SF13 Series Wall Mounted Universal Controller: General
SF13 Series Wall Mounted Universal Controller: General
Features
Universal PID and/or binary control for any analog
input/output signal and range.
Multiple auxiliary functions: heat-cool auto changeover,
automatic enable, setpoint compensation.
Differential, averaging, min and max functions
Cascading of control loops (-W22 type).
Alarm monitoring of low and high limits on all inputs.
Programmable reaction in case of alarm.
Feedback function for inputs and set points.
Functions for dehumidifying, set point shift, cascade
control.
Password protected programmable user and control
parameters.
SF13-W22 also includes
Power Cap protected real-time clock with 48hr power
backup.
7-day programmable schedules, with options including
change of setpoints and direct position of manual
outputs.
Blue backlight.
Applications
Fan coil units VAV Humidifiers Radiant heating
Heat exchangers Air handlers Dehumidifiers Radiant cooling
Zoning Fan, Pump control Ventilation Pressurization
General
SF13-W11: 1 independent control loop, 1 internal temperature sensor, 1 universal input (analog/binary/temp), 2
binary outputs, 1 analog output
SF13-W22: 2 independent control loops, 1 internal temperature sensor, 2 universal inputs, 2 binary outputs, 1
analog output.
Internal temperature sensor standard. Add replaceable humidity element as required: AES-HT-A2 (2%), AES-HT-
A3 (3%), or AES-HT-A5 (5%)
Flexible application configuration is made with a parameter-setting routine using the standard operation terminal.
Name
T C I - W 2 2 - U
Page 1
SF13 Universal Controller
OPERATION
Technical specifications
Notice! Failure to follow specifications and local regulations may cause equipment damage. Misapplication will void
warranty.
Power Supply Power Requirements 24 VAC ±10%, 50/60 Hz,Class 2, 2.0 A, 48 VA max.
24 VDC ±10%
Power Consumption Max. 3 VA
Electrical Connection Terminal Connectors
0.34…2.5 mm2 wire (AWG 24…12)
Clock backup Min. 48 hours
Universal Input Setting for Voltage or Current
Input Signal 0–10 V or 0–20 mA
Resolution 9.76 mV or 0.019 mA (10 bit)
Signal inputs Universal Input Input configured to remote temperature (RT) or digital
input (DI)
Range NTC (Sxx-Tn10 sensor): -40…140 °C (-40…284 °F)
Accuracy -40…0 °C (-40…32 °F): 0.5 K
0…50 °C (32…122 °F): 0.2 K
50…100 °C (122…212 °F): 0.5 K
> 100 °C (> 212 °F): 1 K
Max rH tolerance at 25°C (77°F)
Humidity Sensor AES-HT-Ax: Capacity sensor %rH
Range 0…100 % rH ±5
Measuring Accuracy See Figure to the right ±4
AES-HT-A5
Hysteresis 1% ±3
AES-HT-A3
Repeatability 0.1% ±2
AES-HT-A2
Stability < 0.5% / year ±1
±0
0 10 20 30 40 50 60 70 80 90 10 %rH
Analog Output
Output Signal DC 0–10 V / 0–20 mA
Resolution 9.76 mV /0.019 mA
Maximum Load 20 mA, 500 Ω max.
Signal outputs Relays Outputs
Type of disconnection Micro-interruption
AC Voltage 0…250 VAC, 2(1.2)A max. (Observe local regulation)
DC Voltage 0…30 VDC, 2A max.
Operation To IEC 721-3-3
Climatic Conditions class 3 K5
Temperature 0…50 °C (32…122 °F)
Humidity <95 % r.H. non-condensing
Environment Transport & Storage To IEC 721-3-2 and IEC 721-3-1
Climatic Conditions class 3 K3 and class 1 K3
Temperature -25…70 °C (-13…158 °F)
Humidity <95 % r.H. non-condensing
Mechanical Conditions class 2M2
conforms to
EMC Standard 89/336/EEC EN 61 000-6-1/ EN 61 000-6-3
EMEI Standard 73/23/EEC
Standards Product standards
Automatic electrical controls for EN 60 730 –1
household and similar use
Special requirement on temperature EN 60 730 – 2 – 9
dependent controls
Degree of Protection IP30 to EN 60 529
Pollution Class II (EN 60 730-1)
Safety Class II (IEC 60536) if voltage on DO > 48V
III (IEC 60536) if voltage on DO < 48V
Overvoltage Category II (EN 60 730-1)
Cover, back part Fire proof ABS plastic (UL94 class V-0)
Mounting Plate Galvanized Steel
General Dimension (H x W x D) Front part: 21 x 88 x 88mm (0.8 x 3.5 x 3.5 in.)
