LT-959 FX-350 Installation and Operation Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 72

FX-350 Series

Analog/Addressable Fire Alarm Panels

LT-959 Rev. 6
Installation and Operation Manual June 2017
Table of Contents

1.0 Industry Canada and FCC Notice 8

1.1 Notice for all FX-350 Series Built-In UDACTs Sold in Canada ...................................... 8

2.0 Introduction 10

2.1 Features ......................................................................................................................... 10

3.0 Conventions 12

3.1 Circuits .......................................................................................................................... 12


3.2 Zone/Group .................................................................................................................... 12
3.3 Display Points ............................................................................................................... 12
3.4 Wiring Styles ................................................................................................................. 12

4.0 System Components 13

4.1 Panel Models ................................................................................................................. 13


4.2 Output Class A converter: four circuits .......................................................................... 15
4.3 Polarity reversal/city tie .................................................................................................. 15
4.4 Remote Annunciator ...................................................................................................... 15
4.5 Smart Relay Module ...................................................................................................... 16
4.6 RAM-216 Ancillary Annunciator ..................................................................................... 16
4.7 Panel Components and System Accessories ................................................................ 17
4.8 Analog/Addressable Devices ......................................................................................... 17

5.0 Mechanical Installation 19

5.1 Installing the Enclosures ................................................................................................ 19


5.2 BBX-1024DS and BBX-1024DSR Mechanical Installation ............................................ 22

6.0 Installing Adder Modules 23

6.1 Cable and Jumper Connections for Main Board and Adder Modules ........................... 24
6.2 Connectors and Jumpers on the Main Fire Alarm Board ............................................... 26
6.3 OCAC-304 Output Class A Converter Adder Module ................................................... 26
6.4 Polarity Reversal and City Tie Module (Model PR-300) ............................................... 27
6.5 RAX-332 Display Adder Module .................................................................................... 27

3
Table of Contents

7.0 Circuits and Devices 28

7.1 Addressable/Analog Devices ......................................................................................... 28


7.2 Analog Devices .............................................................................................................. 29
7.3 Contact Inputs ................................................................................................................ 29
7.4 Contact Outputs ............................................................................................................. 29

8.0 Field Wiring 30

8.1 Main Fire Alarm Board Field Wiring ............................................................................... 30


8.2 Loop Isolators ................................................................................................................. 31
8.3 Loop Operation .............................................................................................................. 31
8.4 Indicating (Powered Output) Circuits ............................................................................. 32
8.5 Indicating Circuit Wiring ................................................................................................. 32
8.6 Dialer Wiring ................................................................................................................... 34
8.7 Polarity Reversal and City Tie Module (PR-300) Wiring ............................................... 36
8.8 Auxiliary Power Supplies ................................................................................................ 37
8.9 Power Supply Connections ............................................................................................ 38
8.10 Connecting to a 3G4010 Interface Device for Canada .................................................. 39
8.11 Connecting to a 3G4010CF Interface Device outside Canada ...................................... 40

9.0 System Checkout 41

9.1 Before turning the power ON ....................................................................................... 41


9.2 Power-up procedure ....................................................................................................... 41

10.0 Troubleshooting 42

11.0 Indicators, Controls and Operations 43

11.1 Common Indicators ........................................................................................................ 44


11.2 Common Controls .......................................................................................................... 46
11.3 Single Stage Operation .................................................................................................. 47
11.4 Two-Stage Operation ..................................................................................................... 48
11.5 Positive Alarm Sequence ............................................................................................... 49
11.6 Enabling or Disabling the Positive Alarm Sequence ...................................................... 50
11.7 Input Types .................................................................................................................... 50
11.8 Output Types .................................................................................................................. 53
11.9 Evacuation Codes .......................................................................................................... 53
11.10 Initial Power-up Sequence ............................................................................................. 54

12.0 Remote Annunciator Operation 57

12.1 Conventional Annunciators (RA-1000 Series) ............................................................... 57

4
Table of Contents

12.2 Supervision .................................................................................................................... 57


12.3 Shared Display Annunciator (RAM-300LCD) ................................................................. 57
12.4 Supervision .................................................................................................................... 57

13.0 Dialer Operation 58

13.1 Event Reporting ............................................................................................................. 58


13.2 Telephone line supervision ............................................................................................ 58

14.0 Appendix A: Compatible Receivers 59

15.0 Appendix B: Reporting 60

16.0 Appendix C: Specifications 62

16.1 FX-350 Series Specifications ......................................................................................... 62


16.2 FX-350 System Modules and Annunciators ................................................................... 63

17.0 Appendix D: Power Supply and Battery Calculations 64

18.0 Warranty and Warning Information 66

5
List of Figures
Figure 1 Wallbox Dimensions / Mounting the FX-350 Surface .................................................. 19
Figure 2 Mounting the FX-350 - Flush ......................................................................................... 20
Figure 3 Flush Trim Detail ............................................................................................................ 20
Figure 4 Wallbox Dimensions / Mounting the FX-351/FX-353 Surface /Flush ......................... 21
Figure 5 BBX-1024DS and BBX-1024DSR Installation Instructions and Dimensions ................. 22
Figure 6 Installation of Adder Modules ........................................................................................ 23
Figure 7 Main Fire Alarm Board Cable Connectors and Jumper Locations ................................. 24
Figure 8 Main Board (3 loop model) Cable Connectors and Jumper Locations ........................... 25
Figure 9 OCAC-304 Output Class A Converter Adder Modules .................................................. 26
Figure 10 Polarity Reversal and City Tie Module .......................................................................... 27
Figure 11 Addressable Loop Wiring - Class B or Style 4 ............................................................... 30
Figure 12 Addressable Loop Wiring - Class A or Style 6 ............................................................... 31
Figure 13 Indicating Circuit Class B or Style Y Wiring ................................................................ 34
Figure 14 Indicating Circuit Class A or Style Z Wiring .................................................................. 34
Figure 15 Dialer Wiring ................................................................................................................... 35
Figure 16 Polarity Reversal and City Tie Module Terminal Connection ........................................ 36
Figure 17 Supervision Of Auxiliary Supplies .................................................................................. 37
Figure 18 Main Power Supply Connections ................................................................................... 38
Figure 19 Connecting an FX-350 FACP to a 3G4010 Interface Device ......................................... 39
Figure 20 Connecting an FACP to a 3G4010CF Interface Device outside Canada ....................... 40
Figure 21 LCD Display, LED indicators and control buttons ......................................................... 43
Figure 22 Evacuation and Alert Codes ........................................................................................... 54

6
List of Tables
Table 1 FX-350 Series Comparison Chart .................................................................................. 14
Table 2 Settings permitted in CAN/ULCS527 ............................................................................. 30
Table 3 Loop Wiring Table .......................................................................................................... 31
Table 4 Maximum Wiring Distances ........................................................................................... 32
Table 5 Input Types .................................................................................................................... 50
Table 6 Output Types ................................................................................................................. 53
Table 7 Ademco Contact-ID - FX-350 Series Event Codes ........................................................ 60
Table 8 Security Industries Association SIA-DCS - FX-350 Series Event Codes ....................... 61
Table 9 FX-350 Series Specifications ......................................................................................... 62
Table 10 FX-350 System Modules and Annunciators ................................................................... 63
Table 11 FX-350 Batteries ............................................................................................................ 65

7
1.0 Industry Canada and FCC Notice
1.1 Notice for all FX-350 Series Built-In UDACTs Sold in Canada

Mircom's FX-350 SERIES BUILT-IN UDACT Communicator described in this manual is listed
by Underwriters Laboratories Canada (ULC) for use in slave application in conjunction with a
Listed Fire Alarm Control Panel under Standard ULC-S527-11 (Standard for Control Units for
Fire Alarm Systems) and CAN/ULC-S561-13 (Standard for Installation and Services for Fire
Signal Receiving Centres and Systems). These Communicators should be installed in
accordance with this manual; the Canadian / Provincial / Local Electrical Code; and/or the
local Authority Having Jurisdiction (AHJ).

1.1.1 Industry Canada Notice


Repairs to certified equipment should be made by an authorized Canadian maintenance
facility designated by the supplier. Any repairs or alteration made by the user to this
equipment, or equipment malfunctions, may give the telecommunications company cause to
request the user to disconnect the equipment. Users should ensure for their own protection
that the Earth Ground connections of the power utility, telephone lines and internal metallic
water pipe system, if present, are connected together. This is necessary both for proper
operation and for protection.

! Attention: Users should not attempt to make such connections themselves, but
should contact the appropriate electric inspection authority, or
electrician, as appropriate

1.1.2 Notice for all FX-350 Series Built-in UDACTs Sold in the U.S.A.

i Notes: The Ringer Equivalence Number (REN) assigned to each terminal device
provides an indication of the maximum number of terminals allowed to be
connected to a telephone interface. The termination on an interface may consist
of any combination of devices subject only to the requirement that the sum of the
Ringer Equivalence Numbers of all the devices does not exceed 5.

The Label Identification Number for this product is US:1M8AL02BFX350. The


02B represents the REN without a decimal point (e.g., 02B is a REN of 0.2B). For
earlier products, the REN is separately shown on the label.

Mircom's FX-350 SERIES BUILT-IN UDACT Digital Communicator described in this manual
is listed by Underwriters Laboratories Inc. (ULI) for use in slave application in conjunction with
a Listed Fire Alarm Control Panel under Standard 864 (Control Units for Fire Protective
Signalling Systems). These Communicators comply with the National Fire Protection
Association (NFPA) performance requirements for UDACTs and should be installed in
accordance with NFPA 72 Chapter 4 (Supervising Station Fire Alarm System). These
Communicators should be installed in accordance with this manual; the National Electrical
Code (NFPA 70); and/or the local Authority Having Jurisdiction (AHJ).

1.1.3 FCC Notice


This equipment complies with Part 68 of the FCC rules and the requirements adopted by the
ACTA. On the telco transformer of this equipment is a label that contains, among other
information, a product identifier in the format US:1M8AL02BFX350. If requested, this number

8
Industry Canada and FCC Notice

must be provided to the telephone company. This equipment is capable of seizing the line.
This capability is provided in the hardware.

Type of Service: The Communicator is designed to be used on standard device telephone


lines. It connects to the telephone line by means of a standard jack called the USOC RJ-11C
(or USOC FJ45S). Connection to telephone company provided coin service (central office
implemented systems) is prohibited. Connection to party lines service is subject to state tariffs.

Telephone Company Procedures: The goal of the telephone company is to provide you with
the best service it can. In order to do this, it may occasionally be necessary for them to make
changes in their equipment, operations or procedures. If these changes might affect your
service or the operation of your equipment, the telephone company will give you notice, in
writing, to allow you to make any changes necessary to maintain uninterrupted service.

In certain circumstances, it may be necessary for the telephone company to request


information from you concerning the equipment which you have connected to your telephone
line. Upon request of the telephone company, provide the FCC registration number and the
ringer equivalence number (REN); both of these items are listed on the equipment label. The
sum of all of the RENs on your telephone lines should be less than five in order to assure
proper service from the telephone company. In some cases, a sum of five may not be usable
on a given line.

If Problems Arise: If any of your telephone equipment is not operating properly, you should
immediately remove it from your telephone line, as it may cause harm to the telephone
network. If the telephone company notes a problem, they may temporarily discontinue service.
When practical, they will notify you in advance of this disconnection. If advance notice is not
feasible, you will be notified as soon as possible. When you are notified, you will be given the
opportunity to correct the problem and informed of your right to file a complaint with the FCC.
Contact your telephone company if you have any questions about your phone line. In the
event repairs are ever needed on the Communicator, they should be performed by Mircom
Technologies Ltd. or an authorized representative of Mircom Technologies Ltd. For information
contact Mircom Technologies Ltd. at the address and phone numbers shown on the back page
of this document.

9
2.0 Introduction
Mircoms FX-350 Series Analog/Addressable Fire Alarm Control Panel provides a loop for
60,126 or three loops for 378 input and output devices, four supervised Class B or A (Style Y
or Z) indicating circuits, a full range of auxiliary power supplies, and extensive common control
features via its integrated LCD display and push button console. Many of its features are fully
configurable utilizing the built-in configuration capability via the front panel display and
switches. The panels are available with or without an optional, integrated dialer/modem
(except the FX-353 version which always includes the dialer/modem), and is available (FX-
351 and FX-353 - in a larger enclosure) with an internal LED display for up to 64 points (32
standard). Optional modules include Polarity Reversal and City Tie, RAX-332 LED Display
Adder, and Class A Converter for indicating circuits. Semi-flush or surface mountable
enclosures can be used for retrofits and on new installations. This manual covers the following
panels:

i Note: Installation of the FX-350 Series Fire Alarm Control panel should be in
accordance with Canadian Electrical Code Part 1, ULC-S524 installation of Fire
Alarm System, National Electrical Code NFPA 70 and NFPA 72. Final
acceptance subject to the Local Authority Having Jurisdiction (AHJ).

FX-350-60-DR 60 pt addressable FACP (w/ dialer)

FX-351-LW 126 pt addressable FACP (w/ one 32 point LED display)


FX-351-LDW 126 pt addressable FACP (w/ dialer and one 32 point LED display)
FX-351-LDR 126 pt addressable FACP (w/ dialer)
FX-353-LW 378 pt addressable FACP without LED strip (w/ dual loop adder and one
32 point LED display)
FX-353-LDR 378 pt addressable FACP without LED strip (w/ dialer and dual loop
adder)
FX-350-60D 60 pt addressable FACP (w/ dialer)
FX-351-LD 126 pt addressable FACP (w/ dialer)

2.1 Features

The FX-350 panels support a loop of 60 or 126 analog devices and up to 3 loops of 378
analog devices, including thermal, ion, photo detectors, and contact input and output
devices. Drift compensation and Auto Test features are provided for analog devices.
Four Power Limited Class B (Style Y) indicating circuits. Each indicating circuit may be
configured as Class A (Style Z) using an output Class A converter adder module. Each
indicating circuit may be configured as silenceable signal, non-silenceable signal,
silenceable strobes, non-silenceable strobes, or relay output. The audible signal may be
Steady, Temporal Code, California Code, or March Time. The system provides the
necessary protocols to sync strobes from major manufacturers.
Two-stage, alarm verification, and waterflow retard operations available.
Configurable Signal Silence Inhibit, Auto Signal Silence, Two-Stage Operation, and
One-Man Walk Test. For Canadian installations, disable Auto Signal Silence.
Subsequent Alarm, Supervisory, and Trouble operation.

