Technical catalogue

SACE Emax DC
Low voltage Direct Current
air circuit-breakers
Index
SACE Emax DC circuit-breakers . ............................................................................................ 2

SACE Emax DC switch-disconnectors..................................................................................... 6

Versions and connections ........................................................................................................ 7

Dissipated powers . .................................................................................................................. 8

Temperature derating ............................................................................................................... 9

Protection trip units and trip curves ....................................................................................... 11

Accessories ............................................................................................................................ 25

Overall dimensions ................................................................................................................. 26

Electric wiring diagrams ......................................................................................................... 35

Selection Emax DC................................................................................................................. 44

Ordering codes . .................................................................................................................... 50

Ordering examples ................................................................................................................. 88

ABB SACE 1
1SDC200012D0902
SACE Emax DC circuit-breakers

The SACE Emax range of low voltage circuit-breakers is completed by the new SACE Emax
DC series of circuit-breakers for direct current applications complying with the IEC60947-
2 Standard. Thanks to the exclusive technology applied to the new SACE PR123/DC and
PR122/DC trip units, the SACE Emax DC range allow all installation requirements to be met
and protection up to 1000V DC / 5000A.
With connection of three interruption poles in series, the rated voltage which can be reached
is 750V DC, whereas with four poles in series this rises to 1000V DC.
The withdrawable circuit-breakers must be associated with the fixed parts in a special version
for applications at 750/1000V DC.

Common data
Voltages
Rated service voltage Ue [V] 1000
Rated insulation voltage Ui [V] 1000
Rated impulse withstand voltage Uimp [kV] 12
Operating temperature [C] -25....+70

1SDC200601F0001
Storage temperature [C] -40....+70
Number of poles 3-4
Versions Fixed - Withdrawable

E2 E3 E4 E6
Levels of performance B N N H S H H
Rated uninterrupted current (at 40 C) Iu [A] 800 800
[A] 1000 1000
[A] 1250 1250
[A] 1600 1600 1600 1600 1600
[A] 2000 2000 2000
[A] 2500 2500 2500
[A] 3200 3200 3200
[A] 4000
[A] 5000
Rated ultimate short-circuit breaking capacity Icu according to the
See pages 3, 4 and 5
application network
Rated service short-circuit breaking capacity Ics [%Icu] [kA] 100% 100% 100% 100% 100% 100% 100%
Rated short-time withstand current Icw (0.5s)
@ 500 V DC (3p) [kA] 35 50 60 65 75 100 100
@ 750 V DC (3p) [kA] 25 25 40 40 65 65 65
@ 750 V DC (4p) [kA] 25 40 50 50 65 65 65
@ 1000 V DC (4p) [kA] 25 25 35 40 50 65 65
Rated short-circuit making capacity Icm [%Icu] [kA] 100% 100% 100% 100% 100% 100% 100%
Category of use (according to CEI EN 60947-2) B B B B B B B
Isolation behaviour (according to CEI EN 60947-2)
Overcurrent protection
Electronic trip units for DC applications
Operating times
Closing time (max) [ms] 80 80 80 80 80 80 80
Breaking time for I<Icw (max) (1) [ms] 60 60 60 60 60 60 60
Overall dimensions
Fixed: H = 418 mm - D = 302 mm - W (3/4 poles) [mm] 296/386 296/386 404/530 404/530 566/656 566/656 782/908
Withdrawable: H = 461 mm - D = 396.5 mm - W (3/4 poles) [mm] 324/414 324/414 432/558 432/558 594/684 594/684 810/936
Weights
Fixed 3/4 poles [kg] 50/61 50/61 66/80 66/80 97/117 97/117 140/160
Withdrawable 3/4 poles (including the fixed part) [kg] 50/61 50/61 66/80 66/80 147/165 147/165 210/240
(1) Without intentional delays.

E2 E3 E4 E6
800 800
2500
Iu 1000 1600 1000 1600 2000 2500 1600 2000 3200 4000 5000
3200
1250 1250
Life with regular maintenance N. operations
Mechanical x 1000 25 25 20 20 20 20 15 15 15 12 12 12
Electrical 1000V DC x 1000 15 10 12 10 9 7 7 7 7 5 4 2

2 ABB SACE
1SDC200012D0902
SACE Emax DC circuit-breakers
Rated ultimate short-circuit breaking capacity Icu
according to the type of network

Insulated network (1)


Rated voltage (Ue) 500 750 1000
LOAD - LOAD -

+
L
O
A
- D

LOAD + LOAD + -
+ - +

isolation
protection
PR122/DC
PR123/DC

Icu(2) [kA] [kA] [kA] [kA]


800
1000
B 35 25 25 25
E2 1250
1600
N 1600 50 25 40 25
800
1000
1250
N 60 40 50 35
1600
E3 2000
2500
1600
H 2000 65 (3) 40 50 40
2500
1600
2000
S 75 65 65 50
E4 2500
3200
H 3200 100 65 65 65
3200
E6 H 4000 100 65 65 65
5000
(1)
the possibility of a double earth fault is considered negligible with this type of pole connections. For further information, see QT5: ABB circuit-breakers for direct current applications.
(2)
Icu with L/R = 15ms according to IEC 60946-2 Standard. For Icu with L/R = 5ms and L/R = 30ms, ask ABB.
(3)
85kA only if supplied from below and specifying the following extracode at the ordering stage: 1SDA067148R1. Ics=65kA.

ABB SACE 3
1SDC200012D0902
SACE Emax DC circuit-breakers
Rated ultimate short-circuit breaking capacity Icu
according to the type of network

Network with earthed negative polarity (1)


Rated voltage (Ue) 500 (2)
LOAD -

+
L
O
A
- D

LOAD + -
+

isolation
protection
PR122/DC
PR123/DC
type of fault (3) a b a b
poles in series affected by the fault 3 2 4 3
Icu(4) [kA] [kA]
800
1000
B 35 20 35 35
E2 1250
1600
N 1600 50 25 50 50
800
1000
1250
N 60 30 60 60
1600
E3 2000
2500
1600
H 2000 65(5) 40 65 (5) 65(5)
2500
1600
2000
S 100 50 100 100
E4 2500
3200
H 3200 100 65 100 100
3200
E6 H 4000 100 65 100 100
5000
(1)
for networks with positive earthed polarity, ask ABB.
(2)
for higher voltages, ask ABB.
(3)
for further information, see QT5: ABB circuit-breakers for direct current applications.
(4)
Icu with L/R = 15ms according to IEC 60946-2 Standard. For Icu with L/R = 5ms and L/R = 30ms, ask ABB.
(5)
85kA only if supplied from below and specifying the following extracode at the ordering stage: 1SDA067148R1. Ics=65kA.

4 ABB SACE
1SDC200012D0902
Network with the median point earthed
Rated voltage (Ue) 500 500 750 1000
LOAD -
+
L
O
A
- D
2

2 LOAD +
+ -

PR122/DC - - - -
PR123/DC
type of fault a b c a b c a b c a b c
poles in series affected by the fault 3 2 (U/2) 1 (U/2) 4 2 (U/2) 2 (U/2) 4 2 (U/2) 2 (U/2) 4 2 (U/2) 2 (U/2)
Icu(1) [kA] [kA] [kA] [kA]
800
1000
B 35 35 18 35 35 35 25 25 25 25 25 25
E2 1250
1600
N 1600 50 50 25 50 50 50 40 40 40 25 25 25
800
1000
1250
N 60 60 30 60 60 60 50 50 50 35 35 35
1600
E3 2000
2500
1600
H 2000 65(2) 65 40 65(2) 65 (2) 65 (2) 50 50 50 40 40 40
2500
1600
2000
S 75 75 35 75 75 75 65 65 65 50 50 50
E4 2500
3200
H 3200 100 100 50 100 100 100 65 65 65 65 65 65
3200
E6 H 4000 100 100 65 100 100 100 65 65 65 65 65 65
5000
(1)
Icu with L/R = 15ms according to IEC 60946-2 Standard. For Icu with L/R = 5ms and L/R = 30ms, ask ABB.
(2)
85kA only if supplied from below and specifying the following extracode at the ordering stage: 1SDA067148R1. Ics=65kA.

ABB SACE 5
1SDC200012D0902
SACE Emax switch-disconnectors

ABB SACE has developed the SACE Emax/E MS range of switch-disconnectors for direct cur-
rent applications up to 1000V complying with the international IEC60947-3 Standard. These
circuit-breakers are particularly suitable for use as bus-ties or main switch-disconnectors in
direct current plants, such as applications in the field of electric traction.
The range makes it possible to cover any installation requirement up to 1000V DC / 6300A.
The circuit-breakers are available in the fixed or withdrawable version and in the three-pole
or four-pole version.
With connection of three breaking poles in series, the rated voltage which can be reached is
750V DC, whereas with four poles in series this rises to 1000V DC.
The switch-disconnectors in the SACE Emax/E MS range keep all the overall dimensions
and fixing points of the circuit-breakers of the standard range unchanged. The withdrawable
circuit-breakers must be associated with the fixed parts in a special version for applications
at 750/1000V DC.

E1B/E MS E2N/E MS E3H/E MS E4H/E MS E6H/E MS


Rated current (at 40 C) Iu [A] 800 1250 1250 3200 5000
[A] 1250 1600 1600 4000 6300
[A] 2000 2000
[A] 2500
[A] 3200
Poles 3 4 3 4 3 4 3 4 3 4
Rated service voltage Ue [V] 750 1000 750 1000 750 1000 750 1000 750 1000
Rated insulation voltage Ui [V] 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Rated impulse withstand voltage Uimp [kV] 12 12 12 12 12 12 12 12 12 12
Rated short-time withstand current Icw (1s) [kA] 20 20* 25 25* 40 40* 65 65 65 65
Rated making capacity Icm [%Icw] 100 100 100 100 100 100 100 100 100 100
Note: By means of an extreme protection relay with maximum timing of 500 ms, the Icu breaking capacity is the same as the Icw value (1s).

* The performances at 750 V are:


for E1B/E MS Icw=25kA
for E2N/E MS Icw=40kA
for E3H/E MS Icw=50kA

6 ABB SACE
1SDC200012D0902
Versions and connections

Versions and connections


The Emax DC circuit-breakers are available in the fixed or withdrawable, three-pole or four-
pole versions.
All Emax circuit-breakers for direct current have several poles in series involved in breaking the
fault, so they are mounted on the circuit-breaker terminals of the special connection busbars,
known as U connections.
Selection of the power supply side, from the lower or upper terminals, must only be made at
the time of ordering and cannot be modified later by the customer.
The fixed circuit-breakers are fitted with vertical terminals, whereas it is possible to select
between vertical and horizontal terminals for circuit-breakers in the withdrawable version,.

Fixed circuit-breaker
Vertical rear terminals

Power supply from the lower terminals Power supply from the upper terminals

Withdrawable circuit-breaker
Vertical rear terminals

Power supply from the lower terminals Power supply from the upper terminals

Horizontal rear terminals

Power supply from the lower terminals Power supply from the upper terminals

ABB SACE 7
1SDC200012D0902
Dissipated powers

The dissipated powers for Emax DC circuit-breakers are given below according to:
- range;
- trip unit;
- version;
- number of poles;
- Iu.

Emax DC dissipated powers [W]


Iu [A]
Trip unit Version poles 800 1000 1250 1600 2000 2500 3200 4000 5000
F 3p 42 60 94 136
W 3p 66 98 152 232
PR122/DC
F 4p 51 75 117 174
W 4p 83 125 195 302
E2
F 3p 54 113 176 156
W 3p 78 113 176 252
PR123/DC
F 4p 64 140 219 195
W 4p 96 140 219 323
F 3p 32 61 95 123 216 338
W 3p 47 69 108 207 248 388
PR122/DC
F 4p 38 87 123 184 288 450
W 4p 59 87 136 205 320 500
E3
F 3p 50 68 106 138 216 338
W 3p 60 84 131 179 280 438
PR123/DC
F 4p 55 86 134 184 288 450
W 4p 65 102 159 225 352 550
F 3p 120 188 271
W 3p 195 305 463
PR122/DC
F 4p 136 234 348
W 4p 236 391 604
E4
F 3p 150 234 312
W 3p 225 352 504
PR123/DC
F 4p 180 281 389
W 4p 280 438 645
F 3p 154 304 475
W 3p 276 496 775
PR122/DC
F 4p 246 384 600
W 4p 410 640 1000
E6
F 3p 236 368 575
W 3p 358 560 875
PR123/DC
F 4p 287 448 700
W 4p 451 704 1100

8 ABB SACE
1SDC200012D0902
Temperature derating

The following graphs show derating as the temperature increases for Emax DC circuit-breakers.

E2 DC

2000

1500
800
1000
Iu [A]

1000
1250

500 1600

0
10 20 30 40 50 55 60 70
C

E2 DC 800 1000 1250 1600


C % A % A % A % A
10 100% 800 100% 1000 100% 1250 100% 1600
20 100% 800 100% 1000 100% 1250 100% 1600
30 100% 800 100% 1000 100% 1250 100% 1600
40 100% 800 100% 1000 100% 1250 100% 1600
50 100% 800 100% 1000 100% 1250 100% 1600
55 100% 800 100% 1000 100% 1250 100% 1600
60 100% 800 100% 1000 100% 1250 98% 1567
70 100% 800 100% 1000 100% 1250 94% 1500

E3 DC

3000

2500 800
1000
2000
1250
Iu [A]

1500
1600
1000
2000
500 2500
0
10 20 30 40 50 55 60 70
C

E3 DC 800 1000 1250 1600 2000 2500


C % A % A % A % A % A % A
10 100% 800 100% 1000 100% 1250 100% 1600 100% 2000 100% 2500
20 100% 800 100% 1000 100% 1250 100% 1600 100% 2000 100% 2500
30 100% 800 100% 1000 100% 1250 100% 1600 100% 2000 100% 2500
40 100% 800 100% 1000 100% 1250 100% 1600 100% 2000 100% 2500
50 100% 800 100% 1000 100% 1250 100% 1600 100% 2000 100% 2500
55 100% 800 100% 1000 100% 1250 100% 1600 100% 2000 100% 2500
60 100% 800 100% 1000 100% 1250 100% 1600 100% 2000 100% 2500
70 100% 800 100% 1000 100% 1250 100% 1600 100% 2000 94% 2350

ABB SACE 9
1SDC200012D0902
Temperature derating

E4 DC

3500
3000
2500 1600
2000 2000
Iu [A]

1500 2500
1000 3200
500

0
10 20 30 40 50 55 60 70
C

E4 DC 1600 2000 2500 3200


C % A % A % A % A
10 100% 1600 100% 2000 100% 2500 100% 3200
20 100% 1600 100% 2000 100% 2500 100% 3200
30 100% 1600 100% 2000 100% 2500 100% 3200
40 100% 1600 100% 2000 100% 2500 100% 3200
50 100% 1600 100% 2000 100% 2500 100% 3200
55 100% 1600 100% 2000 100% 2500 100% 3200
60 100% 1600 100% 2000 100% 2500 100% 3200
70 100% 1600 100% 2000 100% 2500 97% 3100

E6 DC

6000

5000

4000 3200
Iu [A]

3000 4000

2000 5000

1000

0
10 20 30 40 50 55 60 70
C

E6 DC 3200 4000 5000


C % A % A % A
0 100% 3200 100% 4000 100% 5000
10 100% 3200 100% 4000 100% 5000
20 100% 3200 100% 4000 100% 5000
30 100% 3200 100% 4000 100% 5000
40 100% 3200 100% 4000 100% 5000
50 100% 3200 100% 4000 100% 5000
55 100% 3200 100% 4000 100% 5000
60 100% 3200 100% 4000 100% 5000
70 100% 3200 100% 4000 96% 4800

10 ABB SACE
1SDC200012D0902
Protection trip units and trip curves
PR122/DC

Characteristics
PR122/DC is the new electronic trip unit for the Emax DC series. The vast range of protec-
tion functions, together with the wide variety of trip thresholds and times, make them suitable
for protection of insulated networks or networks with earthed negative polarity. Consulting
information about the unit and its programming is particularly simple and intuitive thanks to
the LCD graphic display.

The PR122/DC trip unit offers the following protection functions:


overload (L);
selective short-circuit (S);
thermal memory for L and S (cable protection);
instantaneous short-circuit (I);
overtemperature (OT);
zone selectivity for S;
load control (K);
starting threshold.

