LT-959 FX-350 Installation and Operation Manual
LT-959 FX-350 Installation and Operation Manual
LT-959 FX-350 Installation and Operation Manual
LT-959 Rev. 6
Installation and Operation Manual June 2017
Table of Contents
1.1 Notice for all FX-350 Series Built-In UDACTs Sold in Canada ...................................... 8
2.0 Introduction 10
3.0 Conventions 12
6.1 Cable and Jumper Connections for Main Board and Adder Modules ........................... 24
6.2 Connectors and Jumpers on the Main Fire Alarm Board ............................................... 26
6.3 OCAC-304 Output Class A Converter Adder Module ................................................... 26
6.4 Polarity Reversal and City Tie Module (Model PR-300) ............................................... 27
6.5 RAX-332 Display Adder Module .................................................................................... 27
3
Table of Contents
10.0 Troubleshooting 42
4
Table of Contents
5
List of Figures
Figure 1 Wallbox Dimensions / Mounting the FX-350 Surface .................................................. 19
Figure 2 Mounting the FX-350 - Flush ......................................................................................... 20
Figure 3 Flush Trim Detail ............................................................................................................ 20
Figure 4 Wallbox Dimensions / Mounting the FX-351/FX-353 Surface /Flush ......................... 21
Figure 5 BBX-1024DS and BBX-1024DSR Installation Instructions and Dimensions ................. 22
Figure 6 Installation of Adder Modules ........................................................................................ 23
Figure 7 Main Fire Alarm Board Cable Connectors and Jumper Locations ................................. 24
Figure 8 Main Board (3 loop model) Cable Connectors and Jumper Locations ........................... 25
Figure 9 OCAC-304 Output Class A Converter Adder Modules .................................................. 26
Figure 10 Polarity Reversal and City Tie Module .......................................................................... 27
Figure 11 Addressable Loop Wiring - Class B or Style 4 ............................................................... 30
Figure 12 Addressable Loop Wiring - Class A or Style 6 ............................................................... 31
Figure 13 Indicating Circuit Class B or Style Y Wiring ................................................................ 34
Figure 14 Indicating Circuit Class A or Style Z Wiring .................................................................. 34
Figure 15 Dialer Wiring ................................................................................................................... 35
Figure 16 Polarity Reversal and City Tie Module Terminal Connection ........................................ 36
Figure 17 Supervision Of Auxiliary Supplies .................................................................................. 37
Figure 18 Main Power Supply Connections ................................................................................... 38
Figure 19 Connecting an FX-350 FACP to a 3G4010 Interface Device ......................................... 39
Figure 20 Connecting an FACP to a 3G4010CF Interface Device outside Canada ....................... 40
Figure 21 LCD Display, LED indicators and control buttons ......................................................... 43
Figure 22 Evacuation and Alert Codes ........................................................................................... 54
6
List of Tables
Table 1 FX-350 Series Comparison Chart .................................................................................. 14
Table 2 Settings permitted in CAN/ULCS527 ............................................................................. 30
Table 3 Loop Wiring Table .......................................................................................................... 31
Table 4 Maximum Wiring Distances ........................................................................................... 32
Table 5 Input Types .................................................................................................................... 50
Table 6 Output Types ................................................................................................................. 53
Table 7 Ademco Contact-ID - FX-350 Series Event Codes ........................................................ 60
Table 8 Security Industries Association SIA-DCS - FX-350 Series Event Codes ....................... 61
Table 9 FX-350 Series Specifications ......................................................................................... 62
Table 10 FX-350 System Modules and Annunciators ................................................................... 63
Table 11 FX-350 Batteries ............................................................................................................ 65
7
1.0 Industry Canada and FCC Notice
1.1 Notice for all FX-350 Series Built-In UDACTs Sold in Canada
Mircom's FX-350 SERIES BUILT-IN UDACT Communicator described in this manual is listed
by Underwriters Laboratories Canada (ULC) for use in slave application in conjunction with a
Listed Fire Alarm Control Panel under Standard ULC-S527-11 (Standard for Control Units for
Fire Alarm Systems) and CAN/ULC-S561-13 (Standard for Installation and Services for Fire
Signal Receiving Centres and Systems). These Communicators should be installed in
accordance with this manual; the Canadian / Provincial / Local Electrical Code; and/or the
local Authority Having Jurisdiction (AHJ).
! Attention: Users should not attempt to make such connections themselves, but
should contact the appropriate electric inspection authority, or
electrician, as appropriate
1.1.2 Notice for all FX-350 Series Built-in UDACTs Sold in the U.S.A.
i Notes: The Ringer Equivalence Number (REN) assigned to each terminal device
provides an indication of the maximum number of terminals allowed to be
connected to a telephone interface. The termination on an interface may consist
of any combination of devices subject only to the requirement that the sum of the
Ringer Equivalence Numbers of all the devices does not exceed 5.
Mircom's FX-350 SERIES BUILT-IN UDACT Digital Communicator described in this manual
is listed by Underwriters Laboratories Inc. (ULI) for use in slave application in conjunction with
a Listed Fire Alarm Control Panel under Standard 864 (Control Units for Fire Protective
Signalling Systems). These Communicators comply with the National Fire Protection
Association (NFPA) performance requirements for UDACTs and should be installed in
accordance with NFPA 72 Chapter 4 (Supervising Station Fire Alarm System). These
Communicators should be installed in accordance with this manual; the National Electrical
Code (NFPA 70); and/or the local Authority Having Jurisdiction (AHJ).
8
Industry Canada and FCC Notice
must be provided to the telephone company. This equipment is capable of seizing the line.
This capability is provided in the hardware.
Telephone Company Procedures: The goal of the telephone company is to provide you with
the best service it can. In order to do this, it may occasionally be necessary for them to make
changes in their equipment, operations or procedures. If these changes might affect your
service or the operation of your equipment, the telephone company will give you notice, in
writing, to allow you to make any changes necessary to maintain uninterrupted service.
If Problems Arise: If any of your telephone equipment is not operating properly, you should
immediately remove it from your telephone line, as it may cause harm to the telephone
network. If the telephone company notes a problem, they may temporarily discontinue service.
When practical, they will notify you in advance of this disconnection. If advance notice is not
feasible, you will be notified as soon as possible. When you are notified, you will be given the
opportunity to correct the problem and informed of your right to file a complaint with the FCC.
Contact your telephone company if you have any questions about your phone line. In the
event repairs are ever needed on the Communicator, they should be performed by Mircom
Technologies Ltd. or an authorized representative of Mircom Technologies Ltd. For information
contact Mircom Technologies Ltd. at the address and phone numbers shown on the back page
of this document.
9
2.0 Introduction
Mircoms FX-350 Series Analog/Addressable Fire Alarm Control Panel provides a loop for
60,126 or three loops for 378 input and output devices, four supervised Class B or A (Style Y
or Z) indicating circuits, a full range of auxiliary power supplies, and extensive common control
features via its integrated LCD display and push button console. Many of its features are fully
configurable utilizing the built-in configuration capability via the front panel display and
switches. The panels are available with or without an optional, integrated dialer/modem
(except the FX-353 version which always includes the dialer/modem), and is available (FX-
351 and FX-353 - in a larger enclosure) with an internal LED display for up to 64 points (32
standard). Optional modules include Polarity Reversal and City Tie, RAX-332 LED Display
Adder, and Class A Converter for indicating circuits. Semi-flush or surface mountable
enclosures can be used for retrofits and on new installations. This manual covers the following
panels:
i Note: Installation of the FX-350 Series Fire Alarm Control panel should be in
accordance with Canadian Electrical Code Part 1, ULC-S524 installation of Fire
Alarm System, National Electrical Code NFPA 70 and NFPA 72. Final
acceptance subject to the Local Authority Having Jurisdiction (AHJ).
2.1 Features
The FX-350 panels support a loop of 60 or 126 analog devices and up to 3 loops of 378
analog devices, including thermal, ion, photo detectors, and contact input and output
devices. Drift compensation and Auto Test features are provided for analog devices.
