Min.Pulse ACTUAL HOURS VALUE (0...23)
HOURS_IN >Full Hour Pulse Full Hour Pulse MINUTES_OUT
HOURS VALUE TO BE READ (0...23) >Full Day Pulse Full Day 34000
Pulse ACTUAL MINUTES VALUE (0...59)
MINUTES_IN SECONDS_OUT
MINUTES VALUE TO BE READ (0...59) ACTUAL SECONDS VALUE (0...59)
SECONDS_IN MSECONDI_OUT
SECONDS VALUE TO BE READ (0...59) ACTUAL MILLISECONDS VALUE (0...999)
TIME_READ_PULSE
TIME (HOURS, MINUTES, SECONDS) READING PULSE FULL_MIN_PULSE
MINUTE COMPLETED PULSE
MIN_SYNCH_PULSE FULL_HOUR_PULSE
MINUTES SYNCHRONIZATION PULSE HOUR COMPLETED PULSE
HOUR_SYNCH_PULSE FULL_DAY_PULSE
HOURS SYNCHRONIZATION PULSE DAY COMPLETED PULSE
DAY_SYNCH_PULSE
DAY SYNCHRONIZATION PULSE

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/34
1 check Martha Cluster MARTHA PLATF PES page 35
revision date name status: LZ based replaced replaced PES SYSTEM CLOCK MANAGEMENT
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 35 OF 114 PES SYSTEM GENERAL DIAGNOSTIC OUTPUTS

RACK_PES_OK RS14 RACK_PES_OK


HIMA PES RACK FUNCTIONING HIMA PES RACK FUNCTIONING

POWSUPP_24V_OK RS15 PESSYS_OK


24VDC PS1 & PS2 POW. SUPP. IN SERVICE HIMA PES SYSTEM NORMAL FUNCTIONING

SYSERRCODENOERR
& RS13 PES_ALM
PES SYSTEM NO ERROR PRESENT &
35003 HIMA PES SYS. AT LEAST ONE FAULT PRES. SIGNALIZ.
SYSFLTMSK1NOFLT
NO FAULTS IN SYSTEM FAULTS MASK #1 35000

SYSFLTMSK2NOFLT
NO FAULTS IN SYSTEM FAULTS MASK #2

SYSIONOERR
PES I/O MODULES NO ERROR PRESENT

CUM-IOMOD-OK
ALL PES I/O MODULES FUNCTIONING

CUM-CHMODIO-OK
I/O DO MODULES ALL CHANNELS WORKING

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/35
1 check Martha Cluster MARTHA PLATF PES page 36
revision date name status: LZ based replaced replaced PES SYSTEM GENERAL DIAGNOSTIC
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 36 OF 114 TRIP LOGICS PROCESSING (PAGE 1 OF 34) OUTPUTS


SMOKE DETECTORS CONTROL UNIT POWER-ON MANAGEMENT (PAGE 1 OF 2)

003S.2 SMOKE_FAIL IN Q SMOKE_TRIP_INHIB


TP
SMOKE DETECT. SYST. FAIL. NOT PRESENT PT 36003
ET SMOKE TRIP INHIBITION ACTIVATED

011S.2 SMOKE_ALM
SMOKE ALARM STAU ROOM NOT PRESENT

012S.2 SMOKE_FAIL >=1


SMOKE FAIL. STAU ROOM NOT PRESENT

021S.2 SMOKE_ALM
SMOKE ALARM G1 COMPART. NOT PRESENT

022S.2 SMOKE_FAIL 36000


SMOKE FAIL. G1 COMPART. NOT PRESENT

031S.2 SMOKE_ALM
SMOKE ALARM SWTCHBRDS COMP. NOT PRESENT

032S.2 SMOKE_FAIL
SMOKE FAIL. SWTCHBRDS COMP. NOT PRESENT

041S.2 SMOKE_ALM
SMOKE ALARM TRANSF. COMPART. NOT PRESENT

042S.2 SMOKE_FAIL
SMOKE FAIL. TRANSF. COMPART. NOT PRESENT

051S.1 SMOKE_ALM
SMOKE ALARM COMMON LINE NOT PRESENT

052S.1 SMOKE_FAIL
SMOKE FAIL. COMMON LINE NOT PRESENT

SMK_TRP_INH_TIME
SMOKE TRIP INHIBITION TIME

AT THE SMOKE DETECTORS CONTROL UNIT POWER-ON ALL ALARMS AND FAULTS INDICATIONS ARE ACTIVATED AT THE SAME TIME. AT THE OCCURENCE OF
THIS EVENT, A 50 SECONDS INHIBITION OF ALL ALARMS AND FAULTS INDICATIONS IT'S ACTIVATED, TO AVOID THE PES SYSTEM ACTIVATION OF TRIPS
CONDITIONS FOR NON REAL SMOKING PRESENCE DETECTIONS.
Project developed by: GDC
3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/36
1 check Martha Cluster MARTHA PLATF PES page 37
revision date name status: LZ based replaced replaced TRIP LOGICS PROCESSING (PAGE 1 OF 34)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 37 OF 114 TRIP LOGICS PROCESSING (PAGE 2 OF 34) OUTPUTS


SMOKE DETECTORS CONTROL UNIT POWER-ON MANAGEMENT (PAGE 1 OF 2)

003S.2 SMOKE_FAIL 003S.2 SMOKE_FAIL


>=1
SMOKE DETECT. SYST. FAIL. NOT PRESENT 37000 SMOKE DETECT. SYST. FAIL. NOT PRESENT

011S.2 SMOKE_ALM 011S.2 SMOKE_ALM


>=1
SMOKE ALARM STAU ROOM NOT PRESENT 37003 SMOKE ALARM STAU ROOM NOT PRESENT

012S.2 SMOKE_FAIL 012S.2 SMOKE_FAIL


>=1
SMOKE FAIL. STAU ROOM NOT PRESENT 37006 SMOKE FAIL. STAU ROOM NOT PRESENT

021S.2 SMOKE_ALM 021S.2 SMOKE_ALM


>=1
SMOKE ALARM G1 COMPART. NOT PRESENT 37009 SMOKE ALARM G1 COMPART. NOT PRESENT

022S.2 SMOKE_FAIL 022S.2 SMOKE_FAIL


>=1
SMOKE FAIL. G1 COMPART. NOT PRESENT 37012 SMOKE FAIL. G1 COMPART. NOT PRESENT

031S.2 SMOKE_ALM 031S.2 SMOKE_ALM


>=1
SMOKE ALARM SWTCHBRDS COMP. NOT PRESENT 37015 SMOKE ALARM SWTCHBRDS COMP. NOT PRESENT

032S.2 SMOKE_FAIL 032S.2 SMOKE_FAIL


>=1
SMOKE FAIL. SWTCHBRDS COMP. NOT PRESENT 37018 SMOKE FAIL. SWTCHBRDS COMP. NOT PRESENT

041S.2 SMOKE_ALM 041S.2 SMOKE_ALM


>=1
SMOKE ALARM TRANSF. COMPART. NOT PRESENT 37021 SMOKE ALARM TRANSF. COMPART. NOT PRESENT

042S.2 SMOKE_FAIL 042S.2 SMOKE_FAIL


>=1
SMOKE FAIL. TRANSF. COMPART. NOT PRESENT 37024 SMOKE FAIL. TRANSF. COMPART. NOT PRESENT

051S.1 SMOKE_ALM 051S.1 SMOKE_ALM


>=1
SMOKE ALARM COMMON LINE NOT PRESENT 37027 SMOKE ALARM COMMON LINE NOT PRESENT

052S.1 SMOKE_FAIL 052S.1 SMOKE_FAIL


>=1
SMOKE FAIL. COMMON LINE NOT PRESENT 37030 SMOKE FAIL. COMMON LINE NOT PRESENT

SMOKE_TRIP_INHIB
SMOKE TRIP INHIBITION ACTIVATED

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/37
1 check Martha Cluster MARTHA PLATF PES page 38
revision date name status: LZ based replaced replaced TRIP LOGICS PROCESSING (PAGE 2 OF 34)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 38 OF 114 TRIP LOGICS PROCESSING (PAGE 3 OF 34) OUTPUTS


SMOKE DETECTION TRIP AND INERGEN RELEASE MANAGEMENT

011S.2 SMOKE_ALM NO_ALM1 NO_BL 011-2S.2 SMK_TRP


SMOKE ALARM STAU ROOM NOT PRESENT NO_AV1 NO_SC STAU ROOM SMOKE TRIP NOT PRESENT
2oo2ALM
012S.2 SMOKE_FAIL NO_ALM2
011-2S.2 INR_REL
SMOKE FAIL. STAU ROOM NOT PRESENT NO_AV2 38000
STAU ROOM INERGEN RELEASE NOT PRESENT
051S.1 SMOKE_ALM
SMOKE ALARM COMMON LINE NOT PRESENT
052S.1 SMOKE_FAIL
SMOKE FAIL. COMMON LINE NOT PRESENT

021S.2 SMOKE_ALM NO_ALM1 NO_BL 021-2S.2 SMK_TRP


SMOKE ALARM G1 COMPART. NOT PRESENT NO_AV1 NO_SC G1 COMPART. SMOKE TRIP NOT PRESENT
2oo2ALM
022S.2 SMOKE_FAIL NO_ALM2
021-2S.2 INR_REL
SMOKE FAIL. G1 COMPART. NOT PRESENT NO_AV2 38003
G1 COMPART. INERGEN REL. NOT PRESENT
051S.1 SMOKE_ALM
SMOKE ALARM COMMON LINE NOT PRESENT
052S.1 SMOKE_FAIL
SMOKE FAIL. COMMON LINE NOT PRESENT

031S.2 SMOKE_ALM NO_ALM1 NO_BL 031-2S.2 SMK_TRP


SMOKE ALARM SWTCHBRDS COMP. NOT PRESENT NO_AV1 NO_SC SWTCHBRDS COMPART. SMOKE TRIP NOT PRESENT
2oo2ALM
032S.2 SMOKE_FAIL NO_ALM2
031-2S.2 INR_REL
SMOKE FAIL. SWTCHBRDS COMP. NOT PRESENT NO_AV2 38006
SWTCHBRDS COMPART. INERGEN REL. NOT PRES.
051S.1 SMOKE_ALM
SMOKE ALARM COMMON LINE NOT PRESENT
052S.1 SMOKE_FAIL
SMOKE FAIL. COMMON LINE NOT PRESENT

041S.2 SMOKE_ALM NO_ALM1 NO_BL 041-2S.2 SMK_TRP


SMOKE ALARM TRANSF. COMPART. NOT PRESENT NO_AV1 NO_SC TRANSF. COMPART. SMOKE TRIP NOT PRESENT
2oo2ALM
042S.2 SMOKE_FAIL NO_ALM2
041-2S.2 INR_REL
SMOKE FAIL. TRANSF. COMPART. NOT PRESENT NO_AV2 38009
TRANSF. COMPART. INERGEN REL. NOT PRES.
051S.1 SMOKE_ALM
SMOKE ALARM COMMON LINE NOT PRESENT
052S.1 SMOKE_FAIL
SMOKE FAIL. COMMON LINE NOT PRESENT

NOTE: the smoke detectors common line is a common connection of all the seconds smoke detectors of the differents rooms and/or compartments. The intervention
(failure and/or alarm) of at least one of the smoke detectors connected to this common line activates the corresponding signal (failure and/or alarm) of the comon line.

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/38
1 check Martha Cluster MARTHA PLATF PES page 39
revision date name status: LZ based replaced replaced TRIP LOGICS PROCESSING (PAGE 3 OF 34)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 39 OF 114 TRIP LOGICS PROCESSING (PAGE 4 OF 34) OUTPUTS


STAU ROOM TRIP MANAGEMENT

RET2.3 ELETRP_INC S Q RS/1 ST_TRIP


&
ELECT. TRIPS SELECT. INCLUDED POSIT. 39003 R MEMS STAU ROOM TRIP COMMAND
TRUE PRE 39006 ST_TRIP_RES_AV
RB_A/B_REM_TRP &
39009 STAU ROOM TRIP RES. AVAIL.
PLATFORM EMERGENCY TRIP REMOTE COMMAND
ST_TRIP
RPA.2 PLT_ABD &
STAU ROOM TRIP CONDITION PRESENT
PLATF. ABAND. PUSH-BUTTONS NOT ACTIV.

011-2S.2 SMK_TRP 39000


STAU ROOM SMOKE TRIP NOT PRESENT
011F.2 FLAME_ALM
FLAME ALARM STAU ROOM NOT PRESENT
102E.2 EXPG_ALM
EXPL. GAS ALARM STAU ROOM NOT PRES.
R13.2 INR_REL_ST
INERGEN RELEASE STAU ROOM NOT OCCURR.

TRIPS_RES_PB
TRIPS RESET PUSH BUTTON ACTIV.

CAUSES-EFFECTS DIAGRAM REFERENCES

EFFECT:
STAU ROOM TRIP (row 32)

CAUSES:
PLATFORM ABANDON - IMMEDIATE (column 1)
PLATFORM EMERGENCY TRIP REMOTE COMMAND - IMMEDIATE (column 2)
EXPLOSIVE GAS ALARM STAU ROOM - IMMEDIATE (column 50)
SMOKE ALARM STAU ROOM - IMMEDIATE (column 77)
FLAME ALARM STAU ROOM - IMMEDIATE (column 107)
INERGEN MANUAL RELEASE STAU ROOM - IMMEDIATE (column 117)

NOTE:
IN CAUSES-EFFECTS DIAGRAM IT IS NOT PRESENT THE CAUSE:
ELECTRICAL TRIPS SELECTOR INCL./EXCL. - INCLUDED (column 5)
IN THIS APPLICATION PROGRAM IT IS PRESENT INSTEAD THE CAUSE:
ELECTRICAL TRIPS SELECTOR INCL./EXCL. - INCLUDED (column 5)

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/39
1 check Martha Cluster MARTHA PLATF PES page 40
revision date name status: LZ based replaced replaced TRIP LOGICS PROCESSING (PAGE 4 OF 34)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 40 OF 114 TRIP LOGICS PROCESSING (PAGE 5 OF 34) OUTPUTS


G1 COMPARTMENT TRIP MANAGEMENT

RET2.3 ELETRP_INC S Q RS/2 G1_TRIP


&
ELECT. TRIPS SELECT. INCLUDED POSIT. 40003 R MEMS G1 COMPART. TRIP COMMAND
TRUE PRE 40006 G1_TRIP_RES_AV
RB_A/B_REM_TRP &
40009 G1 COMPART. TRIP RES. AVAIL.
PLATFORM EMERGENCY TRIP REMOTE COMMAND
G1_TRIP
RPA.2 PLT_ABD
G1 COMPART. TRIP CONDITION PRESENT
PLATF. ABAND. PUSH-BUTTONS NOT ACTIV.

021-2S.2 SMK_TRP
G1 COMPART. SMOKE TRIP NOT PRESENT
&
012F.2 FLAME_ALM
FLAME ALARM G1 COMPART. NOT PRESENT
112E.2 EXPG_ALM
EXPL. GAS ALARM G1 COMPART. NOT PRES.
R23.2 INR_REL_G1
INERGEN RELEASE G1 COMPART. NOT OCCURR.
40000
031-2S.2 SMK_TRP
SWTCHBRDS COMPART. SMOKE TRIP NOT PRESENT
013F.2 FLAME_ALM
FLAME ALARM SWTCHBRDS COMP. NOT PRESENT
122E.2 EXPG_ALM
EXPL. GAS ALARM SWTCHBRDS COMP. NOT PRESENT CAUSES-EFFECTS DIAGRAM REFERENCES
R33.2 INR_REL_EP
INERGEN RELEASE SWTCHBRDS COMPART. NOT OCCURR.
EFFECT:
G1 COMPARTMENT TRIP (row 21)
011-2S.2 SMK_TRP
STAU ROOM SMOKE TRIP NOT PRESENT CAUSES:
011F.2 FLAME_ALM PLATFORM ABANDON - IMMEDIATE (column 1)
FLAME ALARM STAU ROOM NOT PRESENT PLATFORM EMERGENCY TRIP REMOTE COMMAND - IMMEDIATE (column 2)
102E.2 EXPG_ALM ELECTRICAL TRIPS SELECTOR INCL./EXCL. - INCLUDED (column 5)
EXPL. GAS ALARM STAU ROOM NOT PRES. EXPLOSIVE GAS ALARM G1 COMPARTMENT - IMMEDIATE (column 41)
R13.2 INR_REL_ST EXPLOSIVE GAS ALARM SWITCHBOARDS COMPART. - IMMEDIATE (column 45)
INERGEN RELEASE STAU ROOM NOT OCCURR.
EXPLOSIVE GAS ALARM STAU ROOM - IMMEDIATE (column 50)
SMOKE ALARM G1 COMPARTMENT - IMMEDIATE (column 70)
TRIPS_RES_PB SMOKE ALARM SWITCHBOARDS COMPARTMENT - IMMEDIATE (column 76)
TRIPS RESET PUSH BUTTON ACTIV. SMOKE ALARM STAU ROOM - IMMEDIATE (column 77)
FLAME ALARM G1 COMPARTMENT - IMMEDIATE (column 100)
FLAME ALARM SWITCHBOARDS COMPARTMENT - IMMEDIATE (column 106)
FLAME ALARM STAU ROOM - IMMEDIATE (column 107)
INERGEN MANUAL RELEASE STAU ROOM - IMMEDIATE (column 117)
INERGEN MANUAL RELEASE G1 COMPART. - IMMEDIATE (column 118)
INERGEN MANUAL RELEASE SWITCHBOARDS COMPART. - IMMEDIATE (column 119)

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/40
1 check Martha Cluster MARTHA PLATF PES page 41
revision date name status: LZ based replaced replaced TRIP LOGICS PROCESSING (PAGE 5 OF 34)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 41 OF 114 TRIP LOGICS PROCESSING (PAGE 6 OF 34) OUTPUTS


SWITCHBOARDS COMPARTMENT TRIP MANAGEMENT

RET2.3 ELETRP_INC S Q RS/3 EP_TRIP


&
ELECT. TRIPS SELECT. INCLUDED POSIT. 41003 R MEMS SWTCHBRDS COMPART. TRIP COMMAND
TRUE PRE 41006 EP_TRIP_RES_AV
RB_A/B_REM_TRP &
41009 SWTCHBRDS COMPART. TRIP RES. AVAIL.
PLATFORM EMERGENCY TRIP REMOTE COMMAND
EP_TRIP
RPA.2 PLT_ABD
SWTCHBRDS COMPART. TRIP CONDITION PRESENT
PLATF. ABAND. PUSH-BUTTONS NOT ACTIV.
&
011-2S.2 SMK_TRP
STAU ROOM SMOKE TRIP NOT PRESENT
011F.2 FLAME_ALM
FLAME ALARM STAU ROOM NOT PRESENT
102E.2 EXPG_ALM 41000
EXPL. GAS ALARM STAU ROOM NOT PRES.
R13.2 INR_REL_ST
INERGEN RELEASE STAU ROOM NOT OCCURR.

031-2S.2 SMK_TRP
SWTCHBRDS COMPART. SMOKE TRIP NOT PRESENT
013F.2 FLAME_ALM
FLAME ALARM SWTCHBRDS COMP. NOT PRESENT
122E.2 EXPG_ALM CAUSES-EFFECTS DIAGRAM REFERENCES
EXPL. GAS ALARM SWTCHBRDS COMP. NOT PRESENT
R33.2 INR_REL_EP EFFECT:
INERGEN RELEASE SWTCHBRDS COMPART. NOT OCCURR.
SWITCHBOARDS COMPARTMENT TRIP (row 29)

TRIPS_RES_PB CAUSES:
TRIPS RESET PUSH BUTTON ACTIV. PLATFORM ABANDON - IMMEDIATE (column 1)
PLATFORM EMERGENCY TRIP REMOTE COMMAND - IMMEDIATE (column 2)
ELECTRICAL TRIPS SELECTOR INCL./EXCL. - INCLUDED (column 5)
EXPLOSIVE GAS ALARM STAU ROOM - IMMEDIATE (column 50)
SMOKE ALARM SWITCHBOARDS COMPARTMENT - IMMEDIATE (column 76)
SMOKE ALARM STAU ROOM - IMMEDIATE (column 77)
FLAME ALARM SWITCHBOARDS COMPARTMENT - IMMEDIATE (column 106)
FLAME ALARM STAU ROOM - IMMEDIATE (column 107)
INERGEN MANUAL RELEASE STAU ROOM - IMMEDIATE (column 117)
INERGEN MANUAL RELEASE SWITCHBOARDS COMPART. - IMMEDIATE (column 119)

NOTES:
IN CAUSES-EFFECTS DIAGRAM IT IS NOT PRESENT THE CAUSE:
EXPLOSIVE GAS ALARM SWITCHBOARDS COMPART. - IMMEDIATE (column 45)
IN THIS APPLICATION PROGRAM IT IS PRESENT INSTEAD THE CAUSE:
EXPLOSIVE GAS ALARM SWITCHBOARDS COMPART. - IMMEDIATE (column 45)

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/41
1 check Martha Cluster MARTHA PLATF PES page 42
revision date name status: LZ based replaced replaced TRIP LOGICS PROCESSING (PAGE 6 OF 34)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 42 OF 114 TRIP LOGICS PROCESSING (PAGE 7 OF 34) OUTPUTS


TRANSFORMER COMPARTMENT TRIP MANAGEMENT

RET2.3 ELETRP_INC S Q RS/4 TR_TRIP


&
ELECT. TRIPS SELECT. INCLUDED POSIT. 42003 R MEMS TRANSF. COMPART. TRIP COMMAND
TRUE PRE 42006 TR_TRIP_RES_AV
RB_A/B_REM_TRP &
42009 TRANSF. COMPART. TRIP RES. AVAIL.
PLATFORM EMERGENCY TRIP REMOTE COMMAND
TR_TRIP
RPA.2 PLT_ABD
TRANSF. COMPART. TRIP CONDITION PRESENT
PLATF. ABAND. PUSH-BUTTONS NOT ACTIV.
&
041-2S.2 SMK_TRP
TRANSF. COMPART. SMOKE TRIP NOT PRESENT
014F.2 FLAME_ALM
FLAME ALARM TRANSF. COMPART. NOT PRESENT
132E.2 EXPG_ALM 42000 CAUSES-EFFECTS DIAGRAM REFERENCES
EXPL. GAS ALARM TRANSF. COMP. NOT PRESENT
R43.2 INR_REL_TR
EFFECT:
INERGEN RELEASE TRANSF. COMPART. NOT OCCURR.
TRANSFORMER COMPARTMENT TRIP (row 23) - EX MV CABIN TRIP

031-2S.2 SMK_TRP CAUSES:


SWTCHBRDS COMPART. SMOKE TRIP NOT PRESENT PLATFORM ABANDON - IMMEDIATE (column 1)
013F.2 FLAME_ALM ELECTRICAL TRIPS SELECTOR INCL./EXCL. - INCLUDED (column 5)
FLAME ALARM SWTCHBRDS COMP. NOT PRESENT EXPLOSIVE GAS ALARM TRANSFORMER COMPART. - IMMEDIATE (column 43)
122E.2 EXPG_ALM EXPLOSIVE GAS ALARM SWITCHBOARDS COMPART. - IMMEDIATE (column 45)
EXPL. GAS ALARM SWTCHBRDS COMP. NOT PRESENT SMOKE ALARM TRANSFORMER COMPARTMENT - IMMEDIATE (column 71)
R33.2 INR_REL_EP
SMOKE ALARM SWITCHBOARDS COMPARTMENT - IMMEDIATE (column 76)
FLAME ALARM TRANSFORMER COMPARTMENT - IMMEDIATE (column 101)
INERGEN RELEASE SWTCHBRDS COMPART. NOT OCCURR.
FLAME ALARM SWITCHBOARDS COMPARTMENT - IMMEDIATE (column 106)
TRIPS_RES_PB INERGEN MANUAL RELEASE SWITCHBOARDS COMPART. - IMMEDIATE (column 119)
TRIPS RESET PUSH BUTTON ACTIV. INERGEN MANUAL RELEASE TRANSFORMER COMPART. - IMMEDIATE (column 120)

NOTES:
TRANSFORMER COMPARTMENT TRIP REPLACE MV CABIN TRIP IN CAUSES-
EFFECTS DIAGRAM.
IN CAUSES-EFFECTS DIAGRAM IT IS NOT PRESENT THE CAUSE:
PLATFORM EMERGENCY TRIP REMOTE COMMAND - IMMEDIATE (column 2)
IN CAUSES-EFFECTS DIAGRAM ARE PRESENTS THE CAUSES:
FLAME ALARM STAU ROOM - IMMEDIATE (column 107)
INERGEN MANUAL RELEASE STAU ROOM - IMMEDIATE (column 117)
IN THIS APPLICATION PROGRAM IT IS PRESENT INSTEAD THE CAUSE:
PLATFORM EMERGENCY TRIP REMOTE COMMAND - IMMEDIATE (column 2)
IN THIS APPLICATION PROGRAM ARE NOT PRESENTS INSTEAD THE CAUSES:
FLAME ALARM STAU ROOM - IMMEDIATE (column 107)
INERGEN MANUAL RELEASE STAU ROOM - IMMEDIATE (column 117)

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/42
1 check Martha Cluster MARTHA PLATF PES page 43
revision date name status: LZ based replaced replaced TRIP LOGICS PROCESSING (PAGE 7 OF 34)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 43 OF 114 TRIP LOGICS PROCESSING (PAGE 8 OF 34 OUTPUTS


STAU ROOM AIR DAMPERS CLOSING MANAGEMENT

RET2.3 ELETRP_INC S Q SOV1 ST_CL_DMP


&
ELECT. TRIPS SELECT. INCLUDED POSIT. 43003 R MEMS STAU ROOM AIR DAMPERS CLOSING
TRUE PRE 43006 ST_CL_DMP_RES_AV
RB_A/B_REM_TRP &
43009 STAU ROOM AIR DAMP. CLOSING RES. AVAIL.
PLATFORM EMERGENCY TRIP REMOTE COMMAND
ST_CL_DMP
RPA.2 PLT_ABD
STAU ROOM AIR DAMPERS CLOSING CONDIT. PRES.
PLATF. ABAND. PUSH-BUTTONS NOT ACTIV.
&
011-2S.2 SMK_TRP
STAU ROOM SMOKE TRIP NOT PRESENT
011F.2 FLAME_ALM
FLAME ALARM STAU ROOM NOT PRESENT
102E.2 EXPG_ALM 43000
EXPL. GAS ALARM STAU ROOM NOT PRES.
R13.2 INR_REL_ST
INERGEN RELEASE STAU ROOM NOT OCCURR.

