Mbci PDF
Mbci PDF
Mbci PDF
MBCI
Differential Feeder and
Transformer Feeder
Protection
Differential feeder protection requires a
comparison of the currents entering and
leaving the protected zone. Two MBCI relays
are therefore required, one for each end of the
feeder. A pair of pilot wires is used to transmit
information between the two relays so that
each may be able to compare the current
flowing at its respective end with the current at
the other.
C MODELS AVAILABLE
Trip Trip
> MBCI 01 - Private pilots
Rpp Rpp
T2 T2 > MBCI 02 - Telephone type
T1 Tr Tr T1
Rs Tt øc øc Rs
To To
Pilot wires
OPTIONAL EXTRAS
Ts RVD Ro Ro RVD
V V
> MRTP supervision relay
• Alarm and indication of pilot failure and supervision supply failure
• Suitable for pilot circuits insulated for 5kV or 15kV with pilot isolation
T1 - Summation transformer To - Operating winding Rpp - Pilots padding resistor
T2 - Auxiliary transformer Tr - Restraining winding øc - Phase comparator transformers
RVD - Non linear resistor Tr - Tertiary winding
Ts - Secondary winding Ro - Linear resistor
> MVTW destabilising and Intertripping relay
• Destabilises the feeder protection so that tripping occurs
Figure 1 Basic circuit arrangement
• Intertripping: injects ac voltage into pilot circuit so that tripping occurs
Customer Benefits
> MCRI instantaneous Overcurrent and start/check relay
• High stability for
• High speed operation
through faults
• Fast operation for in • Two phase and earth fault relay
zone faults
• Simultaneous tripping > MCTH transformer inrush Current detector
of relays at each line • Allows MBCI to be applied to transformer feeders
end • Blocks operation of the MBCI relay during transformer inrush conditions
• Low current transformer
requirements
T&D
Protected Zone Protected Zone > Pilot supervision
P1 P2 P2 P1
A
S1 S2 S2 S1
B
C
See
RS
12
13
Note 5 RS Correct interchange of information over the pilot circuit
MBCI Power + MBCI
IA
23 Supply
Circuits 14 VX
–
is essential for the proper functioning of any differential
See
Note 4
24
25
& Enable 11
See
23
24 IA feeder protection. The most common pilot failure is to
Squarer Kt RL1 1
IB 2 Note 2 25
RL1–1 3
26
27 Enable 5 26 IB the open circuit state, caused by the accidental
A 27
IC
I N 28
Level RL2
2 RL1–2
2
4
28 IC excavation of buried pilots or storm damage to
C B Detector 6 IN
Phase OP RL3
Trip/ overhead pilots. With the pilots open circuited the
Rotation KS & RES
1
7
Alarm
RO
Squarer
RL2–1 9
Outputs differential protection will be unstable and will trip the
Case Earth
Case earth See Note 3 8 feeder if sufficient through current is flowing. For this
RL2–2
1
3
2
4
10 reason the circulating current system is often preferred
RPP 17
5 6
7 8 as such schemes will fail safe and trip so that attention
9 10 18 Pilot
11
13
12
14 19
Wires is immediately drawn to the fault.
15 16
17 18
Notes
19 20
1. (a) C.T. shorting links make before (b) & (c) disconnect. 3. Earthing connections are typical only
.
21 22 Module
4. C.T. connections are typical only
.
23 24 terminal block
viewed from
(b)
(c)
Short terminals break before (c)
Long terminal. 5. For overcurrent start schemes, terminal 12 must be
> Destabilising/intertripping
25 26
rear connected directly to D.C. +VE to provide a supply for
27 28
2. Link terminals 11 and 13 except when used with overcurrent the L.E.D. and reset circuits.
check replay type MCRI.
The remote unit of the differential feeder protection can
be caused to operate, provided sufficient line current is
Figure 2 Application diagram: differential feeder
flowing, by open circuiting the pilots. If line current is
protection relay type MBCI
not flowing, the remote unit can be operated
(intertripped) by injecting a current into the pilots.
P6
transformer
S2 S1
transformer
P1
of pilot failure it does not prevent the protection
17 17
P5
P4
P3 X2 X1 operating if primary current above setting is flowing.
P2
MBCI Pilots
P2
MBCI Where this hazard is unacceptable it is necessary to
X2 P3
X1
18
P1 S1 S2
P4
P5
18
add an overcurrent check feature to verify fault
P6
S1 S2 Supervision
isolation
presence.
P1 P2 transformer
20 OP
RL2 RL7
2 1 Supply
19
27
Reset
Fail See
Note 7
> Emergency use for overcurrent protection
A.C. RL1 RL3
OP RL6 1
A.C. Pilot
Auxiliar y Power 2 2
Reset 1
28
Supply S/C RL4–1 3 Output
Supply
13 OP RL8
5 Contacts
Pilot
Vx 14
D.C.
Power
Reset 1
O/C RL4–2
2
4
Change
state for
In the event of a pilot failure which cannot quickly be
Case earth Supply
pilot fail
1 2
RL4
2
6 rectified, the Translay S scheme may be adapted for
3 4
7
Output
5 6 RL5–1 9
Contacts use as a definite time overcurrent relay.