1SDC200607F0001

ABB SACE 11
1SDC200012D0902
Protection trip units and trip curves
PR122/DC

Protection functions and setting values - PR122/DC

Function Trip Threshold Trip time Time Disabling Relation Thermal Zone
threshold step step t=f(I) memory selectivity

Protection against With current If = 3 x I1


overload I1= 0.4...1 x In 0.01 x In t1= 3 s...102 s (1) 3s IEC60255-8

Tolerance (2)
Trip unit between 10%, If 6 x In
1.05 and 1.3 x I1 20%, If > 6 x In

With current If > I2


Selective protection
I2= 0.6...10 x In 0.1 x In t2= 0.05 s...0.35 s 0.01 s t=k
against short-circuit
t2sel= 0.04 s...0.2 s 0.01 s

Tolerance (2)
7%, If 6 x In The best of the two data:
10%, If > 6 x In 10% or 40 ms

With current If 10 x In
0.01 s t=k/I 2
I2= 0.6...10 x In 0.1 x In t2= 0.05 s...0.35 s

Tolerance (2)
7%, If 6 x In 15%, If 6 x In
10%, If > 6 x In 20%, If > 6 x In

Protection against
instantaneous
short-circuit I3= 1.5...10 x In 0.1 x In Instantaneous t=k
Tolerance (2)
10% 30 ms

OT
Protection against
overtemperature Cannot be set Instantaneous t=k

(1) The minimum trip value is 0.5 s, regardless of the type of curve set
(2) These tolerances are valid in the following hypotheses:
- trip unit supplied entirely by the voltage module and/or auxiliary power supply (without start-up)
- trip time set 100 ms

For all cases not contemplated by the above hypotheses, the following tolerance values are valid:

Trip threshold Trip time


L Trip between 1.05 and 1.25 x I1 20%
S 10% 20%
I 15% 60ms

12 ABB SACE
1SDC200012D0902
With plant voltages higher than or equal to 100V, the PR122/DC electronic trip unit guarantees
protection without the need of an auxiliary power supply (24V DC).
The PR122/DC electronic trip unit can, in fact, always be equipped with the PR120/V module
able to supply the trip unit with plant voltages between 250V DC and 1000V DC.
For voltages between 100V DC and 250V DC, it is necessary to request the PR120/LV module,
specifying the extracode 1SDA066223R1.

The following table shows the cases where it is possible to use of the measurement modules
(PR120/V and PR120/LV):

Ue [V] 12 100 250 1000



PR120/LV: PR120/LV + Vaux PR120/LV NO

PR120/V: PR120/V + Vaux PR120/V + Vaux PR120/V


When there is an auxiliary power supply, see the table below for the overall consumption values.

PR122/DC PR120/D-M PR120/K


Auxiliary power supply
24V DC 20% from PR122/DC from PR122/DC
(galvanically insulated)
Maximum ripple 5%
Inrush current @ 24V ~10A for 5 ms
Rated power @ 24V ~3 W +1.5 W +1.5 W

When Emax DC circuit-breakers are used in plants with capacitor banks with possible back-
to-back inrush currents 3xIn, it is necessary to use a 24V DC galvanically insulated auxiliary
power supply.
The range of Emax DC circuit-breakers is normally supplied with power input from the lower
terminals, i.e. the PR120/V-PR120/LV internal connection is on the lower terminals, whereas
the U connections are on the upper terminals:

3D rear view

Front view

For power input to the upper terminals, refer to the Code Section for ordering.

Protection is guaranteed even when the electronic trip unit is not powered thanks to the PR120/DC
module which the PR122/DC is always fitted with.

ABB SACE 13
1SDC200012D0902
Protection trip units and trip curves
PR122/DC

Functions L-S-I

t=k

1SDC200608F0001
Functions L-S-I

I2t = k
1SDC200609F0001

14 ABB SACE
1SDC200012D0902
Protection trip units and trip curves
PR123/DC

Characteristics
With the PR123/DC electronic protection trip unit, the range of trip units available for the Emax
DC series of circuit-breakers is completed.
PR123/DC is a high-performing trip unit capable of carrying out a complete set of protections,
measurements, indications, data storage and circuit-breaker control functions.
PR123/DC not only offers protection but also measurement of current and voltage of both
polarities (+ and -), therefore being suitable for any type of network.
The front interface of the unit, common to PR122/DC, is extremely simple thanks to the aid
of the LCD graphic display.

The PR123/DC trip unit offers the following protection functions:


overload (L);
selective short-circuit (S);
thermal memory for L and S (cable protection);
instantaneous short-circuit (I);
earth fault with adjustable delay (G);
polarity unbalance (U);
protection against overtemperature (OT);
load control (K);
undervoltage (UV);
overvoltage (OV);
active power reversal (RP);
double set of parameters (Dual Setting);
zone selectivity for S and G;
starting thresholds for protection S and I.

1SDC200610F0001

ABB SACE 15
1SDC200012D0902
Protection trip units and trip curves
PR123/DC

Protection functions and setting values - PR123/DC

Function Trip Threshold Trip time Time Disabling Relation Thermal Zone
threshold step step t=f(I) memory selectivity

Protection against With current I = 3 x I1


overload I1 = 0,4...1 x In 0.01 x In t1 = 3 s...102 s (1) 3s IEC60255-8

Tolerance (2)
Trip between 10% If 6 x In
1.05 and 1.3 x I1 20% If > 6 x In

With current I > I2


Selective protection
I2 = 0.6...10 x In 0,1 x In t2 = 0.05 s...0.35 s 0.01 s t=k
against short-circuit
t2sel = 0.04 s...0.2 s 0.01 s

Tolerance (2)
7% If 6 x In The best of the two data:
10% If > 6 x In 10% or 40 ms

With current I = 10 x I1
0.01 s t=k/I2
I2 = 0.6...10 x In 0,1 x In t2 = 0.05 s...0.35 s

Tolerance (2)
7% If 6 x In 15% If 6 x In
10% If > 6 x In 20% If > 6 x In

Selective protection With current I > I2


against short-circuit I2 = 0.6...10 x In 0,1 x In t2 = 0.05 s...0.35 s 0.01 s t=k

Tolerance (2)
7% If 6 x In The best of the two data:
10% If > 6 x In 10% or 40 ms

Protection against
instantaneous
short-circuit I3 = 1.5...10 x In 0.1 x In Instantaneous t=k
Tolerance (2)
10% 30 ms
With current I > I4
Protection against
I4 = 0.2...1 x In 0.02 x In t4 = 0.1 s...1 s 0.05 s t=k
earth fault
t4sel = 0.04 s...0,2 s 0.01 s

The best of the two data:


Tolerance (2)
7% 10% or 40 ms

I4 = 0.2...1 x In 0.02 x In t4 = 0.1 s...1 s 0.05 s t=k/I2


(with I=4xI4)
Tolerance (2)
7% 15%

U Protection against I6 = 5%...90% 5% t6 = 0.5 s...60 s 0.5 s t=k


phase unbalance The best of the two data:
Tolerance (2)
10% 20% or 100 ms
Protection against
OT
overtemperature Cannot be set Instantaneous t=k

Undervoltage U8 = 0.5...0.95 x Un 0.01 x In With voltage U < U8 0.1 s t=k


UV
protection t8 = 0.1 s...5 s

The best of the two data:


Tolerance (2)
5% 20% or 40 ms

OV
Overvoltage U9 = 1.05...1.2 x Un 0.01 x In With voltage U < U9 0.1 s t=k
protection t9 = 0.1 s...5 s

The best of the two data:


Tolerance (2)
5% 20% or 40 ms

RP
Protection against P11 = -0.3...-0.1 x Pn 0.02 x Pn At power P < P11 0.1 s t=k
reversal of power t11 = 0.5 s...25 s

The best of the two data:


Tolerance (2)
10% 10% or 100 ms

(1) The minimum trip value is 0.5 s, regardless of the type of curve set For all cases not contemplated by the above hypothesis, the following tolerance values are valid:
(2) These tolerances are valid with the following hypothesis:
- trip unit supplied from the voltage module and/or auxiliary power supply Trip threshold Trip time
(without start-up) L Trip between 1.05 and 1.3 x I1 20%
- trip time set 100 ms
S 10% 20%
I 15% 60ms
G 15% 20%
Altri 20%

16 ABB SACE
1SDC200012D0902
With plant voltages higher than or equal to 100V, the PR123/DC electronic trip unit guarantees
protection without the need of an auxiliary power supply (24V DC).
The PR123/DC electronic trip unit is, in fact, always fitted with the PR120/V module able to
supply the trip unit with plant voltages between 250V DC and 1000V DC.
For voltages between 100V DC and 250V DC, it is necessary to request the PR120/LV module,
specifying the extracode 1SDA066223R1.

The following table shows the possible cases of use of the measurement modules (PR120/V
and PR120/LV):

Ue [V] 12 100 250 1000



PR120/LV: PR120/LV + Vaux PR120/LV NO

PR120/V: PR120/V + Vaux PR120/V + Vaux PR120/V


When there is an auxiliary power supply, see the table given below for the overall consumption
values.

PR123/DC PR120/D-M PR120/K


Auxiliary power supply
24V DC 20% from PR123/DC from PR123/DC
(galvanically insulated)
Maximum ripple 5%
Inrush current @ 24V ~10A for 5 ms
Rated power @ 24V ~3 W +1,5 W +1,5 W

When Emax DC circuit-breakers are used in plants with capacitor banks with possible inrush
back-to-back currents 3xIn, it is necessary to use a 24V DC galvanically insulated auxiliary
power supply.
The range of Emax DC circuit-breakers is normally supplied with power input from the lower
terminals, i.e. the PR120/V-PR120/LV internal connection is on the lower terminals, whereas
the U connections are on the upper terminals:

3D rear view

Front view

For power input to the upper terminals, refer to the ordering Code Section.

Protection is guaranteed even when there is no power supply to the electronic trip unit thanks
to the PR120/DC module, which the PR1232/DC is always fitted with.

ABB SACE 17
1SDC200012D0902
Protection trip units and trip curves
PR123/DC

Functions L-S-I

t=k

1SDC200608F0001
Functions L-S-I

I2t = k
1SDC200609F0001

18 ABB SACE
1SDC200012D0902
Function G

k
t=
I2

t=k

1SDC200611F0001
Function U

1SDC200612F0001

ABB SACE 19
1SDC200012D0902
Protection trip units and trip curves
PR123/DC

Function RP

RP

1SDC200613F0001
Function UV

UV

1SDC200614F0001

20 ABB SACE
1SDC200012D0902
Function OV

OV

1SDC200615F0001

ABB SACE 21
1SDC200012D0902
Protection trip units and trip curves
PR122/DC and PR123/DC: optional modules

The PR122/DC and PR123/DC electronic trip units can be fitted with the following optional
modules, which are already available on the PR122/P and PR123/P electronic devices for
alternating current applications.

PR122/DC
Code Internal Description
PR123/DC
Internal indication module
1SDA058255R1 PR120/K
(4 outputs with independent terminals)
Internal indication module
1SDA058256R1 PR120/K
(4 outputs + input with common terminal)
1SDA058254R1 PR120/D-M Modbus RTU communication module
1SDA065223R1(1) PR120/LV Measurement module for low voltage (100...250V DC)
Extracode to be specified with the circuit-breaker code to order the PR120/LV low voltage measurement module
(1)

The PR120/LV measurement module and the PR120/DC override protection module are always supplied with the electronic trip units.

PR122/DC
Code External Description
PR123/DC
1SDA058258R1 PR030/B Power supply unit
1SDA058259R1 BT030-USB External wireless communication unit (without wires)
1SDA048964R1 PR010/T External test unit
1SDA059146R1 PR021/K External indication unit

22 ABB SACE
1SDC200012D0902
Protection trip units and trip curves
Measurement

PR122/DC
The following measurements are available:
Current;
Instantaneous value of the current over a period of time (data logger);
Maintenance: Number of operations, percentage of contact wear, storage of opening data
(last 20 trips and 80 events);
The protection finds the historical data of the maximum values of current reading.

PR123/DC
Current;
Maintenance: Number of operations, percentage of contact wear, storage of opening data
(last 20 trips and 80 events);
Voltage;
Instantaneous value of the current/voltage over a period of time (Data Logger);
Power;
Energy;
The protection finds the historical data of the maximum values of current reading, the maxi-
mum voltage and the minimum voltage, the total maximum value and the average value of
the power.

ABB SACE 23
1SDC200012D0902
Protection trip units and trip curves
Functions

The functions available on the PR122/DC and PR123/DC electronic trip units fitted with Modbus
PR120/D-M communication module are listed in the following table.

PR122/DC PR123/DC
+ PR120/D-M + PR120/D-M
Communication functions
Protocol Modbus RTU Modbus RTU

Physical Means RS-485 RS-485

Maximum transmission speed (baud rate) 19200 bps 19200 bps


Measurement functions
Currents
Earth current
Voltage
Power
Energy
Indication functions
LED: Auxiliary power supply, pre-alarm, alarm
Temperature
Indication for L, S, I (and G only with PR123/DC)
Data available
State of the circuit-breaker (open-closed)
Circuit-breaker position (racked-in, racked-out)
Method (local, remote)
Protection parameters set
Parameters for load control
Alarms
Protection L
Protection S
Protection I
Protection G
Trip control for failed fault
Under- and overvoltage protection (timing and trip)
Protection against reversal of power flow (timing and trip)
Maintenance
Total number of operations
Total number of trips
Number of trip tests
Number of manual operations
Number of trips for each distinct protection function
Contact wear (%)
Recording data of the last 20 trips
Controls
Circuit-breaker opening/closing
Reset alarms
Setting protection curves and thresholds
Date and time synchronization from system
Events
Changes in circuit-breaker state, protections and all alarms

24 ABB SACE
1SDC200012D0902
Accessories
Electrical and mechanical accessories

Accessories*
The SACE Emax DC family of circuit-breakers can be fitted with the following electrical and
mechanical accessories, which are already available for the standard family of circuit-breakers
for alternating current applications.

