Practical: Aim:-One Line Diagram

This document provides a load flow analysis report using the Gauss-Seidel method for a power system with 3 buses, 3 transmission lines, 2 generators and 2 loads. It includes details of the network configuration, generator and load specifications, line parameters, bus data, and results of the load flow calculation including bus voltages and line flows. The analysis was performed with a base MVA of 100 MVA and considered the system's nominal operating conditions.

Uploaded by

Mitesh Gandhi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
68 views10 pages

Practical: Aim:-One Line Diagram

This document provides a load flow analysis report using the Gauss-Seidel method for a power system with 3 buses, 3 transmission lines, 2 generators and 2 loads. It includes details of the network configuration, generator and load specifications, line parameters, bus data, and results of the load flow calculation including bus voltages and line flows. The analysis was performed with a base MVA of 100 MVA and considered the system's nominal operating conditions.

Uploaded by

Mitesh Gandhi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 10

PRACTICAL

Aim:-

One line diagram:-

Report:-
LOAD FLOW BY GAUSS-SIEDEL METHOD
CASE NO : 1 CONTINGENCY : 0 SCHEDULE NO : 0
CONTINGENCY NAME : Base Case RATING CONSIDERED : NOMINAL
-------------------------------------------------------------------------------
VERSION NUMBER : 7.3
%% First Power System Network
LARGEST BUS NUMBER USED : 3 ACTUAL NUMBER OF BUSES : 3
NUMBER OF 2 WIND. TRANSFORMERS : 0 NUMBER OF 3 WIND.
TRANSFORMERS : 0
NUMBER OF TRANSMISSION LINES : 3
NUMBER OF SERIES REACTORS : 0 NUMBER OF SERIES CAPACITORS : 0
NUMBER OF CIRCUIT BREAKERS : 0
NUMBER OF SHUNT REACTORS : 0 NUMBER OF SHUNT CAPACITORS :0
NUMBER OF SHUNT IMPEDANCES : 0
NUMBER OF GENERATORS : 2 NUMBER OF LOADS : 2
NUMBER OF LOAD CHARACTERISTICS : 0 NUMBER OF UNDER FREQUENCY
RELAY: 0
NUMBER OF GEN CAPABILITY CURVES: 0 NUMBER OF FILTERS : 0
NUMBER OF TIE LINE SCHEDULES : 0
NUMBER OF CONVERTORS : 0 NUMBER OF DC LINKS : 0
NUMBER OF SHUNT CONNECTED FACTS: 0
POWER FORCED LINES : 0
NUMBER OF TCSC CONNECTED : 0
NUMBER OF SPS CONNECTED : 0
NUMBER OF UPFC CONNECTED : 0
-------------------------------------------------------------------------------
LOAD FLOW WITH GAUSS-SEIDEL METHOD : 5
NUMBER OF ZONES : 1
PRINT OPTION : 4 - DETAILED PRINT
PLOT OPTION : 1 - PLOTTING WITH PU VOLTAGE
NO FREQUENCY DEPENDENT LOAD FLOW, CONTROL OPTION: 0
BASE MVA : 100.000000
NOMINAL SYSTEM FREQUENCY (Hzs) : 50.000000
FREQUENCY DEVIATION (Hzs) : 0.000000
FLOWS IN MW AND MVAR, OPTION :0
SLACK BUS : 1
TRANSFORMER TAP CONTROL OPTION : 0
Q CHECKING LIMIT (ENABLED) : 4
REAL POWER TOLERANCE (PU) : 0.00100
REACTIVE POWER TOLERANCE (PU) : 0.00100
MAXIMUM NUMBER OF ITERATIONS : 15
BUS VOLTAGE BELOW WHICH LOAD MODEL IS CHANGED : 0.75000
CIRCUIT BREAKER RESISTANCE (PU) : 0.00000
CIRCUIT BREAKER REACTANCE (PU) : 0.00010
TRANSFORMER R/X RATIO : 0.05000

------------------------------------------------------------------------------
ANNUAL PERCENTAGE INTEREST CHARGES : 15.000
ANNUAL PERCENT OPERATION & MAINTENANCE CHARGES : 4.000
LIFE OF EQUIPMENT IN YEARS : 20.000
ENERGY UNIT CHARGE (KWHOUR) : 2.500 Rs
LOSS LOAD FACTOR : 0.300
COST PER MVAR IN LAKHS : 5.000 Rs