Four Power Limited Class B (Style Y) indicating circuits. Each indicating circuit may be
configured as Class A (Style Z) using an output Class A converter adder module. Each
indicating circuit may be configured as silenceable signal, non-silenceable signal,
silenceable strobes, non-silenceable strobes, or relay output. The audible signal may be
Steady, Temporal Code, California Code, or March Time. The system provides the
necessary protocols to sync strobes from major manufacturers.
Two-stage, alarm verification, and waterflow retard operations available.
Configurable Signal Silence Inhibit, Auto Signal Silence, Two-Stage Operation, and
One-Man Walk Test. For Canadian installations, disable Auto Signal Silence.
Subsequent Alarm, Supervisory, and Trouble operation.
10
Introduction
11
3.0 Conventions
3.1 Circuits
Refers to a physical electrical interface for the analog loop, indicating signals or relays, and
common alarm, supervisory, and trouble relay outputs.
3.2 Zone/Group
Is a logical concept for a Fire Alarm Protected Area, and will consist of at least one Circuit.
Groups are used extensively in the FX-350 to facilitate annunciation of multiple input and
output points on the 32 (up to 64) LED display and to facilitate bypassing of inputs and
outputs.
The FX-350 provides an LCD display to annunciate the status of the system and connected
devices. The FX-351 and FX-353 also provides up to 64 LED display points on the panel front
in addition to the LCD display. Display points may be assigned to LEDs during configuration to
groups of inputs or outputs. There are two LEDs for every display point: one single color
(amber) and one dual color (red/amber).
The analog loop can be connected in Class B (Style Y) or Class A (Style D) configurations.
Changing the indicating circuits to Class A requires an OCAC-304 adder board which will
convert four indicating zones from Class B (Style Y) circuits to Class A (Style Z). This is done
without reducing the number of circuits.
i Note: The Model FX-350-60-R and FX-350-60DR panels DO NOT recognize any
devices with addresses higher than 60.
12
4.0 System Components
4.1 Panel Models
SYSTEM NORMAL
AC ON AC ON
1 2 3 X 1 2 3 X
ABC DE F ABC DE F
COMMON ALARM COMMON ALARM
ABC DEF
COMMON ALARM
SYSTEM SIGNAL SYSTEM SIGNAL
RESET SILENCE RESET SILENCE
COMMON S UP V
4 5 6 M
GHI JKL MNO
FIRE ALM/SUP/TBL/BLDG FIRE ALM/SUP/TBL/BLDG
COMMON DRILL AUDIBLE SIL DRILL AUDIBLE SIL
TROUBLE
7 8 9 ?
PRS TUV WXY AUTOMATIC ALARM LAM P AUTOMATIC ALARM LAM P
CP U FAULT TEST SIGNAL CANCEL TEST
SIGNAL CANCEL
GROUND
FAULT
* 0 # GENERAL GENERAL
SPARE SPARE
QZ ALARM ALARM
S Y S TE M S IGNAL
RE S E T S ILE NCE
ZO N E -1 ZO N E -1 ZO N E -1 ZO N E -1
FIRE ALM/SUP/TBL/BLDG
DRILL AUDIBLE SIL ZO N E -1 ZO N E -1 ZO N E -1 ZO N E -1
ZO N E -1 ZO N E -1 ZO N E -1 ZO N E -1
ZO N E -1 ZO N E -1 ZO N E -1 ZO N E -1
GE NE RAL
S P ARE ZO N E - 1 ZO N E - 1 ZO N E - 1 ZO N E - 1
ALARM
ZO N E - 1 ZO N E - 1 ZO N E - 1 ZO N E - 1
ZO N E - 1 ZO N E - 1 ZO N E - 1 ZO N E - 1
ZO N E - 1 ZO N E - 1 ZO N E - 1 ZO N E - 1
FX-350 SERIES
Fire Alarm Control Panel
13
System Components
Some models may not be available in all markets. Verify with your local distributor.
14
System Components
Model Description
- SIG1 OUT+
- SIG1 RET+
BLK RED
- SIG2 OUT+
OCAC-304 Output Class A converter module (four
- SIG2 RET+
BLK RED
circuits)
- SIG3 OUT+
- SIG3 RET+
BLK RED
- SIG4 OUT+
- SIG4 RET+
BLK RED
Model Description
#6-32 screws
CITY
TIE
REVER SAL REVER SAL
POLAR ITY POLAR ITY
+ | -
P1 P2
ALAR M
Model Description
Remote Annunciator module, LCD display,
RAM-300LCDR
white painted box
SYSTEM NORMAL
18:01 MON 2003-04-05
SIGNAL
SILENCE 1 2 3 ENTER
ABC DEF
FIRE
DRILL 4 5 6 MENU
GHI JKL MNO
BUZZER
Remote Annunciator Module, LCD display,
RAM-300LCDR
SILENCE 7 8 9 CANCEL
PRS TUV WXY
LAMP
TEST * 0
QZ
# INFO
FA-300 SERIES
Remote Annunciator
15
System Components
Model Description
Smart Relay Module (12 relays) with white
SRM-312W
enclosure
FA-300 SERIES
REMOTE RELAY
Model Description
BUZZER
SILENCE
SIGNAL
SILENCE
RAM-216 16 Zone ancillary annunciator
SWITCH
ENABLE
LAMP SYSTEM
TEST RESET
FIRE ALARM
ANNUNCIATOR
16
System Components
RAX-332 32 Zone Internal Display Adder (for FX-351 and FX-353 only)
17
System Components
MIX-100X (Kit)
Isolator c/w Mounting Base 100XH (Isolator)
100XB (Base)
* Unit employs an integral heat sensor; however it must not be used as a regular heat detector. Refer to the
product data sheet for detailed functionality, operation and application.
Manual configuration for the MIX-3200 is NOT PERMITTED. This device must be configured via the AUTO
CONFIG.
18
5.0 Mechanical Installation
5.1 Installing the Enclosures
Install the FX-350 Series Fire Alarm Panel enclosure as shown below. Mount the enclosure
using the four mounting holes and the screws provided.
Mounting 11"
Hole
1.5"
Mounting
Hole
14.5"
20"
Mounting Hole
4.5"
14.5"
19
Mechanical Installation
11"
1.5"
17"
4 Mounting
Holes for
14.5" Surface
Mounting
22.5"
3.5" is the maximum depth
4" for semi-flush mounting
using the flush trim ring
5"
4. 3.5"
14.5" 1"
5.2 below shows a cross-section of the semi-flush mounted backbox and the trim ring. Make
sure to allow a minimum depth of 1 above the wall surface for proper door opening.
TRIM RING
WALL MIN 1
WOOD OR
METAL STUD
BACKBOX
i Note: See 5.2 for Flush Trim Details for mounting the trim ring.
21
Mechanical Installation
The BBX-1024DS and BBX-1024DSR are suitable for flush or surface mounting, and have a
built-in trim ring.
12.0 "
14.5 "
4.2 "
23.5 "
26.0 "
2.1 "
2.0 "
9.5 "
22
6.0 Installing Adder Modules
The FX-350 Series Fire Alarm panels come pre-assembled with all components and boards
except for Adder Modules. Module installation locations are shown below. Refer to Figure 6
and Figure 7 for Jumper or DIP Switch settings and see Chapter 8.0 Field Wiring on page 30
for wiring specifications.
+
T
B
R
-
Loop
A
T
+
RES
R
-
T
CO
SYSTEM NORMAL
R
LIN E2
T
JW1
+
AC ON
1 2 3
RS -485
X
CLASS- A converter
-
ABC D EF
COMMON ALARM
JW2 board for indicating
S
COMMON SUPV 4 5 6 M
GH I JKL MN O circuits OCAC-304
NO
AU X. R ELAY
7 8 9 ?