Switch-disconnectors for
Ranges Circuit-breakers
applications up to 1000V DC

Circuit-breaker version Fixed Withdrawable Fixed Withdrawable

Shunt opening/closing release (YO/YC)


1a)
and second shunt opening release (YO2)
1b) SOR test unit (test unit)
2a) Undervoltage release (YU)
2b) Delay device for undervoltage release (D)
3) Geared motor for automatic charging of the closing springs (M)
4a) Electrical indication of electronic trip unit tripped
Electrical indication of electronic trip unit tripped with remote
4b)
resetting control
Additional external electrical indication
5b)
of circuit-breaker open/closed
Electrical indication of circuit-breaker
5c)
racked-in/racked-out test/racked-out
5d) Signalling contact for closing springs charged
Signalling contact for undervoltage release
5e)
de-energised (C. Aux YU)
7) Mechanical operation counter
8a) Lock in open position: key
8b) Lock in open position: padlocks
8c) Circuit-breaker lock in racked-in/racked-out/racked-out test position
8d) Accessories for lock in of racked-out/racked-out test position
8e) Accessory for padlock lock of the shutters
8f) Mechanical compartment door lock
9a) Protection on opening and closing pushbuttons
9b) IP54 door protection
10) Interlock between circuit-breakers

LEGENDA * For further information on the accessories, please consult the Emax catalogue: Circuit-break-
ers \ low voltage air.
Optional accessory on fixed circuit-breaker or on moving part
Optional accessory on fixed part
Optional accessory on moving part

ABB SACE 25
1SDC200012D0902
Overall dimensions
Fixed circuit-breaker

Basic version with vertical rear terminals

POWER SUPPLY FROM THE UPPER TERMINALS 6

4 POLES E2 - E4 E3 - E6
3 POLES

3 POLES

4 POLES

POWER SUPPLY FROM THE LOWER TERMINALS 7

1SDC200617F0001
Caption

1 Inside edge of compartment


door
2 Partition (where provided)
3 Circuit-breaker fixing M10
drilling (use M10 screws) E2 III E2 IV
View A View A
4 N. 1 M12 screw (E1, E2, E3)
or n. 2 M12 screws (E4, E6)
for earthing (included in the Iu=1250A Iu=1250A
supply) Iu=1600A Iu=1600A
5 Insulated insulating or
metallic wall
6 For power input to the
UPPER terminals PR120/V
internal connection on the
upper terminals and rear U
connection kit on the lower
terminals
7 For power input to the
LOWER terminals PR120/V
internal connection on the
lower terminals and rear U
connection kit on the upper
terminals
Iu=800A Iu=800A
Iu=1000A Iu=1000A

A B C D
E2 386 296 148 148
E3 530 404 202 202
1SDC200618F0001

E4 746 566 238 328


E6 1034 782 328 454

26 ABB SACE
1SDC200012D0902
E3 III
View A
Iu=2000A
Iu=2500A

Iu=800A
Iu=1000A
Iu=1250A
Iu=1600A

E3 IV
View A Iu=2000A
Iu=2500A

Iu=800A
Iu=1000A
Iu=1250A
Iu=1600A

E4 III
View A

Iu=2500A
Iu=3200A

Iu=1600A
Iu=2000A
1SDC200619F0001

ABB SACE 27
1SDC200012D0902
Overall dimensions
Fixed circuit-breaker

Basic version with vertical rear terminals

E4 IV
View A
Iu=2500A
Iu=3200A

Iu=1600A
Iu=2000A

E6 III
View A

E6 IV
View A
1SDC200620F0001

28 ABB SACE
1SDC200012D0902
Compartment dimensions

A B
Depth
E2 400 490
E3 500 630
3 POLES E4 700 880
4 POLES E6 1000 1260

Through-holes for flexible cables for Compartment door drilling


mechanical interlocks

N 2 holes for
IP54 protection

1SDC200621F0001

ABB SACE 29
1SDC200012D0902
Overall dimensions
Withdrawable circuit-breaker

Basic version with rear vertical terminals

POWER SUPPLY FROM THE UPPER TERMINALS 6

4 POLES
E2-E4 E3-E6
3 POLES

3 POLES
4 POLES

POWER SUPPLY FROM THE LOWER TERMINALS 7

1SDC200622F0001
Caption

1 Inside edge of compartment


door
2 Segregation (where provided)
3 Circuit-breaker fixing M10 E2 III E2 IV
drilling (use M10 screws) View A View A
4 N. 1 M12 screw (E1, E2, E3)
or n. 2 M12 screws (E4, E6)
for earthing (included in the
supply)
5 Insulating wall or insulated Iu=1250A
metal wall Iu=1600A
6 For power input to the
UPPER terminals PR120/V
internal connection on the
upper terminals and rear U
connection kit on the lower
terminals
7 For power input to the
LOWER terminals PR120/V
internal connection on the
lower terminals and rear U
connection kit on the upper
terminals
1SDC200623F0001

A B C D
E2 414 324 162 162
E3 558 432 216 216
E4 774 594 252 342
E6 1062 810 342 468

30 ABB SACE
1SDC200012D0902
E3 III E3 IV
View A View A

E4 III E4 IV
View A View A

Iu=1600A
Iu=2000A

Iu=2500A
Iu=3200A

E6 III E6 IV
View A View A
1SDC200624XF0001

ABB SACE 31
1SDC200012D0902
Overall dimensions
Withdrawable circuit-breaker

Basic version with rear horizontal terminals

POWER SUPPLY FROM THE UPPER TERMINALS 6

4 POLES
E2-E4 E3-E6
3 POLES

8 10 8 8 10 8

465 465
X X X X

264.5 264.5
80 100

71.5 18 18
61.5
3 POLES
4 POLES

348 348

POWER SUPPLY FROM THE LOWER TERMINALS 7

465 465
X X X X
8 10 8 8 10 8

124.5 124.5

1SDC200622AF0001
18 18
Caption

1 Inside edge of compartment 348 348

door
2 Segregation (where provided)
3 Circuit-breaker fixing M10 E2 III E2 IV
drilling (use M10 screws) View A View A
4 N. 1 M12 screw (E1, E2, E3)
or n. 2 M12 screws (E4, E6)
for earthing (included in the 90 90
90 90 90
143
supply) 100 60 100 143
5 Insulating wall or insulated 35
metal wall
13

151 15 151
6 For power input to the
UPPER terminals PR120/V N
internal connection on the
upper terminals and rear U
connection kit on the lower
terminals
7 For power input to the
LOWER terminals PR120/V
internal connection on the
lower terminals and rear U
connection kit on the upper
terminals
1SDC200623AF0001

60
35 13
15
33

A B C D
E2 414 324 162 162
E3 558 432 216 216
E4 774 594 252 342
E6 1062 810 342 468

32 ABB SACE
1SDC200012D0902
E3 III E3 IV
View A 435 View A 561
126 126 126 126 126
205 205
158 158
95 95

96
96 15
171 171

3
35 35 33 35 35

1
3 15
1
33

4 183 4 N 246 2

0
0
2

1
33 1 33

380 40 40 325
225 393,5 225
84 84 370
370 240 240

122 122
49 70 49 70

63

6 200
240 3

E4 III E4 IV
View A 597
View A
777
180 180 180 180 180
323 323
280 280
65 65

13
191 150 191
35 35 35
15 33
2
2
708
4 4
33 528 33 10
10
700
393,5 40 393,5 40
380 400 380 580
84 530 84

122 122

45 45
1 1

E6 III E6 IV
View A 813
View A 1065
252 252 252 252 252
457 457
410 410

85 85
222
211 211
3

35 35 56 35 35
1

15 33

744
2 996 2
4 4
0
33 33 1

10

393,5 40 393,5 40
380 620 380
84 750 84 996
1SDC200624AF0001

122 122

63 63
1 1 866

ABB SACE 33
1SDC200012D0902
Overall dimensions
Circuit-breaker accessories

Compartment dimensions

A B
Depth
E2 400 490
E3 500 630
3 POLES E4 700 880
4 POLES E6 1000 1260

Through-holes for flexible cables Compartment door drilling


for mechanical interlocks

N 2 holes for
IP54 protection

1SDC200626F0001

Mechanical compartment door lock

Compartment door drilling Minimum distance between circuit-breaker and switchboard wall

Fixed version Withdrawable version

A
3 poles 4 poles
E2 180 180
E3 234 234
1SDC200627F0001

E4 270 360
E6 360 486

34 ABB SACE
1SDC200012D0902
Electric wiring diagrams
Information for reading

Caution
Before installation of the circuit-breaker, read note F of the electric wiring diagrams carefully.

State of operation shown


The diagram is shown under the following conditions:
- circuit-breaker in the withdrawable version, open and racked-in
- circuits de-energised
- trip units not tripped
- motor operator with springs discharged.

Versions
The diagram shows a withdrawable version circuit-breaker, but is also valid for fixed version circuit-breakers.
Fixed version
The control circuits are included between the XV terminals (connector X is not supplied).
With this version, the applications indicated in figures 31 and 32 cannot be supplied.
Withdrawable version
The control circuits are included between the poles of connector X (terminal board XV is not supplied).
Version with PR122/DC electronic trip unit
Version with PR123/DC electronic trip unit

Caption
= Number of diagram figure
* = See the note indicated by the letter
A1 = Circuit-breaker accessories
A3 = Accessories placed on the fixed part of the circuit-breaker (only provided with withdrawable version
circuit-breakers)
A4 = Indicative apparatus and connections for control and indication, outside the circuit-breaker
D = Undervoltage release electronic time-delay device, outside the circuit-breaker
F1 = Fuse with delayed intervention
K51 = PR122/DC, PR123/DC type electronic trip unit with the following protection functions:
- L against overload with long inverse time-delay trip - regulation I1
- S against short-circuit with short inverse or definite time-delay trip - regulation I2
- I against short-circuit with instantaneous time trip - regulation I3
- G against earth fault with short inverse time-delay trip - regulation I4
K51/1...8 = PR021/K indication unit contacts
K51/GZin = Zone selectivity: input for protection G (requires Vaux and PR123/DC trip unit)
K51/GZout = Zone selectivity: output for protection G (requires Vaux and PR123/DC trip unit)
K51/IN1 = Programmable digital input (only provided with Vaux and PR122/DC or PR123/DC trip unit with PR120/K
indication module)
K51/P1...P4 = Programmable electrical signals (only provided with Vaux and PR122/DC or PR123/DC trip unit PR120/K
indication module)
K51/SZin = Zone selectivity: input for protection S (requires Vaux and PR123/DC trip unit)
K51/SZout = Zone selectivity: output for protection S (requires Vaux and PR123/DC trip unit)
K51/YC = Closing command from PR122/DC or PR123/DC electronic trip unit connected to a bus system by
means of PR120/D-M communication module
K51/YO = Opening command from PR122/DC or PR123/DC electronic trip unit connected to a bus system by
means of PR120/D-M communication module
M = Motor for charging the closing springs
Q = Circuit-breaker
Q/1...27 = Circuit-breaker auxiliary contacts
S33M/1...3 = Spring charging motor limit contacts
S43 = Changeover contact for preparation of remote/local control
S51 = Contact for electrical indication of circuit-breaker open due to overcurrent release trip. Circuit-breaker
closing can only take place after having pressed the reset pushbutton or after having energised the YR
coil for electrical resetting (if provided)
S75E/1...4 = Contacts for electrical indication of circuit-breaker in racked-out position (only provided with withdrawable
version circuit-breakers)
S75I/1...5 = Contacts for electrical indication of circuit-breaker in racked-in position (only provided with withdrawable
version circuit-breakers)
S75T/1..4 = Contacts for electrical indication of circuit-breaker in racked-out test position (only provided with with-
drawable version circuit-breakers)
SC = Pushbutton or contact for closing the circuit-breaker
SO = Pushbutton or contact for opening the circuit-breaker
SO1 = Pushbutton or contact for opening the circuit-breaker with delayed trip
SO2 = Pushbutton or contact for opening the circuit-breaker with instantaneous trip
SR = Pushbutton or contact for electrical resetting of the circuit-breaker

ABB SACE 35
1SDC200012D0902
Electric wiring diagrams
Information for reading

W1 = Serial interface with the control system (bus system): EIA RS485 interface (see note E)
W2 = Serial interface with the accessories of the PR122/DC and PR123/DC trip units (local bus)
X = Delivery connector for withdrawable version circuit-breaker auxiliary circuits
X1...X7 = Connectors for circuit-breaker accessories
XF = Delivery terminal board for withdrawable version circuit-breaker position contacts (located on the
fixed part of the circuit-breaker)
XK1 = Connector for power circuits of the PR122/DC and PR123/DC trip units
XK2 - XK3 = Connectors for auxiliary circuits of the PR122/DC and PR123/DC trip units
XK4 = Connector for open/closed indication contacts
XO = Connector for the YO1 release
XV = Delivery terminal board for fixed version circuit-breaker auxiliary contacts
YC = Shunt closing release
YO = Shunt opening release
YO1 = Overcurrent release
YO2 = Second shunt opening release (see note Q)
YR = Coil for circuit-breaker electrical resetting
YU = Undervoltage release (see note B and note Q)

Description of figures
Fig. 1 = Circuit of the closing spring charging motor.
Fig. 2 = Circuit of the shunt closing release.
Fig. 4 = Shunt opening release.
Fig. 6 = Instantaneous undervoltage release (see notes B and Q).
Fig. 7 = Undervoltage release with electronic delay device, outside the circuit-breaker (see notes B and Q).
Fig. 8 = Second shunt opening release (see note Q).
Fig. 11 = Contact for electrical signalling of springs charged.
Fig. 12 = Contact for electrical signalling of undervoltage release excited (see notes B and S).
Fig. 13 = Contact for electrical signalling of circuit-breaker open due to trip of the overcurrent release.
Circuit-breaker closing can only take place after having pressed the reset pushbutton on the front
of the circuit-breaker.
Fig. 14 = Contact for electrical signalling of circuit-breaker open due to trip of the overcurrent release and
coil for electric resetting. Circuit-breaker closing can only take place after having pressed the reset
pushbutton or after having energised the coil.
Fig. 21 = First pack of circuit-breaker auxiliary contacts.
Fig. 22 = Second pack of circuit-breaker auxiliary contacts (see note V).
Fig. 23 = Third pack of additional auxiliary contacts outside the circuit-breaker.
Fig. 31 = First pack of contacts for electrical signalling of circuit-breaker in the racked-in, racked-out test
and racked-out position.
Fig. 32 = Second pack of contacts for electrical signalling of circuit-breaker in the racked-in, racked-out test
and racked-out position.
Fig. 42 = Auxiliary circuits of the PR122/DC and PR123/DC trip units (see notes F and V).
Fig. 45 = PR120/D-M communication module circuits of the PR122/DC and PR123/DC trip units (optional,
see note E).
Fig. 46 = PR120/K indication module circuits of the PR122/DC and PR123/DC trip units - connection 1
(optional; see note V).
Fig. 47 = PR120/K indication module circuits of the PR122/DC and PR123/DC trip units - connection 2
(optional; see note V).
Fig. 62 = PR021/K indication module circuits (outside the circuit-breaker)

Incompatibility
The circuits indicated in the following figures cannot be supplied at the same time on the same circuit-breaker:
6-7-8
13 - 14
22 - 46 - 47

36 ABB SACE
1SDC200012D0902
Notes
A) The circuit-breaker is only supplied with the accessories specified in the ABB SACE order acknowledgement. To
make out the order, please consult this catalogue.
B) The undervoltage release is provided for power supply on the generator side of the circuit-breaker or from an
independent source. Circuit-breaker closing is only allowed with the release excited (the lock on closing is made
mechanically). When there is the same power supply for the shunt closing and undervoltage releases, and one
wants automatic circuit-breaker closing on return of the auxiliary voltage, it is necessary to introduce a delay of
30 milliseconds between the instant of undervoltage release consent and excitation of the shunt closing release.
This can be carried out by means of a circuit outside the circuit-breaker including a permanent closing contact, the
contact indicated in figure 12 and a time-delay relay.
E) The details regarding communication with MODBUS Protocol are given in the Modbus System Interface document.
F) The auxiliary Vaux voltage allows activation of all the functionalities of the PR122/DC and PR123/DC trip units. Since
a Vaux insulated from earth is required, it is necessary to use galvanically separated converters conforming to IEC
60950 (UL 1950) Standards or equivalent, which guarantee a common mode current or a leakage current (see IEC
478/1, CEI 22/3) not exceeding 3.5 mA (IEC 60364-41 and CEI 64-8).
N) In the PR122/DC and PR123/DC trip units, the connections with zone selectivity inputs and outputs of must be
made using a bipolar shielded corded cable (see instruction manual) with a length not exceeding 300 m. The shield
must be earthed on the input side of selectivity.
P) In the PR122/DC and PR123/DC trip units with PR120/D-M communication module, the power supply of the YO
and YC coils must not be derived from the main one. The coils can be controlled directly by the K51/YO and K51/
YC contacts with maximum voltage values of 110-120 V DC and 240-250 V AC.
Q) The second shunt opening release is to be installed as an alternative to the undervoltage release.
S) Also available in the version with normally closed contact.
V) When the contacts in fig. 22 are provided (second pack of auxiliary contacts) together with the PR122/DC or PR123/
DC trip unit, the contacts relative to the zone selectivity in fig. 42 (K51/Zin, K51/Zout, K51/Gzin and K51/Gzout) are
not wired. Furthermore, the PR120/K indication module of figure 46 and 47 cannot be supplied.