-------------------------------------------------------------------------------
ZONE WISE MULTIPLICATION FACTORS
ZONE P LOAD Q LOAD P GEN Q GEN SH REACT SH CAP C LOAD

---- -------- -------- -------- -------- -------- -------- --------


0 1.000 1.000 1.000 1.000 1.000 1.000 1.000
1 1.000 1.000 1.000 1.000 1.000 1.000 1.000
-------------------------------------------------------------------------------
BUS DATA
BUS NO. AREA ZONE BUS KV VMIN-PU VMAX-PU NAME

------- ---- ---- -------- -------- -------- --------


1 1 1 220.000 0.950 1.050 Bus1
2 1 1 220.000 0.950 1.050 Bus2
3 1 1 220.000 0.950 1.050 Bus3

-------------------------------------------------------------------------------
TRANSMISSION LINE DATA
STA CKT FROM FROM TO TO LINE PARAMETER RATING KMS kV
NODE NAME* NODE NAME* R(P.U) X(P.U.) B/2(P.U.) MVA
--- --- ---- -------- ---- -------- --------- --------- --------- ------ ----- -----
3 1 1 Bus1 2 Bus2 0.00850 0.07200 0.07450 1000 1.0
3 1 1 Bus1 3 Bus3 0.01000 0.10000 0.10000 1000 1.0
3 1 2 Bus2 3 Bus3 0.01200 0.01000 0.10500 1000 1.0

-------------------------------------------------------------------------------
TOTAL LINE CHARGING SUSCEPTANCE : 0.55900
TOTAL LINE CHARGING MVAR AT 1 PU VOLTAGE : 55.900
-------------------------------------------------------------------------------
TOTAL CAPACITIVE SUSCEPTANCE : 0.00000 pu - 0.000 MVAR
TOTAL INDUCTIVE SUSCEPTANCE : 0.00000 pu - 0.000 MVAR
-------------------------------------------------------------------------------
GENERATOR DATA
SL.NO* FROM FROM REAL Q-MIN Q-MAX V-SPEC CAP. MVA STAT
NODE NAME* POWER(MW) MVAR MVAR P.U. CURV RATING
------ ---- -------- --------- --------- --------- --------- ---- ------- ----
1 2 Bus2 50.0000 -999.0000 999.0000 1.0000 0 1000.00 3
2 1 Bus1 90.0000 -999.0000 998.7490 1.0200 0 1000.00 3
-------------------------------------------------------------------------------
LOAD DATA

SLNO FROM FROM REAL REACTIVE COMP COMPENSATING MVAR


VALUE CHAR F/V
* NODE NAME* MW MVAR MVAR MIN MAX STEP NO NO
STAT
---- ---- -------- -------- -------- -------- ------- ------- ------- ---- ----
1 2 Bus2 20.000 10.000 0.000 0.000 0.000 0.000 0 0
3 0
2 3 Bus3 100.000 50.000 0.000 0.000 0.000 0.000 0 0
3 0
-------------------------------------------------------------------------------
TOTAL SPECIFIED MW GENERATION : 140.00000
TOTAL MIN MVAR LIMIT OF GENERATOR : -1998.00000
TOTAL MAX MVAR LIMIT OF GENERATOR : 1997.74900
TOTAL SPECIFIED MW LOAD : 120.00000 reduced 120.00000
TOTAL SPECIFIED MVAR LOAD : 60.00000 reduced 60.00000
TOTAL SPECIFIED MVAR COMPENSATION : 0.00000 reduced 0.00000
-------------------------------------------------------------------------------
TOTAL (Including out of service units)
TOTAL SPECIFIED MW GENERATION : 140.00000
TOTAL MIN MVAR LIMIT OF GENERATOR : -1998.00000
TOTAL MAX MVAR LIMIT OF GENERATOR : 1997.74900
TOTAL SPECIFIED MW LOAD : 120.00000 reduced 120.00000
TOTAL SPECIFIED MVAR LOAD : 60.00000 reduced 60.00000
TOTAL SPECIFIED MVAR COMPENSATION : 0.00000 reduced 0.00000

