Emax DC
Emax DC
Emax DC
SACE Emax DC
Low voltage Direct Current
air circuit-breakers
Index
SACE Emax DC circuit-breakers . ............................................................................................ 2
Accessories ............................................................................................................................ 25
ABB SACE 1
1SDC200012D0902
SACE Emax DC circuit-breakers
The SACE Emax range of low voltage circuit-breakers is completed by the new SACE Emax
DC series of circuit-breakers for direct current applications complying with the IEC60947-
2 Standard. Thanks to the exclusive technology applied to the new SACE PR123/DC and
PR122/DC trip units, the SACE Emax DC range allow all installation requirements to be met
and protection up to 1000V DC / 5000A.
With connection of three interruption poles in series, the rated voltage which can be reached
is 750V DC, whereas with four poles in series this rises to 1000V DC.
The withdrawable circuit-breakers must be associated with the fixed parts in a special version
for applications at 750/1000V DC.
Common data
Voltages
Rated service voltage Ue [V] 1000
Rated insulation voltage Ui [V] 1000
Rated impulse withstand voltage Uimp [kV] 12
Operating temperature [C] -25....+70
1SDC200601F0001
Storage temperature [C] -40....+70
Number of poles 3-4
Versions Fixed - Withdrawable
E2 E3 E4 E6
Levels of performance B N N H S H H
Rated uninterrupted current (at 40 C) Iu [A] 800 800
[A] 1000 1000
[A] 1250 1250
[A] 1600 1600 1600 1600 1600
[A] 2000 2000 2000
[A] 2500 2500 2500
[A] 3200 3200 3200
[A] 4000
[A] 5000
Rated ultimate short-circuit breaking capacity Icu according to the
See pages 3, 4 and 5
application network
Rated service short-circuit breaking capacity Ics [%Icu] [kA] 100% 100% 100% 100% 100% 100% 100%
Rated short-time withstand current Icw (0.5s)
@ 500 V DC (3p) [kA] 35 50 60 65 75 100 100
@ 750 V DC (3p) [kA] 25 25 40 40 65 65 65
@ 750 V DC (4p) [kA] 25 40 50 50 65 65 65
@ 1000 V DC (4p) [kA] 25 25 35 40 50 65 65
Rated short-circuit making capacity Icm [%Icu] [kA] 100% 100% 100% 100% 100% 100% 100%
Category of use (according to CEI EN 60947-2) B B B B B B B
Isolation behaviour (according to CEI EN 60947-2)
Overcurrent protection
Electronic trip units for DC applications
Operating times
Closing time (max) [ms] 80 80 80 80 80 80 80
Breaking time for I<Icw (max) (1) [ms] 60 60 60 60 60 60 60
Overall dimensions
Fixed: H = 418 mm - D = 302 mm - W (3/4 poles) [mm] 296/386 296/386 404/530 404/530 566/656 566/656 782/908
Withdrawable: H = 461 mm - D = 396.5 mm - W (3/4 poles) [mm] 324/414 324/414 432/558 432/558 594/684 594/684 810/936
Weights
Fixed 3/4 poles [kg] 50/61 50/61 66/80 66/80 97/117 97/117 140/160
Withdrawable 3/4 poles (including the fixed part) [kg] 50/61 50/61 66/80 66/80 147/165 147/165 210/240
(1) Without intentional delays.
E2 E3 E4 E6
800 800
2500
Iu 1000 1600 1000 1600 2000 2500 1600 2000 3200 4000 5000
3200
1250 1250
Life with regular maintenance N. operations
Mechanical x 1000 25 25 20 20 20 20 15 15 15 12 12 12
Electrical 1000V DC x 1000 15 10 12 10 9 7 7 7 7 5 4 2
2 ABB SACE
1SDC200012D0902
SACE Emax DC circuit-breakers
Rated ultimate short-circuit breaking capacity Icu
according to the type of network
+
L
O
A
- D
LOAD + LOAD + -
+ - +
isolation
protection
PR122/DC
PR123/DC
ABB SACE 3
1SDC200012D0902
SACE Emax DC circuit-breakers
Rated ultimate short-circuit breaking capacity Icu
according to the type of network
+
L
O
A
- D
LOAD + -
+
isolation
protection
PR122/DC
PR123/DC
type of fault (3) a b a b
poles in series affected by the fault 3 2 4 3
Icu(4) [kA] [kA]
800
1000
B 35 20 35 35
E2 1250
1600
N 1600 50 25 50 50
800
1000
1250
N 60 30 60 60
1600
E3 2000
2500
1600
H 2000 65(5) 40 65 (5) 65(5)
2500
1600
2000
S 100 50 100 100
E4 2500
3200
H 3200 100 65 100 100
3200
E6 H 4000 100 65 100 100
5000
(1)
for networks with positive earthed polarity, ask ABB.
(2)
for higher voltages, ask ABB.
(3)
for further information, see QT5: ABB circuit-breakers for direct current applications.
(4)
Icu with L/R = 15ms according to IEC 60946-2 Standard. For Icu with L/R = 5ms and L/R = 30ms, ask ABB.
(5)
85kA only if supplied from below and specifying the following extracode at the ordering stage: 1SDA067148R1. Ics=65kA.
4 ABB SACE
1SDC200012D0902
Network with the median point earthed
Rated voltage (Ue) 500 500 750 1000
LOAD -
+
L
O
A
- D
2
2 LOAD +
+ -
PR122/DC - - - -
PR123/DC
type of fault a b c a b c a b c a b c
poles in series affected by the fault 3 2 (U/2) 1 (U/2) 4 2 (U/2) 2 (U/2) 4 2 (U/2) 2 (U/2) 4 2 (U/2) 2 (U/2)
Icu(1) [kA] [kA] [kA] [kA]
800
1000
B 35 35 18 35 35 35 25 25 25 25 25 25
E2 1250
1600
N 1600 50 50 25 50 50 50 40 40 40 25 25 25
800
1000
1250
N 60 60 30 60 60 60 50 50 50 35 35 35
1600
E3 2000
2500
1600
H 2000 65(2) 65 40 65(2) 65 (2) 65 (2) 50 50 50 40 40 40
2500
1600
2000
S 75 75 35 75 75 75 65 65 65 50 50 50
E4 2500
3200
H 3200 100 100 50 100 100 100 65 65 65 65 65 65
3200
E6 H 4000 100 100 65 100 100 100 65 65 65 65 65 65
5000
(1)
Icu with L/R = 15ms according to IEC 60946-2 Standard. For Icu with L/R = 5ms and L/R = 30ms, ask ABB.
(2)
85kA only if supplied from below and specifying the following extracode at the ordering stage: 1SDA067148R1. Ics=65kA.
ABB SACE 5
1SDC200012D0902
SACE Emax switch-disconnectors
ABB SACE has developed the SACE Emax/E MS range of switch-disconnectors for direct cur-
rent applications up to 1000V complying with the international IEC60947-3 Standard. These
circuit-breakers are particularly suitable for use as bus-ties or main switch-disconnectors in
direct current plants, such as applications in the field of electric traction.
The range makes it possible to cover any installation requirement up to 1000V DC / 6300A.
The circuit-breakers are available in the fixed or withdrawable version and in the three-pole
or four-pole version.
With connection of three breaking poles in series, the rated voltage which can be reached is
750V DC, whereas with four poles in series this rises to 1000V DC.
The switch-disconnectors in the SACE Emax/E MS range keep all the overall dimensions
and fixing points of the circuit-breakers of the standard range unchanged. The withdrawable
circuit-breakers must be associated with the fixed parts in a special version for applications
at 750/1000V DC.
6 ABB SACE
1SDC200012D0902
Versions and connections
Fixed circuit-breaker
Vertical rear terminals
Power supply from the lower terminals Power supply from the upper terminals
Withdrawable circuit-breaker
Vertical rear terminals
Power supply from the lower terminals Power supply from the upper terminals
Power supply from the lower terminals Power supply from the upper terminals
ABB SACE 7
1SDC200012D0902
Dissipated powers
The dissipated powers for Emax DC circuit-breakers are given below according to:
- range;
- trip unit;
- version;
- number of poles;
- Iu.
8 ABB SACE
1SDC200012D0902
Temperature derating
The following graphs show derating as the temperature increases for Emax DC circuit-breakers.
E2 DC
2000
1500
800
1000
Iu [A]
1000
1250
500 1600
0
10 20 30 40 50 55 60 70
C
E3 DC
3000
2500 800
1000
2000
1250
Iu [A]
1500
1600
1000
2000
500 2500
0
10 20 30 40 50 55 60 70
C
ABB SACE 9
1SDC200012D0902
Temperature derating
E4 DC
3500
3000
2500 1600
2000 2000
Iu [A]
1500 2500
1000 3200
500
0
10 20 30 40 50 55 60 70
C
E6 DC
6000
5000
4000 3200
Iu [A]
3000 4000
2000 5000
1000
0
10 20 30 40 50 55 60 70
C
10 ABB SACE
1SDC200012D0902
Protection trip units and trip curves
PR122/DC
Characteristics
PR122/DC is the new electronic trip unit for the Emax DC series. The vast range of protec-
tion functions, together with the wide variety of trip thresholds and times, make them suitable
for protection of insulated networks or networks with earthed negative polarity. Consulting
information about the unit and its programming is particularly simple and intuitive thanks to
the LCD graphic display.
1SDC200607F0001
ABB SACE 11
1SDC200012D0902
Protection trip units and trip curves
PR122/DC
Function Trip Threshold Trip time Time Disabling Relation Thermal Zone
threshold step step t=f(I) memory selectivity
Tolerance (2)
Trip unit between 10%, If 6 x In
1.05 and 1.3 x I1 20%, If > 6 x In
Tolerance (2)
7%, If 6 x In The best of the two data:
10%, If > 6 x In 10% or 40 ms
With current If 10 x In
0.01 s t=k/I 2
I2= 0.6...10 x In 0.1 x In t2= 0.05 s...0.35 s
Tolerance (2)
7%, If 6 x In 15%, If 6 x In
10%, If > 6 x In 20%, If > 6 x In
Protection against
instantaneous
short-circuit I3= 1.5...10 x In 0.1 x In Instantaneous t=k
Tolerance (2)
10% 30 ms
OT
Protection against
overtemperature Cannot be set Instantaneous t=k
(1) The minimum trip value is 0.5 s, regardless of the type of curve set
(2) These tolerances are valid in the following hypotheses:
- trip unit supplied entirely by the voltage module and/or auxiliary power supply (without start-up)
- trip time set 100 ms
For all cases not contemplated by the above hypotheses, the following tolerance values are valid:
12 ABB SACE
1SDC200012D0902
With plant voltages higher than or equal to 100V, the PR122/DC electronic trip unit guarantees
protection without the need of an auxiliary power supply (24V DC).