031-2S.2 SMK_TRP
SWTCHBRDS COMPART. SMOKE TRIP NOT PRESENT
013F.2 FLAME_ALM
FLAME ALARM SWTCHBRDS COMP. NOT PRESENT
122E.2 EXPG_ALM CAUSES-EFFECTS DIAGRAM REFERENCES
EXPL. GAS ALARM SWTCHBRDS COMP. NOT PRESENT
R33.2 INR_REL_EP EFFECT:
INERGEN RELEASE SWTCHBRDS COMPART. NOT OCCURR.
STAU ROOM AIR DAMPERS CLOSING (row 38)

TRIPS_RES_PB CAUSES:
TRIPS RESET PUSH BUTTON ACTIV. PLATFORM ABANDON - IMMEDIATE (column 1)
PLATFORM EMERGENCY TRIP REMOTE COMMAND - IMMEDIATE (column 2)
EXPLOSIVE GAS ALARM SWITCHBOARDS COMPART. - IMMEDIATE (column 45)
EXPLOSIVE GAS ALARM STAU ROOM - IMMEDIATE (column 50)
SMOKE ALARM SWITCHBOARDS COMPARTMENT - IMMEDIATE (column 76)
SMOKE ALARM STAU ROOM - IMMEDIATE (column 77)
FLAME ALARM SWITCHBOARDS COMPARTMENT - IMMEDIATE (column 106)
FLAME ALARM STAU ROOM - IMMEDIATE (column 107)
INERGEN MANUAL RELEASE STAU ROOM - IMMEDIATE (column 117)
INERGEN MANUAL RELEASE SWITCHBOARDS COMPART. - IMMEDIATE (column 119)

NOTES:
IN CAUSES-EFFECTS DIAGRAM IT IS NOT PRESENT THE CAUSE:
ELECTRICAL TRIPS SELECTOR INCL./EXCL. - INCLUDED (column 5)
IN THIS APPLICATION PROGRAM IT IS PRESENT INSTEAD THE CAUSE:
ELECTRICAL TRIPS SELECTOR INCL./EXCL. - INCLUDED (column 5)

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/43
1 check Martha Cluster MARTHA PLATF PES page 44
revision date name status: LZ based replaced replaced TRIP LOGICS PROCESSING (PAGE 8 OF 34)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 44 OF 114 TRIP LOGICS PROCESSING (PAGE 9 OF 34) OUTPUTS


G1 COMPARTMENT AIR DAMPERS CLOSING MANAGEMENT

RET2.3 ELETRP_INC S Q SOV2 G1_CL_DMP


&
ELECT. TRIPS SELECT. INCLUDED POSIT. 44003 R MEMS G1 COMPART. AIR DAMPERS CLOSING
TRUE PRE 44006 G1_CL_DMP_RES_AV
RB_A/B_REM_TRP &
44009 G1 COMPART. AIR DAMP. CLOSING RES. AVAIL.
PLATFORM EMERGENCY TRIP REMOTE COMMAND
G1_CL_DMP
RPA.2 PLT_ABD
G1 COMPART. AIR DAMPERS CLOSING CONDIT. PRES.
PLATF. ABAND. PUSH-BUTTONS NOT ACTIV.

021-2S.2 SMK_TRP
G1 COMPART. SMOKE TRIP NOT PRESENT
&
012F.2 FLAME_ALM
FLAME ALARM G1 COMPART. NOT PRESENT
112E.2 EXPG_ALM
EXPL. GAS ALARM G1 COMPART. NOT PRES.
R23.2 INR_REL_G1
INERGEN RELEASE G1 COMPART. NOT OCCURR.
44000 CAUSES-EFFECTS DIAGRAM REFERENCES
031-2S.2 SMK_TRP
SWTCHBRDS COMPART. SMOKE TRIP NOT PRESENT
013F.2 FLAME_ALM
EFFECT:
FLAME ALARM SWTCHBRDS COMP. NOT PRESENT
G1 COMPARTMENT AIR DAMPERS CLOSING (row 39)
122E.2 EXPG_ALM
CAUSES:
EXPL. GAS ALARM SWTCHBRDS COMP. NOT PRESENT
PLATFORM ABANDON - IMMEDIATE (column 1)
R33.2 INR_REL_EP
PLATFORM EMERGENCY TRIP REMOTE COMMAND - IMMEDIATE (column 2)
INERGEN RELEASE SWTCHBRDS COMPART. NOT OCCURR. EXPLOSIVE GAS ALARM G1 COMPARTMENT - IMMEDIATE (column 41)
011-2S.2 SMK_TRP EXPLOSIVE GAS ALARM SWITCHBOARDS COMPART. - IMMEDIATE (column 45)
STAU ROOM SMOKE TRIP NOT PRESENT EXPLOSIVE GAS ALARM STAU ROOM - IMMEDIATE (column 50)
011F.2 FLAME_ALM
SMOKE ALARM G1 COMPARTMENT - IMMEDIATE (column 70)
SMOKE ALARM SWITCHBOARDS COMPARTMENT - IMMEDIATE (column 76)
FLAME ALARM STAU ROOM NOT PRESENT
SMOKE ALARM STAU ROOM - IMMEDIATE (column 77)
102E.2 EXPG_ALM
FLAME ALARM G1 COMPARTMENT - IMMEDIATE (column 100)
EXPL. GAS ALARM STAU ROOM NOT PRES. FLAME ALARM SWITCHBOARDS COMPARTMENT - IMMEDIATE (column 106)
R13.2 INR_REL_ST FLAME ALARM STAU ROOM - IMMEDIATE (column 107)
INERGEN RELEASE STAU ROOM NOT OCCURR. INERGEN MANUAL RELEASE STAU ROOM - IMMEDIATE (column 117)
TRIPS_RES_PB
INERGEN MANUAL RELEASE G1 COMPART. - IMMEDIATE (column 118)
INERGEN MANUAL RELEASE SWITCHBOARDS COMPART. - IMMEDIATE (column 119)
TRIPS RESET PUSH BUTTON ACTIV.

NOTES:
IN CAUSES-EFFECTS DIAGRAM IT IS NOT PRESENT THE CAUSE:
ELECTRICAL TRIPS SELECTOR INCL./EXCL. - INCLUDED (column 5)
IN THIS APPLICATION PROGRAM IT IS PRESENT INSTEAD THE CAUSE:
ELECTRICAL TRIPS SELECTOR INCL./EXCL. - INCLUDED (column 5)

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/44
1 check Martha Cluster MARTHA PLATF PES page 45
revision date name status: LZ based replaced replaced TRIP LOGICS PROCESSING (PAGE 9 OF 34)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 45 OF 114 TRIP LOGICS PROCESSING (PAGE 10 OF 34) OUTPUTS


SWITCHBOARDS COMPARTMENT AIR DAMPERS CLOSING MANAGEMENT

RET2.3 ELETRP_INC S Q SOV3 EP_CL_DMP


&
ELECT. TRIPS SELECT. INCLUDED POSIT. 45003 R MEMS SWTCHBRDS COMPART. AIR DAMPERS CLOSING
TRUE PRE 45006 EP_CL_DMP_RES_AV
RB_A/B_REM_TRP &
45009 G1 COMPART. AIR DAMP. CLOSING RES. AVAIL.
PLATFORM EMERGENCY TRIP REMOTE COMMAND
EP_CL_DMP
RPA.2 PLT_ABD
SWTCHBRDS COMPART. AIR DAMPERS CLOSING CONDIT. PRES.
PLATF. ABAND. PUSH-BUTTONS NOT ACTIV.
&
011-2S.2 SMK_TRP
STAU ROOM SMOKE TRIP NOT PRESENT
011F.2 FLAME_ALM
FLAME ALARM STAU ROOM NOT PRESENT
102E.2 EXPG_ALM 45000
EXPL. GAS ALARM STAU ROOM NOT PRES.
R13.2 INR_REL_ST
INERGEN RELEASE STAU ROOM NOT OCCURR.

031-2S.2 SMK_TRP
SWTCHBRDS COMPART. SMOKE TRIP NOT PRESENT
013F.2 FLAME_ALM
FLAME ALARM SWTCHBRDS COMP. NOT PRESENT
122E.2 EXPG_ALM CAUSES-EFFECTS DIAGRAM REFERENCES
EXPL. GAS ALARM SWTCHBRDS COMP. NOT PRESENT
R33.2 INR_REL_EP EFFECT:
INERGEN RELEASE SWTCHBRDS COMPART. NOT OCCURR.
SWITCHBOARDS COMPARTMENT AIR DAMPERS CLOSING (row 43)

TRIPS_RES_PB CAUSES:
TRIPS RESET PUSH BUTTON ACTIV. PLATFORM ABANDON - IMMEDIATE (column 1)
PLATFORM EMERGENCY TRIP REMOTE COMMAND - IMMEDIATE (column 2)
EXPLOSIVE GAS ALARM SWITCHBOARDS COMPART. - IMMEDIATE (column 45)
EXPLOSIVE GAS ALARM STAU ROOM - IMMEDIATE (column 50)
SMOKE ALARM SWITCHBOARDS COMPARTMENT - IMMEDIATE (column 76)
SMOKE ALARM STAU ROOM - IMMEDIATE (column 77)
FLAME ALARM SWITCHBOARDS COMPARTMENT - IMMEDIATE (column 106)
FLAME ALARM STAU ROOM - IMMEDIATE (column 107)
INERGEN MANUAL RELEASE STAU ROOM - IMMEDIATE (column 117)
INERGEN MANUAL RELEASE SWITCHBOARDS COMPART. - IMMEDIATE (column 119)

NOTES:
IN CAUSES-EFFECTS DIAGRAM IT IS NOT PRESENT THE CAUSE:
ELECTRICAL TRIPS SELECTOR INCL./EXCL. - INCLUDED (column 5)
IN THIS APPLICATION PROGRAM IT IS PRESENT INSTEAD THE CAUSE:
ELECTRICAL TRIPS SELECTOR INCL./EXCL. - INCLUDED (column 5)

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/45
1 check Martha Cluster MARTHA PLATF PES page 46
revision date name status: LZ based replaced replaced TRIP LOGICS PROCESSING (PAGE 10 OF 34)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 46 OF 114 TRIP LOGICS PROCESSING (PAGE 11 OF 34) OUTPUTS


TRANSFORMER COMPARTMENT AIR DAMPERS CLOSING MANAGEMENT

RET2.3 ELETRP_INC S Q SOV4 TR_CL_DMP


&
ELECT. TRIPS SELECT. INCLUDED POSIT. 46003 R MEMS TRANSF. COMPART. AIR DAMPERS CLOSING
TRUE PRE 46006 TR_CL_DMP_RES_AV
RB_A/B_REM_TRP &
46009 TRANSF.COMPART. AIR DAMP.CLOS. RES.AVAIL.
PLATFORM EMERGENCY TRIP REMOTE COMMAND
TR_CL_DMP
RPA.2 PLT_ABD
TRANSF. COMPART. AIR DAMPERS CLOSING CONDIT. PRES.
PLATF. ABAND. PUSH-BUTTONS NOT ACTIV.

011-2S.2 SMK_TRP
STAU ROOM SMOKE TRIP NOT PRESENT
&
011F.2 FLAME_ALM
FLAME ALARM STAU ROOM NOT PRESENT
102E.2 EXPG_ALM
EXPL. GAS ALARM STAU ROOM NOT PRES. CAUSES-EFFECTS DIAGRAM REFERENCES
R13.2 INR_REL_ST
INERGEN RELEASE STAU ROOM NOT OCCURR. EFFECT:
041-2S.2 SMK_TRP
46000 TRANSFORMER COMPARTMENT AIR DAMPERS CLOSING (row 41)
EX MV CABIN AIR DAMPERS CLOSING
TRANSF. COMPART. SMOKE TRIP NOT PRESENT
014F.2 FLAME_ALM
CAUSES:
FLAME ALARM TRANSF. COMPART. NOT PRESENT PLATFORM ABANDON - IMMEDIATE (column 1)
132E.2 EXPG_ALM PLATFORM EMERGENCY TRIP REMOTE COMMAND - IMMEDIATE (column 2)
EXPL. GAS ALARM TRANSF. COMP. NOT PRESENT EXPLOSIVE GAS ALARM TRANSFORMER COMPART. - IMMEDIATE (column 43)
R43.2 INR_REL_TR EXPLOSIVE GAS ALARM SWITCHBOARDS COMPART. - IMMEDIATE (column 45)
INERGEN RELEASE TRANSF. COMPART. NOT OCCURR. EXPLOSIVE GAS ALARM STAU ROOM - IMMEDIATE (column 50)
SMOKE ALARM TRANSFORMER COMPARTMENT - IMMEDIATE (column 71)
031-2S.2 SMK_TRP
SMOKE ALARM SWITCHBOARDS COMPARTMENT - IMMEDIATE (column 76)
SWTCHBRDS COMPART. SMOKE TRIP NOT PRESENT
SMOKE ALARM STAU ROOM - IMMEDIATE (column 77)
013F.2 FLAME_ALM
FLAME ALARM TRANSFORMER COMPARTMENT - IMMEDIATE (column 101)
FLAME ALARM SWTCHBRDS COMP. NOT PRESENT FLAME ALARM SWITCHBOARDS COMPARTMENT - IMMEDIATE (column 106)
122E.2 EXPG_ALM FLAME ALARM STAU ROOM - IMMEDIATE (column 107)
EXPL. GAS ALARM SWTCHBRDS COMP. NOT PRESENT INERGEN MANUAL RELEASE STAU ROOM - IMMEDIATE (column 117)
R33.2 INR_REL_EP INERGEN MANUAL RELEASE SWITCHBOARDS COMPART. - IMMEDIATE (column 119)
INERGEN RELEASE SWTCHBRDS COMPART. NOT OCCURR. INERGEN MANUAL RELEASE TRANSFORMER COMPART. - IMMEDIATE (column 120)
TRIPS_RES_PB
NOTES:
TRIPS RESET PUSH BUTTON ACTIV.
TRANSFORMER COMPARTMENT AIR DAMPERS CLOSING REPLACE MV CABIN AIR
DAMPERS CLOSING OF CAUSES-EFFECTS DIAGRAM.
IN CAUSES-EFFECTS DIAGRAM IT IS NOT PRESENT THE CAUSE:
ELECTRICAL TRIPS SELECTOR INCL./EXCL. - INCLUDED (column 5)
IN THIS APPLICATION PROGRAM IT IS PRESENT INSTEAD THE CAUSE:
ELECTRICAL TRIPS SELECTOR INCL./EXCL. - INCLUDED (column 5)

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/46
1 check Martha Cluster MARTHA PLATF PES page 47
revision date name status: LZ based replaced replaced TRIP LOGICS PROCESSING (PAGE 11 OF 34)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 47 OF 114 TRIP LOGICS PROCESSING (PAGE 12 OF 34) OUTPUTS


MAIN ENTRANCE AIR DAMPERS CLOSING MANAGEMENT

RET2.3 ELETRP_INC S Q SOV5-6 GE_CL_DMP


&
ELECT. TRIPS SELECT. INCLUDED POSIT. 47003 R MEMS MAIN ENTRANCE AIR DAMPERS CLOSING
TRUE PRE 47006 GE_CL_DMP_RES_AV
RB_A/B_REM_TRP &
47009 MAIN ENTRANCE AIR DAMP. CLOSING RES. AVAIL.
PLATFORM EMERGENCY TRIP REMOTE COMMAND
GE_CL_DMP
RPA.2 PLT_ABD
MAIN ENTRANCE AIR DAMPERS CLOSING CONDIT. PRES.
PLATF. ABAND. PUSH-BUTTONS NOT ACTIV.
&
011-2S.2 SMK_TRP
STAU ROOM SMOKE TRIP NOT PRESENT
011F.2 FLAME_ALM
FLAME ALARM STAU ROOM NOT PRESENT
102E.2 EXPG_ALM 47000
EXPL. GAS ALARM STAU ROOM NOT PRES.
R13.2 INR_REL_ST
INERGEN RELEASE STAU ROOM NOT OCCURR.

031-2S.2 SMK_TRP
SWTCHBRDS COMPART. SMOKE TRIP NOT PRESENT CAUSES-EFFECTS DIAGRAM REFERENCES
013F.2 FLAME_ALM
FLAME ALARM SWTCHBRDS COMP. NOT PRESENT
EFFECT:
122E.2 EXPG_ALM
MAIN ENTRANCE AIR DAMPERS CLOSING (row 45)
EX GENERATORS DAMPERS CLOSING
EXPL. GAS ALARM SWTCHBRDS COMP. NOT PRESENT
R33.2 INR_REL_EP
CAUSES:
INERGEN RELEASE SWTCHBRDS COMPART. NOT OCCURR.
PLATFORM ABANDON - IMMEDIATE (column 1)
TRIPS_RES_PB PLATFORM EMERGENCY TRIP REMOTE COMMAND - IMMEDIATE (column 2)
TRIPS RESET PUSH BUTTON ACTIV. EXPLOSIVE GAS ALARM SWITCHBOARDS COMPART. - IMMEDIATE (column 45)
EXPLOSIVE GAS ALARM STAU ROOM - IMMEDIATE (column 50)
SMOKE ALARM SWITCHBOARDS COMPARTMENT - IMMEDIATE (column 76)
SMOKE ALARM STAU ROOM - IMMEDIATE (column 77)
FLAME ALARM SWITCHBOARDS COMPARTMENT - IMMEDIATE (column 106)
FLAME ALARM STAU ROOM - IMMEDIATE (column 107)
INERGEN MANUAL RELEASE STAU ROOM - IMMEDIATE (column 117)
INERGEN MANUAL RELEASE SWITCHBOARDS COMPART. - IMMEDIATE (column 119)

NOTES:
MAIN ENTRANCE AIR DAMPERS CLOSING REPLACE GENERATORS DAMPERS
CLOSING OF CAUSES-EFFECTS DIAGRAM.
IN CAUSES-EFFECTS DIAGRAM IT IS NOT PRESENT THE CAUSE:
ELECTRICAL TRIPS SELECTOR INCL./EXCL. - INCLUDED (column 5)
IN THIS APPLICATION PROGRAM IT IS PRESENT INSTEAD THE CAUSE:
ELECTRICAL TRIPS SELECTOR INCL./EXCL. - INCLUDED (column 5)

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/47
1 check Martha Cluster MARTHA PLATF PES page 48
revision date name status: LZ based replaced replaced TRIP LOGICS PROCESSING (PAGE 12 OF 34)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 48 OF 114 TRIP LOGICS PROCESSING (PAGE 13 OF 34) OUTPUTS


PLATFORM GENERAL TRIP MANAGEMENT

RET2.3 ELETRP_INC S Q SOV7 GEN_TRIP


&
ELECT. TRIPS SELECT. INCLUDED POSIT. 48003 R MEMS PLATFORM GENERAL TRIP COMMAND
TRUE PRE 48006 GEN_TRIP_RES_AV
RB_A/B_REM_TRP &
48009 PLATFORM GENERAL TRIP RESET AVAILABLE
PLATFORM EMERGENCY TRIP REMOTE COMMAND
GEN_TRIP
RPA.2 PLT_ABD
& PLATFORM GENERAL TRIP CONDITION PRESENT
PLATF. ABAND. PUSH-BUTTONS NOT ACTIV.

FUPLGNET
PROD. EMERG. TRIP FROM FUSIB. PLUGS NOT ACTIV. 48000

011-2S.2 SMK_TRP
STAU ROOM SMOKE TRIP NOT PRESENT
011F.2 FLAME_ALM
FLAME ALARM STAU ROOM NOT PRESENT
102E.2 EXPG_ALM
EXPL. GAS ALARM STAU ROOM NOT PRES.
R13.2 INR_REL_ST CAUSES-EFFECTS DIAGRAM REFERENCES
INERGEN RELEASE STAU ROOM NOT OCCURR.
EFFECT:
TRIPS_RES_PB PLATFORM GENERAL TRIP (row 70)
TRIPS RESET PUSH BUTTON ACTIV.
CAUSES:
PLATFORM ABANDON - IMMEDIATE (column 1)
PLATFORM EMERGENCY TRIP REMOTE COMMAND - IMMEDIATE (column 2)
PRODUCTION EMERGENCY TRIP - IMMEDIATE (column 3)
EXPLOSIVE GAS ALARM STAU ROOM - IMMEDIATE (column 50)
SMOKE ALARM STAU ROOM - IMMEDIATE (column 77)
FLAME ALARM STAU ROOM - IMMEDIATE (column 107)
INERGEN MANUAL RELEASE STAU ROOM - IMMEDIATE (column 117)

NOTES:
IN CAUSES-EFFECTS DIAGRAM ARE PRESENTS THE CAUSES:
PRODUCTION EMERGENCY TRIP (column 3)
WELLS HEADS AREA FUSIBLES PLUGS (column 109)
PROCESS MODULE FUSIBLES PLUGS (column 110)
IN THIS APPLICATION PROGRAM IT IS PRESENT INSTEAD THE CAUSE:
PRODUCTION EMERGENCY TRIP FROM FUSIBLES PLUGS NETWORK (column ___)

IN CAUSES-EFFECTS DIAGRAM IT IS NOT PRESENT THE CAUSE:


ELECTRICAL TRIPS SELECTOR INCL./EXCL. - INCLUDED (column 5)
IN THIS APPLICATION PROGRAM IT IS PRESENT INSTEAD THE CAUSE:
ELECTRICAL TRIPS SELECTOR INCL./EXCL. - INCLUDED (column 5)

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/48
1 check Martha Cluster MARTHA PLATF PES page 49
revision date name status: LZ based replaced replaced TRIP LOGICS PROCESSING (PAGE 13 OF 34)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 49 OF 114 TRIP LOGICS PROCESSING (PAGE 14 OF 34) OUTPUTS


PURGING AIR PANEL TRIP MANAGEMENT

RET2.3 ELETRP_INC S Q RS/5 PP_TRIP


&
ELECT. TRIPS SELECT. INCLUDED POSIT. 49003 R MEMS PURGE PANEL TRIP COMMAND
TRUE PRE 49006 PP_TRIP_RES_AV
RB_A/B_REM_TRP &
49009 PURGE PANEL TRIP RESET AVAILABLE
PLATFORM EMERGENCY TRIP REMOTE COMMAND
PP_TRIP
RPA.2 PLT_ABD
PURGE PANEL TRIP CONDITION PRESENT
PLATF. ABAND. PUSH-BUTTONS NOT ACTIV.
&
011-2S.2 SMK_TRP
STAU ROOM SMOKE TRIP NOT PRESENT
011F.2 FLAME_ALM
FLAME ALARM STAU ROOM NOT PRESENT
102E.2 EXPG_ALM 49000
EXPL. GAS ALARM STAU ROOM NOT PRES.
R13.2 INR_REL_ST
INERGEN RELEASE STAU ROOM NOT OCCURR.

031-2S.2 SMK_TRP
SWTCHBRDS COMPART. SMOKE TRIP NOT PRESENT
013F.2 FLAME_ALM
FLAME ALARM SWTCHBRDS COMP. NOT PRESENT
122E.2 EXPG_ALM CAUSES-EFFECTS DIAGRAM REFERENCES
EXPL. GAS ALARM SWTCHBRDS COMP. NOT PRESENT
R33.2 INR_REL_EP EFFECT:
INERGEN RELEASE SWTCHBRDS COMPART. NOT OCCURR.
PURGING AIR PANEL TRIP (row 44)

TRIPS_RES_PB CAUSES:
TRIPS RESET PUSH BUTTON ACTIV. PLATFORM ABANDON - IMMEDIATE (column 1)
PLATFORM EMERGENCY TRIP REMOTE COMMAND - IMMEDIATE (column 2)
EXPLOSIVE GAS ALARM SWITCHBOARDS COMPART. - IMMEDIATE (column 45)
EXPLOSIVE GAS ALARM STAU ROOM - IMMEDIATE (column 50)
SMOKE ALARM SWITCHBOARDS COMPARTMENT - IMMEDIATE (column 76)
SMOKE ALARM STAU ROOM - IMMEDIATE (column 77)
FLAME ALARM SWITCHBOARDS COMPARTMENT - IMMEDIATE (column 106)
FLAME ALARM STAU ROOM - IMMEDIATE (column 107)
INERGEN MANUAL RELEASE STAU ROOM - IMMEDIATE (column 117)
INERGEN MANUAL RELEASE SWITCHBOARDS COMPART. - IMMEDIATE (column 119)

NOTES:
IN CAUSES-EFFECTS DIAGRAM IT IS NOT PRESENT THE CAUSE:
ELECTRICAL TRIPS SELECTOR INCL./EXCL. - INCLUDED (column 5)
IN THIS APPLICATION PROGRAM IT IS PRESENT INSTEAD THE CAUSE:
ELECTRICAL TRIPS SELECTOR INCL./EXCL. - INCLUDED (column 5)

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/49
1 check Martha Cluster MARTHA PLATF PES page 50
revision date name status: LZ based replaced replaced TRIP LOGICS PROCESSING (PAGE 14 OF 34)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 50 OF 114 TRIP LOGICS PROCESSING (PAGE 15 OF 34) OUTPUTS


PRESSURIZATION GENERAL TRIP MANAGEMENT

RET2.3 ELETRP_INC S Q RS11 PRES_TRIP


&
ELECT. TRIPS SELECT. INCLUDED POSIT. 50003 R MEMS PRESSURIZ. GENERAL TRIP COMMAND
TRUE PRE 50006 PRES_TRIP_RES_AV
102E.2 EXPG_ALM &
50009 PRESSURIZ. GENERAL TRIP RESET AVAILABLE
EXPL. GAS ALARM STAU ROOM NOT PRES.
&
PRES_TRIP
112E.2 EXPG_ALM
50000 PRESSURIZ. GENERAL TRIP CONDITION PRESENT
EXPL. GAS ALARM G1 COMPART. NOT PRES.