-------------------------------------------------------------------------------
GENERATOR DATA FOR FREQUENCY DEPENDENT LOAD FLOW
SLNO* FROM FROM P-RATE P-MIN P-MAX %DROOP PARTICI BIAS
NODE NAME* MW MW MW FACTOR SETTING
C0 C1 C2
------ ---- -------- -------- --------- --------- --------- --------- ---------
1 2 Bus2 50.000 0.0000 50.0000 4.0000 0.0000 0.0000
0.0000 0.0000 0.0000
2 1 Bus1 50.000 0.0000 100.0000 4.0000 0.0000 0.0000
0.0000 0.0000 0.0000

Acceleration factor : 1.60

Slack bus angle (degrees) : 0.00

OLD-NUMBER NEW-NUMBER
---------- ----------
1 1
2 2
3 3
NEW-NUMBER OLD-NUMBER
---------- ----------
1 1
2 2
3 3
-------------------------------------------------------------------------------
Y BUS IN OLD AND NEW NUMBERING
SLNO. NEW-NUMBER OLD-NUMBER ADMITTANCE
ROW COLUMN ROW COLUMN YBUS.re YBUS.im
----- ------ ------ ------ ------ ---------- ----------
1 1 1 1 1 2.6072 -23.4245
2 1 2 1 2 -1.6171 13.6980
3 1 3 1 3 -0.9901 9.9010
4 2 2 2 2 50.7975 -54.5021
5 2 3 2 3 -49.1803 40.9836
6 3 3 3 3 50.1704 -50.6796

-------------------------------------------------------------------------------
BUS VOLTAGES AT EACH ITERATION1 Bus1 1.020000+j0.000000
0.000000+j0.000000
2 Bus2 0.999987+j0.005196 -0.000013+j0.005196
3 Bus3 0.982249+j-0.006671 -0.017751+j-0.006671
Iteration count = 1 Error = 0.017728 Bus = 3
1 Bus1 1.020000+j0.000000 0.000000+j0.000000
2 Bus2 0.999924+j-0.012337 -0.000063+j-0.017532
3 Bus3 0.994733+j-0.027725 0.012484+j-0.021054
Iteration count = 2 Error = 0.012847 Bus = 3
1 Bus1 1.020000+j0.000000 0.000000+j0.000000
2 Bus2 0.999833+j-0.018254 -0.000091+j-0.005917
3 Bus3 0.988077+j-0.022956 -0.006656+j0.004770
Iteration count = 3 Error = 0.006776 Bus = 3
1 Bus1 1.020000+j0.000000 0.000000+j0.000000
2 Bus2 0.999775+j-0.021219 -0.000059+j-0.002965
3 Bus3 0.992263+j-0.030228 0.004187+j-0.007272
Iteration count = 4 Error = 0.004381 Bus = 3
1 Bus1 1.020000+j0.000000 0.000000+j0.000000
2 Bus2 0.999738+j-0.022905 -0.000037+j-0.001686
3 Bus3 0.989982+j-0.028073 -0.002281+j0.002155
Iteration count = 5 Error = 0.002343 Bus = 3
1 Bus1 1.020000+j0.000000 0.000000+j0.000000
2 Bus2 0.999722+j-0.023577 -0.000016+j-0.000672
3 Bus3 0.991379+j-0.030398 0.001397+j-0.002325
Iteration count = 6 Error = 0.001465 Bus = 3
1 Bus1 1.020000+j0.000000 0.000000+j0.000000
2 Bus2 0.999711+j-0.024025 -0.000011+j-0.000448
3 Bus3 0.990606+j-0.029577 -0.000773+j0.000820
Iteration count = 7 Error = 0.000798 Bus = 3
-------------------------------------------------------------------------------
BUS VOLTAGES AND POWERS
NODE FROM V-MAG ANGLE MW MVAR MW MVAR MVAR
NO. NAME P.U. DEGREE GEN GEN LOAD LOAD COMP
---- -------- ------ ------ -------- -------- -------- -------- --------
1 Bus1 1.0200 0.00 69.753 32.927 0.000 0.000 0.000
2 Bus2 1.0000 -1.38 50.000 -32.048 20.000 10.000 0.000
3 Bus3 0.9910 -1.71 0.000 0.000 100.000 50.000 0.000

