0% found this document useful (0 votes)
127 views2 pages

Compact NS 33253

This document provides specifications for a Compact NS1250N circuit breaker with a Micrologic 2.0 A trip unit rated for 1250 amps. Key details include: - It is a 3-pole circuit breaker suitable for distribution networks rated for various voltages and breaking capacities up to 50kA. - The trip unit provides long-time overload and instantaneous short-circuit protection with adjustable settings. - Additional information covers environmental ratings, dimensions, certifications and an 18-month warranty period.

Uploaded by

Zoran Nesic
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
127 views2 pages

Compact NS 33253

This document provides specifications for a Compact NS1250N circuit breaker with a Micrologic 2.0 A trip unit rated for 1250 amps. Key details include: - It is a 3-pole circuit breaker suitable for distribution networks rated for various voltages and breaking capacities up to 50kA. - The trip unit provides long-time overload and instantaneous short-circuit protection with adjustable settings. - Additional information covers environmental ratings, dimensions, certifications and an 18-month warranty period.

Uploaded by

Zoran Nesic
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Product data sheet 33253

Characteristics circuit breaker Compact NS1250N - Micrologic 2.0


A - 1250 A - 3 poles 3t

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range Compact
Range of product NS630b...1600
Product or component type Circuit breaker
Device short name Compact NS1250N
Device application Distribution
Poles description 3P
Protected poles description 3t
Network type AC
Breaking capacity code N
Suitability for isolation Yes conforming to IEC 60947-2
Utilisation category Category B
Trip unit name Micrologic 2.0 A
Trip unit technology Electronic
Trip unit rating 1250 A ( 50 C )

Complementary
Network frequency 50/60 Hz
Control type Toggle
Rotary handle
Mounting mode Fixed
Mounting support Backplate
Upside connection Front
Downside connection Front
[In] rated current 1250 A ( 50 C )
[Ui] rated insulation voltage 800 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 8 kV conforming to IEC 60947-2
[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2

Oct 23, 2017


1
Circuit breaker CT rating 1250 A
Breaking capacity 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
40 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
40 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity Ics 30 kA 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Ics 40 kA 500/525 V AC 50/60 Hz conforming to IEC 60947-2
Ics 50 kA 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Ics 50 kA 380/415 V AC 50/60 Hz conforming to IEC 60947-2
Ics 50 kA 440 V AC 50/60 Hz conforming to IEC 60947-2
Auxiliary contact composition Without
Mechanical durability 10000 cycles
Electrical durability 4000 cycles IEC 60947-2 440 V In AC 50/60 Hz
5000 cycles IEC 60947-2 440 V In/2 AC 50/60 Hz
2000 cycles IEC 60947-2 690 V In AC 50/60 Hz
3000 cycles IEC 60947-2 690 V In/2 AC 50/60 Hz
Local signalling Positive contact indication
[Icw] rated short-time withstand current 19.2 kA
Trip unit protection functions Basic protection
Protection type Overload protection (long time)
Instantaneous short-circuit protection
Long time pick-up adjustment type Ir Adjustable
Long time pick-up adjustment range 0.4...1 x In
Long time delay adjustment type Adjustable 9 settings
[Tr] long-time delay adjustment range 0.7...16.6 s 7.2 x Ir
0.7...24 s 6 x Ir
12.5...600 s 1.5 x Ir
Thermal memory 20 mn
Instantaneous pick-up adjustment type Adjustable
Ii
Instantaneous pick-up adjustment 1.5...10 x Ir
range
Integral instant protection 40 kA
Zone selective interlocking ZSI With
Type of measurement Ammeter
Height 327 mm
Width 210 mm
Depth 147 mm

Environment
Standards IEC 60947-2
Product certifications ASEFA
ASTA
IP degree of protection IP40 conforming to IEC 60529
IK degree of protection IK07 conforming to EN 50102
Pollution degree 3 conforming to IEC 60947
Ambient air temperature for operation -25...70 C
Ambient air temperature for storage -50...85 C

Contractual warranty
Warranty period 18 months

You might also like