Power case: ø 58 x 32 mm (ø 2.3” x 1.3”)
Weight (including package) 248 g (8.8 oz)
Page 2
SF13 Universal Controller
OPERATION
Dimensions, mm(inch)
21 Installation
88 (3.5) 32 (1.2) (0.8)
Install the controller on an easy accessible
interior wall, approx. 1.5 m above the floor
in an area of average temperature.
Avoid direct sunlight or other heat sources,
e.g. the area above radiators and heat
emitting equipment.
Avoid locations behind doors, outside walls
and below or above air discharge grills and
88 (3.5)
diffusers.
Location of mounting is less critical if
external temperature sensors are used.
Ensure adequate air circulation to dissipate
heat generated during operation.
Observe local regulations.
Do not mount in a wet or condensation
prone environments.
Connection
0-250VAC, 0-30VDC
24V AC/DC XU1 XU2
Warning:
Live Electrical
2 3 1 7 1 8 Components!
G Q13 G0 X1 G0X2 XT1 XH1 During installation,
testing, servicing and
1 4 5 16 troubleshooting of
G0 Q14 Q24 G0Y1 SF13-W22
Vector Controls
products, it may be
necessary to work with
YB1 YB2 YM1 live electrical
components. Have a
0V (COM) qualified licensed
electrician or other
0V AC
individual who has been
0-250VAC, 0-30VDC properly trained in
handling live electrical
24V AC/DC XU1 components perform
these tasks. Failure to
follow all electrical
2 3 1 7 safety precautions
G Q13 G0X1 XT1 XH1 when exposed to live
electrical components
1 4 5 1 6 SF13-W11 could result in death or
G0 Q14 Q24 G0 Y1 serious injury.
0V AC
Terminal Description
G0 Power supply: 0V, -24VDC; common for power supply, analog in- and outputs
G Power supply: 24VAC, +24VDC
Q.. Binary outputs: Potential free relays contacts (see technical specification)
Yb1,b2 Binary output common
XU1, u2 Universal input: NTC 10kΩ @ 25°C (77°F), 0…10 V or 0…20 mA(selectable by jumper)
Ym1 Analog output: 0…10 V or 0…20 mA*
XT1 Internal temperature input
XH1 Internal humidity input if AES-HT is inserted
Use copper, twisted pair, conductors only. The operating voltage must comply with the requirements for safety extra-low
voltage (SELV) as per EN 60 730. Use safety insulating transformers class II with double insulation as per EN 60 742;
they must be designed for 100% ON-time. When using several transformers in one system, the connection terminal 1
must be galvanically connected. SF13 is designed for operation of AC 24 V safety extra-low voltage and is short-circuit-
proof. Supplying voltages above AC 24 V to low voltage connections may damage the controller or other devices.
Connection to voltages exceeding 42 V endangers personnel safety.
Page 3
SF13 Universal Controller
OPERATIO ON
Operation mode
m symbols Control sym
mbols
C
Comfort (occupied): All control functions operating per set points Heating (R
Reverse) Activ
ve
E
Economy (uno
occupied): Sett points shifted according to
o 1L07, 2L07 Cooling (Direct)
( Active
e
OFF E
Energy Hold Off:
O Outputs arre off, inputs monitored forr alarms Sche
edule Set
Manual Override
Fan Active
Page 4
SF13 Universal Controller
OPERATION
Clock operation
SF13-W22 contains a quartz clock with battery back-up (not available in SF13-W11). Up to 8 mode changes based on
time and day of the week may be programmed. Also position an output or select a set point directly with a time schedule.
A blinking clock indicates that the time has not been setor thatthe unit has been without power for longer than 48 hours.
The time needs to be set to allow time schedules to operate.