-------------------------------------------------------------------------------
NUMBER OF BUSES EXCEEDING MINIMUM VOLTAGE LIMIT (@ mark) : 0
NUMBER OF BUSES EXCEEDING MAXIMUM VOLTAGE LIMIT (# mark) : 0
NUMBER OF GENERATORS EXCEEDING MINIMUM Q LIMIT (< mark) : 0
NUMBER OF GENERATORS EXCEEDING MAXIMUM Q LIMIT (> mark) : 0
-------------------------------------------------------------------------------
LINE FLOWS AND LINE LOSSES
SLNO CS FROM FROM TO TO FORWARD LOSS %
NODE NAME NODE NAME MW MVAR MW MVAR LOADING--
-- -- ---- -------- ---- -------- -------- -------- -------- -------- -------
1 1 1 Bus1 2 Bus2 36.914 16.633 0.1599 -13.8465 4.8&
2 1 1 Bus1 3 Bus3 32.839 16.294 0.1722 -18.5041 4.8&
3 1 2 Bus2 3 Bus3 67.758 -2.117 0.5594 -20.3467 7.0&
-------------------------------------------------------------------------------
! NUMBER OF LINES LOADED BEYOND 125% : 0
@ NUMBER OF LINES LOADED BETWEEN 100% AND 125% : 0
# NUMBER OF LINES LOADED BETWEEN 75% AND 100% : 0
$ NUMBER OF LINES LOADED BETWEEN 50% AND 75% : 0
^ NUMBER OF LINES LOADED BETWEEN 25% AND 50% : 0
& NUMBER OF LINES LOADED BETWEEN 1% AND 25% : 3
* NUMBER OF LINES LOADED BETWEEN 0% AND 1% : 0
-------------------------------------------------------------------------------
ISLAND FREQUENCY SLACK-BUS CONVERGED(1)
------ --------- ----------- ------------
1 50.00000 1 0
-------------------------------------------------------------------------------
Summary of results
TOTAL REAL POWER GENERATION : 119.753 MW
TOTAL REAL POWER INJECT,-ve L : 0.000 MW
TOTAL REACT. POWER GENERATION : 0.879 MVAR
GENERATION pf : 1.000

TOTAL SHUNT REACTOR INJECTION : -0.000 MW


TOTAL SHUNT REACTOR INJECTION : -0.000 MVAR
TOTAL SHUNT CAPACIT.INJECTION : -0.000 MW
TOTAL SHUNT CAPACIT.INJECTION : -0.000 MVAR
TOTAL TCSC REACTIVE DRAWL : 0.000 MVAR
TOTAL SPS REACTIVE DRAWL : 0.000 MVAR
TOTAL UPFC FACTS. INJECTION : -0.0000 MVAR
TOTAL SHUNT FACTS.INJECTION : 0.000 MVAR
TOTAL SHUNT FACTS.DRAWAL : 0.000 MVAR
TOTAL REAL POWER LOAD : 120.000 MW
TOTAL REAL POWER DRAWAL -ve g : 0.000 MW
TOTAL REACTIVE POWER LOAD : 60.000 MVAR
LOAD pf : 0.894
TOTAL COMPENSATION AT LOADS : 0.000 MVAR
TOTAL HVDC REACTIVE POWER : 0.000 MVAR
TOTAL REAL POWER LOSS (AC+DC) : 0.891436 MW ( 0.891436+ 0.000000)
PERCENTAGE REAL LOSS (AC+DC) : 0.744
TOTAL REACTIVE POWER LOSS : -52.697336 MVAR
Zone wise distribution
Description Zone # 1
MW generation 119.7526
MVAR generation 0.8792
MW load 120.0000
MVAR load 60.0000
MVAR compensation 0.0000
MW loss 0.8914
MVAR loss -52.6973
MVAR - inductive 0.0000
MVAR - capacitive 0.0000
Zone wise export(+ve)/import(-ve)
Zone # 1 MW & MVAR
------ -------- -------- 1 -----
Area wise distribution
Description Area # 1
MW generation 119.7526
MVAR generation 0.8792
MW load 120.0000
MVAR load 60.0000
MVAR compensation 0.0000
MW loss 0.8914
MVAR loss -52.6973
MVAR - inductive 0.0000
MVAR - capacitive 0.0000