The PR122/DC electronic trip unit can, in fact, always be equipped with the PR120/V module
able to supply the trip unit with plant voltages between 250V DC and 1000V DC.
For voltages between 100V DC and 250V DC, it is necessary to request the PR120/LV module,
specifying the extracode 1SDA066223R1.
The following table shows the cases where it is possible to use of the measurement modules
(PR120/V and PR120/LV):
When there is an auxiliary power supply, see the table below for the overall consumption values.
When Emax DC circuit-breakers are used in plants with capacitor banks with possible back-
to-back inrush currents 3xIn, it is necessary to use a 24V DC galvanically insulated auxiliary
power supply.
The range of Emax DC circuit-breakers is normally supplied with power input from the lower
terminals, i.e. the PR120/V-PR120/LV internal connection is on the lower terminals, whereas
the U connections are on the upper terminals:
3D rear view
Front view
For power input to the upper terminals, refer to the Code Section for ordering.
Protection is guaranteed even when the electronic trip unit is not powered thanks to the PR120/DC
module which the PR122/DC is always fitted with.
ABB SACE 13
1SDC200012D0902
Protection trip units and trip curves
PR122/DC
Functions L-S-I
t=k
1SDC200608F0001
Functions L-S-I
I2t = k
1SDC200609F0001
14 ABB SACE
1SDC200012D0902
Protection trip units and trip curves
PR123/DC
Characteristics
With the PR123/DC electronic protection trip unit, the range of trip units available for the Emax
DC series of circuit-breakers is completed.
PR123/DC is a high-performing trip unit capable of carrying out a complete set of protections,
measurements, indications, data storage and circuit-breaker control functions.
PR123/DC not only offers protection but also measurement of current and voltage of both
polarities (+ and -), therefore being suitable for any type of network.
The front interface of the unit, common to PR122/DC, is extremely simple thanks to the aid
of the LCD graphic display.
1SDC200610F0001
ABB SACE 15
1SDC200012D0902
Protection trip units and trip curves
PR123/DC
Function Trip Threshold Trip time Time Disabling Relation Thermal Zone
threshold step step t=f(I) memory selectivity
Tolerance (2)
Trip between 10% If 6 x In
1.05 and 1.3 x I1 20% If > 6 x In
Tolerance (2)
7% If 6 x In The best of the two data:
10% If > 6 x In 10% or 40 ms
With current I = 10 x I1
0.01 s t=k/I2
I2 = 0.6...10 x In 0,1 x In t2 = 0.05 s...0.35 s
Tolerance (2)
7% If 6 x In 15% If 6 x In
10% If > 6 x In 20% If > 6 x In
Tolerance (2)
7% If 6 x In The best of the two data:
10% If > 6 x In 10% or 40 ms
Protection against
instantaneous
short-circuit I3 = 1.5...10 x In 0.1 x In Instantaneous t=k
Tolerance (2)
10% 30 ms
With current I > I4
Protection against
I4 = 0.2...1 x In 0.02 x In t4 = 0.1 s...1 s 0.05 s t=k
earth fault
t4sel = 0.04 s...0,2 s 0.01 s
OV
Overvoltage U9 = 1.05...1.2 x Un 0.01 x In With voltage U < U9 0.1 s t=k
protection t9 = 0.1 s...5 s
RP
Protection against P11 = -0.3...-0.1 x Pn 0.02 x Pn At power P < P11 0.1 s t=k
reversal of power t11 = 0.5 s...25 s
(1) The minimum trip value is 0.5 s, regardless of the type of curve set For all cases not contemplated by the above hypothesis, the following tolerance values are valid:
(2) These tolerances are valid with the following hypothesis:
- trip unit supplied from the voltage module and/or auxiliary power supply Trip threshold Trip time
(without start-up) L Trip between 1.05 and 1.3 x I1 20%
- trip time set 100 ms
S 10% 20%
I 15% 60ms
G 15% 20%
Altri 20%
16 ABB SACE
1SDC200012D0902
With plant voltages higher than or equal to 100V, the PR123/DC electronic trip unit guarantees
protection without the need of an auxiliary power supply (24V DC).
The PR123/DC electronic trip unit is, in fact, always fitted with the PR120/V module able to
supply the trip unit with plant voltages between 250V DC and 1000V DC.
For voltages between 100V DC and 250V DC, it is necessary to request the PR120/LV module,
specifying the extracode 1SDA066223R1.
The following table shows the possible cases of use of the measurement modules (PR120/V
and PR120/LV):
When there is an auxiliary power supply, see the table given below for the overall consumption
values.
When Emax DC circuit-breakers are used in plants with capacitor banks with possible inrush
back-to-back currents 3xIn, it is necessary to use a 24V DC galvanically insulated auxiliary
power supply.
The range of Emax DC circuit-breakers is normally supplied with power input from the lower
terminals, i.e. the PR120/V-PR120/LV internal connection is on the lower terminals, whereas
the U connections are on the upper terminals:
3D rear view
Front view
For power input to the upper terminals, refer to the ordering Code Section.
Protection is guaranteed even when there is no power supply to the electronic trip unit thanks
to the PR120/DC module, which the PR1232/DC is always fitted with.
ABB SACE 17
1SDC200012D0902
Protection trip units and trip curves
PR123/DC
Functions L-S-I
t=k
1SDC200608F0001
Functions L-S-I
I2t = k
1SDC200609F0001
18 ABB SACE
1SDC200012D0902
Function G
k
t=
I2
t=k
1SDC200611F0001
Function U
1SDC200612F0001
ABB SACE 19
1SDC200012D0902
Protection trip units and trip curves
PR123/DC
Function RP
RP
1SDC200613F0001
Function UV
UV
1SDC200614F0001
20 ABB SACE
1SDC200012D0902
Function OV
OV
1SDC200615F0001
ABB SACE 21
1SDC200012D0902
Protection trip units and trip curves
PR122/DC and PR123/DC: optional modules
The PR122/DC and PR123/DC electronic trip units can be fitted with the following optional
modules, which are already available on the PR122/P and PR123/P electronic devices for
alternating current applications.
PR122/DC
Code Internal Description
PR123/DC
Internal indication module
1SDA058255R1 PR120/K
(4 outputs with independent terminals)
Internal indication module
1SDA058256R1 PR120/K
(4 outputs + input with common terminal)
1SDA058254R1 PR120/D-M Modbus RTU communication module
1SDA065223R1(1) PR120/LV Measurement module for low voltage (100...250V DC)
Extracode to be specified with the circuit-breaker code to order the PR120/LV low voltage measurement module
(1)
The PR120/LV measurement module and the PR120/DC override protection module are always supplied with the electronic trip units.
PR122/DC
Code External Description
PR123/DC
1SDA058258R1 PR030/B Power supply unit
1SDA058259R1 BT030-USB External wireless communication unit (without wires)
1SDA048964R1 PR010/T External test unit
1SDA059146R1 PR021/K External indication unit
22 ABB SACE
1SDC200012D0902
Protection trip units and trip curves
Measurement
PR122/DC
The following measurements are available:
Current;
Instantaneous value of the current over a period of time (data logger);
Maintenance: Number of operations, percentage of contact wear, storage of opening data
(last 20 trips and 80 events);
The protection finds the historical data of the maximum values of current reading.
PR123/DC
Current;
Maintenance: Number of operations, percentage of contact wear, storage of opening data
(last 20 trips and 80 events);
Voltage;
Instantaneous value of the current/voltage over a period of time (Data Logger);
Power;
Energy;
The protection finds the historical data of the maximum values of current reading, the maxi-
mum voltage and the minimum voltage, the total maximum value and the average value of
the power.
ABB SACE 23
1SDC200012D0902
Protection trip units and trip curves
Functions
The functions available on the PR122/DC and PR123/DC electronic trip units fitted with Modbus
PR120/D-M communication module are listed in the following table.
PR122/DC PR123/DC
+ PR120/D-M + PR120/D-M
Communication functions
Protocol Modbus RTU Modbus RTU
24 ABB SACE
1SDC200012D0902
Accessories
Electrical and mechanical accessories
Accessories*
The SACE Emax DC family of circuit-breakers can be fitted with the following electrical and
mechanical accessories, which are already available for the standard family of circuit-breakers
for alternating current applications.
Switch-disconnectors for
Ranges Circuit-breakers
applications up to 1000V DC
LEGENDA * For further information on the accessories, please consult the Emax catalogue: Circuit-break-
ers \ low voltage air.