Clock setup
Press OPTION > 2 sec. SEL and current time displayed SEL
Press OPTION< 2 sec. to change time,
Minutes blink: UP/DOWN to change, OPTION to save minutes, 00:00
Hours blink: UP/DOWN to change, OPTION to save hour,
Press OPTION to save time,
DAY1 (Mon)
DAY1 blinks: UP/DOWN to change, OPTION to save day
Enable/disable time schedules
Press OPTION > 2 sec. SEL and current time displayed SEL Pro
Press UP:
SEL and PRO displayed, clock symbol blinks PRO OFF/ON
Press OPTION:
Time schedule status displayed OFF or ON:
Press OPTION
OFF/ ON blinks, UP/DOWN to change, OPTION to save
Creating time schedules
Step 1: Select a switching time (Up to 8, Pr01–Pr08)
Press UP while PRO-ON displayed:
Large digits display Pr01, small digits display 00:00 Pr01
Press OPTION:00:00 blinks
Press UP/DOWN to select Pr01switching time from 00:00–23:45 08:00
Press OPTION to save switching time (bar appears indicating step 1 complete):
DAY 1 blinks
Step 2: Apply selected switching time (Pr01) to DAY1 (Mon) – DAY 7 (Sun)
While Pr01 is displayed and DAY1 is blinking: Pr01
Press UP: Activate Pr01 switching time for DAY1 (triangle appears on 1),
Press DOWN: DAY1
Deactivate Pr01 switching time for DAY1(triangle disappears)
Press OPTION to save Pr01 DAY1 (2nd bar indicates step 2 complete):
Repeat for DAY2 – DAY7
1234567
Page 5
SF13 Universal Controller
SETUP AND CONFIGURATION
1. Press UP/DOWN buttons simultaneously for three seconds. The display will show firmware version and revision
number. Press the OPTION button to start login.
2. CODE is shown in small display.
3. Code to access user parameters is 009, control parameter is 241. The access numbers are fixed and cannot be
changed.
4. Select this using UP/DOWN buttons.
5. Press OPTION after selecting the correct code.
6. Once logged in with 009, the user/display parameters are displayed immediately. Once logged in with 241 control
modules are displayed (Lp1, Lp2, 1u, 2u, etc.) –select with UP/DOWN and open with OPTION. As soon as the module
is open its parameters are displayed.
7. Select the parameters with the UP/DOWN buttons. Change a parameter by pressing the OPTION button. Three arrows
are displayed to indicate that the parameter may be modified. Use UP/DOWN buttons to adjust the value.
8. After you are done, press OPTION to save the new value and return to the selection level (arrows disappear when
selection is saved). Pressing left hand POWER button without pressing OPTION will discard the value and return
without saving. For control parameters press POWER again to leave parameter selection and return to control module
selection.
9. Press the POWER to leave the menu. The unit will return to normal operation if no button is pressed for more than 5
minutes.
Page 6
TSF13 Universal Controller
USER CONFIGURATION
Page 7
SF13 Universal Controller
INPUT CONFIGURATION
Set jumpers on the back of the controller: 0–10VDC (default), 0–20mA, or RT/DI (passive temperature or binary)
Further define analog inputs with U00
Match sensor range to input display. With a differential pressure transmitter having 0–200 Pa measuring range set
UO1 display minimum to 0 and U02 display maximum to 200. The allowable range value of -50–205 may be adjusted
with multipliers inU03. The largest displayable values are -990–9999. Limiting range increases resolution. Applies to
analog as well as passive temperature inputs.
For binary input (open/close contact) set the jumper to RT/DI and parameter U00 to an analog input. An open
contact reads as a high value (100%), a closed contact as a low value (0%).
Enable / Disable an alarm. Setting the alarm enable to OFF will prevent the alarm from being displayed on screen. It
may never the less be used to control an output by setting the appropriate output alarm flags. This way, an alarm
limit may be used as interlock.
Specify the input value that triggers an alarm. Hysteresis is the difference between alarm level input and value
required to turn the alarm off. An alarm is displayed as text if enabled (see table). Alarm text can be set to blink
continuously until acknowledged by pressing the OPTION button or only while the alarm conditions are active (see
user parameter UP15).