122E.2 EXPG_ALM
EXPL. GAS ALARM SWTCHBRDS COMP. NOT PRESENT

132E.2 EXPG_ALM
EXPL. GAS ALARM TRANSF. COMP. NOT PRESENT

TRIPS_RES_PB
TRIPS RESET PUSH BUTTON ACTIV.

CAUSES-EFFECTS DIAGRAM REFERENCES

EFFECT:
PRESSURIZATION GENERAL TRIP (row __)

CAUSES:
EXPLOSIVE GAS ALARM G1 COMPARTMENT - IMMEDIATE (column 41)
EXPLOSIVE GAS ALARM TRANSFORMER COMPART. - IMMEDIATE (column 43)
EXPLOSIVE GAS ALARM SWITCHBOARDS COMPART. - IMMEDIATE (column 45)
EXPLOSIVE GAS ALARM STAU ROOM - IMMEDIATE (column 50)

NOTES:
THIS TRIP EFFECT IT IS NOT PRESENT IN CAUSES-EFFECTS DIAGRAM.

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/50
1 check Martha Cluster MARTHA PLATF PES page 51
revision date name status: LZ based replaced replaced TRIP LOGICS PROCESSING (PAGE 15 OF 34)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 51 OF 114 TRIP LOGICS PROCESSING (PAGE 16 OF 34) OUTPUTS


AVAILABLE EMPTY PAGE

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/51
1 check Martha Cluster MARTHA PLATF PES page 52
revision date name status: LZ based replaced replaced TRIP LOGICS PROCESSING (PAGE 16 OF 34)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 52 OF 114 TRIP LOGICS PROCESSING (PAGE 17 OF 34) OUTPUTS


STAU ROOM INERGEN RELEASE COMMAND MANAGEMENT (DELAYED)

WAIT_T_INR_ST
&
52006 INERGEN REL. STAU ROOM T. DEL. ACTIV.
RET2.3 ELETRP_INC S Q R10 INR_ST
&
ELECT. TRIPS SELECT. INCLUDED POSIT. 52009 R MEMS INERGEN RELEASE STAU ROOM COMMAND
TRUE PRE 52012 INR_ST_RES_AV
011-2S.2 INR_REL IN Q &
& TON 52015 INERGEN REL. STAU ROOM RESET AVAIL.
STAU ROOM INERGEN RELEASE NOT PRESENT 52000 PT 52003
ET
INR_ST
011F.2 FLAME_ALM
INERGEN RELEASE STAU ROOM CONDITION PRESENT
FLAME ALARM STAU ROOM NOT PRESENT

TDEL_INR_REL_ST
STAU ROOM INERGEN RELEASE TIME DELAY

TRIPS_RES_PB
TRIPS RESET PUSH BUTTON ACTIV.

CAUSES-EFFECTS DIAGRAM REFERENCES

EFFECT:
STAU ROOM INERGEN RELEASE COMMAND (row 56)
EX STAU ROOM HALON RELEASE COMMAND

CAUSES:
ELECTRICAL TRIPS SELECTOR INCL./EXCL. - INCLUDED (column 5)
SMOKE ALARM STAU ROOM - DELAYED (column 77)
FLAME ALARM STAU ROOM - DELAYED (column 107)

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/52
1 check Martha Cluster MARTHA PLATF PES page 53
revision date name status: LZ based replaced replaced TRIP LOGICS PROCESSING (PAGE 17 OF 34)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 53 OF 114 TRIP LOGICS PROCESSING (PAGE 18 OF 34) OUTPUTS


G1 COMPARTMENT INERGEN RELEASE COMMAND MANAGEMENT (DELAYED)

WAIT_T_INR_G1
&
53006 INERGEN REL. G1 COMPART. T. DEL. ACTIV.
RET2.3 ELETRP_INC S Q R20 INR_G1
&
ELECT. TRIPS SELECT. INCLUDED POSIT. 53009 R MEMS INERGEN RELEASE G1 COMPART. COMMAND
TRUE PRE 53012 INR_G1_RES_AV
021-2S.2 INR_REL IN Q &
& TON 53015 INERGEN REL. G1 COMPART. RESET AVAIL.
G1 COMPART. INERGEN REL. NOT PRESENT 53000 PT 53003
ET
INR_G1
012F.2 FLAME_ALM
INERGEN RELEASE G1 COMPART. CONDITION PRESENT
FLAME ALARM G1 COMPART. NOT PRESENT

TDEL_INR_REL_G1
G1 COMPART. INERGEN RELEASE TIME DELAY

TRIPS_RES_PB
TRIPS RESET PUSH BUTTON ACTIV.

CAUSES-EFFECTS DIAGRAM REFERENCES

EFFECT:
G1 COMPARTMENT INERGEN RELEASE COMMAND (row 49)
EX G1 COMPARTMENT HALON RELEASE COMMAND

CAUSES:
ELECTRICAL TRIPS SELECTOR INCL./EXCL. - INCLUDED (column 5)
SMOKE ALARM G1 COMPARTMENT - DELAYED (column 70)
FLAME ALARM G1 COMPARTMENT - DELAYED (column 100)

NOTES:
IN CAUSES-EFFECTS DIAGRAM IT IS NOT PRESENT THE CAUSE:
SMOKE ALARM G1 COMPARTMENT - DELAYED (column 70)
IN THIS APPLICATION PROGRAM IT IS PRESENT INSTEAD THE CAUSE:
SMOKE ALARM G1 COMPARTMENT - DELAYED (column 70)

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/53
1 check Martha Cluster MARTHA PLATF PES page 54
revision date name status: LZ based replaced replaced TRIP LOGICS PROCESSING (PAGE 18 OF 34)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 54 OF 114 TRIP LOGICS PROCESSING (PAGE 19 OF 34) OUTPUTS


SWITCHBOARDS COMPARTMENT INERGEN RELEASE COMMAND MANAGEMENT (DELAYED)

WAIT_T_INR_EP
&
54006 INERGEN REL. SWTCHBRDS COMP. T. DEL. ACT.
RET2.3 ELETRP_INC S Q R30 INR_EP
&
ELECT. TRIPS SELECT. INCLUDED POSIT. 54009 R MEMS INERGEN REL. SWTCHBRDS COMP. COMMAND
TRUE PRE 54012 INR_EP_RES_AV
031-2S.2 INR_REL IN Q &
& TON 54015 INERGEN REL. SWTCHBRDS COMP. RES. AVAIL.
SWTCHBRDS COMPART. INERGEN REL. NOT PRES. 54000 PT 54003
ET
INR_EP
013F.2 FLAME_ALM
INERGEN REL. SWTCHBRDS COMPART. CONDIT. PRES.
FLAME ALARM SWTCHBRDS COMP. NOT PRESENT

TDEL_INR_REL_EP
SWTCHBRDS COMPART. INERGEN RELEASE TIME DELAY

TRIPS_RES_PB
TRIPS RESET PUSH BUTTON ACTIV.

CAUSES-EFFECTS DIAGRAM REFERENCES

EFFECT:
SWITCHBOARDS COMPARTMENT INERGEN RELEASE COMMAND (row 55)
EX SWITCHBOARDS COMPARTMENT HALON RELEASE COMMAND

CAUSES:
ELECTRICAL TRIPS SELECTOR INCL./EXCL. - INCLUDED (column 5)
SMOKE ALARM SWITCHBOARDS COMPARTMENT - DELAYED (column 76)
FLAME ALARM SWITCHBOARDS COMPARTMENT - DELAYED (column 106)

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/54
1 check Martha Cluster MARTHA PLATF PES page 55
revision date name status: LZ based replaced replaced TRIP LOGICS PROCESSING (PAGE 19 OF 34)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 55 OF 114 TRIP LOGICS PROCESSING (PAGE 20 OF 34) OUTPUTS


TRANSFORMER COMPARTMENT INERGEN RELEASE COMMAND MANAGEMENT (DELAYED)

WAIT_T_INR_TR
&
55006 INERGEN REL. TRANSF. COMP. T. DEL. ACT.
RET2.3 ELETRP_INC S Q R40 INR_TR
&
ELECT. TRIPS SELECT. INCLUDED POSIT. 55009 R MEMS INERGEN REL. TRANSF. COMPART. COMMAND
TRUE PRE 55012 INR_TR_RES_AV
041-2S.2 INR_REL IN Q &
& TON 55015 INERGEN REL. TRANSF. COMP. RESET AVAIL.
TRANSF. COMPART. INERGEN REL. NOT PRES. 55000 PT 55003
ET
INR_TR
014F.2 FLAME_ALM
INERGEN REL. TRANSF. COMPART. CONDIT. PRES.
FLAME ALARM TRANSF. COMPART. NOT PRESENT

TDEL_INR_REL_TR
TRANSF. COMPART. INERGEN RELEASE TIME DELAY

TRIPS_RES_PB
TRIPS RESET PUSH BUTTON ACTIV.

CAUSES-EFFECTS DIAGRAM REFERENCES

EFFECT:
TRANSFORMER COMPARTMENT INERGEN RELEASE COMMAND (row 50)
EX TRANSFORMER COMPARTMENT HALON RELEASE COMMAND

CAUSES:
ELECTRICAL TRIPS SELECTOR INCL./EXCL. - INCLUDED (column 5)
SMOKE ALARM TRANSFORMER COMPARTMENT - DELAYED (column 71)
FLAME ALARM TRANSFORMER COMPARTMENT - DELAYED (column 101)

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/55
1 check Martha Cluster MARTHA PLATF PES page 56
revision date name status: LZ based replaced replaced TRIP LOGICS PROCESSING (PAGE 20 OF 34)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 56 OF 114 TRIP LOGICS PROCESSING (PAGE 21 OF 34) OUTPUTS


AT LEAST ONE TRIP PRESENT SIGNALING

ST_TRIP RS10 ACT_TRIP


STAU ROOM TRIP CONDITION PRESENT AT LEAST ONE TRIP PRESENT SIGNALING

G1_TRIP
G1 COMPART. TRIP CONDITION PRESENT

EP_TRIP
SWTCHBRDS COMPART. TRIP CONDITION PRESENT

TR_TRIP >=1
TRANSF. COMPART. TRIP CONDITION PRESENT

ST_CL_DMP
STAU ROOM AIR DAMPERS CLOSING CONDIT. PRES.

G1_CL_DMP
G1 COMPART. AIR DAMPERS CLOSING CONDIT. PRES.

EP_CL_DMP 56000
SWTCHBRDS COMPART. AIR DAMPERS CLOSING CONDIT. PRES.

TR_CL_DMP
TRANSF. COMPART. AIR DAMPERS CLOSING CONDIT. PRES.

GE_CL_DMP
MAIN ENTRANCE AIR DAMPERS CLOSING CONDIT. PRES.

GEN_TRIP
PLATFORM GENERAL TRIP CONDITION PRESENT

PP_TRIP
PURGE PANEL TRIP CONDITION PRESENT

PRES_TRIP
PRESSURIZ. GENERAL TRIP CONDITION PRESENT

INR_ST
INERGEN RELEASE STAU ROOM CONDITION PRESENT

INR_G1
INERGEN RELEASE G1 COMPART. CONDITION PRESENT

INR_EP
INERGEN REL. SWTCHBRDS COMPART. CONDIT. PRES.

INR_TR
INERGEN REL. TRANSF. COMPART. CONDIT. PRES.

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/56
1 check Martha Cluster MARTHA PLATF PES page 57
revision date name status: LZ based replaced replaced TRIP LOGICS PROCESSING (PAGE 21 OF 34)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 57 OF 114 TRIP LOGICS PROCESSING (PAGE 22 OF 34) OUTPUTS


PURGING AIR PANEL PERMISSIVE MANAGEMENT

RP1.2 PSL_ST RS12 PRG_PRM


STAU ROOM PRESSURIZATION PRESENT PURGE PANEL PERMISSIVE
&
RP2.2 PSL_G1
57000
G1 COMPARTMENT PRESSURIZATION PRESENT

RP3.2 PSL_EP
SWITCHBOARDS COMPART. PRESSURIZ. PRESENT

RP4.2 PSL_TR
TRASFORMER COMPART. PRESSURIZ. PRESENT

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/57
1 check Martha Cluster MARTHA PLATF PES page 58
revision date name status: LZ based replaced replaced TRIP LOGICS PROCESSING (PAGE 22 OF 34)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 58 OF 114 TRIP LOGICS PROCESSING (PAGE 23 OF 34) OUTPUTS


AVAILABLE EMPTY PAGE

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/58
1 check Martha Cluster MARTHA PLATF PES page 59
revision date name status: LZ based replaced replaced TRIP LOGICS PROCESSING (PAGE 23 OF 34)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 59 OF 114 TRIP LOGICS PROCESSING (PAGE 24 OF 34) OUTPUTS


TONE #1 ACTIVATION MANAGEMENT

RPA.2 PLT_ABD CLK FTRIG 59006


Q S Q RT1 TONE1
>=1
PLATF. ABAND. PUSH-BUTTONS NOT ACTIV. 59000 R MEMS TONE #1 ACTIVATION
FALSE PRE 59009 TONE #1 ACTIVATION FOR
RPS1.2 UNM_MAN PLATFORM ABANDON PUSH-BUTTONS OPERATION
>=1
UNMANNED POSIT. SELECT. SIGNALIZ. 59003
TONE1_RES_AV
TONES_SILENCER &
59012 TONE#1 RESET AVAILABLE
TONES CTRL UNIT SILENCER PUSH-BUTTON ACTIV.

CAUSES-EFFECTS DIAGRAM REFERENCES

EFFECTS:
TONE #1 SOUNDER ACTIVATION SWITCHGEARS COMPARTMENT (row 4)
TONE #1 SOUNDER ACTIVATION STAU ROOM (row 9)
TONE #1 SOUNDER ACTIVATION PROCESS MODULE (row 12)
TONE #1 SOUNDER ACTIVATION CELLAR DECK (row 13)
TONE #1 SOUNDER ACTIVATION G1 COMPARTMENT (row 16)

CAUSES:
PLATFORM ABANDON COMMAND (column 1)

NOTES:
TONE #1 = CONTINUOUS RED OPTICAL SIGNALING AND, WITH MANNED
PLATFORM, ALSO 450HZ FREQUENCY CONTINUOUS SOUND (HORN)

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/59
1 check Martha Cluster MARTHA PLATF PES page 60
revision date name status: LZ based replaced replaced TRIP LOGICS PROCESSING (PAGE 24 OF 34)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 60 OF 114 TRIP LOGICS PROCESSING (PAGE 25 OF 34) OUTPUTS


TONE #2 ACTIVATION MANAGEMENT

RMOB.2 MOB_PB CLK FTRIG 60006


Q S Q RT2 TONE2
>=1
MAN OVERBOARD PUSH-BUTTONS NOT ACTIVATED 60000 R MEMS TONE #2 ACTIVATION
FALSE PRE 60009 TONE #2 ACTIVATION FOR
RPS1.2 UNM_MAN MAN OVERBOARD PUSH-BUTTONS OPERATION
>=1
UNMANNED POSIT. SELECT. SIGNALIZ. 60003
TONE2_RES_AV
TONES_SILENCER &
60012 TONE#2 RESET AVAILABLE
TONES CTRL UNIT SILENCER PUSH-BUTTON ACTIV.

CAUSES-EFFECTS DIAGRAM REFERENCES

EFFECTS:
TONE #2 SOUNDER ACTIVATION SWITCHGEARS COMPARTMENT (row 4)
TONE #2 SOUNDER ACTIVATION STAU ROOM (row 9)
TONE #2 SOUNDER ACTIVATION PROCESS MODULE (row 12)
TONE #2 SOUNDER ACTIVATION CELLAR DECK (row 13)
TONE #2 SOUNDER ACTIVATION G1 COMPARTMENT (row 16)

CAUSES:
MAN OVERBOARD COMMAND (column 4)

NOTES:
TONE #2 = CONTINUOUS GREEN OPTICAL SIGNALING AND, WITH
MANNED PLATFORM, ALSO 1200-600HZ FREQUENCY, BITON
DESCENDANT FROM HIGH TO LOW SOUND, REPEATED EVERY 1.5SEC.
CYCLE (YEOW)

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/60
1 check Martha Cluster MARTHA PLATF PES page 61
revision date name status: LZ based replaced replaced TRIP LOGICS PROCESSING (PAGE 25 OF 34)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 61 OF 114 TRIP LOGICS PROCESSING (PAGE 26 OF 34) OUTPUTS


TONE #3 GAS PRESENCE ACTIVATION MANAGEMENT (PAGE 1 OF 4)

011E.2 EXPG_PALM CLK FTRIG 61048


Q RT3_TONE3_1-16/29
>=1
EXPL. GAS PREALARM ZONE #1 WELL HEADS NOT PRES. 61000 TONE #3 ACTIV. CAUSES FROM 1 TO 16

012E.2 EXPG_ALM CLK FTRIG 61051


Q
>=1
EXPL. GAS ALARM ZONE #1 WELL HEADS NOT PRES. 61003

021E.2 EXPG_PALM CLK FTRIG 61054


Q
>=1
EXPL. GAS PREALARM ZONE #2 WELL HEADS NOT PRES. 61006

022E.2 EXPG_ALM CLK FTRIG 61057


Q >=1
>=1
EXPL. GAS ALARM ZONE #2 WELL HEADS NOT PRES. 61009

031E.2 EXPG_PALM CLK FTRIG 61060


Q
>=1
EXPL. GAS PREALARM ZONE #3 WELL HEADS NOT PRES. 61012

032E.2 EXPG_ALM CLK FTRIG 61063


Q
>=1
EXPL. GAS ALARM ZONE #3 WELL HEADS NOT PRES. 61015

041E.2 EXPG_PALM CLK FTRIG 61066


Q 61096
>=1
EXPL. GAS PREALARM ZONE #4 WELL HEADS NOT PRES. 61018

042E.2 EXPG_ALM CLK FTRIG 61069


Q
>=1
EXPL. GAS ALARM ZONE #4 WELL HEADS NOT PRES. 61021

051E.2 EXPG_PALM CLK FTRIG 61072


Q
>=1
EXPL. GAS PREALARM ZONE #5 PROC. MOD. NOT PRES. 61024

052E.2 EXPG_ALM CLK FTRIG 61075


Q
>=1
EXPL. GAS ALARM ZONE #5 PROC. MOD. NOT PRES. 61027

061E.2 EXPG_PALM CLK FTRIG 61078


Q
>=1
EXPL. GAS PREALARM ZONE #6 PROC. MOD. NOT PRES. 61030

062E.2 EXPG_ALM CLK FTRIG 61081


Q
>=1
EXPL. GAS ALARM ZONE #6 PROC. MOD. NOT PRES. 61033

071E.2 EXPG_PALM CLK FTRIG 61084


Q
>=1
EXPL. GAS PREALARM ZONE #7 PROC. MOD. NOT PRES. 61036

072E.2 EXPG_ALM CLK FTRIG 61087


Q
>=1
EXPL. GAS ALARM ZONE #7 PROC. MOD. NOT PRES. 61039

081E.2 EXPG_PALM CLK FTRIG 61090


Q
>=1
EXPL. GAS PREALARM ZONE #8 PROC. MOD. NOT PRES. 61042

082E.2 EXPG_ALM CLK FTRIG 61093


Q
>=1
EXPL. GAS ALARM ZONE #8 PROC. MOD. NOT PRES. 61045

RPS1.2 UNM_MAN
UNMANNED POSIT. SELECT. SIGNALIZ.

3 date name logic version rev


2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/61
1 check Martha Cluster MARTHA PLATF PES page 62
revision date name status: LZ based replaced replaced TRIP LOGICS PROCESSING (PAGE 26 OF 34)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 62 OF 114 TRIP LOGICS PROCESSING (PAGE 27 OF 34) OUTPUTS


TONE #3 GAS PRESENCE ACTIVATION MANAGEMENT (PAGE 2 OF 4)

091E.2 EXPG_PALM CLK FTRIG 62039


Q RT3_TONE3_17-29/29
>=1
EXPL. GAS PREALARM ZONE #9 PROC. MOD. NOT PRES. 62000 TONE #3 ACTIV. CAUSES FROM 17 TO 29

092E.2 EXPG_ALM CLK FTRIG 62042


Q
>=1
EXPL. GAS ALARM ZONE #9 PROC. MOD. NOT PRES. 62003

101E.2 EXPG_PALM CLK FTRIG 62045


Q
>=1
EXPL. GAS PREALARM STAU ROOM NOT PRES. 62006 >=1

102E.2 EXPG_ALM CLK FTRIG 62048


Q
>=1
EXPL. GAS ALARM STAU ROOM NOT PRES. 62009

111E.2 EXPG_PALM CLK FTRIG 62051


Q
>=1
EXPL. GAS PREALARM G1 COMPART. NOT PRES. 62012
62078
112E.2 EXPG_ALM CLK FTRIG 62054
Q
>=1
EXPL. GAS ALARM G1 COMPART. NOT PRES. 62015

121E.2 EXPG_PALM CLK FTRIG 62057


Q
>=1
EXPL. GAS PREALARM SWTCHBRDS COMP. NOT PRESENT 62018

122E.2 EXPG_ALM CLK FTRIG 62060


Q
>=1
EXPL. GAS ALARM SWTCHBRDS COMP. NOT PRESENT 62021

131E.2 EXPG_PALM CLK FTRIG 62063


Q
>=1
EXPL. GAS PREALARM TRANSF. COMP. NOT PRESENT 62024

132E.2 EXPG_ALM CLK FTRIG 62066


Q
>=1
EXPL. GAS ALARM TRANSF. COMP. NOT PRESENT 62027

141E.2 EXPG_PALM CLK FTRIG 62069


Q
>=1
EXPL. GAS PREALARM PRESS. ASPIR. NOT PRESENT 62030

142E.2 EXPG_ALM CLK FTRIG 62072


Q
>=1
EXPL. GAS ALARM PRESS. ASPIR. NOT PRESENT 62033

003E.2 EXPG_FAIL CLK FTRIG 62075


Q
>=1
EXPL. GAS DETECT. SYST. FAIL. NOT PRESENT 62036

RPS1.2 UNM_MAN
UNMANNED POSIT. SELECT. SIGNALIZ.

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/62
1 check Martha Cluster MARTHA PLATF PES page 63
revision date name status: LZ based replaced replaced TRIP LOGICS PROCESSING (PAGE 27 OF 34)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 63 OF 114 TRIP LOGICS PROCESSING (PAGE 28 OF 34) OUTPUTS


TONE #3 GAS PRESENCE ACTIVATION MANAGEMENT (PAGE 3 OF 4)

011E.2 EXPG_PALM EXPG_PALM_ALM_FAIL


012E.2 EXPG_ALM EXPL. GAS PREALARM-ALARM-DET.SYS.FAIL.
021E.2 EXPG_PALM NOT PRESENTS
022E.2 EXPG_ALM
031E.2 EXPG_PALM
032E.2 EXPG_ALM
041E.2 EXPG_PALM
042E.2 EXPG_ALM
&
051E.2 EXPG_PALM
052E.2 EXPG_ALM
061E.2 EXPG_PALM
062E.2 EXPG_ALM
071E.2 EXPG_PALM
072E.2 EXPG_ALM
081E.2 EXPG_PALM
63001

082E.2 EXPG_ALM
091E.2 EXPG_PALM
092E.2 EXPG_ALM
101E.2 EXPG_PALM
102E.2 EXPG_ALM
111E.2 EXPG_PALM
112E.2 EXPG_ALM
&
121E.2 EXPG_PALM
122E.2 EXPG_ALM
131E.2 EXPG_PALM
132E.2 EXPG_ALM
141E.2 EXPG_PALM
142E.2 EXPG_ALM
003E.2 EXPG_FAIL 63000

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/63
1 check Martha Cluster MARTHA PLATF PES page 64
revision date name status: LZ based replaced replaced TRIP LOGICS PROCESSING (PAGE 28 OF 34)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 64 OF 114 TRIP LOGICS PROCESSING (PAGE 29 OF 34) OUTPUTS


TONE #3 GAS PRESENCE ACTIVATION MANAGEMENT (PAGE 4 OF 4)

RT3_TONE3_1-16/29 S Q RT3 TONE3


>=1
TONE #3 ACTIV. CAUSES FROM 1 TO 16 64000 R MEMS TONE #3 ACTIVATION
FALSE PRE 64006 TONE #3 ACTIVATION FOR
RT3_TONE3_17-29/29 EXPLOSIVE GAS PREALARM OR ALARM PRESENT
TONE #3 ACTIV. CAUSES FROM 17 TO 29 EXPLOSIVE GAS DETECTION SYSTEM FAULT

RPS1.2 UNM_MAN
>=1 TONE3_RES_AV
UNMANNED POSIT. SELECT. SIGNALIZ. 64003 &
64009 TONE#3 RESET AVAILABLE
TONES_SILENCER
TONES CTRL UNIT SILENCER PUSH-BUTTON ACTIV.