7 8 11
9 10 MRTP 03 Change
8
11 12 +VE
RL5 state for
2 RL5–2 10
13 14 supply
15 16
RL1 RL2 RL3 RL1 RL2 RL3 12 fail
Case –1 –1 –1 Start –2 –2 –2
17 18
Earth t
19 20
21 22
23 24 Note 1.
25 26
(a) C.T. shorting links make before (b) & (c) disconnect.
27 28
Module terminal block (b) Short terminals break before (c).
viewed from rear (c) Long terminal.
F 15kV — • 1 5 1 5
> Symbols:
G 5kV • • 2 1 5 3 1 5
H 15kV • • 4 1 5 1 5
15kV isolating transformer
Table 1. Typical scheme arragements for plain feeders. See key below
.
J 15kV — 1 8 9 7 1 8
K 5kV • 1 8 2 9 7 1 8 3
1 8 4 9 7 1 8
L 15kV •
M 5kV — 1 8 1 8
N 15kV — 1 8 1 8
O 5kV • 1 8 2 1 8 3
1 8 4 1 8
P 15kV •
Table 2. Typical scheme arragements for transformer feeders. See key below
.
The differential feeder protection circuit is derived from Operation of the destabilising relay results in the
the well known Merz-Price circulating current system. summation current transformer in the differential relay
Figure 1 shows the basic circuit arrangement. A being short circuited and the local relay prevented from
summation current transformer T1 at each line end tripping.
produces a single phase current proportional to the
summated three phase currents in the protected line. The remote relay then sees a single end feed condition
The neutral section of the summation winding is and trips, provided the through current exceeds the no-
tapped to provide alternative sensitivities for earth load fault setting of the protection
faults.
iii
on the delta side of the power transformer. The MFAC
C III C
yn 14 high impedance differential relay may be used to
N.E.R.
initiate an intertrip unit (type MVTW 02)
23 MCTH MCTH 23
24 24
17 17
25 25
26 26
19 19
27 27
28 28
23 MBCI 17 17 MBCI 23
24 24
25 Pilots 25
26 26
27 18 18 17 18 27
28 19 19 28
MVTW03
MFAC14 1
27
RVD3 3
28 11
Note1: It is essential that the current transformer connections are earthed at one point only
.
50Hz or 60Hz
Zener
80
Limiter
> Current withstand ratings
Duration (s) Differential 40
Continuous 2In
3 45In
2 55In 0 1 0 20 30
1 80In A-N fault current (x In)
0.5 100In
> Contact ratings Figure 6 Minimum earth fault current for operation with through load
160
120
80 Kt = 6
Kt = 14
40 Kt = 20
Kt = 40
0
1 2 3 4 5 6 10 20 30 40 50 60 80 100
Current (multiples of setting)
PILOTS UNIT PROTECTION OF
TRANSFORMER FEEDERS
> Pilots isolation
> Fault setting
Pilot isolation transformers are required when any
longitudinally induced voltage in the pilot circuit is likely The relay internal summation is identical to that used
to exceed 5kV: in effect this means when protecting for plain feeders but the turns ratio used is 2.25:6.
feeders operating at voltages in excess of 33kV, unless This will result in secondary settings as given in the
these are short in length. table below:
Ks is a setting multiplier A-N 0.19Ks.In 0.12Ks.In Note 1: There is a restricted earth fault relay in the
And may be varied B-N 0.25Ks.In 0.14Ks.In neutral of the star connected CTs on the
From 0.5-2.0 C-N 0.33Ks.In 0.17Ks.In delta side of the power transformer.
In is the rated relay current A-B 0.8Ks.In This provides protection against earth faults
B-C 1.0Ks.In on the Delta side of the power transformer
when the infeed is into the delta.
C-A 0.44Ks.In
It will provide settings lower than any of the
A-B-C 0.5Ks.In
phase to neutral settings given above.
Table 3
Note 2: The MBCI relay, when used in the
Note: A stabilising resistor is required for single transformer feed application, does not require
phase protection or when MBCI is fed from a stabilising resistor.
delta connected current transformers.
> Cases
> Reduction of induced pilot loop voltage
Relay type MBCI is provided in case 6 as shown
Ideally the pilot cores should be wormed (twisted in Figure 8.
together) so that the induced loop voltage is kept to a
minimum.
2BA connection
screws
354 mm
48 mm
2 holes
6.5 mm 310 mm 48
mm
342 mm
AREVA TRACK RECORD -
TRANSLAY - S SCHEMES
>> MBCI is the second generation Translay - S product.
>> MBCI launched in 1983, with over 13 000 in service worldwide.
>> Sister product MHOR analogue differential protection, and
MiCOM P521 numerical unit protection.
MiCOM is a registered trademark of AREVA. All trade names or trademarks mentioned herein whether registered or not, are the property of their owners. - 389191982 RCS PARIS - Printed in France - SONOVISION-ITEP
AUTOMATION-L3-MBCI-BR-01.05-????-GB - © - AREVA - 2004. AREVA, the AREVA logo and any alternative version thereof are trademarks and service marks of AREVA.