Input 1T 1H 1U 2U
Low limit ALA1 ALA3 ALA5 ALA7
High limit ALA2 ALA4 ALA6 ALA8
Calculate mathematical functions over multiple inputs for loop control or display with xU12. In order to calculate
average, minimum or maximum between several inputs, make sure all the inputs are of identical type and range and
then activate the same function on xU12 on all the selected inputs. The largest input of the group selected will carry
the calculated value. For example: When average is activated on 2U12 and 1U12 = 1, the average is carried on
UI2.UI2 may now be used as input for control loops and it will show the average value of UI1 and UI2 combined. It is
possible to use different functions on different inputs. For example: minimum of UI1 and UI3 and maximum of UI2
and UI4.
The differential function may only be calculated on subsequent inputs. Such as UI2-UI1. The function must only be
activated on the minuend (UI2 in this example). The displayed value of the minuend will change into the difference:
UI2 in – UI1 = UI2 out. It is possible to have multiple differentials on one controller. It is not possible to reverse the
subtraction to UI1-UI2.
Page 8
SF13 Universal Controller
CONTROL LOOP CONFIGURATION
Page 9
SF13 Universal Controller
CONTROL LOOP CONFIGURATION
PI control sequence
Parameter Description Range Default
1L 09 Offset for heating PI sequence per input 0
1L 10 Offset for cooling PI sequence per input 0
1L 11 P-band heating per input 2.0°C(4.0°F)
1L 12 P-band cooling per input 2.0°(4.0°F)
Integral gain heating (0.1 steps)
1L 13 0–25.5 0.0
low= slow reaction, high= fast reaction
1L 14 Integral gain cooling(0.1 steps) 0–25.5 0.0
Measuring interval integral (seconds)
1L 15 0–255 1 sec.
low= fast reaction, high value= slow reaction
Proportional control(P-band)
The proportional control function calculates the output based on the difference between setpoint and measured value.
The proportional band (P-band) defines the difference between setpoint and measured value which will result in a 100%
output. For example, with a heating or reverse 0-10v control sequence, and a 2.0°C (4.0°F) P-band value, at 10v the
controller will be 2.0°C (4.0°F) below setpoint. This is the working range of the proportional control sequence.
Setting the proportional band to 0 disables proportional control.
Integral and Differential control
Proportional control is in most cases a very stable control mode. The flaw of proportional control alone, however, is
that the setpoint is normally not reached. As the measured value gets closer to the setpoint, the output reduces until
it reaches a point, a fraction above or below the setpoint, where the output equals the load. To reach the setpoint and
achieve a higher level in comfort the Integral/Differential function should be activated.
Integral Gain (KI)dynamically increases the output by the selected KI value every Measuring Interval TI until the
setpoint is reached. The challenge is to prevent hunting, where the output increases too fast, the temperature
overshoots the setpoint, the output goes to 0, the temperature undershoots the setpoint, and the cycle repeats itself.
Hunting may result if the integral gainis too high or measuring interval too short. Each system is different. To prevent
instability the P-band should be extended when integral gain is active (L14 or L15 set above 0).
Setting the integral gain to 0 disables integral and differential control.
Recommended Values
heating (air) heating (radiant) humidifying cooling dehumidifying pressure
P-band 2–3°C(4–6°F) 1–1.5°C(2–3°F)
Measuring interval (TI) 2 5 15 1 70 1
Integral gain (KI) 0.2 0.1 0.1 0.2 0.3 0.8
Page 10
SF13 Universal Controller
CONTROL LOOP CONFIGURATION
Digital control sequence
Parameter Description Range Default
Action of stages:
0= cumulative :stage 1 stays on when 2 on comes on
1L 16 0–2 0
1= single :stage 1 turns off when 2 on comes on
2= digital: stage 1 only, stage 2 only, then stage 1 plus 2
1L 17 Offset for heating/reverse binary sequences per input 0.0°(0.0°F)
1L 18 Offset for cooling/direct binary sequences per input 0.0°(0.0°F)
1L 19 Switching span heating per input 1.0°(2.0°F)
1L 20 Switching span cooling per input 1.0°(2.0°F)
1L 21 Switching hysteresis per input 0.5°(1.0°F)
1L 22 Switching delay 0–255s 10s
Activation of reverse/direct (heat/cool) sequence
OFF= activates based on demand
1L 23 ON/OFF OFF
ON = follows heat/cool state of controller: Set manually or by
auxiliary function (FU20-FU23)
1L 24 Delay for heat /cool changeover when L23=OFF 0–255 min 5 min
Cumulative stage action (L16=0)is typically used in electric heat applications, and single stage action (L16=1)in fan
speed applications. Digital stage action (L16=2) is especially useful in electric heat applications to generate three
steps with just two outputs. For example: Step 1=100W, step 2=200W, step 3=300W.
