Energies: A Novel Ground Fault Non-Directional Selective Protection Method For Ungrounded Distribution Networks

Download as pdf or txt
Download as pdf or txt
You are on page 1of 26

Energies 2015, 8, 1291-1316; doi:10.

3390/en8021291
OPEN ACCESS

energies
ISSN 1996-1073
www.mdpi.com/journal/energies
Article

A Novel Ground Fault Non-Directional Selective Protection


Method for Ungrounded Distribution Networks
Ricardo Granizo *, Francisco R. Blánquez, Emilio Rebollo and Carlos A. Platero

Department of Electrical Engineering, Escuela Técnica Superior Ingenieros Industriales,


Technical University of Madrid, C/JoséGutierrez Abascal, 2, Madrid 28006, Spain;
E-Mails: fr.blanquez@gmail.com (F.R.B.); emiliorl10@gmail.com (E.R.);
carlosantonio.platero@upm.es (C.A.P.)

* Author to whom correspondence should be addressed; E-Mail: ricardo.granizo@upm.es;


Tel.: +34-91-336-6842; Fax: +34-91-336-7726.

Academic Editor: Josep M. Guerrero

Received: 5 November 2014 / Accepted: 20 January 2015 / Published: 9 February 2015

Abstract: This paper presents a new selective and non-directional protection method to
detect ground faults in neutral isolated power systems. The new proposed method is based
on the comparison of the rms value of the residual current of all the lines connected to a bus,
and it is able to determine the line with ground defect. Additionally, this method can be used
for the protection of secondary substation. This protection method avoids the unwanted trips
produced by wrong settings or wiring errors, which sometimes occur in the existing
directional ground fault protections. This new method has been validated through computer
simulations and experimental laboratory tests.

Keywords: earth faults; protection; distribution protections; electrical distribution networks

1. Introduction

Distribution power systems are equipped with sophisticated protection devices to keep them safe from
overloads, short circuits, voltage sags and drops and, in general, any operation conditions out of rated
values, something which might represent a clear danger not only to the facilities, but also to the power
system operation. Although in some countries the distribution networks can reach 150 kV [1],
the isolated distribution networks worldwide are normally classified in voltage levels from 1 kV to 45 kV
Energies 2015, 8 1292

and have the advantage that a single phase ground fault (SPGF) of the system does not produce high
ground fault overcurrents; therefore, the whole system remains operational. In this case, the power
system must be designed to withstand high transient and permanent steady state over voltages, so its use
is generally restricted to low and medium voltage systems.
These systems enjoy low current values when a SPGF happens. Such ground fault currents are not
related to the amount of power generated or distributed as they are only produced by the capacitance
distributed in all power elements that form such neutral ungrounded network. Therefore, all kind of
possible distributed generation units (DGs) connected to this kind of networks are not exposed to high
currents values when a SPGF is taking place. These kind of neutral ungrounded networks are designed
to be able to withstand over voltages up to190% of rated voltage value over 8 h [2,3].
A SPGF at one line of an isolated power system makes capacitive currents flow through all the lines,
and the voltages of the phases without defect are increased up to the phase-to-phase voltage level—that
is an overvoltage of 173%.
Lines without ground faults contribute with their own capacitive current flowing from the busbars to
the fault. The direction of the residual current in the line with ground fault is opposite to the direction of
the capacitive currents in the lines without ground defect. Under such circumstances, the existing
protection devices use directional ground fault criterion, measuring the residual current, the residual
voltage and the phase shift between them.
This relay provides ground fault detection, but presents important operational difficulties that could
imply unwanted tripping commands. Such difficulties are related to substations that cannot be removed
from service, while the commissioning jobs must be developed; therefore, there is no chance to test the
directional ground fault protection relays using primary injection tests. Secondary tests are always
satisfactory but they are not enough to grant the correct behaviour of the protection relay when there is
a real ground defect, and in addition, some wrong tripping actions happen from time to time.
The new proposed method is based on the comparison of the rms value of the residual current of all
the lines connected to a bus. As it is a non-directional method, errors in the polarity of the connections
of the current transformers have no influence on its operation. A wrong setting definition is also
eliminated because of its comparison principle. These two last aspects normally drive directional ground
fault protections to make unintended tripping commands.
This paper first describes, in Section 2, the state of the art of fault detection in neutral isolated power
systems. Section 3 describes the principle of operation of the new non-directional method to detect single
phase ground faults at isolated networks. ATP simulation results and laboratory test results are shown in
Section 4 and Section 5, respectively. Finally, in Section 6, the main conclusions are listed.

2. State of the Art

The use of symmetrical components [4] can also be applied to study the ground fault capacitive
current values. Some research works have obtained excellent results using hybrid compensation
methods [5,6] and their use, although it is not widespread employed by distribution electrical companies,
is perfectly applicable to neutral ungrounded networks whereas other investigation works build different
algorithms to determine the ground fault current value [7].
Energies 2015, 8 1293

There are several methods to detect SPGF at neutral ungrounded networks. Some of them use
compensation factors [8] for the residual voltage whereas others study the shape of charge-voltage curves
when a ground fault is present [9]. Other options include the installation of current and voltage
sensors along the medium voltage network and install management software to detect the feeder with
defect [10,11] after the protection systems have tripped the circuit breaker corresponding to the feeder
with ground defect.
New algorithms [12] and methods that compare the ground fault currents to new reference current
magnitude [13] have been also evaluated. Open research that might be applied to the detection and
localization of ground faults is described in [14]. Recently, the use of the Wavelet analysis [15–17] has
achieved excellent results in fault detection. Once the fault has been detected, the different protection
methods can give an alarm or a tripping command in order to avoid damage to the power system
elements, and remove from service the zone with fault condition, providing selectivity. Normally,
the distribution companies use two protection relays to detect and clear the SPGF in neutral
ungrounded networks.
Busbars
A B C LINE 1

IE1  IE2  IE3  IE1


Power transformer
CT
I E 2  I E3
I p1 
Uo TR
GD
PR
Isolated LINE 2
IE2

Uo CT
I E2
Uo I p2 
GD TR
VT PR
LINE 3

I E3

U0
CT
I E3
Uo I p3 
GD TR
PR

Figure 1. Residual current distribution in an underground neutral undergrounded system


with ground fault at F in phase “c” of Line 1.

