Parker Automation XL50 Manual
Parker Automation XL50 Manual
Parker Automation XL50 Manual
XL25/XL50/XL80
Stepper Drives
User Guide
The installation, set-up, test and maintenance procedures given in this User Guide should only be carried
out by competent personnel trained in the installation of electronic equipment. Such personnel should be
aware of the potential electrical and mechanical hazards associated with mains-powered motion control
equipment - please see the safety warning below. The individual or group having overall responsibility for
this equipment must ensure that operators are adequately trained.
Under no circumstances will the suppliers of the equipment be liable for any incidental, consequential or
special damages of any kind whatsoever, including but not limited to lost profits arising from or in any way
connected with the use of the equipment or this user guide.
SAFETY WARNING
High-performance motion control equipment is capable of producing rapid movement and very high forces.
Unexpected motion may occur especially during the development of controller programs. KEEP WELL
CLEAR of any machinery driven by stepper or servo motors. Never touch any part of the equipment while it
is in operation.
This product is sold as a motion control component to be installed in a complete system using good
engineering practice. Care must be taken to ensure that the product is installed and used in a safe manner
according to local safety laws and regulations. In particular, the product must be enclosed such that no part
is accessible while power may be applied.
This and other information from Parker-Hannifin Corporation, its subsidiaries and authorised distributors
provides product or system options for further investigation by users having technical expertise. Before you
select or use any product or system, it is important that you analyse all aspects of your application and
review the information concerning the product in the current product catalogue. The user, through its own
analysis and testing, is solely responsible for making the final selection of the system and components and
assuring that all performance, safety and warning requirements of the application are met.
If the equipment is used in any manner that does not conform to the instructions given in this user guide,
then the protection provided by the equipment may be impaired.
The information in this user guide, including any apparatus, methods, techniques, and concepts described
herein, are the proprietary property of Parker Electromechanical Division or its licensers, and may not be
copied, disclosed, or used for any purpose not expressly authorised by the owner thereof.
Since Parker Electromechanical constantly strives to improve all of its products, we reserve the right to
modify equipment and user guides without prior notice. No part of this user guide may be reproduced in any
form without the prior consent of Parker Electromechanical Division.
Provided the installation requirements described in this user guide are met, and there are
no special requirements of the installation and operating environment so that the
application may be considered typical, the XL drive series installation will conform to the
protection requirements of Council Directive 89/336/EEC as amended by Directive
92/31/EEC on the approximation of the laws of the Member States relating to
Electromagnetic Compatibility when operated and maintained as intended.
In accordance with IEC 61800-3:1997 (Adjustable speed electrical power drive systems)
this product is of the restricted sales distribution class which meets the needs of an
industrial environment when installed as directed. However, further measures may need
to be taken for use of the product in a domestic environment.
The XL drives and XL_PSU power supply described in this user guide contain no
user-serviceable parts. Attempting to open the case of any unit, or to replace any
internal component, may result in damage to the unit and/or personal injury.
Contact Addresses
Caution -
Refer to the
accompanying documentation
Contents
1. Introduction...........................................................................................................1
2. Mechanical Installation .........................................................................................3
3. Electrical Installation.............................................................................................9
4. Control of XL Step Direction Drives......................................................................33
5. Maintenance and Troubleshooting .......................................................................43
6. Hardware Reference ............................................................................................47
Index..........................................................................................................................53
When a user guide is updated, the new or changed text is differentiated with a change
bar in the outside margin (this paragraph is an example). If an entire section is changed,
the change bar is located on the outside margin of the section title.
Known changes required to be made to this issue of user guide are listed below:
Note: This sheet is intended for documenting any changes or corrections necessary in
this issue of user guide. Any necessary changes we become aware of will be added to
this sheet and will be incorporated into the main part of the user guide when it is next
issued.
1. INTRODUCTION 1
1. Introduction
The XL25 and XL50 share a similar case size, while the XL80 is slightly wider. Figure 1-1
illustrates the two case styles. See Mechanical Installation for dimension information.
XL25/50 XL80
Product Features
Further Information
This user guide contains all the necessary information for the effective use of this drive.
However, to gain a more in-depth understanding of drive applications and motion control,
consider attending one of our English Customer Specific Technical Workshops, details of
which can be found on our web site (www.parker-emd.com) under Sales & Services,
Training.
2. Mechanical Installation
Environment
XL25/XL50/XL80 drives have an operating temperature range of 0 to 50C Max, and can be
used within humidity limits of 5-95% non-condensing. The drives should only be used,
guarded from operator contact in an atmosphere of Pollution Degree 2, which means only
dry, non conductive pollution is acceptable. The storage temperature limits are -20 to 70C.
It is recommended the drives are powered from the XL_PSU, which provides all the
necessary power supplies and eliminates the need for an EMC filter. One XL_PSU can
supply up to six drives, alternatively, drives can be powered from a DC supply, fed from an
isolated transformer. The insulation of the transformer must be suitably rated for the
Installation Category and working voltage on the primary.
