0% found this document useful (0 votes)
173 views5 pages

Erroor Code Samsung

The document provides information on error codes, displays, and explanations/checking points for various air conditioning units. It includes sections for indoor units, outdoor units, and inverter units with multiple errors listed under each along with brief descriptions of each error and suggested checks. The majority of errors listed relate to sensor issues that need to be checked and potentially replaced.

Uploaded by

Zdravko Peran
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
173 views5 pages

Erroor Code Samsung

The document provides information on error codes, displays, and explanations/checking points for various air conditioning units. It includes sections for indoor units, outdoor units, and inverter units with multiple errors listed under each along with brief descriptions of each error and suggested checks. The majority of errors listed relate to sensor issues that need to be checked and potentially replaced.

Uploaded by

Zdravko Peran
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 5

Operation =

Flashing Display Timer = Yes


Turbo =
LED Display = E1
Explanation and Checking points = Indoor unit room thermistor error - Open or
Closed Circuit - Check and replace if required

Operation = Yes
Flashing Display Timer = Yes
Turbo =
LED Display = E2
Explanation and Checking points = Indoor unit pipe thermistor error - - Open or
Closed Circuit - Check and replace if required

Operation =
Flashing Display Timer =
Turbo = Yes
LED Display = E3
Explanation and Checking points = Indoor unit fan motor malfunction - Check and
replace if required

Operation =
Flashing Display Timer = Yes
Turbo = Yes
LED Display = E6
Explanation and Checking points = EPROM error - Check and replace PCB if
required

Operation = Yes
Flashing Display Timer = Yes
Turbo = Yes
LED Display = Flashing
Explanation and Checking points = Option code error - Check and input new option
code if required via wireless remote controller
Operation = Yes
Flashing Display Timer =
Turbo = Yes
LED Display =
Explanation and Checking points = Outdoor unit temperature sensor - Open or
Closed Circuit - Check and replace if required

Outdoor Unit

Error Code = Er - E1
Explanation and Checking points = Indoor unit room temperature sensor error (open/short) - Check and replace if
required

Error Code = Er - E5
Explanation and Checking points = Indoor unit heat exchanger out temperature sensor error (open/short) -
Check and replace if required

Error Code = Er - 05
Explanation and Checking points = Indoor unit heat exchanger in temperature sensor error (open/short) -
Check and replace if required

Error Code = Er - 06
Explanation and Checking points = EPROM error - Check and replace PCB if required

Error Code = Er - 09
Explanation and Checking points = Option code error - Check and input new option code if required via wireless
remote controller

Error Code = E3 - 01
Explanation and Checking points = Indoor fan motor malfunction Fan and cable - Check and replace if required

Error Code = Er - 01
Explanation and Checking points = Communication error between the indoor unit and outdoor unit

Error Code = Er - 11
Explanation and Checking points = Abnormal increase of operation current

Error Code = Er - 12
Explanation and Checking points = Abnormal increase of OLP temperature

Error Code = Er - 13
Explanation and Checking points = Abnormal increase of discharge temperature

Error Code = Er - 14
Explanation and Checking points = Over current of IPM circuit Comp. Fan

Error Code = Er - 15
Explanation and Checking points = Abnormal increase of heat sink temperature Fan

Error Code = Er - 10
Explanation and Checking points = BLCD compressor starting error Comp. PCB, Comp wire

Error Code = Er - E6
Explanation and Checking points = deice temp-sensor - Check and replace if required
Error Code = Er - 31
Explanation and Checking points = outdoor temp-sensor - Check and replace if required

Error Code = Er - 32
Explanation and Checking points = discharge temp-sensor - Check and replace if required

Error Code = Er - 33
Explanation and Checking points = discharge temp-sensor - Check and replace if required

Error Code = Er - 17
Explanation and Checking points = Communication error between 2 micom on the outdoor PCB

Error Code = Er - 36
Explanation and Checking points = current sensor error PCB - Check and replace if required

Error Code = Er - 37
Explanation and Checking points = heatsink temp-sensor error PCB - Check and replace if required

Error Code = Er - 38
Explanation and Checking points = Voltage sensor error - Check and replace if required

Inverter Unit

Display = E1 01
Explanation and Checking points = Communication error (indoor unit unable to receive data) - Check cables