The first one is a residual over voltage protection relay (ANSI 59N). This protection relay only
evaluates the residual voltage at the busbars of the substation, not the phase voltage values [18].
This residual voltage is normally measured through three voltage transformers in open delta connection
installed at the medium voltage busbars of the substation. The worst drawback of this way of detection
is that the location of the fault is not possible to determine, as the residual voltage is present in the entire
power system. In fact, depending of the distribution operator company, this type of protection can be
Energies 2015, 8 1294

used to signal an alarm or trip the entire busbar system and remove from service all lines connected to
such busbar system. The trip of the entire busbar system is unacceptable due to a SPGF in any line.
The second protection relay used is the ground directional protection relay (GDPR) [19,20].
This protection is based on the different directions of the residual currents in case of ground fault.
The residual current in the line with ground defect has an opposite direction than in the rest of the lines,
as shown in Figure 1. This protection only has to trip in case of residual current circulating in the
appropriate direction. So in order to distinguish the line with ground defect, it is necessary to measure
the residual current direction at every line connected to the busbars of the substation. For such purpose,
a directional ground fault protection relay is installed at every line.
The evaluation of the direction of the residual current needs the measurement of the residual voltage
as reference vector. This residual voltage is obtained in the same way as described before in the use of
the residual over voltage protection (ANSI 59N). Therefore, when the ground fault residual current and
the residual voltage are over their setting values, a directional comparison between the ground fault
residual current and the residual voltage is done. In function of the angle between them, a tripping
command is performed.
The maximum sensitivity characteristic angle between the residual voltage U0 and the residual current
I0 can be adjusted in the directional protection relays as a function of the neutral point connection.
These protections relays are more expensive than the residual overvoltage relays, as they have to manage
voltages, currents and develop a directional comparison.
This directional protection system is not free of problems. Sometimes, when there is a ground fault in
one line, there are unwanted trips in other lines caused by a wrong setting or wiring errors in their
respective ground fault directional protection relays. These wrong tripping commands cannot be avoided
in some installations where a primary test injection is not possible because the power supply cannot be
switched off; In this case, neither a minimum residual voltage nor a residual current can be injected in
the directional relays, and only secondary tests could be performed.
Under such circumstances, when a real ground defect happens, the correct behaviour of the directional
protection relay cannot be granted. Therefore, only when a ground fault happens, is it possible to detect
an error in the settings or in the wiring of the directional ground protection relays.
Commissioning engineers have to cope with the right identification of the polarity of the VT’s and
CT’s wired to the GDPR as its manufacturer indicates, the right tripping direction indicated by the GDPR
manufacturer, the right tripping angle between residual voltage U0 and the residual current I0 and the
right current circulations when there is a SPGF.
These last drawbacks related to the GDPR make the use of other protection systems interesting,
which could be set in operation without primary test injections and provide full protection with total
selectivity against ground faults to all the lines connected to the same busbars in any substation.
In Figure 2, the circulating currents are shown in all the lines in an underground power system when
a ground defect happens at F location at phase “c” in Line 1. At every phase of the three lines, its own
capacitive current is circulating towards the fault point F except the capacitive current components at
the phase “c” in the entire power system because they are short-circuited. Therefore, the capacitive
current measured by the ring core current transformers CT that embrace the three phases at Lines 2 and 3
are the sum of the capacitive currents of their phases; in Line 2 it is IE2 = ICA,2 + ICB,2, and in Line 3 it is
IE3 = ICA,3 + ICB,3. These currents IE2 and IE3 have direction from the busbars to the line.
Energies 2015, 8 1295

Figure 2. Residual current distribution in a three line neutral ungrounded system with ground
fault at F in phase “c” of Line 1.

However, the capacitive current measured by the ring core current transformer (CT) in Line 1 is the
sum of the capacitive currents IE2 and IE3 with direction from the fault point F to the busbars. The
capacitive current IE1 flows back and forth through the CT of the Line 1, so it is neglected. Every ground
fault directional protection relay installed per line, reads the residual voltage U0 at the busbars obtained
from the voltage transformers (VT) in open-delta connection and the currents Ip1, Ip2 and Ip3.
These Ip1, Ip2 and Ip3 currents are the respective capacitive currents in primary side of
Lines 1, 2 and 3, referred to the secondary side through the current transformer ratio TR of the ring core
current transformers CT used.
In case of having an outdoor power system with feeders, there must be three current transformers
installed in each feeder in Holmgreen connection to be able to read the ground fault current as it is
indicated in Figure 3. In Figures 4–6 the measurements of residual voltage and current in the three GDPR
are illustrated. Only when their settings and the wirings are correct, GDPR in Line 1 is the only one
GDPR which trips when a SPGF happens in Line 1.
From Figures 4–6 it is seen that the Line 1 with ground fault has residual current 3I0,1 leading the
residual voltage 90°, whereas in Lines 2 and 3 without ground defect, their residual currents 3I0,2 and
3I0,3 lag the residual voltage. It can be concluded that when the ground fault directional relays are well
adjusted and wired, their performance is quite good, but in some situations, such as when a new relay is
going to be installed or maintenance works do not allow making primary injection to test the protection
Energies 2015, 8 1296

relays, their behavior is committed. A new protection method that avoids such maintenance problems
and the difficulty of checking the performance of the relays at any time with full effectiveness is
described in this article.
CT PHASE A IA

CT PHASE B IB

CT PHASE C IC

Ia  Ib  Ic GDPR

Figure 3. Current transformers connected in Holmgreen connection.

 
      UA 3U 0
3I0,1  IE1  IE2  IE3  IE1 U A'


I CB,1
 
 UC UB
ICA,1

U B'

Figure 4. Vector diagram. Residual voltage and current in Line 1 with ground defect.