ABB SACE 37
1SDC200012D0902
Electric wiring diagrams
Graphic Symbols (IEC 606 7 and CEI 3- 4 ... 3-26 Standards)

Screen (can be drawn in Connection of conductors Changeover make before


any shape) break position contact
(limit switch)

Timing Terminal or clamp Circuit-breaker-isolator


with automatic opening

Mechanical connection Socket and plug Switch-disconnector


(female and male)

Manual mechanical Motor Control coil


operating mechanism (general symbol) (general symbol)
(general case)

Rotary operating Current transformer Instantaneous


mechanism overcurrent relay

Operating mechanism Closing contact Overcurrent relay with


with pushbutton adjustable short time-delay
characteristic

Equipotentiality Opening contact Overcurrent relay with


short inverse time-delay
characteristic

Galvanically separated Changeover make before Overcurrent relay with


converter break position contact long inverse time-delay
characteristic

Shielded cable conductors Closing position contact Overcurrent relay for earth
(e.g. three conductors) (limit switch) fault with short inverse time
characteristic

1SDC200628F0001
Conductors or corded ca- Opening position contact Fuse
bles (e.g. 3 conductors) (limit switch) (general symbol)

38 ABB SACE
1SDC200012D0902
Electric wiring diagrams
Circuit-breakers

State of operation

+ -

K51
Q

>
XK10
A1I 1 >>
2
A1E XO
>> 1
>>
>

1
Y01
XO

2
C
D

>>
0/

2
12
PR

PR122/DC

XK11
B1I 1
2
B1E
PR123/DC
1SDC200629F0001

Three-pole circuit-breaker with electronic PR122/DC or PR123/DC trip unit

+ -

K51
Q

XK10
A1I 1 >>
2
A1E XO
>> 1
>>>
1

Y01
XO
2
DC

>>
0/

2
12
PR

PR122/DC

XK11
B1I 2
1
B1E
PR123/DC
1SDC200630F0001
C
/D0
12
PR

Four-pole circuit-breaker with electronic PR122/DC or PR123/DC trip unit

ABB SACE 39
1SDC200012D0902
Electric wiring diagrams
Circuit-breakers

Motor operator, shunt opening, closing and undervoltage releases

1SDC200633F0001
Signalling contacts

1SDC200634F0001

40 ABB SACE
1SDC200012D0902
Signalling contacts

1SDC200635F0001
1SDC200636F0001

ABB SACE 41
1SDC200012D0902
Electric wiring diagrams
Circuit-breakers

Auxiliary circuits of the PR122/DC and PR123/DC trip units

CAPTION: see note F.

PR122/DC
PR123/DC

1SDC200637F0001
BUS2

PR120/D-M communication module

PR122/DC
PR123/DC
1SDC200638F0001

BUS1

42 ABB SACE
1SDC200012D0902
PR120/K indication module

(+)

(+)

(+)

PR122/DC PR122/DC
PR123/DC PR123/DC
(-)

(-)

(-)

1SDC200639F0001
PR021/K indication unit

PR122/DC
PR123/DC

BUS2
1SDC200640F0001

ABB SACE 43
1SDC200012D0902
Selection of Emax DC

Emax DC circuit-breakers must be selected on the basis of:


1) Type of network;
2) Rated current (Iu);
3) Rated voltage (Ue);
4) Short-circuit capacity (Icu);
5) Poles;
6) Version (Fixed - F - or Withdrawable - W);
7) Power supply (from the upper or lower terminals).

Plates:

POWER INPUT TO UPPER TERMINALS

1SDC200605F0001
POWER INPUT TO THE LOWER TERMINALS

1SDC200606F0001

44 ABB SACE
1SDC200012D0902
+
L
O
INSULATED A
D
-
NETWORK

Rated
Ue 500 500V Ue 750V 750V Ue 1000V
voltage (Ue)
POLES 3p 4p 3p 4p 4p

LOAD - LOAD -

LOAD + - LOAD + -
+ +
Power supply
from the lower Front view Front view Front view Front view Front view
terminals
(Lower Supply)

3D rear view 3D rear view 3D rear view 3D rear view 3D rear view

+ LOAD +
- + LOAD +
-

LOAD - LOAD -

Power supply
from the upper Front view Front view Front view Front view Front view
terminals
(Upper Supply)

3D rear view 3D rear view 3D rear view 3D rear view 3D rear view

PR122/DC
PR123/DC

ABB SACE 45
1SDC200012D0902
Selection of Emax DC

+
L
NETWORK WITH O
A
D
EARTHED -
2
MEDIAN POINT
2

Rated
Ue 500V 500V Ue 750V 750V Ue 1000V
voltage (Ue)
Poles 3p 4p 4p 4p

LOAD -

LOAD + -
+
Power supply
from the lower Front view Front view Front view Front view
terminals
(Lower Supply)

3D rear view 3D rear view 3D rear view 3D rear view

+ LOAD +
-

LOAD -

Power supply
from the upper Front view Front view Front view Front view
terminals
(Upper Supply)

3D rear view 3D rear view 3D rear view 3D rear view

PR123/DC

46 ABB SACE
1SDC200012D0902
The following tables show the possible configurations according to the type of network:

+
NETWORK WITH L
O
EARTHED -
A
D
NEGATIVE
POLARITY

Rated voltage (Ue) Ue 500 1)

Poles 3p 4p
LOAD -

LOAD + -
+
Power supply
from the lower Front view Front view
terminals
(Lower Supply)

3D rear view 3D rear view

+ LOAD +
-

LOAD -
Power supply
from the upper Front view Front view
terminals
(Upper Supply)

3D rear view 3D rear view

PR122/DC
PR123/DC
1) For higher voltages, ask ABB SACE
It is necessary to specify the 1SDA068806R1 extracode for the special dedicated configuration with 4 poles.

ABB SACE 47
1SDC200012D0902
Selection of Emax DC
Ordering Rules

Fixed circuit-breaker (F)


ABB SACE supplies the circuit-breaker as the standard configuration supplied from the lower terminals.

CODE
LOAD -

+ LOAD + -

To change the power supply side from the lower terminals to the upper ones, it is necessary
to specify the 1SDA058251R1 extracode.

CODE + 1SDA058251R1
+ LOAD +
-

LOAD -

In the case of a network with earthed negative polarity and a four-pole circuit-breaker (4p), it
is always necessary to specify the 1SDA068806R1 extracode

Supplied from the lower terminals

CODE + 1SDA068806R1

Supplied from the upper terminals

CODE + 1SDA058251R1 + 1SDA068806R1

48 ABB SACE
1SDC200012D0902
Withdrawable circuit-breaker (W)
MOVING PART
For the moving part in withdrawable circuit-breakers supplied from the lower terminals, it is sufficient to
indicate just the circuit-breaker code. The voltage sockets are therefore positioned on the lower terminals.

CODE LOAD -
LOAD -

LOAD + -
+ LOAD +
+ -

If supplied from the upper terminals, it is necessary to move the voltage sockets onto the upper
terminals, specifying the 1SDA058251R1 extracode:

CODE + 1SDA058251R1
+ -
+ LOAD +
LOAD +
-

LOAD -
LOAD -

FIXED PART
The configuration of the fixed part for Emax DC circuit-breakers must be constructed starting with
the fixed parts for special applications up to 750/1000V DC and adding the U connection kit:

Power supply from the lower terminals



CODE FOR FIXED PART with vertical terminals + 1SDA065169R1
or
CODE FOR FIXED PART with horizontal terminals + 1SDA067149R1

Power supply from the upper terminals

CODE FOR FIXED PART with vertical terminals + 1SDA065619R1


or
CODE FOR FIXED PART with horizontal terminals + 1SDA067150R1

In the case of a network with earthed negative polarity and 4p circuit-breaker, the 1SDA068806R1
extracode must be specified in addition in order to have 3 poles in series on the positive pole.

ABB SACE 49
1SDC200012D0902
Ordering codes
Insulated network - Lower power supply

1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V

PR122/DC

Vertical terminals 1sda0R1


Size Poles Front view Iu Performance Code
LOAD - 800 B 64580
1000 B 64581
3p 1250 B 64582
B 64583
E2 1600
N 64584
LOAD + -
+
Fixed
F-VR 800 B 64585
1000 B 64586
4p 1250 B 64587
B 64588
1600
N 64589
800 N 64600
1000 N 64601
LOAD - 1250 N 64602
N 64603
1600
3p H 64606
N 64604
LOAD + 2000
+ -
H 64607
N 64605
E3 2500
H 64608
Fixed
F-VR 800 N 64609
1000 N 64610
1250 N 64611
N 64612
1600
4p H 64615
N 64613
2000
H 64616
N 64614
2500
H 64617
LOAD - 1600 S 64636
2000 S 64637
3p 2500 S 64638
S 64639
E4 LOAD + 3200
+ -
H 64640
Fixed
F-VR 1600 S 64641
2000 S 64642
4p 2500 S 64643
S 64644
3200
H 64645
LOAD -
3200 H 64656

3p 4000 H 64657

E6 + LOAD + - 5000 H 64658


Fixed
F-VR 3200 H 64659

4p 4000 H 64660

5000 H 64661

50 ABB SACE
1SDC200012D0902
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V

PR123/DC

Vertical terminals 1sda0R1


Size Poles Front view Iu Performance Code
LOAD - 800 B 64668
1000 B 64669
3p 1250 B 64670
B 64671
E2 1600
N 64672
LOAD + -
+
Fixed
F-VR 800 B 64673
1000 B 64674
4p 1250 B 64675
B 64676
1600
N 64677
800 N 64688
1000 N 64689
LOAD - 1250 N 64690
N 64691
1600
3p H 64694
N 64692
LOAD + 2000
+ -
H 64695
N 64693
E3 2500
H 64696
Fixed
F-VR 800 N 64697
1000 N 64698
1250 N 64699
N 64700
1600
4p H 64703
N 64701
2000
H 64704
N 64702
2500
H 64705
LOAD - 1600 S 64724
2000 S 64725
3p 2500 S 64726
S 64727
E4 LOAD + 3200
+ -
H 64728
Fixed
F-VR 1600 S 64729
2000 S 64730
4p 2500 S 64731
S 64732
3200
H 64733
LOAD -
3200 H 64744

3p 4000 H 64745

E6 + LOAD + - 5000 H 64746


Fixed
F-VR 3200 H 64747

4p 4000 H 64748

5000 H 64749

ABB SACE 51
1SDC200012D0902
Ordering codes
Insulated network - Upper power supply

1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V

PR122/DC

Vertical terminals 1sda0R1 1sda0R1


Size Poles Front view Iu Performance Code + Extracode
+ LOAD +
- 800 B 64580
1000 B 64581
3p 1250 B 64582 + 58251
B 64583
E2 1600
LOAD -
N 64584
Fixed
F-VR 800 B 64585
1000 B 64586
4p 1250 B 64587 + 58251
B 64588
1600
N 64589
800 N 64600
1000 N 64601
+ LOAD +
- 1250 N 64602
N 64603
1600
3p H 64606 + 58251
N 64604
2000
LOAD -
H 64607
N 64605
E3 2500
H 64608
Fixed
F-VR 800 N 64609
1000 N 64610
1250 N 64611
N 64612
1600
4p H 64615 + 58251
N 64613
2000
H 64616
N 64614
2500
H 64617
+ LOAD +
- 1600 S 64636
2000 S 64637
3p 2500 S 64638 + 58251
S 64639
E4 3200
LOAD -
H 64640
Fixed
F-VR 1600 S 64641
2000 S 64642
4p 2500 S 64643 + 58251
S 64644
3200
H 64645
+ -
3200 H 64656
LOAD +

3p 4000 H 64657 + 58251

E6 LOAD - 5000 H 64658


Fixed
F-VR 3200 H 64659

4p 4000 H 64660 + 58251

H 64661

52 ABB SACE
1SDC200012D0902
1SDA0...R1
+
L
O
Ue<100V Vaux is compulsory
A
- D
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V

PR123/DC

Vertical terminals 1sda0R1 1sda0R1


Size Poles Front view Iu Performance Code + Extracode
+ LOAD +
- 800 B 64668
1000 B 64669
3p 1250 B 64670 + 58251
B 64671
E2 1600
LOAD -
N 64672
Fixed
F-VR 800 B 64673
1000 B 64674
4p 1250 B 64675 + 58251
B 64676
1600
N 64677
800 N 64688
1000 N 64689
+ LOAD +
- 1250 N 64690
N 64691
1600
3p H 64694 + 58251
N 64692
2000
LOAD -
H 64695
N 64693
E3 2500
H 64696
Fixed
F-VR 800 N 64697
1000 N 64698
1250 N 64699
N 64700
1600
4p H 64703 + 58251
N 64701
2000
H 64704
N 64702
2500
H 64705
+ LOAD +
- 1600 S 64724
2000 S 64725
3p 2500 S 64726 + 58251
S 64727
E4 3200
LOAD -
H 64728
Fixed
F-VR 1600 S 64729
2000 S 64730
4p 2500 S 64731 + 58251
S 64732
3200
H 64733
+ -
3200 H 64744
LOAD +

3p 4000 H 64745 + 58251

E6 LOAD - 5000 H 64746


Fixed
F-VR 3200 H 64747

4p 4000 H 64748 + 58251

H 64749

ABB SACE 53
1SDC200012D0902
Ordering codes
Insulated network - Lower power supply

1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V

PR122/DC

MP Fixed part
Vertical terminals
1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code Code + Extracode
LOAD - 800 B 64590
1000 B 64591
3p 1250 B 64592 59895 + 65169
B 64593
E2 LOAD + 1600
+ -
N 64594
Withdrawable
W-VR 800 B 64595
1000 B 64596
4p 1250 B 64597 59906 + 65169
B 64598
1600
N 64599
800 N 64618
1000 N 64619
LOAD - 1250 N 64620
N 64621
1600
3p H 64624 59896 + 65169
N 64622
2000
H 64625
LOAD + -
+

N 64623
E3 2500
H 64626
Withdrawable
W-VR 800 N 64627
1000 N 64628
1250 N 62629
N 64630
1600
4p H 64633 59907 + 65169
N 64631
2000
H 64634
N 64632
2500
H 64635
LOAD - 1600 S 64646
2000 S 64647
3p 2500 S 64648 59897 + 65169
S 64649
E4 3200
H 64650
LOAD + -
+
Withdrawable
W-VR 1600 S 64651
2000 S 64652
4p 2500 S 64653 59137 + 65169
S 64654
3200
H 64655
LOAD -
3200 H 64662

3p 4000 H 64663 59140 + 65169

E6 + LOAD + - 5000 H 64664


Withdrawable
W-VR 3200 H 64665

4p 4000 H 64666 59143 + 65169

5000 H 64667

54 ABB SACE
1SDC200012D0902
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V

PR123/DC

MP Fixed part
Vertical terminals
1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code Code + Extracode
LOAD - 800 B 64678
1000 B 64679
3p 1250 B 64680 59895 + 65169
B 64681
E2 LOAD + - 1600
+
N 64682
Withdrawable
W-VR 800 B 64683
1000 B 64684
4p 1250 B 64685 59906 + 65169
B 64686
1600
N 64687
800 N 64706
1000 N 64707
LOAD - 1250 N 64708
N 64709
1600
3p H 64712 59896 + 65169
N 64710
LOAD + 2000
+ -
H 64713
N 64711
E3 2500
H 64714
Withdrawable
W-VR 800 N 64715
1000 N 64716
1250 N 64717
N 64718
1600
4p H 64721 59907 + 65169
N 64719
2000
H 64722
N 64720
2500
H 64723
LOAD - 1600 S 64734
2000 S 64735
3p 2500 S 64736 59897 + 65169
S 64737
E4 LOAD + 3200
+ -
H 64738
Withdrawable
W-VR 1600 S 64739
2000 S 64740
4p 2500 S 64741 59137 + 65169
S 64742
3200
H 64743
LOAD -
3200 H 64750

3p 4000 H 64751 59140 + 65169

E6 + LOAD + - 5000 H 64752


Withdrawable
W-VR 3200 H 64753

4p 4000 H 64754 59143 + 65169

5000 H 64755

ABB SACE 55
1SDC200012D0902
Ordering codes
Insulated network - Upper power supply

1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V

PR122/DC

MP Fixed part
Vertical terminals
1sda0R1 1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code + Extracode Code + Extracode
+ LOAD +
- 800 B 64590 +
1000 B 64591 +
3p 1250 B 64592 + 58251 59895 + 65619
B 64593 +
E2 1600
LOAD -
N 64594 +
Withdrawable
W-VR 800 B 64595 +
1000 B 64596 +
4p 1250 B 64597 + 58251 59906 + 65619
B 64598 +
1600
N 64599 +
800 N 64618 +
1000 N 64619 +
+ LOAD +
- 1250 N 64620 +
N 64621 +
1600
3p H 64624 + 58251 59896 + 65619
N 64622 +
LOAD - 2000
H 64625 +
N 64623 +
E3 2500
H 64626 +
Withdrawable
W-VR 800 N 64627 +
1000 N 64628 +
1250 N 62629 +
N 64630 +
1600
4p H 64633 + 58251 59907 + 65619
N 64631 +
2000
H 64634 +
N 64632 +
2500
H 64635 +
+ LOAD +
- 1600 S 64646 +
2000 S 64647 +
3p 2500 S 64648 + 58251 59897 + 65619
S 64649 +
E4 3200
LOAD -
H 64650 +
Withdrawable
W-VR 1600 S 64651 +
2000 S 64652 +
4p 2500 S 64653 + 58251 59137 + 65619
S 64654 +
3200
H 64655 +
+ -
LOAD +
3200 H 64662 +

