0% found this document useful (0 votes)
446 views2 pages

Mbci - Pilot Wire Diff Relay

1. The document is a commissioning standard test format for a MBCI pilot wire differential relay. 2. It includes general data and information about the relay, mechanical checks and visual inspection items, and electrical tests to check pickup values, timing, and functionality. 3. The electrical tests include checking relay burden, pickup values with and without pilots, timing tests, and verifying proper operation with no pickup for a pilot wire short.

Uploaded by

ratheeshkumard
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
446 views2 pages

Mbci - Pilot Wire Diff Relay

1. The document is a commissioning standard test format for a MBCI pilot wire differential relay. 2. It includes general data and information about the relay, mechanical checks and visual inspection items, and electrical tests to check pickup values, timing, and functionality. 3. The electrical tests include checking relay burden, pickup values with and without pilots, timing tests, and verifying proper operation with no pickup for a pilot wire short.

Uploaded by

ratheeshkumard
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 2

Commissioning Service Department

Commissioning Standard Test Formats


Description: MBCI PILOT WIRE DIFF RELAY Record No.:
Bay no.: Drawing ref.: Sheet: 1 of 2
Contractor: Contract no.: Substation No :

1. GENERAL DATA AND INFORMATION:


Circuit Ref. Designation
Panel No. Serial No.
Make Model No.
Dwg & Sh No. Aux. Voltage
Flag Type No. of Contacts
Stabilizing Resistor

2. MECHANICAL CHECKS AND VISUAL INSPECTION:

ITEM DESCRIPTION CHECKED


1 Inspect for any physical damage or defects.
2 Verify connections as per approved drawings.
3 Check that serial no. of relay matching with serial no. of case.
4 Relay CT shorting function checked.
5 Test switch test for correct function
6 Final set value of stabilizing resistor is set

3. ELECTRICAL TESTS:
3.1 RELAY BURDEN:
Condition Relay DC voltage Relay DC current Nominal DC current Remarks

No Operation
Operation

3.2 PICK UP TEST:


(Operation Values Without Pilots) ---Setting: Rpp = 5 x100, Ks = 1, Kt = 20, N = 3.
Calculated Value Actual Operating Value (mA)
Phase Operating Value
(mA) Pick up (mA) Reset (mA)
R -N
YN
BN
RY
Y-B
B-R
NOTE: PICK UP CURRENT SHOUL BE +/- 10% OF CALCULATED VALUE

Tested by: ENG. Witnessed by: ENG.

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats
Description: MBCI PILOT WIRE DIFF RELAY Record No.:
Bay no.: Drawing ref.: Sheet: 2 of 2
Contractor: Contract no.: Substation No :

3.3 PICK UP TEST (CONN.):


(Operation Values Without Pilots) ---Setting: Rpp = 5x100, Ks = 1, Kt = 20, N = 6.
Actual Operating Value (mA)
Phase Operating Value Calculated Value
Pick up (mA) Reset (mA)
RN
YN
BN
NOTE: PICK UP CURRENT SHOULD BE +/- 10% OF CALCULATED VALUE:

3.3 TIMING TEST:


Current = Actual Operating Time at Multiple of KT in milliseconds
Phase
5 x Pick Up 6 14 20 40
Typical
RN
Actual

4. FUNCTIONAL TEST:

Item Description Checked

1 All output contacts resistance measured.


2 All LED operation checked.
3 No Operation for Pilot shorted for secondary injection of 5xIn

Tested by: ENG. Witnessed by: ENG.

Signature & Date: Signature & Date:

You might also like