Switching hysteresis (L21) is the difference between switching on and switching off. A small hysteresis will increase
the number of switching cycles and thus the wear on associated equipment.
With switching delay (L22) cumulative stages will not switch on simultaneously. With a sudden demand or initial
power stage 2 will not start earlier than 10 seconds (default value) after stage 1 has been initiated.
Legend
QH2, QR2 QC1, QD1 QC2, QD2 T, U Input signal
ON OQH Offset heating/direct
OQC Offset cooling/reverse
XDZ Dead zone
XSBY Economy set point shift
WH WC
OFF WH Set point heating/reverse
OSH XDZ OSC T [°C, F] WC Set point cooling/direct
XH
U [V, mA] QC, QD Binary sequences cooling/direct
QH, QR Binary sequences heating/reverse
Page 11
SF13 Universal Controller
OUTPUT CONFIGURATION
Output configuration
Analog output configuration (1A)
Parameter Description Range Default
Select control loop or special function (0= OFF):
1= LP1, 2= LP2
1A 00 3= Dehumidify (4 pipe, max LP1 cooling, LP2 direct) 0–5 1
4= Manual position ingor by time schedule (0–100%)
5= Transmit value of an input
When 1A00=1configure output:
0= Heating/reverse
1= Cooling/direct
2= Heating and cooling (2 pipe)
3= Transmit set point
1A 01 0–4 0
When 1A00 = 4 Manual positioning or time schedule controlled
0 = time schedule only
1 = manual positioning and by time schedule
When 1A00=5, select input (0= function disabled):
1= 1T, 2= 1H, 3= 1U, 4= 2U
1A 02 Type of output signal: OFF= 0–10V, 0–20mA, ON= 2–10V, 4–20mA ON/OFF OFF
1A 03 Minimum limitation of output signal default and in loop heating mode 0–100% 0
1A 04 Maximum limitation of output signal default and in loop heating mode 0–100% 100%
1A 05 Minimum limitation of output signal in loop cooling mode 0–100% 0%
1A 06 Maximum limitation of output signal in loop cooling mode 0–100% 100%
Choose alarm to set output to 100% (output 0%on conflicting alarms)
1A 07 ALA1–ALA8
Alarm: 1 2 3 4 5 6 7 8
Choose alarm to set output to 0%. (output 0% on conflicting alarms)
1A 08 ALA1–ALA8
Alarm: 1 2 3 4 5 6 7 8
1A 09 Transmit value (1A00=5): minimum input value per input 0°C
1A 10 Transmit value (1A00=5): maximum input value per input 100°C
Set jumpers on the back of the controller: 0–10VDC (default), or 0–20mA.Further define analog outputs with
A02.Custom ranges can be created by setting minimum and maximum signal limits.
A control loop, special function, digital control or analog control sequence is not active until it is assigned an output.
Low and high limit alarms are defined with input parameters. With output parameters assign an Output Priority
alarm to an output and select output state. The required output for each alarm can be 1. Alarm level low
individually selected. Multiple alarms can be signed to one output. If one alarm is selected to 2. Alarm level high
simultaneously activate and deactivate an output, the one to de-activate has precedence. 3. Operation mode OFF
4. Control function
With manual positioning (1A00=4) position the output by time schedule or directly in 0.5%
steps. Setting 1A01 to 0 will disable manual positioning. The output will then only be controlled by time schedule.
With dehumidifying (1A00=3)the maximum value is taken of cooling and dehumidifying PI sequences. Cooling will
operate when the humidity is too high (even without demand) and heating will activate to dehumidify the air.