Optional accessory on fixed circuit-breaker or on moving part
Optional accessory on fixed part
Optional accessory on moving part
ABB SACE 25
1SDC200012D0902
Overall dimensions
Fixed circuit-breaker
4 POLES E2 - E4 E3 - E6
3 POLES
3 POLES
4 POLES
1SDC200617F0001
Caption
A B C D
E2 386 296 148 148
E3 530 404 202 202
1SDC200618F0001
26 ABB SACE
1SDC200012D0902
E3 III
View A
Iu=2000A
Iu=2500A
Iu=800A
Iu=1000A
Iu=1250A
Iu=1600A
E3 IV
View A Iu=2000A
Iu=2500A
Iu=800A
Iu=1000A
Iu=1250A
Iu=1600A
E4 III
View A
Iu=2500A
Iu=3200A
Iu=1600A
Iu=2000A
1SDC200619F0001
ABB SACE 27
1SDC200012D0902
Overall dimensions
Fixed circuit-breaker
E4 IV
View A
Iu=2500A
Iu=3200A
Iu=1600A
Iu=2000A
E6 III
View A
E6 IV
View A
1SDC200620F0001
28 ABB SACE
1SDC200012D0902
Compartment dimensions
A B
Depth
E2 400 490
E3 500 630
3 POLES E4 700 880
4 POLES E6 1000 1260
N 2 holes for
IP54 protection
1SDC200621F0001
ABB SACE 29
1SDC200012D0902
Overall dimensions
Withdrawable circuit-breaker
4 POLES
E2-E4 E3-E6
3 POLES
3 POLES
4 POLES
1SDC200622F0001
Caption
A B C D
E2 414 324 162 162
E3 558 432 216 216
E4 774 594 252 342
E6 1062 810 342 468
30 ABB SACE
1SDC200012D0902
E3 III E3 IV
View A View A
E4 III E4 IV
View A View A
Iu=1600A
Iu=2000A
Iu=2500A
Iu=3200A
E6 III E6 IV
View A View A
1SDC200624XF0001
ABB SACE 31
1SDC200012D0902
Overall dimensions
Withdrawable circuit-breaker
4 POLES
E2-E4 E3-E6
3 POLES
8 10 8 8 10 8
465 465
X X X X
264.5 264.5
80 100
71.5 18 18
61.5
3 POLES
4 POLES
348 348
465 465
X X X X
8 10 8 8 10 8
124.5 124.5
1SDC200622AF0001
18 18
Caption
door
2 Segregation (where provided)
3 Circuit-breaker fixing M10 E2 III E2 IV
drilling (use M10 screws) View A View A
4 N. 1 M12 screw (E1, E2, E3)
or n. 2 M12 screws (E4, E6)
for earthing (included in the 90 90
90 90 90
143
supply) 100 60 100 143
5 Insulating wall or insulated 35
metal wall
13
151 15 151
6 For power input to the
UPPER terminals PR120/V N
internal connection on the
upper terminals and rear U
connection kit on the lower
terminals
7 For power input to the
LOWER terminals PR120/V
internal connection on the
lower terminals and rear U
connection kit on the upper
terminals
1SDC200623AF0001
60
35 13
15
33
A B C D
E2 414 324 162 162
E3 558 432 216 216
E4 774 594 252 342
E6 1062 810 342 468
32 ABB SACE
1SDC200012D0902
E3 III E3 IV
View A 435 View A 561
126 126 126 126 126
205 205
158 158
95 95
96
96 15
171 171
3
35 35 33 35 35
1
3 15
1
33
4 183 4 N 246 2
0
0
2
1
33 1 33
380 40 40 325
225 393,5 225
84 84 370
370 240 240
122 122
49 70 49 70
63
6 200
240 3
E4 III E4 IV
View A 597
View A
777
180 180 180 180 180
323 323
280 280
65 65
13
191 150 191
35 35 35
15 33
2
2
708
4 4
33 528 33 10
10
700
393,5 40 393,5 40
380 400 380 580
84 530 84
122 122
45 45
1 1
E6 III E6 IV
View A 813
View A 1065
252 252 252 252 252
457 457
410 410
85 85
222
211 211
3
35 35 56 35 35
1
15 33
744
2 996 2
4 4
0
33 33 1
10
393,5 40 393,5 40
380 620 380
84 750 84 996
1SDC200624AF0001
122 122
63 63
1 1 866
ABB SACE 33
1SDC200012D0902
Overall dimensions
Circuit-breaker accessories
Compartment dimensions
A B
Depth
E2 400 490
E3 500 630
3 POLES E4 700 880
4 POLES E6 1000 1260
N 2 holes for
IP54 protection
1SDC200626F0001
Compartment door drilling Minimum distance between circuit-breaker and switchboard wall
A
3 poles 4 poles
E2 180 180
E3 234 234
1SDC200627F0001
E4 270 360
E6 360 486
34 ABB SACE
1SDC200012D0902
Electric wiring diagrams
Information for reading
Caution
Before installation of the circuit-breaker, read note F of the electric wiring diagrams carefully.
Versions
The diagram shows a withdrawable version circuit-breaker, but is also valid for fixed version circuit-breakers.
Fixed version
The control circuits are included between the XV terminals (connector X is not supplied).
With this version, the applications indicated in figures 31 and 32 cannot be supplied.
Withdrawable version
The control circuits are included between the poles of connector X (terminal board XV is not supplied).
Version with PR122/DC electronic trip unit
Version with PR123/DC electronic trip unit
Caption
= Number of diagram figure
* = See the note indicated by the letter
A1 = Circuit-breaker accessories
A3 = Accessories placed on the fixed part of the circuit-breaker (only provided with withdrawable version
circuit-breakers)
A4 = Indicative apparatus and connections for control and indication, outside the circuit-breaker
D = Undervoltage release electronic time-delay device, outside the circuit-breaker
F1 = Fuse with delayed intervention
K51 = PR122/DC, PR123/DC type electronic trip unit with the following protection functions:
- L against overload with long inverse time-delay trip - regulation I1
- S against short-circuit with short inverse or definite time-delay trip - regulation I2
- I against short-circuit with instantaneous time trip - regulation I3
- G against earth fault with short inverse time-delay trip - regulation I4
K51/1...8 = PR021/K indication unit contacts
K51/GZin = Zone selectivity: input for protection G (requires Vaux and PR123/DC trip unit)
K51/GZout = Zone selectivity: output for protection G (requires Vaux and PR123/DC trip unit)
K51/IN1 = Programmable digital input (only provided with Vaux and PR122/DC or PR123/DC trip unit with PR120/K
indication module)
K51/P1...P4 = Programmable electrical signals (only provided with Vaux and PR122/DC or PR123/DC trip unit PR120/K
indication module)
K51/SZin = Zone selectivity: input for protection S (requires Vaux and PR123/DC trip unit)
K51/SZout = Zone selectivity: output for protection S (requires Vaux and PR123/DC trip unit)
K51/YC = Closing command from PR122/DC or PR123/DC electronic trip unit connected to a bus system by
means of PR120/D-M communication module
K51/YO = Opening command from PR122/DC or PR123/DC electronic trip unit connected to a bus system by
means of PR120/D-M communication module
M = Motor for charging the closing springs
Q = Circuit-breaker
Q/1...27 = Circuit-breaker auxiliary contacts
S33M/1...3 = Spring charging motor limit contacts
S43 = Changeover contact for preparation of remote/local control
S51 = Contact for electrical indication of circuit-breaker open due to overcurrent release trip. Circuit-breaker
closing can only take place after having pressed the reset pushbutton or after having energised the YR
coil for electrical resetting (if provided)
S75E/1...4 = Contacts for electrical indication of circuit-breaker in racked-out position (only provided with withdrawable
version circuit-breakers)
S75I/1...5 = Contacts for electrical indication of circuit-breaker in racked-in position (only provided with withdrawable
version circuit-breakers)
S75T/1..4 = Contacts for electrical indication of circuit-breaker in racked-out test position (only provided with with-
drawable version circuit-breakers)
SC = Pushbutton or contact for closing the circuit-breaker
SO = Pushbutton or contact for opening the circuit-breaker
SO1 = Pushbutton or contact for opening the circuit-breaker with delayed trip
SO2 = Pushbutton or contact for opening the circuit-breaker with instantaneous trip
SR = Pushbutton or contact for electrical resetting of the circuit-breaker
ABB SACE 35
1SDC200012D0902
Electric wiring diagrams
Information for reading
W1 = Serial interface with the control system (bus system): EIA RS485 interface (see note E)
W2 = Serial interface with the accessories of the PR122/DC and PR123/DC trip units (local bus)
X = Delivery connector for withdrawable version circuit-breaker auxiliary circuits
X1...X7 = Connectors for circuit-breaker accessories
XF = Delivery terminal board for withdrawable version circuit-breaker position contacts (located on the
fixed part of the circuit-breaker)
XK1 = Connector for power circuits of the PR122/DC and PR123/DC trip units
XK2 - XK3 = Connectors for auxiliary circuits of the PR122/DC and PR123/DC trip units
XK4 = Connector for open/closed indication contacts
XO = Connector for the YO1 release
XV = Delivery terminal board for fixed version circuit-breaker auxiliary contacts
YC = Shunt closing release
YO = Shunt opening release
YO1 = Overcurrent release
YO2 = Second shunt opening release (see note Q)
YR = Coil for circuit-breaker electrical resetting
YU = Undervoltage release (see note B and note Q)
Description of figures
Fig. 1 = Circuit of the closing spring charging motor.
Fig. 2 = Circuit of the shunt closing release.
Fig. 4 = Shunt opening release.
Fig. 6 = Instantaneous undervoltage release (see notes B and Q).
Fig. 7 = Undervoltage release with electronic delay device, outside the circuit-breaker (see notes B and Q).
Fig. 8 = Second shunt opening release (see note Q).
Fig. 11 = Contact for electrical signalling of springs charged.
Fig. 12 = Contact for electrical signalling of undervoltage release excited (see notes B and S).
Fig. 13 = Contact for electrical signalling of circuit-breaker open due to trip of the overcurrent release.
Circuit-breaker closing can only take place after having pressed the reset pushbutton on the front
of the circuit-breaker.
Fig. 14 = Contact for electrical signalling of circuit-breaker open due to trip of the overcurrent release and
coil for electric resetting. Circuit-breaker closing can only take place after having pressed the reset
pushbutton or after having energised the coil.
Fig. 21 = First pack of circuit-breaker auxiliary contacts.
Fig. 22 = Second pack of circuit-breaker auxiliary contacts (see note V).
Fig. 23 = Third pack of additional auxiliary contacts outside the circuit-breaker.
Fig. 31 = First pack of contacts for electrical signalling of circuit-breaker in the racked-in, racked-out test
and racked-out position.
Fig. 32 = Second pack of contacts for electrical signalling of circuit-breaker in the racked-in, racked-out test
and racked-out position.
Fig. 42 = Auxiliary circuits of the PR122/DC and PR123/DC trip units (see notes F and V).