Drive Cooling
XL25 and XL50 drives are cooled by natural convection, whilst the XL80 is fitted with an
integral fan. To aid cooling, drives should be installed vertically in an area where there is at
least a 50mm air gap above and below the package and a 10mm gap either side. Avoid
mounting heat producing equipment directly below a drive.
In the final installation, check that the ambient temperature specification of 50C Max
(without forced air cooling) is not exceeded directly below the top-most drives and that any
circulating air flow is not being blocked from reaching the drives. For cabinet cooling
calculations a drive dissipation figure of 15W can be assumed for the XL25/XL50 and 25W
for the XL80.
4 XL25, XL50 & XL80 STEPPER DRIVE USER GUIDE
Drive Dimensions
XL25 and XL50 drives share the same dimensions which are shown in Figure 2-1.
15
4.5
10
5
175
195
185 ctrs
130
XL80 has the dimensions shown in Figure 2-2. Note the double slot fixing used on the base
of this wider drive. The XL80 has the same fixing positions as the XL_PSU, but the drive is
slightly wider (51mm) than the XL_PSU.
51
4.5
25.5
137.4 max (with fixings)
5
10
X1
+DC
-DC
+24V
GND
MOTOR
MOTOR
185 ctrs
SCN
195
X2
175
CTRL
I/O
XL
X3
OSC
HV ST
4.5
130
13 ref 25 ctrs
XL_PSU Dimensions
The XL_PSU dimensions are shown in Figure 2-3.
50
25 Mounting holes
4.5 mm diameter
+DC (80V)
-DC
+24V
GND
P1
N MAINS
INPUT
L
175 110V-230V~
50/60 Hz
250VA 185 195
P2
XL
Power
Supply
Unit
HV STATUS
BRAKING RES.
24V STATUS
The supply should be mounted with a minimum free space of 50mm both below and above
its case. A side clearance of 10mm free space on both sides should be allowed.
Note, the supply must not be mounted above or close to other products which generate a
significant amount of heat by radiation or convection.
2. MECHANICAL INSTALLATION 7
Do not back drive the motor, that is use the motor in an application that may cause the
motor shaft to be mechanically rotated in a manner uncontrolled by the drive.
Back driving the motor at high speed may damage the drive.
Back driving the motor at low to medium speeds may establish sufficient voltage on
the drives capacitors to energise the drive.
8 XL25, XL50 & XL80 STEPPER DRIVE USER GUIDE
3. ELECTRICAL INSTALLATION 9
3. Electrical Installation
Precautions
During installation, take the normal precautions against damage caused by electrostatic
discharges. Earthed wrist straps should always be worn.
All user I/O connections should be screened, using 360 braided screen - do not use a foil
screen.
A switch or circuit breaker must be included in the installation, which must be clearly marked
as the disconnecting device and should be within easy reach of the machine operator.
Cabinet Installation
To produce an EMC and LVD compliant installation it is recommended that drives are
mounted within a steel equipment cabinet. This form of enclosure is not essential to
achieving EMC compliance, but does offer the benefits of operator protection and reduces
the contamination of the equipment from industrial processes.
A steel equipment cabinet will screen radiated emissions provided all panels are bonded to a
central earth point. Separate earth circuits are commonly used within equipment cabinets to
minimise the interaction between independent circuits. A circuit switching large currents and
sharing a common earth return with another low level signal circuit could conduct electrical
noise into the low level circuit, thereby possibly interfering with its operation. For this reason
so called dirty earth and clean earth circuits may be formed within the same cabinet, but all
such circuits will eventually need to be returned to the cabinets main star earth point.
Individual drives are designed to be mounted on a metal earth plane to which the EMC
filters earth connection is also attached. The earth plane will have its own individual star
point earth which should be hard wired (using an insulated copper conductor) back to the
cabinets clean earth connection point.
10 XL25, XL50 & XL80 STEPPER DRIVE USER GUIDE
X1 IMPORTANT
1 DC+
2 DC- Connect positive voltage
3 EARTH to pin 1 and negative to
4 24V DC
5 0V (GND 24V) pin 2. Reversing polarity
6 A+ will damage the drive.
7 A-
8 MOTOR GND
9 B+
10 B-
Mating connector type is: Wieland 8213B/10 F OB, part number 25.323.4053.0
Supply Requirements
XL drives must be powered from DC supplies as specified below:
XL Power Supply
The XL_PSU module is a 250W, power factor corrected, switched mode power supply for
use with XL stepper drives. Designed for direct operation from world-wide single phase AC
input voltages, the supply is capable of powering up to six drives without the need for an
EMC mains input filter*. The use of the XL_PSU offers the following benefits:
Physical Appearance
Housed in a slim, 50mm-wide metal case, the XL_PSU is shown in Figure 3-2. This form of
case matches the appearance of the XL drives and has the same height and depth.
AC Supply Connections
Input AC supplies need to be connected to the 3-way mains input connector P2. Use
approved mains cable, with a minimum wire size of 0.75mm2. The supplied mating
connector is a Phoenix Contact, having the name MSTB 2,5/3-STF-5,08 and order number
1777992.
