GTP Inverter Transformer Rev 02

This document provides technical details for a 4 MVA inverter duty transformer. It lists 34 specifications for the transformer including its manufacturer, voltage and frequency ratings, winding configuration, cooling type, efficiency levels, temperature rise, and overload capacity. Key details are the transformer's 1.16% total losses, 98.57% maximum efficiency at 100% load, and ability to withstand overloads as specified in relevant IS standards.

Uploaded by

Jaks Jaks
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views5 pages

GTP Inverter Transformer Rev 02

This document provides technical details for a 4 MVA inverter duty transformer. It lists 34 specifications for the transformer including its manufacturer, voltage and frequency ratings, winding configuration, cooling type, efficiency levels, temperature rise, and overload capacity. Key details are the transformer's 1.16% total losses, 98.57% maximum efficiency at 100% load, and ability to withstand overloads as specified in relevant IS standards.

Uploaded by

Jaks Jaks
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

DOC TECHNICAL PARTICULARS: 4 MVA INVERTER DUTY TRANSFORMER

Total losses 1.16% of total MVA Rev 02, DATE : 04/12/2017

S.L.No. DESCRIPTION DETAILS PARAMETER

1 Name of manufacturer Schneider Electric Infra Ltd

2 KVA Rating 4000

2.1 HV : 4000

2.2 LV1 + LV2 2000+2000

3 No of phase and rated frequency 3, 50 Hz

3.1 Permissible variation in voltage + - 10%

3.2 Permissible variation in Frequency + - 3% (As per IS 2026)

3.3 Combine variation in voltage & frequency 10%

4 No-load voltage ( kV) & Current (A)

4.1 Voltage(KV)

4.1.1 HV 11

4.1.2 LV-1 & LV-2 0.575-0.575

4.2 Current (A)

4.2.1 HV 209.95

4.2.2 LV-1 & LV-2 2008.17 - 2008.17

5 Connection

5.1 HV Delta

5.2 LV-1 & LV-2 Star

5.3 VECTOR GROUP Dy11y11

6 HV & LV winding material Electrolytic Copper

7 Insulation Medium Mineral oil as per IS 335

8 Insulation level ( Impulse withstand )(kVpeak)

a HV 75

b LV 40

9 Insulation level ( power frequency withstand ) (kVrms)

a HV 28

b LV 10

10 Core Details Max Flux Density

a Max. Flux Density

at 100% rated voltage ( Tesla ) 1.73 TESLA

at 110% rated voltage ( Tesla) 1.903 TESLA

11 Tapping

a Range +5% to -5% @ 2.5%

b No of Steps 4

c On HV YES

d Tap changer type OCTC


o
12 Temperature rise of oil/winding over design ambient temperature of 50(oC) 50 / 55 ( C)

Hot spot temperature over a maximum yearly weighted average ambient temperature of o
13 o 98 C
32 C

14 Short circuit Thermal withstand time secs 2

15 % Impedance at 75C, rated current & Frequency (IS Tol) (Between HV & LV) at Principal Tap at 4000 kVA 6.25

15.1 % Impedance limit(Between HV & LV) @ Principal Tap 4.5% (Min) 7% (Max)

15.2 % Impedance at 75C, rated current & Frequency (IS Tol) (Between LV & LV) 7% (Min)
16 Total loss at rated voltage and frequency(KW)(MAX) for 4000 KVA at 75 DegC' 46.4

No Load Losses (KW) (MAX) 4.4

Load Losses (KW) (MAX) 42.0

17 Efficiency (%) 0.8 pf upf

a 100 % load 98.57 98.85

b 75% load 98.85 99.07

c 50% load 99.08 99.26

18 % Load at which Max Efficiency occurs (%) 32.367

19 Maximum Efficiency (%) 99.325

20 Regulation at full load 0.8pf% (%) 4.63

21 Regulation at full load upf% (%) 1.24

22 Bushings HV LV-1 & LV-2

a Reference standard As per Relevant IS

b Type of bushing Porcelain Epoxy

c Voltage Rating kV 17.5 3.6

d Short Ckt Current Rating kA 18.5 kA for 1 sec 36.5 for 1 sec.