Input values of inputs and set points of control loops may be transmitted on the analog outputs.
For VAV Function individual minimum and
maximum limits may be assigned for cooling and Cooling
heating. In VAV applications maximum cooling YC1,YD1
output matches the maximum air volume the Heating
VAV box is set to deliver. As demand for airflow 100 YH1,YR1
1A06
in cooling mode decreases, airflow dwindles until
it reaches minimum cooling output (1A05). This 50
1A04
minimum will be based on the airflow needed at 1A03 1A05
design cooling and is typically 10% to 15% of 0
WH WC
maximum cooling airflow. When this minimum is
reached the system is in dead-band – neither T (°C/F), U(V, mA)
heating nor cooling. Minimum airflow in heating XDZ
mode is set with 1A03. As the system moves into
heating mode, heating airflow increases until it
reaches the maximum heating output (1A04), typically 30 to 50% of maximum cooling airflow.
Page 12
SF13 Universal Controller
OUTPUT CONFIGURATION
Digital output configuration (1d, 2d)
Settings for floating point outputs (1d00 or 2d00=ON)
Parameter Description Range Default
Enable digital or floating point output
1d00 OFF= 1dand 2d are two digital outputs ON/OFF OFF
ON = 1dand 2d are one floating point output (1d open,2d close)
Select control loop or special function (0= OFF)
1= LP1, 2= LP2
1d01 3= Dehumidify (4 pipe, max LP1 cooling, LP2 direct) 0–5 0
4= Manual positioning (open/close)
5= Controller state functions
If1d01=1 configure output:
0=Heating/reverse
1= Cooling/direct
2= Heating and cooling (2 pipe)
If 1d01 = 4 Manual positioning or time schedule controlled
0 = Time schedule controlled only
1d02 0–5 0
1 = Manual positioning and time schedule controlled
If 1d01=5 select state functions:
0= ON if controller operation state is ON
1= ON while demand on any output
2= ON while controller in heating mode and operation state ON
3= ON while controller in cooling mode and operation state ON
1d03 Running time (from open to close) 0–255s 90s
1d04 Switching difference for floating point signal 0–100s 5s
1d05 Not used
Choose alarm to set output to 100% (output 0% on conflicting alarms)
1d06 ALA1–ALA8
Alarm: 1 2 3 4 5 6 7 8
Choose alarm to set output to 0% (output 0% on conflicting alarms)
1d07 ALA1–ALA8
Alarm: 1 2 3 4 5 6 7 8
1d08 Not used
1d09 Not used
Low and high limit alarms are defined with input parameters. With output parameters assign an Output Priority
alarm to an output and select output state. Each alarm’s required output can be individually 1. Alarm level low
selected. Multiple alarms can be signed to one output. Should one alarm be simultaneously 2. Alarm level high
selected to activate and deactivate the output, the one to de-activate has precedence. 3. Operation mode OFF
4. Control function
With manual positioning (1d01=4) position the output directly (open/close).
With dehumidifying (1d01=3) the maximum value is taken of cooling and dehumidifying. Cooling will operate when
the humidity is too high (even without demand) and heating will activate to dehumidify the air.
For floating point outputs the running time of the actuator used needs to be specified with 1d03. Running time is
defined as the time required for the actuator to run from fully open to fully closed and vice versa. Actuators with a
fixed running time are recommended. Once fully open or fully closed the running time for the actuator is extended for
a full run-time cycle. This will allow the actuator position to be synchronized in case it has been moved during off time
or an actuator with variable running time was used. Use switching difference parameter 1d04, to reduce the switching
frequency of the actuator. The actuator will only move if the difference to the current actuator position is larger than
this parameter.
State functions (1d01=5)activate the output based on certain conditions with or without a demand for heating or
cooling, in either comfort or standby mode. In Energy Hold OFF mode (EHO) the output will be off.
