POINT I/O 120V AC Input Module: Installation Instructions
POINT I/O 120V AC Input Module: Installation Instructions
POINT I/O 120V AC Input Module: Installation Instructions
Table of Contents
Topic Page
Important User Information 2
Specifications 20
2 POINT I/O 120V AC Input Module
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages
resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the
many variables and requirements associated with any particular installation, Rockwell Automation, Inc.
cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits,
equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell
Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
SHOCK HAZARD: Labels may be on or inside the equipment (for example, drive or
motor) to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment (for example, drive or
motor) to alert people that surfaces may reach dangerous temperatures.
IMPORTANT Identifies information that is critical for successful application and understanding of
the product.
1 0
1
2
10
3
9 4
8
5
7
6
45713
Description Description
1 Module locking mechanism 6 Mounting base – 1734-TB, 1734-TBS
4 Removable Terminal Block (RTB) handle 9 DIN rail locking screw (orange)
1
2
8
4
6
5
45712
Description Description
1 Module locking mechanism 6 Interlocking side pieces
ATTENTION: This product is grounded through the DIN rail to chassis ground.
Use zinc plated yellow-chromate steel DIN rail to assure proper grounding. The
use of other DIN rail materials (for example, aluminum or plastic) that can
corrode, oxidize, or are poor conductors, can result in improper or intermittent
grounding. Secure DIN rail to mounting surface approximately every 200 mm
(7.8 in.) and use end-anchors appropriately.
1. Position the mounting base vertically above the installed units (adapter, power
supply or existing module).
31586
2. Slide the mounting base down allowing the interlocking side pieces to engage the
adjacent module or adapter.
3. Press firmly to seat the mounting base on the DIN rail. The mounting base snaps
into place.
WARNING: When you insert or remove the module while backplane power is
on, an electrical arc can occur. This could cause an explosion in hazardous
location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
Repeated electrical arcing causes excessive wear to contacts on both the
module and its mating connector. Worn contacts may create electrical
resistance that can affect module operation.
1734-TB base
45696
1734-TOP base
45697
1. Using a bladed screwdriver, rotate the keyswitch on the mounting base clockwise
until the number required for the type of module being installed aligns with the
notch in the base.
2. Make certain the DIN rail locking screw is in the horizontal position. You cannot
insert the module if the locking mechanism is unlocked.
3. Insert the module straight down into the mounting base and press to secure. The
module locks into place.
1. Insert the end opposite the handle into the base unit. This end has a curved
section that engages with the wiring base.
2. Rotate the terminal block into the wiring base until it locks itself in place.
3. If an I/O module is installed, snap the RTB handle into place on the module.
ule
odatus
MSt
Net
NO
wor
k
us
Stat :
DE
AC
Insert the module
0V t
12 Inpu
0
1
straight down into
the mounting base
45716
WARNING: For 1734-RTBS and 1734-RTB3S, to latch and un-latch the wire,
insert a bladed screwdriver (catalog number 1492-N90 – 3 mm diameter blade)
into the opening at approximately 73° (blade surface is parallel with top surface
of the opening) and push up gently.
73° 85°
WARNING: For 1734-TOPS and 1734-TOP3S, to latch and un-latch the wire,
insert a bladed screwdriver (catalog number 1492-N90 – 3 mm diameter) into
the opening at approximately 97° (blade surface is parallel with top surface of
the opening) and press in (do not push up or down).