P2
L N EARTH (GND.)
Output Connections
1
+DC (80V)
2
3
-DC
4
5 EXT. BRAKING RES.
6
7
+24V P1
8 Phoenix Contact
9 10-way female socket
GND
10
Power out (+80V) is taken from pins 1 and 2 (use 32/02 1 mm2 cable), the return connection
being pins 3 and 4. +24V is available on pins 7 and 8 with the return connection being made
to the GND pins 9 and 10. The earth pin 6 is internally connected to the -DC pins 3 and 4.
The supplied mating connector is a Phoenix Contact, having the name IC 2,5/10-STF-5,08
and order number 1825394.
3. ELECTRICAL INSTALLATION 13
No connection exists between the earth pin 6 and the GND pins 9 and 10
Supply/Drive Connections
When used to supply up to six drives the power supply can be wired as shown in Figure 3-5.
Mininum spacing
10 mm between drives & PSU
+DC (80V)
-DC
+24V
GND
MAINS
N
INPUT
L
110V-230V~
50/60 Hz
250VA
XL
Power
Supply
Unit
HV STATUS
BRAKING RES.
24V STATUS
Red
Black
Green/yellow
Note: A kit of five connecting links is available, called XL-connect. You will need one kit for
every drive.
14 XL25, XL50 & XL80 STEPPER DRIVE USER GUIDE
Note: If a braking resistor is fitted, a ferrite ring-core needs to be fitted over the braking
resistor leads, as shown in Figure 3-6. A suitable ring-core is the Parker Chomerics part
number H8FE-1115-NC, as used for the drives motor cable. The ferrite may be held in
place using heat shrinkable tubing, or cable ties. An in-line 5 X 20 mm fuse is recommended
to be fitted between pin 2 of P1 and the braking resistor. The fuse should have a maximum
value of 3.15A with a time delay low breaking characteristic.
The braking resistor should be wired using 16/02 0.5 mm2 cable.
1
2
3 Maximum
4 distance
150 mm
5
6
7
P1
8 Ferrite
9 absorber
10
In-line
fuse holder
These components are
to be mounted away from
operator contact. High voltages
and high temperature can
External braking be expected during normal
resistor. operation.
An internal dump switch has a peak rating of 800W. The dump resistor used should be
10 Ohms (nominal) with a power rating of 100W.
The XL drives and XL_PSU power supply described in this user guide contain no user-
serviceable parts. Attempting to open the case of any unit, or to replace any internal
component, may result in damage to the unit and/or personal injury.
3. ELECTRICAL INSTALLATION 17
Transformer Sizing
A DC input is required by the drive, which can be generated by rectifying and smoothing the
secondary voltage of a transformer. This is an unregulated supply so do not select a
secondary voltage which generates a DC output that exceeds 80V.
The size of transformer required for a stepper drive installation depends very much on the
application and on the maximum shaft power delivered by individual motors. However, the
following figures may be taken as a guide.
Assuming a torque margin of 25-30% has been allowed, the maximum demand from a single
XL25 drive is approximately 80VA, 125VA for an XL50 and 170VA for an XL80. These are
peak figures, which in most practical situations, and particularly in point-to-point positioning
systems, will cause the average power demand to be much lower than this. The peak power
demand may be significantly higher if a high performance enhanced-hybrid motor is used.
In multi-axis applications, the peak demand will depend on the maximum number of axes
running simultaneously; very little power is used by a stationary axis. You should allow
approximately 10VA for a stationary XL25 axis, 15VA for a stationary XL50 axis and 25VA
18 XL25, XL50 & XL80 STEPPER DRIVE USER GUIDE
for a stationary XL80 axis. For example, a typical system with four XL50 drives in which no
more than two axes are in motion at any one time would comfortably operate from a 250-
300VA transformer.
Fuses
Fuses should be time delay, high breaking capacity and should be rated for the number of
drives and expected in-rush current.
AC Fuse
The secondary AC fuse is intended to protect power supply components and should have a
value twice that of the bridge rectifier current rating with a minimum value of 5A to prevent
nuisance blowing.
Line Fuse
Fit line fuses to protect the transformer and associated wiring. If you cannot identify the live
wire, fuse both phase conductors. Calculate the fuse value using:
1.5 VA
in amps, but needs to be a minimum of 2A to cope with in-
supply volts
rush current
The +24V supply is connected to X1.4 and the return to X1.5, the total wire length, from
supply to drive, must not exceed 10m.
Connect the +24V supply 0V line to system earth (0V) at some convenient point before the
EMC filter input.
X1
4
5
- +
LOAD
3VK3
LINE
To backplane
star earth point +24V
0V
The supply should be fused with a quick acting fuse, rated at 3A for up to 10 axes, with a 2A
increase for every extra 5 axes. Note: The +24V supply used must meet the voltage
requirements specification of +24V DC +10% -15%, ripple <1V p-p.