EXPG_PALM_ALM_FAIL
EXPL. GAS PREALARM-ALARM-DET.SYS.FAIL.
NOT PRESENTS

CAUSES-EFFECTS DIAGRAM REFERENCES

EFFECTS:
TONE #3 SOUNDER ACTIVATION SWITCHGEARS COMPARTMENT (row 4)
TONE #3 SOUNDER ACTIVATION STAU ROOM (row 9)
TONE #3 SOUNDER ACTIVATION PROCESS MODULE (row 12)
TONE #3 SOUNDER ACTIVATION CELLAR DECK (row 13)
TONE #3 SOUNDER ACTIVATION G1 COMPARTMENT (row 16)

CAUSES:
EXPLOSIVE GAS PREALARM PRESENT
EXPLOSIVE GAS ALARM PRESENT
EXPLOSIVE GAS DETECTION SYSTEM FAULT

NOTES:
TONE #3 = FLASHING RED OPTICAL SIGNALING AND, WITH MANNED
PLATFORM, ALSO 600-1250HZ FREQUENCY, BITON FAST SOUND,
REPEATED EVERY 0.25SEC. CYCLE (YELP)

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/64
1 check Martha Cluster MARTHA PLATF PES page 65
revision date name status: LZ based replaced replaced TRIP LOGICS PROCESSING (PAGE 29 OF 34)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 65 OF 114 TRIP LOGICS PROCESSING (PAGE 30 OF 34) OUTPUTS


TONE #4 SMOKE AND/OR FLAME PRESENCE ACTIVATION MANAGEMENT (PAGE 1 OF 4)

012F.2 FLAME_PALM CLK FTRIG 65048


Q RT4_TONE4_1-16/25
>=1
FLAME PREALARM STAU ROOM NOT PRESENT 65000 TONE #4 ACTIV. CAUSES FROM 1 TO 16

011F.2 FLAME_ALM CLK FTRIG 65051


Q
>=1
FLAME ALARM STAU ROOM NOT PRESENT 65003

022F.2 FLAME_PALM CLK FTRIG 65054


Q
>=1
FLAME PREALARM G1 COMPART. NOT PRESENT 65006

012F.2 FLAME_ALM CLK FTRIG 65057


Q >=1
>=1
FLAME ALARM G1 COMPART. NOT PRESENT 65009

032F.2 FLAME_PALM CLK FTRIG 65060


Q
>=1
FLAME PREALARM SWTCHBRDS COMP. NOT PRESENT 65012

013F.2 FLAME_ALM CLK FTRIG 65063


Q
>=1
FLAME ALARM SWTCHBRDS COMP. NOT PRESENT 65015

042F.2 FLAME_PALM CLK FTRIG 65066


Q 65096
>=1
FLAME PREALARM TRANSF. COMPART. NOT PRESENT 65018

014F.2 FLAME_ALM CLK FTRIG 65069


Q
>=1
FLAME ALARM TRANSF. COMPART. NOT PRESENT 65021

003F.2 FLAME_FAIL CLK FTRIG 65072


Q
>=1
FLAME DETECT. SYST. FAIL. NOT PRESENT 65024

012S.2 SMOKE_FAIL CLK FTRIG 65075


Q
>=1
SMOKE FAIL. STAU ROOM NOT PRESENT 65027

011S.2 SMOKE_ALM CLK FTRIG 65078


Q
>=1
SMOKE ALARM STAU ROOM NOT PRESENT 65030

022S.2 SMOKE_FAIL CLK FTRIG 65081


Q
>=1
SMOKE FAIL. G1 COMPART. NOT PRESENT 65033

021S.2 SMOKE_ALM CLK FTRIG 65084


Q
>=1
SMOKE ALARM G1 COMPART. NOT PRESENT 65036

032S.2 SMOKE_FAIL CLK FTRIG 65087


Q
>=1
SMOKE FAIL. SWTCHBRDS COMP. NOT PRESENT 65039

031S.2 SMOKE_ALM CLK FTRIG 65090


Q
>=1
SMOKE ALARM SWTCHBRDS COMP. NOT PRESENT 65042

042S.2 SMOKE_FAIL CLK FTRIG 65093


Q
>=1
SMOKE FAIL. TRANSF. COMPART. NOT PRESENT 65045

RPS1.2 UNM_MAN
UNMANNED POSIT. SELECT. SIGNALIZ.

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/65
1 check Martha Cluster MARTHA PLATF PES page 66
revision date name status: LZ based replaced replaced TRIP LOGICS PROCESSING (PAGE 30 OF 34)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 66 OF 114 TRIP LOGICS PROCESSING (PAGE 31 OF 34) OUTPUTS


TONE #4 SMOKE AND/OR FLAME PRESENCE ACTIVATION MANAGEMENT (PAGE 2 OF 4)

041S.2 SMOKE_ALM CLK FTRIG 66027


Q RT4_TONE4_17-25/25
>=1
SMOKE ALARM TRANSF. COMPART. NOT PRESENT 66000 TONE #4 ACTIV. CAUSES FROM 17 TO 25

052S.1 SMOKE_FAIL CLK FTRIG 66030


Q
>=1
SMOKE FAIL. COMMON LINE NOT PRESENT 66003
>=1
051S.1 SMOKE_ALM CLK FTRIG 66033
Q
>=1
SMOKE ALARM COMMON LINE NOT PRESENT 66006

003S.2 SMOKE_FAIL CLK FTRIG 66036


Q
>=1 66054
SMOKE DETECT. SYST. FAIL. NOT PRESENT 66009

R13.2 INR_REL_ST CLK FTRIG 66039


Q
>=1
INERGEN RELEASE STAU ROOM NOT OCCURR. 66012

R23.2 INR_REL_G1 CLK FTRIG 66042


Q
>=1
INERGEN RELEASE G1 COMPART. NOT OCCURR. 66015

R33.2 INR_REL_EP CLK FTRIG 66045


Q
>=1
INERGEN RELEASE SWTCHBRDS COMPART. NOT OCCURR. 66018

R43.2 INR_REL_TR CLK FTRIG 66048


Q
>=1
INERGEN RELEASE TRANSF. COMPART. NOT OCCURR. 66021

FUPLGNET CLK FTRIG 66051


Q
>=1
PROD. EMERG. TRIP FROM FUSIB. PLUGS NOT ACTIV. 66024

RPS1.2 UNM_MAN
UNMANNED POSIT. SELECT. SIGNALIZ.

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/66
1 check Martha Cluster MARTHA PLATF PES page 67
revision date name status: LZ based replaced replaced TRIP LOGICS PROCESSING (PAGE 31 OF 34)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 67 OF 114 TRIP LOGICS PROCESSING (PAGE 32 OF 34) OUTPUTS


TONE #4 SMOKE AND/OR FLAME PRESENCE ACTIVATION MANAGEMENT (PAGE 3 OF 4)

012F.2 FLAME_PALM FLM-SMK_PALM_ALM_FAIL


011F.2 FLAME_ALM FLAME PREALARM-ALARM-DET.SYS.FAIL. NOT PRESENTS
022F.2 FLAME_PALM SMOKE ALARM-FAIL.-DET.SYS.FAIL. NOT PRESENTS
INERGEN RELEAE NOT OCCURRED
012F.2 FLAME_ALM PROD. EMERG. TRIP FROM FUSIB. PLUGS NOT ACTIV.
032F.2 FLAME_PALM
013F.2 FLAME_ALM
042F.2 FLAME_PALM
014F.2 FLAME_ALM
&
003F.2 FLAME_FAIL
012S.2 SMOKE_FAIL
011S.2 SMOKE_ALM
022S.2 SMOKE_FAIL
021S.2 SMOKE_ALM
032S.2 SMOKE_FAIL
031S.2 SMOKE_ALM
67001

042S.2 SMOKE_FAIL
041S.2 SMOKE_ALM
052S.1 SMOKE_FAIL
051S.1 SMOKE_ALM
003S.2 SMOKE_FAIL
&
R13.2 INR_REL_ST
R23.2 INR_REL_G1
R33.2 INR_REL_EP
R43.2 INR_REL_TR
FUPLGNET 67000

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/67
1 check Martha Cluster MARTHA PLATF PES page 68
revision date name status: LZ based replaced replaced TRIP LOGICS PROCESSING (PAGE 32 OF 34)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 68 OF 114 TRIP LOGICS PROCESSING (PAGE 33 OF 34) OUTPUTS


TONE #4 SMOKE AND/OR FLAME PRESENCE ACTIVATION MANAGEMENT (PAGE 4 OF 4)

RT4_TONE4_1-16/25 S Q RT4 TONE4


>=1
TONE #4 ACTIV. CAUSES FROM 1 TO 16 68000 R MEMS TONE #4 ACTIVATION
FALSE PRE 68006 TONE #4 ACTIVATION FOR
RT4_TONE4_17-25/25
FLAME PREALARM OR ALARM PRESENT
TONE #4 ACTIV. CAUSES FROM 17 TO 25 FLAME DETECTION SYSTEM FAULT
SMOKE FAILURE OR SMOKE ALARM PRESENT
RPS1.2 UNM_MAN INERGEN RELEASE OCCURRED
>=1
UNMANNED POSIT. SELECT. SIGNALIZ. 68003 PSD FROM FUSIBLE PLUGS ACTIVATED

TONES_SILENCER
TONE4_RES_AV
TONES CTRL UNIT SILENCER PUSH-BUTTON ACTIV. &
68009 TONE#4 RESET AVAILABLE
FLM-SMK_PALM_ALM_FAIL
FLAME PREALARM-ALARM-DET.SYS.FAIL. NOT PRESENTS
SMOKE ALARM-FAIL.-DET.SYS.FAIL. NOT PRESENTS
INERGEN RELEAE NOT OCCURRED
PROD. EMERG. TRIP FROM FUSIB. PLUGS NOT ACTIV.

CAUSES-EFFECTS DIAGRAM REFERENCES NOTES:


TONE #4 = FLASHING GREEN OPTICAL SIGNALING AND, WITH MANNED
EFFECTS: PLATFORM, ALSO 500-1200HZ FREQUENCY, BITON ASCENDANT FROM
TONE #4 SOUNDER ACTIVATION SWITCHGEARS COMPARTMENT (row 4) LOW TO HIGH SOUND, REPEATED EVERY 4.1SEC. CYCLE (SLOW-WHOOP)
TONE #4 SOUNDER ACTIVATION STAU ROOM (row 9)
TONE #4 SOUNDER ACTIVATION PROCESS MODULE (row 12) IN CAUSES-EFFECTS DIAGRAM ARE NOT PRESENTS THE CAUSES:
TONE #4 SOUNDER ACTIVATION CELLAR DECK (row 13) SMOKE FAILURE
TONE #4 SOUNDER ACTIVATION G1 COMPARTMENT (row 16) INERGEN RELEASE STAU ROOM
INERGEN RELEASE G1 COMPARTMENT
CAUSES: INERGEN RELEASE SWITCHBOARDS COMPARTMENT
FLAME PREALARM PRESENT INERGEN RELEASE TRANSFORMER COMPARTMENT
FLAME ALARM PRESENT PRODUCTION EMERGENCY TRIP FROM FUSIBLE PLUGS
FLAME DETECTION SYSTEM FAULT IN THIS APPLICATION PROGRAM ARE PRESENTS INSTEAD THE CAUSES:
SMOKE FAILURE SMOKE FAILURE
SMOKE ALARM PRESENT INERGEN RELEASE STAU ROOM
SMOKE DETECTION SYSTEM FAULT INERGEN RELEASE G1 COMPARTMENT
INERGEN RELEASE OCCURRED INERGEN RELEASE SWITCHBOARDS COMPARTMENT
PRODUCTION EMERGENCY TRIP FROM FUSIBLE PLUGS ACTIVATED INERGEN RELEASE TRANSFORMER COMPARTMENT
PRODUCTION EMERGENCY TRIP FROM FUSIBLE PLUGS

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/68
1 check Martha Cluster MARTHA PLATF PES page 69
revision date name status: LZ based replaced replaced TRIP LOGICS PROCESSING (PAGE 33 OF 34)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 69 OF 114 TRIP LOGICS PROCESSING (PAGE 34 OF 34) OUTPUTS


AVAILABLE EMPTY PAGE

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/69
1 check Martha Cluster MARTHA PLATF PES page 70
revision date name status: LZ based replaced replaced TRIP LOGICS PROCESSING (PAGE 34 OF 34)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 70 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL OUTPUTS ELABORATION (PAGE 1 OF 19) OUTPUTS
MODBUS FUNCTION CODE 03: READ HOLDING (OUTPUT) REGISTER (SINGLE OR MULTIPLE)

OUTPUTS_ENABLED
WRITING OUTPUTS VALUES ENABLED EN
MOVE
CUERROR 70000 IN01 OT MODB-EXP-WORD-500
CU MODULE ERROR EN IN02 MODBUS WORD REGISTER SENT: 500
MOVE
HWCLKDISTSUP 70003 IN03
HARDWARE CLOCK DISTURB. DURING START-UP EN IN04
MOVE
HWWDGERROR 70006 IN05
HARDWARE WATCHDOG ERROR EN IN06
MOVE
MEMERROR 70009 IN07
MEMORY ERROR EN IN08
MOVE 16BOOLtoWORD
PROGRCRASHERROR 70012 IN09
PROGRAM CRASH ERROR EN IN10
MOVE
TIMEOUTERROR 70015 IN11
TIMEOUT ERROR EN IN12
MOVE
HWCLKDEVH 70018 IN13
DEVIATION HARDWARE CLOCK NOT TOLERABLE EN IN14
MOVE
HWCLKDISTOP 70021 IN15
HARDWARE CLOCK DISTURB. DURING OPERATION EN IN16 70048
MOVE
I/OCONNERROR 70024
Software Digital Outputs via ModBus serial link
CONNECTION TO I/O LEVEL ERROR EN
Managed as a block of 16 values (=1 word, =1 ModBus register)
MOVE
PSMONERROR 70027 Input IN01 correspond to bit 0 of the ModBus register
POWER SUPPLY MONITORING ERROR EN Input IN16 correspond to bit 15 of the ModBus register
MOVE Holding Register: 500
ADDRTSTI/OERROR 70030
ADDRESS TEST I/O SUBRACK ERROR EN
MOVE
TDELCUERROR 70033
TIME DELAY OTHER CU ERROR EN
MOVE
OUTNOZSUP 70036
OUTPUTS NOT SET TO 0 DURING START-UP EN
MOVE
HWCLKDEVT 70039
DEVIATION HARDWARE CLOCK TOLERABLE EN
MOVE
SYSFLTMSK1_BIT15 70042
SYSTEM FAULTS MASK #1 - BIT15 not used EN
MOVE
MEMDIFFERROR 70045
MEMORY NOT IDENTICAL ERROR

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/70
1 check Martha Cluster MARTHA PLATF PES page 71
revision date name status: LZ based replaced replaced SOFTWARE DIG. OUT. ELAB. (PAGE 1 OF 19)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 71 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL OUTPUTS ELABORATION (PAGE 2 OF 19) OUTPUTS
MODBUS FUNCTION CODE 03: READ HOLDING (OUTPUT) REGISTER (SINGLE OR MULTIPLE)

OUTPUTS_ENABLED
WRITING OUTPUTS VALUES ENABLED EN
MOVE
VMON3.3VCU1ERROR 71000 IN01 OT MODB-EXP-WORD-501
VOLTAGE MONITORING 3.3V CU1 ERROR EN IN02 MODBUS WORD REGISTER SENT: 501
MOVE
VMON3.3VCU2ERROR 71003 IN03
VOLTAGE MONITORING 3.3V CU2 ERROR EN IN04
MOVE
PS1ERROR 71006 IN05
POWER SUPPLY PS1 ERROR EN IN06
MOVE
PS2ERROR 71009 IN07
POWER SUPPLY PS2 ERROR EN IN08
MOVE
71012
16BOOLtoWORD
PS3ERROR IN09
POWER SUPPLY PS3 ERROR EN IN10
MOVE
NOISEBLANKACT 71015 IN11
NOISE BLANKING IS ACTIVE EN IN12
MOVE
CU1ERROR 71018 IN13
ERROR IN CENTRAL MODULE 1 EN IN14
MOVE
CU2ERROR 71021 IN15
ERROR IN CENTRAL MODULE 2 EN IN16 71048
MOVE
COPR1CU1ERROR 71024
Software Digital Outputs via ModBus serial link
COPROCESSOR MODULE 1 NEXT TO CU 1 EN Managed as a block of 16 values (=1 word, =1 ModBus register)
MOVE
COPR2CU1ERROR 71027 Input IN01 correspond to bit 0 of the ModBus register
COPROCESSOR MODULE 2 NEXT TO CU 1 EN Input IN16 correspond to bit 15 of the ModBus register
MOVE Holding Register: 501
COPR3CU1ERROR 71030
COPROCESSOR MODULE 3 NEXT TO CU 1 EN
MOVE
COPR1CU2ERROR 71033
COPROCESSOR MODULE 1 NEXT TO CU 2 EN
MOVE
COPR2CU2ERROR 71036
COPROCESSOR MODULE 2 NEXT TO CU 2 EN
MOVE
COPR3CU2ERROR 71039
COPROCESSOR MODULE 3 NEXT TO CU 2 EN
MOVE
BATTCU1ERROR 71042
BACKUP BATTERY ON CENTRAL MODULE 1 EN
MOVE
BATTCU2ERROR 71045
BACKUP BATTERY ON CENTRAL MODULE 2

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/71
1 check Martha Cluster MARTHA PLATF PES page 72
revision date name status: LZ based replaced replaced SOFTWARE DIG. OUT. ELAB. (PAGE 2 OF 19)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 72 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL OUTPUTS ELABORATION (PAGE 3 OF 19) OUTPUTS
MODBUS FUNCTION CODE 03: READ HOLDING (OUTPUT) REGISTER (SINGLE OR MULTIPLE)

OUTPUTS_ENABLED
WRITING OUTPUTS VALUES ENABLED EN
MOVE
CU1RUNRAM 72000 IN01 OT MODB-EXP-WORD-502
CU1 MOD. IN SERVICE - PARAM. IN RAM MEM. EN IN02 MODBUS WORD REGISTER SENT: 502
MOVE
CU1RUNEPROM 72003 IN03
CU1 MOD. IN SERVICE - PARAM. IN EPROM MEM. EN IN04
MOVE
CU2RUNRAM 72006 IN05
CU2 MOD. IN SERVICE - PARAM. IN RAM MEM. EN IN06
MOVE
CU2RUNEPROM 72009 IN07
CU2 MOD. IN SERVICE - PARAM. IN EPROM MEM. EN IN08
MOVE 16BOOLtoWORD
SYSERRCODENOERR 72012 IN09
PES SYSTEM NO ERROR PRESENT EN IN10
MOVE
SYSIOERR 72015 IN11
AT LEAST ONE I/O ERROR PRESENT EN IN12
MOVE
SYSFORBACC 72018 IN13
ATTEMPTED TO PERFORM A FORBIDDEN FUNCTION EN IN14
MOVE
SYSFORSWIN 72021 IN15
AT LEAST ONE INPUT VARIABLE FORCED EN IN16 72048
MOVE
SYSFORSWOT 72024
Software Digital Outputs via ModBus serial link
AT LEAST ONE OUTPUT VARIABLE FORCED EN Managed as a block of 16 values (=1 word, =1 ModBus register)
MOVE
SYSMSTFORSWIN 72027 Input IN01 correspond to bit 0 of the ModBus register
INPUTS FORCE MAIN SWITCH ACTIVATED EN Input IN16 correspond to bit 15 of the ModBus register
MOVE Holding Register: 502
SYSMSTFORSWOT 72030
OUTPUTS FORCE MAIN SWITCH ACTIVATED EN
MOVE
SYSNORMAL 72033
PES SYSTEM NORMAL FUNCTIONING EN
MOVE
SYSSINGCH 72036
REDUNDANT PES SYSTEM WITH ONLY ONE CU IN SERVICE EN
MOVE
INPUTS_ENABLED 72039
READING INPUTS VALUES ENABLED EN
MOVE
OUTPUTS_ENABLED 72042
WRITING OUTPUTS VALUES ENABLED EN
MOVE
ERR-SLOT01 72045
ERROR MODULE I/O SLOT01 - F3236 - DI1

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/72
1 check Martha Cluster MARTHA PLATF PES page 73
revision date name status: LZ based replaced replaced SOFTWARE DIG. OUT. ELAB. (PAGE 3 OF 19)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 73 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL OUTPUTS ELABORATION (PAGE 4 OF 19) OUTPUTS
MODBUS FUNCTION CODE 03: READ HOLDING (OUTPUT) REGISTER (SINGLE OR MULTIPLE)

OUTPUTS_ENABLED
WRITING OUTPUTS VALUES ENABLED EN
MOVE
ERR-SLOT02 73000 IN01 OT MODB-EXP-WORD-503
ERROR MODULE I/O SLOT02 - F3236 - DI2 EN IN02 MODBUS WORD REGISTER SENT: 503
MOVE
ERR-SLOT03 73003 IN03
ERROR MODULE I/O SLOT03 - F3236 - DI3 EN IN04
MOVE
ERR-SLOT04 73006 IN05
ERROR MODULE I/O SLOT04 - F3236 - DI4 EN IN06
MOVE
ERR-SLOT05 73009 IN07
ERROR MODULE I/O SLOT05 - F3236 - DI5 EN IN08
MOVE 16BOOLtoWORD
ERR-SLOT06 73012 IN09
ERROR MODULE I/O SLOT06 - empty EN IN10
MOVE
ERR-SLOT07 73015 IN11
ERROR MODULE I/O SLOT07 - empty EN IN12
MOVE
ERR-SLOT08 73018 IN13
ERROR MODULE I/O SLOT08 - F3331 - DO1 EN IN14
MOVE
ERR-SLOT09 73021 IN15
ERROR MODULE I/O SLOT09 - F3331 - DO2 EN IN16 73048
MOVE
ERR-SLOT10 73024
Software Digital Outputs via ModBus serial link
ERROR MODULE I/O SLOT10 - F3331 - DO3 EN Managed as a block of 16 values (=1 word, =1 ModBus register)
MOVE
ERR-SLOT11 73027 Input IN01 correspond to bit 0 of the ModBus register
ERROR MODULE I/O SLOT11 - F3331 - DO4 EN Input IN16 correspond to bit 15 of the ModBus register
MOVE Holding Register: 503
ERR-SLOT12 73030
ERROR MODULE I/O SLOT12 - F3331 - DO5 EN
MOVE
ERR-SLOT13 73033
ERROR MODULE I/O SLOT13 - F3331 - DO6 EN
MOVE
CUM-IOMOD-OK 73036
ALL PES I/O MODULES FUNCTIONING EN
MOVE
ERR-SLOT08-CH1 73039
ERROR CH.1 MOD. I/O SLOT08 - F3331 - DO1 EN
MOVE
ERR-SLOT08-CH2 73042
ERROR CH.2 MOD. I/O SLOT08 - F3331 - DO1 EN
MOVE
ERR-SLOT08-CH3 73045
ERROR CH.3 MOD. I/O SLOT08 - F3331 - DO1

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/73
1 check Martha Cluster MARTHA PLATF PES page 74
revision date name status: LZ based replaced replaced SOFTWARE DIG. OUT. ELAB. (PAGE 4 OF 19)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 74 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL OUTPUTS ELABORATION (PAGE 5 OF 19) OUTPUTS
MODBUS FUNCTION CODE 03: READ HOLDING (OUTPUT) REGISTER (SINGLE OR MULTIPLE)

OUTPUTS_ENABLED
WRITING OUTPUTS VALUES ENABLED EN
MOVE
ERR-SLOT08-CH4 74000 IN01 OT MODB-EXP-WORD-504
ERROR CH.4 MOD. I/O SLOT08 - F3331 - DO1 EN IN02 MODBUS WORD REGISTER SENT: 504
MOVE
ERR-SLOT08-CH5 74003 IN03
ERROR CH.5 MOD. I/O SLOT08 - F3331 - DO1 EN IN04
MOVE
ERR-SLOT08-CH6 74006 IN05
ERROR CH.6 MOD. I/O SLOT08 - F3331 - DO1 EN IN06
MOVE
ERR-SLOT08-CH7 74009 IN07
ERROR CH.7 MOD. I/O SLOT08 - F3331 - DO1 EN IN08
MOVE 16BOOLtoWORD
ERR-SLOT08-CH8 74012 IN09
ERROR CH.8 MOD. I/O SLOT08 - F3331 - DO1 EN IN10
MOVE
ERRCUM-SLOT08 74015 IN11
CUMUL. ERR. MODULE I/O SLOT08 - F3331 - DO1 EN IN12
MOVE
ERR-SLOT09-CH1 74018 IN13
ERROR CH.1 MOD. I/O SLOT08 - F3331 - DO2 EN IN14
MOVE
ERR-SLOT09-CH2 74021 IN15
ERROR CH.2 MOD. I/O SLOT08 - F3331 - DO2 EN IN16 74048
MOVE
ERR-SLOT09-CH3 74024
Software Digital Outputs via ModBus serial link
ERROR CH.3 MOD. I/O SLOT08 - F3331 - DO2 EN
Managed as a block of 16 values (=1 word, =1 ModBus register)
MOVE
ERR-SLOT09-CH4 74027 Input IN01 correspond to bit 0 of the ModBus register
ERROR CH.4 MOD. I/O SLOT08 - F3331 - DO2 EN Input IN16 correspond to bit 15 of the ModBus register
MOVE Holding Register: 504
ERR-SLOT09-CH5 74030
ERROR CH.5 MOD. I/O SLOT08 - F3331 - DO2 EN
MOVE
ERR-SLOT09-CH6 74033
ERROR CH.6 MOD. I/O SLOT08 - F3331 - DO2 EN
MOVE
ERR-SLOT09-CH7 74036
ERROR CH.7 MOD. I/O SLOT08 - F3331 - DO2 EN
MOVE
ERR-SLOT09-CH8 74039
ERROR CH.8 MOD. I/O SLOT08 - F3331 - DO2 EN
MOVE
ERRCUM-SLOT09 74042
CUMUL. ERR. MODULE I/O SLOT08 - F3331 - DO2 EN
MOVE
ERR-SLOT10-CH1 74045
ERROR CH.1 MOD. I/O SLOT08 - F3331 - DO3