Page 13
SF13 Universal Controller
OUTPUT CONFIGURATION
Digital output configuration (1d, 2d)
Settings for digital outputs (1d00 or 2d00=OFF)
Parameter Description Range Default
Enable digital or floating point output
1d 00 OFF= 1d and 2d are two digital outputs ON/OFF OFF
ON = 1d and 2d are one floating point output (1d open,2d close)
Select control loop or special function (0= OFF)
1= LP1, 2= LP2
1d 01 3= Dehumidify (4 pipe, max LP1 cooling, LP2 direct) 0–5 0
4= Manual positioning (on/off)
5= State functions
When 1d01=1, configure output:
0= Stage 1 heating/reverse
1= Stage 1 cooling/direct
2= Stage 1 heating and cooling, reverse and direct
3= Stage 2 heating/reverse
4= Stage 2 cooling/direct
5= Stage 2 heating and cooling, reverse and direct
1d 02 If 1d01 = 4 Manual positioning or time schedule controlled 0–5 0
0 = Time schedule controlled only
1 = Manual positioning and time schedule controlled
When 1d01=5, select state functions:
0= ON if controller operation state is ON
1= ON while demand on any output
2= ON while controller in heating mode and operation state ON
3= ON while controller in cooling mode and operation state ON
Switch-off delay (time output active with no more demand)
1d 03 0–255 90sec
Delay is in seconds or minutes depending on d09
Switch-on delay(time demand active before output on)
1d 04 In state mode 1d01=5 outputs disabled during switch-on delay 0–255 5 sec
Delay is in seconds or minutes depending on d09
1d 05 Activate PWM, set cycle time, seconds (>0activates, 0 deactivates) 0–1650s 0s
Choose alarm to set output to ON (output OFF on conflicting alarms)
1d 06 ALA1–ALA8
Alarm: 1 2 3 4 5 6 7 8
Choose alarm to set output to OFF (output OFF on conflicting alarms)
1d 07 ALA1–ALA8
Alarm: 1 2 3 4 5 6 7 8
1d 08 Display fan symbol while active ON/OFF OFF
1d 09 Binary switching delays in minutes or seconds ON, OFF OFF
OFF = delays are in seconds, ON = delays are in minutes
Low and high limit alarms are defined with input parameters. With output parameters assign Output Priority
an alarm to an output and select output state. Each alarm’s required output can be 1. Alarm level low
individually selected. Multiple alarms can be signed to one output. Should one alarm be 2. Alarm level high
simultaneously selected to activate and deactivate the output, the one to de-activate has 3. Operation mode OFF
precedence. 4. Control function
Page 14
SF13 Universal Controller
AUX FUNCTIONS CONFIGURATION
Auxiliary functions
Summer/winter compensation
Parameter Description Range Default
Select compensation input (0= function disabled):
Fu 00 0–4 0
1= 1T, 2= 1H, 3= 1U, 4= 2U
Winter compensation set point setback
Fu 01 OFF= shift toward control loop heating set point minimum ON/OFF OFF
ON= shift toward control loop heating set point maximum
Fu 02 Winter compensation lower limit value – end shift per input 5°C(41°F)
Fu 03 Winter compensation upper limit value – start shift per input 20°C(68°F)
Summer compensation set point setback
Fu 04 OFF= shift toward control loop cooling set point minimum ON/OFF ON
ON= shift toward control loop cooling set point maximum
Fu 05 Summer compensation lower limit value – start shift per input 35°C(95°F)
Fu 06 Summer compensation upper limit value – end shift per input 40°C(104°F)
Fu 07 Show hot/cool symbol while compensation active ON/OFF OFF
Comfort/economy mode changeover
Fu 08 Select comfort/economy changeover input (0= disabled): 0–4 0
1= 1T, 2= 1H, 3= 1U, 4= 2U
Fu 09 Economy activation delay (seconds) -1275s 300s
Fu 10 Input limit 1 per input 10
Fu 11 Input limit 2 Per input 90
Summer/winter compensation changes the set point due to a change in an input value, typically, but not limited to,
an outdoor temperature input. Winter compensation starts when outside temperature drops below the upper limit of
winter compensation (FU03). At maximum winter compensation the actual set point will be equal to the control loop’s
maximum heating set point (L02). Summer compensation starts when outside temperature exceeds the lower limit
for summer compensation (FU05). At maximum summer compensation the actual set point will be equal to the
control loop’s maximum cooling set point (L04). Activate summer/winter compensation with control loop configuration
parameter(L05).