10
Introduction

provides a regulated, supervised 21.1VDC auxiliary power supply @ 500mA max.;


unfiltered, unsupervised 24V FWR power supply @ 1.7 A max and a resettable auxiliary
power supply @ 300mA max.
Relay Contacts for Common Alarm, Common Supervisory and Common Trouble all
non-disconnectable and Auxiliary Alarm Relay (disconnectable).
Output for remote trouble indicator and Buzzer (RTI).
RS-485 Interface for RAM-300LCD Annunciators, RA-1000 Series Remote
Annunciators and SRM-312 Smart Relay Modules (max total of 7 remote annunciators).
Optional Module for City Tie and Polarity Reversal Signaling.
Extensive transient protection
With or without built-in UDACT (Digital Alarm Communicator Transmitter)
Extensive and easy configuration of the panel via the integrated LCD display and
keypad
Remote dial up (with built-in UDACT version) for event log checking and/or configuration
changing

11
3.0 Conventions
3.1 Circuits

Refers to a physical electrical interface for the analog loop, indicating signals or relays, and
common alarm, supervisory, and trouble relay outputs.

3.2 Zone/Group

Is a logical concept for a Fire Alarm Protected Area, and will consist of at least one Circuit.
Groups are used extensively in the FX-350 to facilitate annunciation of multiple input and
output points on the 32 (up to 64) LED display and to facilitate bypassing of inputs and
outputs.

3.3 Display Points

The FX-350 provides an LCD display to annunciate the status of the system and connected
devices. The FX-351 and FX-353 also provides up to 64 LED display points on the panel front
in addition to the LCD display. Display points may be assigned to LEDs during configuration to
groups of inputs or outputs. There are two LEDs for every display point: one single color
(amber) and one dual color (red/amber).

3.4 Wiring Styles

The analog loop can be connected in Class B (Style Y) or Class A (Style D) configurations.
Changing the indicating circuits to Class A requires an OCAC-304 adder board which will
convert four indicating zones from Class B (Style Y) circuits to Class A (Style Z). This is done
without reducing the number of circuits.

i Note: The Model FX-350-60-R and FX-350-60DR panels DO NOT recognize any
devices with addresses higher than 60.

12
4.0 System Components
4.1 Panel Models

SYSTEM NORMAL SYSTEM NORMAL


DEC 3, 2009 3:25AM DEC 03, 2009 10:25AM

SYSTEM NORMAL
AC ON AC ON
1 2 3 X 1 2 3 X
ABC DE F ABC DE F
COMMON ALARM COMMON ALARM

DEC 03, 2010 02:41PM COMMON SUPV


4 5 6 M COMMON SUPV
4 5 6 M
GHI JK L MNO GHI JK L MNO

COMMON TROUBLE COMMON TROUBLE


7 8
T UV
9 ? 7 8
T UV
9 ?
P RS WX Y P RS WX Y
CPU FAULT CPU FAULT

AC ON GROUND FAULT * 0 # GROUND FAULT * 0 #


1 2 3 X QZ QZ

ABC DEF
COMMON ALARM
SYSTEM SIGNAL SYSTEM SIGNAL
RESET SILENCE RESET SILENCE

COMMON S UP V
4 5 6 M
GHI JKL MNO
FIRE ALM/SUP/TBL/BLDG FIRE ALM/SUP/TBL/BLDG
COMMON DRILL AUDIBLE SIL DRILL AUDIBLE SIL
TROUBLE
7 8 9 ?
PRS TUV WXY AUTOMATIC ALARM LAM P AUTOMATIC ALARM LAM P
CP U FAULT TEST SIGNAL CANCEL TEST
SIGNAL CANCEL

GROUND
FAULT
* 0 # GENERAL GENERAL
SPARE SPARE
QZ ALARM ALARM

S Y S TE M S IGNAL
RE S E T S ILE NCE

ZO N E -1 ZO N E -1 ZO N E -1 ZO N E -1

FIRE ALM/SUP/TBL/BLDG
DRILL AUDIBLE SIL ZO N E -1 ZO N E -1 ZO N E -1 ZO N E -1

ZO N E -1 ZO N E -1 ZO N E -1 ZO N E -1

AUTOMATIC ALARM LAMP


SIGNAL CANCEL TE S T

ZO N E -1 ZO N E -1 ZO N E -1 ZO N E -1

GE NE RAL
S P ARE ZO N E - 1 ZO N E - 1 ZO N E - 1 ZO N E - 1
ALARM

ZO N E - 1 ZO N E - 1 ZO N E - 1 ZO N E - 1

ZO N E - 1 ZO N E - 1 ZO N E - 1 ZO N E - 1

ZO N E - 1 ZO N E - 1 ZO N E - 1 ZO N E - 1

FX-350 SERIES
Fire Alarm Control Panel

FX-350 SERIES FX-350 SERIES


Fire Alarm Control Panel Fire Alarm Control Panel

FX-350-60DR FX-351-LDR FX-351-LW FX-350-60D


FX-353-LDR FX-351-LDW FX-351-LD
FX-353-LW

All FX-350 Series Panels have the following features:

Multi-zone fire alarm control panel with 2 x 20 LCD display.


Style Y or Style D analog loop(s).
Four Power Limited Class B (Style Y) indicating circuits (max 1.7 Amps each - 5 Amps
total).
Dedicated common alarm, supervisory, trouble, and auxiliary alarm relays.
Additional RAX-332 Display Adders can be added to provide 64 annunciation points per
added.
An optional OCAC-304 Class A converter module may be used to convert the indicating
circuits to Class A (Style Z).
Additional outputs include connections for a RTI remote trouble indicator, PR-300
Reverse Polarity Module, an RS-485 bus for connection of up to seven RAM-300LCDs,
SRM-312s and RA-1000 Series annunciators.
Auxiliary power is available in the form of 24V FWR unfiltered and unsupervised, 24VDC
filtered and regulated, and resettable auxiliary power supply.

13
System Components

See Table 1 for the specifics of each panel.

Table 1 FX-350 Series Comparison Chart

Model # of devices # of 2 line UDACT Door # of 32 Max # of Dual


analog Digital point LED LED Loop
Color
loops Communicator Displays Displays Adder
(y/n) (y/n)

FX-350-60-DR 60 1 y red n/a n/a n

FX-351-LW 126 1 n white 1 2 n

FX-351-LDW 126 1 y white 1 2 n

FX-351-LDR 126 1 y red 0 2 n

FX-353-LW 378 3 n white 1 2 y

FX-353-LDR 378 3 y red 0 2 y

FX-350-60D purchased purchased


60 1 y 2 n
separately separately

FX-351-LD purchased purchased


126 1 y 2 n
separately separately

Some models may not be available in all markets. Verify with your local distributor.

14
System Components

4.2 Output Class A converter: four circuits

Model Description

- SIG1 OUT+

- SIG1 RET+
BLK RED

- SIG2 OUT+
OCAC-304 Output Class A converter module (four

- SIG2 RET+
BLK RED

circuits)
- SIG3 OUT+

- SIG3 RET+
BLK RED

- SIG4 OUT+

- SIG4 RET+
BLK RED

4.3 Polarity reversal/city tie

Model Description

Mounting hole for


+ | -

#6-32 screws
CITY
TIE
REVER SAL REVER SAL
POLAR ITY POLAR ITY
+ | -

P1 P2
ALAR M

Mounting hole for


#6-32 screws PR-300 Polarity Reversal and/or City Tie Module
+ | -
SU PV
JW4

4.4 Remote Annunciator

Model Description
Remote Annunciator module, LCD display,
RAM-300LCDR
white painted box
SYSTEM NORMAL
18:01 MON 2003-04-05

A.C. ON ALARM SUPV TRBL CPU FAIL


SYSTEM
RESET

SIGNAL
SILENCE 1 2 3 ENTER
ABC DEF

FIRE
DRILL 4 5 6 MENU
GHI JKL MNO

BUZZER
Remote Annunciator Module, LCD display,
RAM-300LCDR
SILENCE 7 8 9 CANCEL
PRS TUV WXY

LAMP
TEST * 0
QZ
# INFO

red painted box


Advanced Life Safety Solutions

FA-300 SERIES
Remote Annunciator

15
System Components

4.5 Smart Relay Module

Model Description
Smart Relay Module (12 relays) with white
SRM-312W
enclosure

Smart Relay Module (12 relays) with red


SRM-312R
enclosure
Advanced Life Safety Solutions

FA-300 SERIES
REMOTE RELAY

4.6 RAM-216 Ancillary Annunciator

Model Description

A.C. COMMON SIGNAL


ON TROUBLE SILEBCE

BUZZER
SILENCE
SIGNAL
SILENCE
RAM-216 16 Zone ancillary annunciator
SWITCH
ENABLE

LAMP SYSTEM
TEST RESET

FIRE ALARM
ANNUNCIATOR

16
System Components

4.7 Panel Components and System Accessories

MODEL NO. DESCRIPTIONS

ALC-252 252 Point Dual Loop Addressable Adder

RAX-332 32 Zone Internal Display Adder (for FX-351 and FX-353 only)

RAM-208/R 8 LED Remote Annunciator

RAM-1016/TZ Remote Annunciator with 16 bi-colored (red and yellow) LEDs.


TZ version has 32 yellow LEDs for trouble indication.

RAM-1032/TZ Remote Annunciator with 32 bi-colored (red and yellow) LEDs.


TZ version has 32 yellow LEDs for trouble indication.

RAX-1048/TZ Remote Annunciator with 48 bi-colored (red and yellow) LEDs.


TZ version has 48 yellow LEDs for trouble indication.

MGD-32 Graphic Annunciator

AGD-048 Graphic Annunciator Adder Driver Board

RTI-1 Remote Trouble Indicator, Buzzer and LED

FA-300-TRB Trim Ring For Small Enclosure (Black)

FA-UNIV-TRB Universal Trim Ring For Big Enclosure (Black)

BB-1001(R) Enclosure for one annunciator, white. R version is red.

BB-1002(R) Enclosure for two annunciators, white. R version is red.

BB-1003(R) Enclosure for three annunciators, white. R version is red.

BB-1008(R) Enclosure for eight annunciators, white. R version is red.

BB-1012(R) Enclosure for twelve annunciators, white. R version is red.

MP-300 End-of-line resistor plate, 3.9K ohm

BC-160 External Battery Cabinet

4.8 Analog/Addressable Devices

Description Mircom Model

Ionization Smoke Detector (U.S. Model Only) MIX-3000

Photoelectric Smoke Detector MIX-3100

* Multi-sensor (photoelectric with supplemental rate-of-rise heat sensor) MIX-3200

Heat Detector MIX-3300

Bases Mircom Model

4 inch Standard Base MIX-2000

6 inch E-Z Fit Base MIX-2001

17
System Components

6 inch Base with Relay MIX-2001R

6 inch Base with Sounder MIX-2001H

6 inch Base with Temporal Tone Sounder MIX-2001HT

Ancillary Modules Mircom Model

Priority Monitor Module MIX-100P

Mini Priority Monitor Module MIX-101P

Single Relay Output Module (1 Form C Contacts, 2 Gang Mount) 55000-820

Supervised Control Module MIX-100S

MIX-100X (Kit)
Isolator c/w Mounting Base 100XH (Isolator)
100XB (Base)

Addressable Duct Detectors Mircom Model

Ionization Duct Smoke Detector (UL Listed) MIX-DH3000

Photoelectric Duct Smoke Detector (UL Listed) MIX-DH3100

Ionization Duct Smoke Detector with relay (UL Listed) MIX-DH3000R

Photoelectric Duct Smoke Detector with relay (UL Listed) MIX-DH-3100R

Addressable Pull Stations Mircom Model

Addressable Single Stage Pull Station MS-401ID(U)

Addressable Two Stage Pull Station (Canadian Model Only) MS-402ID

Addressable Single Stage Single Action Pull Station MS-701ID(U)

Addressable Two Stage Single Action Pull Station MS-702ID(U)

Addressable Single Stage Dual Action Pull Station MS-710ID(U)

* Unit employs an integral heat sensor; however it must not be used as a regular heat detector. Refer to the
product data sheet for detailed functionality, operation and application.
Manual configuration for the MIX-3200 is NOT PERMITTED. This device must be configured via the AUTO
CONFIG.

18
5.0 Mechanical Installation
5.1 Installing the Enclosures

Install the FX-350 Series Fire Alarm Panel enclosure as shown below. Mount the enclosure
using the four mounting holes and the screws provided.

Mounting 11"
Hole

1.5"

Mounting
Hole

14.5"
20"

Mounting Hole

5.4" Mounting Hole

4.5"

14.5"

Figure 1 Wallbox Dimensions / Mounting the FX-350 Surface

19
Mechanical Installation

11"

1.5"

PLACE FA-300TRB TRIM RING OVER BACKBOX

17"
4 Mounting
Holes for
14.5" Surface
Mounting

Adhere trim ring to


wall surface around
FX-350 backbox 20.0"

22.5"
3.5" is the maximum depth
4" for semi-flush mounting
using the flush trim ring

5"
4. 3.5"

14.5" 1"

1" is the minimum depth


above the wall required
for semi-flush mounting
using the flush trim ring

Figure 2 Mounting the FX-350 - Flush

5.2 below shows a cross-section of the semi-flush mounted backbox and the trim ring. Make
sure to allow a minimum depth of 1 above the wall surface for proper door opening.

TRIM RING

WALL MIN 1

WOOD OR
METAL STUD

BACKBOX

Figure 3 Flush Trim Detail


20
Mechanical Installation

Figure 4 Wallbox Dimensions / Mounting the FX-351/FX-353 Surface /Flush

i Note: See 5.2 for Flush Trim Details for mounting the trim ring.

21
Mechanical Installation

5.2 BBX-1024DS and BBX-1024DSR Mechanical Installation

The BBX-1024DS and BBX-1024DSR are suitable for flush or surface mounting, and have a
built-in trim ring.

Dimensions of Enclosure (minus built in trim ring) 14.5 x 4.2 x 26


Distance between horizontal mounting screws 12
Distance between vertical mounting screws 23.5
Complete Dimensions of Enclosures 16.3 x 5.5 x 27.5

External Dimensions Mounting Dimensions

12.0 "

14.5 "

4.2 "

23.5 "

26.0 "

Side View Top View

2.1 "

1.3 " 1.7 "


1.3 "
6.0 "

2.0 "

9.5 "

Figure 5 BBX-1024DS and BBX-1024DSR Installation Instructions and Dimensions

22
6.0 Installing Adder Modules
The FX-350 Series Fire Alarm panels come pre-assembled with all components and boards
except for Adder Modules. Module installation locations are shown below. Refer to Figure 6
and Figure 7 for Jumper or DIP Switch settings and see Chapter 8.0 Field Wiring on page 30
for wiring specifications.