+
PR S TU V WXY
- SIG1 OUT+
- SIG1 RE T+
RED
BLK
NC
CPU FAULT
SI G 1
+ -
* 0 #
NO
GROUND FAULT
QZ
- SIG2 OUT+
- SIG2 RET+
RED
BLK
RELA Y
JW6
ALARM
S IG 2
C
ALM/SUP/TBL/BLDG
-
AUDIBLE SIL
SYST EM SIGNAL
+
RESET SIL ENCE
- SIG3 OUT+
- SIG3 RE T+
RED
tie module PR -300 .
BLK
SI G 3
NO
S UPERVIS O RY
F IRE ALM/SUP/TBL/
C
- SIG4 OUT+
-S IG4 RET+
RED
BLK
DRIL L
with two screws provided JW5
SI G 4
NC
AUX
C
+ -
GENERAL
AL ARM SPARE
NC
SU PPLY
4-WI RE
SUPPLY
POWER
RTI UNFILTERED
JW 7 P12 PO RT FW R24VDC
TO PR-300 MO DULE
JW 9 TRB TRL CO M- CO M+
Transformer
P8 P4 P3 P2
TO RAX-332
Power supply
board
P2
P3
P1
AC wiring terminal
+ - + -
BATTERY BATTERY
23
Installing Adder Modules
6.1 Cable and Jumper Connections for Main Board and Adder
Modules
RS-232C PORT
For PC programming
JW3
For PC programming use UIMA
Interface module not UL-864 or
ULC-527 listed. Please refer to JW4 Addressable
+
T
B
Loop
R
L I N E1
Telephone line #1
-
L o op
A
T
+
RES
R
-
T
CO
R
LI N E 2
RES
OCT 21 , 2005 02 : 41 AM
R
JW1
+
RS-485 for AC ON
R S- 4 8 5
1 2 3 X
-
JW2
S
COMMON SUPV
4 5 6 M
GH I JKL MN O
NO
A U X . R EL A Y
7 8 9 ?
+
PR S TU V WXY
RE D
BL K
NC
CPU FAULT
SIG 1
-
* 0 #
NO
GROUND FAULT
+
JW6
QZ
R ED
B LK
R E LA Y
AL ARM
SI G 2
Alarm Relay
C
-
NC
SYST EM SIGNAL
+
RESET SIL ENCE
RE D
BL K
SIG 3
NO
S U PE R V I S O R Y
-
R E LA Y
F IRE ALM/SUP/TBL/BLDG
C
AUDIBLE SIL
Supervisory Relay
RE D
BL K
DRIL L
SI G 4
JW5
NC
-
AUTOMATIC ALARM L AMP
SIGNAL CANCEL
NO
T EST
+ Auxiliary
S U P P LY
T R O U B LE
R E LA Y
A UX
C
Supply
-
S UP P L Y
4- W I R E
Resettable
S U P PL Y
POW ER
Auxiliary
JW7 P12
RTI
PO RT
UNFILTERED
FW R 24 VDC Supply
JW9 TRB TRL CO M - CO M +
P8 P4 P3 P2
Figure 7 Main Fire Alarm Board Cable Connectors and Jumper Locations
24
Installing Adder Modules
Figure 8 below shows the main board for the 3 loop addressable model. It is the same as the
single loop model with two additional addressable loops.
+
T
D ocument LT-929 for details
CO
B
R
L I N E1
Telephone line #1
-
L o op
A
T
+
RES
R
-
T
CO
R
LI N E 2
RES
OCT 21 , 2005 02 : 41 AM
R
JW1
+
RS-485 for AC ON
R S- 4 8 5
1 2 3 X
-
JW2
S
COMMON SUPV
4 5 6 M
GHI JKL MNO
NO
A U X . R EL A Y
7 8 9 ?
+
PR S TU V WXY
RED
BL K
NC
SIG 1
CPU FAULT
-
* 0 #
NO
GROUND FAULT
+
QZ
JW6
R ED
B LK
R E LA Y
AL ARM
SI G 2
Alarm Relay
C
-
NC
SYST EM SIGNAL
+
RESET SIL ENCE
RED
BL K
SIG 3
NO
S U PE R V I S O R Y
-
R E LA Y
ALM/SUP/TBL/BLDG
C
F IRE
Supervisory Relay
RED
AUDIBLE SIL
BL K
DRIL L
SI G 4
JW5
NC
-
AUTOMATIC ALARM L AMP
NO
+
Auxiliary
S U P P LY
T R O U B LE
R E LA Y
A UX
C
Supply
-
Trouble Relay GENERAL
AL ARM
SPARE
+
NC
S UP P L Y
4- W I R E
Resettable
S UP PLY
POWER
-
Auxiliary
JW7 P 12
RTI
PO RT
UNFILTERED
FW R 24 VDC Supply
JW9 TRB TRL CO M - CO M +
P8 P4 P3 P2
Figure 8 Main Board (3 loop model) Cable Connectors and Jumper Locations
25
Installing Adder Modules
P8 Cable from P1 of the PR-300 Polarity Reversal and City Tie Module connects here.
Otherwise not used.
P4 Cable from connector P1 of the RAX-332 Display Adder Module connects here.
Otherwise not used.
JW1 On the Main Fire Alarm Module, this jumper is not used, open.
JW2 Remove this jumper if a remote annunciator is used.
JW3 Not used, open.
JW4 Not used, open.
JW5 Normally open. Place jumper here and power down (AC and batteries) and power back
to restore Master Passcode. After reset, remove jumper and leave normally open.
JW6 Normally open to BLOCK remote configuration via modem. Place jumper here to
ALLOW for remote configuration.
JW7 On the Main Fire Alarm Module, this jumper must be removed if a PR-300 Polarity
Reversal and City Tie Module is installed.
JW8 Not used, open.
JW9 Not used, open.
JW10 Not used, open.
JW11 Not used, open.
JW12 Not used, open.
Mounting hole
for #6-32 screw
Wire to Main Board
OCAC-304
- SIG2 OUT+ - SIG1 OUT+
Mounting hole
for #6-32 screw
Indicating circuits must be wired from the OCAC-304 to the main Fire Alarm board. For
example indicating circuit 1 positive (red wire) and negative (black wire) is wired from the
Class A Converter Module to the positive and negative terminals of Indicating circuit 1 on the
Main Fire Alarm board.
26
Installing Adder Modules
The actual indicating zone is wired from the SIGNAL OUT positive and negative to the
signaling devices and then wired back to the SIGNAL RET positive and negative.
Mount the PR-300 on the left side panel of the backbox with the two screws provided, refer to
Figure 10.
+ | -
#6-32 screws
CITY
TIE
REVER SAL REVER SAL
POLAR ITY POLAR ITY
+ | -
P1 P2
ALAR M
Mounting hole for
#6-32 screws
+ | -
SU PV
JW4
The Alarm Transmit signal to the PR-300 can be programmed to turn OFF when signal silence
is active. This allows the City Tie Box to be manually reset. On subsequent alarms the
silenceable signals will resound and the City Tie Box will be retriggered.
The Trouble Transmit signal to the PR-300 can be programmed to delay AC power fail 0, 1, 2,
or 3 hours if this is the only system trouble.
The RAX-332 Display Adder Module is used only with the FX-351 and FX-353 Fire Alarm
Panels. No jumpers or other physical configuration steps are required to install this second
RAX-332 Display Adder Module. Remove the blank cover plate from the front door and install
the RAX-332 with the clear cover in the opening with the hardware provided. Disconnect main
and standby power and connect the cable of the second RAX-332 into the open, remaining
header of the existing RAX-332. The additional LEDs will be available for configuration as
LEDs 33 to 64, when the system power is restored.
27
7.0 Circuits and Devices
7.1 Addressable/Analog Devices
The FX-350 supports up to 3 loops of addressable/analog devices. The device loop can be
used to connect up to 60, 126 or 378 analog devices and addressable input or output modules
on an unshielded twisted pair (UTP). The devices must be compatible with the Mircom device
protocol.
