Pages From Iom - 111
Pages From Iom - 111
Pages From Iom - 111
Line
The unit has one 19 mm (3/4-in.) condensate drain ! WARNING
connection on the end of the condensate pan (see Fig. 18).
See Figs. 1, 2 and 3, item “E”, in the view labeled “BACK ELECTRICAL SHOCK HAZARD
(HORIZONTAL DISCHARGE W/O ECON)” for the Failure to follow this warning could result in personal
location of the condensate drain connection. injury or death.
Do not use gas piping as an electrical ground. Unit
cabinet must have an uninterrupted, unbroken
electrical ground to minimize the possibility of
personal injury if an electrical fault should occur. This
ground may consist of electrical wire connected to
unit ground lug in control compartment, or conduit
approved for electrical ground when installed in
accordance with local electrical codes or in absence
of local codes, it is recommended that the U.S.A.
standard ANSI/NFPA 70, National Electrical Code
50TC-- D
(NEC), be followed.
CONDENSATE
DRAIN
CONNECTION NOTE: Field-- supplied wiring shall conform with the
limitations of minimum 33_C (63_F) rise.
C10729 Field power wires are connected to the unit at line-- side
Fig. 18 - Condensate Drain Pan Connection pressure lugs on the terminal block (see Fig. 20 or the
wiring diagram label for control box component
The piping for the condensate drain and external trap can arrangement) or at factory-- installed option non-- fused
be completed after the unit is in place. Hand tighten disconnect switch. Use copper conductors only.
fittings to the drain pan fitting. Provide adequate support
for the drain line. Failure to do so can result in damage to BLK
LOAD
SIDE
MINIMUM PITCH
25 mm (1 in.) PER BASE RAIL
3m (10 ft.) OF LINE
LINE
76 mm SIDE
(3 in.)
OPEN MIN
VENT
SEE
DETAIL A
TO ROOF SEE NOTE
DRAIN
L1
L2
L3
ROOF
CURB DETAIL A
DRAIN PLUG
CONTROL BOX
NOTE: Trap should be deep enough to offset maximum unit static
C11181
difference. A 102 mm (4 in.) trap. is recommended
Fig. 20 - Location of TB1
C11354
Fig. 19 - Condensate Drain Piping Details NOTE: Make field power connections directly to line
connection pressure lugs only.
All units must have an external trap for condensate
The unit is factory wired for the voltage shown on the
drainage. Install a trap at least 102 mm (4-in.) deep and
nameplate. Refer to unit label diagram for additional
protect against freeze-up. If drain line is installed
information.
downstream from the external trap, pitch the line away from
the unit at 25 mm in 3 m (1-in. per 10 ft) of run. Do not use
a pipe size smaller than the unit connection of 19 mm
(3/4 -in.).
18