JW3 RS-232C P ORT

For PC programming use UIMA


Interface module not UL-864 or JW4

+
T

ULC-527 listed. Please refer to


CO

B
R

Document LT-929 for details


LI NE1

-
Loop
A
T

+
RES
R

-
T
CO

SYSTEM NORMAL
R

LIN E2
T

OCT 21 , 2005 02:41AM


RES
R

JW1
+

AC ON
1 2 3
RS -485

X
CLASS- A converter
-

ABC D EF
COMMON ALARM
JW2 board for indicating
S

COMMON SUPV 4 5 6 M
GH I JKL MN O circuits OCAC-304
NO

AU X. R ELAY

COMMON TROUBLE (4 circuits )


C

7 8 9 ?

+
PR S TU V WXY

- SIG1 OUT+

- SIG1 RE T+
RED
BLK
NC

CPU FAULT

SI G 1

+ -
* 0 #
NO

GROUND FAULT
QZ

- SIG2 OUT+

- SIG2 RET+
RED
BLK
RELA Y

JW6
ALARM

S IG 2
C

ALM/SUP/TBL/BLDG

-
AUDIBLE SIL

Reverse polarity and city


NC

SYST EM SIGNAL

+
RESET SIL ENCE

- SIG3 OUT+

- SIG3 RE T+
RED
tie module PR -300 .

BLK
SI G 3
NO

S UPERVIS O RY

Mounted on hex spacer -


R ELAY

F IRE ALM/SUP/TBL/
C

BLDG AUDIBLE SIL


+

- SIG4 OUT+

-S IG4 RET+
RED
BLK
DRIL L
with two screws provided JW5
SI G 4
NC

AUTOMATIC ALARM L AMP


NO

SIGNAL CANCEL T EST


+
SU PPLY
TROU BLE
RELAY

AUX
C

+ -

GENERAL
AL ARM SPARE
NC

SU PPLY
4-WI RE
SUPPLY
POWER

RTI UNFILTERED
JW 7 P12 PO RT FW R24VDC
TO PR-300 MO DULE
JW 9 TRB TRL CO M- CO M+
Transformer
P8 P4 P3 P2
TO RAX-332

Power supply
board

PR- 300 is mounted B A TTE RY S E C TX


+

here for FX- 351


P4

P2
P3

P1

AC wiring terminal

+ - + -

BATTERY BATTERY

Figure 6 Installation of Adder Modules

23
Installing Adder Modules

6.1 Cable and Jumper Connections for Main Board and Adder
Modules

RS-232C PORT
For PC programming

JW3
For PC programming use UIMA
Interface module not UL-864 or
ULC-527 listed. Please refer to JW4 Addressable

+
T

Document LT-929 for details


CO

B
Loop
R

L I N E1

Telephone line #1

-
L o op
A
T

+
RES
R

-
T

CO
R

LI N E 2

Telephone line #2 SYSTEM NORMAL


T

RES

OCT 21 , 2005 02 : 41 AM
R

JW1
+

RS-485 for AC ON
R S- 4 8 5

1 2 3 X
-

annunciators COMMON ALARM


ABC D EF

JW2
S

COMMON SUPV
4 5 6 M
GH I JKL MN O
NO

A U X . R EL A Y

Auxiliary Relay COMMON TROUBLE


C

7 8 9 ?

+
PR S TU V WXY

RE D
BL K
NC

CPU FAULT

SIG 1

-
* 0 #
NO

GROUND FAULT

+
JW6
QZ

R ED
B LK
R E LA Y
AL ARM

SI G 2
Alarm Relay
C

-
NC

SYST EM SIGNAL

+
RESET SIL ENCE

RE D
BL K
SIG 3
NO

S U PE R V I S O R Y

-
R E LA Y

F IRE ALM/SUP/TBL/BLDG
C

AUDIBLE SIL
Supervisory Relay

RE D
BL K
DRIL L

SI G 4
JW5
NC

-
AUTOMATIC ALARM L AMP
SIGNAL CANCEL
NO

T EST

+ Auxiliary
S U P P LY
T R O U B LE
R E LA Y

A UX
C

Supply
-

Trouble Relay GENERAL


AL ARM
SPARE
+
NC

S UP P L Y
4- W I R E

Resettable
S U P PL Y
POW ER

Auxiliary
JW7 P12
RTI
PO RT
UNFILTERED
FW R 24 VDC Supply
JW9 TRB TRL CO M - CO M +

P8 P4 P3 P2

Connect to PR-300 Connect to RAX-332


Connect to Unfiltered
Remote trouble 24V supply
indicator

Figure 7 Main Fire Alarm Board Cable Connectors and Jumper Locations

24
Installing Adder Modules

Figure 8 below shows the main board for the 3 loop addressable model. It is the same as the
single loop model with two additional addressable loops.

R S -232C POR T Addressable


F or PC programming
Loops
1 3 2
JW3
F or P C programming us e U IM A
Interface module not U L-864 or
U LC-527 lis ted. P leas e refer to JW4

+
T
D ocument LT-929 for details

CO

B
R

L I N E1
Telephone line #1

-
L o op
A
T

+
RES
R

-
T

CO
R

LI N E 2

Telephone line #2 SYSTEM NORMAL


T

RES

OCT 21 , 2005 02 : 41 AM
R

JW1
+

RS-485 for AC ON
R S- 4 8 5

1 2 3 X
-

annunciators COMMON ALARM


ABC DEF

JW2
S

COMMON SUPV
4 5 6 M
GHI JKL MNO
NO

A U X . R EL A Y

Auxiliary Relay COMMON TROUBLE


C

7 8 9 ?

+
PR S TU V WXY

RED
BL K
NC

SIG 1
CPU FAULT

-
* 0 #
NO

GROUND FAULT

+
QZ
JW6

R ED
B LK
R E LA Y
AL ARM

SI G 2
Alarm Relay
C

-
NC

SYST EM SIGNAL

+
RESET SIL ENCE

RED
BL K
SIG 3
NO

S U PE R V I S O R Y

-
R E LA Y

ALM/SUP/TBL/BLDG
C

F IRE

Supervisory Relay

RED
AUDIBLE SIL

BL K
DRIL L

SI G 4
JW5
NC

-
AUTOMATIC ALARM L AMP
NO

SIGNAL CANCEL T EST

+
Auxiliary

S U P P LY
T R O U B LE
R E LA Y

A UX
C

Supply

-
Trouble Relay GENERAL
AL ARM
SPARE

+
NC

S UP P L Y
4- W I R E
Resettable
S UP PLY
POWER

-
Auxiliary
JW7 P 12
RTI
PO RT
UNFILTERED
FW R 24 VDC Supply
JW9 TRB TRL CO M - CO M +

P8 P4 P3 P2

Connect to PR-300 Connect to RAX-332


Connect to Unfiltered
Remote trouble 24V supply
indicator

Figure 8 Main Board (3 loop model) Cable Connectors and Jumper Locations

25
Installing Adder Modules

6.2 Connectors and Jumpers on the Main Fire Alarm Board

P8 Cable from P1 of the PR-300 Polarity Reversal and City Tie Module connects here.
Otherwise not used.
P4 Cable from connector P1 of the RAX-332 Display Adder Module connects here.
Otherwise not used.
JW1 On the Main Fire Alarm Module, this jumper is not used, open.
JW2 Remove this jumper if a remote annunciator is used.
JW3 Not used, open.
JW4 Not used, open.
JW5 Normally open. Place jumper here and power down (AC and batteries) and power back
to restore Master Passcode. After reset, remove jumper and leave normally open.
JW6 Normally open to BLOCK remote configuration via modem. Place jumper here to
ALLOW for remote configuration.
JW7 On the Main Fire Alarm Module, this jumper must be removed if a PR-300 Polarity
Reversal and City Tie Module is installed.
JW8 Not used, open.
JW9 Not used, open.
JW10 Not used, open.
JW11 Not used, open.
JW12 Not used, open.

6.3 OCAC-304 Output Class A Converter Adder Module

Mounting hole
for #6-32 screw
Wire to Main Board
OCAC-304
- SIG2 OUT+ - SIG1 OUT+

- SIG2 RET+ - SIG1 RET+


BLK RED
BLK RED

- SIG4 OUT+ - SIG3 OUT+

- SIG4 RET+ - SIG3 RET+


BLK RED
BLK RED

Mounting hole
for #6-32 screw

Figure 9 OCAC-304 Output Class A Converter Adder Modules

Indicating circuits must be wired from the OCAC-304 to the main Fire Alarm board. For
example indicating circuit 1 positive (red wire) and negative (black wire) is wired from the
Class A Converter Module to the positive and negative terminals of Indicating circuit 1 on the
Main Fire Alarm board.

26
Installing Adder Modules

The actual indicating zone is wired from the SIGNAL OUT positive and negative to the
signaling devices and then wired back to the SIGNAL RET positive and negative.

6.4 Polarity Reversal and City Tie Module (Model PR-300)

Mount the PR-300 on the left side panel of the backbox with the two screws provided, refer to
Figure 10.

Mounting hole for

+ | -
#6-32 screws

CITY
TIE
REVER SAL REVER SAL
POLAR ITY POLAR ITY
+ | -
P1 P2

ALAR M
Mounting hole for
#6-32 screws

+ | -
SU PV
JW4

Figure 10 Polarity Reversal and City Tie Module

6.4.1 PR-300 Cable and Jumper Settings


The following hardware configuration must be performed before installing the PR-300.

P1 Cable connects to P8 (bottom left-hand corner) on the Main Fire Alarm


Board.
JW4 Not used. Keep jumper intact.

The Alarm Transmit signal to the PR-300 can be programmed to turn OFF when signal silence
is active. This allows the City Tie Box to be manually reset. On subsequent alarms the
silenceable signals will resound and the City Tie Box will be retriggered.

The Trouble Transmit signal to the PR-300 can be programmed to delay AC power fail 0, 1, 2,
or 3 hours if this is the only system trouble.

6.5 RAX-332 Display Adder Module

The RAX-332 Display Adder Module is used only with the FX-351 and FX-353 Fire Alarm
Panels. No jumpers or other physical configuration steps are required to install this second
RAX-332 Display Adder Module. Remove the blank cover plate from the front door and install
the RAX-332 with the clear cover in the opening with the hardware provided. Disconnect main
and standby power and connect the cable of the second RAX-332 into the open, remaining
header of the existing RAX-332. The additional LEDs will be available for configuration as
LEDs 33 to 64, when the system power is restored.

27
7.0 Circuits and Devices
7.1 Addressable/Analog Devices

The FX-350 supports up to 3 loops of addressable/analog devices. The device loop can be
used to connect up to 60, 126 or 378 analog devices and addressable input or output modules
on an unshielded twisted pair (UTP). The devices must be compatible with the Mircom device
protocol.

The loop interface software continuously supervises the devices on its loop against those
found during configuration for the following conditions:

device missing
unconfigured device responding
two or more devices responding to the same address
wrong device type
A communication or addressing error on a device is reported as a trouble on the associated
zone LED if configured.

The addressable loop can be configured for class A or B operation. "T-tapping" is allowed
(Refer to device installation documentation for details).

Devices on the loop have an optional LED which normally flashes when the device is polled
and goes ON steady when the device is active (alarm for an input device or active for an
output device). The flashing of the LED on polling for sensors can be suppressed during
configuration. For input or output modules, the LED always flashes when polling. The software
limits the maximum number of the devices which can have their LED turned ON when active to
fifteen (15).

Certain devices are designed to support an optional external LED, which operates when the
LED on the device is activated. Remote/external LEDs must NOT be used on this system. The
panel can provide up to 350mA of current to the devices on the loop. A maximum line loss of 5
volts is permitted, so the loop distance, wire size, and maximum number of devices are limited
by this constraint.

The devices should be installed using unshielded twisted pair (UTP). The total line drop on the
loop must not exceed 5 volts at the last device. The calculations required to determine the
maximum permissible loop wiring distance with various combinations of devices is relatively
complicated, and when isolators are used, includes a consideration of device inrush currents
which must not exceed 20mA for a single isolator. In no case should more that twenty devices
be connected to a single isolator. To simplify the calculation process, please utilize the loop
calculator program located on the Mircom website at http:/www.mircom.com in order to
determine maximum loop lengths, number of devices, and wire sizes etc.

It is also important to note that the device LEDs present a significant extra load on the loop
which must be considered in calculating permissible loop lengths, battery capacities, etc.
Please refer to the device Installation Instructions and other documentation provided with the
addressable devices, bases, and isolators for further information. The system will
automatically limit the maximum number of device LEDs which can be illuminated to
15.

28
Circuits and Devices

7.2 Analog Devices

The system supports Mircom MIX-3000 Series photo, ion, multi-sensor and thermal (heat)
type analog detectors, as well as contact input and output devices. The detectors may be
configured as non-verified or verified alarm inputs. To determine an alarm condition, the
system polls the analog device and compares the analog value against stored thresholds for
pre-alarm and alarm conditions.

A range of thresholds is provided for each type of analog device (except for contact devices),
corresponding to the agency approved range of threshold for a particular device type. Each
device can be individually configured to a value in the range of threshold for day time and
one for the night time or after hours operation; i.e. a device may be configured to a low
sensitivity for day time and high sensitivity at night time. The day time threshold will be used
unless the after hours operation is active.

7.2.1 Drift Compensation


The FX-350 will automatically adjust for gradually increasing affects of dust and other
accumulations of dirt in the detectors. It will adjust the thresholds to compensate for a detector
going dirty according to the gradual change in the normal clean air value received. When it can
no longer compensate for an increasingly dirty detector, a dirty detector trouble is indicated for
that device.

7.2.2 Auto Test


Periodically each detector is commanded to return an alarm value to test its ability to alarm. If
it fails the test, a trouble is indicated on that device.

7.3 Contact Inputs


Contact input modules on the addressable/analog device loop may be configured as any of
the following input types:

non-verified alarm inputs latching supervisory inputs trouble only inputs


waterflow inputs monitor inputs remote switch inputs
non-latching supervisory inputs

7.4 Contact Outputs

Contact output modules on the addressable/analog device loop may be configured as any of
the following output types:

signals
strobes
relay outputs
Analog devices may be installed with relay or sounder bases. The outputs of these bases are
activated when the device active LED turns ON steady in response to an alarm. The command
to activate the output is separate from the command that activates the LED and they are not
subject to the same restrictions as the LED. Output modules configured as signals are not
stroked by software at the current signal rate. When the system commands them to be either
in alert or in evacuation, the panel will simply activate them continuously. It is possible to
provide stroked operation by connecting the signal power to a conventional signal output
which is stroking at the correct rate when the device is active. Depending on the device, the
system can detect open and short troubles and report it as an output circuit trouble.

29
8.0 Field Wiring
Table 2 Settings permitted in CAN/ULCS527

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES

This product incorporates field-programmable software. In order for the product to comply with the
requirements in CAN/ULCS527, Standard for Control Units for Fire Alarm Systems, certain programming
features or options must be limited to specific values or not used at all as indicated below.

