C FIX Report0

1) The document provides design specifications and results for a fischer Bolt anchor FAZ II 10/10 zinc plated steel anchor with an anchorage depth of 40mm in normal weight concrete. 2) The design was conducted using the TR055/ETAG 001 Annex C Method A approach and results in a maximum tensile load capacity of 2.95kN and maximum utilization ratios of 36.2% for concrete cone failure. 3) The input parameters included a 167mm x 120mm x 6mm base plate on cracked, dry concrete without edge reinforcement and subjected to static loading conditions. The output verifies the anchor design is sufficient to resist the specified design loads.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
135 views7 pages

C FIX Report0

1) The document provides design specifications and results for a fischer Bolt anchor FAZ II 10/10 zinc plated steel anchor with an anchorage depth of 40mm in normal weight concrete. 2) The design was conducted using the TR055/ETAG 001 Annex C Method A approach and results in a maximum tensile load capacity of 2.95kN and maximum utilization ratios of 36.2% for concrete cone failure. 3) The input parameters included a 167mm x 120mm x 6mm base plate on cracked, dry concrete without edge reinforcement and subjected to static loading conditions. The output verifies the anchor design is sufficient to resist the specified design loads.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

C-FIX 1.65.0.

0
Database version
2017.12.4.14.32
Date
27/12/2017

fischer FZE

Jebel Ali Free Zone Warehouse No XB


01
P.O. Box 261738 Dubai

[email protected]
www.fischer.ae

Design Specifications
Anchor
Anchor system fischer Bolt anchor FAZ II
Anchor Bolt anchor FAZ II 10/10, zinc plated steel
Anchorage depth 40 mm
Design Data Anchor design in Concrete according European Technical
Assessment ETA-05/0069, Option 1,
Issued 03/07/2017

Geometry / Loads / Scale units


mm, kN, kNm

Value of design actions (including

partial safety factor for the load) Static

Not drawn to scale

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 1
C-FIX 1.65.0.0
Database version
2017.12.4.14.32
Date
27/12/2017

Input data

Design method TR055/ETAG 001, Annex C, Method A


Base material Normal weight concrete, C35/45, EN 206
Concrete condition Cracked, dry hole
Reinforcement No or standard reinforcement. No edge reinforcement. With
reinforcement against splitting
Drilling method hammer drilling
Installation type Push-through installation
Annular gap Annular gap not filled
Type of loading Static or quasi-static
Base plate location Base plate flush installed on base material
Base plate geometry 167 mm x 120 mm x 6 mm
Profile type Customized profile

Design actions *⁾
# NSd VSd,x VSd,y MSd,x MSd,y MT,Sd Type of loading
kN kN kN kNm kNm kNm
1 5.89 0.00 -2.83 0.00 0.00 0.00 Static or quasi-static

*⁾ The required partial safety factors for actions are included

Resulting anchor forces


Tensile action Shear Action Shear Action x Shear Action y
Anchor no. kN kN kN kN
1 2.95 1.42 0.00 -1.42
2 2.95 1.42 0.00 -1.42

max. concrete compressive strain : 0.00 ‰


max. concrete compressive stress : 0.0 N/mm²
Resulting tensile actions : 5.89 kN , X/Y position ( 0 / 0 )
Resulting compression actions : 0.00 kN , X/Y position ( 0 / 0 )

Resistance to tension loads

Action Capacity Utilisation βN


Proof kN kN %
Steel failure * 2.95 18.87 15.6
Pullout failure * 2.95 11.61 25.4
Concrete cone failure 2.95 8.15 36.2

* Most unfavourable anchor

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 2
C-FIX 1.65.0.0
Database version
2017.12.4.14.32
Date
27/12/2017

Steel failure

( NRd,s )

NRk,s γMs NRd,s NSd βN,s


kN kN kN %
28.30 1.50 18.87 2.95 15.6

βN,s
Anchor no. % Group N° Decisive Beta
1 15.6 1 βN,s;1
2 15.6 2 βN,s;2

Pullout failure

( NRd,p )

NRk,p Ψc γMp NRd,p NSd βN,p


kN kN kN %
17.42 1.340 1.50 11.61 2.95 25.4

The given Psi,c-factor may has been determined by interpolation.