97°
1734-IA2 1734-IA4
120VAC 120VAC
Input Input
Status of Input 0 0
Status of Input 0 0
Status of Input 1 1
Status of Input 1 1
Status of Input 2 2
Status of Input 3 3
1734 1734
IA2 IA4
L2/N L2/N L1 L1
L1 L1 L1 L1
45715 45714
1734-IA2
0 1
Ch 0 Ch 1
2 3
Prox NC NC Prox
4 5
Two-wire Three-wire
L2/N L2/N
6 7
L1 L1
1 1 5 7
1734-IA4
0 1
Ch 0 Ch 1
2 3
Ch 2 Ch 3
Prox Prox 5
Prox Prox
4
L1 L1
6 7
L1 L1
1 1 5
2 2 6
3 3 7
1734-IA2 1734-IA4
Status of Input 2
Status of Input 3
44214 44215
Specifications
POINT I/O 120V AC Input Module – 1734-IA2, 1734-IA4, Series C
Attribute Value
Number of inputs 1734-IA2 – 2 (1 group of 2) nonisolated, sinking
1734-IA4 – 4 (1 group of 4) nonisolated, sinking
On-state voltage range, min 65V AC
On-state voltage range, nom 120V AC
On-state voltage range, max 132V AC
On-state current, min 4.0 mA @ 65V AC, 60 Hz
On-state current, nom 7.5 mA @ 120V AC, 60 Hz
On-state current, max 8.5 mA @ 132V AC, 60 Hz
Off-state voltage, max 43V AC
Off-state current, max 2.7 mA @ 43V AC
Input impedance, nom 10.6 kΩ
General Specifications
Attribute Value
Terminal base screw torque 0.8 Nm (7 lb-in.)
Module location 1734-TB, 1734-TBS, 1734-TOP, or 1734-TOPS wiring base assembly
POINTBus current, max 75 mA @ 5V DC
Power dissipation 1734-IA2 – 0.35 W @ 132V AC
1734-IA4 – 0.50 W @ 132V AC
Thermal dissipation 1734-IA2 – 1.19 BTU/hr @ 132V AC
1734-IA4 – 1.71 BTU/hr @ 132V AC
Isolation voltage 240V (continuous), type tested @ 3250V DC for 60 s, field-side to
system
External AC power supply 120V AC @ 60 Hz
voltage, nom
External AC power supply 85...132V AC, 47...63 Hz
voltage range
Dimensions (HxWxD), approx. 56.0 x 12.0 x 75.5 mm
(2.21 x 0.47 x 2.97 in.)
Wiring category(1) 1 – on signal ports
Wire size Determined by installed terminal block
General Specifications
Attribute Value
Weight, approx. 30.9 g (1.09 oz)
North American temp code T4A
IEC temp code T4
Enclosure type rating None (open-style)
Delay time(2) 20 ms hardware filter plus 1...65 ms digital filter programmable in
Off to On and On to Off increments of 1 ms
Keyswitch position 8
(1) Use this conductor category information for planning conductor routing as described in Industrial Automation Wiring
and Grounding Guidelines, publication 1770-IN041.
(2) Input off-to-on filter time is the time from a valid input signal to recognition by the module. Input on-to-off filter time is
the time from the input signal dropping below the valid level to recognition by the module. Due to the randomness of
the AC line-cycle measurement capture point and response time of the hardware filter, the maximum hardware delay is
20 ms plus the filter time.
Environmental Specifications
Attribute Value
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20...55 °C (-4...131 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):
-40...85 °C (-40...185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5...95% non-condensing
Vibration IEC 60068-2-6 (Test Fc, Operating):
5 g @ 10...500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50 g
Emissions CISPR 11:
Group 1, Class A
Environmental Specifications
Attribute Value
ESD Immunity IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF Immunity IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
EFT/B Immunity IEC 61000-4-4:
±4 kV @ 5 kHz on signal ports
Surge transient Immunity IEC 61000-4-5:
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF Immunity IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80%AM from 150 kHz…80 MHz
Certifications
Certifications
For an additional level of technical phone support for installation, configuration and troubleshooting, we
offer TechConnect support programs. For more information, contact your local distributor or Rockwell
Automation representative, or visit http://www.rockwellautomation.com/support/.
Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the information that's
contained in this manual. You can also contact a special Customer Support number for initial help in getting
your product up and running.
United States Contact your distributor. You must provide a Customer Support case number
(call the phone number above to obtain one) to your distributor to complete
the return process.
Outside United States Please contact your local Rockwell Automation representative for the return
procedure.