3p 4000 H 64663 + 58251 59140 + 65619

E6 LOAD - 5000 H 64664 +


Withdrawable
W-VR 3200 H 64665 +

4p 4000 H 64666 + 58251 59143 + 65619

5000 H 64667 +

56 ABB SACE
1SDC200012D0902
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V

PR123/DC

MP Fixed part
Vertical terminals
1sda0R1 1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code + Extracode Code + Extracode
+ LOAD +
- 800 B 64678 +
1000 B 64679 +
3p 1250 B 64680 + 58251 59895 + 65619
B 64681 +
E2 1600
LOAD -
N 64682 +
Withdrawable
W-VR 800 B 64683 +
1000 B 64684 +
4p 1250 B 64685 + 58251 59906 + 65619
B 64686 +
1600
N 64687 +
800 N 64706 +
1000 N 64707 +
+ LOAD +
- 1250 N 64708 +
N 64709 +
1600
3p H 64712 + 58251 59896 + 65619
N 64710 +
LOAD - 2000
H 64713 +
N 64711 +
E3 2500
H 64714 +
Withdrawable
W-VR 800 N 64715 +
1000 N 64716 +
1250 N 64717 +
N 64718 +
1600
4p H 64721 + 58251 59907 + 65619
N 64719 +
2000
H 64722 +
N 64720 +
2500
H 64723 +
+ LOAD +
- 1600 S 64734 +
2000 S 64735 +
3p 2500 S 64736 + 58251 59897 + 65619
S 64737 +
E4 3200
LOAD -
H 64738 +
Withdrawable
W-VR 1600 S 64739 +
2000 S 64740 +
4p 2500 S 64741 + 58251 59137 + 65619
S 64742 +
3200
H 64743 +
+ -
LOAD +
3200 H 64750 +

3p 4000 H 64751 + 58251 59140 + 65619

E6 LOAD - 5000 H 64752 +


Withdrawable
W-VR 3200 H 64753 +

4p 4000 H 64754 + 58251 59143 + 65619

5000 H 64755 +

ABB SACE 57
1SDC200012D0902
Ordering codes
Insulated network - Lower power supply

1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V

PR122/DC

MP Fixed part
Horizontal terminals
1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code Code + Extracode
LOAD - 800 B 64590
1000 B 64591
3p 1250 B 64592 59891 + 67149
B 64593
E2 1600
N 64594
LOAD + -
+
Withdrawable
W-HR 800 B 64595
1000 B 64596
4p 1250 B 64597 59903 + 67149
B 64598
1600
N 64599
800 N 64618
1000 N 64619
LOAD - 1250 N 64620
N 64621
1600
3p H 64624 59892 + 67149
N 64622
LOAD + 2000
+ -
H 64625
N 64623
E3 2500
H 64626
Withdrawable
W-HR 800 N 64627
1000 N 64628
1250 N 62629
N 64630
1600
4p H 64633 59904 + 67149
N 64631
2000
H 64634
N 64632
2500
H 64635
LOAD - 1600 S 64646
2000 S 64647
3p 2500 S 64648 59893 + 67149
S 64649
E4 LOAD + 3200
+ -
H 64650
Withdrawable
W-HR 1600 S 64651
2000 S 64652
4p 2500 S 64653 59136 + 67149
S 64654
3200
H 64655
LOAD -
3200 H 64662

3p 4000 H 64663 59139 + 67149

E6 + LOAD + - 5000 H 64664


Withdrawable
W-HR 3200 H 64665

4p 4000 H 64666 59142 + 67149

5000 H 64667

58 ABB SACE
1SDC200012D0902
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V

PR123/DC

MP Fixed part
Horizontal terminals
1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code Code + Extracode
LOAD - 800 B 64678
1000 B 64679
3p 1250 B 64680 59891 + 67149
B 64681
E2 1600
N 64682
LOAD + -
+
Withdrawable
W-HR 800 B 64683
1000 B 64684
4p 1250 B 64685 59903 + 67149
B 64686
1600
N 64687
800 N 64706
1000 N 64707
LOAD - 1250 N 64708
N 64709
1600
3p H 64712 59892 + 67149
N 64710
LOAD + 2000
+ -
H 64713
N 64711
E3 2500
H 64714
Withdrawable
W-HR 800 N 64715
1000 N 64716
1250 N 64717
N 64718
1600
4p H 64721 59904 + 67149
N 64719
2000
H 64722
N 64720
2500
H 64723
LOAD - 1600 S 64734
2000 S 64735
3p 2500 S 64736 59893 + 67149
S 64737
E4 LOAD + 3200
+ -
H 64738
Withdrawable
W-HR 1600 S 64739
2000 S 64740
4p 2500 S 64741 59136 + 67149
S 64742
3200
H 64743
LOAD -
3200 H 64750

3p 4000 H 64751 59139 + 67149

E6 + LOAD + - 5000 H 64752


Withdrawable
W-HR 3200 H 64753

4p 4000 H 64754 59142 + 67149

5000 H 64755

ABB SACE 59
1SDC200012D0902
Ordering codes
Insulated network - Upper power supply

1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V

PR122/DC

MP Fixed part
Horizontal terminals
1sda0R1 1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code + Code Extracode + Extracode
+ LOAD +
- 800 B 64590 +
1000 B 64591 +
3p 1250 B 64592 + 58251 59891 + 67150
B 64593 +
E2 1600
LOAD -
N 64594 +
Withdrawable
W-HR 800 B 64595 +
1000 B 64596 +
4p 1250 B 64597 + 58251 59903 + 67150
B 64598 +
1600
N 64599 +
800 N 64618 +
1000 N 64619 +
+ LOAD +
- 1250 N 64620 +
N 64621 +
1600
3p H 64624 + 58251 59892 + 67150
N 64622 +
2000
H 64625 +
LOAD -

N 64623 +
E3 2500
H 64626 +
Withdrawable
W-HR 800 N 64627 +
1000 N 64628 +
1250 N 62629 +
N 64630 +
1600
4p H 64633 + 58251 59904 + 67150
N 64631 +
2000
H 64634 +
N 64632 +
2500
H 64635 +
+ LOAD +
- 1600 S 64646 +
2000 S 64647 +
3p 2500 S 64648 + 58251 59893 + 67150
S 64649 +
E4 3200
LOAD -
H 64650 +
Withdrawable
W-HR 1600 S 64651 +
2000 S 64652 +
4p 2500 S 64653 + 58251 59136 + 67150
S 64654 +
3200
H 64655 +
+ -
3200 H 64662 +
LOAD +

3p 4000 H 64663 + 58251 59139 + 67150

E6 LOAD - 5000 H 64664 +


Withdrawable
W-HR 3200 H 64665 +

4p 4000 H 64666 + 58251 59142 + 67150

5000 H 64667 +

60 ABB SACE
1SDC200012D0902
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V

PR123/DC

MP Fixed part
Horizontal terminals
1sda0R1 1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code + Code Extracode + Extracode
+ LOAD +
- 800 B 64678 +
1000 B 64679 +
3p 1250 B 64680 + 58251 59891 + 67150
B 64681 +
E2 1600
LOAD -
N 64682 +
Withdrawable
W-HR 800 B 64683 +
1000 B 64684 +
4p 1250 B 64685 + 58251 59903 + 67150
B 64686 +
1600
N 64687 +
800 N 64706 +
1000 N 64707 +
+ LOAD +
- 1250 N 64708 +
N 64709 +
1600
3p H 64712 + 58251 59892 + 67150
N 64710 +
2000
H 64713 +
LOAD -

N 64711 +
E3 2500
H 64714 +
Withdrawable
W-HR 800 N 64715 +
1000 N 64716 +
1250 N 64717 +
N 64718 +
1600
4p H 64721 + 58251 59904 + 67150
N 64719 +
2000
H 64722 +
N 64720 +
2500
H 64723 +
+ LOAD +
- 1600 S 64734 +
2000 S 64735 +
3p 2500 S 64736 + 58251 59893 + 67150
S 64737 +
E4 3200
LOAD -
H 64738 +
Withdrawable
W-HR 1600 S 64739 +
2000 S 64740 +
4p 2500 S 64741 + 58251 59136 + 67150
S 64742 +
3200
H 64743 +
+ -
3200 H 64750 +
LOAD +

3p 4000 H 64751 + 58251 59139 + 67150

E6 LOAD - 5000 H 64752 +


Withdrawable
W-HR 3200 H 64753 +

4p 4000 H 64754 + 58251 59142 + 67150

5000 H 64755 +

ABB SACE 61
1SDC200012D0902
Ordering codes
Network median point earthed - Lower power supply

1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
2 Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
2

PR123/DC

Vertical terminals 1sda0R1


Size Poles Front view Iu Performance Code
LOAD - 800 B 64668
1000 B 64669
3p 1250 B 64670
B 64671
E2 LOAD + - 1600
+
N 64672
Fixed
F-VR 800 B 64673
1000 B 64674
4p 1250 B 64675
B 64676
1600
N 64677
800 N 64688
1000 N 64689
LOAD - 1250 N 64690
N 64691
1600
3p H 64694
N 64692
2000
H 64695
LOAD + -
+

N 64693
E3 2500
H 64696
Fixed
F-VR 800 N 64697
1000 N 64698
1250 N 64699
N 64700
1600
4p H 64703
N 64701
2000
H 64704
N 64702
2500
H 64705
LOAD - 1600 S 64724
2000 S 64725
3p 2500 S 64726
S 64727
E4 LOAD + 3200
+ -
H 64728
Fixed
F-VR 1600 S 64729
2000 S 64730
4p 2500 S 64731
S 64732
3200
H 64733
LOAD -
3200 H 64744

3p 4000 H 64745

E6 + LOAD + - 5000 H 64746


Fixed
F-VR 3200 H 64747

4p 4000 H 64748

5000 H 64749

62 ABB SACE
1SDC200012D0902
Ordering codes
Network median point earthed - Upper power supply

1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
2 Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
2

PR123/DC

Vertical terminals 1sda0R1 1sda0R1


Size Poles Front view Iu Performance Code + Extracode
+ LOAD +
- 800 B 64668 +
1000 B 64669 +
3p 1250 B 64670 + 58251
B 64671 +
E2 1600
LOAD -
N 64672 +
Fixed
F-VR 800 B 64673 +
1000 B 64674 +
4p 1250 B 64675 + 58251
B 64676 +
1600
N 64677 +
800 N 64688 +
1000 N 64689 +
+ LOAD +
- 1250 N 64690 +
N 64691 +
1600
3p H 64694 + 58251
N 64692 +
2000
LOAD -
H 64695 +
N 64693 +
E3 2500
H 64696 +
Fixed
F-VR 800 N 64697 +
1000 N 64698 +
1250 N 64699 +
N 64700 +
1600
4p H 64703 + 58251
N 64701 +
2000
H 64704 +
N 64702 +
2500
H 64705 +
+ LOAD +
- 1600 S 64724 +
2000 S 64725 +
3p 2500 S 64726 + 58251
S 64727 +
E4 3200
H 64728 +
LOAD -

Fixed
F-VR 1600 S 64729 +
2000 S 64730 +
4p 2500 S 64731 + 58251
S 64732 +
3200
H 64733 +
+ -
3200 H 64744 +
LOAD +

3p 4000 H 64745 + 58251

E6 LOAD - 5000 H 64746 +


Fixed
F-VR 3200 H 64747 +

4p 4000 H 64748 + 58251

5000 H 64749 +

ABB SACE 63
1SDC200012D0902
Ordering codes
Network median point earthed - Lower power supply

1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
2 Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
2

PR123/DC

MP Fixed part
Vertical terminals
1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code Code + Extracode
LOAD - 800 B 64678
1000 B 64679
3p 1250 B 64680 59895 + 65169
B 64681
E2 LOAD + - 1600
+
N 64682
Withdrawable
W-VR 800 B 64683
1000 B 64684
4p 1250 B 64685 59906 + 65169
B 64686
1600
N 64687
800 N 64706
1000 N 64707
LOAD - 1250 N 64708
N 64709
1600
3p H 64712 59896 + 65169
N 64710
LOAD + 2000
+ -
H 64713
N 64711
E3 2500
H 64714
Withdrawable
W-VR 800 N 64715
1000 N 64716
1250 N 64717
N 64718
1600
4p H 64721 59907 + 65169
N 64719
2000
H 64722
N 64720
2500
H 64723
LOAD - 1600 S 64734
2000 S 64735
3p 2500 S 64736 59897 + 65169
S 64737
E4 LOAD + 3200
+ -
H 64738
Withdrawable
W-VR 1600 S 64739
2000 S 64740
4p 2500 S 64741 59137 + 65169
S 64742
3200
H 64743
LOAD -
3200 H 64750

3p 4000 H 64751 59140 + 65169

E6 + LOAD + - 5000 H 64752


Withdrawable
W-VR 3200 H 64753

4p 4000 H 64754 59143 + 65169

5000 H 64755

64 ABB SACE
1SDC200012D0902
Ordering codes
Network median point earthed - Upper power supply

1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
2 Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
2

PR123/DC

MP Fixed part
Vertical terminals
1sda0R1 1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code + Extracode Code + Extracode
+ LOAD +
- 800 B 64678 +
1000 B 64679 +
3p 1250 B 64680 + 58251 59895 + 65619
B 64681 +
E2 1600
LOAD -
N 64682 +
Withdrawable
W-VR 800 B 64683 +
1000 B 64684 +
4p 1250 B 64685 + 58251 59906 + 65619
B 64686 +
1600
N 64687 +
800 N 64706 +
1000 N 64707 +
+ LOAD +
- 1250 N 64708 +
N 64709 +
1600
3p H 64712 + 58251 59896 + 65619
N 64710 +
2000
LOAD -
H 64713 +
N 64711 +
E3 2500
H 64714 +
Withdrawable
W-VR 800 N 64715 +
1000 N 64716 +
1250 N 64717 +
N 64718 +
1600
4p H 64721 + 58251 59907 + 65619
N 64719 +
2000
H 64722 +
N 64720 +
2500
H 64723 +
+ LOAD +
- 1600 S 64734 +
2000 S 64735 +
3p 2500 S 64736 + 58251 59897 + 65619
S 64737 +
E4 3200
LOAD -
H 64738 +
Withdrawable
W-VR 1600 S 64739 +
2000 S 64740 +
4p 2500 S 64741 + 58251 59137 + 65619
S 64742 +
3200
H 64743 +
+ -
3200 H 64750 +
LOAD +

3p 4000 H 64751 + 58251 59140 + 65619

E6 LOAD - 5000 H 64752 +


Withdrawable
W-VR 3200 H 64753 +

4p 4000 H 64754 + 58251 59143 + 65619

5000 H 64755 +

ABB SACE 65
1SDC200012D0902
Ordering codes
Network median point earthed - Lower power supply

1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
2 Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
2

PR123/DC

MP Fixed part
Vertical terminals
1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code Code + Extracode
LOAD - 800 B 64678
1000 B 64679
3p 1250 B 64680 59891 + 67149
B 64681
E2 + LOAD + - 1600
N 64682
Withdrawable
W-HR 800 B 64683
1000 B 64684
4p 1250 B 64685 59903 + 67149
B 64686
1600
N 64687
800 N 64706
1000 N 64707
LOAD - 1250 N 64708
N 64709
1600
3p H 64712 59892 + 67149
N 64710
2000
H 64713
LOAD + -
+

N 64711
E3 2500
H 64714
Withdrawable
W-HR 800 N 64715
1000 N 64716
1250 N 64717
N 64718
1600
4p H 64721 59904 + 67149
N 64719
2000
H 64722
N 64720
2500
H 64723
LOAD - 1600 S 64734
2000 S 64735
3p 2500 S 64736 59893 + 67149
S 64737
E4 LOAD + 3200
+ -
H 64738
Withdrawable
W-HR 1600 S 64739
2000 S 64740
4p 2500 S 64741 59136 + 67149
S 64742
3200
H 64743
LOAD -
3200 H 64750

3p 4000 H 64751 59139 + 67149

E6 + LOAD + - 5000 H 64752


Withdrawable
W-HR 3200 H 64753

4p 4000 H 64754 59142 + 67149

5000 H 64755

66 ABB SACE
1SDC200012D0902
Ordering codes
Network median point earthed - Upper power supply

1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
2 Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
2