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/74
1 check Martha Cluster MARTHA PLATF PES page 75
revision date name status: LZ based replaced replaced SOFTWARE DIG. OUT. ELAB. (PAGE 5 OF 19)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 75 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL OUTPUTS ELABORATION (PAGE 6 OF 19) OUTPUTS
MODBUS FUNCTION CODE 03: READ HOLDING (OUTPUT) REGISTER (SINGLE OR MULTIPLE)

OUTPUTS_ENABLED
WRITING OUTPUTS VALUES ENABLED EN
MOVE
ERR-SLOT10-CH2 75000 IN01 OT MODB-EXP-WORD-505
ERROR CH.2 MOD. I/O SLOT08 - F3331 - DO3 EN IN02 MODBUS WORD REGISTER SENT: 505
MOVE
ERR-SLOT10-CH3 75003 IN03
ERROR CH.3 MOD. I/O SLOT08 - F3331 - DO3 EN IN04
MOVE
ERR-SLOT10-CH4 75006 IN05
ERROR CH.4 MOD. I/O SLOT08 - F3331 - DO3 EN IN06
MOVE
ERR-SLOT10-CH5 75009 IN07
ERROR CH.5 MOD. I/O SLOT08 - F3331 - DO3 EN IN08
MOVE 16BOOLtoWORD
ERR-SLOT10-CH6 75012 IN09
ERROR CH.6 MOD. I/O SLOT08 - F3331 - DO3 EN IN10
MOVE
ERR-SLOT10-CH7 75015 IN11
ERROR CH.7 MOD. I/O SLOT08 - F3331 - DO3 EN IN12
MOVE
ERR-SLOT10-CH8 75018 IN13
ERROR CH.8 MOD. I/O SLOT08 - F3331 - DO3 EN IN14
MOVE
ERRCUM-SLOT10 75021 IN15
CUMUL. ERR. MODULE I/O SLOT08 - F3331 - DO3 EN IN16 75048
MOVE
ERR-SLOT11-CH1 75024
Software Digital Outputs via ModBus serial link
ERROR CH.1 MOD. I/O SLOT08 - F3331 - DO4 EN
Managed as a block of 16 values (=1 word, =1 ModBus register)
MOVE
ERR-SLOT11-CH2 75027 Input IN01 correspond to bit 0 of the ModBus register
ERROR CH.2 MOD. I/O SLOT08 - F3331 - DO4 EN Input IN16 correspond to bit 15 of the ModBus register
MOVE Holding Register: 505
ERR-SLOT11-CH3 75030
ERROR CH.3 MOD. I/O SLOT08 - F3331 - DO4 EN
MOVE
ERR-SLOT11-CH4 75033
ERROR CH.4 MOD. I/O SLOT08 - F3331 - DO4 EN
MOVE
ERR-SLOT11-CH5 75036
ERROR CH.5 MOD. I/O SLOT08 - F3331 - DO4 EN
MOVE
ERR-SLOT11-CH6 75039
ERROR CH.6 MOD. I/O SLOT08 - F3331 - DO4 EN
MOVE
ERR-SLOT11-CH7 75042
ERROR CH.7 MOD. I/O SLOT08 - F3331 - DO4 EN
MOVE
ERR-SLOT11-CH8 75045
ERROR CH.8 MOD. I/O SLOT08 - F3331 - DO4

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/75
1 check Martha Cluster MARTHA PLATF PES page 76
revision date name status: LZ based replaced replaced SOFTWARE DIG. OUT. ELAB. (PAGE 6 OF 19)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 76 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL OUTPUTS ELABORATION (PAGE 7 OF 19) OUTPUTS
MODBUS FUNCTION CODE 03: READ HOLDING (OUTPUT) REGISTER (SINGLE OR MULTIPLE)

OUTPUTS_ENABLED
WRITING OUTPUTS VALUES ENABLED EN
MOVE
ERRCUM-SLOT11 76000 IN01 OT MODB-EXP-WORD-506
CUMUL. ERR. MODULE I/O SLOT08 - F3331 - DO4 EN IN02 MODBUS WORD REGISTER SENT: 506
MOVE
ERR-SLOT12-CH1 76003 IN03
ERROR CH.1 MOD. I/O SLOT08 - F3331 - DO5 EN IN04
MOVE
ERR-SLOT12-CH2 76006 IN05
ERROR CH.2 MOD. I/O SLOT08 - F3331 - DO5 EN IN06
MOVE
ERR-SLOT12-CH3 76009 IN07
ERROR CH.3 MOD. I/O SLOT08 - F3331 - DO5 EN IN08
MOVE 16BOOLtoWORD
ERR-SLOT12-CH4 76012 IN09
ERROR CH.4 MOD. I/O SLOT08 - F3331 - DO5 EN IN10
MOVE
ERR-SLOT12-CH5 76015 IN11
ERROR CH.5 MOD. I/O SLOT08 - F3331 - DO5 EN IN12
MOVE
ERR-SLOT12-CH6 76018 IN13
ERROR CH.6 MOD. I/O SLOT08 - F3331 - DO5 EN IN14
MOVE
ERR-SLOT12-CH7 76021 IN15
ERROR CH.7 MOD. I/O SLOT08 - F3331 - DO5 EN IN16 76048
MOVE
ERR-SLOT12-CH8 76024
Software Digital Outputs via ModBus serial link
ERROR CH.8 MOD. I/O SLOT08 - F3331 - DO5 EN
Managed as a block of 16 values (=1 word, =1 ModBus register)
MOVE
ERRCUM-SLOT12 76027 Input IN01 correspond to bit 0 of the ModBus register
CUMUL. ERR. MODULE I/O SLOT08 - F3331 - DO5 EN Input IN16 correspond to bit 15 of the ModBus register
MOVE Holding Register: 506
ERR-SLOT13-CH1 76030
ERROR CH.1 MOD. I/O SLOT08 - F3331 - DO6 EN
MOVE
ERR-SLOT13-CH2 76033
ERROR CH.2 MOD. I/O SLOT08 - F3331 - DO6 EN
MOVE
ERR-SLOT13-CH3 76036
ERROR CH.3 MOD. I/O SLOT08 - F3331 - DO6 EN
MOVE
ERR-SLOT13-CH4 76039
ERROR CH.4 MOD. I/O SLOT08 - F3331 - DO6 EN
MOVE
ERR-SLOT13-CH5 76042
ERROR CH.5 MOD. I/O SLOT08 - F3331 - DO6 EN
MOVE
ERR-SLOT13-CH6 76045
ERROR CH.6 MOD. I/O SLOT08 - F3331 - DO6

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/76
1 check Martha Cluster MARTHA PLATF PES page 77
revision date name status: LZ based replaced replaced SOFTWARE DIG. OUT. ELAB. (PAGE 7 OF 19)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 77 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL OUTPUTS ELABORATION (PAGE 8 OF 19) OUTPUTS
MODBUS FUNCTION CODE 03: READ HOLDING (OUTPUT) REGISTER (SINGLE OR MULTIPLE)

OUTPUTS_ENABLED
WRITING OUTPUTS VALUES ENABLED EN
MOVE
ERR-SLOT13-CH7 77000 IN01 OT MODB-EXP-WORD-507
ERROR CH.7 MOD. I/O SLOT08 - F3331 - DO6 EN IN02 MODBUS WORD REGISTER SENT: 507
MOVE
ERR-SLOT13-CH8 77003 IN03
ERROR CH.8 MOD. I/O SLOT08 - F3331 - DO6 EN IN04
MOVE
ERRCUM-SLOT13 77006 IN05
CUMUL. ERR. MODULE I/O SLOT08 - F3331 - DO6 EN IN06
MOVE
CHERR-SLOT08 77009 IN07
AT LST ONE ERR. CHAN. MOD. I/O SLOT08 - F3331 - DO1 EN IN08
MOVE
77012
16BOOLtoWORD
CHERR-SLOT09 IN09
AT LST ONE ERR. CHAN. MOD. I/O SLOT09 - F3331 - DO2 EN IN10
MOVE
CHERR-SLOT10 77015 IN11
AT LST ONE ERR. CHAN. MOD. I/O SLOT10 - F3331 - DO3 EN IN12
MOVE
CHERR-SLOT11 77018 IN13
AT LST ONE ERR. CHAN. MOD. I/O SLOT11 - F3331 - DO4 EN IN14
MOVE
CHERR-SLOT12 77021 IN15
AT LST ONE ERR. CHAN. MOD. I/O SLOT12 - F3331 - DO5 EN IN16 77048
MOVE
CHERR-SLOT13 77024
Software Digital Outputs via ModBus serial link
AT LST ONE ERR. CHAN. MOD. I/O SLOT13 - F3331 - DO6 EN Managed as a block of 16 values (=1 word, =1 ModBus register)
MOVE
CUM-CHMODIO-OK 77027 Input IN01 correspond to bit 0 of the ModBus register
I/O DO MODULES ALL CHANNELS WORKING EN Input IN16 correspond to bit 15 of the ModBus register
MOVE Holding Register: 507
003F.2 FLAME_FAIL 77030
FLAME DETECT. SYST. FAIL. NOT PRESENT EN
MOVE
003E.2 EXPG_FAIL 77033
EXPL. GAS DETECT. SYST. FAIL. NOT PRESENT EN
MOVE
RPA.2 PLT_ABD 77036
PLATF. ABAND. PUSH-BUTTONS NOT ACTIV. EN
MOVE
RPS1.2 UNM_MAN 77039
UNMANNED POSIT. SELECT. SIGNALIZ. EN
MOVE
RET2.3 ELETRP_INC 77042
ELECT. TRIPS SELECT. INCLUDED POSIT. EN
MOVE
RMOB.2 MOB_PB 77045
MAN OVERBOARD PUSH-BUTTONS NOT ACTIVATED

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/77
1 check Martha Cluster MARTHA PLATF PES page 78
revision date name status: LZ based replaced replaced SOFTWARE DIG. OUT. ELAB. (PAGE 8 OF 19)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 78 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL OUTPUTS ELABORATION (PAGE 9 OF 19) OUTPUTS
MODBUS FUNCTION CODE 03: READ HOLDING (OUTPUT) REGISTER (SINGLE OR MULTIPLE)

OUTPUTS_ENABLED
WRITING OUTPUTS VALUES ENABLED EN
MOVE
003S.2 SMOKE_FAIL 78000 IN01 OT MODB-EXP-WORD-508
SMOKE DETECT. SYST. FAIL. NOT PRESENT EN IN02 MODBUS WORD REGISTER SENT: 508
MOVE
DMP5.2 DMP_GEN 78003 IN03
MAIN ENTRANCE AIR DAMPERS CLOSED EN IN04
MOVE
012F.2 FLAME_PALM 78006 IN05
FLAME PREALARM STAU ROOM NOT PRESENT EN IN06
MOVE
022F.2 FLAME_PALM 78009 IN07
FLAME PREALARM G1 COMPART. NOT PRESENT EN IN08
MOVE 16BOOLtoWORD
032F.2 FLAME_PALM 78012 IN09
FLAME PREALARM SWTCHBRDS COMP. NOT PRESENT EN IN10
MOVE
042F.2 FLAME_PALM 78015 IN11
FLAME PREALARM TRANSF. COMPART. NOT PRESENT EN IN12
MOVE
011F.2 FLAME_ALM 78018 IN13
FLAME ALARM STAU ROOM NOT PRESENT EN IN14
MOVE
012F.2 FLAME_ALM 78021 IN15
FLAME ALARM G1 COMPART. NOT PRESENT EN IN16 78048
MOVE
013F.2 FLAME_ALM 78024
Software Digital Outputs via ModBus serial link
FLAME ALARM SWTCHBRDS COMP. NOT PRESENT EN Managed as a block of 16 values (=1 word, =1 ModBus register)
MOVE
014F.2 FLAME_ALM 78027 Input IN01 correspond to bit 0 of the ModBus register
FLAME ALARM TRANSF. COMPART. NOT PRESENT EN Input IN16 correspond to bit 15 of the ModBus register
MOVE Holding Register: 508
011E.2 EXPG_PALM 78030
EXPL. GAS PREALARM ZONE #1 WELL HEADS NOT PRES. EN
MOVE
012E.2 EXPG_ALM 78033
EXPL. GAS ALARM ZONE #1 WELL HEADS NOT PRES. EN
MOVE
021E.2 EXPG_PALM 78036
EXPL. GAS PREALARM ZONE #2 WELL HEADS NOT PRES. EN
MOVE
022E.2 EXPG_ALM 78039
EXPL. GAS ALARM ZONE #2 WELL HEADS NOT PRES. EN
MOVE
031E.2 EXPG_PALM 78042
EXPL. GAS PREALARM ZONE #3 WELL HEADS NOT PRES. EN
MOVE
032E.2 EXPG_ALM 78045
EXPL. GAS ALARM ZONE #3 WELL HEADS NOT PRES.

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/78
1 check Martha Cluster MARTHA PLATF PES page 79
revision date name status: LZ based replaced replaced SOFTWARE DIG. OUT. ELAB. (PAGE 9 OF 19)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 79 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL OUTPUTS ELABORATION (PAGE 10 OF 19) OUTPUTS
MODBUS FUNCTION CODE 03: READ HOLDING (OUTPUT) REGISTER (SINGLE OR MULTIPLE)

OUTPUTS_ENABLED
WRITING OUTPUTS VALUES ENABLED EN
MOVE
041E.2 EXPG_PALM 79000 IN01 OT MODB-EXP-WORD-509
EXPL. GAS PREALARM ZONE #4 WELL HEADS NOT PRES. EN IN02 MODBUS WORD REGISTER SENT: 509
MOVE
042E.2 EXPG_ALM 79003 IN03
EXPL. GAS ALARM ZONE #4 WELL HEADS NOT PRES. EN IN04
MOVE
051E.2 EXPG_PALM 79006 IN05
EXPL. GAS PREALARM ZONE #5 PROC. MOD. NOT PRES. EN IN06
MOVE
052E.2 EXPG_ALM 79009 IN07
EXPL. GAS ALARM ZONE #5 PROC. MOD. NOT PRES. EN IN08
MOVE 16BOOLtoWORD
061E.2 EXPG_PALM 79012 IN09
EXPL. GAS PREALARM ZONE #6 PROC. MOD. NOT PRES. EN IN10
MOVE
062E.2 EXPG_ALM 79015 IN11
EXPL. GAS ALARM ZONE #6 PROC. MOD. NOT PRES. EN IN12
MOVE
071E.2 EXPG_PALM 79018 IN13
EXPL. GAS PREALARM ZONE #7 PROC. MOD. NOT PRES. EN IN14
MOVE
072E.2 EXPG_ALM 79021 IN15
EXPL. GAS ALARM ZONE #7 PROC. MOD. NOT PRES. EN IN16 79048
MOVE
081E.2 EXPG_PALM 79024
Software Digital Outputs via ModBus serial link
EXPL. GAS PREALARM ZONE #8 PROC. MOD. NOT PRES. EN Managed as a block of 16 values (=1 word, =1 ModBus register)
MOVE
082E.2 EXPG_ALM 79027 Input IN01 correspond to bit 0 of the ModBus register
EXPL. GAS ALARM ZONE #8 PROC. MOD. NOT PRES. EN Input IN16 correspond to bit 15 of the ModBus register
MOVE Holding Register: 509
091E.2 EXPG_PALM 79030
EXPL. GAS PREALARM ZONE #9 PROC. MOD. NOT PRES. EN
MOVE
092E.2 EXPG_ALM 79033
EXPL. GAS ALARM ZONE #9 PROC. MOD. NOT PRES. EN
MOVE
101E.2 EXPG_PALM 79036
EXPL. GAS PREALARM STAU ROOM NOT PRES. EN
MOVE
102E.2 EXPG_ALM 79039
EXPL. GAS ALARM STAU ROOM NOT PRES. EN
MOVE
111E.2 EXPG_PALM 79042
EXPL. GAS PREALARM G1 COMPART. NOT PRES. EN
MOVE
112E.2 EXPG_ALM 79045
EXPL. GAS ALARM G1 COMPART. NOT PRES.

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/79
1 check Martha Cluster MARTHA PLATF PES page 80
revision date name status: LZ based replaced replaced SOFTWARE DIG. OUT. ELAB. (PAGE 10 OF 19)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 80 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL OUTPUTS ELABORATION (PAGE 11 OF 19) OUTPUTS
MODBUS FUNCTION CODE 03: READ HOLDING (OUTPUT) REGISTER (SINGLE OR MULTIPLE)

OUTPUTS_ENABLED
WRITING OUTPUTS VALUES ENABLED EN
MOVE
121E.2 EXPG_PALM 80000 IN01 OT MODB-EXP-WORD-510
EXPL. GAS PREALARM SWTCHBRDS COMP. NOT PRESENT EN IN02 MODBUS WORD REGISTER SENT: 510
MOVE
122E.2 EXPG_ALM 80003 IN03
EXPL. GAS ALARM SWTCHBRDS COMP. NOT PRESENT EN IN04
MOVE
131E.2 EXPG_PALM 80006 IN05
EXPL. GAS PREALARM TRANSF. COMP. NOT PRESENT EN IN06
MOVE
132E.2 EXPG_ALM 80009 IN07
EXPL. GAS ALARM TRANSF. COMP. NOT PRESENT EN IN08
MOVE 16BOOLtoWORD
141E.2 EXPG_PALM 80012 IN09
EXPL. GAS PREALARM PRESS. ASPIR. NOT PRESENT EN IN10
MOVE
142E.2 EXPG_ALM 80015 IN11
EXPL. GAS ALARM PRESS. ASPIR. NOT PRESENT EN IN12
MOVE
RP1.2 PSL_ST 80018 IN13
STAU ROOM PRESSURIZATION PRESENT EN IN14
MOVE
RP2.2 PSL_G1 80021 IN15
G1 COMPARTMENT PRESSURIZATION PRESENT EN IN16 80048
MOVE
RP3.2 PSL_EP 80024
Software Digital Outputs via ModBus serial link
SWITCHBOARDS COMPART. PRESSURIZ. PRESENT EN
Managed as a block of 16 values (=1 word, =1 ModBus register)
MOVE
RP4.2 PSL_TR 80027 Input IN01 correspond to bit 0 of the ModBus register
TRASFORMER COMPART. PRESSURIZ. PRESENT EN Input IN16 correspond to bit 15 of the ModBus register
MOVE Holding Register: 510
011S.2 SMOKE_ALM 80030
SMOKE ALARM STAU ROOM NOT PRESENT EN
MOVE
021S.2 SMOKE_ALM 80033
SMOKE ALARM G1 COMPART. NOT PRESENT EN
MOVE
031S.2 SMOKE_ALM 80036
SMOKE ALARM SWTCHBRDS COMP. NOT PRESENT EN
MOVE
041S.2 SMOKE_ALM 80039
SMOKE ALARM TRANSF. COMPART. NOT PRESENT EN
MOVE
012S.2 SMOKE_FAIL 80042
SMOKE FAIL. STAU ROOM NOT PRESENT EN
MOVE
022S.2 SMOKE_FAIL 80045
SMOKE FAIL. G1 COMPART. NOT PRESENT

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/80
1 check Martha Cluster MARTHA PLATF PES page 81
revision date name status: LZ based replaced replaced SOFTWARE DIG. OUT. ELAB. (PAGE 11 OF 19)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 81 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL OUTPUTS ELABORATION (PAGE 12 OF 19) OUTPUTS
MODBUS FUNCTION CODE 03: READ HOLDING (OUTPUT) REGISTER (SINGLE OR MULTIPLE)

OUTPUTS_ENABLED
WRITING OUTPUTS VALUES ENABLED EN
MOVE
032S.2 SMOKE_FAIL 81000 IN01 OT MODB-EXP-WORD-511
SMOKE FAIL. SWTCHBRDS COMP. NOT PRESENT EN IN02 MODBUS WORD REGISTER SENT: 511
MOVE
042S.2 SMOKE_FAIL 81003 IN03
SMOKE FAIL. TRANSF. COMPART. NOT PRESENT EN IN04
MOVE
DMP1.2 DMP_ST 81006 IN05
STAU ROOM AIR DAMPERS CLOSED EN IN06
MOVE
DMP2.2 DMP_G1 81009 IN07
G1 COMPART. AIR DAMPERS CLOSED EN IN08
MOVE 16BOOLtoWORD
DMP3.2 DMP_EP 81012 IN09
SWTCHBRDS COMPART. AIR DAMPERS CLOSED EN IN10
MOVE
DMP4.2 DMP_TR 81015 IN11
TRANSF. COMPART. AIR DAMPERS CLOSED EN IN12
MOVE
R13.2 INR_REL_ST 81018 IN13
INERGEN RELEASE STAU ROOM NOT OCCURR. EN IN14
MOVE
R23.2 INR_REL_G1 81021 IN15
INERGEN RELEASE G1 COMPART. NOT OCCURR. EN IN16 81048
MOVE
R33.2 INR_REL_EP 81024
Software Digital Outputs via ModBus serial link
INERGEN RELEASE SWTCHBRDS COMPART. NOT OCCURR. EN
Managed as a block of 16 values (=1 word, =1 ModBus register)
MOVE
R43.2 INR_REL_TR 81027 Input IN01 correspond to bit 0 of the ModBus register
INERGEN RELEASE TRANSF. COMPART. NOT OCCURR. EN Input IN16 correspond to bit 15 of the ModBus register
MOVE Holding Register: 511
051S.1 SMOKE_ALM 81030
SMOKE ALARM COMMON LINE NOT PRESENT EN
MOVE
052S.1 SMOKE_FAIL 81033
SMOKE FAIL. COMMON LINE NOT PRESENT EN
MOVE
TONES_SILENCER 81036
TONES CTRL UNIT SILENCER PUSH-BUTTON ACTIV. EN
MOVE
RB_A/B_REM_TRP 81039
PLATFORM EMERGENCY TRIP REMOTE COMMAND EN
MOVE
FUPLGNET 81042
PROD. EMERG. TRIP FROM FUSIB. PLUGS NOT ACTIV. EN
MOVE
POWSUPP_24V_OK 81045
24VDC PS1 & PS2 POW. SUPP. IN SERVICE

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/81
1 check Martha Cluster MARTHA PLATF PES page 82
revision date name status: LZ based replaced replaced SOFTWARE DIG. OUT. ELAB. (PAGE 12 OF 19)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 82 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL OUTPUTS ELABORATION (PAGE 13 OF 19) OUTPUTS
MODBUS FUNCTION CODE 03: READ HOLDING (OUTPUT) REGISTER (SINGLE OR MULTIPLE)

OUTPUTS_ENABLED
WRITING OUTPUTS VALUES ENABLED EN
MOVE
RACK_PES_OK 82000 IN01 OT MODB-EXP-WORD-512
HIMA PES RACK FUNCTIONING EN IN02 MODBUS WORD REGISTER SENT: 512
MOVE
RS15 PESSYS_OK 82003 IN03
HIMA PES SYSTEM NORMAL FUNCTIONING EN IN04
MOVE
RS13 PES_ALM 82006 IN05
HIMA PES SYS. AT LEAST ONE FAULT PRES. SIGNALIZ. EN IN06
MOVE
SMOKE_TRIP_INHIB 82009 IN07
SMOKE TRIP INHIBITION ACTIVATED EN IN08
011-2S.2 SMK_TRP
MOVE
82012 IN09
16BOOLtoWORD
STAU ROOM SMOKE TRIP NOT PRESENT EN IN10
MOVE
011-2S.2 INR_REL 82015 IN11
STAU ROOM INERGEN RELEASE NOT PRESENT EN IN12
MOVE
021-2S.2 SMK_TRP 82018 IN13
G1 COMPART. SMOKE TRIP NOT PRESENT EN IN14
MOVE
021-2S.2 INR_REL 82021 IN15
G1 COMPART. INERGEN REL. NOT PRESENT EN IN16 82048
MOVE
031-2S.2 SMK_TRP 82024
Software Digital Outputs via ModBus serial link
SWTCHBRDS COMPART. SMOKE TRIP NOT PRESENT EN
Managed as a block of 16 values (=1 word, =1 ModBus register)
MOVE
031-2S.2 INR_REL 82027 Input IN01 correspond to bit 0 of the ModBus register
SWTCHBRDS COMPART. INERGEN REL. NOT PRES. EN Input IN16 correspond to bit 15 of the ModBus register
MOVE Holding Register: 512
041-2S.2 SMK_TRP 82030
TRANSF. COMPART. SMOKE TRIP NOT PRESENT EN
MOVE
041-2S.2 INR_REL 82033
TRANSF. COMPART. INERGEN REL. NOT PRES. EN
MOVE
RS/1 ST_TRIP 82036
STAU ROOM TRIP COMMAND EN
MOVE
ST_TRIP 82039
STAU ROOM TRIP CONDITION PRESENT EN
MOVE
RS/2 G1_TRIP 82042
G1 COMPART. TRIP COMMAND EN
MOVE
G1_TRIP 82045
G1 COMPART. TRIP CONDITION PRESENT

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/82
1 check Martha Cluster MARTHA PLATF PES page 83
revision date name status: LZ based replaced replaced SOFTWARE DIG. OUT. ELAB. (PAGE 13 OF 19)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 83 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL OUTPUTS ELABORATION (PAGE 14 OF 19) OUTPUTS
MODBUS FUNCTION CODE 03: READ HOLDING (OUTPUT) REGISTER (SINGLE OR MULTIPLE)