The loop interface software continuously supervises the devices on its loop against those
found during configuration for the following conditions:
device missing
unconfigured device responding
two or more devices responding to the same address
wrong device type
A communication or addressing error on a device is reported as a trouble on the associated
zone LED if configured.
The addressable loop can be configured for class A or B operation. "T-tapping" is allowed
(Refer to device installation documentation for details).
Devices on the loop have an optional LED which normally flashes when the device is polled
and goes ON steady when the device is active (alarm for an input device or active for an
output device). The flashing of the LED on polling for sensors can be suppressed during
configuration. For input or output modules, the LED always flashes when polling. The software
limits the maximum number of the devices which can have their LED turned ON when active to
fifteen (15).
Certain devices are designed to support an optional external LED, which operates when the
LED on the device is activated. Remote/external LEDs must NOT be used on this system. The
panel can provide up to 350mA of current to the devices on the loop. A maximum line loss of 5
volts is permitted, so the loop distance, wire size, and maximum number of devices are limited
by this constraint.
The devices should be installed using unshielded twisted pair (UTP). The total line drop on the
loop must not exceed 5 volts at the last device. The calculations required to determine the
maximum permissible loop wiring distance with various combinations of devices is relatively
complicated, and when isolators are used, includes a consideration of device inrush currents
which must not exceed 20mA for a single isolator. In no case should more that twenty devices
be connected to a single isolator. To simplify the calculation process, please utilize the loop
calculator program located on the Mircom website at http:/www.mircom.com in order to
determine maximum loop lengths, number of devices, and wire sizes etc.
It is also important to note that the device LEDs present a significant extra load on the loop
which must be considered in calculating permissible loop lengths, battery capacities, etc.
Please refer to the device Installation Instructions and other documentation provided with the
addressable devices, bases, and isolators for further information. The system will
automatically limit the maximum number of device LEDs which can be illuminated to
15.
28
Circuits and Devices
The system supports Mircom MIX-3000 Series photo, ion, multi-sensor and thermal (heat)
type analog detectors, as well as contact input and output devices. The detectors may be
configured as non-verified or verified alarm inputs. To determine an alarm condition, the
system polls the analog device and compares the analog value against stored thresholds for
pre-alarm and alarm conditions.
A range of thresholds is provided for each type of analog device (except for contact devices),
corresponding to the agency approved range of threshold for a particular device type. Each
device can be individually configured to a value in the range of threshold for day time and
one for the night time or after hours operation; i.e. a device may be configured to a low
sensitivity for day time and high sensitivity at night time. The day time threshold will be used
unless the after hours operation is active.
Contact output modules on the addressable/analog device loop may be configured as any of
the following output types:
signals
strobes
relay outputs
Analog devices may be installed with relay or sounder bases. The outputs of these bases are
activated when the device active LED turns ON steady in response to an alarm. The command
to activate the output is separate from the command that activates the LED and they are not
subject to the same restrictions as the LED. Output modules configured as signals are not
stroked by software at the current signal rate. When the system commands them to be either
in alert or in evacuation, the panel will simply activate them continuously. It is possible to
provide stroked operation by connecting the signal power to a conventional signal output
which is stroking at the correct rate when the device is active. Depending on the device, the
system can detect open and short troubles and report it as an output circuit trouble.
29
8.0 Field Wiring
Table 2 Settings permitted in CAN/ULCS527
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the
requirements in CAN/ULCS527, Standard for Control Units for Fire Alarm Systems, certain programming
features or options must be limited to specific values or not used at all as indicated below.
Wire devices to the addressable loop as shown in Figure 11 for Class B (Style 4) or Figure 12
for Class A (Style 6). Refer to Table 3 for loop wire gauges. Wire devices to addressable
loops 2 and 3, if available, in the same manner.
+
CLASS B
WIRING
B
-
Loop
A
+
-
ION SMOKE
DETECTOR
OUTPUT MODULE
PHOTO SMOKE
DETECTOR
30
Field Wiring
To limit the number of addressable devices compromised by a short on the addressable loop,
isolators (MIX-100X, 100XH, or 100XB) may be used to isolate the affect of the short circuit. If
the impact of a short circuit must be limited to only one device, an isolating base must be used
for each detector. A maximum of twenty devices can be connected between isolators, or
between the panel and the first isolator, as long as the maximum in-rush current for the
devices on one segment of the loop does not exceed 20 mA. Refer to the installation
instructions for addressable devices for additional details.
+
CLASS A
B
WIRING
-
Loop
A
+
-
ION SMOKE
DETECTOR
OUTPUT MODULE
PHOTO SMOKE
DETECTOR
When there is a short circuit on the Class A loop with isolators installed, the isolators isolate
the shorted fault, the panel detects it as an open loop and generates an open loop trouble.
31
Field Wiring
When a Class A loop is opened there may be a few missing devices reported by the panel
which will be restored once the panel has established the Class A connection.
i Note: When there is an "Open loop trouble" look for both open and shorts on the loop.
As a guide line the isolators which are activated in response to a short will have
their LED ON; look for the short between the two isolators with their LEDs ON.
Powered output circuits can be configured as signal, strobe or relay outputs. Powered output
circuits are supervised while they are not active for both open circuits and shorts. The circuit
will not actually be activated if there is a short trouble on the circuit. It will be activated if an
open trouble is indicated. Since open circuit supervision does not operate while the circuit is in
alarm, if the circuit was in trouble before it was activated, it will still indicate trouble while
active. The trouble condition will be re-evaluated when supervision resumes.
Output circuits configured as strobes can have sync protocol for synchronization if configured.
Certain strobe and strobe/horns models of the following manufacturers are supported.
If the strobe is configured as silenceable strobe both the horn and the strobe are silenced
(stopped) by pressing the 'signal silence' button
The FX-350 Series Addressable Fire Alarm Panel supports Class B (Style Y) and Class A
(Style Z) wiring for its indicating circuits. Each circuit is supervised by a 3.9K End-of-Line
resistor. Each indicating circuit provides up to 1.7 Amperes, total 5 Amperes of current
maximum if no auxiliary power is used. Wire indicating circuits as in Figure 11 for Class B
(Style Y) or as in Figure 12 for Class A (Style Z).
Amperes ft m ft m ft m ft m Ohms
32
Field Wiring
INDICATING INDICATING
CIRCUIT #1 CIRCUIT - 1
INDICATING
STYLE Y
CIRCUIT #2
WIRING
INDICATING
CIRCUIT - 2
33
Field Wiring
STYLE Z
FIRE PANEL MAIN BOARD WIRING
INDICATING
CIRCUIT 1
OUT+
BLK RED
SIG 1
- SIG1
CIRCUIT #1
-
OUT+
BLK RED
+
SIG 2
INDICATING
CIRCUIT #2
- SIG2
-
STYLE Z
WIRING
2 MORE INDICATING
CIRCUITS NOT SHOWN INDICATING
CIRCUIT 2
OCAC-304 CLASS A
CONVERTER MODULE
BELL
If you have Fire Alarm Panel model FX-350-60-DR, FX-350-126-DR, FX-350-378-LDR, FX-
351-LDW or FX-353-DR, there is a dialer on board and terminals marked Line 1 and Line 2
must be wired as shown in Figure 15 below. Terminals are located in the top left hand corner of
34
Field Wiring
the main fire alarm board, from the top down. Refer to Figure 6 and Figure 7 for terminal
locations.
RJ31X
GREEN
T
1 4
TIP
CO
RED 2 3
R
LINE-1
BROWN
RING
T
RES
7 6
GREY 8 5 Public switch
R
Telephone company
wiring
TIP
T
CO
RING
R
Refer to Chapter 13.0 Dialer Operation on page 58 and Chapter 15.0 Appendix B:
Reporting on page 60 for more information regarding the built-in dialer.
35
Field Wiring
Wire the PR-300 Polarity Reversal and City Tie Module (if used) as shown in Figure 16 below.