EMC Installation
These EMC installation recommendations are based on the expertise acquired during the
development of compliant applications which Parker believe are typical of the way a drive or
drives may be used. Provided you have no special installation requirements or untypical
operating environment requirements, XL drives will conform with current EMC Directives, as
defined at the front of this user guide.
General Requirements
XL drives will require an external filter to meet EMC installation compliance requirements,
unless they use the XL_PSU. It is recommended that the drive is mounted on a conductive
panel which is shared with the EMC filters. If the panel has a paint finish, it will be necessary
to remove the paint in certain areas to ensure filters and drives make a good large-area
metal to metal contact between case and panel.
20 XL25, XL50 & XL80 STEPPER DRIVE USER GUIDE
Filters should be mounted close to the drive and supply wiring kept as short as practical.
Attempt to layout the wiring in a way that minimises cross-coupling between filtered and non-
filtered conductors. This means avoiding running wires from the output of a filter close to
those connected to its input. Where you wish to minimise the cross-coupling between wires
avoid running them side-by-side one another, if they must cross, cross them at 90 to each
other. Keep wiring supported and close to cabinet metalwork. A typical EMC layout is given
in Figure 3-9.
Recommended EMC filter types are CORCOM 6FC10 for loads up to 6A and 3VK3 for the
+24V supply up to 3A. Larger systems may require higher current rated filters.
Lead length X1
restriction
(less than 1 metre)
X2
DC Supply
CABINET
BACK
X3 PLANE
- +
Output
(load)
CORCOM LOAD
6FC10 3VK3
LINE
(line)
Input
All motor connections must be made using a high quality braided-screen cable. Cables
using a metallised plastic bandage for an earth screen are unsuitable and in fact provide
very little screening. Care must be taken when terminating the cable screen, the screen
itself is comparatively fragile; bending it round a tight radius can seriously affect the
screening performance. The selected cable must have a temperature rating which is
adequate for the expected operating temperature of the motor case.
At the drive end of the cable, a 360 connection to the screen should be made using the
brass P-clip provided beneath the motor connector. The diameter of the P-clip is 6mm for
use with the ready made motor cables having 1mm2 conductors. The P-clip needs to be
firmly clamped to the copper braid. If the connection appears loose, fold the braid back on
itself to increase the amount of braid under the clip and re-tighten.
Custom cables will require the cable insulation to be removed to expose the braided screen.
If you are using a motor cable with 2.5mm2 conductors the size of the brass P-clip will need
to be 9mm to accommodate the increased cable diameter. A ferrite absorber, with a
specification matching that of the Chomerics H8FE-1115-NC, is also required to be
positioned on the motor cable using heat shrink sleeving or cable ties. The position of the
absorber should be just below the drive, as shown in Figure 3-10. Always secure the cable
using the P-clip, as shown. Do not rely upon the connector alone holding the motor cable in
place. The X1 connector must not be stressed by hanging cables, as this may lead to
connector over-heating.
22 XL25, XL50 & XL80 STEPPER DRIVE USER GUIDE
X1
Red
Black
Green/yellow
Exposed braid
under P-clip
X2
X3
Ferrite
absorber
There must be no break in the 360 coverage that the screen provides around the cable
conductors. If a connector must be used it should retain the 360 coverage, possibly by the
use of an additional metallic casing where it passes through the bulkhead of the enclosure.
The cable screen must not be bonded to the cabinet at the point of entry. Its function is to
return high-frequency chopping current back to the drive. This may require mounting the
connector on a sub-panel insulated from the main cabinet, or using a connector having an
internal screen which is insulated from the connector housing. Within the cabinet itself, all
the motor cables should lie in the same trunking as far as possible. They must be kept
separate from any low-level control signal cables. This applies particularly where the control
cables are un-screened and run close to the drive.
Note that the motor cable routing within the equipment cabinet should be kept at least
300mm away from I/O cables carrying control signals.
3. ELECTRICAL INSTALLATION 23
Motor Selection
Usually optimum performance will be obtained when the current rating of the motor is
between 1 and 1.5 times the drive rating, but remember the current rating of a motor is its
DC rating, whilst drives are rated at peak output. To match a particular motors current
rating, multiply the drives peak output current by 0.7. Drives can be de-rated to
accommodate motors with lower current ratings (using the bit switch), however the high
speed torque will be reduced.
Do not use a drive setting which gives an output current greater than the motor rating.
With 4 lead motors the bipolar rating is quoted and this should match the criteria stated
above.
With 8 lead motors the bipolar rating of the motor, which is normally quoted, refers to a
parallel winding connection. With the windings connected in series the current rating of the
motor connection will be 50% that of the bipolar rating, and the motor will give improved low-
speed torque, but reduced high-speed torque.
The XL25/XL50/XL80 will drive motors having an inductance as low as 0.5mH, but the
recommended motor inductance range is between 0.8mH and 10mH.
24 XL25, XL50 & XL80 STEPPER DRIVE USER GUIDE
Performance of the XL25/XL50/XL80 is optimised for the following motor types, listed in
Table 3-3 and Table 3-4.