Fig. 45 = PR120/D-M communication module circuits of the PR122/DC and PR123/DC trip units (optional,
see note E).
Fig. 46 = PR120/K indication module circuits of the PR122/DC and PR123/DC trip units - connection 1
(optional; see note V).
Fig. 47 = PR120/K indication module circuits of the PR122/DC and PR123/DC trip units - connection 2
(optional; see note V).
Fig. 62 = PR021/K indication module circuits (outside the circuit-breaker)
Incompatibility
The circuits indicated in the following figures cannot be supplied at the same time on the same circuit-breaker:
6-7-8
13 - 14
22 - 46 - 47
36 ABB SACE
1SDC200012D0902
Notes
A) The circuit-breaker is only supplied with the accessories specified in the ABB SACE order acknowledgement. To
make out the order, please consult this catalogue.
B) The undervoltage release is provided for power supply on the generator side of the circuit-breaker or from an
independent source. Circuit-breaker closing is only allowed with the release excited (the lock on closing is made
mechanically). When there is the same power supply for the shunt closing and undervoltage releases, and one
wants automatic circuit-breaker closing on return of the auxiliary voltage, it is necessary to introduce a delay of
30 milliseconds between the instant of undervoltage release consent and excitation of the shunt closing release.
This can be carried out by means of a circuit outside the circuit-breaker including a permanent closing contact, the
contact indicated in figure 12 and a time-delay relay.
E) The details regarding communication with MODBUS Protocol are given in the Modbus System Interface document.
F) The auxiliary Vaux voltage allows activation of all the functionalities of the PR122/DC and PR123/DC trip units. Since
a Vaux insulated from earth is required, it is necessary to use galvanically separated converters conforming to IEC
60950 (UL 1950) Standards or equivalent, which guarantee a common mode current or a leakage current (see IEC
478/1, CEI 22/3) not exceeding 3.5 mA (IEC 60364-41 and CEI 64-8).
N) In the PR122/DC and PR123/DC trip units, the connections with zone selectivity inputs and outputs of must be
made using a bipolar shielded corded cable (see instruction manual) with a length not exceeding 300 m. The shield
must be earthed on the input side of selectivity.
P) In the PR122/DC and PR123/DC trip units with PR120/D-M communication module, the power supply of the YO
and YC coils must not be derived from the main one. The coils can be controlled directly by the K51/YO and K51/
YC contacts with maximum voltage values of 110-120 V DC and 240-250 V AC.
Q) The second shunt opening release is to be installed as an alternative to the undervoltage release.
S) Also available in the version with normally closed contact.
V) When the contacts in fig. 22 are provided (second pack of auxiliary contacts) together with the PR122/DC or PR123/
DC trip unit, the contacts relative to the zone selectivity in fig. 42 (K51/Zin, K51/Zout, K51/Gzin and K51/Gzout) are
not wired. Furthermore, the PR120/K indication module of figure 46 and 47 cannot be supplied.
ABB SACE 37
1SDC200012D0902
Electric wiring diagrams
Graphic Symbols (IEC 606 7 and CEI 3- 4 ... 3-26 Standards)
Shielded cable conductors Closing position contact Overcurrent relay for earth
(e.g. three conductors) (limit switch) fault with short inverse time
characteristic
1SDC200628F0001
Conductors or corded ca- Opening position contact Fuse
bles (e.g. 3 conductors) (limit switch) (general symbol)
38 ABB SACE
1SDC200012D0902
Electric wiring diagrams
Circuit-breakers
State of operation
+ -
K51
Q
>
XK10
A1I 1 >>
2
A1E XO
>> 1
>>
>
1
Y01
XO
2
C
D
>>
0/
2
12
PR
PR122/DC
XK11
B1I 1
2
B1E
PR123/DC
1SDC200629F0001
+ -
K51
Q
XK10
A1I 1 >>
2
A1E XO
>> 1
>>>
1
Y01
XO
2
DC
>>
0/
2
12
PR
PR122/DC
XK11
B1I 2
1
B1E
PR123/DC
1SDC200630F0001
C
/D0
12
PR
ABB SACE 39
1SDC200012D0902
Electric wiring diagrams
Circuit-breakers
1SDC200633F0001
Signalling contacts
1SDC200634F0001
40 ABB SACE
1SDC200012D0902
Signalling contacts
1SDC200635F0001
1SDC200636F0001
ABB SACE 41
1SDC200012D0902
Electric wiring diagrams
Circuit-breakers
PR122/DC
PR123/DC
1SDC200637F0001
BUS2
PR122/DC
PR123/DC
1SDC200638F0001
BUS1
42 ABB SACE
1SDC200012D0902
PR120/K indication module
(+)
(+)
(+)
PR122/DC PR122/DC
PR123/DC PR123/DC
(-)
(-)
(-)
1SDC200639F0001
PR021/K indication unit
PR122/DC
PR123/DC
BUS2
1SDC200640F0001
ABB SACE 43
1SDC200012D0902
Selection of Emax DC
Plates:
1SDC200605F0001
POWER INPUT TO THE LOWER TERMINALS
1SDC200606F0001
44 ABB SACE
1SDC200012D0902
+
L
O
INSULATED A
D
-
NETWORK
Rated
Ue 500 500V Ue 750V 750V Ue 1000V
voltage (Ue)
POLES 3p 4p 3p 4p 4p
LOAD - LOAD -
LOAD + - LOAD + -
+ +
Power supply
from the lower Front view Front view Front view Front view Front view
terminals
(Lower Supply)
3D rear view 3D rear view 3D rear view 3D rear view 3D rear view
+ LOAD +
- + LOAD +
-
LOAD - LOAD -
Power supply
from the upper Front view Front view Front view Front view Front view
terminals
(Upper Supply)
3D rear view 3D rear view 3D rear view 3D rear view 3D rear view
PR122/DC
PR123/DC
ABB SACE 45
1SDC200012D0902
Selection of Emax DC
+
L
NETWORK WITH O
A
D
EARTHED -
2
MEDIAN POINT
2
Rated
Ue 500V 500V Ue 750V 750V Ue 1000V
voltage (Ue)
Poles 3p 4p 4p 4p
LOAD -
LOAD + -
+
Power supply
from the lower Front view Front view Front view Front view
terminals
(Lower Supply)
+ LOAD +
-
LOAD -
Power supply
from the upper Front view Front view Front view Front view
terminals
(Upper Supply)
PR123/DC
46 ABB SACE
1SDC200012D0902
The following tables show the possible configurations according to the type of network:
+
NETWORK WITH L
O
EARTHED -
A
D
NEGATIVE
POLARITY
Poles 3p 4p
LOAD -
LOAD + -
+
Power supply
from the lower Front view Front view
terminals
(Lower Supply)
+ LOAD +
-
LOAD -
Power supply
from the upper Front view Front view
terminals
(Upper Supply)
PR122/DC
PR123/DC
1) For higher voltages, ask ABB SACE
It is necessary to specify the 1SDA068806R1 extracode for the special dedicated configuration with 4 poles.
ABB SACE 47
1SDC200012D0902
Selection of Emax DC
Ordering Rules
CODE
LOAD -
+ LOAD + -
To change the power supply side from the lower terminals to the upper ones, it is necessary
to specify the 1SDA058251R1 extracode.
CODE + 1SDA058251R1
+ LOAD +
-
LOAD -
In the case of a network with earthed negative polarity and a four-pole circuit-breaker (4p), it
is always necessary to specify the 1SDA068806R1 extracode
CODE + 1SDA068806R1
48 ABB SACE
1SDC200012D0902
Withdrawable circuit-breaker (W)
MOVING PART
For the moving part in withdrawable circuit-breakers supplied from the lower terminals, it is sufficient to
indicate just the circuit-breaker code. The voltage sockets are therefore positioned on the lower terminals.
CODE LOAD -
LOAD -
LOAD + -
+ LOAD +
+ -
If supplied from the upper terminals, it is necessary to move the voltage sockets onto the upper
terminals, specifying the 1SDA058251R1 extracode:
CODE + 1SDA058251R1
+ -
+ LOAD +
LOAD +
-
LOAD -
LOAD -
FIXED PART
The configuration of the fixed part for Emax DC circuit-breakers must be constructed starting with
the fixed parts for special applications up to 750/1000V DC and adding the U connection kit:
In the case of a network with earthed negative polarity and 4p circuit-breaker, the 1SDA068806R1
extracode must be specified in addition in order to have 3 poles in series on the positive pole.