e Current Rating Amps 630 3150

f Creepage distance mm/KV 25 Not applicable

23 Current Density (A/mm2) 4.5 A/mm2 at LV and 4.3 A/mm2 at HV at N tap

24 Fitting & Accessories as per specification Yes, IS2026 & CBIP

25 Reference standard IS 2026

26 Termination

a HV Please refer HV cable Box Drawing

b LV-1, LV-2 Please refer LV cable Box Drawing

c Auxiliary Supply TAPPING Please refer Schematic Drawing

27 Accessories minimum requirement Please refer Schematic Drawing

28 Noise level As per NEMA standard

29 SCADA Signal Requirement Please refer Schematic Drawing

30 Weight in Kgs (Approximate)

a Core and winding assembly

b Tank &Fittings
Refer OGA
c Oil

d Total weight

31 Approximate Overall dimension (in mm)

a Overall Length

b Overall breadth

c Overall Height Refer OGA

32 Approximate Weight of Heaviest package (KG)

33 Approximate transport dimensions of largest package LxBxH (mm)

34 Overload capcity of Transformer As per IS 2026 , Part-7 & IS 6600

35 WTI CT -HV 221 / 1.75 A, CLASS 5, 10 VA

Will be provided to meet the Max Load losses

Refer above point Nos : 15 , 15.1 & 15.2

6.16 % (Approx) @ 4 MVA Base

Refer above point Nos : 15 & 15.1

As per IS 2026

Refer above point Nos : 15 , 15.1 & 36.C for %X ,%Z &
%R -1.05%, X/R = 5.86 (Approx)

Approx 65 % to 130 % of Positive Sequence


Parameters
As per CBIP

Refer above point Nos : 15 & 15.1

Approx 65 % to 130 % of Positive Sequence Impedance

6.16 % (Approx) @ Unity Pf and


0.8 pf will not guarantee.

1.24 (Approx)

4.63 (Approx)

Windings Bushings

100 / %Z x Fulload 18.5 kA for 1 sec


Rated Current 36.5 for 1 sec.

Core Type

Steplap /Interleaved

1.73 TESLA

Approx 1.5 % of Full load Current referred to HV Side

Aprrox 0.2 to 0.8

As per CBIP

CRGO/ M5

0.3 (Approx)

No , Bolted design

Fiber glass/Teflon tape

Carlite

Yes

Approx -Watts/Kg - 1.42 @ 1.7 Tesla

Yes

Core Type

Yes

Approx 10 to 14 times of full load Current referred from


HV Side and Duration in milli sec

Layer

Foil/Layer

Electrolytic Copper

4.5 A/mm2 at LV and 4.3 A/mm2 at HV at N tap

NO, Not required low Voltage windings

Yes

Common ring will be provided

No, in between LV& HV , Shield is provided for inverter


Application

Insulation Paper
Insulation Paper, Pressboard material

Insulation Paper, Pressboard material

Not Required for this type winding Construction , hence


not Provided.

Yes

40 Kv peak

75 Kv peak

Conventional

4 mm (Approx)

Mild Steel

As per CBIP

Refer OGA

Approx 7.5 % of Total Volume of oil in Tank

Approx 3 % of Total Volume of Conservator

Included in Overall dimensions

Included in Tank & Fittings Weight

1 mm (approx)

Tank

As per CBIP

Atvus/Sukrut , Magnetic Oil level guage

Atvus/Sukrut , Double float

Precimeasure, Dial Type

Refer Schematic Drawing

NO

Refer OGA

Included in Core & Windings (Un tanking weight)

Included in Tank & Fittings Weight

As per SEIL Standard material


Sufficient Clearances will be provided to perform
dieclectric tests

Yes

As per CBIP

Refer above point no : 41

As per IS 335

Since it is a Small Transformer , so not provided

Yes but total loading should be based on corresponding


LV Operating

Yes but total loading should be based on corresponding


LV Operating
+ - 3% (As per IS 2026)

4.5 A/mm2 at LV and 4.3 A/mm2 at HV at N tap

Note: All fittings and Accessories will be as per SEIL Standard Vendor list Only.

Prepared By: BV Checked By : IDK