OUTPUTS_ENABLED
WRITING OUTPUTS VALUES ENABLED EN
MOVE
RS/3 EP_TRIP 83000 IN01 OT MODB-EXP-WORD-513
SWTCHBRDS COMPART. TRIP COMMAND EN IN02 MODBUS WORD REGISTER SENT: 513
MOVE
EP_TRIP 83003 IN03
SWTCHBRDS COMPART. TRIP CONDITION PRESENT EN IN04
MOVE
RS/4 TR_TRIP 83006 IN05
TRANSF. COMPART. TRIP COMMAND EN IN06
MOVE
TR_TRIP 83009 IN07
TRANSF. COMPART. TRIP CONDITION PRESENT EN IN08
MOVE
83012
16BOOLtoWORD
SOV1 ST_CL_DMP IN09
STAU ROOM AIR DAMPERS CLOSING EN IN10
MOVE
ST_CL_DMP 83015 IN11
STAU ROOM AIR DAMPERS CLOSING CONDIT. PRES. EN IN12
MOVE
SOV2 G1_CL_DMP 83018 IN13
G1 COMPART. AIR DAMPERS CLOSING EN IN14
MOVE
G1_CL_DMP 83021 IN15
G1 COMPART. AIR DAMPERS CLOSING CONDIT. PRES. EN IN16 83048
MOVE
SOV3 EP_CL_DMP 83024
Software Digital Outputs via ModBus serial link
SWTCHBRDS COMPART. AIR DAMPERS CLOSING EN Managed as a block of 16 values (=1 word, =1 ModBus register)
MOVE
EP_CL_DMP 83027 Input IN01 correspond to bit 0 of the ModBus register
SWTCHBRDS COMPART. AIR DAMPERS CLOSING CONDIT. PRES. EN Input IN16 correspond to bit 15 of the ModBus register
MOVE Holding Register: 513
SOV4 TR_CL_DMP 83030
TRANSF. COMPART. AIR DAMPERS CLOSING EN
MOVE
TR_CL_DMP 83033
TRANSF. COMPART. AIR DAMPERS CLOSING CONDIT. PRES. EN
MOVE
SOV5-6 GE_CL_DMP 83036
MAIN ENTRANCE AIR DAMPERS CLOSING EN
MOVE
GE_CL_DMP 83039
MAIN ENTRANCE AIR DAMPERS CLOSING CONDIT. PRES. EN
MOVE
SOV7 GEN_TRIP 83042
PLATFORM GENERAL TRIP COMMAND EN
MOVE
GEN_TRIP 83045
PLATFORM GENERAL TRIP CONDITION PRESENT

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/83
1 check Martha Cluster MARTHA PLATF PES page 84
revision date name status: LZ based replaced replaced SOFTWARE DIG. OUT. ELAB. (PAGE 14 OF 19)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 84 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL OUTPUTS ELABORATION (PAGE 15 OF 19) OUTPUTS
MODBUS FUNCTION CODE 03: READ HOLDING (OUTPUT) REGISTER (SINGLE OR MULTIPLE)

OUTPUTS_ENABLED
WRITING OUTPUTS VALUES ENABLED EN
MOVE
RS/5 PP_TRIP 84000 IN01 OT MODB-EXP-WORD-514
PURGE PANEL TRIP COMMAND EN IN02 MODBUS WORD REGISTER SENT: 514
MOVE
PP_TRIP 84003 IN03
PURGE PANEL TRIP CONDITION PRESENT EN IN04
MOVE
RS11 PRES_TRIP 84006 IN05
PRESSURIZ. GENERAL TRIP COMMAND EN IN06
MOVE
PRES_TRIP 84009 IN07
PRESSURIZ. GENERAL TRIP CONDITION PRESENT EN IN08
MOVE 16BOOLtoWORD
R10 INR_ST 84012 IN09
INERGEN RELEASE STAU ROOM COMMAND EN IN10
MOVE
INR_ST 84015 IN11
INERGEN RELEASE STAU ROOM CONDITION PRESENT EN IN12
MOVE
R20 INR_G1 84018 IN13
INERGEN RELEASE G1 COMPART. COMMAND EN IN14
MOVE
INR_G1 84021 IN15
INERGEN RELEASE G1 COMPART. CONDITION PRESENT EN IN16 84048
MOVE
R30 INR_EP 84024
Software Digital Outputs via ModBus serial link
INERGEN REL. SWTCHBRDS COMP. COMMAND EN Managed as a block of 16 values (=1 word, =1 ModBus register)
MOVE
INR_EP 84027 Input IN01 correspond to bit 0 of the ModBus register
INERGEN REL. SWTCHBRDS COMPART. CONDIT. PRES. EN Input IN16 correspond to bit 15 of the ModBus register
MOVE Holding Register: 514
R40 INR_TR 84030
INERGEN REL. TRANSF. COMPART. COMMAND EN
MOVE
INR_TR 84033
INERGEN REL. TRANSF. COMPART. CONDIT. PRES. EN
MOVE
RS10 ACT_TRIP 84036
AT LEAST ONE TRIP PRESENT SIGNALING EN
MOVE
RS12 PRG_PRM 84039
PURGE PANEL PERMISSIVE EN
MOVE
RT1 TONE1 84042
TONE #1 ACTIVATION EN
MOVE
RT2 TONE2 84045
TONE #2 ACTIVATION

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/84
1 check Martha Cluster MARTHA PLATF PES page 85
revision date name status: LZ based replaced replaced SOFTWARE DIG. OUT. ELAB. (PAGE 15 OF 19)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 85 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL OUTPUTS ELABORATION (PAGE 16 OF 19) OUTPUTS
MODBUS FUNCTION CODE 03: READ HOLDING (OUTPUT) REGISTER (SINGLE OR MULTIPLE)

OUTPUTS_ENABLED
WRITING OUTPUTS VALUES ENABLED EN
MOVE
RT3 TONE3 85000 IN01 OT MODB-EXP-WORD-515
TONE #3 ACTIVATION EN IN02 MODBUS WORD REGISTER SENT: 515
MOVE
RT4 TONE4 85003 IN03
TONE #4 ACTIVATION EN IN04
MOVE
TRIPS_RES_PB 85006 IN05
TRIPS RESET PUSH BUTTON ACTIV. EN IN06
MOVE
WAIT_T_INR_ST 85009 IN07
INERGEN REL. STAU ROOM T. DEL. ACTIV. EN IN08
MOVE 16BOOLtoWORD
WAIT_T_INR_G1 85012 IN09
INERGEN REL. G1 COMPART. T. DEL. ACTIV. EN IN10
MOVE
WAIT_T_INR_EP 85015 IN11
INERGEN REL. SWTCHBRDS COMP. T. DEL. ACT. EN IN12
MOVE
WAIT_T_INR_TR 85018 IN13
INERGEN REL. TRANSF. COMP. T. DEL. ACT. EN IN14
MOVE
FULL_MIN_PULSE 85021 IN15
MINUTE COMPLETED PULSE EN IN16 85048
MOVE
FULL_HOUR_PULSE 85024
Software Digital Outputs via ModBus serial link
HOUR COMPLETED PULSE EN Managed as a block of 16 values (=1 word, =1 ModBus register)
MOVE
FULL_DAY_PULSE 85027 Input IN01 correspond to bit 0 of the ModBus register
DAY COMPLETED PULSE EN Input IN16 correspond to bit 15 of the ModBus register
MOVE Holding Register: 515
AVAILABLE SPARE DIGITAL OUTPUT (NOT USED) FALSE 85030
EN
MOVE
AVAILABLE SPARE DIGITAL OUTPUT (NOT USED) FALSE 85033
EN
MOVE
AVAILABLE SPARE DIGITAL OUTPUT (NOT USED) FALSE 85036
EN
MOVE
AVAILABLE SPARE DIGITAL OUTPUT (NOT USED) FALSE 85039
EN
MOVE
AVAILABLE SPARE DIGITAL OUTPUT (NOT USED) FALSE 85042
EN
MOVE
AVAILABLE SPARE DIGITAL OUTPUT (NOT USED) FALSE 85045

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/85
1 check Martha Cluster MARTHA PLATF PES page 86
revision date name status: LZ based replaced replaced SOFTWARE DIG. OUT. ELAB. (PAGE 16 OF 19)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 86 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL OUTPUTS ELABORATION (PAGE 17 OF 19) OUTPUTS
MODBUS FUNCTION CODE 03: READ HOLDING (OUTPUT) REGISTER (SINGLE OR MULTIPLE)

OUTPUTS_ENABLED
WRITING OUTPUTS VALUES ENABLED EN
MOVE
AVAILABLE SPARE DIGITAL OUTPUT (NOT USED) FALSE 86000 IN01 OT MODB-EXP-WORD-516
EN IN02 MODBUS WORD REGISTER SENT: 516
MOVE
AVAILABLE SPARE DIGITAL OUTPUT (NOT USED) FALSE 86003 IN03
EN IN04
MOVE
AVAILABLE SPARE DIGITAL OUTPUT (NOT USED) FALSE 86006 IN05
EN IN06
MOVE
AVAILABLE SPARE DIGITAL OUTPUT (NOT USED) FALSE 86009 IN07
EN IN08
MOVE 16BOOLtoWORD
AVAILABLE SPARE DIGITAL OUTPUT (NOT USED) FALSE 86012 IN09
EN IN10
MOVE
AVAILABLE SPARE DIGITAL OUTPUT (NOT USED) FALSE 86015 IN11
EN IN12
MOVE
AVAILABLE SPARE DIGITAL OUTPUT (NOT USED) FALSE 86018 IN13
EN IN14
MOVE
AVAILABLE SPARE DIGITAL OUTPUT (NOT USED) FALSE 86021 IN15
EN IN16 86048
MOVE
AVAILABLE SPARE DIGITAL OUTPUT (NOT USED) FALSE 86024
Software Digital Outputs via ModBus serial link
EN
MOVE Managed as a block of 16 values (=1 word, =1 ModBus register)
AVAILABLE SPARE DIGITAL OUTPUT (NOT USED) FALSE 86027 Input IN01 correspond to bit 0 of the ModBus register
EN Input IN16 correspond to bit 15 of the ModBus register
MOVE Holding Register: 516
AVAILABLE SPARE DIGITAL OUTPUT (NOT USED) FALSE 86030
EN
MOVE
AVAILABLE SPARE DIGITAL OUTPUT (NOT USED) FALSE 86033
EN
MOVE
AVAILABLE SPARE DIGITAL OUTPUT (NOT USED) FALSE 86036
EN
MOVE
AVAILABLE SPARE DIGITAL OUTPUT (NOT USED) FALSE 86039
EN
MOVE
AVAILABLE SPARE DIGITAL OUTPUT (NOT USED) FALSE 86042
EN
MOVE
AVAILABLE SPARE DIGITAL OUTPUT (NOT USED) FALSE 86045

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/86
1 check Martha Cluster MARTHA PLATF PES page 87
revision date name status: LZ based replaced replaced SOFTWARE DIG. OUT. ELAB. (PAGE 17 OF 19)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 87 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL OUTPUTS ELABORATION (PAGE 18 OF 19) OUTPUTS
MODBUS FUNCTION CODE 03: READ HOLDING (OUTPUT) REGISTER (SINGLE OR MULTIPLE)

OUTPUTS_ENABLED
WRITING OUTPUTS VALUES ENABLED EN
>WORD
SYSERRCODE 87000 MODB-EXP-WORD-517
SYSTEM ERRORS CODE EN MODBUS WORD REGISTER SENT: 517
>WORD
SYSNUMFORBACC 87003 MODB-EXP-WORD-518
NUMB. OF ATTEMP. TO PERFORM A FORBID. FUNC. EN MODBUS WORD REGISTER SENT: 518
MOVE
SYSCODEVER 87006 MODB-EXP-WORD-519
PES RESOURCE CURRENT CODE VERSION EN MODBUS WORD REGISTER SENT: 519
MOVE
SYSRUNVER 87009 MODB-EXP-WORD-520
PES RESOURCE CURRENT RUN VERSION EN MODBUS WORD REGISTER SENT: 520
>WORD
CYCLE_TIME 87012 MODB-EXP-WORD-521
APPLICATION PROGRAM EXECUTION CYCLE TIME (msec) EN MODBUS WORD REGISTER SENT: 521
>WORD
CYCLE_FREQ 87015 MODB-EXP-WORD-522
APPLICATION PROGRAM EXECUTION FREQUENCY (Hz) EN MODBUS WORD REGISTER SENT: 522
>WORD
YEAR_OUT 87018 MODB-EXP-WORD-523
ACTUAL YEAR VALUE (0...99) EN MODBUS WORD REGISTER SENT: 523
>WORD
MONTH_OUT 87021 MODB-EXP-WORD-524
ACTUAL MONTH VALUE (1...12) EN MODBUS WORD REGISTER SENT: 524
>WORD
DAY_OUT 87024 MODB-EXP-WORD-525
ACTUAL DAY VALUE (1...31) EN MODBUS WORD REGISTER SENT: 525
>WORD
HOURS_OUT 87027 MODB-EXP-WORD-526
ACTUAL HOURS VALUE (0...23) EN MODBUS WORD REGISTER SENT: 526
>WORD
MINUTES_OUT 87030 MODB-EXP-WORD-527
ACTUAL MINUTES VALUE (0...59) EN MODBUS WORD REGISTER SENT: 527
>WORD
SECONDS_OUT 87033 MODB-EXP-WORD-528
ACTUAL SECONDS VALUE (0...59) EN MODBUS WORD REGISTER SENT: 528
>WORD
MSECONDI_OUT 87036 MODB-EXP-WORD-529
ACTUAL MILLISECONDS VALUE (0...999) MODBUS WORD REGISTER SENT: 529

16#FFFF MODB-EXP-WORD-LIM
MODBUS ANAL. SIGN. SENT MEM. AREA LIMIT (500...999)
16#FFFF MODB-IMP/EXP-WORD-LIM
MODBUS ANAL. SIGN. REC./SENT MEM. AREA LIMIT (1000...1499)

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/87
1 check Martha Cluster MARTHA PLATF PES page 88
revision date name status: LZ based replaced replaced SOFTWARE DIG. OUT. ELAB. (PAGE 18 OF 19)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 88 OF 114 SOFTWARE - MODBUS SERIAL LINK - DIGITAL OUTPUTS ELABORATION (PAGE 19 OF 19) OUTPUTS
AVAILABLE EMPTY PAGE
MODBUS FUNCTION CODE 01: READ COIL (OUTPUT) STATUS (SINGLE OR MULTIPLE)

TRUE MODB-EXP-BOOL-500
MODBUS DIG. SIGN. SENT: 500 - AVAILAB. (NOT USED)
TRUE MODB-EXP-BOOL-LIM
MODBUS DIG. SIGN. SENT MEM. AREA LIMIT (500...999)
TRUE MODB-IMP/EXP-BOOL-LIM
MODBUS DIG. SIGN. REC./SENT MEM. AREA LIMIT (1000...1499)

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/88
1 check Martha Cluster MARTHA PLATF PES page 89
revision date name status: LZ based replaced replaced SOFTWARE DIG. OUT. ELAB. (PAGE 19 OF 19)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 89 OF 114 HARDWIRED DIGITAL OUTPUTS ELABORATION (PAGE 1 OF 4) OUTPUTS

OUTPUTS_ENABLED
WRITING OUTPUTS VALUES ENABLED EN
MOVE
RS/1 ST_TRIP 89000 00.08.01
STAU ROOM TRIP COMMAND EN Terminal strip: TB-DO-01 Terminals: 1(0Vcc), 2(Ch01 - d2)
MOVE
RS/2 G1_TRIP 89003
00.08.02
G1 COMPART. TRIP COMMAND EN
MOVE Terminal strip: TB-DO-01 Terminals: 3(0Vcc), 4(Ch02 - d4)
RT1 TONE1 89006
TONE #1 ACTIVATION EN 00.08.03
MOVE
RT2 TONE2 89009 Terminal strip: TB-DO-01 Terminals: 5(0Vcc), 6(Ch03 - d6)
TONE #2 ACTIVATION EN
MOVE 00.08.04
RT3 TONE3 89012
Terminal strip: TB-DO-01 Terminals: 7(0Vcc), 8(Ch04 - d8)
TONE #3 ACTIVATION EN
MOVE
RT4 TONE4 89015 00.08.05
TONE #4 ACTIVATION EN Terminal strip: TB-DO-01 Terminals: 9(0Vcc), 10(Ch05 - d10)
MOVE
R10 INR_ST 89018
00.08.06
INERGEN RELEASE STAU ROOM COMMAND EN
MOVE Terminal strip: TB-DO-01 Terminals: 11(0Vcc), 12(Ch06 - d12)
SOV7 GEN_TRIP 89021
PLATFORM GENERAL TRIP COMMAND 00.08.07
Module: Digital Outputs
Model: F3331 Terminal strip: TB-DO-01 Terminals: 13(0Vcc), 14(Ch07 - d14)
Cable: Z7138
00.08.08
Rack: Rack00
Position: Slot08 Terminal strip: TB-DO-01 Terminals: 15(0Vcc), 16(Ch08 - d16)

OUTPUTS_ENABLED
WRITING OUTPUTS VALUES ENABLED EN
MOVE
RS11 PRES_TRIP 89024 00.09.01
PRESSURIZ. GENERAL TRIP COMMAND EN Terminal strip: TB-DO-02 Terminals: 1(0Vcc), 2(Ch01 - d2)
MOVE
R20 INR_G1 89027
00.09.02
INERGEN RELEASE G1 COMPART. COMMAND EN
MOVE Terminal strip: TB-DO-02 Terminals: 3(0Vcc), 4(Ch02 - d4)
RS12 PRG_PRM 89030
PURGE PANEL PERMISSIVE EN 00.09.03
MOVE
R30 INR_EP 89033 Terminal strip: TB-DO-02 Terminals: 5(0Vcc), 6(Ch03 - d6)
INERGEN REL. SWTCHBRDS COMP. COMMAND EN
MOVE 00.09.04
R40 INR_TR 89036
Terminal strip: TB-DO-02 Terminals: 7(0Vcc), 8(Ch04 - d8)
INERGEN REL. TRANSF. COMPART. COMMAND EN
MOVE
RS10 ACT_TRIP 89039 00.09.05
AT LEAST ONE TRIP PRESENT SIGNALING EN Terminal strip: TB-DO-02 Terminals: 9(0Vcc), 10(Ch05 - d10)
MOVE
RS/3 EP_TRIP 89042
00.09.06
SWTCHBRDS COMPART. TRIP COMMAND EN
MOVE Terminal strip: TB-DO-02 Terminals: 11(0Vcc), 12(Ch06 - d12)
RS/4 TR_TRIP 89045
TRANSF. COMPART. TRIP COMMAND 00.09.07
Module: Digital Outputs
Model: F3331 Terminal strip: TB-DO-02 Terminals: 13(0Vcc), 14(Ch07 - d14)
Cable: Z7138
00.09.08
Rack: Rack00
Position: Slot09 Terminal strip: TB-DO-02 Terminals: 15(0Vcc), 16(Ch08 - d16)

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/89
1 check Martha Cluster MARTHA PLATF PES page 90
revision date name status: LZ based replaced replaced HARDWIRED DIG. OUT. ELAB. (PAGE 1 OF 4)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 90 OF 114 HARDWIRED DIGITAL OUTPUTS ELABORATION (PAGE 2 OF 4) OUTPUTS

OUTPUTS_ENABLED
WRITING OUTPUTS VALUES ENABLED EN
MOVE
RS/5 PP_TRIP 90000 00.10.01
PURGE PANEL TRIP COMMAND EN Terminal strip: TB-DO-03 Terminals: 1(0Vcc), 2(Ch01 - d2)
MOVE
RS13 PES_ALM 90003
00.10.02
HIMA PES SYS. AT LEAST ONE FAULT PRES. SIGNALIZ. EN
MOVE Terminal strip: TB-DO-03 Terminals: 3(0Vcc), 4(Ch02 - d4)
SPARE_DO3_CH3 90006
AVAILABLE DIGITAL OUTPUT (NOT USED) EN 00.10.03
MOVE
SPARE_DO3_CH4 90009 Terminal strip: TB-DO-03 Terminals: 5(0Vcc), 6(Ch03 - d6)
AVAILABLE DIGITAL OUTPUT (NOT USED) EN
MOVE 00.10.04
SOV1 ST_CL_DMP 90012
Terminal strip: TB-DO-03 Morsetti: 7(0Vcc), 8(Ch04 - d8)
STAU ROOM AIR DAMPERS CLOSING EN
MOVE
SOV2 G1_CL_DMP 90015 00.10.05
G1 COMPART. AIR DAMPERS CLOSING EN Terminal strip: TB-DO-03 Terminals: 9(0Vcc), 10(Ch05 - d10)
MOVE
SOV3 EP_CL_DMP 90018
00.10.06
SWTCHBRDS COMPART. AIR DAMPERS CLOSING EN
MOVE Terminal strip: TB-DO-03 Terminals: 11(0Vcc), 12(Ch06 - d12)
SOV4 TR_CL_DMP 90021
TRANSF. COMPART. AIR DAMPERS CLOSING 00.10.07
Module: Digital Outputs
Model: F3331 Terminal strip: TB-DO-03 Terminals: 13(0Vcc), 14(Ch07 - d14)
Cable: Z7138
00.10.08
Rack: Rack00
Position: Slot10 Terminal strip: TB-DO-03 Terminals: 15(0Vcc), 16(Ch08 - d16)

OUTPUTS_ENABLED
WRITING OUTPUTS VALUES ENABLED EN
MOVE
SOV5-6 GE_CL_DMP 90024 00.11.01
MAIN ENTRANCE AIR DAMPERS CLOSING EN Terminal strip: TB-DO-04 Terminals: 1(0Vcc), 2(Ch01 - d2)
MOVE
SPARE_DO4_CH2 90027
00.11.02
AVAILABLE DIGITAL OUTPUT (NOT USED) EN
MOVE Terminal strip: TB-DO-04 Terminals: 3(0Vcc), 4(Ch02 - d4)
SPARE_DO4_CH3 90030
AVAILABLE DIGITAL OUTPUT (NOT USED) EN 00.11.03
MOVE
SPARE_DO4_CH4 90033 Terminal strip: TB-DO-04 Terminals: 5(0Vcc), 6(Ch03 - d6)
AVAILABLE DIGITAL OUTPUT (NOT USED) EN
MOVE 00.11.04
SPARE_DO4_CH5 90036
Terminal strip: TB-DO-04 Terminals: 7(0Vcc), 8(Ch04 - d8)
AVAILABLE DIGITAL OUTPUT (NOT USED) EN
MOVE
SPARE_DO4_CH6 90039 00.11.05
AVAILABLE DIGITAL OUTPUT (NOT USED) EN Terminal strip: TB-DO-04 Terminals: 9(0Vcc), 10(Ch05 - d10)
MOVE
RS14 RACK_PES_OK 90042
00.11.06
HIMA PES RACK FUNCTIONING EN
MOVE Terminal strip: TB-DO-04 Terminals: 11(0Vcc), 12(Ch06 - d12)
RS15 PESSYS_OK 90045
HIMA PES SYSTEM NORMAL FUNCTIONING 00.11.07
Module: Digital Outputs
Model: F3331 Terminal strip: TB-DO-04 Terminals: 13(0Vcc), 14(Ch07 - d14)
Cable: Z7138
Rack: Rack00 00.11.08
Position: Slot11 Terminal strip: TB-DO-04 Terminals: 15(0Vcc), 16(Ch08 - d16)

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/90
1 check Martha Cluster MARTHA PLATF PES page 91
revision date name status: LZ based replaced replaced HARDWIRED DIG. OUT. ELAB. (PAGE 2 OF 4)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 91 OF 114 HARDWIRED DIGITAL OUTPUTS ELABORATION (PAGE 3 OF 4) OUTPUTS

OUTPUTS_ENABLED
WRITING OUTPUTS VALUES ENABLED EN
MOVE
SPARE_DO5_CH1 91000 00.12.01
AVAILABLE DIGITAL OUTPUT (NOT USED) EN Terminal strip: TB-DO-05 Terminals: 1(0Vcc), 2(Ch01 - d2)
MOVE
SPARE_DO5_CH2 91003
00.12.02
AVAILABLE DIGITAL OUTPUT (NOT USED) EN
MOVE Terminal strip: TB-DO-05 Terminals: 3(0Vcc), 4(Ch02 - d4)
SPARE_DO5_CH3 91006
AVAILABLE DIGITAL OUTPUT (NOT USED) EN 00.12.03
MOVE
SPARE_DO5_CH4 91009 Terminal strip: TB-DO-05 Terminals: 5(0Vcc), 6(Ch03 - d6)
AVAILABLE DIGITAL OUTPUT (NOT USED) EN
MOVE 00.12.04
SPARE_DO5_CH5 91012
Terminal strip: TB-DO-05 Terminals: 7(0Vcc), 8(Ch04 - d8)
AVAILABLE DIGITAL OUTPUT (NOT USED) EN
MOVE
SPARE_DO5_CH6 91015 00.12.05
AVAILABLE DIGITAL OUTPUT (NOT USED) EN Terminal strip: TB-DO-05 Terminals: 9(0Vcc), 10(Ch05 - d10)
MOVE
SPARE_DO5_CH7 91018
00.12.06
AVAILABLE DIGITAL OUTPUT (NOT USED) EN
MOVE Terminal strip: TB-DO-05 Terminals: 11(0Vcc), 12(Ch06 - d12)
SPARE_DO5_CH8 91021
AVAILABLE DIGITAL OUTPUT (NOT USED) 00.12.07
Module: Digital Outputs
Model: F3331 Terminal strip: TB-DO-05 Terminals: 13(0Vcc), 14(Ch07 - d14)
Cable: Z7138
Rack: Rack00 00.12.08
Position: Slot12 Terminal strip: TB-DO-05 Terminals: 15(0Vcc), 16(Ch08 - d16)

OUTPUTS_ENABLED
WRITING OUTPUTS VALUES ENABLED EN
MOVE
SPARE_DO6_CH1 91024 00.13.01
AVAILABLE DIGITAL OUTPUT (NOT USED) EN Terminal strip: TB-DO-06 Terminals: 1(0Vcc), 2(Ch01 - d2)
MOVE
SPARE_DO6_CH2 91027
00.13.02
AVAILABLE DIGITAL OUTPUT (NOT USED) EN
MOVE Terminal strip: TB-DO-06 Terminals: 3(0Vcc), 4(Ch02 - d4)
SPARE_DO6_CH3 91030
AVAILABLE DIGITAL OUTPUT (NOT USED) EN 00.13.03
MOVE
SPARE_DO6_CH4 91033 Terminal strip: TB-DO-06 Terminals: 5(0Vcc), 6(Ch03 - d6)
AVAILABLE DIGITAL OUTPUT (NOT USED) EN
MOVE 00.13.04
SPARE_DO6_CH5 91036
Terminal strip: TB-DO-06 Terminals: 7(0Vcc), 8(Ch04 - d8)
AVAILABLE DIGITAL OUTPUT (NOT USED) EN
MOVE
SPARE_DO6_CH6 91039 00.13.05
AVAILABLE DIGITAL OUTPUT (NOT USED) EN Terminal strip: TB-DO-06 Terminals: 9(0Vcc), 10(Ch05 - d10)
MOVE
SPARE_DO6_CH7 91042
00.13.06
AVAILABLE DIGITAL OUTPUT (NOT USED) EN
MOVE Terminal strip: TB-DO-06 Terminals: 11(0Vcc), 12(Ch06 - d12)
SPARE_DO6_CH8 91045
AVAILABLE DIGITAL OUTPUT (NOT USED) 00.13.07
Module: Digital Outputs
Model: F3331 Terminal strip: TB-DO-06 Terminals: 13(0Vcc), 14(Ch07 - d14)
Cable: Z7138
Rack: Rack00 00.13.08
Position: Slot13 Terminal strip: TB-DO-06 Terminals: 15(0Vcc), 16(Ch08 - d16)

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/91
1 check Martha Cluster MARTHA PLATF PES page 92
revision date name status: LZ based replaced replaced HARDWIRED DIG. OUT. ELAB. (PAGE 3 OF 4)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

INPUTS PAGE 92 OF 114 HARDWIRED DIGITAL OUTPUTS ELABORATION (PAGE 4 OF 4) OUTPUTS


AVAILABLE EMPTY PAGE

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/92
1 check Martha Cluster MARTHA PLATF PES page 93
revision date name status: LZ based replaced replaced HARDWIRED DIG. OUT. ELAB. (PAGE 4 OF 4)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

CAUSES PAGE 93 OF 114 TRIP LOGICS VISUALIZATION (PAGE 1 OF 22) EFFECT


AT LEAST ONE TRIP PRESENT SIGNALING

ST_TRIP
STAU ROOM TRIP CONDITION PRESENT

G1_TRIP
G1 COMPART. TRIP CONDITION PRESENT

EP_TRIP
SWTCHBRDS COMPART. TRIP CONDITION PRESENT

TR_TRIP
TRANSF. COMPART. TRIP CONDITION PRESENT

ST_CL_DMP
STAU ROOM AIR DAMPERS CLOSING CONDIT. PRES.