 
 UA 3U 0
U A'

 
UC UB

 U B'
I CA,2

I CB , 2

 
3I0,2  I E 2

Figure 5. Vector diagram. Residual voltage and current in Line 2 with ground defect in Line 1.
Energies 2015, 8 1297

 
 UA 3U 0
U A'

 
UC UB

 U B'

I CA,3
I CB , 3

 
3I 0 , 3  I E 3

Figure 6. Vector diagram. Residual voltage and current in Line 3 with ground defect in Line 1.

3. Principle of Operation of the New Selective Ground Fault Detection Technique

Before explaining the new principle of operation, the circulating of defect and capacitive currents
when there is a SPGF in an isolated network is explained in detail.
In cases of ground fault, the capacitive currents of all the n−1 lines without defect will circulate to the
line with ground defect. On the other hand, in any line free of defects, only its own capacitive current IE
will flow as indicated in Figure 1. This can be expressed as follows:
Residual capacitive current in line with no ground defect: I E , NGD  I E (A)
n 1 (1)
Residual capacitive current in line with ground defect: I E ,WGD   I E , NGD (A)
1

where IE,NGD is the capacitive current IE of any of the n–1 lines with no ground defect (NGD), whereas
the capacitive current of the line with ground defect (WGD), IE,WGD, is the sum of the n−1 capacitive
currents IE of the rest of the lines with no ground defect.
When a power system has a ground fault at any undergrounded line “i” in phase “a” for example,
the modules of the capacitive currents ICBi and ICCi of phases “b” and “c” are given by the equation:

U phase
I CBi  I CCi   3· U phase·j·
2· ·f · L (A)
C ph·
XC
(2)
1
XC 

2· ·f ·
C ph

where Uphase is the nominal phase-to-neutral voltage of the power system, XC is the capacitive ground
impedance value, f is the frequency of the power system, Cph is the capacitance per length unit of one
phase and L is the length of the line or cable. The larger the capacitance, the greater capacitive current
the line will have. Normally this capacitance Cph is given in F/km. When the power system is free of
ground faults, the capacitive currents in any line have the same value in all its phases.
Figure 2 shows an example of the circulating currents in all the lines in an underground 20 kV power
system when a SPGF happens in Line 1, phase “c” in point F. The lengths of the Lines 1, 2 and 3 are
Energies 2015, 8 1298

6, 10 and 8 km respectively; each line has one single cable per phase with a capacitance to earth
0.25 μF/km which represents about 1.57 A/km/phase. These data represent in Line 1 a current value of
IE1 = 18.84 A, in Line 2 it is IE2 = 31.407 A and in Line 3 IE3 = 25.122 A. The current IE1 circulates back
and forth through the CT installed in Line 1 so it does not affect in the current value measured whereas
both currents IE2 and IE3 circulate from busbars to the fault point F. Therefore, the circulating currents
measured by the three CTs are: 56.53 A in Line 1 with direction from the fault point F to the busbars;
31.40 A in Line 2 with direction from the busbars to the fault point, and 25.12 A in Line 3 from the
busbars to the fault point.
The proposed method is based on the comparison of the rms values of the residual current of all the
lines connected to a bus. Figure 2 shows how Line 1 with SPGF has the highest residual current
compared to the residual currents in Lines 2 and 3 without ground defect. An additional condition for
verifying the presence of a ground fault in the power system should be the evaluation of a minimum
residual voltage to avoid undesirable tripping commands [21]. Therefore, in a power system with more
than two lines, in the case of a ground fault, the line with ground defect would have the biggest residual
current of all the lines.

3.1. Ground Fault Detection Method for Main Substations

At main substations fed directly by power transformers, in the line that has a SPGF, a residual current
can be measured that corresponds to the addition of the capacitive currents of the rest lines in service
without ground fault. In each of the healthy lines, the residual currents correspond to their own capacitive
currents. The line with SPGF is easily detectable in this type of substation by comparing the rms values
of the residual currents. The line with the highest residual current is the line that has a ground fault.
As shown in Figure 2, the line with ground defect (Line 1) has a residual current corresponding to the
sum of the capacitive currents of the other lines: IE2 + IE3, while in Lines 2 and 3, the residual currents
are IE2 and IE3, respectively.

3.2. Ground Fault Detection Algorithm for Secondary Substations

In power systems with one main substation and several secondary substations, the new non-directional
method should be implemented in the main substation and in the secondary substations. Secondary
substations correspond to those that have incoming feeders/lines and outgoing feeders/lines connected
at the same busbars and can be considered as a single bus in the network.
As shown in Figure 7, where there are one main substation and three secondary substations. In case
of a SPGF, if the described method to detect ground faults is used in the secondary substations, tripping
commands will take place at all secondary substations simultaneously. The reason is that when there is
a ground fault, defect currents flow at every single line of the network. According to this new method
presented for main substations, the line with the highest residual current at every substation will be
tripped, and this line could be the line that has a ground fault or simply the longest line of the substation.
For instance, in the power system represented in Figure 7, in case of a fault in Line 12, not only the
outgoing Line 12 would be tripped, but also the longest lines at secondary substations 2 and 3 (Line 23
and Line 32 respectively). Therefore, an important part of the power system will be disconnected
inappropriately. This fact is considered by the proposed method in the specific case of secondary
Energies 2015, 8 1299

substations. The method requires choosing the principal line or lines that supply electrical power to the
busbars, as well as the outgoing lines that set out from such busbars. Once this selection is defined,
the procedure to determine where the fault is to check two conditions.

CT-M33
Line 33

CT-M3 CT-M3'
Line 3
CT-M32
Line 32

VT-3

Uo-3
CT-M31
Line 31

Secondary
Substation 3

Power transformer
CT-M23
CT-MP Line 23

CT-M2 CT-M2'
Line 2
CT-M22
Line 22
Isolated
VT-2

Uo-2
CT-M21
VT-MP Line 21

Uo-MP Secondary
Substation 2

CT-M13
Line 13

CT-M1 CT-M1'
Line 1
CT-M12
Main Line 12
Substation

VT-1

Uo-1
CT-M11
Line 11

Secondary
Substation 1

Figure 7. Highest ground fault currents at isolated network with secondary substations.
Ground fault at Line 12.

