Fault Level Calc
Fault Level Calc
1) TRANSFORMER
= 750 x 3500
1.732 x 33
= 45.93 KA
DERATING FACTORS
= 55.56 Amps
K : IS A CONSTANT = 0.094
A = ISH x T 45.92 x 1
=
K 0.094
= 488.58 SQ. MM
HERE t : 1 SECONDS
K : 205 FOR COPPER
S = Ixt
K
= 65 x 1000 x 1
205
= 317.07 SQ. MM
HENCE, 50 x 6.35 MM COPPER STRIP IS ADEQUATE
HERE t : 1 SECONDS
K : 205 FOR COPPER
S = Ixt
K
= 50 x 1000 x 1
205
= 243.90 SQ. MM
HERE t : 1 SECONDS
K : 205 FOR COPPER
S = Ixt
K
= 38 x 1000 x 1
205
= 185.37 SQ. MM
HERE t : 1 SECONDS
K : 205 FOR COPPER
S = Ixt
K
= 35 x 1000 x 1
205
= 170.73 SQ. MM
HENCE, 32 x 6 MM COPPER STRIP IS ADEQUATE
E. SIZE OF EARTHING CONDUCTORS UPTO 25 KA FAULT CURRENT
HERE t : 1 SECONDS
K : 205 FOR COPPER
S = Ixt
K
= 25 x 1000 x 1
205
= 121.95 SQ. MM
S = Ixt
K
= 15 x 1000 x 1
205
= 73.17 SQ. MM
= 5.625
= 2000 x 100
5.625
= 35,556 KVA
= 35,556 KVA
1.732 x 0.433
= 47.41 KA
SAY = 50 KA
4) SELECTION OF LT XLPE CABLE BASED ON SHORT CIRCUIT CURRENT
BY USING FORMULA
ISH = KxA
T
K : IS A CONSTANT = 0.094
A = ISH x T 61.35 x 1
K 0.094
= 652.66 SQ. MM
WHEN
T : DURATION OF SHORT CIRCUIT IN SECONDS = 0.25 SEC
A = 61.35 x 0.25
0.094
= 326.33 SQ. MM
= 13,812.15KVA
Short Circuit Current = Fault KVA
3 x KV at Fault Point
= 13812.15
1.732 x 0.415
= 19,216.11Amps
b. Diversity = 80%
e. Total = 937.00KW
Derating Factor :-
Hence selected cable is 5 nos.of 4cx400 sqmm AL armoured XLPE cable is selected.
= 13,812.15KVA
Short Circuit Current = Fault KVA
3 x KV at Fault Point
= 13812.15
1.732 x 0.415
= 19,216.11Amps
b. Diversity = 80%
e. Total = 374.79KW
Derating Factor :-
Hence selected cable is 2 nos.of 4cx400 sqmm AL armoured XLPE cable is selected.
= 13,812.15KVA
Short Circuit Current = Fault KVA
3 x KV at Fault Point
= 13812.15
1.732 x 0.415
= 19,216.11Amps
b. Diversity = 80%
e. Total = 325.56KW
Derating Factor :-
Hence selected cable is 2 nos.of 4cx300 sqmm AL armoured XLPE cable is selected.
= 13,141.11KVA
Short Circuit Current = Fault KVA
3 x KV at Fault Point
= 13141.11
1.732 x 0.415
= 18,282.53Amps