W
1L01 FU04-OFF
FU01-OFF
1L03
T [°C,F],
U[V,mA]
Use comfort/economy mode changeover with key card switches, occupancy sensors, etc. Set input limit 1 and 2 with
possibilities below. Example: When Limit 2 is greater than Limit 1, switch comfort-to-economy at the lower value,
economy-to-comfort at the higher value. Activate comfort/economy change over with loop configuration
parameter(L07).
Standby Standby
Page 15
SF13 Universal Controller
AUX FUNCTIONS CONFIGURATION
Enable/disable
Parameter Description Range Default
Fu 12 Select enable–disable input (0=function disabled): 0–4 0
1= 1T, 2= 1H, 3= 1U, 4= 2U
FU 13 Manual override permitted (without waiting for delay). This function ON/OFF OFF
allows starting the controller, even the enable conditions are not met.
The controller will switch off again if the running conditions are not met
until the disable delay is expired.
Fu 14 Enable delay (seconds) 0–1275s 0
Fu 15 Disable delay (seconds) 0–1275s 300
Fu 16 Range of limits: ON/OFF OFF
OFF = When limit 2 is greater than limit 1, enable when input value is
greater than limit 2,disable when input value is less than limit 1. When
limit 2 is less than limit 1, enable when input value less than limit 1,
disable when input value is greater than limit 2.
ON = When limit 2 is greater than limit 1enable when input value is
between limit 1 and limit 2. When limit 2 is less than limit 1, enable
when input value below limit 2 or above limit 1
Fu 17 Input limit 1 per input 10
Fu 18 Input limit 2 Per input 90
Fu 19 Disable in case of alarms Selection
Enable or disable the controller based on desired input values, such as high or low temperature, occupancy sensor,
window contact, etc. Can be used as and function where several conditions must be met before disable or enable.
Time schedules do not override, but manual override is permitted. Delay times may be assigned for both enable and
disable (allows for the controller to start before validation of operation values takes place). Set input limit 1 and 2
with options below. Example: With FU16=OFF, and Limit 2 > Limit 1, switch enable-to-disable at Limit 1, disable-to-
enable at Limit 2.
Enable Enable
Mode Mode
FU16 = OFF
Disable Disable
Limit Limit Limit Limit
Input Input
1 2 2 1
Enable
Mode Mode
Enable
FU16 = ON
Disable Disable
Limit Limit Limit Limit Input
Input
1 2 2 1
Page 16
SF13 Universal Controller
AUX FUNCTIONS CONFIGURATION
Heating/cooling mode changeover
Parameter Description Range Default
Fu 20 Select heat/cool changeover input (0=function disabled): 0–6 0
1= 1T, 2= 1H, 3= 1U, 4= 2U, 5= h/c status loop 1,
6= h/c status loop 2
Fu 21 Cooling activation delay (seconds) 0–1275s 300
Fu 22 Input limit 1 per input 20
Fu 23 Input limit 2 per input 40
Switch heating/cooling state based on a universal input value. The input may be from a supply media (air or water)
or outdoor air temperature sensor. For supply media temperature we recommend switching to cooling at 16°C/61°F
and to heating at 28°C/83°F. For outdoor temperature we recommend switching to cooling at 28°C/83°F and to
heating at 16°C/61°F outdoor temperature. These recommendations are given as suggestions. The ideal settings may
be different on the actual project depending on climatic and system conditions.
The change between heating and cooling is delayed to avoid unnecessary switching (FU21). Heat/cool status of one
control loop may also be determined by the heat/cool state of the other loop (FU20= 5 or 6). The control loop used to
determine the heat /cool state must be set to demand-based heating and cooling with (L23). Set limit 1 and limit 2 to
switch between heating and cooling with options below. Example: When Limit 2 is greater than Limit 1, switch heat to
cool at Limit 1, cool to heat at Limit 2. For binary open/close contact, open is a high value (100%), closed is a low
value (0%).
Cool Cool
Page 17
SF13 Universal Controller
AUX FUNCTIONS CONFIGURATION
Page 18
SF13 Universal Controller
AUX FUNCTIONS CONFIGURATION
Page 19
SF13 Universal Controller
AUX FUNCTIONS CONFIGURATION
Page 20