Large Motors
The largest recommended motor size is a 34-frame 3-stack. Please contact Parker EMD if
you wish to use a larger frame motor.
In the majority of applications the drive will be used with an eight lead motor with the
windings connected in parallel or series, as shown in Figure 3-11. Motor connections will
need to be determined from the motors data sheet. These are normally identified by wire
colour or terminal markings, depending upon the make of the motor.
- + - +
MOTOR CONNECTOR
X1 +
6 A+
7 A-
- SAFETY
8 Gnd MOTOR
+ EARTH
9 B+
10 B-
- PARALLEL
Motor case CONNECTIONS
- + - +
MOTOR CONNECTOR
X1 +
6 A+
7 A-
- SAFETY
8 Gnd MOTOR
+ EARTH
9 B+
10 B-
- SERIES
Motor case
CONNECTIONS
The motor case temperature may exceed 70C and should be guarded from operator
contact.
26 XL25, XL50 & XL80 STEPPER DRIVE USER GUIDE
Note: In the case of stepper motors, locked rotor conditions do not cause an overload, so the
only foreseeable failure mode is a short circuit which is immediately detected by the
protection circuit.
Note: The SY56 can be supplied as a 4-terminal motor, as shown in Figure 3-12.
2 3 45
Control Wiring
The XL drive connector layout is shown in Figure 3-13.
X1 Power
& Motor
10
mating Motor scn.
connector
for X1 9 5 Ctrl
X2 I/O
6
D-type 9-way
Bit female socket
switch
15 8
X3 OSC
9 D-type 15-way
1
female socket
LEDs
HVST
Terminal Description
X3 Connector
User control signals are routed to the drives internal oscillator via connector X3. A multi-way
screened cable should be used for all control signal connections, with the screen terminated
onto the D-type shell.
Connector Type
15-way D-type female connector.
*Output pulse width typically 1s (maximum frequency 200 kHz). This is an open collector
output which will require an external pull-up resistor of 4k7 (0.25W) to the +24V supply.
3. ELECTRICAL INSTALLATION 31
X2 Connector
Connector X2 is used for axis control, where an external controller is used to provide system
intelligence and generates the necessary Step and Direction signals. A multi-way screened
cable should be used for these control signals, where the screen makes a 360 connection
at both ends of the cable.
Connector Type
9-way D-type female.
*Low going signal which occurs 50 times per motor revolution. If the drive is set to 4000
steps/rev, the zero phase signal will be active every 80 motor steps, or every
8 motor steps when the drive is set to 400 steps/rev.
Note: The FAULT and ZERO PHASE outputs are connected internally as shown. The
FAULT output transistor is normally turned ON, turning OFF when a fault occurs. The ZERO
PHASE output transistor is normally OFF and turns ON at positions of zero phase.
It is recommended that motor connections are made directly between the motor and drive,
avoiding any switching devices, such as contactors or relays. However, if such switching is
essential, precautions must be taken to ensure motor connections are switched in both
phases when the drive is de-energised and the motor current has collapsed to zero. It is
essential to ensure that the contactor/relay does not open or close when the drive is
energised.
Connector Type
Mating connector type is: Wieland 8213B/10 F OB, part number 25.323.4053.0
Overview
This section describes the operation of XL step direction drives using the internal oscillator or
external control. Internal oscillator operation is used for stand-alone applications, where a
single axis is being controlled manually or via a dedicated interface. External control allows
the drive to be used in multi axis applications where an external controller provides all the
necessary intelligence and generates the required Step and Direction signals.
Compared to the DIN Rail H & L drives: XL does not offer boost, has only a DC power input,
and has no power dump option, unless used with the XL_PSU.
Default Settings
When the drive leaves the factory the default settings are as follows:
Control step/direction
Standby current reduction 50%
Resolution 4000 steps per rev.
Current 50% of peak rating
To alter these default values see Bit Switch Settings later in this section.
Drive
(DIR+)
STEP+ HCPL2631
SDOWN+ 220R
(DIR-)
STEP-
SDOWN-
The motor performs a step when Step+ goes high with respect to Step-. The maximum
frequency on the step input is 200kHz, allowing a theoretical maximum speed of 3000rpm to
be achieved at a resolution of 4000 steps/rev. In practice the maximum attainable speed will
34 XL25, XL50 & XL80 STEPPER DRIVE USER GUIDE
depend on the characteristics of the motor in use. The allowable width of the step pulse
depends on the maximum input frequency to be used; the pulse width should never exceed
the interval between pulses, in other words the signal becomes a square wave at the
maximum frequency. Therefore at 200kHz the maximum pulse width is 2.5S. The
minimum step pulse width is 1S.
With the motor connected according to the information supplied, it should rotate clockwise
when viewed from the shaft end when Direction+ is high with respect to Direction-. The
direction signal should only be changed when the motor is stationary, and to maintain
positional integrity the first step pulse should not occur within 1S of a direction change.