Program feature or Permitted in CAN/ Settings permitted in


Possible settings\methods
option ULCS527? (Y/N) CAN/ULCS527

JW4 (Orange Wire) Intact =


Buzzer silence & Lamp Test
local function only. System
System Reset and Reset & Signal Silence are Leave JW4 intact on
Signal Silence on RAM- N disabled. RAM-208/216
208/216
Cut Jumper (Orange Wire) to
have all remote functions
operate.

8.1 Main Fire Alarm Board Field Wiring

Wire devices to the addressable loop as shown in Figure 11 for Class B (Style 4) or Figure 12
for Class A (Style 6). Refer to Table 3 for loop wire gauges. Wire devices to addressable
loops 2 and 3, if available, in the same manner.
+

CLASS B
WIRING
B
-
Loop
A

+
-

ION SMOKE
DETECTOR
OUTPUT MODULE
PHOTO SMOKE
DETECTOR

HEAT DETECTOR PULL STATION

Figure 11 Addressable Loop Wiring - Class B or Style 4

30
Field Wiring

Table 3 Loop Wiring Table

This Loop Wiring Table is for reference only and should


UNSHIELDED LOOP TOTAL (OUT not be used without a detailed loop calculation.
TWISTED PAIR AND IN) WIRE RUN
WIRE GAUGE Maximum Loop Current: 350 mA
AWG FEET METRES Maximum Loop Resistance: 35 subtract 0.2 Ohms per
12 20,000 6098 isolator.

14 15,942 4859 Maximum Loop Capacitance: 0.5 F

16 9960 3036 Maximum Number of Isolators is 40.


18 6265 1910

8.2 Loop Isolators

To limit the number of addressable devices compromised by a short on the addressable loop,
isolators (MIX-100X, 100XH, or 100XB) may be used to isolate the affect of the short circuit. If
the impact of a short circuit must be limited to only one device, an isolating base must be used
for each detector. A maximum of twenty devices can be connected between isolators, or
between the panel and the first isolator, as long as the maximum in-rush current for the
devices on one segment of the loop does not exceed 20 mA. Refer to the installation
instructions for addressable devices for additional details.
+

CLASS A
B

WIRING
-
Loop
A

+
-

ION SMOKE
DETECTOR
OUTPUT MODULE
PHOTO SMOKE
DETECTOR

HEAT DETECTOR INPUT MODULE

Figure 12 Addressable Loop Wiring - Class A or Style 6

8.3 Loop Operation

When there is a short circuit on the Class A loop with isolators installed, the isolators isolate
the shorted fault, the panel detects it as an open loop and generates an open loop trouble.

31
Field Wiring

When a Class A loop is opened there may be a few missing devices reported by the panel
which will be restored once the panel has established the Class A connection.

i Note: When there is an "Open loop trouble" look for both open and shorts on the loop.
As a guide line the isolators which are activated in response to a short will have
their LED ON; look for the short between the two isolators with their LEDs ON.

8.4 Indicating (Powered Output) Circuits

Powered output circuits can be configured as signal, strobe or relay outputs. Powered output
circuits are supervised while they are not active for both open circuits and shorts. The circuit
will not actually be activated if there is a short trouble on the circuit. It will be activated if an
open trouble is indicated. Since open circuit supervision does not operate while the circuit is in
alarm, if the circuit was in trouble before it was activated, it will still indicate trouble while
active. The trouble condition will be re-evaluated when supervision resumes.

Output circuits configured as strobes can have sync protocol for synchronization if configured.
Certain strobe and strobe/horns models of the following manufacturers are supported.

All normal non-sychronized horns


Faraday
System Sensor
Wheelock
Gentex
Mircom
When configured as normal, the output circuit is ON continuously when activated and does not
use any sync protocol. When configured as non-silenceable strobes, the strobes cannot be
silenced, but the horn can be silenced by pressing the 'signal silence' button

If the strobe is configured as silenceable strobe both the horn and the strobe are silenced
(stopped) by pressing the 'signal silence' button

8.5 Indicating Circuit Wiring

The FX-350 Series Addressable Fire Alarm Panel supports Class B (Style Y) and Class A
(Style Z) wiring for its indicating circuits. Each circuit is supervised by a 3.9K End-of-Line
resistor. Each indicating circuit provides up to 1.7 Amperes, total 5 Amperes of current
maximum if no auxiliary power is used. Wire indicating circuits as in Figure 11 for Class B
(Style Y) or as in Figure 12 for Class A (Style Z).

Table 4 Maximum Wiring Distances

TOTAL MAXIMUM WIRING RUN TO LAST DEVICE (ELR) MAX. LOOP


SIGNAL RESISTANCE
LOAD 18AWG 16AWG 14AWG 12AWG

Amperes ft m ft m ft m ft m Ohms

0.06 2350 716 3750 1143 6000 1829 9500 2895 30

0.12 1180 360 1850 567 3000 915 4720 1438 15

0.30 470 143 750 229 1200 366 1900 579 6

32
Field Wiring

Table 4 Maximum Wiring Distances

TOTAL MAXIMUM WIRING RUN TO LAST DEVICE (ELR) MAX. LOOP


SIGNAL RESISTANCE
LOAD 18AWG 16AWG 14AWG 12AWG

0.60 235 71 375 114 600 183 950 289 3

0.90 156 47 250 76 400 122 630 192 2

1.20 118 36 185 56 300 91 470 143 1.5

1.50 94 29 150 46 240 73 380 115 1.2

1.70 78 24 125 38 200 61 315 96 1.0

i Notes: For Class A wiring the resistance in ohms is multiplied by two.

Maximum voltage drop should not exceed 1.8 volts.

FIRE PANEL MAIN BOARD


STYLE Y
WIRING
- SIG 2 + - SIG 1 +

INDICATING INDICATING
CIRCUIT #1 CIRCUIT - 1

INDICATING
STYLE Y
CIRCUIT #2
WIRING

INDICATING
CIRCUIT - 2

BELL STROBE HORN 3 .9 K 1 /2 W A T T E L R

NOTE: WIRE INDICATING CIRCUITS # 3 AND #4 IN THE SAME WAY AS


#1 AND #2

33
Field Wiring

Figure 13 Indicating Circuit Class B or Style Y Wiring

STYLE Z
FIRE PANEL MAIN BOARD WIRING

INDICATING
CIRCUIT 1

OUT+
BLK RED
SIG 1

- SIG2 RET+ - SIG1 RET+


INDICATING +

- SIG1
CIRCUIT #1
-

OUT+
BLK RED
+
SIG 2

INDICATING
CIRCUIT #2

- SIG2
-
STYLE Z
WIRING

2 MORE INDICATING
CIRCUITS NOT SHOWN INDICATING
CIRCUIT 2

OCAC-304 CLASS A
CONVERTER MODULE

BELL

NOTE: WIRE INDICATING CIRCUITS # 3 AND #4 IN THE SAME WAY


STROBE
AS #1 AND #2
HORN

Figure 14 Indicating Circuit Class A or Style Z Wiring

8.6 Dialer Wiring

If you have Fire Alarm Panel model FX-350-60-DR, FX-350-126-DR, FX-350-378-LDR, FX-
351-LDW or FX-353-DR, there is a dialer on board and terminals marked Line 1 and Line 2
must be wired as shown in Figure 15 below. Terminals are located in the top left hand corner of

34
Field Wiring

the main fire alarm board, from the top down. Refer to Figure 6 and Figure 7 for terminal
locations.

FIRE ALARM MAIN BOARD

RJ31X
GREEN
T
1 4
TIP
CO

RED 2 3
R

LINE-1
BROWN
RING
T
RES

7 6
GREY 8 5 Public switch
R

Telephone company
wiring
TIP
T
CO

RING
R

LINE-2 premise telephone


IF permitted
T
RES

Line 2 is Wired as shown for Line 1


R

Figure 15 Dialer Wiring

Refer to Chapter 13.0 Dialer Operation on page 58 and Chapter 15.0 Appendix B:
Reporting on page 60 for more information regarding the built-in dialer.

35
Field Wiring

8.7 Polarity Reversal and City Tie Module (PR-300) Wiring

Wire the PR-300 Polarity Reversal and City Tie Module (if used) as shown in Figure 16 below.
Power Limited cable type FPL, FPLR or FPLP must be used. For USA installation, the installer
must use Atlantic Scientific (Tel: 407-725-8000), Model #24544 Protective Device, or
similar UL-Listed QVRG secondary protector, as shown. For use in Canada, the Protective
Device is not required but still recommended.

PR-300

+ PROTECTOR
1 1 +
CITY TIE LOCAL ENERGY USE A SHORTING WIRE
RATED - 24VDC FILTERED WHEN THE CITY TIE IS NOT
TRIP COIL - 14 Ohms, 210mA, 2 2 - USED
5mV RIPPLE
-

UNPROTECTED
S S

PROTECTED
NOT POWER LIMITED
+
POLARITY REVERSAL ALARM
1 1 +
24VDC OPEN
12VDC AT 3.5mA
8mA MAX. SHORT
2 2 -
- POWER LIMITED S S CONFORMS TO NEMA STANDARD
+ SB3-1969 INTENDED FOR
CONNECTION TO POLARITY
POLARITY REVERSAL SUPV .
REVERSAL CIRCUIT OF A REMOTE
24VDC OPEN
STATION RECEIVING UNIT HAVING
12VDC AT 3.5mA DIN RAIL CONNECTION
8mA MAX. SHORT COMPATIBLE RATINGS
TO EARTH GROUND
- POWER LIMITED PROTECTOR
1 1 +
2 2
-
UNPROTECTED

S S
PROTECTED

1 1 EITHER THE CITY TIE or


POLARITY REVERSAL
2 2 INTERFACE MAY BE
USED, NOT BOTH.
S S

DIN RAIL CONNECTION


TO EARTH GROUND

NOTES:
1. Plug PR-300 ribbon cable P1 into connector P8 of the Main Fire Alarm board.
2. Cut Jumper JW1 on the PR-300 Polarity Reversal and City Tie Module in order to
transmit a trouble condition from the Polarity Reversal Alarm terminals to the
monitoring station.
3. Cut Jumper JW2 on the PR-300 Polarity Reversal and City Tie Module in order to
transmit a trouble condition from the Polarity Reversal Supervisory terminals to the
monitoring station.
4. Remove jumper plug from JW7 on the Main Fire Alarm board.
5. For USA installation, the installer must use an Atlantic Scientific (Tel. 407-725-8000),
Model #24544 Protective Device or similar UL-Listed QVRG secondary protector.
6. The Polarity Reversal interface is Power Limited and must use power limited cable
type FPL, FPLR or FPLP from the PR-300 to the Protectors.

Figure 16 Polarity Reversal and City Tie Module Terminal Connection

36
Field Wiring

8.8 Auxiliary Power Supplies

8.8.1 Aux 2 Resettable Auxiliary Power (supervised, regulated)


The AUX 2 resettable auxiliary power supply is supervised for shorts, therefore a short will
disconnect the power until the RESET button is pressed. A trouble signal will be generated if
there is a short. The circuit must be supervised for opens utilizing the End of Line Relay Model
PAM-3 as shown in Figure 17. This supply is rated at 21.1 VDC regulated / 300 mA max / 1 V
voltage drop maximum.

8.8.2 Auxiliary Supply (supervised, regulated)


Supervised auxiliary power is used to power the remote annunciators and smart relay
modules. This filtered circuit is supervised for shorts, therefore a short will disconnect the
power until the RESET button is pressed. A trouble signal will be generated if there is a
short. The circuit must be supervised for opens utilizing the End of Line Relay Model PAM-3 as
shown in Figure 17. This supply is rated at 21.1 VDC regulated / 500 mA max / 1 V voltage
drop maximum.

8.8.3 Unfiltered Supply (unsupervised, unregulated)


This unregulated supply is not supervised. When required, it is recommended that the circuit
be supervised for opens utilizing the (UL listed - S3403) End of Line Relay Model PAM-3 as
shown in Figure 17. This supply is rated at 24 VDC / 1.7 A max. If there is a short on this
circuit, the auxiliary power does not recover automatically when the short is removed. The
main power and the battery must be disconnected, then reconnected and the panel reset to
re-establish the auxiliary power supply.

FIRE ALARM MAIN BOARD


Supervision for Auxiliary Supplies
AUX 2
RESETTABLE + Class B (Style B)
AUXILIARY
POWER
- Connect auxiliary devices here* WIRING
DETECTOR POWER SUPPLY
6 5
22VDC, 200mA
OR MAX. CURRENT - 300mA
AUXILIARY MAX. RIPPLE VOL. 5mV 2
(POWER LIMITED)
* Use this supervision 3

SUPPLY set-up only if auxiliary 1


4
OR devices are used
UNFILTERED END OF LINE RELAY
SUPPLY E.O.L.
47K Ohms

MINI MONITOR
MODULE
Red Violet
MIX-101P
White
+

Red
B
+ -

Black
Loop
A

Black

ION SMOKE PHOTO SMOKE


HEAT DETECTOR
LEGEND DETECTOR DETECTOR

Figure 17 Supervision Of Auxiliary Supplies

37
Field Wiring

8.9 Power Supply Connections

The power supply is located directly behind and below the main board. The ratings are:

Electrical Input rating 120 VAC, 60Hz, 1.73A / 240VAC, 50Hz, 0.864A
Battery fuse on Main module 10A, slow blow micro fuse (not replaceable)

! Caution: The main AC branch circuit connection for the Fire Alarm Control Unit must
provide a dedicated continuous power without any disconnect devices. Use
#12 AWG wire with 600-volt insulation and proper over-current circuit
protection that complies with the local codes. Refer to 16.0 Appendix C:
Specifications on page 62 for specifications.

i Note: Ensure that the AC supply is disconnected before wiring the power to the panel.
Wire the AC power to the AC wiring terminals as shown in Figure 18 using the
proper wire gauge. Fire alarm systems must be installed in compliance with local
codes and standards and with the Authority Having Jurisdiction (AHJ)

TRANSFORMER
POWER SUPPLY

RTI UNFILTERED
JW7 RIBBON CABLE PORT FWR 24VDC
TO PR-300 MODULE
P3 P2 TRB TRL COM- COM+

POWER P5
CONNECTOR P6
Yellow
240VAC 50Hz
Red
120VAC 60Hz
BATTERY SEC TX Black
- N
P3 +

Green
P1

P2
P4

POWER SUPPLY BOARD Ground

RED BLACK
RED

+ - + -
AC WIRING TERMINALS

BATTERY BATTERY

Figure 18 Main Power Supply Connections

i Note: The FX-350 panel is capable of being wired for 120 VAC or 240 VAC 50/60 Hz
as shown above. A good ground connection to the Ground" terminal is
essential to electrical safety, ensure proper operation, and specified noise
immunity.

38
Field Wiring

8.10 Connecting to a 3G4010 Interface Device for Canada

A typical connection is shown in Figure 19. The PCS-100 Passive Communications Interface
Board (sold separately) is required.