G1_CL_DMP
G1 COMPART. AIR DAMPERS CLOSING CONDIT. PRES.

EP_CL_DMP
SWTCHBRDS COMPART. AIR DAMPERS CLOSING CONDIT. PRES.

TR_CL_DMP
TRANSF. COMPART. AIR DAMPERS CLOSING CONDIT. PRES. RS10 ACT_TRIP
>=1
AT LEAST ONE TRIP PRESENT SIGNALING
GE_CL_DMP
MAIN ENTRANCE AIR DAMPERS CLOSING CONDIT. PRES.

GEN_TRIP
PLATFORM GENERAL TRIP CONDITION PRESENT

PP_TRIP
PURGE PANEL TRIP CONDITION PRESENT

PRES_TRIP
PRESSURIZ. GENERAL TRIP CONDITION PRESENT

INR_ST
INERGEN RELEASE STAU ROOM CONDITION PRESENT

INR_G1
INERGEN RELEASE G1 COMPART. CONDITION PRESENT

INR_EP
INERGEN REL. SWTCHBRDS COMPART. CONDIT. PRES.

INR_TR
INERGEN REL. TRANSF. COMPART. CONDIT. PRES.

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/93
1 check Martha Cluster MARTHA PLATF PES page 94
revision date name status: LZ based replaced replaced TRIP LOGICS VISUALIZAT. (PAGE 1 OF 22)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

CAUSES PAGE 94 OF 114 TRIP LOGICS VISUALIZATION (PAGE 2 OF 22) EFFECT


STAU ROOM TRIP COMMAND CAUSES-EFFECT

RET2.3 ELETRP_INC
ELECT. TRIPS SELECT. INCLUDED POSIT.

RB_A/B_REM_TRP
PLATFORM EMERGENCY TRIP REMOTE COMMAND

RPA.2 PLT_ABD
PLATF. ABAND. PUSH-BUTTONS NOT ACTIV.

011S.2 SMOKE_ALM
SMOKE ALARM STAU ROOM NOT PRESENT
012S.2 SMOKE_FAIL 2oo2 VOTING
SMOKE FAIL. STAU ROOM NOT PRESENT (two out of two) 011-2S.2 SMK_TRP TRIP LOGIC RS/1 ST_TRIP
TRIP LOGIC STAU ROOM SMOKE TRIP NOT PRESENT PROCESSING STAU ROOM TRIP COMMAND
051S.1 SMOKE_ALM
PROCESSING
SMOKE ALARM COMMON LINE NOT PRESENT
052S.1 SMOKE_FAIL
SMOKE FAIL. COMMON LINE NOT PRESENT

011F.2 FLAME_ALM
FLAME ALARM STAU ROOM NOT PRESENT
102E.2 EXPG_ALM
EXPL. GAS ALARM STAU ROOM NOT PRES.
R13.2 INR_REL_ST
INERGEN RELEASE STAU ROOM NOT OCCURR.

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/94
1 check Martha Cluster MARTHA PLATF PES page 95
revision date name status: LZ based replaced replaced TRIP LOGICS VISUALIZAT. (PAGE 2 OF 22)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

CAUSES PAGE 95 OF 114 TRIP LOGICS VISUALIZATION (PAGE 3 OF 22) EFFECT


G1 COMPARTMENT TRIP COMMAND CAUSES-EFFECT

RET2.3 ELETRP_INC
ELECT. TRIPS SELECT. INCLUDED POSIT.
RB_A/B_REM_TRP
PLATFORM EMERGENCY TRIP REMOTE COMMAND
RPA.2 PLT_ABD
021S.2 SMOKE_ALM PLATF. ABAND. PUSH-BUTTONS NOT ACTIV.
SMOKE ALARM G1 COMPART. NOT PRESENT
022S.2 SMOKE_FAIL 2oo2 VOTING
SMOKE FAIL. G1 COMPART. NOT PRESENT (two out of two) 021-2S.2 SMK_TRP
TRIP LOGIC G1 COMPART. SMOKE TRIP NOT PRESENT
051S.1 SMOKE_ALM
PROCESSING
SMOKE ALARM COMMON LINE NOT PRESENT
052S.1 SMOKE_FAIL
012F.2 FLAME_ALM
SMOKE FAIL. COMMON LINE NOT PRESENT
FLAME ALARM G1 COMPART. NOT PRESENT
112E.2 EXPG_ALM
EXPL. GAS ALARM G1 COMPART. NOT PRES.
R23.2 INR_REL_G1
031S.2 SMOKE_ALM INERGEN RELEASE G1 COMPART. NOT OCCURR.
SMOKE ALARM SWTCHBRDS COMP. NOT PRESENT
032S.2 SMOKE_FAIL 2oo2 VOTING
SMOKE FAIL. SWTCHBRDS COMP. NOT PRESENT (two out of two) 031-2S.2 SMK_TRP TRIP LOGIC RS/2 G1_TRIP
TRIP LOGIC SWTCHBRDS COMPART. SMOKE TRIP NOT PRESENT PROCESSING G1 COMPART. TRIP COMMAND
051S.1 SMOKE_ALM
PROCESSING
SMOKE ALARM COMMON LINE NOT PRESENT
052S.1 SMOKE_FAIL
013F.2 FLAME_ALM
SMOKE FAIL. COMMON LINE NOT PRESENT
FLAME ALARM SWTCHBRDS COMP. NOT PRESENT
122E.2 EXPG_ALM
EXPL. GAS ALARM SWTCHBRDS COMP. NOT PRESENT
R33.2 INR_REL_EP
011S.2 SMOKE_ALM INERGEN RELEASE SWTCHBRDS COMPART. NOT OCCURR.
SMOKE ALARM STAU ROOM NOT PRESENT
012S.2 SMOKE_FAIL 2oo2 VOTING
SMOKE FAIL. STAU ROOM NOT PRESENT (two out of two) 011-2S.2 SMK_TRP
TRIP LOGIC STAU ROOM SMOKE TRIP NOT PRESENT
051S.1 SMOKE_ALM
PROCESSING
SMOKE ALARM COMMON LINE NOT PRESENT
052S.1 SMOKE_FAIL
011F.2 FLAME_ALM
SMOKE FAIL. COMMON LINE NOT PRESENT
FLAME ALARM STAU ROOM NOT PRESENT
102E.2 EXPG_ALM
EXPL. GAS ALARM STAU ROOM NOT PRES.
R13.2 INR_REL_ST
INERGEN RELEASE STAU ROOM NOT OCCURR.

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/95
1 check Martha Cluster MARTHA PLATF PES page 96
revision date name status: LZ based replaced replaced TRIP LOGICS VISUALIZAT. (PAGE 3 OF 22)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

CAUSES PAGE 96 OF 114 TRIP LOGICS VISUALIZATION (PAGE 4 OF 22) EFFECT


SWITCHBOARDS COMPARTMENT TRIP COMMAND CAUSES-EFFECT

RET2.3 ELETRP_INC
ELECT. TRIPS SELECT. INCLUDED POSIT.

RB_A/B_REM_TRP
PLATFORM EMERGENCY TRIP REMOTE COMMAND

RPA.2 PLT_ABD
PLATF. ABAND. PUSH-BUTTONS NOT ACTIV.

011S.2 SMOKE_ALM
SMOKE ALARM STAU ROOM NOT PRESENT
012S.2 SMOKE_FAIL 2oo2 VOTING
SMOKE FAIL. STAU ROOM NOT PRESENT (two out of two) 011-2S.2 SMK_TRP
TRIP LOGIC STAU ROOM SMOKE TRIP NOT PRESENT
051S.1 SMOKE_ALM
PROCESSING
SMOKE ALARM COMMON LINE NOT PRESENT
052S.1 SMOKE_FAIL
SMOKE FAIL. COMMON LINE NOT PRESENT

011F.2 FLAME_ALM
FLAME ALARM STAU ROOM NOT PRESENT
102E.2 EXPG_ALM RS/3 EP_TRIP
TRIP LOGIC
EXPL. GAS ALARM STAU ROOM NOT PRES. SWTCHBRDS COMPART. TRIP
PROCESSING COMMAND
R13.2 INR_REL_ST
INERGEN RELEASE STAU ROOM NOT OCCURR.

031S.2 SMOKE_ALM
SMOKE ALARM SWTCHBRDS COMP. NOT PRESENT
032S.2 SMOKE_FAIL 2oo2 VOTING
SMOKE FAIL. SWTCHBRDS COMP. NOT PRESENT (two out of two) 031-2S.2 SMK_TRP
TRIP LOGIC SWTCHBRDS COMPART. SMOKE TRIP NOT PRESENT
051S.1 SMOKE_ALM
PROCESSING
SMOKE ALARM COMMON LINE NOT PRESENT
052S.1 SMOKE_FAIL
SMOKE FAIL. COMMON LINE NOT PRESENT

013F.2 FLAME_ALM
FLAME ALARM SWTCHBRDS COMP. NOT PRESENT
122E.2 EXPG_ALM
EXPL. GAS ALARM SWTCHBRDS COMP. NOT PRESENT
R33.2 INR_REL_EP
INERGEN RELEASE SWTCHBRDS COMPART. NOT OCCURR.

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/96
1 check Martha Cluster MARTHA PLATF PES page 97
revision date name status: LZ based replaced replaced TRIP LOGICS VISUALIZAT. (PAGE 4 OF 22)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

CAUSES PAGE 97 OF 114 TRIP LOGICS VISUALIZATION (PAGE 5 OF 22) EFFECT


TRANSFORMER COMPARTMENT TRIP COMMAND CAUSES-EFFECT

RET2.3 ELETRP_INC
ELECT. TRIPS SELECT. INCLUDED POSIT.

RB_A/B_REM_TRP
PLATFORM EMERGENCY TRIP REMOTE COMMAND

RPA.2 PLT_ABD
PLATF. ABAND. PUSH-BUTTONS NOT ACTIV.

041S.2 SMOKE_ALM
SMOKE ALARM TRANSF. COMPART. NOT PRESENT
042S.2 SMOKE_FAIL 2oo2 VOTING
SMOKE FAIL. TRANSF. COMPART. NOT PRESENT (two out of two) 041-2S.2 SMK_TRP
TRIP LOGIC TRANSF. COMPART. SMOKE TRIP NOT PRESENT
051S.1 SMOKE_ALM
PROCESSING
SMOKE ALARM COMMON LINE NOT PRESENT
052S.1 SMOKE_FAIL
SMOKE FAIL. COMMON LINE NOT PRESENT

014F.2 FLAME_ALM
FLAME ALARM TRANSF. COMPART. NOT PRESENT
132E.2 EXPG_ALM RS/4 TR_TRIP
TRIP LOGIC
EXPL. GAS ALARM TRANSF. COMP. NOT PRESENT TRANSF. COMPART. TRIP COMMAND
PROCESSING
R43.2 INR_REL_TR
INERGEN RELEASE TRANSF. COMPART. NOT OCCURR.

031S.2 SMOKE_ALM
SMOKE ALARM SWTCHBRDS COMP. NOT PRESENT
032S.2 SMOKE_FAIL 2oo2 VOTING
SMOKE FAIL. SWTCHBRDS COMP. NOT PRESENT (two out of two) 031-2S.2 SMK_TRP
TRIP LOGIC SWTCHBRDS COMPART. SMOKE TRIP NOT PRESENT
051S.1 SMOKE_ALM
PROCESSING
SMOKE ALARM COMMON LINE NOT PRESENT
052S.1 SMOKE_FAIL
SMOKE FAIL. COMMON LINE NOT PRESENT

013F.2 FLAME_ALM
FLAME ALARM SWTCHBRDS COMP. NOT PRESENT
122E.2 EXPG_ALM
EXPL. GAS ALARM SWTCHBRDS COMP. NOT PRESENT
R33.2 INR_REL_EP
INERGEN RELEASE SWTCHBRDS COMPART. NOT OCCURR.

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/97
1 check Martha Cluster MARTHA PLATF PES page 98
revision date name status: LZ based replaced replaced TRIP LOGICS VISUALIZAT. (PAGE 5 OF 22)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

CAUSES PAGE 98 OF 114 TRIP LOGICS VISUALIZATION (PAGE 6 OF 22) EFFECT


STAU ROOM AIR DAMPERS CLOSING CAUSES-EFFECT

RET2.3 ELETRP_INC
ELECT. TRIPS SELECT. INCLUDED POSIT.

RB_A/B_REM_TRP
PLATFORM EMERGENCY TRIP REMOTE COMMAND

RPA.2 PLT_ABD
PLATF. ABAND. PUSH-BUTTONS NOT ACTIV.

011S.2 SMOKE_ALM
SMOKE ALARM STAU ROOM NOT PRESENT
012S.2 SMOKE_FAIL 2oo2 VOTING
SMOKE FAIL. STAU ROOM NOT PRESENT (two out of two) 011-2S.2 SMK_TRP
TRIP LOGIC STAU ROOM SMOKE TRIP NOT PRESENT
051S.1 SMOKE_ALM
PROCESSING
SMOKE ALARM COMMON LINE NOT PRESENT
052S.1 SMOKE_FAIL
SMOKE FAIL. COMMON LINE NOT PRESENT

011F.2 FLAME_ALM
FLAME ALARM STAU ROOM NOT PRESENT
102E.2 EXPG_ALM SOV1 ST_CL_DMP
TRIP LOGIC
EXPL. GAS ALARM STAU ROOM NOT PRES. STAU ROOM AIR DAMPERS CLOSING
PROCESSING
R13.2 INR_REL_ST
INERGEN RELEASE STAU ROOM NOT OCCURR.

031S.2 SMOKE_ALM
SMOKE ALARM SWTCHBRDS COMP. NOT PRESENT
032S.2 SMOKE_FAIL 2oo2 VOTING
SMOKE FAIL. SWTCHBRDS COMP. NOT PRESENT (two out of two) 031-2S.2 SMK_TRP
TRIP LOGIC SWTCHBRDS COMPART. SMOKE TRIP NOT PRESENT
051S.1 SMOKE_ALM
PROCESSING
SMOKE ALARM COMMON LINE NOT PRESENT
052S.1 SMOKE_FAIL
SMOKE FAIL. COMMON LINE NOT PRESENT

013F.2 FLAME_ALM
FLAME ALARM SWTCHBRDS COMP. NOT PRESENT
122E.2 EXPG_ALM
EXPL. GAS ALARM SWTCHBRDS COMP. NOT PRESENT
R33.2 INR_REL_EP
INERGEN RELEASE SWTCHBRDS COMPART. NOT OCCURR.

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/98
1 check Martha Cluster MARTHA PLATF PES page 99
revision date name status: LZ based replaced replaced TRIP LOGICS VISUALIZAT. (PAGE 6 OF 22)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

CAUSES PAGE 99 OF 114 TRIP LOGICS VISUALIZATION (PAGE 7 OF 22) EFFECT


G1 COMPARTMENT AIR DAMPERS CLOSING CAUSES-EFFECT

RET2.3 ELETRP_INC
ELECT. TRIPS SELECT. INCLUDED POSIT.
RB_A/B_REM_TRP
PLATFORM EMERGENCY TRIP REMOTE COMMAND
RPA.2 PLT_ABD
021S.2 SMOKE_ALM PLATF. ABAND. PUSH-BUTTONS NOT ACTIV.
SMOKE ALARM G1 COMPART. NOT PRESENT
022S.2 SMOKE_FAIL 2oo2 VOTING
SMOKE FAIL. G1 COMPART. NOT PRESENT (two out of two) 021-2S.2 SMK_TRP
TRIP LOGIC G1 COMPART. SMOKE TRIP NOT PRESENT
051S.1 SMOKE_ALM
PROCESSING
SMOKE ALARM COMMON LINE NOT PRESENT
052S.1 SMOKE_FAIL
012F.2 FLAME_ALM
SMOKE FAIL. COMMON LINE NOT PRESENT
FLAME ALARM G1 COMPART. NOT PRESENT
112E.2 EXPG_ALM
EXPL. GAS ALARM G1 COMPART. NOT PRES.
R23.2 INR_REL_G1
031S.2 SMOKE_ALM INERGEN RELEASE G1 COMPART. NOT OCCURR.
SMOKE ALARM SWTCHBRDS COMP. NOT PRESENT
032S.2 SMOKE_FAIL 2oo2 VOTING
SMOKE FAIL. SWTCHBRDS COMP. NOT PRESENT (two out of two) 031-2S.2 SMK_TRP TRIP LOGIC SOV2 G1_CL_DMP
TRIP LOGIC SWTCHBRDS COMPART. SMOKE TRIP NOT PRESENT PROCESSING G1 COMPART. AIR DAMPERS CLOSING
051S.1 SMOKE_ALM
PROCESSING
SMOKE ALARM COMMON LINE NOT PRESENT
052S.1 SMOKE_FAIL
013F.2 FLAME_ALM
SMOKE FAIL. COMMON LINE NOT PRESENT
FLAME ALARM SWTCHBRDS COMP. NOT PRESENT
122E.2 EXPG_ALM
EXPL. GAS ALARM SWTCHBRDS COMP. NOT PRESENT
R33.2 INR_REL_EP
011S.2 SMOKE_ALM INERGEN RELEASE SWTCHBRDS COMPART. NOT OCCURR.
SMOKE ALARM STAU ROOM NOT PRESENT
012S.2 SMOKE_FAIL 2oo2 VOTING
SMOKE FAIL. STAU ROOM NOT PRESENT (two out of two) 011-2S.2 SMK_TRP
TRIP LOGIC STAU ROOM SMOKE TRIP NOT PRESENT
051S.1 SMOKE_ALM
PROCESSING
SMOKE ALARM COMMON LINE NOT PRESENT
052S.1 SMOKE_FAIL
011F.2 FLAME_ALM
SMOKE FAIL. COMMON LINE NOT PRESENT
FLAME ALARM STAU ROOM NOT PRESENT
102E.2 EXPG_ALM
EXPL. GAS ALARM STAU ROOM NOT PRES.
R13.2 INR_REL_ST
INERGEN RELEASE STAU ROOM NOT OCCURR.

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/99
1 check Martha Cluster MARTHA PLATF PES page 100
revision date name status: LZ based replaced replaced TRIP LOGICS VISUALIZAT. (PAGE 7 OF 22)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

CAUSES PAGE 100 OF 114 TRIP LOGICS VISUALIZATION (PAGE 8 OF 22) EFFECT
SWITCHBOARDS COMPARTMENT AIR DAMPERS CLOSING CAUSES-EFFECT

RET2.3 ELETRP_INC
ELECT. TRIPS SELECT. INCLUDED POSIT.

RB_A/B_REM_TRP
PLATFORM EMERGENCY TRIP REMOTE COMMAND

RPA.2 PLT_ABD
PLATF. ABAND. PUSH-BUTTONS NOT ACTIV.

011S.2 SMOKE_ALM
SMOKE ALARM STAU ROOM NOT PRESENT
012S.2 SMOKE_FAIL 2oo2 VOTING
SMOKE FAIL. STAU ROOM NOT PRESENT (two out of two) 011-2S.2 SMK_TRP
TRIP LOGIC STAU ROOM SMOKE TRIP NOT PRESENT
051S.1 SMOKE_ALM
PROCESSING
SMOKE ALARM COMMON LINE NOT PRESENT
052S.1 SMOKE_FAIL
SMOKE FAIL. COMMON LINE NOT PRESENT

011F.2 FLAME_ALM
FLAME ALARM STAU ROOM NOT PRESENT
102E.2 EXPG_ALM SOV3 EP_CL_DMP
TRIP LOGIC
EXPL. GAS ALARM STAU ROOM NOT PRES. SWTCHBRDS COMPART. AIR
PROCESSING DAMPERS CLOSING
R13.2 INR_REL_ST
INERGEN RELEASE STAU ROOM NOT OCCURR.

031S.2 SMOKE_ALM
SMOKE ALARM SWTCHBRDS COMP. NOT PRESENT
032S.2 SMOKE_FAIL 2oo2 VOTING
SMOKE FAIL. SWTCHBRDS COMP. NOT PRESENT (two out of two) 031-2S.2 SMK_TRP
TRIP LOGIC SWTCHBRDS COMPART. SMOKE TRIP NOT PRESENT
051S.1 SMOKE_ALM
PROCESSING
SMOKE ALARM COMMON LINE NOT PRESENT
052S.1 SMOKE_FAIL
SMOKE FAIL. COMMON LINE NOT PRESENT

013F.2 FLAME_ALM
FLAME ALARM SWTCHBRDS COMP. NOT PRESENT
122E.2 EXPG_ALM
EXPL. GAS ALARM SWTCHBRDS COMP. NOT PRESENT
R33.2 INR_REL_EP
INERGEN RELEASE SWTCHBRDS COMPART. NOT OCCURR.

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/100
1 check Martha Cluster MARTHA PLATF PES page 101
revision date name status: LZ based replaced replaced TRIP LOGICS VISUALIZAT. (PAGE 8 OF 22)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

CAUSES PAGE 101 OF 114 TRIP LOGICS VISUALIZATION (PAGE 9 OF 22) EFFECT
TRANSFORMER COMPARTMENT AIR DAMPERS CLOSING CAUSES-EFFECT

RET2.3 ELETRP_INC
ELECT. TRIPS SELECT. INCLUDED POSIT.
RB_A/B_REM_TRP
PLATFORM EMERGENCY TRIP REMOTE COMMAND
RPA.2 PLT_ABD
011S.2 SMOKE_ALM PLATF. ABAND. PUSH-BUTTONS NOT ACTIV.
SMOKE ALARM STAU ROOM NOT PRESENT
012S.2 SMOKE_FAIL 2oo2 VOTING
SMOKE FAIL. STAU ROOM NOT PRESENT (two out of two) 011-2S.2 SMK_TRP
TRIP LOGIC STAU ROOM SMOKE TRIP NOT PRESENT
051S.1 SMOKE_ALM
PROCESSING
SMOKE ALARM COMMON LINE NOT PRESENT
052S.1 SMOKE_FAIL
011F.2 FLAME_ALM
SMOKE FAIL. COMMON LINE NOT PRESENT
FLAME ALARM STAU ROOM NOT PRESENT
102E.2 EXPG_ALM
EXPL. GAS ALARM STAU ROOM NOT PRES.
R13.2 INR_REL_ST
041S.2 SMOKE_ALM INERGEN RELEASE STAU ROOM NOT OCCURR.
SMOKE ALARM TRANSF. COMPART. NOT PRESENT
042S.2 SMOKE_FAIL 2oo2 VOTING SOV4 TR_CL_DMP
SMOKE FAIL. TRANSF. COMPART. NOT PRESENT (two out of two) 041-2S.2 SMK_TRP TRIP LOGIC
TRANSF. COMPART. AIR
TRIP LOGIC TRANSF. COMPART. SMOKE TRIP NOT PRESENT PROCESSING DAMPERS CLOSING
051S.1 SMOKE_ALM
PROCESSING
SMOKE ALARM COMMON LINE NOT PRESENT
052S.1 SMOKE_FAIL
014F.2 FLAME_ALM
SMOKE FAIL. COMMON LINE NOT PRESENT
FLAME ALARM TRANSF. COMPART. NOT PRESENT
132E.2 EXPG_ALM
EXPL. GAS ALARM TRANSF. COMP. NOT PRESENT
R43.2 INR_REL_TR
031S.2 SMOKE_ALM INERGEN RELEASE TRANSF. COMPART. NOT OCCURR.
SMOKE ALARM SWTCHBRDS COMP. NOT PRESENT
032S.2 SMOKE_FAIL 2oo2 VOTING
SMOKE FAIL. SWTCHBRDS COMP. NOT PRESENT (two out of two) 031-2S.2 SMK_TRP
TRIP LOGIC SWTCHBRDS COMPART. SMOKE TRIP NOT PRESENT
051S.1 SMOKE_ALM
PROCESSING
SMOKE ALARM COMMON LINE NOT PRESENT
052S.1 SMOKE_FAIL
013F.2 FLAME_ALM
SMOKE FAIL. COMMON LINE NOT PRESENT
FLAME ALARM SWTCHBRDS COMP. NOT PRESENT
122E.2 EXPG_ALM
EXPL. GAS ALARM SWTCHBRDS COMP. NOT PRESENT
R33.2 INR_REL_EP
INERGEN RELEASE SWTCHBRDS COMPART. NOT OCCURR.