Connect the step-down signal to the normal step inputs and the step-up signal to the
direction inputs. The motor should rotate clockwise from a step-up pulse and counter-
clockwise from a step-down pulse. The guidelines regarding step pulse width are the same
for step-up/step-down as for step-direction operation.
Drive Drive
+12V +12V
SLOW FAST
+
-
When the Slow input is taken low, the oscillator will run at a constant frequency determined
by the Slow Range programming resistor. The frequency must therefore correspond to a
speed within the start-stop range of the motor. Taking the Fast input low will cause the
oscillator to accelerate up to the programmed Fast speed at a preset rate. The preset rate
may be reduced by the addition of an external capacitor. Alternatively, an analogue input
allows the Fast speed to be controlled by an external signal in the range 0-10V DC.
4. CONTROL OF DIN RAIL STEP DIRECTION DRIVES 35
A separate Auxiliary Direction input is provided to control motor direction when the internal
oscillator is used. This input is internally pulled up to +12V and if left open-circuit will
produce counter clockwise (CCW) rotation, for a correctly wired motor. Taking this input low
will reverse direction provided that the differential Direction+ and Direction- inputs are open-
circuit.
External External
slow speed fast speed
set resistor set resistor
The required resistor value may be estimated from Tables A & B below. These tables show
the approximate shaft speeds obtained at a resolution of 4000 steps/rev; at 2000, 800 or 400
steps/rev, the shaft speed will be respectively 2, 5 and 10 times faster for the same resistor
value. Note that the quoted speeds are nominal and are subject to a 20% tolerance.
If a potentiometer is to be used to vary the speed, it is preferable to use the analogue control
input rather than to adjust the Fast programming resistor. The analogue control input
operates via the acceleration/deceleration circuit, therefore turning the potentiometer rapidly
will not de-synchronise the motor.
36 XL25, XL50 & XL80 STEPPER DRIVE USER GUIDE
Table 4-1. Fast range speed vs. resistor value at 4000 steps/rev.
Table 4-2. Slow range speed vs. resistor value at 4000 steps/rev.
8 8 2K precision
15 potentiometer
15
direction
slow
fast
Analogue
speed
- - Optional control
Optional acceleration
+ acceleration + capacitor
capacitor
Fast speed 9 Fast speed 9
resistor* 1 resistor* 1
Slow speed
resistor*
The motor shaft should not be rotated at high speed with the drive de-energised as this may
damage the power output stage.
Fault. If the drive shuts down as a result of a fault condition, such as an external short circuit
or over-temperature fault, the Fault output will turn OFF. This output is opto-isolated but has
a common return with the Zero Phase signal (see circuit in Figure 4-7). The signal may be
used to indicate to an external controller that the drive has shut down. De-energise and re-
energise the drive, or cycle the power, to reset the fault condition. Please refer to the
troubleshooting section for information on fault diagnosis.
The opto is ON for a drive HEALTHY signal and so turns OFF under fault conditions.
4. CONTROL OF DIN RAIL STEP DIRECTION DRIVES 39
2K2
FAULT+ FAULT+
4 4
OR User
8 8 FAULT-
FAULT- input
4K7 circuit
0V
0V
Zero Phase. The 'Zero Phase' condition corresponds with a specific current combination in
the motor windings which occurs 50 times per revolution. This output turns on when the
drive is at each Zero Phase point, and it indicates that the motor shaft is in one of 50 specific
and repeatable orientations. The function may be used to improve homing repeatability by
offsetting the effect of small variations in the home switch operating point.
The drive is reset to the Zero Phase state at power-up (orange LED).
Oscillator monitor. This is an output signal which may be used to monitor the step pulse
stream from the internal oscillator. For instance it may be taken to a counter to indicate
current position or to provide feedback when the oscillator is used within a positioning
system. The signal comes from an NPN open-collector transistor which turns on during each
step pulse. The pulse width is typically 1s wide and a maximum frequency of 200kHz.
40 XL25, XL50 & XL80 STEPPER DRIVE USER GUIDE
The drive is supplied with all bit switches turned OFF, as shown.
X2
OFF
1 2 3 4 5 6 7 8
ON
X3
Switch Functions
Bits 6,7 and 8 set the motor current as a percentage of the drives peak current rating:
Maintenance
XL systems do not require any routine maintenance, but occasional checking of the following
points is recommended.
Motor inspection
Periodically check the motor to ensure that the mounting bolts and couplings are tight.
Check that the motor cables are not being damaged by moving parts and are not being
pulled or forced into tight bends during machine operation. Check all cable connectors and
particularly the safety earth connection.
Drive inspection
Check that the drives are clear of loose material and that there is adequate clearance to
allow a free flow of air through the ventilation slots. Check that drive fixing screws are tight
and that the motor screen connection is secure.
Troubleshooting
IMPORTANT NOTE - ensure that power is turned off before any connections are
removed or changed. Removing a drive with power applied can turn a recoverable fault
situation into a major problem.