ABB SACE 49
1SDC200012D0902
Ordering codes
Insulated network - Lower power supply
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
PR122/DC
3p 4000 H 64657
4p 4000 H 64660
5000 H 64661
50 ABB SACE
1SDC200012D0902
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
PR123/DC
3p 4000 H 64745
4p 4000 H 64748
5000 H 64749
ABB SACE 51
1SDC200012D0902
Ordering codes
Insulated network - Upper power supply
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
PR122/DC
H 64661
52 ABB SACE
1SDC200012D0902
1SDA0...R1
+
L
O
Ue<100V Vaux is compulsory
A
- D
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
PR123/DC
H 64749
ABB SACE 53
1SDC200012D0902
Ordering codes
Insulated network - Lower power supply
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
PR122/DC
MP Fixed part
Vertical terminals
1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code Code + Extracode
LOAD - 800 B 64590
1000 B 64591
3p 1250 B 64592 59895 + 65169
B 64593
E2 LOAD + 1600
+ -
N 64594
Withdrawable
W-VR 800 B 64595
1000 B 64596
4p 1250 B 64597 59906 + 65169
B 64598
1600
N 64599
800 N 64618
1000 N 64619
LOAD - 1250 N 64620
N 64621
1600
3p H 64624 59896 + 65169
N 64622
2000
H 64625
LOAD + -
+
N 64623
E3 2500
H 64626
Withdrawable
W-VR 800 N 64627
1000 N 64628
1250 N 62629
N 64630
1600
4p H 64633 59907 + 65169
N 64631
2000
H 64634
N 64632
2500
H 64635
LOAD - 1600 S 64646
2000 S 64647
3p 2500 S 64648 59897 + 65169
S 64649
E4 3200
H 64650
LOAD + -
+
Withdrawable
W-VR 1600 S 64651
2000 S 64652
4p 2500 S 64653 59137 + 65169
S 64654
3200
H 64655
LOAD -
3200 H 64662
5000 H 64667
54 ABB SACE
1SDC200012D0902
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
PR123/DC
MP Fixed part
Vertical terminals
1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code Code + Extracode
LOAD - 800 B 64678
1000 B 64679
3p 1250 B 64680 59895 + 65169
B 64681
E2 LOAD + - 1600
+
N 64682
Withdrawable
W-VR 800 B 64683
1000 B 64684
4p 1250 B 64685 59906 + 65169
B 64686
1600
N 64687
800 N 64706
1000 N 64707
LOAD - 1250 N 64708
N 64709
1600
3p H 64712 59896 + 65169
N 64710
LOAD + 2000
+ -
H 64713
N 64711
E3 2500
H 64714
Withdrawable
W-VR 800 N 64715
1000 N 64716
1250 N 64717
N 64718
1600
4p H 64721 59907 + 65169
N 64719
2000
H 64722
N 64720
2500
H 64723
LOAD - 1600 S 64734
2000 S 64735
3p 2500 S 64736 59897 + 65169
S 64737
E4 LOAD + 3200
+ -
H 64738
Withdrawable
W-VR 1600 S 64739
2000 S 64740
4p 2500 S 64741 59137 + 65169
S 64742
3200
H 64743
LOAD -
3200 H 64750
5000 H 64755
ABB SACE 55
1SDC200012D0902
Ordering codes
Insulated network - Upper power supply
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
PR122/DC
MP Fixed part
Vertical terminals
1sda0R1 1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code + Extracode Code + Extracode
+ LOAD +
- 800 B 64590 +
1000 B 64591 +
3p 1250 B 64592 + 58251 59895 + 65619
B 64593 +
E2 1600
LOAD -
N 64594 +
Withdrawable
W-VR 800 B 64595 +
1000 B 64596 +
4p 1250 B 64597 + 58251 59906 + 65619
B 64598 +
1600
N 64599 +
800 N 64618 +
1000 N 64619 +
+ LOAD +
- 1250 N 64620 +
N 64621 +
1600
3p H 64624 + 58251 59896 + 65619
N 64622 +
LOAD - 2000
H 64625 +
N 64623 +
E3 2500
H 64626 +
Withdrawable
W-VR 800 N 64627 +
1000 N 64628 +
1250 N 62629 +
N 64630 +
1600
4p H 64633 + 58251 59907 + 65619
N 64631 +
2000
H 64634 +
N 64632 +
2500
H 64635 +
+ LOAD +
- 1600 S 64646 +
2000 S 64647 +
3p 2500 S 64648 + 58251 59897 + 65619
S 64649 +
E4 3200
LOAD -
H 64650 +
Withdrawable
W-VR 1600 S 64651 +
2000 S 64652 +
4p 2500 S 64653 + 58251 59137 + 65619
S 64654 +
3200
H 64655 +
+ -
LOAD +
3200 H 64662 +
5000 H 64667 +
56 ABB SACE
1SDC200012D0902
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
PR123/DC
MP Fixed part
Vertical terminals
1sda0R1 1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code + Extracode Code + Extracode
+ LOAD +
- 800 B 64678 +
1000 B 64679 +
3p 1250 B 64680 + 58251 59895 + 65619
B 64681 +
E2 1600
LOAD -
N 64682 +
Withdrawable
W-VR 800 B 64683 +
1000 B 64684 +
4p 1250 B 64685 + 58251 59906 + 65619
B 64686 +
1600
N 64687 +
800 N 64706 +
1000 N 64707 +
+ LOAD +
- 1250 N 64708 +
N 64709 +
1600
3p H 64712 + 58251 59896 + 65619
N 64710 +
LOAD - 2000
H 64713 +
N 64711 +
E3 2500
H 64714 +
Withdrawable
W-VR 800 N 64715 +
1000 N 64716 +
1250 N 64717 +
N 64718 +
1600
4p H 64721 + 58251 59907 + 65619
N 64719 +
2000
H 64722 +
N 64720 +
2500
H 64723 +
+ LOAD +
- 1600 S 64734 +
2000 S 64735 +
3p 2500 S 64736 + 58251 59897 + 65619
S 64737 +
E4 3200
LOAD -
H 64738 +
Withdrawable
W-VR 1600 S 64739 +
2000 S 64740 +
4p 2500 S 64741 + 58251 59137 + 65619
S 64742 +
3200
H 64743 +
+ -
LOAD +
3200 H 64750 +
5000 H 64755 +
ABB SACE 57
1SDC200012D0902
Ordering codes
Insulated network - Lower power supply
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
PR122/DC
MP Fixed part
Horizontal terminals
1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code Code + Extracode
LOAD - 800 B 64590
1000 B 64591
3p 1250 B 64592 59891 + 67149
B 64593
E2 1600
N 64594
LOAD + -
+
Withdrawable
W-HR 800 B 64595
1000 B 64596
4p 1250 B 64597 59903 + 67149
B 64598
1600
N 64599
800 N 64618
1000 N 64619
LOAD - 1250 N 64620
N 64621
1600
3p H 64624 59892 + 67149
N 64622
LOAD + 2000
+ -
H 64625
N 64623
E3 2500
H 64626
Withdrawable
W-HR 800 N 64627
1000 N 64628
1250 N 62629
N 64630
1600
4p H 64633 59904 + 67149
N 64631
2000
H 64634
N 64632
2500
H 64635
LOAD - 1600 S 64646
2000 S 64647
3p 2500 S 64648 59893 + 67149
S 64649
E4 LOAD + 3200
+ -
H 64650
Withdrawable
W-HR 1600 S 64651
2000 S 64652
4p 2500 S 64653 59136 + 67149
S 64654
3200
H 64655
LOAD -
3200 H 64662
5000 H 64667
58 ABB SACE
1SDC200012D0902
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
PR123/DC
MP Fixed part
Horizontal terminals
1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code Code + Extracode
LOAD - 800 B 64678
1000 B 64679
3p 1250 B 64680 59891 + 67149
B 64681
E2 1600
N 64682
LOAD + -
+
Withdrawable
W-HR 800 B 64683
1000 B 64684
4p 1250 B 64685 59903 + 67149
B 64686
1600
N 64687
800 N 64706
1000 N 64707
LOAD - 1250 N 64708
N 64709
1600
3p H 64712 59892 + 67149
N 64710
LOAD + 2000
+ -
H 64713
N 64711
E3 2500
H 64714
Withdrawable
W-HR 800 N 64715
1000 N 64716
1250 N 64717
N 64718
1600
4p H 64721 59904 + 67149
N 64719
2000
H 64722
N 64720
2500
H 64723
LOAD - 1600 S 64734
2000 S 64735
3p 2500 S 64736 59893 + 67149
S 64737
E4 LOAD + 3200
+ -
H 64738
Withdrawable
W-HR 1600 S 64739
2000 S 64740
4p 2500 S 64741 59136 + 67149
S 64742
3200
H 64743
LOAD -
3200 H 64750
5000 H 64755
ABB SACE 59
1SDC200012D0902
Ordering codes
Insulated network - Upper power supply
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
PR122/DC
MP Fixed part
Horizontal terminals
1sda0R1 1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code + Code Extracode + Extracode
+ LOAD +
- 800 B 64590 +
1000 B 64591 +
3p 1250 B 64592 + 58251 59891 + 67150
B 64593 +
E2 1600
LOAD -
N 64594 +
Withdrawable
W-HR 800 B 64595 +
1000 B 64596 +
4p 1250 B 64597 + 58251 59903 + 67150
B 64598 +
1600
N 64599 +
800 N 64618 +
1000 N 64619 +
+ LOAD +
- 1250 N 64620 +
N 64621 +
1600
3p H 64624 + 58251 59892 + 67150
N 64622 +
2000
H 64625 +
LOAD -
N 64623 +
E3 2500
H 64626 +
Withdrawable
W-HR 800 N 64627 +
1000 N 64628 +
1250 N 62629 +
N 64630 +
1600
4p H 64633 + 58251 59904 + 67150
N 64631 +
2000
H 64634 +
N 64632 +
2500
H 64635 +
+ LOAD +
- 1600 S 64646 +
2000 S 64647 +
3p 2500 S 64648 + 58251 59893 + 67150
S 64649 +
E4 3200
LOAD -
H 64650 +
Withdrawable
W-HR 1600 S 64651 +
2000 S 64652 +
4p 2500 S 64653 + 58251 59136 + 67150
S 64654 +
3200
H 64655 +
+ -
3200 H 64662 +
LOAD +
5000 H 64667 +
60 ABB SACE
1SDC200012D0902
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
PR123/DC
MP Fixed part
Horizontal terminals