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/101
1 check Martha Cluster MARTHA PLATF PES page 102
revision date name status: LZ based replaced replaced TRIP LOGICS VISUALIZAT. (PAGE 9 OF 22)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

CAUSES PAGE 102 OF 114 TRIP LOGICS VISUALIZATION (PAGE 10 OF 22) EFFECT
MAIN ENTRANCE AIR DAMPERS CLOSING CAUSES-EFFECT

RET2.3 ELETRP_INC
ELECT. TRIPS SELECT. INCLUDED POSIT.

RB_A/B_REM_TRP
PLATFORM EMERGENCY TRIP REMOTE COMMAND

RPA.2 PLT_ABD
PLATF. ABAND. PUSH-BUTTONS NOT ACTIV.

011S.2 SMOKE_ALM
SMOKE ALARM STAU ROOM NOT PRESENT
012S.2 SMOKE_FAIL 2oo2 VOTING
SMOKE FAIL. STAU ROOM NOT PRESENT (two out of two) 011-2S.2 SMK_TRP
TRIP LOGIC STAU ROOM SMOKE TRIP NOT PRESENT
051S.1 SMOKE_ALM
PROCESSING
SMOKE ALARM COMMON LINE NOT PRESENT
052S.1 SMOKE_FAIL
SMOKE FAIL. COMMON LINE NOT PRESENT

011F.2 FLAME_ALM
FLAME ALARM STAU ROOM NOT PRESENT
SOV5-6 GE_CL_DMP
102E.2 EXPG_ALM TRIP LOGIC
MAIN ENTRANCE AIR DAMPERS
EXPL. GAS ALARM STAU ROOM NOT PRES. PROCESSING CLOSING
R13.2 INR_REL_ST
INERGEN RELEASE STAU ROOM NOT OCCURR.

031S.2 SMOKE_ALM
SMOKE ALARM SWTCHBRDS COMP. NOT PRESENT
032S.2 SMOKE_FAIL 2oo2 VOTING
SMOKE FAIL. SWTCHBRDS COMP. NOT PRESENT (two out of two) 031-2S.2 SMK_TRP
TRIP LOGIC SWTCHBRDS COMPART. SMOKE TRIP NOT PRESENT
051S.1 SMOKE_ALM
PROCESSING
SMOKE ALARM COMMON LINE NOT PRESENT
052S.1 SMOKE_FAIL
SMOKE FAIL. COMMON LINE NOT PRESENT

013F.2 FLAME_ALM
FLAME ALARM SWTCHBRDS COMP. NOT PRESENT
122E.2 EXPG_ALM
EXPL. GAS ALARM SWTCHBRDS COMP. NOT PRESENT
R33.2 INR_REL_EP
INERGEN RELEASE SWTCHBRDS COMPART. NOT OCCURR.

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/102
1 check Martha Cluster MARTHA PLATF PES page 103
revision date name status: LZ based replaced replaced TRIP LOGICS VISUALIZAT. (PAGE 10 OF 22)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

CAUSES PAGE 103 OF 114 TRIP LOGICS VISUALIZATION (PAGE 11 OF 22) EFFECT
PLATFORM GENERAL TRIP COMMAND CAUSES-EFFECT

RET2.3 ELETRP_INC
ELECT. TRIPS SELECT. INCLUDED POSIT.

RB_A/B_REM_TRP
PLATFORM EMERGENCY TRIP REMOTE COMMAND

RPA.2 PLT_ABD
PLATF. ABAND. PUSH-BUTTONS NOT ACTIV.

FUPLGNET
PROD. EMERG. TRIP FROM FUSIB. PLUGS NOT ACTIV.

011S.2 SMOKE_ALM
SMOKE ALARM STAU ROOM NOT PRESENT
TRIP LOGIC SOV7 GEN_TRIP
012S.2 SMOKE_FAIL 2oo2 VOTING PROCESSING PLATFORM GENERAL TRIP COMMAND
SMOKE FAIL. STAU ROOM NOT PRESENT (two out of two) 011-2S.2 SMK_TRP
TRIP LOGIC STAU ROOM SMOKE TRIP NOT PRESENT
051S.1 SMOKE_ALM
PROCESSING
SMOKE ALARM COMMON LINE NOT PRESENT
052S.1 SMOKE_FAIL
SMOKE FAIL. COMMON LINE NOT PRESENT

011F.2 FLAME_ALM
FLAME ALARM STAU ROOM NOT PRESENT
102E.2 EXPG_ALM
EXPL. GAS ALARM STAU ROOM NOT PRES.
R13.2 INR_REL_ST
INERGEN RELEASE STAU ROOM NOT OCCURR.

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/103
1 check Martha Cluster MARTHA PLATF PES page 104
revision date name status: LZ based replaced replaced TRIP LOGICS VISUALIZAT. (PAGE 11 OF 22)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

CAUSES PAGE 104 OF 114 TRIP LOGICS VISUALIZATION (PAGE 12 OF 22) EFFECT
PURGE PANEL TRIP COMMAND CAUSES-EFFECT

RET2.3 ELETRP_INC
ELECT. TRIPS SELECT. INCLUDED POSIT.

RB_A/B_REM_TRP
PLATFORM EMERGENCY TRIP REMOTE COMMAND

RPA.2 PLT_ABD
PLATF. ABAND. PUSH-BUTTONS NOT ACTIV.

011S.2 SMOKE_ALM
SMOKE ALARM STAU ROOM NOT PRESENT
012S.2 SMOKE_FAIL 2oo2 VOTING
SMOKE FAIL. STAU ROOM NOT PRESENT (two out of two) 011-2S.2 SMK_TRP
TRIP LOGIC STAU ROOM SMOKE TRIP NOT PRESENT
051S.1 SMOKE_ALM
PROCESSING
SMOKE ALARM COMMON LINE NOT PRESENT
052S.1 SMOKE_FAIL
SMOKE FAIL. COMMON LINE NOT PRESENT

011F.2 FLAME_ALM TRIP LOGIC RS/5 PP_TRIP


FLAME ALARM STAU ROOM NOT PRESENT PROCESSING PURGE PANEL TRIP COMMAND
102E.2 EXPG_ALM
EXPL. GAS ALARM STAU ROOM NOT PRES.
R13.2 INR_REL_ST
INERGEN RELEASE STAU ROOM NOT OCCURR.

031S.2 SMOKE_ALM
SMOKE ALARM SWTCHBRDS COMP. NOT PRESENT
032S.2 SMOKE_FAIL 2oo2 VOTING
SMOKE FAIL. SWTCHBRDS COMP. NOT PRESENT (two out of two) 031-2S.2 SMK_TRP
TRIP LOGIC SWTCHBRDS COMPART. SMOKE TRIP NOT PRESENT
051S.1 SMOKE_ALM
PROCESSING
SMOKE ALARM COMMON LINE NOT PRESENT
052S.1 SMOKE_FAIL
SMOKE FAIL. COMMON LINE NOT PRESENT

013F.2 FLAME_ALM
FLAME ALARM SWTCHBRDS COMP. NOT PRESENT
122E.2 EXPG_ALM
EXPL. GAS ALARM SWTCHBRDS COMP. NOT PRESENT
R33.2 INR_REL_EP
INERGEN RELEASE SWTCHBRDS COMPART. NOT OCCURR.

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/104
1 check Martha Cluster MARTHA PLATF PES page 105
revision date name status: LZ based replaced replaced TRIP LOGICS VISUALIZAT. (PAGE 12 OF 22)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

CAUSES PAGE 105 OF 114 TRIP LOGICS VISUALIZATION (PAGE 13 OF 22) EFFECT
PRESSURIZATION GENERAL TRIP COMMAND CAUSES-EFFECT

RET2.3 ELETRP_INC
ELECT. TRIPS SELECT. INCLUDED POSIT.

102E.2 EXPG_ALM
EXPL. GAS ALARM STAU ROOM NOT PRES.

112E.2 EXPG_ALM TRIP LOGIC RS11 PRES_TRIP


EXPL. GAS ALARM G1 COMPART. NOT PRES. PROCESSING PRESSURIZ. GENERAL TRIP COMMAND

122E.2 EXPG_ALM
EXPL. GAS ALARM SWTCHBRDS COMP. NOT PRESENT

132E.2 EXPG_ALM
EXPL. GAS ALARM TRANSF. COMP. NOT PRESENT

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/105
1 check Martha Cluster MARTHA PLATF PES page 106
revision date name status: LZ based replaced replaced TRIP LOGICS VISUALIZAT. (PAGE 13 OF 22)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

CAUSES PAGE 106 OF 114 TRIP LOGICS VISUALIZATION (PAGE 14 OF 22) EFFECT
STAU ROOM INERGEN RELEASE COMMAND (DELAYED) CAUSES-EFFECT

RET2.3 ELETRP_INC
ELECT. TRIPS SELECT. INCLUDED POSIT.

011S.2 SMOKE_ALM
SMOKE ALARM STAU ROOM NOT PRESENT
012S.2 SMOKE_FAIL 2oo2 VOTING
SMOKE FAIL. STAU ROOM NOT PRESENT (two out of two) 011-2S.2 INR_REL
TRIP LOGIC R10 INR_ST
TRIP LOGIC STAU ROOM INERGEN RELEASE NOT PRESENT PROCESSING INERGEN RELEASE STAU ROOM COMMAND
051S.1 SMOKE_ALM
PROCESSING
SMOKE ALARM COMMON LINE NOT PRESENT
052S.1 SMOKE_FAIL
SMOKE FAIL. COMMON LINE NOT PRESENT

011F.2 FLAME_ALM
FLAME ALARM STAU ROOM NOT PRESENT

NOTE: When both smoke sensors are in failure, the inergen release condition is not activated.

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/106
1 check Martha Cluster MARTHA PLATF PES page 107
revision date name status: LZ based replaced replaced TRIP LOGICS VISUALIZAT. (PAGE 14 OF 22)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

CAUSES PAGE 107 OF 114 TRIP LOGICS VISUALIZATION (PAGE 15 OF 22) EFFECT
G1 COMPARTMENT INERGEN RELEASE COMMAND (DELAYED) CAUSES-EFFECT

RET2.3 ELETRP_INC
ELECT. TRIPS SELECT. INCLUDED POSIT.

021S.2 SMOKE_ALM
SMOKE ALARM G1 COMPART. NOT PRESENT
022S.2 SMOKE_FAIL 2oo2 VOTING R20 INR_G1
SMOKE FAIL. G1 COMPART. NOT PRESENT (two out of two) 021-2S.2 INR_REL
TRIP LOGIC INERGEN RELEASE G1 COMPART. COMMAND
TRIP LOGIC G1 COMPART. INERGEN REL. NOT PRESENT PROCESSING
051S.1 SMOKE_ALM
PROCESSING
SMOKE ALARM COMMON LINE NOT PRESENT
052S.1 SMOKE_FAIL
SMOKE FAIL. COMMON LINE NOT PRESENT

012F.2 FLAME_ALM
FLAME ALARM G1 COMPART. NOT PRESENT

NOTE: When both smoke sensors are in failure, the inergen release condition is not activated.

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/107
1 check Martha Cluster MARTHA PLATF PES page 108
revision date name status: LZ based replaced replaced TRIP LOGICS VISUALIZAT. (PAGE 15 OF 22)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

CAUSES PAGE 108 OF 114 TRIP LOGICS VISUALIZATION (PAGE 16 OF 22) EFFECT
SWITCHBOARDS COMPARTMENT INERGEN RELEASE COMMAND (DELAYED) CAUSES-EFFECT

RET2.3 ELETRP_INC
ELECT. TRIPS SELECT. INCLUDED POSIT.

031S.2 SMOKE_ALM
SMOKE ALARM SWTCHBRDS COMP. NOT PRESENT
032S.2 SMOKE_FAIL 2oo2 VOTING
SMOKE FAIL. SWTCHBRDS COMP. NOT PRESENT (two out of two) 031-2S.2 INR_REL
TRIP LOGIC R30 INR_EP
TRIP LOGIC SWTCHBRDS COMPART. INERGEN REL. NOT PRES. PROCESSING INERGEN REL. SWTCHBRDS COMP. COMMAND
051S.1 SMOKE_ALM
PROCESSING
SMOKE ALARM COMMON LINE NOT PRESENT
052S.1 SMOKE_FAIL
SMOKE FAIL. COMMON LINE NOT PRESENT

013F.2 FLAME_ALM
FLAME ALARM SWTCHBRDS COMP. NOT PRESENT

NOTE: When both smoke sensors are in failure, the inergen release condition is not activated.

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/108
1 check Martha Cluster MARTHA PLATF PES page 109
revision date name status: LZ based replaced replaced TRIP LOGICS VISUALIZAT. (PAGE 16 OF 22)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

CAUSES PAGE 109 OF 114 TRIP LOGICS VISUALIZATION (PAGE 17 OF 22) EFFECT
TRANSFORMER COMPARTMENT INERGEN RELEASE COMMAND (DELAYED) CAUSES-EFFECT

RET2.3 ELETRP_INC
ELECT. TRIPS SELECT. INCLUDED POSIT.

041S.2 SMOKE_ALM
SMOKE ALARM TRANSF. COMPART. NOT PRESENT
042S.2 SMOKE_FAIL 2oo2 VOTING
SMOKE FAIL. TRANSF. COMPART. NOT PRESENT (two out of two) 041-2S.2 INR_REL
TRIP LOGIC R40 INR_TR
TRIP LOGIC TRANSF. COMPART. INERGEN REL. NOT PRES. PROCESSING INERGEN REL. TRANSF. COMPART. COMMAND
051S.1 SMOKE_ALM
PROCESSING
SMOKE ALARM COMMON LINE NOT PRESENT
052S.1 SMOKE_FAIL
SMOKE FAIL. COMMON LINE NOT PRESENT

014F.2 FLAME_ALM
FLAME ALARM TRANSF. COMPART. NOT PRESENT

NOTE: When both smoke sensors are in failure, the inergen release condition is not activated.

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/109
1 check Martha Cluster MARTHA PLATF PES page 110
revision date name status: LZ based replaced replaced TRIP LOGICS VISUALIZAT. (PAGE 17 OF 22)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

CAUSES PAGE 110 OF 114 TRIP LOGICS VISUALIZATION (PAGE 18 OF 22) EFFECT
TONE #1 ACTIVATION CAUSES-EFFECT

RPS1.2 UNM_MAN
UNMANNED POSIT. SELECT. SIGNALIZ.
RT1 TONE1
RPA.2 PLT_ABD
PLATF. ABAND. PUSH-BUTTONS NOT ACTIV.
TRIP LOGIC TONE #1 ACTIVATION
PROCESSING TONE #1 ACTIVATION FOR
PLATFORM ABANDON PUSH-BUTTONS OPERATION
TONES_SILENCER
TONES CTRL UNIT SILENCER PUSH-BUTTON ACTIV.

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/110
1 check Martha Cluster MARTHA PLATF PES page 111
revision date name status: LZ based replaced replaced TRIP LOGICS VISUALIZAT. (PAGE 18 OF 22)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

CAUSES PAGE 111 OF 114 TRIP LOGICS VISUALIZATION (PAGE 19 OF 22) EFFECT
TONE #2 ACTIVATION CAUSES-EFFECT

RPS1.2 UNM_MAN
UNMANNED POSIT. SELECT. SIGNALIZ.

RMOB.2 MOB_PB RT2 TONE2


MAN OVERBOARD PUSH-BUTTONS NOT ACTIVATED
TRIP LOGIC TONE #2 ACTIVATION
PROCESSING
TONE #2 ACTIVATION FOR
TONES_SILENCER MAN OVERBOARD PUSH-BUTTONS OPERATION
TONES CTRL UNIT SILENCER PUSH-BUTTON ACTIV.

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/111
1 check Martha Cluster MARTHA PLATF PES page 112
revision date name status: LZ based replaced replaced TRIP LOGICS VISUALIZAT. (PAGE 19 OF 22)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

CAUSES PAGE 112 OF 114 TRIP LOGICS VISUALIZATION (PAGE 20 OF 22) EFFECT
TONE #3 ACTIVATION CAUSES-EFFECT (EXPLOSIVE GAS DETECTED)

RPS1.2 UNM_MAN TONES_SILENCER


UNMANNED POSIT. SELECT. SIGNALIZ. TONES CTRL UNIT SILENCER PUSH-BUTTON ACTIV.

011E.2 EXPG_PALM 101E.2 EXPG_PALM


EXPL. GAS PREALARM ZONE #1 WELL HEADS NOT PRES. EXPL. GAS PREALARM STAU ROOM NOT PRES.
012E.2 EXPG_ALM 102E.2 EXPG_ALM
EXPL. GAS ALARM ZONE #1 WELL HEADS NOT PRES. EXPL. GAS ALARM STAU ROOM NOT PRES.
021E.2 EXPG_PALM 111E.2 EXPG_PALM
EXPL. GAS PREALARM ZONE #2 WELL HEADS NOT PRES. EXPL. GAS PREALARM G1 COMPART. NOT PRES.
022E.2 EXPG_ALM 112E.2 EXPG_ALM
EXPL. GAS ALARM ZONE #2 WELL HEADS NOT PRES. EXPL. GAS ALARM G1 COMPART. NOT PRES.
031E.2 EXPG_PALM 121E.2 EXPG_PALM
EXPL. GAS PREALARM ZONE #3 WELL HEADS NOT PRES. EXPL. GAS PREALARM SWTCHBRDS COMP. NOT PRESENT
032E.2 EXPG_ALM 122E.2 EXPG_ALM
EXPL. GAS ALARM ZONE #3 WELL HEADS NOT PRES. EXPL. GAS ALARM SWTCHBRDS COMP. NOT PRESENT
041E.2 EXPG_PALM 131E.2 EXPG_PALM
EXPL. GAS PREALARM ZONE #4 WELL HEADS NOT PRES. EXPL. GAS PREALARM TRANSF. COMP. NOT PRESENT
042E.2 EXPG_ALM 132E.2 EXPG_ALM
EXPL. GAS ALARM ZONE #4 WELL HEADS NOT PRES. EXPL. GAS ALARM TRANSF. COMP. NOT PRESENT
RT3 TONE3
051E.2 EXPG_PALM 141E.2 EXPG_PALM TRIP LOGIC
TONE #3 ACTIVATION
EXPL. GAS PREALARM ZONE #5 PROC. MOD. NOT PRES. EXPL. GAS PREALARM PRESS. ASPIR. NOT PRESENT PROCESSING
TONE #3 ACTIVATION FOR
052E.2 EXPG_ALM 142E.2 EXPG_ALM EXPLOSIVE GAS PREALARM OR ALARM PRESENT
EXPL. GAS ALARM ZONE #5 PROC. MOD. NOT PRES. EXPL. GAS ALARM PRESS. ASPIR. NOT PRESENT EXPLOSIVE GAS DETECTION SYSTEM FAULT
061E.2 EXPG_PALM 003E.2 EXPG_FAIL
EXPL. GAS PREALARM ZONE #6 PROC. MOD. NOT PRES. EXPL. GAS DETECT. SYST. FAIL. NOT PRESENT
062E.2 EXPG_ALM
EXPL. GAS ALARM ZONE #6 PROC. MOD. NOT PRES.
071E.2 EXPG_PALM
EXPL. GAS PREALARM ZONE #7 PROC. MOD. NOT PRES.
072E.2 EXPG_ALM
EXPL. GAS ALARM ZONE #7 PROC. MOD. NOT PRES.
081E.2 EXPG_PALM
EXPL. GAS PREALARM ZONE #8 PROC. MOD. NOT PRES.
082E.2 EXPG_ALM
EXPL. GAS ALARM ZONE #8 PROC. MOD. NOT PRES.
091E.2 EXPG_PALM
EXPL. GAS PREALARM ZONE #9 PROC. MOD. NOT PRES.
092E.2 EXPG_ALM
EXPL. GAS ALARM ZONE #9 PROC. MOD. NOT PRES.

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/112
1 check Martha Cluster MARTHA PLATF PES page 113
revision date name status: LZ based replaced replaced TRIP LOGICS VISUALIZAT. (PAGE 20 OF 22)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

CAUSES PAGE 113 OF 114 TRIP LOGICS VISUALIZATION (PAGE 21 OF 22) EFFECT
TONE #4 ACTIVATION CAUSES-EFFECT (FLAME AND/OR SMOKE DETECTED)

RPS1.2 UNM_MAN TONES_SILENCER


UNMANNED POSIT. SELECT. SIGNALIZ. TONES CTRL UNIT SILENCER PUSH-BUTTON ACTIV.

012F.2 FLAME_PALM 052S.1 SMOKE_FAIL


FLAME PREALARM STAU ROOM NOT PRESENT SMOKE FAIL. COMMON LINE NOT PRESENT
011F.2 FLAME_ALM 051S.1 SMOKE_ALM
FLAME ALARM STAU ROOM NOT PRESENT SMOKE ALARM COMMON LINE NOT PRESENT
022F.2 FLAME_PALM 003S.2 SMOKE_FAIL
FLAME PREALARM G1 COMPART. NOT PRESENT SMOKE DETECT. SYST. FAIL. NOT PRESENT
012F.2 FLAME_ALM R13.2 INR_REL_ST
FLAME ALARM G1 COMPART. NOT PRESENT INERGEN RELEASE STAU ROOM NOT OCCURR.
032F.2 FLAME_PALM R23.2 INR_REL_G1
FLAME PREALARM SWTCHBRDS COMP. NOT PRESENT INERGEN RELEASE G1 COMPART. NOT OCCURR.
013F.2 FLAME_ALM R33.2 INR_REL_EP
FLAME ALARM SWTCHBRDS COMP. NOT PRESENT INERGEN RELEASE SWTCHBRDS COMPART. NOT OCCURR.
042F.2 FLAME_PALM R43.2 INR_REL_TR
FLAME PREALARM TRANSF. COMPART. NOT PRESENT INERGEN RELEASE TRANSF. COMPART. NOT OCCURR.
014F.2 FLAME_ALM FUPLGNET
RT4 TONE4
FLAME ALARM TRANSF. COMPART. NOT PRESENT PROD. EMERG. TRIP FROM FUSIB. PLUGS NOT ACTIV. TRIP LOGIC TONE #4 ACTIVATION
003F.2 FLAME_FAIL PROCESSING
TONE #4 ACTIVATION FOR
FLAME DETECT. SYST. FAIL. NOT PRESENT FLAME PREALARM OR ALARM PRESENT
012S.2 SMOKE_FAIL FLAME DETECTION SYSTEM FAULT
SMOKE FAIL. STAU ROOM NOT PRESENT SMOKE FAILURE OR SMOKE ALARM PRESENT
INERGEN RELEASE OCCURRED
011S.2 SMOKE_ALM
PSD FROM FUSIBLE PLUGS ACTIVATED
SMOKE ALARM STAU ROOM NOT PRESENT
022S.2 SMOKE_FAIL
SMOKE FAIL. G1 COMPART. NOT PRESENT
021S.2 SMOKE_ALM
SMOKE ALARM G1 COMPART. NOT PRESENT
032S.2 SMOKE_FAIL
SMOKE FAIL. SWTCHBRDS COMP. NOT PRESENT
031S.2 SMOKE_ALM
SMOKE ALARM SWTCHBRDS COMP. NOT PRESENT
042S.2 SMOKE_FAIL
SMOKE FAIL. TRANSF. COMPART. NOT PRESENT
041S.2 SMOKE_ALM
SMOKE ALARM TRANSF. COMPART. NOT PRESENT

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/113
1 check Martha Cluster MARTHA PLATF PES page 114
revision date name status: LZ based replaced replaced TRIP LOGICS VISUALIZAT. (PAGE 21 OF 22)
Order No. of 115 sh.
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Offenders
will be held liable for the payment of damages. All rights reserved in the event of
the grant of a patent, utility model or ornamental design registration.

CAUSES PAGE 114 OF 114 TRIP LOGICS VISUALIZATION (PAGE 22 OF 22) EFFECT
AVAILABLE EMPTY PAGE

Project developed by: GDC


3 date name logic version rev
2 made Date Name DMH Ltd E&P LNBR/NCDI ELOP II ApplicationProgram coordinates A/114
1 check Martha Cluster MARTHA PLATF PES page 115
revision date name status: LZ based replaced replaced TRIP LOGICS VISUALIZAT. (PAGE 22 OF 22)