InteliSys NTC Hybrid 2 0 User Guide r1
InteliSys NTC Hybrid 2 0 User Guide r1
InteliSys NTC Hybrid 2 0 User Guide r1
Hybrid
Firmware for
InteliSysNTC Hybrid
SW version 2.0.0
1 General information 2
2 New features 3
3 Abstract 4
4 Conditions 6
5 General installation structure 7
6 Required communication lines 8
7 Required data exchange 10
8 Configuration of InteliSysNTCHybrid for communication with UC-7112-LX Plus 13
9 Communication redundancy 15
10 Sharing the signals 17
11 Recommended settings for a hybrid site control 18
12 Related information 19
Information about ComAp solution for hybrid applications can be found here: Hybrid power plant using ComAps
hybrid solution
For complete description of hybrid applications see our Hybrid Application Guide.
1If FUEL SAVE mode is active, only up to 11 gen-sets can be operated in power management
In this case there is a single Modbus line used for communication between the InteliSys NTC Hybrid controller
and the PV/wind inverter. The data among ComAp controllers, including InteliSysNTC Hybrid, is shared via
CAN2. There could be up to 32 slaves on the Modbus line, however it is recommended to communicate through
a cluster controller if there is a number of inverters, which collects and distributes all data from and to all the
inverters and communicates with the InteliSysNTC Hybrid over one communication line only.
See chapters Sharing the signals (page 17) for more details.
Note: It is also possible to use RS232 connection for Modbus. But RS232 port is not electrically isolated and
without any additional isolation therefore it should be used only for very short connection.
From the
Actual active power Information for InteliSysNTCHybrid for calculation of the inverters to
from the RE source Dynamic Spinning Reserve InteliSys
NTCHybrid
From
Requested active
InteliSys
power from the RE Request to adjust RE source output NTCHybrid to
source
the inverter
From
InteliSysNTC
Dynamic Spinning Information for ComAp controllers to provide sufficient load
Hybrid to
Reserve reserve to cover RE output fluctuations
ComAp genset
controllers
From ComAp
genset
Total running gensets
For the purpose to limit RE power output controllers to
actual power
InteliSysNTC
Hybrid
From ComAp
genset
Total running gensets
For the purpose to limit RE power output controllers to
nominal power
InteliSysNTC
Hybrid
Source: This Value is received from the Concentrator. The
From the
Concentrator reads the "Inverter P Actual" from each Inverter.
PV P actual Concentrator
This value is a summ of all P Actual of the inverters behind the
to the HMC
Concentrator
Source: This Value is received from the Concentrator.
From the
Concentrator reads the "Inverter Q Actual" from each Inverter.
PV Q actual Concentrator
This value is a summ of all Q Actual of the inverters behind the
to the HMC
concentrator
PV Nomin power Source: This Value is received from the Concentrator. From the
IMPORTANT: All values are set to zero after each time interval (day, week, month, year). Change of
the time settings in the controller will reset the statistics! Switching of the controller does not reset
the statistics, unless it is switched on again after certain period within which some of the time
intervals elapsed (typically daily statistics).
Setpoints Value
Comms settings/RS232(2) mode MODBUS-DIRECT
Comms settings/RS232(2) MBCSpd 57600 bps
Comms settings/Contr. address 1
For setting the gateway please follow UC-7112-LX Plus Operator guide
Connection between gateway and PV inverter can be via RS485 (Modbus RTU) or via ethernet (Modbus TCP).
At website www.comap-control.com. you can find settings for PV inverters. If you need connect PV inverter
which is not available, please contact technical support ([email protected]) or your local distributor.
Note: It is possible to communicate with up to 16 inverters with one gateway
The following response will be received when the writing was successful: 01 06 18 C0 00 01 4F D7
The source of DSR in InteliSys NTC Hybrid would be PLC AOUT (PLC Analog Output; the name of the PLC
AOUT can be named arbitrarily by the user, e.g.DSR)
This DSR value then needs to be linked to the Logical Analog Function DynSpinResReq; .-click on LAI tab in
GenConfig and select Logical Analog Function DynSpinResReq. On the right side you can see Source value
selection, as shown below on the picture. Navigate to PLC group and select DSR.
The DSR value must be then shared to the other gen-set controllers using SHAOUT1-1 output (this value is
received in all other controllers on SHAIN1-1 input). G o to tab Modules, click on Extension modules Virtual
Shared, select SHAOUT and click on Insert. Then navigate to tab I/O, click on analog outputsSHAOUT
(1) and click on e.g. AOUT1. On the right side from PLCselect the configured PLC-AOUT 1 (DSR).
In the case that Mains is also a source of power for the system the function needs to be modified accordingly
(depending on various settings).
Example: A load of 800kW is partially supplied from a PV (600kW) and partially from a running gen-set
(200kW). However the minumim gen-set loading prescribes at least 300kW. Therefore the difference of
100kW of load which are currently supplied by the PV inverter but should be supplied from the gen-set. As a
result power produced by the PV must be cut by 100kW and thus the InteliSysNTC Hybrid controller will write
the requested power cut to the PV inverter. When the PV output is lowered, the minimum gen-set loading
level is not violated.
Archives (*.ant)
For InteliSysNTC Hybrid
IH-SPTM-1.0.0.ant
IH-SPI-1.0.0.ant
IH-MINT-1.0.0.ant
IH-Combi-1.0.0.ant
IH-MCB-2.0.0.ant
IH-MGCB-2.0.0.ant