1sda0R1 1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code + Code Extracode + Extracode
+ LOAD +
- 800 B 64678 +
1000 B 64679 +
3p 1250 B 64680 + 58251 59891 + 67150
B 64681 +
E2 1600
LOAD -
N 64682 +
Withdrawable
W-HR 800 B 64683 +
1000 B 64684 +
4p 1250 B 64685 + 58251 59903 + 67150
B 64686 +
1600
N 64687 +
800 N 64706 +
1000 N 64707 +
+ LOAD +
- 1250 N 64708 +
N 64709 +
1600
3p H 64712 + 58251 59892 + 67150
N 64710 +
2000
H 64713 +
LOAD -
N 64711 +
E3 2500
H 64714 +
Withdrawable
W-HR 800 N 64715 +
1000 N 64716 +
1250 N 64717 +
N 64718 +
1600
4p H 64721 + 58251 59904 + 67150
N 64719 +
2000
H 64722 +
N 64720 +
2500
H 64723 +
+ LOAD +
- 1600 S 64734 +
2000 S 64735 +
3p 2500 S 64736 + 58251 59893 + 67150
S 64737 +
E4 3200
LOAD -
H 64738 +
Withdrawable
W-HR 1600 S 64739 +
2000 S 64740 +
4p 2500 S 64741 + 58251 59136 + 67150
S 64742 +
3200
H 64743 +
+ -
3200 H 64750 +
LOAD +
5000 H 64755 +
ABB SACE 61
1SDC200012D0902
Ordering codes
Network median point earthed - Lower power supply
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
2 Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
2
PR123/DC
N 64693
E3 2500
H 64696
Fixed
F-VR 800 N 64697
1000 N 64698
1250 N 64699
N 64700
1600
4p H 64703
N 64701
2000
H 64704
N 64702
2500
H 64705
LOAD - 1600 S 64724
2000 S 64725
3p 2500 S 64726
S 64727
E4 LOAD + 3200
+ -
H 64728
Fixed
F-VR 1600 S 64729
2000 S 64730
4p 2500 S 64731
S 64732
3200
H 64733
LOAD -
3200 H 64744
3p 4000 H 64745
4p 4000 H 64748
5000 H 64749
62 ABB SACE
1SDC200012D0902
Ordering codes
Network median point earthed - Upper power supply
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
2 Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
2
PR123/DC
Fixed
F-VR 1600 S 64729 +
2000 S 64730 +
4p 2500 S 64731 + 58251
S 64732 +
3200
H 64733 +
+ -
3200 H 64744 +
LOAD +
5000 H 64749 +
ABB SACE 63
1SDC200012D0902
Ordering codes
Network median point earthed - Lower power supply
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
2 Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
2
PR123/DC
MP Fixed part
Vertical terminals
1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code Code + Extracode
LOAD - 800 B 64678
1000 B 64679
3p 1250 B 64680 59895 + 65169
B 64681
E2 LOAD + - 1600
+
N 64682
Withdrawable
W-VR 800 B 64683
1000 B 64684
4p 1250 B 64685 59906 + 65169
B 64686
1600
N 64687
800 N 64706
1000 N 64707
LOAD - 1250 N 64708
N 64709
1600
3p H 64712 59896 + 65169
N 64710
LOAD + 2000
+ -
H 64713
N 64711
E3 2500
H 64714
Withdrawable
W-VR 800 N 64715
1000 N 64716
1250 N 64717
N 64718
1600
4p H 64721 59907 + 65169
N 64719
2000
H 64722
N 64720
2500
H 64723
LOAD - 1600 S 64734
2000 S 64735
3p 2500 S 64736 59897 + 65169
S 64737
E4 LOAD + 3200
+ -
H 64738
Withdrawable
W-VR 1600 S 64739
2000 S 64740
4p 2500 S 64741 59137 + 65169
S 64742
3200
H 64743
LOAD -
3200 H 64750
5000 H 64755
64 ABB SACE
1SDC200012D0902
Ordering codes
Network median point earthed - Upper power supply
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
2 Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
2
PR123/DC
MP Fixed part
Vertical terminals
1sda0R1 1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code + Extracode Code + Extracode
+ LOAD +
- 800 B 64678 +
1000 B 64679 +
3p 1250 B 64680 + 58251 59895 + 65619
B 64681 +
E2 1600
LOAD -
N 64682 +
Withdrawable
W-VR 800 B 64683 +
1000 B 64684 +
4p 1250 B 64685 + 58251 59906 + 65619
B 64686 +
1600
N 64687 +
800 N 64706 +
1000 N 64707 +
+ LOAD +
- 1250 N 64708 +
N 64709 +
1600
3p H 64712 + 58251 59896 + 65619
N 64710 +
2000
LOAD -
H 64713 +
N 64711 +
E3 2500
H 64714 +
Withdrawable
W-VR 800 N 64715 +
1000 N 64716 +
1250 N 64717 +
N 64718 +
1600
4p H 64721 + 58251 59907 + 65619
N 64719 +
2000
H 64722 +
N 64720 +
2500
H 64723 +
+ LOAD +
- 1600 S 64734 +
2000 S 64735 +
3p 2500 S 64736 + 58251 59897 + 65619
S 64737 +
E4 3200
LOAD -
H 64738 +
Withdrawable
W-VR 1600 S 64739 +
2000 S 64740 +
4p 2500 S 64741 + 58251 59137 + 65619
S 64742 +
3200
H 64743 +
+ -
3200 H 64750 +
LOAD +
5000 H 64755 +
ABB SACE 65
1SDC200012D0902
Ordering codes
Network median point earthed - Lower power supply
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
2 Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
2
PR123/DC
MP Fixed part
Vertical terminals
1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code Code + Extracode
LOAD - 800 B 64678
1000 B 64679
3p 1250 B 64680 59891 + 67149
B 64681
E2 + LOAD + - 1600
N 64682
Withdrawable
W-HR 800 B 64683
1000 B 64684
4p 1250 B 64685 59903 + 67149
B 64686
1600
N 64687
800 N 64706
1000 N 64707
LOAD - 1250 N 64708
N 64709
1600
3p H 64712 59892 + 67149
N 64710
2000
H 64713
LOAD + -
+
N 64711
E3 2500
H 64714
Withdrawable
W-HR 800 N 64715
1000 N 64716
1250 N 64717
N 64718
1600
4p H 64721 59904 + 67149
N 64719
2000
H 64722
N 64720
2500
H 64723
LOAD - 1600 S 64734
2000 S 64735
3p 2500 S 64736 59893 + 67149
S 64737
E4 LOAD + 3200
+ -
H 64738
Withdrawable
W-HR 1600 S 64739
2000 S 64740
4p 2500 S 64741 59136 + 67149
S 64742
3200
H 64743
LOAD -
3200 H 64750
5000 H 64755
66 ABB SACE
1SDC200012D0902
Ordering codes
Network median point earthed - Upper power supply
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
2 Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
2
PR123/DC
MP Fixed part
Vertical terminals
1sda0R1 1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code + Extracode Code + Extracode
+ LOAD +
- 800 B 64678 +
1000 B 64679 +
3p 1250 B 64680 + 58251 59891 + 67150
B 64681 +
E2 1600
LOAD -
N 64682 +
Withdrawable
W-HR 800 B 64683 +
1000 B 64684 +
4p 1250 B 64685 + 58251 59903 + 67150
B 64686 +
1600
N 64687 +
800 N 64706 +
1000 N 64707 +
+ LOAD +
- 1250 N 64708 +
N 64709 +
1600
3p H 64712 + 58251 59892 + 67150
N 64710 +
2000
LOAD -
H 64713 +
N 64711 +
E3 2500
H 64714 +
Withdrawable
W-HR 800 N 64715 +
1000 N 64716 +
1250 N 64717 +
N 64718 +
1600
4p H 64721 + 58251 59904 + 67150
N 64719 +
2000
H 64722 +
N 64720 +
2500
H 64723 +
+ LOAD +
- 1600 S 64734 +
2000 S 64735 +
3p 2500 S 64736 + 58251 59893 + 67150
S 64737 +
E4 3200
LOAD -
H 64738 +
Withdrawable
W-HR 1600 S 64739 +
2000 S 64740 +
4p 2500 S 64741 + 58251 59136 + 67150
S 64742 +
3200
H 64743 +
+ -
3200 H 64750 +
LOAD +
5000 H 64755 +
ABB SACE 67
1SDC200012D0902
Ordering codes
Network with earthed negative polarity -
Lower power supply
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe500V* PR120/V
* For higher voltages, contact ABB
PR122/DC
N 64605 +
E3 2500
H 64608 +
Fixed
F-VR 800 N 64609 +
1000 N 64610 +
1250 N 64611 +
N 64612 +
1600
4p H 64615 + 68806
N 64613 +
2000
H 64616 +
N 64614 +
2500
H 64617 +
LOAD - 1600 S 64636 +
2000 S 64637 +
3p 2500 S 64638 + -
S 64639 +
E4 LOAD + - 3200
+
H 64640 +
Fixed
F-VR 1600 S 64641 +
2000 S 64642 +
4p 2500 S 64643 + 68806
S 64644 +
3200
H 64645 +
LOAD -
3200 H 64656 +
3p 4000 H 64657 + -
5000 H 64661 +
68 ABB SACE
1SDC200012D0902
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe500V* PR120/V
* For higher voltages, contact ABB
PR123/DC
N 64693 +
E3 2500
H 64696 +
Fixed
F-VR 800 N 64697 +
1000 N 64698 +
1250 N 64699 +
N 64700 +
1600
4p H 64703 + 68806
N 64701 +
2000
H 64704 +
N 64702 +
2500
H 64705 +
LOAD - 1600 S 64724 +
2000 S 64725 +
3p 2500 S 64726 + -
S 64727 +
E4 LOAD + 3200
+ -
H 64728 +
Fixed
F-VR 1600 S 64729 +
2000 S 64730 +
4p 2500 S 64731 + 68806
S 64732 +
3200
H 64733 +
LOAD -
3200 H 64744 +
3p 4000 H 64745 + -
5000 H 64749 +
ABB SACE 69
1SDC200012D0902
Ordering codes
Network with earthed negative polarity -
Upper power supply
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe500V* PR120/V
* For higher voltages, contact ABB
PR122/DC
Fixed
F-VR 1600 S 64641 + +
2000 S 64642 + +
4p 2500 S 64643 + 58251 + 68806
S 64644 + +
3200
H 64645 + +
+ -
LOAD +
3200 H 64656 + +
5000 H 64661 + +