Power Limited cable type FPL, FPLR or FPLP must be used. For USA installation, the installer
must use Atlantic Scientific (Tel: 407-725-8000), Model #24544 Protective Device, or
similar UL-Listed QVRG secondary protector, as shown. For use in Canada, the Protective
Device is not required but still recommended.
PR-300
+ PROTECTOR
1 1 +
CITY TIE LOCAL ENERGY USE A SHORTING WIRE
RATED - 24VDC FILTERED WHEN THE CITY TIE IS NOT
TRIP COIL - 14 Ohms, 210mA, 2 2 - USED
5mV RIPPLE
-
UNPROTECTED
S S
PROTECTED
NOT POWER LIMITED
+
POLARITY REVERSAL ALARM
1 1 +
24VDC OPEN
12VDC AT 3.5mA
8mA MAX. SHORT
2 2 -
- POWER LIMITED S S CONFORMS TO NEMA STANDARD
+ SB3-1969 INTENDED FOR
CONNECTION TO POLARITY
POLARITY REVERSAL SUPV .
REVERSAL CIRCUIT OF A REMOTE
24VDC OPEN
STATION RECEIVING UNIT HAVING
12VDC AT 3.5mA DIN RAIL CONNECTION
8mA MAX. SHORT COMPATIBLE RATINGS
TO EARTH GROUND
- POWER LIMITED PROTECTOR
1 1 +
2 2
-
UNPROTECTED
S S
PROTECTED
NOTES:
1. Plug PR-300 ribbon cable P1 into connector P8 of the Main Fire Alarm board.
2. Cut Jumper JW1 on the PR-300 Polarity Reversal and City Tie Module in order to
transmit a trouble condition from the Polarity Reversal Alarm terminals to the
monitoring station.
3. Cut Jumper JW2 on the PR-300 Polarity Reversal and City Tie Module in order to
transmit a trouble condition from the Polarity Reversal Supervisory terminals to the
monitoring station.
4. Remove jumper plug from JW7 on the Main Fire Alarm board.
5. For USA installation, the installer must use an Atlantic Scientific (Tel. 407-725-8000),
Model #24544 Protective Device or similar UL-Listed QVRG secondary protector.
6. The Polarity Reversal interface is Power Limited and must use power limited cable
type FPL, FPLR or FPLP from the PR-300 to the Protectors.
36
Field Wiring
MINI MONITOR
MODULE
Red Violet
MIX-101P
White
+
Red
B
+ -
Black
Loop
A
Black
37
Field Wiring
The power supply is located directly behind and below the main board. The ratings are:
Electrical Input rating 120 VAC, 60Hz, 1.73A / 240VAC, 50Hz, 0.864A
Battery fuse on Main module 10A, slow blow micro fuse (not replaceable)
! Caution: The main AC branch circuit connection for the Fire Alarm Control Unit must
provide a dedicated continuous power without any disconnect devices. Use
#12 AWG wire with 600-volt insulation and proper over-current circuit
protection that complies with the local codes. Refer to 16.0 Appendix C:
Specifications on page 62 for specifications.
i Note: Ensure that the AC supply is disconnected before wiring the power to the panel.
Wire the AC power to the AC wiring terminals as shown in Figure 18 using the
proper wire gauge. Fire alarm systems must be installed in compliance with local
codes and standards and with the Authority Having Jurisdiction (AHJ)
TRANSFORMER
POWER SUPPLY
RTI UNFILTERED
JW7 RIBBON CABLE PORT FWR 24VDC
TO PR-300 MODULE
P3 P2 TRB TRL COM- COM+
POWER P5
CONNECTOR P6
Yellow
240VAC 50Hz
Red
120VAC 60Hz
BATTERY SEC TX Black
- N
P3 +
Green
P1
P2
P4
RED BLACK
RED
+ - + -
AC WIRING TERMINALS
BATTERY BATTERY
i Note: The FX-350 panel is capable of being wired for 120 VAC or 240 VAC 50/60 Hz
as shown above. A good ground connection to the Ground" terminal is
essential to electrical safety, ensure proper operation, and specified noise
immunity.
38
Field Wiring
A typical connection is shown in Figure 19. The PCS-100 Passive Communications Interface
Board (sold separately) is required.
Telephone
To GSM/GPRS
Line A
Connection
T1
R1
ALARM NO Z1
RELAY C
SPV NO Z2
RELAY C
FX-350 TRBL
RELAY
NO
C
Z3
3G4010 Router
COM Computer
SG-Systems
Console 2.1
JW1
+ AUX SUPPLY
GND
24V
POWER
- PCS-100
PGM4
NC COM NO
TBL RELAY
EOL SUR-GARD
(-) Printer
DC IN SYSTEM IV
(+)
Internal IP : X.X.X.X
Addressable module External IP : X.X.X.X
configured as 3G4010 Default Gateway : X.X.X.X
radio trouble Sub-Net Mask:X.X.X.X
Port #: YYYY (UDP)
3G4010 TRBL
Typical Installation in Canada
- All units must be installed in the same room
- All extended wiring must be in metallic conduit
- Wiring between FACP and 3G4010:18 m max.
- Contact DSC to reprogram the zone inputs to match
the FACP as shown in this diagram
i Note: The DSC interface device 3G4010 is required if the installation requires ULC
S559 certification. The DSC interface device 3G4010CF is required if the
installation requires UL864 9th edition certification.
39
Field Wiring
A typical connection is shown in Figure 20. The 3G4010CF is powered separately from the
PCS-100 and requires 2 DSC RM-2 relays (sold separately). The PCS-100 Passive
Communications Interface Board (sold separately) is also required.
FX-350 - 3G4010CF Connection - Typical Diagram
Telephone
Line A
Connection
To GSM/GPRS
Line 1 Line 2
C.O. C.O.
T1
R1
ALARM NO Z1 Internet
RELAY C
SPV NO Z2
3G4010CF
RELAY C
FX-350 TRBL NO Z3
RELAY C
PS4086
COM Router
AC IN
JW1
Computer
- PCS-100 SG-Systems
PGM4
+
NC COM NO
TBL RELAY
Console 2.1
DC IN
EOL -
Printer SUR-GARD
SYSTEM IV
Transformer Battery Internal IP : X.X.X.X
Addressable
External IP : X.X.X.X
module configured Default Gateway : X.X.X.X
as 3G4010CF radio Sub-Net Mask:X.X.X.X
3G4010CF trouble
TRBL - - Port #: YYYY (UDP)
+
+
DSC DSC
RM-2 RM-2
Relay Relay
NC COM NO NC COM NO
EOL EOL
3G4010CF 3G4010CF
Typical Installation outside Canada
TRBL TRBL
Addressable module
configured as AC - All units must be installed in the same room
failure trouble - All extended wiring must be in metallic conduit
Addressable module - Wiring between FACP and 3G4010CF: 20 feet max.
configured as low - Contact DSC to reprogram the zone inputs to match the
battery trouble FACP as shown in this diagram
- Use 2 DSC RM-2 Relays (sold separately) to supervise
both AC failure trouble and low battery trouble
- Install the DSC RM-2 Relays inside the 3G4010CF
enclosure above the PS4086
i Note: The DSC interface device 3G4010 is required if the installation requires ULC
S559 certification. The DSC interface device 3G4010CF is required if the
installation requires UL864 9th edition certification.
40
9.0 System Checkout
9.1 Before turning the power ON
To prevent sparking, do not connect the batteries. Connect the batteries after powering the
system from the main AC supply.
1. Check that all adder modules are installed in the proper location with the proper
connections.
2. Check all field (external) wiring for opens, shorts, and ground.
3. Check that all interconnection cables are secure, and that all connectors are plugged in
properly.
4. Check all jumpers and switches for proper setting.
5. Check the AC power wiring for proper connection.
6. Check that the chassis is connected to earth ground (cold water pipe).
7. Make sure to close the front cover plate before powering the system from main AC
supply.
The best way to set up a panel for the first time is to avoid connecting any field wiring at first.
To begin set up, power up the panel with end of line resistors connected where appropriate,
then connect the battery. The panel will show System Restart Active. Press System Reset
button to reset the panel. If the panel is free of trouble, connect one circuit at a time, checking
for troubles each time. If a trouble occurs at any point during the set-up, correct the fault, then
continue connecting the field wiring.
1. Power up the panel. The "AC-ON" green LED and the Common Trouble LED should
illuminate, and the buzzer should sound. Press the System Reset button. Since the
batteries are not connected, the trouble buzzer should sound intermittently and the
common trouble LED should flash.
2. Connect the batteries while observing correct polarity: the red wire is positive (+) and
black wire is negative(-). All indicators should be OFF except for normal power "AC ON"
green LED.
3. Configure the Fire Alarm Control Panel as described in the System Configuration
section.
41
10.0 Troubleshooting
Symptoms Possible Cause
Circuit Trouble Normally when a circuit trouble occurs, its designated trouble indicator will be illuminated, as
well as the common trouble indicator and trouble buzzer. To correct the fault, check for open
wiring on that particular circuit loop or that the Circuit Disconnect Switch is in the ON or
CLOSED position. Note: Disconnecting a Circuit will cause a system trouble (off-normal
position).
Remote Trouble Remote Trouble will be indicated on the main panel display for any failure reported by, or
failure to communicate with a remote annunciator or other remote device.
Ground Fault This panel has a common ground fault detector. To correct the fault, check for any external
wiring touching the chassis or other Earth Ground connection.
Battery Trouble Check for the presence of batteries and their conditions. Low voltage (below 20.4V) will
cause a battery trouble. If battery trouble condition persists, replace batteries as soon as
possible.
Walk Test Mode If the Walk Test LED is illuminated steadily, the system is in Walk Test Mode.
Common Trouble If only a common trouble is indicated on the main panel and none of the above confirming
trouble indicators are ON, check the following for possible fault:
Check for any missing interconnection wiring.
Check for any Module missing that was part of the Configuration.
Check for improperly secured cabling.
42
11.0 Indicators, Controls and Operations
Figure 21 below shows the common display panel for both the FX-350, FX-351 and the FX-
353 Fire Alarm Control Panels.
SYSTEM NORMAL
DEC 03, 2009 02:41AM
AC ON
1 2 3 X
ABC DEF
COMMON ALARM
COMMON S UP V 4 5 6 M
GHI JKL MNO
COMMON
TROUBLE
7 8 9 ?
PRS TUV WXY
CP U FAULT
GROUND * 0 #
FAULT QZ
S Y S TE M S IGNAL
RE S E T S I L E NCE
FIRE ALM/SUP/TBL/
DRI LL BLDG AUDIBLE SIL
GE NE RAL BATTERY/CHARGER
ALARM TROUBLE
The display panel on the FX-350/FX-351/353 main fire alarm control board consists of:
LED Indicators may be amber, red, or green, and may illuminate continuously, or at one of
following Flash Rates:
i Note: Each RAX-332 display is supplied with blank paper labels (#NP-681) for sliding
into the plastic label template on the display.
43
Indicators, Controls and Operations
11.1.1 Buzzer
The Buzzer is activated by any of the following:
11.1.2 AC On LED
The AC On LED illuminates steady green while AC ON
44
Indicators, Controls and Operations
In a ULC application the amber Battery/Charger Trouble LED illuminates steady when any
Battery/Charger Trouble occurs.
45
Indicators, Controls and Operations
Push and hold this button to get detailed information about any displayed item.
addressable device configured as General Alarm. The General Alarm condition remains active
until the panel is reset.
Resets Aux Resettable Power Supply Turns off all Indicating Circuits
Turns OFF Signal Silence, Ack & GA LEDs Turns off Fire Drill
Stops and resets all Timers Processes inputs as new events
Reset cannot be activated until the
Aux Disconnect is not affected Signal Silence Inhibit timer has
expired
Pressing Reset button after a PAS
Acknowledge will reset the system
and clear the alarm event.
! Attention: After power-up, press the System Reset button to bring the system to
normal and restore the system power up trouble.
In a single stage system, all alarm inputs are treated in a similar manner. Alarm inputs include
any of the following: non-verified alarm, verified alarm, waterflow alarm, and general alarm
circuits. Any of these alarm inputs occurring when the panel is not already in alarm cause the
following:
47
Indicators, Controls and Operations
Subsequent alarms when the panel is already in alarm, cause the following:
In a Two-Stage system, alarm inputs are either First Stage (alert) inputs or Second Stage
(general alarm) inputs. First stage inputs include inputs from the following types of circuits:
non-verified alarm, verified alarm, and waterflow alarm. Second stage inputs include alarms
on the general alarm circuits, activation of the General Alarm button, or expiration of the Auto
General Alarm timer. Any of these alarm inputs occurring when the panel is not already in
alarm cause the following:
48
Indicators, Controls and Operations
turns OFF, and the Auto Signal Silence timer, if configured, is restarted. For Canadian
installations, disable Auto Signal Silence.
If the panel is not already in General Alarm, additional non-disconnected signals
programmed to the new input are activated with the Alert Code (see section 11.8 Output
Types on page 53).
If the panel is not already in General Alarm and if the AUTOMATIC ALARM SIGNAL CANCEL LED is
ON steady indicating that the Auto General Alarm timer has been acknowledged the timer is restarted
and the AUTOMATIC ALARM SIGNAL CANCEL LED is extinguished.
A second stage alarm (general alarm) when the panel is already in alarm causes the following:
i Note: All circuits with process type designated as signal are automatically correlated
to the fire drill and general alarm status.
In a Positive Alarm Sequence (PAS) system, only smoke detectors can be dedicated as PAS
inputs. PAS Inputs can only be from the following types of circuits: non-verified alarm and
verified alarm. Any of these alarm inputs occurring when the panel is not already in alarm
cause the following:
49
Indicators, Controls and Operations
To enable or disable the Positive Alarm Sequence, from the Keypad of the FACP press
M to enter the Menu
Using the Up and Down Arrow buttons, scroll to Operation and press the enter key
In the Operation Menu scroll to Positive Alarm and press enter
You will now see displayed the current status of the Positive Alarm Sequence and will be
prompted to change status.
If you do not wish to change the status, press the cancel key
50
Indicators, Controls and Operations
Waterflow Alarm Waterflow inputs are sampled every second. If 10 samples are in alarm in any given
15 second period, an alarm condition is confirmed and the alarm is processed as for
non-verified inputs.
The alarm zone status indicator flashes whenever even one sample indicates an
alarm condition. If the alarm is confirmed the indicator will go steady, it will be turned
OFF when 15 seconds elapses without any samples in the alarm condition. The
waterflow retard operation operates regardless of whether or not the system is in
alarm.
Note: Do not use the retard operation with any external retarding device.
Non-Latching When an un-bypassed supervisory input goes into alarm the common supervisory
Supervisory sequence is activated. Un-bypassed relay, signal, and strobe outputs are updated
according to their programming and supervisory zone status indicators associated
with the input are activated.
Supervisory activations are displayed on the shared display in the common queue
with supervisory as the second highest priority.
When a non-latched supervisory input is restored, outputs programmed to it also
return to normal unless they are also programmed to other active inputs. Zone display
indicators will also be updated to indicate that the input is no longer active and the
message will be removed from the shared display common queue. If there are no
other active supervisory inputs the common supervisory condition will be restored.
Latching Latched supervisory inputs operate the same as non-latched supervisory inputs
Supervisory except that the alarm condition is latched: restoration of the circuit (from alarm to
normal) is ignored until system reset.
51
Indicators, Controls and Operations
Trouble-Only An alarm condition on an un-bypassed trouble only input initiates the common trouble
sequence as a trouble. The status is reflected on trouble zone indicators and in the
common queue on the shared display with trouble-only as the third priority. They may
also be programmed to relay, signal, and strobe outputs.
Note that the trouble condition initiated as a result of an alarm on a trouble-only input
is separate from the circuit or device supervision trouble.
Remote Switch Remote switch inputs may be used to provide remote control of system common
Inputs controls. Remote switches are processed as a toggle operation. When the circuit is
activated it sends an event through the system similar to pressing the switch on the
front panel. When the circuit is restored it is ignored. For example if a remote switch is
associated with the fire drill common control activating it once when drill is not
activated will turn on drill and activating it again will turn off drill.
Remote switches are supervised to ensure that they do not get "stuck" in the "ON"
position. If they remain active for more than 30 seconds a circuit trouble is generated.
Remote switches themselves are not correlated to relay, signal, and strobe outputs
although the feature they are associated with may be.
52
Indicators, Controls and Operations
Relay Un-bypassed relay outputs are activated if any un-bypassed input circuit or common
system status which has been programmed to it is active. If the relay is configured as
"silenceable" it is inhibited when common auxiliary disconnect is active. Relays also
turned off if they are bypassed or if all inputs and system status correlated to it are
restored or bypassed.
i Note: Silencing of the horn depends on the feature provided by the manufacturer of the
horn/strobe combination. Some models of the horn/strobe combination may not
have this feature and will not work as described above.
Two-stage codes:
53
Indicators, Controls and Operations
Continuous
0.5s
0.5s
1.5s
Temporal Code
0.5s
0.5s March Code
5s 10s
California Code
0.5s
Alert Code
2.5s
When the system powers up, it performs an initial self diagnostic and executes a system reset
to reset all external devices. The common trouble sequence is then initiated. The system must
be reset manually to clear the trouble. At power-up, a check is performed on the configuration
data, program, and RAM memory. If an error is found, the system is placed in trouble but the
system attempts to continue to operate.
The power-up sequence will occur when power is first applied to the panel, when power is
restored after a total power failure (including battery power), or when the watchdog timer
expires. It is also implicitly executed when the system comes out of configuration mode after
auto-configure or a new configuration has been downloaded from the configurator.
The power-up complete status is set to indicate that the system power-up is complete and the
system is in normal operating mode.
Shared Display
The shared display consist of a 2 line by 20 characters LCD and alpha numeric keys. It
operates in three basic modes: status display mode, queue display mode and command
mode. Status display mode displays system activity when the queues are empty. When there
are items in the queues, queue display mode is used to browse the status of all active points in
the queues. Command mode which allows the user to execute certain commands, performs
certain system test and front panel configuration of the system.
UP/DOWN scroll through common alarm, supv, trouble and property and building safety
2
ABC queue
scroll through menu selections when in command mode
8
TUV
54
Indicators, Controls and Operations
INFO displays additional information for the currently selected item in queue display
? mode or when a pre-alarm, alarm verification or retard operation is active in
status display mode
MENU enter command mode or returns to base menu if already in command mode
M
CANCEL cancels current operation in command mode and returns to previous menu, or
X exits command mode if at base menu
ALPHA NUMERIC KEYS Some commands require the entry of numeric values, for example loop and
device address for device configuration or changing the time etc.
1 2 3
ABC DEF
Some configuration requires entering the alpha keys for example the labels for
4 5 6
GHI JKL MNO circuits. Multiple key presses are required for entering an appropriate alpha
7 8 9
character. First key press enters the numeric character, the second key press
PRS TUV WXY
enters the first alpha character and another key press will enter the second alpha
* 0
QZ
# character and so on. The sequence is repeated with subsequent key presses.
System Normal
12:47 MON 2005 -10-03
Pre-alarm detected
12:47 MON 2005 -10-03
OR
Alarm verification
12:47 MON 2005 -10-03
OR
Retard verification
12:47 MON 2005 -10-03
If the device or circuit returns to normal, the system normal message will be re-displayed. If
multiple pre-alarms or alarm verification sequences are active at the same time only the first is
displayed. Pressing the INFO button while the pre-alarm or verification message is active will
display additional information on the circuit or device as described under queue display mode.
55
Indicators, Controls and Operations
Where:
the first line shows the process type and the input or output designation
the second line shows the active status or the trouble status depending on the circuit
type and the location of the message in the queue along with the total number of
messages in the queue
pressing the INFO key provides some additional information
the first line shows the process type
the second line shows the loop# where the device is connected and the device address
For internal troubles the 2 line message is an internally formatted message which identifies the
trouble along with any additional information which can help in diagnostics. Whenever there
are active inputs in any of the queues the display will automatically display the oldest un-
viewed event in the highest priority queue. The queue priority is a follows: alarm (highest),
supervisory, trouble, property and building safety (lowest). During queue display mode, the
messages in the queue can be scrolled using the UP and DOWN key. For non-latching inputs
(property and building safety, non-latching supervisory, troubles) the message is removed
from the queue when the circuit is restored. Latching input types will only be removed at
system reset.
56
12.0 Remote Annunciator Operation
The FX-350 supports two types on annunciators: conventional LED/switch annunciators and a
shared display (LCD) annunciator. Both types are connected to the panel via the RS-485 serial
link.
The FX-350 is designed to interface with the RA-1000 series of conventional LED
annunciators. The LEDs may be configured to zone status indicators. Each conventional
annunciator contains a local alert buzzer. Under normal operation the alert buzzer is controlled
by the system and operates in an identical manner as the one in the main panel. If
communication fails it is processed locally.
12.2 Supervision
The communications with each annunciator is constantly supervised both by the panel and by
the annunciator. If communications fails, the panel will activate the common trouble sequence.
The number of annunciators is set during panel configuration. If there is a mismatch in the total
number of annunciators the panel will generate communications trouble. When the correct
number of annunciators is detected the troubles will clear.
The shared display annunciator has identical operation to the main shared display and
operates in conjunction with the main display (viewing items in the queues on one shared
display flag the items as viewed on all shared displays). The shared display annunciator
contains a local alert buzzer. Under normal operation the alert buzzer is controlled by the
system and operates in an identical manner as the one in the main panel. If communication
fails it is processed locally. The configuration cannot be performed by the shared display
annunciator.
12.4 Supervision
The supervision of the shared display annunciator is same as for the remote LED
annunciators
The SRM-312 Smart Relay Module is connected on the RS-485 loop along with other remote
annunciators, but provides 12 relay contact outputs which actuate according to the first 12
remote LED groups. The relays are bypassed by Auxiliary Bypass, and the unit is supervised
as one of the (maximum) eight permitted annunciators.
57
13.0 Dialer Operation
The FX-350 Series (models with a D suffix) Fire Control panels are equipped with a built-in
dialer. The dialer provides a means to communicate panel status to the remote central
monitoring station using two dedicated phone lines.
There are many standard protocols for communicating with the central monitoring station, but
the two most commonly used are supported by this panel
SIA DCS
Contact ID
Events are reported in a special format depending upon the protocol selected.
DC voltage
dial tone, stuttered dial tone and message waiting tone
The supervision is carried out every two minutes; first the DC voltage is supervised and if it is
detected the dial tone is monitored. If the phone lines are equipped with a house phone and
with proper connection if the house phone is in use the supervision is suspended until the
house phone is ON-HOOK again.
If there is an event to be reported in the dialer queue and the house phone is in use the dialer
tries the second line to report the event if that lines house phone is also in use the dialer
seizes the line thus disconnecting the house phone and reports the event.
58
14.0 Appendix A: Compatible Receivers
The dialers that are built into select models of the FX-350 Series Fire Alarm Control Panels
are compatible with the following Digital Alarm Communicator Receivers (DACR):
i Note: * When used with DSC GS4010 or DSC GS4010CF Universal Wireless Alarm
Communicator through wireless IP connection.