The first condition is to detect a SPGF in the system by the measurement of the residual voltage U0.
If the value of this residual voltage U0 is above a previous setting value, the next step is triggered.
Now the defect current rms values due to the capacitance of the system at every incoming and outgoing
line at any secondary substation are read out and evaluated. The algorithm checks if the sum of all
outgoing rms residual current values is equal to the sum of all incoming rms residual current values in a
secondary substation. If so, the fault is not taking place at any outgoing line of that secondary substation.
But if this second condition is not fulfilled at any secondary substation, the new system will trip the line
with highest defect current at that secondary substation. The algorithm of the method is shown in Figure 8.
Energies 2015, 8 1300


U0

 
U 0  U 0 setting 
No
Yes

Measure IE RMS Measure IE RMS


Current values of “j” Current values of “i”
Main Supply Lines Outgoing Lines (OL)
(MSL) connected to a connected to a busbar
busbar system Bk system Bk

m n
 I Ejk  MSL    I Eik OL 
j 1 i 1 Yes
k k
(Outgoing lines without
defect, ground fault at
No another substation)

max I Eik OL   Outgoing  Line ik  Fault

Trip  Outgoing  Lineik

Figure 8. Secondary substation. Algorithm for SPGF detection.

3.3. Examples of Application of the New Method

The working principle of the new method is evaluated in two different scenarios:

3.3.1. Ground Fault in an Outgoing Line of any Secondary Substation

Let us consider a network composed of a main substation and three secondary substations, shown in
Figure 9, where a SPGF has occurred in Line 22. The measurements of the current transformers of the
main and secondary lines are summarized in Table 1. In this example, using the appropriated criteria for
a secondary substation, the new selective ground fault method operates as follows:
- When the residual voltage level is over the setting value, the residual currents are evaluated.
- At secondary substation 1, the defect current measured at the incoming Line 1 by the current
transformer CT-M1’ has an rms value equal to the sum of the rms values of the defect currents
measured at the outgoing Lines 11, 12 and 13 by their respective current transformers CT-M11,
Energies 2015, 8 1301

CT-M12 and CT-M13. Using the second condition criterion, it is concluded that the fault is not
located at any of these outgoing lines. The same conclusion can be made for secondary substation 3.
- At secondary substation 2, the defect current measured at the incoming Line 2 by its current
transformer CT-M’ has a different rms value from the sum of the rms values of the defect currents
measured at the outgoing Lines 21, 22 and 23 by their respective current transformers CT-M21,
CT-M22 and CT-M23. Now, as the highest defect current is measured at outgoing Line 22,
the conclusion from employing the second condition criteria is that the fault is in such line.
- At the main substation, the defect current measured at the outgoing Line 2 by its current
transformer CT-M2 has the highest rms value of all the outgoing currents in Lines 1, 2 and 3
measured by their respective current transformers CT-M1, CT-M2 and CT-M3. The new method
would switch off Line 2as a consequence of the first condition criterion.
To avoid a tripping order at the outgoing Line 2 at the main substation before a tripping order at the
outgoing Line 22, there must be a time delay between such commands. Tripping orders at secondary
substations must be quicker than the main substation ones to provide selectivity.
CT-M33
Line 33

CT-M3 CT-M3' I E 33
Line 3
CT-M32
Line 32
IE3
VT-3
I E 32
Uo-3
CT-M31
Line 31

Secondary
Substation 3 I E 31
Power transformer
CT-MP I E 1  I E 11  I E 12  I E 13  I E 2 CT-M23
Line 23
 I E 3  I E 31  I E 32  I E 33

CT-M2 CT-M2' I E 23
Line 2
CT-M22
Line 22
Isolated

I E 1  I E 11  I E 12  I E 13 VT-2

 I E 3  I E 31  I E 32  I E 33 Uo-2
CT-M21
VT-MP Line 21

Uo-MP Secondary
Substation 2 I E 21

CT-M13
Line 13

CT-M1 CT-M1' I E 13
Line 1
CT-M12
Main Line 12
Substation
I E1
VT-1 I E12
Uo-1
CT-M11
Line 11

Secondary I E 11
Substation 1

Figure 9. Highest ground fault currents at neutral undergrounded network with secondary
substations. SPGF at Line 22.
Energies 2015, 8 1302

Table 1. Residual current measurements. Ground fault at Line 22—Phase “a”—rms current
value (A).
Main station Secondary substation II
IE1 + IE11 + IE12 + IE13 + IE3 + IE31 +
CT-MP 0 CT-M2’
IE32 + IE33 + IE2
CT-M1 IE1 + IE11 + IE12 + IE13 CT-M21 IE21
IE1 + IE11 + IE12 + IE13 + IE1 + IE11 + IE12 + IE13 + IE3 + IE31 +
CT-M2 CT-M22
IE3 + IE31 + IE32 + IE33 IE32 + IE33 + IE2 + IE21 + IE23
CT-M3 IE3 + IE31 + IE32 + IE33 CT-M23 IE23
Secondary substation I Secondary substation III
CT-M1’ IE1 + IE11 + IE12 + IE13 CT-M3’ IE3 + IE31 + IE32 + IE33
CT-M11 IE11 CT-M31 IE31
CT-M12 IE12 CT-M32 IE32
CT-M13 IE13 CT-M33 IE33

3.3.2. SPGF in a Line That Connects a Main Substation with a Secondary One

Now the network study is represented in Figure 10, where a ground fault has occurred in Line 2.
In this case, the new selective ground fault method operates as follows:
- Residual voltage level is over the setting value, so the residual currents are evaluated.
- At secondary substation 1, the defect current measured at the incoming Line 1 by its current
transformer CT-M1’ has an rms value equal to the sum of the rms values of the defect currents
measured at the outgoing Lines 11, 12 and 13 by their respective current transformers CT-M11,
CT-M12 and CT-M13. The fault is not located at any of these outgoing lines as a result of
second condition criterion. The same conclusion can be reached for the secondary
substation 2 and 3.
- At the main substation, the defect current measured at the incoming line by CT-MP has a different
rms value than the sum of the rms values of the defect currents measured at the outgoing
Lines 1, 2 and 3 by their respective current transformers CT-M1, CT-M2 and CT.M3. The defect
current measured at the outgoing Line 2 by CT-M2 has the highest rms value of all the outgoing
lines. The new method would switch off Line 2 as the result of the first condition criteria.
The SPGF at outgoing Line 2 is cleared following the first criterion of maximum rms value, as well;
there is no tripping command at any other secondary substation as a result of the evaluation of the second
condition criterion. Table 2 shows the results of the current transformers placed at the main and
secondary substations indicated in Figure 10. The same result is obtained when the SPGF is at Lines 1
and 3. Finally, application at busbars that couple different substations has also given excellent results,
with its implementation also being suitable.
Energies 2015, 8 1303