70 ABB SACE
1SDC200012D0902
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe500V* PR120/V
* For higher voltages, contact ABB
PR123/DC
Fixed
F-VR 800 B 64673 + +
1000 B 64674 + +
4p 1250 B 64675 + 58251 + 68806
B 64676 + +
1600
N 64677 + +
800 N 64688 + +
1000 N 64689 + +
+ LOAD +
- 1250 N 64690 + +
N 64691 + +
1600
3p H 64694 + 58251 + -
N 64692 + +
2000
LOAD -
H 64695 + +
N 64693 + +
E3 2500
H 64696 + +
Fixed
F-VR 800 N 64697 + +
1000 N 64698 + +
1250 N 64699 + +
N 64700 + +
1600
4p H 64703 + 58251 + 68806
N 64701 + +
2000
H 64704 + +
N 64702 + +
2500
H 64705 + +
+ LOAD +
- 1600 S 64724 + +
2000 S 64725 + +
3p 2500 S 64726 + 58251 + -
S 64727 + +
E4 3200
H 64728 + +
LOAD -
Fixed
F-VR 1600 S 64729 + +
2000 S 64730 + +
4p 2500 S 64731 + 58251 + 68806
S 64732 + +
3200
H 64733 + +
+ -
LOAD +
3200 H 64744 + +
5000 H 64749 + +
ABB SACE 71
1SDC200012D0902
Ordering codes
Network with earthed negative polarity -
Lower power supply
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe500V* PR120/V
* For higher voltages, contact ABB
PR122/DC
MP Fixed part
Vertical terminals
1sda0R1 1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code Code + Extracode + Extracode
LOAD - 800 B 64590
1000 B 64591
3p 1250 B 64592 59895 + 65169 + -
B 64593
E2 1600
N 64594
LOAD + -
+
Withdrawable
W-VR 800 B 64595
1000 B 64596
4p 1250 B 64597 59906 + 65169 + 68806
B 64598
1600
N 64599
800 N 64618
1000 N 64619
LOAD - 1250 N 64620
N 64621
1600
3p H 64624 59896 + 65169 + -
N 64622
2000
H 64625
LOAD + -
+
N 64623
E3 2500
H 64626
Withdrawable
W-VR 800 N 64627
1000 N 64628
1250 N 62629
N 64630
1600
4p H 64633 59907 + 65169 + 68806
N 64631
2000
H 64634
N 64632
2500
H 64635
LOAD - 1600 S 64646
2000 S 64647
3p 2500 S 64648 59897 + 65169 + -
S 64649
E4 LOAD + 3200
+ -
H 64650
Withdrawable
W-VR 1600 S 64651
2000 S 64652
4p 2500 S 64653 59137 + 65169 + 68806
S 64654
3200
H 64655
LOAD -
3200 H 64662
5000 H 64667
72 ABB SACE
1SDC200012D0902
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe500V* PR120/V
* For higher voltages, contact ABB
PR123/DC
MP Fixed part
Vertical terminals
1sda0R1 1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code Code + Extracode + Extracode
LOAD - 800 B 64678
1000 B 64679
3p 1250 B 64680 59895 + 65169 + -
B 64681
E2 LOAD + - 1600
+
N 64682
Withdrawable
W 800 B 64683
1000 B 64684
4p 1250 B 64685 59906 + 65169 + 68806
B 64686
1600
N 64687
800 N 64706
1000 N 64707
LOAD - 1250 N 64708
N 64709
1600
3p H 64712 59896 + 65169 + -
N 64710
LOAD + - 2000
+
H 64713
N 64711
E3 2500
H 64714
Withdrawable
W 800 N 64715
1000 N 64716
1250 N 64717
N 64718
1600
4p H 64721 59907 + 65169 + 68806
N 64719
2000
H 64722
N 64720
2500
H 64723
LOAD - 1600 S 64734
2000 S 64735
3p 2500 S 64736 59897 + 65169 + -
S 64737
E4 3200
H 64738
LOAD + -
+
Withdrawable
W 1600 S 64739
2000 S 64740
4p 2500 S 64741 59137 + 65169 + 68806
S 64742
3200
H 64743
LOAD -
3200 H 64750
5000 H 64755
ABB SACE 73
1SDC200012D0902
Ordering codes
Network with earthed negative polarity -
Upper power supply
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe500V* PR120/V
* For higher voltages, contact ABB
PR122/DC
MP Fixed part
Vertical terminals
1sda0R1 1sda0R1 1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code + Code Code + Extracode + Extracode
+ LOAD +
- 800 B 64590 +
1000 B 64591 +
3p 1250 B 64592 + 58251 59895 + 65619 + -
B 64593 +
E2 LOAD - 1600
N 64594 +
Withdrawable
W-VR 800 B 64595 +
1000 B 64596 +
4p 1250 B 64597 + 58251 59906 + 65619 + 68806
B 64598 +
1600
N 64599 +
800 N 64618 +
1000 N 64619 +
+ LOAD +
- 1250 N 64620 +
N 64621 +
1600
3p H 64624 + 58251 59896 + 65619 + -
N 64622 +
2000
LOAD -
H 64625 +
N 64623 +
E3 2500
H 64626 +
Withdrawable
W-VR 800 N 64627 +
1000 N 64628 +
1250 N 62629 +
N 64630 +
1600
4p H 64633 + 58251 59907 + 65619 + 68806
N 64631 +
2000
H 64634 +
N 64632 +
2500
H 64635 +
+ LOAD +
- 1600 S 64646 +
2000 S 64647 +
3p 2500 S 64648 + 58251 59897 + 65619 + -
S 64649 +
E4 3200
LOAD -
H 64650 +
Withdrawable
W-VR 1600 S 64651 +
2000 S 64652 +
4p 2500 S 64653 + 58251 59137 + 65619 + 68806
S 64654 +
3200
H 64655 +
+ -
LOAD +
3200 H 64662 +
5000 H 64667 +
74 ABB SACE
1SDC200012D0902
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe500V* PR120/V
* For higher voltages, contact ABB
PR123/DC
MP Fixed part
Vertical terminals
1sda0R1 1sda0R1 1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code + Extracode Code + Extracode + Extracode
+ LOAD +
- 800 B 64678 +
1000 B 64679 +
3p 1250 B 64680 + 58251 59895 + 65619 + -
B 64681 +
E2 1600
N 64682 +
LOAD -
Withdrawable
W-VR 800 B 64683 +
1000 B 64684 +
4p 1250 B 64685 + 58251 59906 + 65619 + 68806
B 64686 +
1600
N 64687 +
800 N 64706 +
1000 N 64707 +
+ LOAD +
- 1250 N 64708 +
N 64709 +
1600
3p H 64712 + 58251 59896 + 65619 + -
N 64710 +
2000
LOAD -
H 64713 +
N 64711 +
E3 2500
H 64714 +
Withdrawable
W-VR 800 N 64715 +
1000 N 64716 +
1250 N 64717 +
N 64718 +
1600
4p H 64721 + 58251 59907 + 65619 + 68806
N 64719 +
2000
H 64722 +
N 64720 +
2500
H 64723 +
+ LOAD +
- 1600 S 64734 +
2000 S 64735 +
3p 2500 S 64736 + 58251 59897 + 65619 + -
S 64737 +
E4 3200
H 64738 +
LOAD -
Withdrawable
W-VR 1600 S 64739 +
2000 S 64740 +
4p 2500 S 64741 + 58251 59137 + 65619 + 68806
S 64742 +
3200
H 64743 +
+ -
3200 H 64750 +
LOAD +
5000 H 64755 +
ABB SACE 75
1SDC200012D0902
Ordering codes
Network with earthed negative polarity -
Lower power supply
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe500V* PR120/V
* For higher voltages, contact ABB
PR122/DC
MP Fixed part
Horizontal terminals
1sda0R1 1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code Code + Extracode + Extracode
LOAD - 800 B 64590
1000 B 64591
3p 1250 B 64592 59891 + 67149 + -
B 64593
E2 LOAD + - 1600
+
N 64594
Withdrawable
W-HR 800 B 64595
1000 B 64596
4p 1250 B 64597 59903 + 67149 + 68806
B 64598
1600
N 64599
800 N 64618
1000 N 64619
LOAD - 1250 N 64620
N 64621
1600
3p H 64624 59892 + 67149 + -
N 64622
LOAD + - 2000
+
H 64625
N 64623
E3 2500
H 64626
Withdrawable
W-HR 800 N 64627
1000 N 64628
1250 N 62629
N 64630
1600
4p H 64633 59904 + 67149 + 68806
N 64631
2000
H 64634
N 64632
2500
H 64635
LOAD - 1600 S 64646
2000 S 64647
3p 2500 S 64648 59893 + 67149 + -
S 64649
E4 LOAD + 3200
+ -
H 64650
Withdrawable
W-HR 1600 S 64651
2000 S 64652
4p 2500 S 64653 59136 + 67149 + 68806
S 64654
3200
H 64655
LOAD -
3200 H 64662
5000 H 64667
76 ABB SACE
1SDC200012D0902
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe500V* PR120/V
* For higher voltages, contact ABB
PR123/DC
MP Fixed part
Horizontal terminals
1sda0R1 1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code Code + Extracode + Extracode
LOAD - 800 B 64678
1000 B 64679
3p 1250 B 64680 59891 + 67149 + -
B 64681
E2 LOAD + - 1600
+
N 64682
Withdrawable
W-HR 800 B 64683
1000 B 64684
4p 1250 B 64685 59903 + 67149 + 68806
B 64686
1600
N 64687
800 N 64706
1000 N 64707
LOAD - 1250 N 64708
N 64709
1600
3p H 64712 59892 + 67149 + -
N 64710
LOAD + 2000
+ -
H 64713
N 64711
E3 2500
H 64714
Withdrawable
W-HR 800 N 64715
1000 N 64716
1250 N 64717
N 64718
1600
4p H 64721 59904 + 67149 + 68806
N 64719
2000
H 64722
N 64720
2500
H 64723
LOAD - 1600 S 64734
2000 S 64735
3p 2500 S 64736 59893 + 67149 + -
S 64737
E4 LOAD + 3200
+ -
H 64738
Withdrawable
W-HR 1600 S 64739
2000 S 64740
4p 2500 S 64741 59136 + 67149 + 68806
S 64742
3200
H 64743
LOAD -
3200 H 64750
5000 H 64755
ABB SACE 77
1SDC200012D0902
Ordering codes
Network with earthed negative polarity -
Upper power supply
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe500V* PR120/V
* For higher voltages, contact ABB
PR122/DC
MP Fixed part
Horizontal terminals
1sda0R1 1sda0R1 1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code + Code Code + Extracode + Extracode