For information on Compatible DACR Receivers see 14.0 Appendix A: Compatible


Receivers on page 59.
FX-350 - 3G4010 Connection - Typical Diagram

Telephone
To GSM/GPRS
Line A
Connection

Line 1 Line 2 Internet


C.O. C.O.

T1
R1
ALARM NO Z1
RELAY C

SPV NO Z2
RELAY C

FX-350 TRBL
RELAY
NO
C
Z3

3G4010 Router

COM Computer
SG-Systems
Console 2.1
JW1

+ AUX SUPPLY
GND
24V
POWER

PGM4 GND 14V

- PCS-100
PGM4
NC COM NO

TBL RELAY

EOL SUR-GARD
(-) Printer
DC IN SYSTEM IV
(+)
Internal IP : X.X.X.X
Addressable module External IP : X.X.X.X
configured as 3G4010 Default Gateway : X.X.X.X
radio trouble Sub-Net Mask:X.X.X.X
Port #: YYYY (UDP)

3G4010 TRBL
Typical Installation in Canada
- All units must be installed in the same room
- All extended wiring must be in metallic conduit
- Wiring between FACP and 3G4010:18 m max.
- Contact DSC to reprogram the zone inputs to match
the FACP as shown in this diagram

Figure 19 Connecting an FX-350 FACP to a 3G4010 Interface Device

i Note: The DSC interface device 3G4010 is required if the installation requires ULC
S559 certification. The DSC interface device 3G4010CF is required if the
installation requires UL864 9th edition certification.

39
Field Wiring

8.11 Connecting to a 3G4010CF Interface Device outside Canada

For information on Compatible DACR Receivers see 14.0 Appendix A: Compatible


Receivers on page 59.

A typical connection is shown in Figure 20. The 3G4010CF is powered separately from the
PCS-100 and requires 2 DSC RM-2 relays (sold separately). The PCS-100 Passive
Communications Interface Board (sold separately) is also required.
FX-350 - 3G4010CF Connection - Typical Diagram

Telephone
Line A
Connection
To GSM/GPRS

Line 1 Line 2
C.O. C.O.
T1
R1

ALARM NO Z1 Internet
RELAY C

SPV NO Z2
3G4010CF
RELAY C

FX-350 TRBL NO Z3
RELAY C

PS4086
COM Router
AC IN
JW1

+ AUX SUPPLY +12V COM ACT LBT BAT+ BAT-


GND
24V
POWER

PGM4 GND 14V

Computer
- PCS-100 SG-Systems
PGM4
+
NC COM NO

TBL RELAY

Console 2.1
DC IN
EOL -

Printer SUR-GARD
SYSTEM IV
Transformer Battery Internal IP : X.X.X.X
Addressable
External IP : X.X.X.X
module configured Default Gateway : X.X.X.X
as 3G4010CF radio Sub-Net Mask:X.X.X.X
3G4010CF trouble
TRBL - - Port #: YYYY (UDP)
+
+

DSC DSC
RM-2 RM-2
Relay Relay

NC COM NO NC COM NO

EOL EOL

3G4010CF 3G4010CF
Typical Installation outside Canada
TRBL TRBL
Addressable module
configured as AC - All units must be installed in the same room
failure trouble - All extended wiring must be in metallic conduit
Addressable module - Wiring between FACP and 3G4010CF: 20 feet max.
configured as low - Contact DSC to reprogram the zone inputs to match the
battery trouble FACP as shown in this diagram
- Use 2 DSC RM-2 Relays (sold separately) to supervise
both AC failure trouble and low battery trouble
- Install the DSC RM-2 Relays inside the 3G4010CF
enclosure above the PS4086

Figure 20 Connecting an FACP to a 3G4010CF Interface Device outside Canada

i Note: The DSC interface device 3G4010 is required if the installation requires ULC
S559 certification. The DSC interface device 3G4010CF is required if the
installation requires UL864 9th edition certification.

40
9.0 System Checkout
9.1 Before turning the power ON

To prevent sparking, do not connect the batteries. Connect the batteries after powering the
system from the main AC supply.

1. Check that all adder modules are installed in the proper location with the proper
connections.
2. Check all field (external) wiring for opens, shorts, and ground.
3. Check that all interconnection cables are secure, and that all connectors are plugged in
properly.
4. Check all jumpers and switches for proper setting.
5. Check the AC power wiring for proper connection.
6. Check that the chassis is connected to earth ground (cold water pipe).
7. Make sure to close the front cover plate before powering the system from main AC
supply.
The best way to set up a panel for the first time is to avoid connecting any field wiring at first.
To begin set up, power up the panel with end of line resistors connected where appropriate,
then connect the battery. The panel will show System Restart Active. Press System Reset
button to reset the panel. If the panel is free of trouble, connect one circuit at a time, checking
for troubles each time. If a trouble occurs at any point during the set-up, correct the fault, then
continue connecting the field wiring.

9.2 Power-up procedure

After completing the system checkout procedures outlined above,

1. Power up the panel. The "AC-ON" green LED and the Common Trouble LED should
illuminate, and the buzzer should sound. Press the System Reset button. Since the
batteries are not connected, the trouble buzzer should sound intermittently and the
common trouble LED should flash.
2. Connect the batteries while observing correct polarity: the red wire is positive (+) and
black wire is negative(-). All indicators should be OFF except for normal power "AC ON"
green LED.
3. Configure the Fire Alarm Control Panel as described in the System Configuration
section.

41
10.0 Troubleshooting
Symptoms Possible Cause

Circuit Trouble Normally when a circuit trouble occurs, its designated trouble indicator will be illuminated, as
well as the common trouble indicator and trouble buzzer. To correct the fault, check for open
wiring on that particular circuit loop or that the Circuit Disconnect Switch is in the ON or
CLOSED position. Note: Disconnecting a Circuit will cause a system trouble (off-normal
position).

Remote Trouble Remote Trouble will be indicated on the main panel display for any failure reported by, or
failure to communicate with a remote annunciator or other remote device.

Ground Fault This panel has a common ground fault detector. To correct the fault, check for any external
wiring touching the chassis or other Earth Ground connection.

Battery Trouble Check for the presence of batteries and their conditions. Low voltage (below 20.4V) will
cause a battery trouble. If battery trouble condition persists, replace batteries as soon as
possible.

Walk Test Mode If the Walk Test LED is illuminated steadily, the system is in Walk Test Mode.

Common Trouble If only a common trouble is indicated on the main panel and none of the above confirming
trouble indicators are ON, check the following for possible fault:
Check for any missing interconnection wiring.
Check for any Module missing that was part of the Configuration.
Check for improperly secured cabling.

42
11.0 Indicators, Controls and Operations
Figure 21 below shows the common display panel for both the FX-350, FX-351 and the FX-
353 Fire Alarm Control Panels.

SYSTEM NORMAL
DEC 03, 2009 02:41AM

AC ON
1 2 3 X
ABC DEF
COMMON ALARM

COMMON S UP V 4 5 6 M
GHI JKL MNO
COMMON
TROUBLE
7 8 9 ?
PRS TUV WXY
CP U FAULT

GROUND * 0 #
FAULT QZ

S Y S TE M S IGNAL
RE S E T S I L E NCE

FIRE ALM/SUP/TBL/
DRI LL BLDG AUDIBLE SIL

AUTOMATIC ALARM LAMP


SIGNAL CANCEL TE S T

GE NE RAL BATTERY/CHARGER
ALARM TROUBLE

Figure 21 LCD Display, LED indicators and control buttons

The display panel on the FX-350/FX-351/353 main fire alarm control board consists of:

a two line by twenty character LCD display


a sixteen button keypad
common LED Indicators
common control buttons
FX-351 and FX-353 models are equipped with one RAX-332 LED display adder (32 zone
annunciation), with provision for a second optional adder (see section 4.1 Panel Models on
page 13 for further explanation) for another 32 zone annunciation for a total of 64 zone
annunciation. Each LED zone has a red/amber alarm/supervisory LED and an amber trouble
LED.

LED Indicators may be amber, red, or green, and may illuminate continuously, or at one of
following Flash Rates:

Steady (Alarm) - ON continuously.


Fast Flash (Supervisory) - 120 flashes per minute, 50% duty cycle.
Trouble Flash (Trouble) - 20 flashes per minute, 50% duty cycle.
Red indicators are used for Alarm, amber indicators for Trouble or Supervisory and green for
power ON.

i Note: Each RAX-332 display is supplied with blank paper labels (#NP-681) for sliding
into the plastic label template on the display.

43
Indicators, Controls and Operations

11.1 Common Indicators

11.1.1 Buzzer
The Buzzer is activated by any of the following:

Fire Alarm: Steady


Supervisory Alarm: Fast flash rate
Trouble: trouble flash rate
Property and Building Safety: Configurable to sound at trouble flash rate

11.1.2 AC On LED
The AC On LED illuminates steady green while AC ON

the main AC power is within acceptable levels. It


turns off when the power level falls below the COMMON ALARM

power-fail threshold and the panel switches to


standby (battery) power. COMMON SUPV

11.1.3 Common Alarm LED COMMON


TROUBLE

The Common Alarm LED illuminates steady red CPU FAULT


whenever the panel is in alarm. An alarm results
from any alarm on any point or input programmed GROUND
FAULT
as alarm or activation of the manual General
Alarm button. Since all alarms are latched until the
alarm conditions are cleared and the panel is
reset, the LED will remain ON until then. SYSTEM
RESET

11.1.4 Common Supervisory LED


The Common Supervisory LED flashes amber at the Supervisory or Fast Flash rate when
there is a supervisory alarm in the panel resulting from any un-bypassed latching or non-
latching supervisory circuit. The LED turns OFF if all non-latching Supervisory Circuits are
restored and there are no active latching supervisory circuits. Latching supervisory alarms
remain active until the panel is reset.

11.1.5 Common Trouble LED


The Common Trouble LED flashes amber at the Trouble Flash rate when the panel detects
any trouble condition in the system. The LED turns OFF once all troubles are cleared.

11.1.6 CPU Fault LED


The CPU Fault LED flashes amber at the Trouble Flash rate when the panel detects a fault on
the CPU. It is turned OFF when the CPU fault is corrected.

11.1.7 Ground Fault LED


The Ground Fault LED flashes amber at the trouble flash rate when the Ground Fault Detector
detects a ground fault on any field wiring. It turns off immediately after the ground fault is
cleared.

11.1.8 System Reset LED


The amber System Reset LED will illuminate steadily after the system reset button has been
pressed and the system is resetting.

44
Indicators, Controls and Operations

11.1.9 Signal Silence LED S Y S TE M S IGNAL


RE S E T S I L E NCE

The Signal Silence LED flashes


amber at the Trouble Flash rate FIRE ALM/SUP/TBL/
DRI LL BLDG AUDIBLE SIL

after indicating circuits are silenced


AUTOMATIC ALARM LAMP
either by the Signal Silence button, SIGNAL CANCEL TE S T

or by the Auto Signal Silence Timer. GE NE RAL BATTERY/CHARGER

It turns OFF after the signals are re- ALARM TROUBLE

sounded by a subsequent alarm.


For Canadian installations, disable Auto Signal Silence.

11.1.10Fire Drill LED


The Fire Drill LED turns ON steady amber while Fire Drill is active.

11.1.11ALM/SUP/TBL/BLDG AUDIBLE SIL LED (Buzzer Silence)


The ALM/SUP/TBL/BLDG AUDIBLE SIL LED flashes amber at the Trouble Flash rate when
the ALM/SUP/TBL/BLDG AUDIBLE SIL button is pressed. Any new alarm, supervisory or
trouble events will resound the buzzer and will cause the ALM/SUP/TBL/BLDG AUDIBLE SIL
LED to turn off.

11.1.12AUTOMATIC ALARM SIGNAL CANCEL LED (Acknowledge)


If the panel is configured as a two stage system, the AUTOMATIC ALARM SIGNAL CANCEL
LED turns ON steady amber after the Auto General Alarm Timer is cancelled by the activation
of the AUTOMATIC ALARM SIGNAL CANCEL or Signal Silence buttons. If the Auto General
Alarm Timer times out and puts the panel into General Alarm, the AUTOMATIC ALARM
SIGNAL CANCEL LED turns OFF. If the panel is configured as Positive Alarm Sequence
(PAS), the AUTOMATIC ALARM SIGNAL CANCEL LED flashes amber at the Fast Flash rate
while a timer counts down 15 seconds to common alarm.

11.1.13General Alarm LED


The red General Alarm LED illuminates steadily after the General Alarm button is pressed, a
general alarm initiating circuit is activated, or the Auto General Alarm timer times out. Once
the General Alarm LED turns on, it will stay active until the panel is reset.

11.1.14Lamp Test LED


The amber Lamp Test LED will illuminate steadily after the Lamp Test button is pressed and
while system is in Lamp Test mode.

11.1.15Battery/Charger Trouble LED


In a ULI application the amber Battery/Charger Trouble LED flashes at the Trouble Flash rate
when any Battery/Charger Trouble occurs.

In a ULC application the amber Battery/Charger Trouble LED illuminates steady when any
Battery/Charger Trouble occurs.

11.1.16LEDs 1 to 32 for FX-351 and FX-353 Series Only


Points labelled 1 to 32 are available for alarm, supervisory, and property and building safety
annunciation (bi-coloured red/amber LEDs) and trouble annunciation (amber LEDs).

11.1.17RAX-332 LEDs 33 to 64 for FX-351 and FX-353 Series Only


Points labelled 33 to 64 are available for alarm, supervisory, and property and building safety
annunciation (bi-coloured red/amber LEDs) and trouble annunciation (amber LEDs).

45
Indicators, Controls and Operations

11.2 Common Controls

11.2.1 LCD Display


The display is a two line, 20 character back-lit alphanumeric LCD. It displays information
regarding the panel, its circuits, and devices. An on-screen cursor is controlled by the cursor
buttons (located to the right of the display) for menu selection and control. Report information
provided by the LCD display includes Alarm, Event Log, Current Levels, Verification, and
Maintenance reports.

11.2.2 Cursor Buttons


Located at key number 2, 8, 6 and 4. The cursor
buttons Up (next), Down (previous), Right, and Left 1 2 3 X
allow you to select items on the LCD display. The Up ABC DEF

and Down buttons scroll through lists in a continuous


loop. 4 5 6 M
GHI JKL MNO

11.2.3 Enter Button 7 8 9 ?


PRS TUV WXY
Use this button to select a displayed item on the LCD
display. * 0 #
QZ

11.2.4 Cancel Button X

Use this button to cancel an operation or exit a menu.

11.2.5 Menu Button M

Use this button to view the Command Menu.

11.2.6 Info Button ?

Push and hold this button to get detailed information about any displayed item.