CT-M33
Line 33

CT-M3 CT-M3' I E 33
Line 3
CT-M32
Line 32
IE3
VT-3
I E 32
Uo-3
CT-M31
Line 31

Secondary
Substation 3 I E 31

CT-M23
Line 23

CT-M2 CT-M2' I E 23
Line 2
Power transformer CT-M22
Line 22
CT-MP

VT-2
I E 1  I E 11  I E 12  I E 13 I E 22
Uo-2
 I E 3  I E 31  I E 32  I E 33 CT-M21
Line 21

Isolated Secondary
Substation 2 I E 21

VT-MP

Uo-MP

CT-M13
Line 13

CT-M1 CT-M1' I E 13
Line 1
CT-M12
Main Line 12
Substation
I E1
VT-1 I E12
Uo-1
CT-M11
Line 11

Secondary I E 11
Substation 1

Figure 10. Highest SPGF currents at isolated network with main and secondary substations.
Ground fault at Line 2.

Table 2. Residual Current Measurements. SPGF at Line 2—Phase “a”—rms current value (A).
Main station Secondary substation II
CT-MP 0 CT-M2’ IE2 + IE21 + IE22 + IE23
CT-M1 IE1 + IE11 + IE12 + IE13 CT-M21 IE21
CT-M2 IE1 + IE11 + IE12 + IE13 + IE3 + IE31 + IE32 + IE33 CT-M22 IE22
CT-M3 IE3 + IE31 + IE32 + IE33 CT-M23 IE23
Secondary substation I Secondary substation III
CT-M1’ IE1 + IE11 + IE12 + IE13 CT-M3’ IE3 + IE31 + IE32 + IE33
CT-M11 IE11 CT-M31 IE31
CT-M12 IE12 CT-M32 IE32
CT-M13 IE13 CT-M33 IE33
Energies 2015, 8 1304

In Table 3 the main differences between the different protection methods used to detect and clear
SPGF at neutral ungrounded networks are listed.

Table 3. Comparison of the main features of the protection methods used nowadays to detect
and clear SPGF at neutral ungrounded networks.
Protection method
Check list for
Residual voltage Ground fault directional New method non
commissioning
(ANSI 59N) overcurrent (ANSI 67N) directional
Check VT polarity No Yes No
Check CT polarity No Yes No
Check wiring polarity of VT’s to
No Yes No
protection system
check wiring polarity of CT’s to
No Yes No
protection system
Check tripping angle
No Yes No
between I0 and U0
Selective tripping No Yes Yes
Easy to set in operation Yes No Yes
Cost of the protection system Low High Low
Time to put the protection
Short Long Short
system into operation
Primary injection needed to test
No Yes No
its functionality

4. Analysis of Simulation Results

The proposed selective SPGF protection method was simulated using Alternative Transient Program
(ATP) while post-processing was done using Matlab. An equivalent “pi” model for lines was used as
well as power transformers rated 132/20 kV, 10 MVA, with YNd11 connection group. The simplest and
simplified schematic with one incoming line with 50 km in length and three outgoing lines with equal
lengths of 150 km without any load connected (a) and the same circuit with different loads (b) are shown
in Figure 11.
The parameters of any equivalent “pi” feeder for conductor type LA56 with diameter Φ = 9.45 mm
and delta disposition (Dab = 4 m, Dac = 2.3324 m, Dbc = 2.3324 m) are: R = 0.6136 Ω/km;
X = 0.4148 Ω/km and C = 0.28 μF/km. Loads: Z1 = 960 + j719.42 Ω; Z2 = 545 + j263.89 Ω;
Z3 = 380 + j124.72 Ω.
Energies 2015, 8 1305

Figure 11. ATP single line diagram for main substation arrangement.

4.1. Main Substation

To simulate the new method for the detection of which line suffers a ground fault condition, a power
system formed by three outgoing lines, of identical lengths, has been used, as seen in Figure 6.
Simulations with load (a) and without load (b) at each line terminal have been carried out. In the
simulation, ground faults were simulated at different phases and at different places with different
resistance values up to 30 Ω. For instance, a ground fault at single line diagram shown in Figure 11 is
evaluated at Line 1 phase “a” under no load conditions. Voltages under such fault condition at the
distribution 20 kV busbars are shown in Figure 12. Voltages at the same distribution 20 kV busbars
under the same fault conditions as before, but with load in the three feeders, turned out to be not so
high—between 8 and 10 kV less. In Figure 13, all SPGF currents of all lines connected to the 20 kV
busbars are represented considering the network as indicated in Figure 11 with load (b). The simulation
results shown in Figure 13 are indicated in Table 4. It can be clearly observed that the line with the defect
is the one which has the greatest residual current, its value being the sum of the other residual currents
(IE1 = IE2 + IE3 + IE0). It is totally correct to say that using this proposed method in a main substation,
a ground fault can easily be detected in a selective way.
Energies 2015, 8 1306

Figure 12. Phase voltages at main distribution busbars. SPGF at phase “a”—Line 1.

Figure 13. Ground fault currents at main distribution busbars. SPGF at phase “a”—Line 1.