+ LOAD +
- 800 B 64590 +
1000 B 64591 +
3p 1250 B 64592 + 58251 59891 + 67150 + -
B 64593 +
E2 1600
N 64594 +
LOAD -
Withdrawable
W-HR 800 B 64595 +
1000 B 64596 +
4p 1250 B 64597 + 58251 59903 + 67150 + 68806
B 64598 +
1600
N 64599 +
800 N 64618 +
1000 N 64619 +
+ LOAD +
- 1250 N 64620 +
N 64621 +
1600
3p H 64624 + 58251 59892 + 67150 + -
N 64622 +
2000
H 64625 +
LOAD -
N 64623 +
E3 2500
H 64626 +
Withdrawable
W-HR 800 N 64627 +
1000 N 64628 +
1250 N 62629 +
N 64630 +
1600
4p H 64633 + 58251 59904 + 67150 + 68806
N 64631 +
2000
H 64634 +
N 64632 +
2500
H 64635 +
+ LOAD +
- 1600 S 64646 +
2000 S 64647 +
3p 2500 S 64648 + 58251 59893 + 67150 + -
S 64649 +
E4 3200
LOAD -
H 64650 +
Withdrawable
W-HR 1600 S 64651 +
2000 S 64652 +
4p 2500 S 64653 + 58251 59136 + 67150 + 68806
S 64654 +
3200
H 64655 +
+ -
3200 H 64662 +
LOAD +
5000 H 64667 +
78 ABB SACE
1SDC200012D0902
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe500V* PR120/V
* For higher voltages, contact ABB
PR123/DC
MP Fixed part
Horizontal terminals
1sda0R1 1sda0R1 1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code + Code Code + Extracode + Extracode
+ LOAD +
- 800 B 64678 +
1000 B 64679 +
3p 1250 B 64680 + 58251 59891 + 67150 + -
B 64681 +
E2 1600
N 64682 +
LOAD -
Withdrawable
W-HR 800 B 64683 +
1000 B 64684 +
4p 1250 B 64685 + 58251 59903 + 67150 + 68806
B 64686 +
1600
N 64687 +
800 N 64706 +
1000 N 64707 +
+ LOAD +
- 1250 N 64708 +
N 64709 +
1600
3p H 64712 + 58251 59892 + 67150 + -
N 64710 +
2000
H 64713 +
LOAD -
N 64711 +
E3 2500
H 64714 +
Withdrawable
W-HR 800 N 64715 +
1000 N 64716 +
1250 N 64717 +
N 64718 +
1600
4p H 64721 + 58251 59904 + 67150 + 68806
N 64719 +
2000
H 64722 +
N 64720 +
2500
H 64723 +
+ LOAD +
- 1600 S 64734 +
2000 S 64735 +
3p 2500 S 64736 + 58251 59893 + 67150 + -
S 64737 +
E4 3200
LOAD -
H 64738 +
Withdrawable
W-HR 1600 S 64739 +
2000 S 64740 +
4p 2500 S 64741 + 58251 59136 + 67150 + 68806
S 64742 +
3200
H 64743 +
+ -
3200 H 64750 +
LOAD +
5000 H 64755 +
ABB SACE 79
1SDC200012D0902
Ordering codes
SACE Emax switch-disconnectors for applications
up to 1000V DC
1SDA......R1
3 Poles 4 Poles
750V DC 1000V DC
80 ABB SACE
1SDC200012D0902
Ordering codes
Fixed parts for SACE Emax switch-disconnectors for
applications up to 1000V DC
1SDA......R1
3 Poles 4 Poles
750V DC 1000V DC
FP = Fixed part
E1 MS/E HR 059890 059902
Withdrawable (W) - MP VR 059894 059905
FL 059898 059908
HR FP = Fixed part
E2 MS/E HR 059891 059903
Withdrawable (W) - MP VR 059895 059906
FL 059899 059909
FP = Fixed part
E3 MS/E HR 059892 059904
Withdrawable (W) - MP VR 059896 059907
VR FL 059900 059910
FP = Fixed part
E4 MS/E HR 059893 059136
Withdrawable (W) - MP VR 059897 059137
FL 059901 059138
FP = Fixed part
E6 MS/E HR 059139 059142
Withdrawable (W) - MP VR 059140 059143
FL
FL 059141 059144
ABB SACE 81
1SDC200012D0902
Ordering codes
SACE Emax DC accessories
Electrical accessories
1sdaR1
82 ABB SACE
1SDC200012D0902
1sdaR1
ABB SACE 83
1SDC200012D0902
Ordering codes
SACE Emax DC accessories
1sdaR1
3 poles 4 poles
84 ABB SACE
1SDC200012D0902
Mechanical accessories
1sdaR1
Padlocks
E2/6 DC 8mm 064512
ABB SACE 85
1SDC200012D0902
Ordering codes
SACE Emax DC accessories
1sdaR1
1sdaR1
3 poles 4 poles
86 ABB SACE
1SDC200012D0902
Auxiliary units
1sdaR1
BT030-USB
E1/6 BT030-USB 058259
ABB SACE 87
1SDC200012D0902
Ordering Examples
+
L
O
A
- D
LOAD + LOAD + -
+ - +
isolation
protection
PR122/DC
PR123/DC
88 ABB SACE
1SDC200012D0902
According to plant requirements, the choice falls on E2B 3p because it has a value of Icu 20kA,
800A rated current and is fitted with PR122/DC.
As for all the withdrawable version circuit-breakers, both the moving part and the fixed part
must be ordered:
Moving part: as the standard solution, ABB SACE supplies the Emax DC moving parts with
voltage sockets located on the lower terminals, according to power supply from these same
terminals.
Fixed part: The same fixed parts with horizontal terminals as the switch-disconnectors are used
for special direct current applications (MS/E) up to 750V DC if they are 3p, up to 1000V DC if
they are 4p.
LOAD -
LOAD + -
+
ABB SACE 89
1SDC200012D0902
Ordering Examples
Plant requirements:
- Type of network: with median point earthed
- Rated current (Iu): 2500A
- Rated voltage (Ue): 1000V
- Short-circuit capacity (Icu): 30kA
- Version: Fixed (F)
- Power supply: from the vertical upper terminals
2 LOAD +
+ -
PR122/DC - - - -
PR123/DC
type of fault a b c a b c a b c a b c
poles in series affected by the fault 3 2 (U/2) 1 (U/2) 4 2 (U/2) 2 (U/2) 4 2 (U/2) 2 (U/2) 4 2 (U/2) 2 (U/2)
Icu(1) [kA] [kA] [kA] [kA]
800
1000
B 35 35 18 35 35 35 25 25 25 25 25 25
E2 1250
1600
N 1600 50 50 25 50 50 50 40 40 40 25 25 25
800
1000
1250
N 60 60 30 60 60 60 50 50 50 35 35 35
1600
E3 2000
2500
1600
H 2000 65(2) 65 40 65(2) 65(2) 65 (2) 50 50 50 40 40 40
2500
1600
2000
S 75 75 35 75 75 75 65 65 65 50 50 50
E4 2500
3200
H 3200 100 100 50 100 100 100 65 65 65 65 65 65
3200
E6 H 4000 100 100 65 100 100 100 65 65 65 65 65 65
5000
(1)
Icu with L/R = 15ms according to IEC 60946-2 Standard. For Icu with L/R = 5ms and L/R = 30ms, ask ABB.
(2)
85kA only if supplied from below and specifying the following extracode at the ordering stage: 1SDA067148R1. Ics=65kA.
90 ABB SACE
1SDC200012D0902
According to plant requirements, the choice falls on E3N because it has a value of Icu 30kA and
2500A rated current. Since a voltage Ue 750V is required, the version with 4 poles is necessary.
E3N20 PR123/DC 4p power supply from the upper terminals
As the standard solution, ABB SACE supplies fixed direct current circuit-breakers supplied from the
lower terminals. In the case of power supply from the upper terminals, it is necessary to specify the
1SDA058251R1 extracode at the time of ordering.
ABB SACE 91
1SDC200012D0902
Ordering Examples
Plant requirements:
- Type of network: with earthed negative polarity
- Rated current (Iu): 1600A
- Rated voltage (Ue): 400V
- Short-circuit capacity (Icu): 65kA also in the case of type b fault
- Version: Withdrawable (W)
- Power supply: from the lower terminals
- Vertical terminals
- Protections: LSIG
+
L
O
A
- D
LOAD + -
+
isolation
protection
PR122/DC
PR123/DC
type of fault(3) a b a b
poles in series affected by the fault 3 2 4 3
Icu(4) [kA] [kA]
800
1000
B 35 20 35 35
E2 1250
1600
N 1600 50 25 50 50
800
1000
1250
N 60 30 60 60
1600
E3 2000
2500
1600
H 2000 65(5) 40 65 (5) 65(5)
2500
1600
2000
S 100 50 100 100
E4 2500
3200
H 3200 100 65 100 100
3200
E6 H 4000 100 65 100 100
5000
(1)
for networks with positive earthed polarity, ask ABB.
(2)
for higher voltages, ask ABB.
(3)
for further information, see QT5: ABB circuit-breakers for direct current applications.
(4)
Icu with L/R = 15ms according to IEC 60946-2 Standard. For Icu with L/R = 5ms and L/R = 30ms, ask ABB.
(5)
85kA only if supplied from below and specifying the following extracode at the ordering stage: 1SDA067148R1. Ics=65kA.
92 ABB SACE
1SDC200012D0902
According to plant requirements, the choice falls on E3H because it has a value of Icu (up to 500V)
65kA and 1600A rated current, 4 poles.
E3H 16 PR123/DC 4p F VR
As the standard solution, ABB SACE supplies fixed direct current circuit-breakers supplied from the
lower terminals. The 4-pole configuration for network with earthed negative polarity requires a special
extracode which makes it possible to have 3 poles in series on the positive polarity (not earthed):
1SDA068806R1.
Emax DC E3H 16 PR123/DC 4p power upper supply with horizontal terminals (HR)
1SDA064703R1 E3H 1600 PR123/DC-In=1600 4p F
+
1SDA068806R1 Extracode for special connection with 3 poles in series on the positive polarity (not earthed)
ABB SACE 93
1SDC200012D0902