FX27 /727 is a memory board. It has a battery back-up and holds ALL parameters and
machine data. If control locks-up or starts acting differently than what it is supposed to,
the data in this board might be scrambled. Power surge or lightning strike can cause the
same problem also. In this situation, FX27 /727 needs to be blanked.
Following are 4 methods one can use depending upon the circumstances.
1. Turn ON control
2. Press DIAG then NEXT 4 times
76543210
3. Enter (1000) ( 1 ) (M2), INPUT twice
4. Press GRAF, Enter CPU(L) INPUT
5. Power OFF/ON
6. Confirm 0’s in parameter values
7. Input parameters
8. Power OFF/ON
Method 2 (Mazatrol: T2, T3 with sys s/w Ver B4 or higher. It will not be effective for
earlier versions)
Note: a. This procedure will not put 0’s in parameter fields instead there will be “ * ”
and scrambled values.
b. Using this procedure on M1 control can simulate a locked operation panel/
Control. Hold ATC button, move through parameters screen and enter a few
parameters. Power Off/On. Enter the rest of the parameters. Format memory
using the –9999 or 7777 procedure. If everything fails, use Method 4.
1. With control power OFF, connect the PC cable to the RS232 slot on FX01/701 SCN
1
2. Flip over dip SW 8 on the FX01/701
3. Start communication program (preferably ProComm plus) on the PC
4. Set communication parameters on PC as follows:
(for ProComm: Press ALT P, change as following, and save before proceeding)