Table 4. Residual current measurements. SPGF at Line 1—Phase “a”—rms current value (A).
Main station
IE0 IE1 IE2 IE3
(a) 3.71 25.81 11.05 11.05
(b) 3.10 21.78 9.34 9.34

4.2. Secondary Substations

Figure 14 shows a network with one main substation and four secondary substations. Feeders L11,
L12, L31, L32, L33, L41 and L42 supply different loads while feeders L2, L34 and L43 are energized
without any load connected. Ground fault at Line 2 in phase “a” is evaluated, and the result shows that
Energies 2015, 8 1307

ground fault current measurements at 20 kV busbars verify the proposed method. Ground fault currents
at outgoing Lines1, 3 and 4 with no fault, keep the same phase angle, whereas the ground fault current
at the Line 2 with ground defect has a 180°phase angle difference compared to those of Lines1, 3 and 4
(Figure 15). The sum of the rms ground fault current values of Lines 0, 1, 3 and 4 is practically the same
as that in Line 2.

Figure 14. Single line diagram for main and secondary substations.
Energies 2015, 8 1308

Figure 15. Ground fault currents at main distribution busbars. Single ground fault at
phase “a”—Line 2.

On the other hand, the evaluation of the defect currents at the three secondary substations has shown
that the incoming defect current rms value has the same defect current value as has the sum of the rms
defect current values of all the outgoing lines, at each of the three secondary substations. Therefore,
no tripping command will be given at any other secondary substation. Evaluation of the highest defect
current rms value at the main substation will give a tripping order to the Line 2 switchgear where the
ground fault is taking place. These results are listed in Table 5. In Figure 15, the ground fault currents
of all lines connected to the 20 kV busbars are represented.

Table 5. Residual current measurements. SPGF at Line 2—Phase “a”—rms current value (A).
Main station
IE0 IE1 IE2 IE3 IE4
1.25 6.44 24.80 11.92 5.19
Secondary substation I
IE1 IE11 IE12
5.17 2.58 2.59
Secondary substation II
IE2 IE2
24.80 24.80
Secondary substation III
IE30 IE31 IE32 IE33 IE34
10.63 2.66 2.67 2.67 2.65
Secondary Substation IV
IE4 IE41 IE42 IE43
3.92 1.31 1.31 1.31
Energies 2015, 8 1309

5. Experimental Results

To test the validity of the proposed SPGF detection method and its computer simulation results,
different laboratory tests have been performed on an isolated network. These tests try to verify the
operating principle of the detection technique.

5.1. Experimental Setup

The tests were carried out on an isolated network supplied by a power transformer rated 800 VA,
400/100 Vac, and YNy0 connection group. Up to nine line modules with equivalent circuit “pi”
were used, as shown in Figure 16. A per unit system of SB = 800 VA, UB = 100 V, IB = 4.618 A, and
ZB = 12.5 Ω was selected to represent all values. These practical tests were carried out with loads and
no loads at the end of the lines. The parameters of any equivalent “pi” feeder, also shown in Figure 16,
have the following characteristics: R = 88.48 mΩ, L = 4 mH, and C = 4 μF each capacitor.

Figure 16. Top: Actual network experiment set-up. Three identical lines. (1: Power transformer,
2: Equivalent “pi” module, 3: Ground fault resistance). Bottom: Equivalent “pi” module and
parameter values.

Several SPGFs at different phases, lines, and configurations were implemented in the real
isolated network erected in the laboratory. The ground fault resistance was shifted from 0 to 2.4 p.u. in
all cases studied.
Energies 2015, 8 1310

5.2. Three Lines with Identical Lengths

This kind of single line network scheme is shown in Figure 17, where the lines have a total equivalent
length of 150 km. Without any load connected (c), the measurements taken when a single ground fault
is present at Line 1 are listed in Table 6, including the fault resistance Rf and the residual voltage U0
measured at the busbars. The results show that the defect current measured at Line 1 has the highest
value, compared to those registered at Lines 2 and 3. As shown in Table 6, the faults can be clearly
located with different fault resistance values, chosen at random. The results obtained when having loads
(d) as 300 VA in Line 1, 50 VA in Line 2 and 150 VA in Line 3 are listed in Table 7. Again, the results
show that the defect current measured at Line 1 has the highest value, compared to those registered at
Lines 2 and 3.

Figure 17. Single line diagram with three lines with equal length. SPGF at phase “a”—Line 1.

Table 6. Experimental results. Three lines not loaded with identical length. Residual current
measurements IE in per unit values (p.u.). SPGF at Line 1—Phase “a”.
Main station
Rf U0 L1 L2 L3 IE1,a
0.00 1.38 0.80 0.40 0.40 1.18
0.32 1.21 0.70 0.35 0.35 1.03
0.56 1.19 0.73 0.34 0.34 0.97
0.80 1.03 0.59 0.30 0.30 0.88
1.04 0.82 0.47 0.24 0.24 0.70
1.20 0.75 0.47 0.23 0.23 0.69
1.60 0.62 0.36 0.18 0.18 0.53
2.00 0.53 0.30 0.15 0.15 0.45
2.40 0.47 0.26 0.13 0.13 0.39
Energies 2015, 8 1311

Table 7. Experimental results. Three lines loaded with identical length. Residual current
measurements IE in per unit values (p.u.). SPGF at Line 1—Phase “a”.
Main station
Rf U0 L1 L2 L3 IE1,a
0.00 1.38 0.78 0.39 0.39 1.16
0.32 1.21 0.73 0.36 0.36 1.08
0.56 1.19 0.64 0.32 0.32 0.95
0.80 1.03 0.57 0.28 0.28 0.84
1.04 0.82 0.50 0.25 0.25 0.74
1.20 0.75 0.45 0.22 0.22 0.66
1.60 0.62 0.36 0.18 0.18 0.53
2.00 0.53 0.31 0.15 0.15 0.45
2.40 0.47 0.27 0.13 0.13 0.40

Figure 18. Multiple line network. SPGF at Line 12.

5.3. Three Different Line Lengths

This network is formed by three lines with different lengths of 150, 250, and 50 km. This kind of
network with a SPGF at Line 12 is shown at Figure 18. Without any load connected (e), the
measurements taken at Line 1 when a SPGF is present at Line 12 are listed in Table 8, where the fault
resistance Rf and residual voltage U0 measured at the main station are also included. The results show
that the defect current measured at Line1A has the highest value, compared to those registered at
Lines 2A and 3A. On the other hand, at Secondary Substation II, the incoming defect current at Line 2
Energies 2015, 8 1312

is equal to the sum of the defect currents at outgoing Lines 21 and 22. Also in Figure 18, with different
loads connected (f) in Lines 11, 21 and 3, the measurements taken when a SPGF is present at Lines 12
are listed in Table 9, where the fault resistance Rf and residual voltage U0 measured at the main station
are also included. Table 10 shows the defect currents at substations I and II as well as the defect current.
The results again show that the defect current measured at Line 1A has the highest value, compared to
those registered at Lines 2A and 3A. On the other hand, at Secondary Substation II, the incoming defect
current at Line 2 is equal to the sum of the defect currents at outgoing Lines 21 and 22.