PR123/DC

MP Fixed part
Vertical terminals
1sda0R1 1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code + Extracode Code + Extracode
+ LOAD +
- 800 B 64678 +
1000 B 64679 +
3p 1250 B 64680 + 58251 59891 + 67150
B 64681 +
E2 1600
LOAD -
N 64682 +
Withdrawable
W-HR 800 B 64683 +
1000 B 64684 +
4p 1250 B 64685 + 58251 59903 + 67150
B 64686 +
1600
N 64687 +
800 N 64706 +
1000 N 64707 +
+ LOAD +
- 1250 N 64708 +
N 64709 +
1600
3p H 64712 + 58251 59892 + 67150
N 64710 +
2000
LOAD -
H 64713 +
N 64711 +
E3 2500
H 64714 +
Withdrawable
W-HR 800 N 64715 +
1000 N 64716 +
1250 N 64717 +
N 64718 +
1600
4p H 64721 + 58251 59904 + 67150
N 64719 +
2000
H 64722 +
N 64720 +
2500
H 64723 +
+ LOAD +
- 1600 S 64734 +
2000 S 64735 +
3p 2500 S 64736 + 58251 59893 + 67150
S 64737 +
E4 3200
LOAD -
H 64738 +
Withdrawable
W-HR 1600 S 64739 +
2000 S 64740 +
4p 2500 S 64741 + 58251 59136 + 67150
S 64742 +
3200
H 64743 +
+ -
3200 H 64750 +
LOAD +

3p 4000 H 64751 + 58251 59139 + 67150

E6 LOAD - 5000 H 64752 +


Withdrawable
W-HR 3200 H 64753 +

4p 4000 H 64754 + 58251 59142 + 67150

5000 H 64755 +

ABB SACE 67
1SDC200012D0902
Ordering codes
Network with earthed negative polarity -
Lower power supply

1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe500V* PR120/V
* For higher voltages, contact ABB

PR122/DC

Vertical terminals 1sda0R1 1sda0R1


Size Poles Front view Iu Performance Code + Extracode
LOAD - 800 B 64580 +
1000 B 64581 +
3p 1250 B 64582 + -
B 64583 +
E2 + LOAD + - 1600
N 64584 +
Fixed
F-VR 800 B 64585 +
1000 B 64586 +
4p 1250 B 64587 + 68806
B 64588 +
1600
N 64589 +
800 N 64600 +
1000 N 64601 +
LOAD - 1250 N 64602 +
N 64603 +
1600
3p H 64606 + -
N 64604 +
2000
H 64607 +
LOAD + -
+

N 64605 +
E3 2500
H 64608 +
Fixed
F-VR 800 N 64609 +
1000 N 64610 +
1250 N 64611 +
N 64612 +
1600
4p H 64615 + 68806
N 64613 +
2000
H 64616 +
N 64614 +
2500
H 64617 +
LOAD - 1600 S 64636 +
2000 S 64637 +
3p 2500 S 64638 + -
S 64639 +
E4 LOAD + - 3200
+
H 64640 +
Fixed
F-VR 1600 S 64641 +
2000 S 64642 +
4p 2500 S 64643 + 68806
S 64644 +
3200
H 64645 +
LOAD -
3200 H 64656 +

3p 4000 H 64657 + -

E6 + LOAD + - 5000 H 64658 +


Fixed
F-VR 3200 H 64659 +

4p 4000 H 64660 + 68806

5000 H 64661 +

68 ABB SACE
1SDC200012D0902
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe500V* PR120/V
* For higher voltages, contact ABB

PR123/DC

Vertical terminals 1sda0R1 1sda0R1


Size Poles Front view Iu Performance 1sda0R1 + Extracode
LOAD - 800 B 64668 +
1000 B 64669 +
3p 1250 B 64670 + -
B 64671 +
E2 + LOAD + - 1600
N 64672 +
Fixed
F-VR 800 B 64673 +
1000 B 64674 +
4p 1250 B 64675 + 68806
B 64676 +
1600
N 64677 +
800 N 64688 +
1000 N 64689 +
LOAD - 1250 N 64690 +
N 64691 +
1600
3p H 64694 + -
N 64692 +
2000
H 64695 +
LOAD + -
+

N 64693 +
E3 2500
H 64696 +
Fixed
F-VR 800 N 64697 +
1000 N 64698 +
1250 N 64699 +
N 64700 +
1600
4p H 64703 + 68806
N 64701 +
2000
H 64704 +
N 64702 +
2500
H 64705 +
LOAD - 1600 S 64724 +
2000 S 64725 +
3p 2500 S 64726 + -
S 64727 +
E4 LOAD + 3200
+ -
H 64728 +
Fixed
F-VR 1600 S 64729 +
2000 S 64730 +
4p 2500 S 64731 + 68806
S 64732 +
3200
H 64733 +
LOAD -
3200 H 64744 +

3p 4000 H 64745 + -

E6 + LOAD + - 5000 H 64746 +


Fixed
F-VR 3200 H 64747 +

4p 4000 H 64748 + 68806

5000 H 64749 +

ABB SACE 69
1SDC200012D0902
Ordering codes
Network with earthed negative polarity -
Upper power supply

1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe500V* PR120/V
* For higher voltages, contact ABB

PR122/DC

Vertical terminals 1sda0R1 1sda0R1 1sda0R1


Size Poles Front view Iu Performance Code + Extracode + Extracode
+ LOAD +
- 800 B 64580 + +
1000 B 64581 + +
3p 1250 B 64582 + 58251 + -
B 64583 + +
E2 LOAD - 1600
N 64584 + +
Fixed
F-VR 800 B 64585 + +
1000 B 64586 + +
4p 1250 B 64587 + 58251 + 68806
B 64588 + +
1600
N 64589 + +
800 N 64600 + +
1000 N 64601 + +
+ LOAD +
- 1250 N 64602 + +
N 64603 + +
1600
3p H 64606 + 58251 + -
N 64604 + +
2000
LOAD -
H 64607 + +
N 64605 + +
E3 2500
H 64608 + +
Fixed
F-VR 800 N 64609 + +
1000 N 64610 + +
1250 N 64611 + +
N 64612 + +
1600
4p H 64615 + 58251 + 68806
N 64613 + +
2000
H 64616 + +
N 64614 + +
2500
H 64617 + +
+ LOAD +
- 1600 S 64636 + +
2000 S 64637 + +
3p 2500 S 64638 + 58251 + -
S 64639 + +
E4 3200
H 64640 + +
LOAD -

Fixed
F-VR 1600 S 64641 + +
2000 S 64642 + +
4p 2500 S 64643 + 58251 + 68806
S 64644 + +
3200
H 64645 + +
+ -
LOAD +
3200 H 64656 + +

3p 4000 H 64657 + 58251 + -

E6 LOAD - 5000 H 64658 + +


Fixed
F-VR 3200 H 64659 + +

4p 4000 H 64660 + 58251 + 68806

5000 H 64661 + +

70 ABB SACE
1SDC200012D0902
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe500V* PR120/V
* For higher voltages, contact ABB

PR123/DC

Vertical terminals 1sda0R1 1sda0R1 1sda0R1


Size Poles Front view Iu Performance Code + Extracode + Extracode
+ LOAD +
- 800 B 64668 + +
1000 B 64669 + +
3p 1250 B 64670 + 58251 + -
B 64671 + +
E2 1600
N 64672 + +
LOAD -

Fixed
F-VR 800 B 64673 + +
1000 B 64674 + +
4p 1250 B 64675 + 58251 + 68806
B 64676 + +
1600
N 64677 + +
800 N 64688 + +
1000 N 64689 + +
+ LOAD +
- 1250 N 64690 + +
N 64691 + +
1600
3p H 64694 + 58251 + -
N 64692 + +
2000
LOAD -
H 64695 + +
N 64693 + +
E3 2500
H 64696 + +
Fixed
F-VR 800 N 64697 + +
1000 N 64698 + +
1250 N 64699 + +
N 64700 + +
1600
4p H 64703 + 58251 + 68806
N 64701 + +
2000
H 64704 + +
N 64702 + +
2500
H 64705 + +
+ LOAD +
- 1600 S 64724 + +
2000 S 64725 + +
3p 2500 S 64726 + 58251 + -
S 64727 + +
E4 3200
H 64728 + +
LOAD -

Fixed
F-VR 1600 S 64729 + +
2000 S 64730 + +
4p 2500 S 64731 + 58251 + 68806
S 64732 + +
3200
H 64733 + +
+ -
LOAD +
3200 H 64744 + +

3p 4000 H 64745 + 58251 + -

E6 LOAD - 5000 H 64746 + +


Fixed
F-VR 3200 H 64747 + +

4p 4000 H 64748 + 58251 + 68806

5000 H 64749 + +

ABB SACE 71
1SDC200012D0902
Ordering codes
Network with earthed negative polarity -
Lower power supply

1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe500V* PR120/V
* For higher voltages, contact ABB

PR122/DC

MP Fixed part
Vertical terminals
1sda0R1 1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code Code + Extracode + Extracode
LOAD - 800 B 64590
1000 B 64591
3p 1250 B 64592 59895 + 65169 + -
B 64593
E2 1600
N 64594
LOAD + -
+
Withdrawable
W-VR 800 B 64595
1000 B 64596
4p 1250 B 64597 59906 + 65169 + 68806
B 64598
1600
N 64599
800 N 64618
1000 N 64619
LOAD - 1250 N 64620
N 64621
1600
3p H 64624 59896 + 65169 + -
N 64622
2000
H 64625
LOAD + -
+

N 64623
E3 2500
H 64626
Withdrawable
W-VR 800 N 64627
1000 N 64628
1250 N 62629
N 64630
1600
4p H 64633 59907 + 65169 + 68806
N 64631
2000
H 64634
N 64632
2500
H 64635
LOAD - 1600 S 64646
2000 S 64647
3p 2500 S 64648 59897 + 65169 + -
S 64649
E4 LOAD + 3200
+ -
H 64650
Withdrawable
W-VR 1600 S 64651
2000 S 64652
4p 2500 S 64653 59137 + 65169 + 68806
S 64654
3200
H 64655
LOAD -
3200 H 64662

3p 4000 H 64663 59140 + 65169 + -

E6 + LOAD + - 5000 H 64664


Withdrawable
W-VR 3200 H 64665

4p 4000 H 64666 59143 + 65169 + 68806

5000 H 64667

72 ABB SACE
1SDC200012D0902
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe500V* PR120/V
* For higher voltages, contact ABB

PR123/DC

MP Fixed part
Vertical terminals
1sda0R1 1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code Code + Extracode + Extracode
LOAD - 800 B 64678
1000 B 64679
3p 1250 B 64680 59895 + 65169 + -
B 64681
E2 LOAD + - 1600
+
N 64682
Withdrawable
W 800 B 64683
1000 B 64684
4p 1250 B 64685 59906 + 65169 + 68806
B 64686
1600
N 64687
800 N 64706
1000 N 64707
LOAD - 1250 N 64708
N 64709
1600
3p H 64712 59896 + 65169 + -
N 64710
LOAD + - 2000
+
H 64713
N 64711
E3 2500
H 64714
Withdrawable
W 800 N 64715
1000 N 64716
1250 N 64717
N 64718
1600
4p H 64721 59907 + 65169 + 68806
N 64719
2000
H 64722
N 64720
2500
H 64723
LOAD - 1600 S 64734
2000 S 64735
3p 2500 S 64736 59897 + 65169 + -
S 64737
E4 3200
H 64738
LOAD + -
+
Withdrawable
W 1600 S 64739
2000 S 64740
4p 2500 S 64741 59137 + 65169 + 68806
S 64742
3200
H 64743
LOAD -
3200 H 64750

3p 4000 H 64751 59140 + 65169 + -

E6 + LOAD + - 5000 H 64752


Withdrawable
W 3200 H 64753

4p 4000 H 64754 59143 + 65169 + 68806

5000 H 64755

ABB SACE 73
1SDC200012D0902
Ordering codes
Network with earthed negative polarity -
Upper power supply

1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe500V* PR120/V
* For higher voltages, contact ABB

PR122/DC

MP Fixed part
Vertical terminals
1sda0R1 1sda0R1 1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code + Code Code + Extracode + Extracode
+ LOAD +
- 800 B 64590 +
1000 B 64591 +
3p 1250 B 64592 + 58251 59895 + 65619 + -
B 64593 +
E2 LOAD - 1600
N 64594 +
Withdrawable
W-VR 800 B 64595 +
1000 B 64596 +
4p 1250 B 64597 + 58251 59906 + 65619 + 68806
B 64598 +
1600
N 64599 +
800 N 64618 +
1000 N 64619 +
+ LOAD +
- 1250 N 64620 +
N 64621 +
1600
3p H 64624 + 58251 59896 + 65619 + -
N 64622 +
2000
LOAD -
H 64625 +
N 64623 +
E3 2500
H 64626 +
Withdrawable
W-VR 800 N 64627 +
1000 N 64628 +
1250 N 62629 +
N 64630 +
1600
4p H 64633 + 58251 59907 + 65619 + 68806
N 64631 +
2000
H 64634 +
N 64632 +
2500
H 64635 +
+ LOAD +
- 1600 S 64646 +
2000 S 64647 +
3p 2500 S 64648 + 58251 59897 + 65619 + -
S 64649 +
E4 3200
LOAD -
H 64650 +
Withdrawable
W-VR 1600 S 64651 +
2000 S 64652 +
4p 2500 S 64653 + 58251 59137 + 65619 + 68806
S 64654 +
3200
H 64655 +
+ -
LOAD +
3200 H 64662 +

3p 4000 H 64663 + 58251 59140 + 65619 + -

E6 LOAD - 5000 H 64664 +


Withdrawable
W-VR 3200 H 64665 +

4p 4000 H 64666 + 58251 59143 + 65619 + 68806

5000 H 64667 +

74 ABB SACE
1SDC200012D0902
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe500V* PR120/V
* For higher voltages, contact ABB

PR123/DC

MP Fixed part
Vertical terminals
1sda0R1 1sda0R1 1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code + Extracode Code + Extracode + Extracode
+ LOAD +
- 800 B 64678 +
1000 B 64679 +
3p 1250 B 64680 + 58251 59895 + 65619 + -
B 64681 +
E2 1600
N 64682 +
LOAD -

Withdrawable
W-VR 800 B 64683 +
1000 B 64684 +
4p 1250 B 64685 + 58251 59906 + 65619 + 68806
B 64686 +
1600
N 64687 +
800 N 64706 +
1000 N 64707 +
+ LOAD +
- 1250 N 64708 +
N 64709 +
1600
3p H 64712 + 58251 59896 + 65619 + -
N 64710 +
2000
LOAD -
H 64713 +
N 64711 +
E3 2500
H 64714 +
Withdrawable
W-VR 800 N 64715 +
1000 N 64716 +
1250 N 64717 +
N 64718 +
1600
4p H 64721 + 58251 59907 + 65619 + 68806
N 64719 +
2000
H 64722 +
N 64720 +
2500
H 64723 +
+ LOAD +
- 1600 S 64734 +
2000 S 64735 +
3p 2500 S 64736 + 58251 59897 + 65619 + -
S 64737 +
E4 3200
H 64738 +
LOAD -

Withdrawable
W-VR 1600 S 64739 +
2000 S 64740 +
4p 2500 S 64741 + 58251 59137 + 65619 + 68806
S 64742 +
3200
H 64743 +
+ -
3200 H 64750 +
LOAD +

3p 4000 H 64751 + 58251 59140 + 65619 + -

E6 LOAD - 5000 H 64752 +


Withdrawable
W-VR 3200 H 64753 +

4p 4000 H 64754 + 58251 59143 + 65619 + 68806

5000 H 64755 +

ABB SACE 75
1SDC200012D0902
Ordering codes
Network with earthed negative polarity -
Lower power supply

1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe500V* PR120/V
* For higher voltages, contact ABB