Display = E1 02
Explanation and Checking points = Communication error (outdoor unit unable to communicate) -
Check addresses

Display = E1 21
Explanation and Checking points = Indoor unit room temperature sensor error (Open/Short) - Check and replace if
required

Display = E1 22
Explanation and Checking points = Indoor unit sensor error - Evaporator pipe in sensor error (Open/Short) -
Check and replace if required

Display = E1 23
Explanation and Checking points = Indoor unit sensor error - Evaporator pipe out sensor error (Open/Short) -
Check and replace if required

Display = E1 28
Explanation and Checking points = Indoor unit sensor error - Evaporator pipe out sensor detached

Display = E1 30
Explanation and Checking points = Indoor unit heat exchanger in & out temperature sensor detached

Display = E1 54
Explanation and Checking points = Indoor unit fan malfunction

Display = E1 61
Explanation and Checking points = More than 2 indoor units cool and heat simultaneously

Display = E1 62
Explanation and Checking points = EPROM error
Display = E1 63
Explanation and Checking points = Option code setting error

Display = E1 85
Explanation and Checking points = Cable miss wiring

Display = E2 01
Explanation and Checking points = The number of indoor unit mismatched

Display = E2 02
Explanation and Checking points = Communication error (outdoor unable to receive data)

Display = E2 03
Explanation and Checking points = Communication error between two microcontroller on the outdoor PCB

Display = E2 21
Explanation and Checking points = Outdoor temperature sensor error (Short/Open) - Check and replace if
required

Display = E2 37
Explanation and Checking points = Condenser temperature sensor error (Short/Open) - Check and replace if
required

Display = E2 46
Explanation and Checking points = Condenser temperature sensor detached

Display = E2 51
Explanation and Checking points = Compressor discharge sensor error (Short/Open) - Check and replace if
required

Display = E2 59
Explanation and Checking points = Outdoor unit error

Display = E2 60
Explanation and Checking points = Compressor discharge sensor error (Short/Open) - Check and replace if
required

Display = E2 61
Explanation and Checking points = Compressor discharge sensor detached

Display = E3 20
Explanation and Checking points = Compressor OLP sensor error (Short/Open) - Check and replace if required

Display = E4 01
Explanation and Checking points = Indoor unit heat exchanger freezing and compressor stop (cooling mode)

Display = E4 04
Explanation and Checking points = Outdoor unit overload and compressor stop (protection control in heating
mode)

Display = E4 16
Explanation and Checking points = Outdoor unit high discharge temperature and compressor stop (heating mode)

Display = E4 19
Explanation and Checking points = Outdoor unit EEV open error (self diagnosis) - Check and replace if required

Display = E4 22
Explanation and Checking points = Outdoor unit EEV close error (self diagnosis) - Check and replace if required

Display = E4 40
Explanation and Checking points = High temperature (over 30C) of outdoor as heating mode

Display = E4 41
Explanation and Checking points = Low temperature (under -5C) of indoor as cooling mode

Display = E4 60
Explanation and Checking points = Wrong connection between communication and power cable

Display = E4 61
Explanation and Checking points = Inverter compressor starting failure (5 times)

Display = E4 62
Explanation and Checking points = Compressor trip by input current limit control

Display = E4 63
Explanation and Checking points = Compressor trip by OLP temperature limit control

Display = E4 64
Explanation and Checking points = Compressor peak current protection

Display = E4 65
Explanation and Checking points = Compressor overload protection by current

Display = E4 66
Explanation and Checking points = DC-link voltage error (under 150V or over 410V)

Display = E4 67
Explanation and Checking points = Compressor rotation error

Display = E4 68
Explanation and Checking points = Current sensor error - Check and replace if required

Display = E4 69
Explanation and Checking points = DC-link voltage sensor error - Check and replace if required

Display = E4 70
Explanation and Checking points = Compressor overload protection - Check refrigerant charge and
heat exchangers

Display = E4 71
Explanation and Checking points = EPROM error - Check and replace PCB if required

Display = E4 72
Explanation and Checking points = AC line zero-crossing detection circuit error - Check power supply

Display = E5 54
Explanation and Checking points = No refrigerant error (self diagnosis) - Check refrigerant charge