Table 8. Experimental results. Three lines not loaded with different lengths. Residual current
measurements IE in per unit values (p.u.). SPGF at Line 12—Phase “a”.
Main station Secondary substation II
Rf U0 L1A L2A L3A IE12,a L2 L21 L22
0.00 0.72 0.73 0.61 0.12 1.08 0.37 0.25 0.12
0.32 0.66 0.71 0.59 0.11 1.04 0.34 0.23 0.11
0.55 0.61 0.68 0.56 0.11 1.00 0.31 0.21 0.10
0.80 0.51 0.58 0.49 0.10 0.87 0.27 0.18 0.09
1.04 0.48 0.49 0.38 0.07 0.68 0.25 0.17 0.08
1.20 0.40 0.45 0.37 0.07 0.66 0.21 0.14 0.07
1.60 0.33 0.36 0.30 0.06 0.53 0.17 0.12 0.05
2.00 0.28 0.30 0.25 0.05 0.44 0.14 0.10 0.04
2.40 0.24 0.27 0.23 0.02 0.39 0.12 0.08 0.04

Table 9. Experimental results. Lines with and without load with different lengths.
Residual current measurements IE in per unit values (p.u.). SPGF at Line 12—Phase “a”.
Main station
Rf U0 L1A L2A L3A L0A
0.00 0.91 3.27 2.76 0.53 0.0074
0.32 0.84 2.56 2.25 0.44 0.0081
0.55 0.79 2.34 2.01 0.38 0.0056
0.80 0.66 2.18 1.76 0.34 0.0028
1.04 0.59 2.11 1.43 0.29 0.0020
1.20 0.48 2.03 1.70 0.33 0.0021
1.60 0.37 1.63 1.37 0.27 0.0012
2.00 0.33 1.40 1.18 0.23 0.0017
2.40 0.27 1.22 1.02 0.20 0.0048

In general terms, it must be said that the results obtained within these tests have turned out to be totally
similar to the ATP simulations carried out. Again, different fault resistance values were tested with
satisfactory results.
Energies 2015, 8 1313

Table 10. Experimental results. Lines with and without load with different lengths.
Residual current measurements IE in per unit values (p.u.). SPGF at Line 12—Phase “a”.
Secondary substation I Secondary substation II
Rf L1 L11 L12 IE12,a L2 L21 L22
0.00 3.68 0.52 4.32 4.85 1.66 0.55 1.12
0.32 3.04 0.39 3.36 3.70 1.38 0.41 0.96
0.55 2.73 0.35 3.02 3.46 1.21 0.37 0.83
0.80 2.47 0.28 2.75 3.18 1.09 0.36 0.73
1.04 2.11 0.30 2.42 2.92 1.06 0.32 0.73
1.20 2.01 0.32 2.68 2.79 1.03 0.34 0.67
1.60 1.90 0.26 2.16 2.42 0.83 0.27 0.55
2.00 1.62 0.22 1.81 2.06 0.71 0.24 0.46
2.40 1.41 0.19 1.60 1.78 0.61 0.21 0.40

6. Conclusions

A new selective single phase ground fault technique for neutral undergrounded networks has been
presented in this article. This new method is suitable for all kinds of main substations with at least three
feeders and secondary substations. The proposed non-directional detection technique is based on the
comparison of the rms value of the ground fault currents at each line position of each substation.
At main substations, the highest ground fault current module belongs to the line with the ground fault.
At secondary substations, if the ground fault current at the incoming line of the main busbars has the
same rms value as the arithmetic sum of all outgoing ground fault currents, the fault is not located at any
of the outgoing lines connected to those busbars, provided that a minimum residual voltage over an
established setting value is present.
ATP simulations with different substation configurations turned out to be totally satisfactory as well
as the experimental results of the laboratory tests. All of them show that the localization of the single
phase ground fault is easy to find, without any possible mistake, identifying the corresponding line as
the “line with ground fault condition.”
This new protection technique has the following advantages, when compared to traditional directional
ground fault protection devices:
1. It is much easier to measure the values of the ground defect currents than evaluate the direction
of the ground defect currents compared to the residual voltage.
2. In substations that cannot be removed from service, primary injection tests are not able to be
developed, and the correct operation of the directional ground fault protection relays is not
secured, whereas this new method is able to be totally commissioned without primary injection
tests and its good performance can be granted without removing the substation from service.
3. Unintentional wrong tripping commands given by directional protection relays due to wrong CTs
and VTs polarities connections are avoided, as directional criterion is not used.
4. It reduces dramatically the time and costs of installation and commissioning compared to the use
of directional ground fault protection relays.
The aforementioned advantages provide a great improvement in the network protection system as
unintended trips caused by single ground faults are eliminated.
Energies 2015, 8 1314

Author Contributions

Ricardo Granizo has deeply analyzed the ungrounded distribution power systems and developed the
algorithm proposed for this new method through computer simulations. Francisco R. Blánquez and
Emilio Rebollo contributed with the set up of the model tested in the laboratory and check the
experimental results with the simulation results. Carlos A. Platero contributed with an exhaustive review
of the current protection systems installed at ungrounded power systems. All authors have contributed
in the drafting and extensive revisions of the text as well as in all the processes to test, draft and obtain
the approval of the patent “System and method for selective non-directional earth-fault protection in
isolated neutral networks” with patent No. 2374345 (11 February 2013).

Nomenclature:

a, b, c Phase “a”, “b”, “c”.


ANSI: American National Standard Institute.
CT: Current transformer.
CT-Mi: Current transformer for residual measurement in one end in line “i”.
CT-Mi’: Current transformer for residual measurement in the other end in line “i”.
CT-MP: Current transformer for residual measurement in main power transformer output.
Cph: Capacitance to earth of one line phase.
DGs: Distributed generation units.
f: Frequency of the power system.
GDPR: Ground directional protection relay.
i: Number of line: 1, 2, 3,…n.
Ia: Current in phase “a” at the protection relay side.
IA,IB,IC: Capacitive currents in feeders at the primary side.
ICAi: Capacitive current at line “i” in phase “a”.
IEi: Capacitive current in line “i”.
IEi,a: Defect current at phase “a” at principal line “i”.
3I0,i: Residual current in line “i”.
Ipi: Capacitive current in line “i” at protection relay side.
L: Length of the line.
rms: Root mean square.
SPGF: Single phase ground fault.
TR: Current transformer ratio.
UA: Voltage in phase “a” without ground defect.
UA’: Voltage in phase “a” with ground defect.
Uphase: Rated phase voltage of the power system.
Uo: Residual voltage.
Uo-i: Residual voltage at substation “i”.
U0-MP: Residual voltage at main power station.
VT: Voltage transformers.
VT-i: Voltage transformers in substation “i”.
VT-MP: Voltage transformers in main power station.
XCa: Capacitive impedance of phase “a”.
Energies 2015, 8 1315

Conflicts of Interest

The authors declare no conflict of interest.

References

1. L’Abbate, A.; Fulli, G.; Starr, F.; Peteves, S. Distributed power generation in Europe: Technical
issues for further integration. JRC European Commission Scientific and Technical Report.
EUR 23234 EN, 2007.
2. Russell Mason, C. The Art and Science of Protective Relaying; Wiley: New York, NY, USA, 1956;
(sixth enlarged edition, 1967).
3. Horowitz, S.H.; Phadke, A.G. Power System Relaying, 3rd ed.; Wiley: New York, NY, USA, 2008.
4. Huang, S.J.; Wan, H.H. A Method to enhance ground-fault computation. IEEE Power Eng. Lett.
IEEE Trans. Power Syst. 2010, 25, 1190–1191.
5. Lin, W.M.; Ou, T.C. Unbalanced distribution network fault analysis with hybrid compensation.
IET Gener. Transmiss. Distrib. 2011, 5, 92–100.
6. Ou, T.C. A novel unsymmetrical faults analysis for microgrid distribution systems. Int. J. Electr.
Power Energy Syst. 2012, 43, 1017–1024.
7. Ou, T.C. Ground fault current analysis with a direct building algorithm for microgrid distribution.
Int. J. Electr. Power Energy Syst. 2013, 53, 867–875.
8. Lin, X.; Ke, S.; Gao, Y.; Wang, B.; Liu, P. A selective single phase-to-ground fault protection for
neutral uneffectively grounded systems. IJEPES 2011, 33, 1012–1017.
9. Henriksen, T. Faulty feeder identification in high impedance grounded network using
charge-voltage relationship. Electr. Power Syst. Res. 2011, 81, 1832–1839.
10. Tamo, T.; Voufo, J. Fault diagnosis on medium voltage (MV) electric power distribution networks:
The case of the downstream network of the AES-SONEL Ngousso sub-station. Energies 2009, 2,
243–257.
11. Conti, S.; Nicotra, S. Procedures for fault location and isolation to solve protection selectivity
problems in MV distribution networks with dispersed generation. Electr. Power Syst. Res. 2009,
79, 57–64.
12. Saha, M.M.; Izykowsky, J.; Rosolowsky, E. Fault Location on Power Networks; Springer-Verlag:
Berlin, Germany, 2009.
13. Granizo, R.; Blánquez, F.R.; Rebollo, E.; Platero, C.A. New selective earth faults only current
directional method for isolated neutral systems. In Proceedings of the Environment and Electrical
Engineering (EEEIC), Venice, Italy, 18–25 May 2012; pp. 18–25.
14. Chen, L.; Yang, Q.; Wang, J.; Sima, W.; Yuan, T. Classification of fundamental ferroresonance,
single phase-to-ground and wire breakage over-voltages in isolated neutral networks. Energies
2011, 4, 1301–1320.
15. Magnano, F.H.; Bur, A. Fault location using Wavelets. IEEE Trans. Power Deliv. 1998, 13, 1475–1480.
16. Huang, J.; Hu, X.; Li, X.; Hu, H.; Lv, Y. A novel single-phase earth fault feeder detection by
traveling wave and wavelets. In Proceedings of the International Conference on Power System
Technology, Chongqing, China, 22–26 October 2006; pp. 22–26.
Energies 2015, 8 1316

17. Elkalashy, N.; Lehtonen, M.; Darwish, H.; Taalab, A.M.; Izzularab, M. Operation evaluation of
DWT-based earth fault detection in unearthed MV networks. In Proceedings of the MEPCON
International Middle-East Power System Conference, Aswan, Egypt, 12–15 March 2008;
pp. 208–212.
18. Xyngi, I.; Popov, M. Smart protection in Dutch medium voltage distributed generation systems.
In Proceedings of the IEEE PES Innovative Smart Grid Technologies Conference Europe
(ISGT Europe), Gothenburg, Sweden, 11–13 October 2010; pp. 1–8.
19. Ukil, A.; Deck, B.; Shah, V. Smart distribution protection using current-only directional overcurrent
relay. In Proceedings of the IEEE PES Innovative Smart Grid Technologies Conference Europe
(ISGT Europe), Gothenburg, Sweden, 11–13 October 2010; pp. 1–7.
20. Stojanovic, A.N.; Djuric, M.B. An algorithm for directional earth-fault relay with no voltage inputs.
Electr. Power Syst. Res. 2013, 96, 144–149.
21. Universidad Politécnica de Madrid. System and method for selective non-directional earth-fault
protection in isolated neutral networks. Spanish Patent No. 2374345, 11 February 2013.

© 2015 by the authors; licensee MDPI, Basel, Switzerland. This article is an open access article
distributed under the terms and conditions of the Creative Commons Attribution license
(http://creativecommons.org/licenses/by/4.0/).

You might also like