PR122/DC

MP Fixed part
Horizontal terminals
1sda0R1 1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code Code + Extracode + Extracode
LOAD - 800 B 64590
1000 B 64591
3p 1250 B 64592 59891 + 67149 + -
B 64593
E2 LOAD + - 1600
+
N 64594
Withdrawable
W-HR 800 B 64595
1000 B 64596
4p 1250 B 64597 59903 + 67149 + 68806
B 64598
1600
N 64599
800 N 64618
1000 N 64619
LOAD - 1250 N 64620
N 64621
1600
3p H 64624 59892 + 67149 + -
N 64622
LOAD + - 2000
+
H 64625
N 64623
E3 2500
H 64626
Withdrawable
W-HR 800 N 64627
1000 N 64628
1250 N 62629
N 64630
1600
4p H 64633 59904 + 67149 + 68806
N 64631
2000
H 64634
N 64632
2500
H 64635
LOAD - 1600 S 64646
2000 S 64647
3p 2500 S 64648 59893 + 67149 + -
S 64649
E4 LOAD + 3200
+ -
H 64650
Withdrawable
W-HR 1600 S 64651
2000 S 64652
4p 2500 S 64653 59136 + 67149 + 68806
S 64654
3200
H 64655
LOAD -
3200 H 64662

3p 4000 H 64663 59139 + 67149 + -

E6 + LOAD + - 5000 H 64664


Withdrawable
W-HR 3200 H 64665

4p 4000 H 64666 59142 + 67149 + 68806

5000 H 64667

76 ABB SACE
1SDC200012D0902
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe500V* PR120/V
* For higher voltages, contact ABB

PR123/DC

MP Fixed part
Horizontal terminals
1sda0R1 1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code Code + Extracode + Extracode
LOAD - 800 B 64678
1000 B 64679
3p 1250 B 64680 59891 + 67149 + -
B 64681
E2 LOAD + - 1600
+
N 64682
Withdrawable
W-HR 800 B 64683
1000 B 64684
4p 1250 B 64685 59903 + 67149 + 68806
B 64686
1600
N 64687
800 N 64706
1000 N 64707
LOAD - 1250 N 64708
N 64709
1600
3p H 64712 59892 + 67149 + -
N 64710
LOAD + 2000
+ -
H 64713
N 64711
E3 2500
H 64714
Withdrawable
W-HR 800 N 64715
1000 N 64716
1250 N 64717
N 64718
1600
4p H 64721 59904 + 67149 + 68806
N 64719
2000
H 64722
N 64720
2500
H 64723
LOAD - 1600 S 64734
2000 S 64735
3p 2500 S 64736 59893 + 67149 + -
S 64737
E4 LOAD + 3200
+ -
H 64738
Withdrawable
W-HR 1600 S 64739
2000 S 64740
4p 2500 S 64741 59136 + 67149 + 68806
S 64742
3200
H 64743
LOAD -
3200 H 64750

3p 4000 H 64751 59139 + 67149 + -

E6 + LOAD + - 5000 H 64752


Withdrawable
W-HR 3200 H 64753

4p 4000 H 64754 59142 + 67149 + 68806

5000 H 64755

ABB SACE 77
1SDC200012D0902
Ordering codes
Network with earthed negative polarity -
Upper power supply

1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe500V* PR120/V
* For higher voltages, contact ABB

PR122/DC

MP Fixed part
Horizontal terminals
1sda0R1 1sda0R1 1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code + Code Code + Extracode + Extracode
+ LOAD +
- 800 B 64590 +
1000 B 64591 +
3p 1250 B 64592 + 58251 59891 + 67150 + -
B 64593 +
E2 1600
N 64594 +
LOAD -

Withdrawable
W-HR 800 B 64595 +
1000 B 64596 +
4p 1250 B 64597 + 58251 59903 + 67150 + 68806
B 64598 +
1600
N 64599 +
800 N 64618 +
1000 N 64619 +
+ LOAD +
- 1250 N 64620 +
N 64621 +
1600
3p H 64624 + 58251 59892 + 67150 + -
N 64622 +
2000
H 64625 +
LOAD -

N 64623 +
E3 2500
H 64626 +
Withdrawable
W-HR 800 N 64627 +
1000 N 64628 +
1250 N 62629 +
N 64630 +
1600
4p H 64633 + 58251 59904 + 67150 + 68806
N 64631 +
2000
H 64634 +
N 64632 +
2500
H 64635 +
+ LOAD +
- 1600 S 64646 +
2000 S 64647 +
3p 2500 S 64648 + 58251 59893 + 67150 + -
S 64649 +
E4 3200
LOAD -
H 64650 +
Withdrawable
W-HR 1600 S 64651 +
2000 S 64652 +
4p 2500 S 64653 + 58251 59136 + 67150 + 68806
S 64654 +
3200
H 64655 +
+ -
3200 H 64662 +
LOAD +

3p 4000 H 64663 + 58251 59139 + 67150 + -

E6 LOAD - 5000 H 64664 +


Withdrawable
W-HR 3200 H 64665 +

4p 4000 H 64666 + 58251 59142 + 67150 + 68806

5000 H 64667 +

78 ABB SACE
1SDC200012D0902
1SDA0...R1
+
L
O Ue<100V Vaux is compulsory
A
D
-
Ue 100VUe250V Specific extracode for PR120/LV 65223
250VUe500V* PR120/V
* For higher voltages, contact ABB

PR123/DC

MP Fixed part
Horizontal terminals
1sda0R1 1sda0R1 1sda0R1 1sda0R1 1sda0R1
Size Poles Front view Iu Performance Code + Code Code + Extracode + Extracode
+ LOAD +
- 800 B 64678 +
1000 B 64679 +
3p 1250 B 64680 + 58251 59891 + 67150 + -
B 64681 +
E2 1600
N 64682 +
LOAD -

Withdrawable
W-HR 800 B 64683 +
1000 B 64684 +
4p 1250 B 64685 + 58251 59903 + 67150 + 68806
B 64686 +
1600
N 64687 +
800 N 64706 +
1000 N 64707 +
+ LOAD +
- 1250 N 64708 +
N 64709 +
1600
3p H 64712 + 58251 59892 + 67150 + -
N 64710 +
2000
H 64713 +
LOAD -

N 64711 +
E3 2500
H 64714 +
Withdrawable
W-HR 800 N 64715 +
1000 N 64716 +
1250 N 64717 +
N 64718 +
1600
4p H 64721 + 58251 59904 + 67150 + 68806
N 64719 +
2000
H 64722 +
N 64720 +
2500
H 64723 +
+ LOAD +
- 1600 S 64734 +
2000 S 64735 +
3p 2500 S 64736 + 58251 59893 + 67150 + -
S 64737 +
E4 3200
LOAD -
H 64738 +
Withdrawable
W-HR 1600 S 64739 +
2000 S 64740 +
4p 2500 S 64741 + 58251 59136 + 67150 + 68806
S 64742 +
3200
H 64743 +
+ -
3200 H 64750 +
LOAD +

3p 4000 H 64751 + 58251 59139 + 67150 + -

E6 LOAD - 5000 H 64752 +


Withdrawable
W-HR 3200 H 64753 +

4p 4000 H 64754 + 58251 59142 + 67150 + 68806

5000 H 64755 +

ABB SACE 79
1SDC200012D0902
Ordering codes
SACE Emax switch-disconnectors for applications
up to 1000V DC

1SDA......R1
3 Poles 4 Poles
750V DC 1000V DC

E1B/E MS 08 Iu (40 C) = 800 A Icw (1 s) = 20 kA


Fixed (F) HR = Horizontal rear terminals 059041 059042
1SDC200259F0001

E1B/E MS 12 Iu (40 C) = 1250 A Icw (1 s) = 20 kA


Fixed (F) HR = Horizontal rear terminals 059043 059044
E1B/E MS 08 Iu (40 C) = 800 A Icw (1 s) = 20 kA
Withdrawable (W) - MP MP = Moving part 059045 059046
E1B/E MS 12 Iu (40 C) = 1250 A Icw (1 s) = 20 kA
Withdrawable (W) - MP MP = Moving part 059047 059048
E2N/E MS 12 Iu (40 C) = 1250 A Icw (1 s) = 25 kA
Fixed (F) HR = Horizontal rear terminals 059049 059050
E2N/E MS 16 Iu (40 C) = 1600 A Icw (1 s) = 25 kA
Fixed (F) HR = Horizontal rear terminals 059051 059052
E2N/E MS 20 Iu (40 C) = 2000 A Icw (1 s) = 25 kA
Fixed (F) HR = Horizontal rear terminals 059053 059054
E2N/E MS 12 Iu (40 C) = 1250 A Icw (1 s) = 25 kA
Withdrawable (W) - MP MP = Moving part 059055 059056
E2N/E MS 16 Iu (40 C) = 1600 A Icw (1 s) = 25 kA
Withdrawable (W) - MP MP = Moving part 059057 059058
E2N/E MS 20 Iu (40 C) = 2000 A Icw (1 s) = 25 kA
Withdrawable (W) - MP MP = Moving part 059059 059060
E3H/E MS 12 Iu (40 C) = 1250 A Icw (1 s) = 40 kA
Fixed (F) HR = Horizontal rear terminals 059061 059062
1SDC200260F0001

E3H/E MS 16 Iu (40 C) = 1600 A Icw (1 s) = 40 kA


Fixed (F) HR = Horizontal rear terminals 059063 059064
E3H/E MS 20 Iu (40 C) = 2000 A Icw (1 s) = 40 kA
Fixed (F) HR = Horizontal rear terminals 059065 059066
E3H/E MS 25 Iu (40 C) = 2500 A Icw (1 s) = 40 kA
Fixed (F) HR = Horizontal rear terminals 059067 059068
E3H/E MS 32 Iu (40 C) = 3200 A Icw (1 s) = 40 kA
Fixed (F) HR = Horizontal rear terminals 059069 059070
E3H/E MS 12 Iu (40 C) = 1250 A Icw (1 s) = 40 kA
Withdrawable (W) - MP MP = Moving part 059071 059072
E3H/E MS 16 Iu (40 C) = 1600 A Icw (1 s) = 40 kA
Withdrawable (W) - MP MP = Moving part 059073 059074
E3H/E MS 20 Iu (40 C) = 2000 A Icw (1 s) = 40 kA
Withdrawable (W) - MP MP = Moving part 059075 059076
E3H/E MS 25 Iu (40 C) = 2500 A Icw (1 s) = 40 kA
Withdrawable (W) - MP MP = Moving part 059077 059078
E3H/E MS 32 Iu (40 C) = 3200 A Icw (1 s) = 40 kA
Withdrawable (W) - MP MP = Moving part 059079 059080
E4H/E MS 32 Iu (40 C) = 3200 A Icw (1 s) = 65 kA
Fixed (F) HR = Horizontal rear terminals 059081 058911
E4H/E MS 40 Iu (40 C) = 4000 A Icw (1 s) = 65 kA
Fixed (F) HR = Horizontal rear terminals 059082 058913
E4H/E MS 32 Iu (40 C) = 3200 A Icw (1 s) = 65 kA
Withdrawable (W) - MP MP = Moving part 059083 058912
E4H/E MS 40 Iu (40 C) = 4000 A Icw (1 s) = 65 kA
Withdrawable (W) - MP MP = Moving part 059084 058914
E6H/E MS 40 Iu (40 C) = 4000 A Icw (1 s) = 65 kA
Fixed (F) HR = Horizontal rear terminals 058915 058921
1SDC200262F0001

E6H/E MS 50 Iu (40 C) = 5000 A Icw (1 s) = 65 kA


Fixed (F) HR = Horizontal rear terminals 058917 058923
E6H/E MS 63 Iu (40 C) = 6300 A Icw (1 s) = 65 kA
Fixed (F) HR = Horizontal rear terminals 058919 058925
E6H/E MS 40 Iu (40 C) = 4000 A Icw (1 s) = 65 kA
Withdrawable (W) - MP MP = Moving part 058916 058922
E6H/E MS 50 Iu (40 C) = 5000 A Icw (1 s) = 65 kA
Withdrawable (W) - MP MP = Moving part 058918 058924
E6H/E MS 63 Iu (40 C) = 6300 A Icw (1 s) = 65 kA
Withdrawable (W) - MP MP = Moving part 058920 058926

80 ABB SACE
1SDC200012D0902
Ordering codes
Fixed parts for SACE Emax switch-disconnectors for
applications up to 1000V DC

1SDA......R1
3 Poles 4 Poles
750V DC 1000V DC

FP = Fixed part
E1 MS/E HR 059890 059902
Withdrawable (W) - MP VR 059894 059905
FL 059898 059908
HR FP = Fixed part
E2 MS/E HR 059891 059903
Withdrawable (W) - MP VR 059895 059906
FL 059899 059909
FP = Fixed part
E3 MS/E HR 059892 059904
Withdrawable (W) - MP VR 059896 059907
VR FL 059900 059910
FP = Fixed part
E4 MS/E HR 059893 059136
Withdrawable (W) - MP VR 059897 059137
FL 059901 059138
FP = Fixed part
E6 MS/E HR 059139 059142
Withdrawable (W) - MP VR 059140 059143
FL
FL 059141 059144

ABB SACE 81
1SDC200012D0902
Ordering codes
SACE Emax DC accessories

Electrical accessories
1sdaR1

Undervoltage release - YU (2a)


E2/6 DC 24V DC 038286
E2/6 DC 30V AC / DC 038287
E2/6 DC 48V AC / DC 038288
E2/6 DC 60V AC / DC 038289
E2/6 DC 110...120V AC / DC 038290
E2/6 DC 120127V AC / DC 038291
E2/6 DC 220240V AC / DC 038292
E2/6 DC 240250V AC / DC 038293
E2/6 DC 380400V AC 038294
E2/6 DC 440480V AC 038295
Note: the shunt opening (YO) and closing (YC) releases are constructionally identical and therefore interchangeable. Their function is
linked to the assembly position on the circuit-breaker.

Electronic time-delay device for undervoltage release - D (2b)


E2/6 DC 24V DC 050157
E2/6 DC 30V AC / DC 050158
E2/6 DC 48V AC / DC 050159
E2/6 DC 60V AC / DC 050160
E2/6 DC 110...120V AC / DC 050161
E2/6 DC 120127V AC / DC 050162
E2/6 DC 220240V AC / DC 050163
E2/6 DC 240250V AC / DC 050164
E2/6 DC 380400V AC 050165
E2/6 DC 440480V AC 050166
Note: supplied with support for special releases.

Shunt closing release - YC (1a)


E2/6 DC 24V DC 038296
E2/6 DC 30V AC / DC 038297
E2/6 DC 48V AC / DC 038298
E2/6 DC 60V AC / DC 038299
E2/6 DC 110...120V AC / DC 038300
E2/6 DC 120127V AC / DC 038301
E2/6 DC 220240V AC / DC 038302
E2/6 DC 240250V AC / DC 038303
E2/6 DC 380400V AC 038304
E2/6 DC 440480V AC 038305
Note: the shunt opening (YO) and closing (YC) releases are constructionally identical and therefore interchangeable. Their function is
linked to the assembly position on the circuit-breaker.

SOR Test Unit - (1b)


E2/6 DC 050228

Undervoltage release - YU (2a)


E2/6 DC 24V DC 038306
E2/6 DC 30V AC / DC 038307
E2/6 DC 48V AC / DC 038308
E2/6 DC 60V AC / DC 038309
E2/6 DC 110...120V AC / DC 038310
E2/6 DC 120127V AC / DC 038311
E2/6 DC 220240V AC / DC 038312
E2/6 DC 240250V AC / DC 038313
E2/6 DC 380400V AC 038314
E2/6 DC 440480V AC 038315

82 ABB SACE
1SDC200012D0902
1sdaR1

Electronic time-delay device for undervoltage release - D (2b)


E2/6 DC 24...30V DC 038316
E2/6 DC 48V AC / DC 038317
E2/6 DC 60V AC / DC 038318
E2/6 DC 110...127V AC / DC 038319
E2/6 DC 220250V AC / DC 038320

Geared motor for automatic charging of the closing springs - M (3)


E2/6 DC 24...30V AC / DC 038321
E2/6 DC 4860V AC / DC 038322
E2/6 DC 100...130V AC / DC 038323
E2/6 DC 220250V AC / DC 038324
Note: it is always supplied with limit contact and microswitch for indication of closing springs charged (accessory 5d)

Overcurrent release trip indication - (4a)


E2/6 DC 058260

Electrical indication of overcurrent release trip by remote control - (4b)


E2/6 DC 220...240V AC/DC 058261
E2/6 DC 110...130V AC/DC 058262
E2/6 DC 24...30V AC/DC 058263

Electrical indication of circuit-breaker open/closed - Q1 ... 10 - (5a)


E2/6 DC - PR122-3/DC 4 auxiliary contacts (2NO+2NC+2PR122-3) 068801 (c)
E2/6 DC - PR122-3/DC 4 auxiliary contacts (2NO+2NC+2PR122-3) for digital signals 068802
E2/6 DC - PR122-3/DC 10 auxiliary contacts (5NO+5NC+2PR122-3 - installed) 068803 (a)
E2/6 DC - PR122-3/DC 10 auxiliary contacts (5NO+5NC+2PR122-3 - not installed) 068804 (b)
E2/6 DC - PR122-3/DC 10 auxiliary contacts (5NO+5NC+2PR122-3) for digital signals 068805
Note: (a) Can only be ordered mounted with circuit-breakers.
(b) Can only be ordered loose in the case of circuit-breakers.
(c) Already included for circuit-breakers with PR122/DC and PR123/DC. Can only be ordered as loose accessories.