11.2.7 Signal Silence Button


Pressing the Signal Silence button after the panel is in alarm turns ON the Signal Silence LED
and de-activates any silenceable indicating circuits. Non-silenceable circuits are unaffected.
Signals will re-sound upon any subsequent alarm. This button does not function during any
configured Signal Silence Inhibit Timer period. It also does not function if indicating circuits are
active as the result of a Fire Drill. In a two-stage system, the Signal Silence button silences the
stage 1 and stage 2 alarms.

11.2.8 Fire Drill Button


The Fire Drill button activates all programmed and non-disconnected indicating circuits, but
does not transmit any Alarms via the city tie or common alarm relay. The Fire Drill is cancelled
by pressing the button again (toggle switch), or if the panel goes into a true alarm.

11.2.9 General Alarm Button


Pressing the General Alarm button immediately sends the panel into General Alarm. It will also
re-activate the signals if they have been silenced during General Alarm initiated through an
46
Indicators, Controls and Operations

addressable device configured as General Alarm. The General Alarm condition remains active
until the panel is reset.

11.2.10System Reset Button


The System Reset button resets the panel and all circuits:

Resets Aux Resettable Power Supply Turns off all Indicating Circuits
Turns OFF Signal Silence, Ack & GA LEDs Turns off Fire Drill
Stops and resets all Timers Processes inputs as new events
Reset cannot be activated until the
Aux Disconnect is not affected Signal Silence Inhibit timer has
expired
Pressing Reset button after a PAS
Acknowledge will reset the system
and clear the alarm event.

! Attention: After power-up, press the System Reset button to bring the system to
normal and restore the system power up trouble.

11.2.11AUTOMATIC ALARM SIGNAL CANCEL Button (Two Stage or PAS only)


If the panel is configured for two stage operation, activation of the AUTOMATIC ALARM
SIGNAL CANCEL button while the Auto General Alarm Timer is timing (e.g. there is an alarm
in the panel but it is still in the first stage) cancels the timer and turns the AUTOMATIC ALARM
SIGNAL CANCEL LED ON steady amber. If the panel is configured for Positive Alarm
Sequence (PAS), activation of the AUTOMATIC ALARM SIGNAL CANCEL button within 15
seconds of a PAS alarm will delay a common alarm activation for 60 seconds.

11.2.12Lamp Test Button


Pressing and holding the Lamp Test button causes all front panel indicators to illuminate and
sounds the buzzer steadily. Bi-coloured LEDs will illuminate twice to show both colors. If lamp
test is active for more than ten seconds, the Common Trouble LED activates.

11.3 Single Stage Operation

In a single stage system, all alarm inputs are treated in a similar manner. Alarm inputs include
any of the following: non-verified alarm, verified alarm, waterflow alarm, and general alarm
circuits. Any of these alarm inputs occurring when the panel is not already in alarm cause the
following:

The buzzer sounds steadily


If fire drill is active, it is cancelled
The Common Alarm LED turns ON
The Common Alarm relay activates if Aux disconnect is not active
The Auto Signal Silence timer, if configured, starts. For Canadian installations, disable
Auto Signal Silence.
The Signal Silence Inhibit timer, if configured, starts
All non-disconnected indicating programmed to the input are activated provided that Aux
disconnect is not active

47
Indicators, Controls and Operations

Non-disconnected strobes associated with the input are activated


Non-disconnected signals associated with the input are activated at the evacuation rate
Pressing the General Alarm button on the panel also initiates a general alarm.

Subsequent alarms when the panel is already in alarm, cause the following:

The alert buzzer sounds steadily


If Signals have been silenced, they are resounded, the Signal Silence LED turns OFF,
and the Auto Signal Silence timer, if configured, is restarted. For Canadian installations,
disable Auto Signal Silence.
Any additional non-disconnected strobes associated with the input are activated
continuously
Any additional non-disconnected signals associated with the new input are activated at
the evacuation rate

11.4 Two-Stage Operation

In a Two-Stage system, alarm inputs are either First Stage (alert) inputs or Second Stage
(general alarm) inputs. First stage inputs include inputs from the following types of circuits:
non-verified alarm, verified alarm, and waterflow alarm. Second stage inputs include alarms
on the general alarm circuits, activation of the General Alarm button, or expiration of the Auto
General Alarm timer. Any of these alarm inputs occurring when the panel is not already in
alarm cause the following:

The buzzer sounds steadily.


If fire drill is active, it is cancelled.
The Common Alarm LED turns ON
The Common Alarm relay activates if Aux disconnect is not active.
The Auto Signal Silence timer, if configured, starts. For Canadian installations, disable
Auto Signal Silence.
The Signal Silence Inhibit timer, if configured, starts.
All non-disconnected outputs programmed to the input are activated provided that Aux
disconnect is not active.
If the alarm is a Second Stage alarm,

All non-disconnected strobe circuits are activated continuously, if correlated to an alarm


input.
All non-disconnected signal circuits are activated at the evacuation rate, if correlated to
an alarm input.
The General Alarm LED turns ON.
If the alarm is a First Stage alarm,

Non-disconnected strobe circuits programmed to that circuit are activated continuously.


Non-disconnected signal circuits programmed to that circuit are activated with the alert
code (see section 11.8 Output Types on page 53).
The Auto General Alarm timer, if configured, starts.
Subsequent First Stage alarms when the panel is already in alarm, cause the following:

The buzzer sounds steadily.


If signals have been silenced as a result of the silence button or the Auto signal silence
timer, signals are resounded as they were before signal silence, the Signal Silence LED

48
Indicators, Controls and Operations

turns OFF, and the Auto Signal Silence timer, if configured, is restarted. For Canadian
installations, disable Auto Signal Silence.
If the panel is not already in General Alarm, additional non-disconnected signals
programmed to the new input are activated with the Alert Code (see section 11.8 Output
Types on page 53).
If the panel is not already in General Alarm and if the AUTOMATIC ALARM SIGNAL CANCEL LED is
ON steady indicating that the Auto General Alarm timer has been acknowledged the timer is restarted
and the AUTOMATIC ALARM SIGNAL CANCEL LED is extinguished.
A second stage alarm (general alarm) when the panel is already in alarm causes the following:

The buzzer sounds steadily.


All non-disconnected signals are activated at the evacuation rate.
If the Signal Silence LED is ON, it turns OFF and the Auto Signal Silence timer, if
configured, is restarted. For Canadian installations, disable Auto Signal Silence.
The AUTOMATIC ALARM SIGNAL CANCEL LED if ON, turns OFF.
Alarm inputs are latching, they remain active until system reset.

i Note: All circuits with process type designated as signal are automatically correlated
to the fire drill and general alarm status.

11.5 Positive Alarm Sequence

In a Positive Alarm Sequence (PAS) system, only smoke detectors can be dedicated as PAS
inputs. PAS Inputs can only be from the following types of circuits: non-verified alarm and
verified alarm. Any of these alarm inputs occurring when the panel is not already in alarm
cause the following:

The buzzer sounds steadily.


If fire drill is active, it is cancelled.
The Common Alarm LED turns ON
The individual zone LED (if programmed) turns ON.
The Common Alarm relay does not activate.
The PAS timer starts for 15 seconds.
All outputs programmed to the input are not activated.
When the PAS alarm has been acknowledged within 15 seconds, the following sequence
occurs:

The buzzer is silenced.


The Common Alarm LED stays ON.
The individual zone LED (if programmed) stays ON.
The PAS timer starts for 180 seconds (3 minutes). This is the time allotted to reset the
system and avoid any true alarm sequence.
When the PAS alarm has been acknowledged and the system reset (and there are no new
alarms), within the given time limits, the following occurs:

The buzzer stays silenced.


The Common Alarm LED turns OFF.

49
Indicators, Controls and Operations

The individual zone LED (if programmed) turns OFF.


The alarm event is cancelled. No log reference.
The fire alarm system returns to normal.
If at any time during the Positive Alarm Sequence a second alarm (PAS or otherwise) is
actuated, the fire alarm will go into evacuation mode. In a preconfigured FACP the Positive
Alarm Sequence may be enabled or disabled as the user requires.

11.6 Enabling or Disabling the Positive Alarm Sequence

To enable or disable the Positive Alarm Sequence, from the Keypad of the FACP press
M to enter the Menu
Using the Up and Down Arrow buttons, scroll to Operation and press the enter key
In the Operation Menu scroll to Positive Alarm and press enter
You will now see displayed the current status of the Positive Alarm Sequence and will be
prompted to change status.

Pos Alarm disabled


Enable? Y

If you wish to change the status press the enter key.

i Note: There will be no notification message advising a change of status

If you do not wish to change the status, press the cancel key

11.7 Input Types

Table 5 shows input types available for programming.

Table 5 Input Types

Input Types Description


Non-Verified When an un-bypassed non-verified alarm input goes into alarm the common alarm
Alarm sequence is activated. Un-bypassed relay, signal, and strobe outputs are updated
according to their programming and alarm zone status indicators associated with the
input are activated. Alarm input activations are displayed on the shared display in the
common queue with alarm as the highest priority and is displayed first.
A pre-alarm condition on a device configured as an alarm input is displayed on the
shared display and on the alarm zone status indicator. If the pre-alarm condition is
restored the status will be cleared. If the input goes from pre-alarm to alarm, the pre-
alarm status will be replaced with the alarm status for the input.
Once an alarm input is in alarm the alarm condition is latched until system reset
(changes in status from alarm to pre-alarm or to normal are ignored).

50
Indicators, Controls and Operations

Table 5 Input Types (Continued)

Input Types Description


Verified Alarm When an un-bypassed verified alarm input goes into alarm, if the system is not
already in alarm, the alarm is verified over a period of time to determine if the alarm
condition is valid. For addressable analog devices, when a device goes into alarm, a
35 second timer is started. When the 35 second delay times out, the device is
monitored for the next 60 seconds, if it goes into alarm again during this time the
alarm is confirmed. Once the alarm condition is confirmed, the alarm is processed as
for non-verified inputs.
If the system goes into alarm at any point during verification process (due to an alarm
on another device or circuit), the verification process is aborted and the alarm is
immediately confirmed. If another Verified Alarm Input goes into alarm during the
verification process, the verification is aborted and the alarm is confirmed on both
inputs. A trouble detected on the circuit being verified during the verification period
will also cause the verification to be aborted and the alarm confirmed.
An alarm zone status indicator flashes during the alarm verification process. If the
alarm is confirmed the indicator will go steady, otherwise it will be turned off.
Once the system is in alarm verified alarm circuits operate the same as non-verified
circuits.The pre-alarm condition on verified alarm inputs is processed the same as
non-verified inputs; i.e. it is not verified.
A count is maintained of the number of times each verified input has gone through its
verification process without confirming an alarm. These counts can be retrieved for
reporting purposes and cleared.

Waterflow Alarm Waterflow inputs are sampled every second. If 10 samples are in alarm in any given
15 second period, an alarm condition is confirmed and the alarm is processed as for
non-verified inputs.
The alarm zone status indicator flashes whenever even one sample indicates an
alarm condition. If the alarm is confirmed the indicator will go steady, it will be turned
OFF when 15 seconds elapses without any samples in the alarm condition. The
waterflow retard operation operates regardless of whether or not the system is in
alarm.
Note: Do not use the retard operation with any external retarding device.

Non-Latching When an un-bypassed supervisory input goes into alarm the common supervisory
Supervisory sequence is activated. Un-bypassed relay, signal, and strobe outputs are updated
according to their programming and supervisory zone status indicators associated
with the input are activated.
Supervisory activations are displayed on the shared display in the common queue
with supervisory as the second highest priority.
When a non-latched supervisory input is restored, outputs programmed to it also
return to normal unless they are also programmed to other active inputs. Zone display
indicators will also be updated to indicate that the input is no longer active and the
message will be removed from the shared display common queue. If there are no
other active supervisory inputs the common supervisory condition will be restored.

Latching Latched supervisory inputs operate the same as non-latched supervisory inputs
Supervisory except that the alarm condition is latched: restoration of the circuit (from alarm to
normal) is ignored until system reset.

51
Indicators, Controls and Operations

Table 5 Input Types (Continued)

Input Types Description


Property and The operation of the Property and Building Safety input type applies to initiating
Building Safety circuits associated with property and building safety. Property and building safety
(Monitor) input status may be reflected on property and building safety zone indicators and in
the common queue, with property and building safety having the lowest priority on the
shared display. They may also be programmed to relay, signal, and strobe outputs.
When an un-bypassed property and building safety circuit goes into alarm, the status
display and programmed outputs are activated. When it restores the status display,
the outputs restore unless they are also programmed to other active inputs.

Trouble-Only An alarm condition on an un-bypassed trouble only input initiates the common trouble
sequence as a trouble. The status is reflected on trouble zone indicators and in the
common queue on the shared display with trouble-only as the third priority. They may
also be programmed to relay, signal, and strobe outputs.
Note that the trouble condition initiated as a result of an alarm on a trouble-only input
is separate from the circuit or device supervision trouble.

Remote Switch Remote switch inputs may be used to provide remote control of system common
Inputs controls. Remote switches are processed as a toggle operation. When the circuit is
activated it sends an event through the system similar to pressing the switch on the
front panel. When the circuit is restored it is ignored. For example if a remote switch is
associated with the fire drill common control activating it once when drill is not
activated will turn on drill and activating it again will turn off drill.
Remote switches are supervised to ensure that they do not get "stuck" in the "ON"
position. If they remain active for more than 30 seconds a circuit trouble is generated.
Remote switches themselves are not correlated to relay, signal, and strobe outputs
although the feature they are associated with may be.

52
Indicators, Controls and Operations

11.8 Output Types

Table 6 Output Types

Output Type Description


Signal This output type is for audible devices such as bells and piezo mini-horns. Signals
operate in alert (two stage) and/or evacuation rate.

Strobe Normal (non-sync):


Strobe circuits operate similar to signals except that they are always turned ON
continuously (they are not affected by the alert or evacuation rates) if configured as
normal. When configured as normal the output circuit does not use any sync protocol.
Normal strobes can be silenceable or non-silenceable.
Synchronized:
Output circuits configured as strobes can have sync protocol for synchronization.
When the output circuit is configured as strobe and also configured as non-
silenceable and the device used on the output is a combination of horn and strobe,
then if the signal silence is activated while the circuit is active the horn(s) are silenced
while the strobe keeps on flashing. Synchronized strobes and strobe/horn models of
the following manufacturers are supported: Faraday, System Sensor, Wheelock,
Gentex, and Mircom.

Relay Un-bypassed relay outputs are activated if any un-bypassed input circuit or common
system status which has been programmed to it is active. If the relay is configured as
"silenceable" it is inhibited when common auxiliary disconnect is active. Relays also
turned off if they are bypassed or if all inputs and system status correlated to it are
restored or bypassed.

i Note: Silencing of the horn depends on the feature provided by the manufacturer of the
horn/strobe combination. Some models of the horn/strobe combination may not
have this feature and will not work as described above.