βN,p
Anchor no. % Group N° Decisive Beta
1, 2 25.4 1 βN,p;1

Concrete cone failure

( NRd,c )

Eq. (5.2)

Eq. (5.2a)

Eq. (5.2c)

Eq. (5.2d)

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 3
C-FIX 1.65.0.0
Database version
2017.12.4.14.32
Date
27/12/2017

Eq. (5.2e)

NRk,c γMc NRd,c NSd βN,c


kN kN kN %
12.22 1.50 8.15 2.95 36.2

βN,c
Anchor no. % Group N° Decisive Beta
1 36.2 1 βN,c;1
2 36.2 2 βN,c;2

Resistance to shear loads

Proof Action Capacity Utilisation βV


kN kN %
Steel failure without lever arm * 1.42 17.12 8.3
Concrete pry-out failure 1.42 21.18 6.7
Concrete edge failure 2.83 39.46 7.2

* Most unfavourable anchor

Steel failure without lever arm

( VRd,s )

VRk,s γMs VRd,s VSd βVs


kN kN kN %
21.40 1.25 17.12 1.42 8.3

βVs
Anchor no. % Group N° Decisive Beta
1 8.3 1 βVs;1
2 8.3 2 βVs;2

Concrete pry-out failure

( VRd,cp )

Eq. (5.6)

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 4
C-FIX 1.65.0.0
Database version
2017.12.4.14.32
Date
27/12/2017

Eq. (5.2)

Eq. (5.2a)

Eq. (5.2c)

Eq. (5.2d)

Eq. (5.2e)

VRk,cp γMc VRd,cp VSd βV,cp


kN kN kN %
31.77 1.50 21.18 1.42 6.7

βV,cp
Anchor no. % Group N° Decisive Beta
1 6.7 1 βV,cp;1
2 6.7 2 βV,cp;2

Concrete edge failure

( VRd,c )

Eq. (5.7)

Eq. (5.7a)

Eq. (5.7b/c)

Eq. (5.7e)

Eq. (5.7f)

Eq. (5.7g)

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 5
C-FIX 1.65.0.0
Database version
2017.12.4.14.32
Date
27/12/2017

Eq. (5.7h)

VRk,c γMc VRd,c VSd βV,c


kN kN kN %
59.19 1.50 39.46 2.83 7.2

βV,c
Anchor no. % Group N° Decisive Beta
1, 2 7.2 1 βV,c;1

Utilization of tension and shear loads

Tension loads Utilisation βN Shear Loads Utilisation βV


% %
Steel failure * 15.6 Steel failure without lever arm * 8.3
Pullout failure * 25.4 Concrete pry-out failure 6.7
Concrete cone failure 36.2 Concrete edge failure 7.2

* Most unfavourable anchor

Resistance to combined tensile and shear loads


Eq. (5.8a)
Proof successful Eq. (5.8b)

Eq. (5.9)

Information concerning the anchor plate


Base plate details
Plate thickness specified by user without proof t = 6 mm

Profile type Customized profile

Technical remarks
All data and information in the software is based on fischer products and common engineering knowledge. Please
check all the proof results against local valid standards and approvals.
As fischer is not the design office, the attached is no guarantee for incorrect input or assumptions. Any
recommendations have to be approved by the building-authority or project engineer. Results are valid only for
anchor system calculated in the attached. If any part of the system is changed, it will invalidate this report and new
calculations would be required. The calculation was done under the assumption that a sufficient
splitting reinforcement is available. In this case the spliiting
failure can be omitted.
The transmission of the anchor loads to the supports of the concrete member shall be shown for the ultimate limit state and
the serviceability limit state; for this purpose, the normal verifications shall be carried out under due consideration of the
actions introduced by the anchors. For these verifications the additional provisions given in the current design method shall
be taken into account.
As a pre-condition the anchor plate is assumed to be flat when subjected to the actions. Therefore, the plate must be
sufficiently stiff. The C-Fix anchor plate design is based on a proof of stresses and does not allow a statement about
the stiffness of the plate. The proof of the necessary stiffness is not carried out by C-Fix.
The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 6
C-FIX 1.65.0.0
Database version
2017.12.4.14.32
Date
27/12/2017

Installation data
Anchor
Anchor system fischer Bolt anchor FAZ II
Anchor Bolt anchor FAZ II 10/10, zinc Art.-No. 94981
plated steel

Accessories Blow-out pump ABG big Art.-No. 89300


Hammer drill bit SDS Plus IV Art.-No. 504140
10/100/160

Installation details
Thread diameter M 10
Drill hole diameter d0 = 10 mm
Drill hole depth h2 = 63 mm
Anchorage depth hef = 40 mm
Drilling method hammer drilling
Drill hole cleaning only blow out by hand
Installation type Push-through installation
Annular gap Annular gap not filled
Installation torque Tinst = 45.0 Nm
Socket size 17 mm
Base plate thickness t = 6 mm
Total fixing thickness tfix = 6 mm
Tfix,max tfix, max = 30 mm

Base plate details


Base plate material Customized
Base plate thickness t = 6 mm
Clearance hole in base df=12 mm
plate

Attachment
Profile type Customized profile
Distance between profiles 56 mm

Profile dimensions mm
Height 5
Width 120

Anchor coordinates

x y
Anchor no. mm mm
1 -64.25 0
2 64.25 0

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 7