Additional external electrical indication of circuit-breaker open/closed - Q11 ... 25 - (5b)


E2/6 DC 15 additional auxiliary contacts (version for fixed/ withdrawable racked-in) 043475 (a)
E2/6 DC 15 additional auxiliary contacts (version for withdrawable racked-in/ test) 048827
15 additional auxiliary contacts for digital signals (version for
E2/6 DC 050145 (a)
fixed/withdrawable racked-in)
15 additional auxiliary contacts for digital signals (version for
E2/6 DC 050151
withdrawable racked-in/ test)
Nota: Outside the circuit-breaker. To be requested in alternative to the different types of interlocks (accessory 10) and to the mechanical
compartment door lock (accessory 8f).
(a) For fixed version, also request the interlock plate (accessory 10.4).

ABB SACE 83
1SDC200012D0902
Ordering codes
SACE Emax DC accessories

1sdaR1
3 poles 4 poles

Electrical indication of circuit-breaker racked-in/isolated test/isolated S75 - (5c)


E2/6 DC 5 auxiliary contacts 038361 038361
E1-E2 10 auxiliary contacts 038360 043467
E3 10 auxiliary contacts 043468 043469
E4-E6 10 auxiliary contacts 043470 043470
E2/6 DC 5 auxiliary contacts for digital signals 050146 050146
E1-E2 10 auxiliary contacts for digital signals 050147 050148
E4-6 10 auxiliary contacts for digital signals 050147 050147
E3 10 auxiliary contacts for digital signals 050149 050150

Signalling contact for closing springs charged S33 M/2- (5d)


E2/6 DC 038325
Note: already supplied with the geared motor for automatic charging of the closing springs.

Contact for signalling undervoltage release de-energised - (5e)


E2/6 DC 1 normally closed contact 038341
E2/6 DC 1 normally open contact 038340

84 ABB SACE
1SDC200012D0902
Mechanical accessories
1sdaR1

Mechanical operation counter - (7)


E2/6 DC 038345

Locks in open position - (8a-8b)


with key (8a)
E2/6 DC for 1 circuit-breaker (different keys) 058271
E2/6 DC for groups of circuit-breakers (same keys N.20005) 058270
E2/6 DC for groups of circuit-breakers (same keys N.20006) 058274
E2/6 DC for groups of circuit-breakers (same keys N.20007) 058273
E2/6 DC for groups of circuit-breakers (same keys N.20008) 058272
E2/6 DC for groups of circuit-breakers (same keys N.20009) 064503
with padlocks (8b)
E2/6 DC 4 mm 038351 (a)
E2/6 DC 8 mm 064504
Note: (a) to be requested in alternative to the opening and closing pushbutton protection (accessory 9a).

Circuit-breaker lock in racked-in/test/racked-out position - (8c)


E2/6 DC for 1 circuit-breaker (different keys and with padlocks 4mm) 058278
E2/6 DC for groups of circuit-breakers (same keys N.2005 and with padlocks 4mm) 058277
E2/6 DC for groups of circuit-breakers (same keys N.2006 and with padlocks 4mm) 058281
E2/6 DC for groups of circuit-breakers (same keys N.2007 and with padlocks 4mm) 058280
E2/6 DC for groups of circuit-breakers (same keys N.2008 and with padlocks 4mm 058279
E2/6 DC for groups of circuit-breakers (same keys N.2009 and with padlocks 4mm) 064505
E2/6 DC for 1 circuit-breaker (same keys N.2009 and with padlocks 6mm) 064506
E2/6 DC for groups of circuit-breakers (same keys N.2005 and with padlocks 6mm) 064507
E2/6 DC for groups of circuit-breakers (same keys N.2006 and with padlocks 6mm) 064508
E2/6 DC for groups of circuit-breakers (same keys N.2007 and with padlocks 6mm) 064509
E2/6 DC for groups of circuit-breakers (same keys N.2008 and with padlocks 6mm) 064510
E2/6 DC for groups of circuit-breakers (same keys N.2009 and with padlocks 6mm) 064511

Padlocks
E2/6 DC 8mm 064512

Preset for key lock


RONIS

Cap preset 058315


Lock in open position 058276
Lock in racked-in/test/racked-out position 058314
CASTELL

Lock in open position 058275

Accessory for lock in test/racked-out position - (8d)


E1/6 038357
Note: to be requested for completion of the circuit-breaker lock in racked-in / test / racked-out position (accessory 8c)

Accessory for shutter padlock lock - (8e)


E2/6 DC 038363

Mechanical compartment door lock - (8f)


E2/6 DC 045039
Note:
- to be requested with interlock for fixed circuit-breaker/moving part of withdrawable circuit-breaker (accessory 10.2)
- for fixed version, also request interlock plate 10.4
- to be ordered in alternative to the cable interlocks (accessory 10.1), and in alternative to the 15 additional auxiliary contacts (accessory 5b).

ABB SACE 85
1SDC200012D0902
Ordering codes
SACE Emax DC accessories

1sdaR1

Opening and closing pushbutton protection - (9a)


E2/6 DC 038343
Note: to be requested in alternative to the lock with padlocks in open position (accessory 8b).

IP54 Door protection - (9b)


E2/6 DC Different keys 038344
E2/6 DC Same keys 065622

Protection for sealable relay - (9c)


E2/6 DC for PR121 058316
E2/6 DC for PR122/PR123 058317

Mechanical interlock - (10)

10.1 Interlock cables for fixed circuit-breakers or fixed parts


E2/6 DC A - horizontal 038329
E2/6 DC B - horizontal 038330
E2/6 DC C - horizontal 038331
E2/6 DC D - horizontal 038332
E2/6 DC A - vertical 038333
E2/6 DC B - vertical 038334
E2/6 DC C - vertical 038335
E2/6 DC D - vertical 038336
Note: request one type of cable for each interlock. To be requested on one of the fixed circuit-breakers or on one of the fixed parts.

10.1 Extended interlock cables for fixed circuit-breakers or fixed parts


E2/6 DC A - horizontal extended cables 066090
E2/6 DC B - horizontal extended cables 066091
E2/6 DC C - horizontal extended cables 066092
E2/6 DC D - horizontal extended cables 066093
E2/6 DC A - vertical extended cables 066094
E2/6 DC B - vertical extended cables 066095
E2/6 DC C - vertical extended cables 066096
E2/6 DC D - vertical extended cables 066097
Note: request one type of cable for each interlock. To be requested on one of the fixed circuit-breakers or on one of the fixed parts.

1sdaR1
3 poles 4 poles

10.3 Interlock for fixed circuit-breaker/moving part of withdrawable circuit-breaker


E1-E2 038366 038366
E3 038367 038367
E4 038368 043466
E6 043466 038369
Note: request an accessory for each fixed circuit-breaker/moving part of withdrawable circuit-breaker.

10.4 Interlock for fixed circuit-breaker/fixed part of withdrawable


E2/6 DC Interlock A / B / D 038364
E2/6 DC Interlock C 038365
Note: request an accessory for each fixed circuit-breaker/moving part of withdrawable circuit-breaker.

10.5 Interlock plate for fixed circuit-breaker


E2/6 DC 038358
Note: only request for fixed circuit-breaker.

86 ABB SACE
1SDC200012D0902
Auxiliary units
1sdaR1

PR010/T test and programming unit


E2/6 DC PR010/T 048964

PR021/K indication unit


E2/6 DC PR021/K 059146

PR120/K indication module


E2/6 DC PR120/K (4 Outputs with independent terminals) 058255
E2/6 DC PR120/K (4 Outputs + 1 Input with one terminal in common) 058256

PR120/LV voltage measurement module for 100VUe250V


E2/6 DC PR120/LV 065223
Note: Each Emax DC circuit-breaker has the PR120/V voltage measurement module included. The PR120/LV is used for 100V<Ue<250V

PR120/D-M (Modbus RTU) communication module


E1/6 PR120/D-M 058254

BT030-USB
E1/6 BT030-USB 058259

ABB SACE 87
1SDC200012D0902
Ordering Examples

Selection of an Emax DC circuit-breaker depends on the plant requirements:


a. Plant requirements:
- Type of network: insulated network
- Rated current (Iu): 800A
- Rated voltage (Ue): 110V
- Short-circuit capacity: Icu= 20kA
- Version: Withdrawable (W)
- Power supply: from the lower terminals
- Protections required of the trip unit: LSI
- Terminals: horizontal rear (HR)

Insulated network (1)


Rated voltage (Ue) 500 750 1000
LOAD - LOAD -

+
L
O
A
- D

LOAD + LOAD + -
+ - +

isolation
protection
PR122/DC
PR123/DC

Icu(2) [kA] [kA] [kA] [kA]


800
1000
B 35 25 25 25
E2 1250
1600
N 1600 50 25 40 25
800
1000
1250
N 60 40 50 35
1600
E3 2000
2500
1600
H 2000 65 (3) 40 50 40
2500
1600
2000
S 75 65 65 50
E4 2500
3200
H 3200 100 65 65 65
3200
E6 H 4000 100 65 65 65
5000
(1)
the possibility of a double earth fault is considered negligible with this type of pole connections. For further information, see QT5: ABB circuit-breakers for direct current applications.
(2)
Icu with L/R = 15ms according to IEC 60946-2 Standard. For Icu with L/R = 5ms and L/R = 30ms, ask ABB.
(3)
85kA only if supplied from below and specifying the following extracode at the ordering stage: 1SDA067148R1. Ics=65kA.

88 ABB SACE
1SDC200012D0902
According to plant requirements, the choice falls on E2B 3p because it has a value of Icu 20kA,
800A rated current and is fitted with PR122/DC.

As for all the withdrawable version circuit-breakers, both the moving part and the fixed part
must be ordered:
Moving part: as the standard solution, ABB SACE supplies the Emax DC moving parts with
voltage sockets located on the lower terminals, according to power supply from these same
terminals.
Fixed part: The same fixed parts with horizontal terminals as the switch-disconnectors are used
for special direct current applications (MS/E) up to 750V DC if they are 3p, up to 1000V DC if
they are 4p.

LOAD -

LOAD + -
+

3D rear view Front view

Emax DC fixed E2B 3pole with horizontal terminals (HR)


1SDA064590R1 E2B 800 PR122/DC-In=800A MP
+
1SDA065223R1 EXTRACODE for voltage 100VUe250V
1SDA059891R1 FIXED PART E2 3p HR
+
1SDA067149R1 EXTRACODE for power supply from the lower terminals

ABB SACE 89
1SDC200012D0902
Ordering Examples

Plant requirements:
- Type of network: with median point earthed
- Rated current (Iu): 2500A
- Rated voltage (Ue): 1000V
- Short-circuit capacity (Icu): 30kA
- Version: Fixed (F)
- Power supply: from the vertical upper terminals

Network with the median point earthed


Rated voltage (Ue) 500 500 750 1000
LOAD -
+
L
O
A
- D
2

2 LOAD +
+ -

PR122/DC - - - -
PR123/DC
type of fault a b c a b c a b c a b c
poles in series affected by the fault 3 2 (U/2) 1 (U/2) 4 2 (U/2) 2 (U/2) 4 2 (U/2) 2 (U/2) 4 2 (U/2) 2 (U/2)
Icu(1) [kA] [kA] [kA] [kA]
800
1000
B 35 35 18 35 35 35 25 25 25 25 25 25
E2 1250
1600
N 1600 50 50 25 50 50 50 40 40 40 25 25 25
800
1000
1250
N 60 60 30 60 60 60 50 50 50 35 35 35
1600
E3 2000
2500
1600
H 2000 65(2) 65 40 65(2) 65(2) 65 (2) 50 50 50 40 40 40
2500
1600
2000
S 75 75 35 75 75 75 65 65 65 50 50 50
E4 2500
3200
H 3200 100 100 50 100 100 100 65 65 65 65 65 65
3200
E6 H 4000 100 100 65 100 100 100 65 65 65 65 65 65
5000
(1)
Icu with L/R = 15ms according to IEC 60946-2 Standard. For Icu with L/R = 5ms and L/R = 30ms, ask ABB.
(2)
85kA only if supplied from below and specifying the following extracode at the ordering stage: 1SDA067148R1. Ics=65kA.

90 ABB SACE
1SDC200012D0902
According to plant requirements, the choice falls on E3N because it has a value of Icu 30kA and
2500A rated current. Since a voltage Ue 750V is required, the version with 4 poles is necessary.

E3N20 PR123/DC 4p power supply from the upper terminals
As the standard solution, ABB SACE supplies fixed direct current circuit-breakers supplied from the
lower terminals. In the case of power supply from the upper terminals, it is necessary to specify the
1SDA058251R1 extracode at the time of ordering.

3D rear view Front view

Emax DC E4S /DC 4p power with upper supply


1SDA064702R1 E3N 2500 PR123/DC-In=2500A 4p F VR
+
1SDA058251R1 Extracode for power supply from the upper terminals

ABB SACE 91
1SDC200012D0902
Ordering Examples

Plant requirements:
- Type of network: with earthed negative polarity
- Rated current (Iu): 1600A
- Rated voltage (Ue): 400V
- Short-circuit capacity (Icu): 65kA also in the case of type b fault
- Version: Withdrawable (W)
- Power supply: from the lower terminals
- Vertical terminals
- Protections: LSIG

Network with earthed negative polarity (1)


Rated voltage (Ue) 500 (2)
LOAD -

+
L
O
A
- D

LOAD + -
+

isolation
protection
PR122/DC
PR123/DC
type of fault(3) a b a b
poles in series affected by the fault 3 2 4 3
Icu(4) [kA] [kA]
800
1000
B 35 20 35 35
E2 1250
1600
N 1600 50 25 50 50
800
1000
1250
N 60 30 60 60
1600
E3 2000
2500
1600
H 2000 65(5) 40 65 (5) 65(5)
2500
1600
2000
S 100 50 100 100
E4 2500
3200
H 3200 100 65 100 100
3200
E6 H 4000 100 65 100 100
5000
(1)
for networks with positive earthed polarity, ask ABB.
(2)
for higher voltages, ask ABB.
(3)
for further information, see QT5: ABB circuit-breakers for direct current applications.
(4)
Icu with L/R = 15ms according to IEC 60946-2 Standard. For Icu with L/R = 5ms and L/R = 30ms, ask ABB.
(5)
85kA only if supplied from below and specifying the following extracode at the ordering stage: 1SDA067148R1. Ics=65kA.

92 ABB SACE
1SDC200012D0902
According to plant requirements, the choice falls on E3H because it has a value of Icu (up to 500V)
65kA and 1600A rated current, 4 poles.

E3H 16 PR123/DC 4p F VR
As the standard solution, ABB SACE supplies fixed direct current circuit-breakers supplied from the
lower terminals. The 4-pole configuration for network with earthed negative polarity requires a special
extracode which makes it possible to have 3 poles in series on the positive polarity (not earthed):
1SDA068806R1.

3D rear view Front view

Emax DC E3H 16 PR123/DC 4p power upper supply with horizontal terminals (HR)
1SDA064703R1 E3H 1600 PR123/DC-In=1600 4p F
+
1SDA068806R1 Extracode for special connection with 3 poles in series on the positive polarity (not earthed)

ABB SACE 93
1SDC200012D0902
Contact us

ABB SACE The data and illustrations are not binding. We reserve

1SDC200012D0202 - 2009.12
the right to modify the contents of this document on the
A division of ABB S.p.A. basis of technical development of the products, without
L.V. Breakers prior notice.

Via Baioni, 35 Copyright 2009 ABB.


24123 Bergamo All rights reserved.

Phone: +39 035 395.111


Fax: +39 035 395.306-433

www.abb.com