The XL drives and XL_PSU power supply described in this user guide contain no user-
serviceable parts. Attempting to open the case of any unit, or to replace any internal
component, may result in damage to the unit and/or personal injury.
44 XL25, XL50 & XL80 STEPPER DRIVE USER GUIDE
The drive LEDs are 3-colour devices and provide information on the state of the drive as
shown in Figure 5-1.
Step-direction
Drive
When this LED is orange, the drive is in a standby or de-energised state but is otherwise
healthy. In this condition there will be no holding torque from the motor and the drive will not
respond to step pulses. If this is the cause of the problem, check the status of the differential
Shutdown inputs (X2 pins 5 and 9) and also the auxiliary Shutdown input on X3 pin 13.
If the centre LED is red it indicates that the drive has shut down due to a fault condition.
This may be due to any of the following causes:
1. The power input voltage is either too high or too low. Check that the supply is within the
limits specified in the Hardware Reference Section.
2. The X1 connector may not be fully inserted into the drive - check that the wiring is not
preventing the connector from being pushed fully home.
3. There is a short circuit across two of the motor connections or between one of the motor
connections and ground. Disconnect power, remove X1 and check the motor connections
with a meter. This condition may also arise if a very low inductance motor is used - the
preferred range is 0.8mH to 10mH.
5. MAINTENANCE AND TROUBLESHOOTING 45
4. The drive has shut down due to excess temperature rise. Check that the ventilation slots
at the top and bottom of the housing are not obstructed and that there is free flow of air
through the drive. Make sure that the drive is not mounted directly above a source of heat
such as a power supply, and if possible check the ambient temperature in the vicinity of the
drive casing. Allow the drive to cool down and re-check. If the motor has ample torque for
the application, try reducing the current setting on the bit switch which will reduce the drive
dissipation.
5. There is an internal fault in the drive or with the internally-generated logic supply. In
either case the drive will need to be returned for repair.
Right LED
This LED has no function in the XL25/XL50 or XL80 drive.
Further checks
If you can safely do so, check that there is holding torque from the motor. However, take
care not to touch any part of the system if this could result in personal injury should
unexpected motion occur - see the safety warning at the front of this User Guide.
Disconnect power, remove X1 and check the motor connections for continuity across each
phase. Check that the drive has not been de-energised by a Shutdown signal as detailed
above.
This suggests that step pulses are not reaching the drive, or that they are not at the required
level. This could be caused by bit switch 2 being in the ON position whilst the direction input
signal is active. Note: If you are attempting to operate in STEP/DIRECTION mode, but the
motor only steps in one direction, check the setting of bit switch 2 (it should be OFF).
If step pulses are generated by an external source, the required signal on the step and
direction inputs is differential at nominal TTL (5V) levels. The minimum differential voltage is
3.5V and step pulses must be at least 1S wide.
If the internal oscillator on the drive is being used to generate step pulses, but the motor is
not moving, check the following points:
1. An external 24V DC supply is required to run the internal oscillator (it is not needed if the
drive is controlled from an external step/direction source). The oscillator will not run if the
polarity of this supply is incorrect - positive should be on X1 pin 4 and negative (or 0V) on
X1 pin 5.
2. For the oscillator to run, a logic low level (<1V) must be present on either the Slow or Fast
control inputs, or the analogue speed control input must be above the 0.5V deadband.
46 XL25, XL50 & XL80 STEPPER DRIVE USER GUIDE
3. An appropriate speed control resistor or potentiometer must be fitted between the Slow
and/or Fast range set input and a 12V reference terminal (two reference terminals are
provided to make wiring easier).
If an oscilloscope is available, the oscillator output pulses may be checked on the Monitor
terminal (X3 pin 5), provided a pull-up resistor is fitted.
Parker may at their discretion authorise direct shipment to and from Poole, Offenburg or
Rohnert Park, but only by prior arrangement with your supplier. Existing UK, European and
USA customers who purchase equipment directly from Parker should contact Poole,
Offenburg or Rohnert Park for further information (contact numbers are at the front of this
User Guide).
6. HARDWARE REFERENCE 47
6. Hardware Reference
Oscillator Specification
Parameter Value
Speed ranges at 4000 steps/rev
Fast range 0-50 revs/sec
Slow range 0-8 revs/sec (higher speeds available at
lower drive resolution)
Speed adjustment - slow External resistor - see table 4-2
Speed adjustment - fast External resistor or 0-10V analogue input
Analogue fast speed adjustment <0.5V = zero speed, +10V = max speed
Preset acceleration time (Fast range only) 45mS
Preset deceleration time (Fast range only) 30mS
Accel/decel time adjustment External capacitor (for capacitor C in F, new
accel time = preset time x {C+4.7}/4.7)
Oscillator monitor output NPN open-collector transistor, 30mA max
ON current, 30V max OFF voltage.
1s pulse width, 200kHz max.