11.9 Evacuation Codes

Single stage codes

Continuous On 100% of the time


Temporal Code 3 of 0.5 second ON, 0.5 second OFF then, 1.5 second pause
March Code 0.5 second ON, 0.5 second OFF
California Code 5 seconds ON, 10 seconds OFF

Two-stage codes:

Alert Code 0.5 second ON, 2.5 seconds OFF


General Alarm Evacuation code as selected from Figure18 below.

53
Indicators, Controls and Operations

Continuous

0.5s
0.5s
1.5s
Temporal Code

0.5s
0.5s March Code

5s 10s
California Code

0.5s
Alert Code
2.5s

Figure 22 Evacuation and Alert Codes

11.10Initial Power-up Sequence

When the system powers up, it performs an initial self diagnostic and executes a system reset
to reset all external devices. The common trouble sequence is then initiated. The system must
be reset manually to clear the trouble. At power-up, a check is performed on the configuration
data, program, and RAM memory. If an error is found, the system is placed in trouble but the
system attempts to continue to operate.

The power-up sequence will occur when power is first applied to the panel, when power is
restored after a total power failure (including battery power), or when the watchdog timer
expires. It is also implicitly executed when the system comes out of configuration mode after
auto-configure or a new configuration has been downloaded from the configurator.

The power-up complete status is set to indicate that the system power-up is complete and the
system is in normal operating mode.

Shared Display

The shared display consist of a 2 line by 20 characters LCD and alpha numeric keys. It
operates in three basic modes: status display mode, queue display mode and command
mode. Status display mode displays system activity when the queues are empty. When there
are items in the queues, queue display mode is used to browse the status of all active points in
the queues. Command mode which allows the user to execute certain commands, performs
certain system test and front panel configuration of the system.

The following push buttons are used by the shared display:

UP/DOWN scroll through common alarm, supv, trouble and property and building safety
2
ABC queue
scroll through menu selections when in command mode
8
TUV

RIGHT/ moves to next or previous field or digit in command mode


4 6 LEFT
GHI MNO Make selection for example checking/un-checking the selection box
Right key to add items for example Remote LED groups, correlation etc.
Left key to delete items for example led groups etc.

54
Indicators, Controls and Operations

INFO displays additional information for the currently selected item in queue display
? mode or when a pre-alarm, alarm verification or retard operation is active in
status display mode
MENU enter command mode or returns to base menu if already in command mode
M

ENTER accepts currently selected item or menu selection in command mode

CANCEL cancels current operation in command mode and returns to previous menu, or
X exits command mode if at base menu

ALPHA NUMERIC KEYS Some commands require the entry of numeric values, for example loop and
device address for device configuration or changing the time etc.
1 2 3
ABC DEF
Some configuration requires entering the alpha keys for example the labels for
4 5 6
GHI JKL MNO circuits. Multiple key presses are required for entering an appropriate alpha
7 8 9
character. First key press enters the numeric character, the second key press
PRS TUV WXY
enters the first alpha character and another key press will enter the second alpha
* 0
QZ
# character and so on. The sequence is repeated with subsequent key presses.

11.10.1Status Display Mode


The display is in status display mode when there are no items in the queue and command
mode is not active. When there are no active alarms on the system, the display will show a
system normal message. By default the message is displayed in the following format

System Normal
12:47 MON 2005 -10-03

When there is a pre-alarm, alarm verification active or retard verification in process on a


device the system normal message is replaced by a message in the following format:

Pre-alarm detected
12:47 MON 2005 -10-03

OR

Alarm verification
12:47 MON 2005 -10-03

OR

Retard verification
12:47 MON 2005 -10-03

If the device or circuit returns to normal, the system normal message will be re-displayed. If
multiple pre-alarms or alarm verification sequences are active at the same time only the first is
displayed. Pressing the INFO button while the pre-alarm or verification message is active will
display additional information on the circuit or device as described under queue display mode.

55
Indicators, Controls and Operations

11.10.2 Queue Display Mode


Active inputs are all combined together and displayed in one queue with alarm, supervisory,
trouble, or property and building safety and having priority in the same sequence as they are
listed with alarm as the highest priority. In addition any internal non-fatal troubles which will
cause the common trouble sequence to be activated will also result in a specific message to
be placed in the queue with trouble level priority. The message is displayed in the following
format:

Signal opt Conventional signal


Short ckt trb 01/04 Lp:0 Addr :002
Pressing INFO Key

Where:

the first line shows the process type and the input or output designation
the second line shows the active status or the trouble status depending on the circuit
type and the location of the message in the queue along with the total number of
messages in the queue
pressing the INFO key provides some additional information
the first line shows the process type
the second line shows the loop# where the device is connected and the device address
For internal troubles the 2 line message is an internally formatted message which identifies the
trouble along with any additional information which can help in diagnostics. Whenever there
are active inputs in any of the queues the display will automatically display the oldest un-
viewed event in the highest priority queue. The queue priority is a follows: alarm (highest),
supervisory, trouble, property and building safety (lowest). During queue display mode, the
messages in the queue can be scrolled using the UP and DOWN key. For non-latching inputs
(property and building safety, non-latching supervisory, troubles) the message is removed
from the queue when the circuit is restored. Latching input types will only be removed at
system reset.

56
12.0 Remote Annunciator Operation
The FX-350 supports two types on annunciators: conventional LED/switch annunciators and a
shared display (LCD) annunciator. Both types are connected to the panel via the RS-485 serial
link.

12.1 Conventional Annunciators (RA-1000 Series)

The FX-350 is designed to interface with the RA-1000 series of conventional LED
annunciators. The LEDs may be configured to zone status indicators. Each conventional
annunciator contains a local alert buzzer. Under normal operation the alert buzzer is controlled
by the system and operates in an identical manner as the one in the main panel. If
communication fails it is processed locally.

12.2 Supervision

The communications with each annunciator is constantly supervised both by the panel and by
the annunciator. If communications fails, the panel will activate the common trouble sequence.
The number of annunciators is set during panel configuration. If there is a mismatch in the total
number of annunciators the panel will generate communications trouble. When the correct
number of annunciators is detected the troubles will clear.

12.3 Shared Display Annunciator (RAM-300LCD)

The shared display annunciator has identical operation to the main shared display and
operates in conjunction with the main display (viewing items in the queues on one shared
display flag the items as viewed on all shared displays). The shared display annunciator
contains a local alert buzzer. Under normal operation the alert buzzer is controlled by the
system and operates in an identical manner as the one in the main panel. If communication
fails it is processed locally. The configuration cannot be performed by the shared display
annunciator.

12.4 Supervision

The supervision of the shared display annunciator is same as for the remote LED
annunciators

The SRM-312 Smart Relay Module is connected on the RS-485 loop along with other remote
annunciators, but provides 12 relay contact outputs which actuate according to the first 12
remote LED groups. The relays are bypassed by Auxiliary Bypass, and the unit is supervised
as one of the (maximum) eight permitted annunciators.

57
13.0 Dialer Operation
The FX-350 Series (models with a D suffix) Fire Control panels are equipped with a built-in
dialer. The dialer provides a means to communicate panel status to the remote central
monitoring station using two dedicated phone lines.

There are many standard protocols for communicating with the central monitoring station, but
the two most commonly used are supported by this panel

SIA DCS
Contact ID

13.1 Event Reporting

Events are reported in a special format depending upon the protocol selected.

13.2 Telephone line supervision

The phone lines are supervised for the presence of

DC voltage
dial tone, stuttered dial tone and message waiting tone

The supervision is carried out every two minutes; first the DC voltage is supervised and if it is
detected the dial tone is monitored. If the phone lines are equipped with a house phone and
with proper connection if the house phone is in use the supervision is suspended until the
house phone is ON-HOOK again.

If there is an event to be reported in the dialer queue and the house phone is in use the dialer
tries the second line to report the event if that lines house phone is also in use the dialer
seizes the line thus disconnecting the house phone and reports the event.

58
14.0 Appendix A: Compatible Receivers
The dialers that are built into select models of the FX-350 Series Fire Alarm Control Panels
are compatible with the following Digital Alarm Communicator Receivers (DACR):

DACR Receiver Model Protocols


SurGard MLR2 Multi-Line Receiver (ULC, ULI approved) SIA-DCS and Ademco Contact ID
SurGard SLR Single-Line Receiver (ULC, ULI approved) SIA-DCS and Ademco Contact ID
Osborne-Hoffman Quickalert! II Receiver (ULI approved) SIA-DCS and Ademco Contact ID
Osborne-Hoffman OH-2000 Receiver (ULI Approved) SIA-DCS and Ademco Contact ID
Silent Knight Model 9500 Receiver (ULI Approved) SIA-DCS and Ademco Contact ID
Radionics Model D6500 Receiver (ULI Approved) SIA-DCS and Ademco Contact ID
Radionics Model D6600 Receiver (ULI Approved) SIA-DCS and Ademco Contact ID
DSC SurGard System III Receiver (ULC, ULI Approved)* SIA Contact ID
DSC SurGard System IV Receiver (ULC, ULI Approved)* SIA Contact ID

i Note: * When used with DSC GS4010 or DSC GS4010CF Universal Wireless Alarm
Communicator through wireless IP connection.

59
15.0 Appendix B: Reporting
Table 7 Ademco Contact-ID - FX-350 Series Event Codes
Description Event Qualifier Code Group # Contact #
Family
Phone Line #1 trouble detected Trouble New event 1 351 00 000

Phone Line #2 trouble detected Trouble New event 1 352 00 000


Phone Line #1 trouble restored Trouble Restore 3 351 00 000

Phone Line #2 trouble restored Trouble Restore 3 352 00 000

Failure to report to an Account Trouble New event 1 354 Acct # Acct #

Report to an Account successful Trouble Restore 3 354 Acct # Acct #

RS-485 Communication Trouble Trouble New event 1 350 00 485

Periodic (24 hr) Test Event (NORMAL) Test New event 1 602 00 000
Periodic (24 hr) Test Event (OFF NORMAL) Test New event 1 608 00 000
Manually initiated dialer test Test New event 1 601 00 000

Zone Fire Alarm Alarm New event 1 110 00 NNN

Zone Fire Alarm restored Alarm Restore 3 110 00 NNN

Zone Trouble detected Trouble New event 1 300 00 NNN


Zone Trouble restored Trouble Restore 3 300 00 NNN

Zone Supervisory condition Supervisory New event 1 200 00 NNN

Zone Supervisory restored Supervisory Restore 3 200 00 NNN

Water flow Alarm New event 1 113 00 NNN

Water flow restored Alarm Restore 3 113 00 NNN

Indicating Zone Trouble Trouble New event 1 320 00 NNN

Indicating Zone Trouble restored Trouble Restore 3 320 00 NNN

General Alarm Alarm New event 1 140 00 NNN


General Alarm restored Alarm Restore 3 140 00 NNN

AC power lost Trouble New event 1 301 00 000

AC power restored Trouble Restore 3 301 00 000

Battery Low Trouble New event 1 302 00 000

Battery Low restored Trouble Restore 3 302 00 000

Ground Fault Trouble New event 1 310 00 000

Ground Fault restored Trouble Restore 3 310 00 000

SIA protocol does not define indicating zone troubles, but lists it as Untyped Zone Trouble/
Restore.

60
Appendix B: Reporting

Table 8 Security Industries Association SIA-DCS - FX-350 Series Event Codes


Event Description Event Qualifier SIA Event Parameter
Family Code
Phone Line #1 trouble detected Trouble New event LT 001

Phone Line #2 trouble detected Trouble New event LT 002

Phone Line #1 trouble restored Trouble Restore LR 001

Phone Line #2 trouble restored Trouble Restore LR 002


Failure to report to an Account Trouble New event RT Acct #

Report to an Account successful Trouble Restore YK Acct #

RS485 Communication Trouble Trouble New event YS 485

Periodic (24 hr) Test Event (Normal) Test New event RP 000

Periodic (24 hr) Test Event (Off-normal) Test New event RY 000

Manually initiated dialer test Test New event RX 000

Zone Fire Alarm Alarm New event FA NNN

Zone Fire Alarm restored Alarm Restore FH NNN

Zone Trouble detected Trouble New event FT NNN

Zone Trouble restored Trouble Restore FJ NNN

Zone Supervisory condition Supervisory New event FS NNN

Zone Supervisory restored Supervisory Restore FR NNN

Water flow alarm Alarm New event WA NNN

Water flow alarm restored Alarm Restore WH NNN

General Alarm Alarm New event QA NNN

General Alarm restored Alarm Restore QH NNN


Indicating Zone Trouble (*) Trouble New event UT NNN

Indicating Zone Trouble restored (*) Trouble Restore UR NNN


AC power lost Trouble New event AT 000

AC power restored Trouble Restore AR 000

Battery Low Trouble New event YT 000

Battery Low restored Trouble Restore YR 000


Ground Fault Trouble New event YP 000

Ground Fault restored Trouble Restore YQ 000

61
16.0 Appendix C: Specifications
16.1 FX-350 Series Specifications

Table 9 FX-350 Series Specifications

FX-350 Series Fire Control Panel Chassis


General Digital signal processor based design, fully configurable from front panel with password
protection.

Addressable loops One analog loop capable of addressing 126 Mircom addressable devices, or three analog
loops capable of addressing 378 Mircom addressable devices.

Power Limited / 37VDC / 400mA / maximum loop resistance depends on number of


devices and device type.

Indicating (NAC) 4 supervised style Y (Class B) indicating circuits, configured as strobes or audibles.
Circuits Terminals are labelled as SIG 1, SIG 2, SIG 3 and SIG 4.

Power limited / Regulated 24VDC FWR / 1.7A @ 49C per circuit

Aux. Supply resettable Power limited / 21.1 VDC Filtered regulated / 500mA max

Resettable Auxiliary
Terminals are labelled 4-WIRE.
Power (Aux 2)

Power Limited/21.1 VDC regulated / 300 mA max.

RS-485 Connection For Remote Annunciators. Terminals are labelled RS485.

Electrical ratings Power limited / Regulated 24VDC FWR / 1.7A @ 49C per circuit.

Max power allowed 5A


1.7A (aux power unfiltered if used)
0.5A (aux power filtered if used)
0.3A (resettable auxiliary power if used)

If no auxiliaries are used the max power is 5A for the indicating circuits.

Auxiliary relays Must be connected to a listed power limited source of supply. Terminals are
(resistive loads) labelled ALARM, TROUBLE, SUPV.

Common alarm Form C, 1 Amp, 28 VDC

Common Supv Form C, 1 Amp, 28 VDC

Common Trouble Form C, 1 Amp, 28 VDC

Unfiltered supply Power limited / Regulated 24VDC FWR / 1.7A max at 49C

Battery Type 24VDC Gel Cell/Sealed lead acid 10AH to 24AH

Charging capability 10AH to 24AH

Current Consumption standby: 200 mA


alarm: 350 mA

Protection 10A on board (F1) slow blow micro fuse

62
Appendix C: Specifications

Table 9 FX-350 Series Specifications (Continued)

FX-350 Series Fire Control Panel Chassis


Compliance System Model FX-350 SERIES, Fire Alarm Control Panel

System Type Local, Auxiliary (using PR-300), Remote Protected


Premise Station (using PR-300 or FX-350-60-DR or
FX-350-126-DR), Central Station Protected
Premises (using FX-350-60-DR or FX-350-126-DR).
Proprietary Protected Premise Unit, where PPU is
neither co-located with, nor integral with the
supervising station (NFPA 72).

Type of Service A, M, WF, SS

Type of Signalling Non-Coded

Applicable Standards NFPA 70 and 72, UL 864 R9, ULC-S524, ULC-


S527-11, ULC-S559-13

16.2 FX-350 System Modules and Annunciators

Table 10 FX-350 System Modules and Annunciators

FX-350 System Modules and Annunciators


OCAC-304 Output Class A Converter Module standby: 0 mA / alarm: 0 mA

RAM-208 Zone Remote Annunciator Standby 35mA / alarm 90mA

RAM-216 Zone Ancillary Annunciator Standby 35mA / alarm 140mA

RAM-300LCD LCD Remote Annunciator Standby 16mA / alarm 40mA

PR-300 Polarity Reversal and City Tie Module power limited / 24VDC unfiltered / 250mA max
/14Ohms trip
coil

Polarity Reversal power limited / 24VDC open / 12VDC at


3.5mA / 8.5mA max
(shorted)

Polarity Reversal Supv. Terminal 24VDC (normal) / -24VDC (supervisory) / 0V


(trouble)

Polarity Reversal Alarm Terminal 24VDC (normal) / -24VDC (alarm) / 0V


(trouble)

Current Consumption standby 50mA / alarm 300mA (city tie in use) /


alarm 70mA
(city tie not in use)

RTI Remote Trouble Indicator Standby 35mA / alarm 35mA

63
17.0 Appendix D: Power Supply and
Battery Calculations

POWER REQUIREMENTS (ALL CURRENTS ARE IN AMPERES)


TOTAL TOTAL
Model Number Description Qty STANDBY ALARM
STANDBY ALARM
FX-350-60-DR Main Panel c/w Dialer X 0.220 = 0.380 =
FX-350-60-D Main Panel c/w Dialer X 0.220 = 0.380 =
FX-351-LW Main Panel c/w 1 RAX-332
X 0.210 = 0.390 (Note 1) =
FX-353-LW LED Displays

FX-351-LDW/R Main Panel, c/w 1 RAX-332


X 0.230 = 0.400 (Note 1) =
FX-353-LDR LED Displays and Dialer
FX-351-LD Main Panel c/w Dialer X 0.220 = 0.380 =
252 Point Dual Loop
ALC-252 x 0.120 = 0.230 =
Addressable Adder
RAX-332 32 LED Display X 0.005 = 0.010 =
Polarity Reversal and City
PR-300 X 0.050 = 0.300 =
Tie Module
RAM-300-LCDW/R Remote LCD Annunciator X 0.016 = 0.040 =
Remote Annunciator, 8
RAM-208 X 0.0350 = 0.090 =
Zone LED
Ancillary Annunciator, 16
RAM-216 X 0.0350 = 0.140 =
Zone LED
RTI-1 Remote Trouble Indicator X 0.035 = 0.035 =
MIX-3000 Ionization Detector X 0.00028 = 0.00028 =
MIX-3100 Photoelectric Detector X 0.0004 = 0.0034 =
MIX-3200 Multi-sensor Detector X 0.0005 = 0.0035 =
MIX-3300 Heat Detector X 0.0005 = 0.0034 =
MIX-100P Priority Monitor Module X 0.0006 = 0.0046 =
MIX-101P Mini Priority Monitor Module X 0.0006 = 0.0046 =
MIX-100R Relay Output Module X 0.00085 = 0.0035 =
MIX-100S Supervised Control Module X 0.00100 = 0.00100 =
MIX-100X (Kit)

100XH (Isolator) Isolator c/w Mounting Base X 0.000035 = 0.000035 =

100XB (Base)
MIX-2001R Relay Base X 0.0 = 0.046 =
Device & Remote LEDs (Maximum 30) X 0.0040 =
Signal Load (bells, horns, strobes, and etc.) X =
Auxiliary Power Supply for Annunciators, etc. (See Note 2) = =
Total currents (Add above currents) STANDBY(A) ALARM (B) =

i Notes: Assumes 25% of Zone LEDS (i.e. 15) are ON during alarm.

See specific installation documentation for standby and alarm currents for other
annunciators listed in Panel Components and Accessories. Observe maximum
auxiliary power supply ratings for lamp test conditions for remote annunciators.

64
Appendix D: Power Supply and Battery Calculations

Battery Capacity Requirement


Battery (AH) = (Standby Current Total x Discharge Time) + (Alarm Current Total x Alarm Time)

( [STANDBY (A) ______ ] X [(24 or 60 Hours) ___ ] ) + ( [ALARM (B) ______ ] X [Alarm in Hr. _____ ] ) = (C) ______AH

Total Alarm Current must be 5.5 amperes or less. Indicating Circuits must not to exceed 5 amperes.

Battery Selection:
Battery Size = Multiply (C) by 1.20 to derate battery.

Mircom recommends the following batteries for use with this panel:

Table 11 FX-350 Batteries

MIRCOM BATTERY SIZE UL/ULC RATING


BA-110 12AH 10AH

BA-117 18AH 17AH

BA-124 26AH 24AH

Batteries:

BA-110 (12 AH) will fit into the FX-350 backbox.


BA-110 (12 AH) and BA-117 (18 AH) will fit into the FX-351/353 and BBX-1024DS(R)
backboxes.
BA-124 (26 AH) batteries will fit into the BC-160 Battery Cabinet.
Use of alternative batteries may result in failure of the panel to meet agency and regulatory
requirements, and may result in shortened battery life. Batteries should be tested regularly,
and replaced at least every three years.

65
18.0 Warranty and Warning Information

WARNING!
Please read this document CAREFULLY, as it contains important warnings, life-safety, and
practical information about all products manufactured by the Mircom Group of Companies,
including Mircom and Secutron branded products, which shall include without limitation all fire
alarm, nurse call, building automation and access control and card access products
(hereinafter individually or collectively, as applicable, referred to as Mircom System).

NOTE TO ALL READERS:


1. Nature of Warnings. The within warnings are communicated to the reader out of an
abundance of caution and create no legal obligation for Mircom Group of Companies,
whatsoever. Without limiting the generality of the foregoing, this document shall NOT be
construed as in any way altering the rights and obligations of the parties, governed by the legal
documents that apply in any given circumstance.
2. Application. The warnings contained in this document apply to all Mircom System and shall
be read in conjunction with:
a. the product manual for the specific Mircom System that applies in given circumstances;
b. legal documents that apply to the purchase and sale of a Mircom System, which may
include the companys standard terms and conditions and warranty statements;
c. other information about the Mircom System or the parties rights and obligations as may
be application to a given circumstance.
3. Security and Insurance. Regardless of its capabilities, no Mircom System is a substitute for
property or life insurance. Nor is the system a substitute for property owners, renters, or other
occupants to act prudently to prevent or minimize the harmful effects of an emergency
situation. Building automation systems produced by the Mircom Group of Companies are not
to be used as a fire, alarm, or life-safety system.

NOTE TO INSTALLERS:
All Mircom Systems have been carefully designed to be as effective as possible. However,
there are circumstances where they may not provide protection. Some reasons for system
failure include the following. As the only individual in contact with system users, please bring
each item in this warning to the attention of the users of this Mircom System. Failure to
properly inform system end-users of the circumstances in which the system might fail may
result in over-reliance upon the system. As a result, it is imperative that you properly inform
each customer for whom you install the system of the possible forms of failure:

4. Inadequate Installation. All Mircom Systems must be installed in accordance with all the
applicable codes and standards in order to provide adequate protection. National standards
require an inspection and approval to be conducted by the local authority having jurisdiction
following the initial installation of the system and following any changes to the system. Such
inspections ensure installation has been carried out properly.
5. Inadequate Testing. Most problems that would prevent an alarm a Mircom System from
operating as intended can be discovered by regular testing and maintenance. The complete
system should be tested by the local authority having jurisdiction immediately after a fire,
storm, earthquake, accident, or any kind of construction activity inside or outside the premises.

66
Warranty and Warning Information

The testing should include all sensing devices, keypads, consoles, alarm indicating devices
and any other operational devices that are part of the system.

NOTE TO USERS:
All Mircom Systems have been carefully designed to be as effective as possible. However,
there are circumstances where they may not provide protection. Some reasons for system
failure include the following. The end user can minimize the occurrence of any of the following
by proper training, testing and maintenance of the Mircom Systems:

6. Inadequate Testing and Maintenance. It is imperative that the systems be periodically


tested and subjected to preventative maintenance. Best practices and local authority having
jurisdiction determine the frequency and type of testing that is required at a minimum. Mircom
System may not function properly, and the occurrence of other system failures identified below
may not be minimized, if the periodic testing and maintenance of Mircom Systems is not
completed with diligence and as required.
7. Improper Operation. It is important that all system users be trained in the correct operation
of the alarm system and that they know how to respond when the system indicates an alarm.
A Mircom System may not function as intended during an emergency situation where the user
is unable to operate a panic or emergency switch by reason of permanent or temporary
physical disability, inability to reach the device in time, unfamiliarity with the correct operation,
or related circumstances.
8. Insufficient Time. There may be circumstances when a Mircom System will operate as
intended, yet the occupants will not be protected from the emergency due to their inability to
respond to the warnings in a timely manner. If the system is monitored, the response may not
occur in time enough to protect the occupants or their belongings.
9. Carelessness or Safety Hazards. Moreover, smoke detectors may not provide timely
warning of fires caused by carelessness or safety hazards such as smoking in bed, violent
explosions, escaping gas, improper storage of flammable materials, overloaded electrical
circuits or children playing with matches or arson.
10. Power Failure. Some Mircom System components require adequate electrical power supply
to operate. Examples include: smoke detectors, beacons, HVAC, and lighting controllers. If a
device operates only by AC power, any interruption, however brief, will render that device
inoperative while it does not have power. Power interruptions of any length are often
accompanied by voltage fluctuations which may damage Mircom Systems or other electronic
equipment. After a power interruption has occurred, immediately conduct a complete system
test to ensure that the system operates as intended.
11. Battery Failure. If the Mircom System or any device connected to the system operates from
batteries it is possible for the batteries to fail. Even if the batteries have not failed, they must be
fully charged, in good condition, and installed correctly. Some Mircom Systems use
replaceable batteries, which have a limited life-span. The expected battery life is variable and
in part dependent on the device environment, usage and type. Ambient conditions such as
high humidity, high or low temperatures, or large temperature fluctuations may reduce the
expected battery life. Moreover, some Mircom Systems do not have a battery monitor that
would alert the user in the event that the battery is nearing its end of life. Regular testing and
replacements are vital for ensuring that the batteries function as expected, whether or not a
device has a low-battery monitor.
12. Physical Obstructions. Motion sensors that are part of a Mircom System must be kept clear
of any obstacles which impede the sensors ability to detect movement. Signals being
communicated by a Mircom System may not reach the receiver if an item (such as metal,
water, or concrete) is placed on or near the radio path. Deliberate jamming or other
inadvertent radio signal interference can also negatively affect system operation.

67
Warranty and Warning Information

13. Wireless Devices Placement Proximity. Moreover all wireless devices must be a minimum
and maximum distance away from large metal objects, such as refrigerators. You are required
to consult the specific Mircom System manual and application guide for any maximum
distances required between devices and suggested placement of wireless devices for optimal
functioning.
14. Failure to Trigger Sensors. Moreover, Mircom Systems may fail to operate as intended if
motion, heat, or smoke sensors are not triggered.
a. Sensors in a fire system may fail to be triggered when the fire is in a chimney, walls, roof,
or on the other side of closed doors. Smoke and heat detectors may not detect smoke
or heat from fires on another level of the residence or building. In this situation the
control panel may not alert occupants of a fire.
b. Sensors in a nurse call system may fail to be triggered when movement is occurring
outside of the motion sensors range. For example, if movement is occurring on the other
side of closed doors or on another level of the residence or building the motion detector
may not be triggered. In this situation the central controller may not register an alarm
signal.
15. Interference with Audible Notification Appliances. Audible notification appliances may be
interfered with by other noise sources such as stereos, radios, televisions, air conditioners,
appliances, or passing traffic. Audible notification appliances, however loud, may not be heard
by a hearing-impaired person.
16. Other Impairments. Alarm notification appliances such as sirens, bells, horns, or strobes
may not warn or waken a sleeping occupant if there is an intervening wall or door. It is less
likely that the occupants will be alerted or awakened when notification appliances are located
on a different level of the residence or premise.
17. Software Malfunction. Most Mircom Systems contain software. No warranties are provided
as to the software components of any products or stand-alone software products within a
Mircom System. For a full statement of the warranties and exclusions and limitations of
liability please refer to the companys standard Terms and Conditions and Warranties.
18. Telephone Lines Malfunction. Telephone service can cause system failure where telephone
lines are relied upon by a Mircom System. Alarms and information coming from a Mircom
System may not be transmitted if a phone line is out of service or busy for a certain period of
time. Alarms and information may not be transmitted where telephone lines have been
compromised by criminal tampering, local construction, storms or earthquakes.
19. Component Failure. Although every effort has been made to make this Mircom System as
reliable as possible, the system may fail to function as intended due to the failure of a
component.
20. Integrated Products. Mircom System might not function as intended if it is connected to a
non-Mircom product or to a Mircom product that is deemed non-compatible with a particular
Mircom System. A list of compatible products can be requested and obtained.

Warranty
Purchase of all Mircom products is governed by:

https://www.mircom.com/product-warranty

https://www.mircom.com/purchase-terms-and-conditions

https://www.mircom.com/software-license-terms-and-conditions

68
CANADA - Main Office U.S.A TECHNICAL SUPPORT Mircom 2017
25 Interchange Way 4575 Witmer Industrial Estates North America Printed in Canada
Vaughan, ON L4K 5W3 Niagara Falls, NY 14305 Tel: (888) Mircom5 Subject to change without prior notice
Tel: (888) 660-4655 Tel: (888) 660-4655 (888) 647-2665
(905) 660-4655 (905) 660-4655 International www.mircomgroup.com
Fax: (905) 660-4113 Fax: (905) 660-4113 Tel: (905) 647-2665

You might also like