59
15.0 Appendix B: Reporting
Table 7 Ademco Contact-ID - FX-350 Series Event Codes
Description Event Qualifier Code Group # Contact #
Family
Phone Line #1 trouble detected Trouble New event 1 351 00 000
Periodic (24 hr) Test Event (NORMAL) Test New event 1 602 00 000
Periodic (24 hr) Test Event (OFF NORMAL) Test New event 1 608 00 000
Manually initiated dialer test Test New event 1 601 00 000
SIA protocol does not define indicating zone troubles, but lists it as Untyped Zone Trouble/
Restore.
60
Appendix B: Reporting
Periodic (24 hr) Test Event (Normal) Test New event RP 000
Periodic (24 hr) Test Event (Off-normal) Test New event RY 000
61
16.0 Appendix C: Specifications
16.1 FX-350 Series Specifications
Addressable loops One analog loop capable of addressing 126 Mircom addressable devices, or three analog
loops capable of addressing 378 Mircom addressable devices.
Indicating (NAC) 4 supervised style Y (Class B) indicating circuits, configured as strobes or audibles.
Circuits Terminals are labelled as SIG 1, SIG 2, SIG 3 and SIG 4.
Aux. Supply resettable Power limited / 21.1 VDC Filtered regulated / 500mA max
Resettable Auxiliary
Terminals are labelled 4-WIRE.
Power (Aux 2)
Electrical ratings Power limited / Regulated 24VDC FWR / 1.7A @ 49C per circuit.
If no auxiliaries are used the max power is 5A for the indicating circuits.
Auxiliary relays Must be connected to a listed power limited source of supply. Terminals are
(resistive loads) labelled ALARM, TROUBLE, SUPV.
Unfiltered supply Power limited / Regulated 24VDC FWR / 1.7A max at 49C
62
Appendix C: Specifications
PR-300 Polarity Reversal and City Tie Module power limited / 24VDC unfiltered / 250mA max
/14Ohms trip
coil
63
17.0 Appendix D: Power Supply and
Battery Calculations
100XB (Base)
MIX-2001R Relay Base X 0.0 = 0.046 =
Device & Remote LEDs (Maximum 30) X 0.0040 =
Signal Load (bells, horns, strobes, and etc.) X =
Auxiliary Power Supply for Annunciators, etc. (See Note 2) = =
Total currents (Add above currents) STANDBY(A) ALARM (B) =
i Notes: Assumes 25% of Zone LEDS (i.e. 15) are ON during alarm.
See specific installation documentation for standby and alarm currents for other
annunciators listed in Panel Components and Accessories. Observe maximum
auxiliary power supply ratings for lamp test conditions for remote annunciators.
64
Appendix D: Power Supply and Battery Calculations
( [STANDBY (A) ______ ] X [(24 or 60 Hours) ___ ] ) + ( [ALARM (B) ______ ] X [Alarm in Hr. _____ ] ) = (C) ______AH
Total Alarm Current must be 5.5 amperes or less. Indicating Circuits must not to exceed 5 amperes.
Battery Selection:
Battery Size = Multiply (C) by 1.20 to derate battery.
Mircom recommends the following batteries for use with this panel:
Batteries:
65
18.0 Warranty and Warning Information
WARNING!
Please read this document CAREFULLY, as it contains important warnings, life-safety, and
practical information about all products manufactured by the Mircom Group of Companies,
including Mircom and Secutron branded products, which shall include without limitation all fire
alarm, nurse call, building automation and access control and card access products
(hereinafter individually or collectively, as applicable, referred to as Mircom System).
NOTE TO INSTALLERS:
All Mircom Systems have been carefully designed to be as effective as possible. However,
there are circumstances where they may not provide protection. Some reasons for system
failure include the following. As the only individual in contact with system users, please bring
each item in this warning to the attention of the users of this Mircom System. Failure to
properly inform system end-users of the circumstances in which the system might fail may
result in over-reliance upon the system. As a result, it is imperative that you properly inform
each customer for whom you install the system of the possible forms of failure:
4. Inadequate Installation. All Mircom Systems must be installed in accordance with all the
applicable codes and standards in order to provide adequate protection. National standards
require an inspection and approval to be conducted by the local authority having jurisdiction
following the initial installation of the system and following any changes to the system. Such
inspections ensure installation has been carried out properly.
5. Inadequate Testing. Most problems that would prevent an alarm a Mircom System from
operating as intended can be discovered by regular testing and maintenance. The complete
system should be tested by the local authority having jurisdiction immediately after a fire,
storm, earthquake, accident, or any kind of construction activity inside or outside the premises.
66
Warranty and Warning Information
The testing should include all sensing devices, keypads, consoles, alarm indicating devices
and any other operational devices that are part of the system.
NOTE TO USERS:
All Mircom Systems have been carefully designed to be as effective as possible. However,
there are circumstances where they may not provide protection. Some reasons for system
failure include the following. The end user can minimize the occurrence of any of the following
by proper training, testing and maintenance of the Mircom Systems:
67
Warranty and Warning Information
13. Wireless Devices Placement Proximity. Moreover all wireless devices must be a minimum
and maximum distance away from large metal objects, such as refrigerators. You are required
to consult the specific Mircom System manual and application guide for any maximum
distances required between devices and suggested placement of wireless devices for optimal
functioning.
14. Failure to Trigger Sensors. Moreover, Mircom Systems may fail to operate as intended if
motion, heat, or smoke sensors are not triggered.
a. Sensors in a fire system may fail to be triggered when the fire is in a chimney, walls, roof,
or on the other side of closed doors. Smoke and heat detectors may not detect smoke
or heat from fires on another level of the residence or building. In this situation the
control panel may not alert occupants of a fire.
b. Sensors in a nurse call system may fail to be triggered when movement is occurring
outside of the motion sensors range. For example, if movement is occurring on the other
side of closed doors or on another level of the residence or building the motion detector
may not be triggered. In this situation the central controller may not register an alarm
signal.
15. Interference with Audible Notification Appliances. Audible notification appliances may be
interfered with by other noise sources such as stereos, radios, televisions, air conditioners,
appliances, or passing traffic. Audible notification appliances, however loud, may not be heard
by a hearing-impaired person.
16. Other Impairments. Alarm notification appliances such as sirens, bells, horns, or strobes
may not warn or waken a sleeping occupant if there is an intervening wall or door. It is less
likely that the occupants will be alerted or awakened when notification appliances are located
on a different level of the residence or premise.
17. Software Malfunction. Most Mircom Systems contain software. No warranties are provided
as to the software components of any products or stand-alone software products within a
Mircom System. For a full statement of the warranties and exclusions and limitations of
liability please refer to the companys standard Terms and Conditions and Warranties.
18. Telephone Lines Malfunction. Telephone service can cause system failure where telephone
lines are relied upon by a Mircom System. Alarms and information coming from a Mircom
System may not be transmitted if a phone line is out of service or busy for a certain period of
time. Alarms and information may not be transmitted where telephone lines have been
compromised by criminal tampering, local construction, storms or earthquakes.
19. Component Failure. Although every effort has been made to make this Mircom System as
reliable as possible, the system may fail to function as intended due to the failure of a
component.
20. Integrated Products. Mircom System might not function as intended if it is connected to a
non-Mircom product or to a Mircom product that is deemed non-compatible with a particular
Mircom System. A list of compatible products can be requested and obtained.
Warranty
Purchase of all Mircom products is governed by:
https://www.mircom.com/product-warranty
https://www.mircom.com/purchase-terms-and-conditions
https://www.mircom.com/software-license-terms-and-conditions
68
CANADA - Main Office U.S.A TECHNICAL SUPPORT Mircom 2017
25 Interchange Way 4575 Witmer Industrial Estates North America Printed in Canada
Vaughan, ON L4K 5W3 Niagara Falls, NY 14305 Tel: (888) Mircom5 Subject to change without prior notice
Tel: (888) 660-4655 Tel: (888) 660-4655 (888) 647-2665
(905) 660-4655 (905) 660-4655 International www.mircomgroup.com
Fax: (905) 660-4113 Fax: (905) 660-4113 Tel: (905) 647-2665