+12V reference supply current limit 10mA
Parameter Value
Input voltage
Nominal 110 to 230 V AC RMS
Min/Max 95 to 264V AC RMS
Mains supply frequency range 50/60Hz +/- 2Hz
Input power factor Better than 0.9 at 250W load
Output voltage 80V DC 5% (no load)
Output current
230V AC input, no 24V load 3.1A continuous, 7.5A peak
230V AC input, max 24V load 2.6A continuous, 7.0A peak
<150V AC input, no 24V load 2.5A continuous, 6.2A peak
<150V AC input, max 24V load 2.0A continuous, 5.7A peak
Protection Short circuit / overload protected
On board capacitance 6600F
24V Auxiliary output
Voltage 24V DC +10% -15%
Current 1.8A Max
Protection Short circuit / overload protected
Output cable length restriction not to exceed 10m in length
Total output power 250W continuous
Peak 600W for 1 second.
Below input voltages of 150V AC,
output power is 200W continuous,
500W peak.
Protection circuits
XL_PSU Module Overtemperature
Output
Current Short circuit / Overload
Power Excessive continuous power
+24V supply
Current Short circuit
Voltage Reverse polarity
Connection / disconnection Hot plugging protection
Parameter Value
Housing Two part brushed aluminium case
Dimensions
Depth 130 mm Max
Width 50 mm Max
Height 175 mm Max (195 mm at flange
mount)
Weight 1 kg
Parameter Value
Pollution Degree 2
Installation category II*
Operating temperature range 0 to 50C ambient
Storage temperature range -20 to 70C
Humidity 5 to 95% non condensing
Altitude 2000 metres
Ingress protection IP20
Cooling Natural convection with integral fan.
Unit to be mounted vertically with at
least 50mm free space above and
below the package. Side clearance of
10mm free space both sides.
*Note: Installation category (also called Overvoltage Category) specifies the level of mains
voltage surges that the equipment will be subjected to. The category depends upon the
location of the equipment, and on any external surge protection provided. Equipment in an
industrial environment, directly connected to major feeders/short branch circuits, is subjected
to Installation Category III. If this is the case, a reduction to Installation Category II is
required. This can be achieved by use of an isolating transformer with an earthed screen
between primary and secondary, or by fitting varistors from live to neutral and from neutral to
earth. Varistors for a 120V AC input should be rated to absorb at least 40 Joules. For
example, DIN-rail mounted surge suppressor RS 240-062 (110V AC, 70J) or
Farnell 294-275 (110V AC, 80J) would be suitable. Varistors for a 240V AC input should be
rated to absorb at least 80 Joules. For example, DIN-rail mounted surge suppressor RS
240-078 (240V AC, 140J) or Farnell 294-287 (240V AC, 140J) would be suitable.
52 XL25, XL50 & XL80 STEPPER DRIVE USER GUIDE
INDEX 53
Index
+ Drive inspection, 43
+24V fuse rating, 19 Dump resistor connections, 15
+24V supply connections, 19 E
+24V supply lead length restrictions, 19 Earth arrangements, 9
A Earth wiring, 10
Absorber ferrite, 23 Electrostatic precautions, 9
AC fuse value, 18 EMC
Acceleration capacitor, 37 typical installation, 20
Acceleration setting, 37 EMC filter
Adjustments, 2 spacing, 20
Air gap distances, 3 EMC Installation, 19
Analogue control input, 35 general requirements, 19
Auxiliary direction input, 35 EMC requirements, 9
Axis control connector, 31 EMC wiring
Axis control screened cables, 31 recommendations, 20
B Environment specification, 48
Bipolar rating, 23 External control connector, 31
Bit switch External speed control, 34
cycle power, 40 F
default settings, 40 Factory settings, 33
settings, 40 Fast input, 34
Bit switch default settings, 33 Fault output, 38
Braking resistor, 16 Ferrite absorber
Braking resistor calculations, 14 Curie temperature, 23
Braking resistor connections, 15 impedance, 23
Bus voltage, 47 part number, 23
C size, 23
Cabinet installation, 9 Ferrite absorber specification, 23
Capacitor acceleration control, 37 Function indicators, 2
Chop frequency, 47 Fuse for +24V supply, 19
Clean earth, 9 H
Control input connector X3, 30 Humidity, 48
Control of drives, 33 I
Cooling requirements, 3 Inputs & outputs, 2
Current switch settings, 41 Installation, 9
D Installation Category, 3
DC supplies, 10 Installation safety requirements, 9
DC supply volts, 10 Internal oscillator, 34
Default settings, 33 L
Dimensions, 4 Large motors, 25
Disconnecting device, 9 Line fuse type, 18
Drive Line fuse values, 18
cooling, 3 Low voltage operation, 18
dimensions, 4 LVD requirements, 9
mechanical mounting, 5
54 INDEX
Customer Feedback
If you have spotted any errors, omissions or inconsistent information within this user guide
please let us know. Either use this page (or a photocopy) to describe the error and Fax. it to
the number given below. Alternatively, you may phone or email the correction.
Part number: 1600. _ _ _ . _ _ Found on the title page in the bottom left corner.
Your name: