Column Supported Two-Way Post-Tensioned Floor Interenational Version TN460-SI
Column Supported Two-Way Post-Tensioned Floor Interenational Version TN460-SI
Column Supported Two-Way Post-Tensioned Floor Interenational Version TN460-SI
This font is used for the numerical work that is part of (b) See through View of the Floor System (P472)
the design. 0-1 3D Views of the Floor System
The following text font is used, wherever comments 3. LOADS
are made to supplement the calculations: 3.1 Selfweight
3.2 Superimposed Dead Load
This font is used to add clarification to the calcula- 3.3 Live Load
tions. 4. DESIGN PARAMETERS
4.1 Applicable Code
DESIGN STEPS 4.2 Cover to Rebar and Prestressing Strands
1. GEOMETRY AND STRUCTURAL SYSTEM 4.3 Allowable Stresses
1.1 Overview 4.4 Crack Width Limitation
1.2 Geometry and Support Conditions 4.5 Allowable Deflection
1.3 Support Lines and Tributaries 5. ACTIONS DUE TO DEAD AND LIVE LOADS
1.4 Idealized Design Strip 6. POST-TENSIONING
2. MATERIAL PROPERTIES 6.1 Selection of Design Parameters
2.1 Concrete 6.2 Selection of Post-tensioning Tendon Force and
2.2 Nonprestressed Reinforcement Profile
2.3 Prestressing 6.3 Selection of Number of Strands
6.4 Calculation of Balanced Load
1 TheSimpleFrameMethod(SFM)inUKandtheliterature 6.5 Determination of Actions Due to Balanced
basedonUKpracticeisreferredtoasEquivalentFrame (post-tensioning) Loads
Method.Itisbasedstrictlyonthecross-sectionalgeom- 7. CODE CHECK FOR SERVICEABILITY
etryoftheslabframebeingdesigned.ThetermEquivalent 7.1 Load Combinations
FrameMethodintheUSliteratureisbasedonanapproxi- 7.2 Stress Check
mationthatisintendedtosimulatethetwo-wayactionofa 7.3 Crack Width Control
floorslab.ItisdescribedinvariousversionsofACI318.
Two-Way Floor Design Example 6-3
1.1 Overview
Nahid building is a multi-story structure supported
on walls and columns. The lateral loads are resisted by
shear walls in two directions. The floor of the building is
a two-way post-tensioned slab resting on columns and
walls. The calculations that follow represent the design
of one region of the floor slab identified by gridline B,
and referred to as design strip B. The remainder of
the floor slab can be designed in a similar manner. The
design is performed using the current versions of IBC;
ACI-318; EC2 and TR-43. FIGURE 1.1-1
FIGURE 1.1-3
FIGURE 1.3-1
excessive (more than 4200 mm2) [Aalami, 1989]. To
avoid congestion of top reinforcement, the column
drops at these locations were enlarged to qualify
them as drop panels. These locations are marked
as B, C, D and F in Fig.1.2-2. While it is practical to
eliminate column drops at locations A and E through
provision of punching shear reinforcement, the drop
panels cannot be eliminated without causing con-
gestion in top rebar.
Section Properties
1.4 Idealized Design Strip The section properties of each span are calculated us-
Design Strip Dimensions ing the gross cross-sectional area of the idealized de-
The extracted design is straightened to simplify anal- sign strip as shown in Figs. 1.4-1 and 1.4-2.
ysis (Fig. 1.3-2b). The tributaries of each span of the
extracted design strip are adjusted to the maximum The stiffening of the slab due to the added thickness
width of the respective span on each side of the sup- of the column drops and drop panels are accounted
port line. The dimensions of the final design strip are for in the calculation through their section properties.
shown in Figs. 1.4-1 and 1.4-2a. In SFM adopted in this example, the added stiffness in
the slab immediately over the support is not included
For gravity design of the structure, the practice in in the analysis. However, the EFM of analysis allows
selection of boundary conditions of the extracted for the aforementioned increase in stiffness.
design strip is verbalized in ACI/IBC as follows. The
strip is modeled with one level of supports imme-
diately above and below the level under consider-
ation. The far ends of the supports are assumed fixed
against rotation.
2 - MATERIAL PROPERTIES
2.1 Concrete
fc, fck (28 day cylinder strength)2 = 40 MPa
Weight = 24 kN/m 3
FIGURE 1.4-1 Elastic Modulus 4700fc = 29725 MPa [ACI]
= 22* 103* [(fck +8)/ 10] 0.3 3 [EC2, TR-43]
= 35220 MPa
Creep coefficient = 2
Material factor, c = 1 [ACI]; 1.50 [EC2, TR-43]
2 Wherecubestrengthisspecified,thefollowingconver-
sionisused:cylinderstrength=0.8timescubestrength
FIGURE 1.4-2 3 EN1992-1-1:2004(E)Table3.1
6-6 Design of Post Tensioned Buildings
2.3 Prestressing (Figs 2.3-1 through 2.3-3) Wobble Coefficient of Friction (K) = 0.003 rad/m
Materiallow relaxation, seven wire ASTM 416 strand Anchor Set (Wedge Draw-in) = 6 mm
Nominal strand diameter = 13 mm Offset of strand to duct centroid (z) = 3 mm
Strand area = 99 mm2 Effective stress after all losses = 1100 MPa
Elastic Modulus = 200000 MPa
Ultimate strength of strand (fpu) = 1860 MPa 3 - LOADS
Material factor, c = 1 [ACI]; 1.15 [EC2, TR-43]
3.1 Selfweight
System Slab=(240/1000)* 2400* 9.81/1000
Unbonded System = 5.65 kN/m2
Angular coefficient of friction () = 0.07
Wobble coefficient of friction (K) = 0.003 rad/m 3.2 Superimposed Dead Load
Anchor set (wedge draw-in) = 6 mm Superimposed dead load = 2.00 kN/m2
Stressing force = 80% of specified ultimate strength Total Dead Load = SW + SDL = 7.65 kN/m2
Effective stress after all losses4 = 1200 MPa Span 1 DL = 7.65* 8.00 m = 61.20 kN/m
Span 2 DL = 7.65* 9.35 m = 71.53 kN/m
Bonded System Span 3 DL = 7.65* 10.60 m = 81.09 kN/m
Use flat ducts 20x80mm; 0.35 mm thick metal sheet Span 4 DL = 7.65* 10.35 m = 79.18 kN/m
housing up to five strands Added dead load due to column drop, drop panel and
Angular Coefficient of Friction () = 0.2 transverse beam:
Column drop DL (support 3)
4 For hand calculation, an effective stress of tendon is used. = 0.2*1.5*2400*9.81/1000 = 7.06 kN/m
The effective stress is the average stress along the length of Load extends 0.75 m on each side of support 3)
a tendon after all immediate and long-term losses. The value Drop panel DL (support 4) =.2*3.6*2400*9.81/1000
selected for effective stresses is a conservative estimate. = 16.95 kN/m (Load extends 1.8 m on each side of
When effective stress is used in design, the stressed support 4)
lengths of tendons are kept short, as it is described later in
Added beam depth (cantilever)
the calculations.
Two-Way Floor Design Example 6-7
5 Live load for residential floors is generally 2 kN/m2. For 4.2 Cover to Rebar and Prestressing Strands
commercial buildings it is somewhat more. Herein, conser- Minimum rebar cover = 20 mm top and bottom
vatively 3kN/m2 is assumed. Live load is generally reduced
based on the floor area it covers. Reduction of live load is Unbonded System
described in IBC 2012 (Chapter 16). In this design example, The slab is assumed to be in a non-corrosive envi-
live load is not reduced. ronment. Cover to its reinforcement is based on a
6 ACI 318-11 (13.7.6) 2-hour fire rating with the exterior spans considered
6-8 Design of Post Tensioned Buildings
For flat slabs, allowable stresses are the same for both Prestressed members with bonded tendons:
bonded and unbonded systems, as well as for frequent 0.2 mm; to be checked for frequent load case.
and quasi-permanent load combinations.
14 The amount of bonded reinforcement to be added is ex-
There are two thresholds for hypothetical tension plained in Section 7.4 Minimum Reinforcement.
stresses. If the hypothetical tension stresses are be- 15 TR-43, 5.8.1 Table 3
12 EN 1992-1-1:2004(E), Section 5.10.2.2(5) 16 EN 1992-1-1:2004(E),Eqn.3-23
13 TR-43 Second Edition, Table 4. For tensilestress, stress 17 TR-43 Second Edition, Table 5.
limit without bonded reinforcement is considered. 18 EN1992-1-1-2004 (E) Table 7.1N
6-10 Design of Post Tensioned Buildings
Prestressed members with unbonded tendons: 0.3 deflections in EC2 are essentially the same as that of
mm; to be checked at quasi-permanent load case. ACI 318. The impact of vertical displacement on the
function of the installed members and the visual im-
C. Based on TR-43 pact on occupants determine the allowable values.
For both prestressed systems19 = 0.2 mm The following are suggested values:
Examples of the EFM in the literature are generally For deflection control the selfweight of the critical
limited to flat plates mostly without column drop or span is recommended to be balanced to a minimum
drop panel, and with uniform tributaries. The use
of computer programs with EFM formulation is the Table 5-1 Moments at Face-of-Support and Midspan
practical way for design of complex floor systems (T158SI)
with column drop, and/or drop panel, irregular trib-
utaries and non-uniform loads.
of 60%. Non-critical spans need not be balanced to The effective stress assumed in a strand is based on
the same extent. the statistical analysis of common floor slab dimen-
sions for the following conditions (Fig. C6.1-1):
Effective stress in prestressing strand
For unbonded tendons: fse = 1200 MPa (i) Members have dimensions common in building
For bonded tendons: fse = 1100 MPa construction;
Span 1 Force = 1.0 MPa* 1.92e+6/1000 = 1920 kN shows two examples of balanced loading for mem-
No. of Tendons = 1920/119.0 = 16.13; say 17 bers of uniform thickness.
Calculated values for other spans are shown in table
below Span 1
Refer to Fig C6.2-1 and Fig. 6.4-1
Bonded Tendon a = 12027 = 93 mm
Span 1 Area = 8.0 m* 1000* 240 mm = 1.92e+6 mm2 b = 21327 = 186 mm
Span 1 Force = 1.0 MPa* 1.92e+6/1000 = 1920 kN L = 9.00 m
No. of Tendons = 1920/109.0 = 17.61; say 18 c = {[93/186]0.5/[1 + (93/186)0.5]}* 9.00 = 3.73 m
Wb/tendon = 2 P*a/c2 = 119.0 kN* (2*93/1000)/3.732
It is noted that the number of strands required to = 119.0 kN/tendon* 0.013/m =1.59 kN/m/tendon
satisfy the same criterion differs between the un- For 20 tendons Wb = 1.59/ tendon* 20 tendons
bonded and bonded systems. Due to higher friction = 31.8 kN/m
losses, when using bonded systems, more strands % of DL Balanced = 31.8/ 61.20 = 52%
are generally needed to satisfy the in-service condi- (less than 60% target, but considered acceptable)
tion of design. For brevity, without compromising Balanced load reaction, left = 31.8 kN/m* 3.73
the process of calculation, in the following the same = 118.61 kN
number of strands is selected for both systems. Balanced load reaction, right= 31.8 kN/m* 5.27
= 167.59 kN
The number of strands in Table 6.3-1 is based on a
minimum precompression of 1.0 MPa at the midsec- The profiles of the first and last spans are chosen
tion of each span. The added cross-sectional area of such that the upward force on the structure due to the
column drops, drop panels and transverse beams tendon is uniform. This is done by choosing the loca-
are disregarded in the calculation of the force for
minimum precompression. The selected number of
tendons is chosen to avoid an overly complicated
tendon layout. Again, the precompression limit is
disregarded for the cantilever, since the large value
obtained is due to the depth of the beam having been
used in the calculations, as opposed to slab depth.
FIGURE 6.4-1
tion of the tendon low point such that in each span
the profile is a continuous parabola (Fig. C6.2-1). Both
spans appear to be critical and will be designed for
maximum drape, in order to utilize the maximum
amount of balanced loading. If the low point of the
tendon is not selected at the location determined by FIGURE C6.4-1
c, two distinct parabolas result. Figure C6.2-2 illus-
trates the condition, where the low point is not at cen-
ter of a tendon span.
Span 2
Span 2 has 20 continuous strands and three short
strands (added tendons) that extend from span 3 to
span 2 and terminate at its right end. The balanced
load from each is calculated separately.
Continuous Tendons
a = 186 mm FIGURE C6.4-2
L = 10.0 m
end. Hence the vertical balanced loads of these ten-
For a symmetrical parabola of span L, drape a, dons will be downward, with a concentrated upward
and uniform force P, the force normal to L is given force at the dead end.
by 8P*a/L2.
a = 93 mm
Wb/ tendon = 8*P*a/ L2 = (8*119*186/1000) /102 c = 0.20* 10 = 2.00 m
= 1.77 kN/m Wb = (3* 119.0* 2* 93/1000)/2.02 16.60 kN/m
For 20 tendons Wb = 1.77* 20 tendons = 35.41 kN/m Concentrated force at dead end = 16.60* 2.0
% DL Balanced = 35.41/71.53 = 50% OK = 33.20 kN
Balanced load reaction: PT-induced Moments Due to Shift in Centroid
Left = 35.41 kN/m* 5m = 177.05 kN
Right = 35.41 kN/m* 5m = 177.05 kN Because the centroid of the design strip section is
shifted at the face of the column drop, drop panel
Added Tendons and the edge beam, there will be a moment due to
axial force from prestressing at each of these loca-
Increase in the number of strands from 20 to 23, from tions. These moments must be included in the bal-
the third span on, results in 3 strands from the third anced loading to obtain a complete and correct so-
span to terminate in the second span. The terminat- lution. The moments are simply the post-tensioning
ed three strands are dead-ended in the second span. force in the section multiplied by the shift in the sec-
The dead end is located at a distance 0.20*L from the tions centroid (see Fig. 6.4-2).
right support, at the centroid of the design strip (Fig.
C6.4-1). The tendons are assumed horizontal over Moment at Face of Column Drop
the support and concave downward toward the dead M = P* shift in centroid (e) = P* (Yt-Left-Yt-Right)
6-16 Design of Post Tensioned Buildings
FIGURE C6.4-2
FIGURE 6.5-1
ACI, IBC
FIGURE 6.4-3 Total load condition 1*DL + 1*LL + 1*PT
Sustained load condition 1*DL + 0.3*LL + 1*PT23
26.90*10.5*15.85-(192.60+ 165.44)*10.6-117.02*21.1-
71.16+8.21+134.11+62.95-134.11-273.70+273.70 =
0.46 0 kN-m OK 23 ACI-318 specifies a sustained load case, but does not
stipulate the fraction of live load to be considered sus-
6.5 Determination of Actions due to Balanced (Post- tained. It is left to the judgment of the design engineer to
Tensioning) Loads determine the applicable fraction. The fraction selected var-
The distributions of post-tensioning moments due to ies between 0.2 and 0.5. The most commonly used fraction
balanced loading, and the corresponding reactions at is 0.3, as it is adopted in this design example.
6-18 Design of Post Tensioned Buildings
Stresses
= (MD + ML + MPT)/S + P/A
S = I/Yc
Where, MD, ML, and MPT are the moments across the
entire tributary of the design strip. S is the section FIGURE 7.2-1
modulus of the entire tributary; A is the cross-sec-
tional area of the entire tributary; I is the second
moment of area of the entire tributary; and Yc is the Top Fiber
distance of the centroid of the entire tributary to the = 579.42* 10002/2.446e+8-0.85 = 1.52 MPa Tension
farthest tension fiber of the entire tributary. < 3.16 MPa OK
AS = 0.00075* Acf
At section A (Fig. 7.2-1):
In direction of design strip:
AS = 0.00075* 0.5*(10600*240 +10500*240)
= 1899 mm2
In the orthogonal direction to the design strip the
spans adjacent to the support under consideration are
10.60 and 10.35 m. Hence,
AS = 0.00075* 0.5*(10600*240 +10350*240)
= 1886 mm2
As = 1899 mm2 applies
Number of bars = 1899/201 = 9.4
Use 10-16mm bars = 10* 201 mm2 = 2010 > 1899 mm2
provided top
Spans
At Point C in Span
At midspan As = Nc/(0.5*fy) if hypothetical tensile
stress > 0.166*fc
where Nc is the total of tension force in the tensile zone
of the section
Computed hypothetical tensile stress: fct = 1.95MPa
Stress Limit = 0.166* 40 = 1.05 MPa
1.95 MPa > 1.05 MPa Minimum steel is required
Compressive stress at top: fc = 4.15 MPa
The relationships given in Fig. 7.4-1 will be used to deter- FIGURE 7.4-1 Distribution of Strain Over Section of
mine the force of tensile zone (Nc) Member
Depth of tension zone from bottom hypothetical tensile stresses. The minimum require-
= 1.95* 240/(1.95+4.15) = 77 mm ment is handled through the relationship between the
Nc = 77mm* 1.95 MPa* 10350/(2* 1000) cracking moment of a section and its nominal strength
= 777.03 kN in bending. This is handled in the strength check of the
As = 777.03*1000 /(0.5*460) = 3378 mm2 member.
Number of bars = 3378/ 201 =16.8
Use 17-16 mm bars = 17* 201 = 3417 > 3378 mm2 OK B. Based on EC229
EC2 specifies the same requirement for minimum
Bonded (Grouted) Tendons reinforcement at supports and spans, and also for
There is no requirements for minimum reinforcement both unbonded and bonded tendons. Two checks ap-
based on either geometry of the design strip, nor its ply. One is based on the cross-sectional geometry of
28 ACI318-11Section18.9.3.2 29 EN1992-1-1:2004(E),Section9.3.1&7.3.2
6-22 Design of Post Tensioned Buildings
the design strip and its material properties and the Since in EC2 the minimum reinforcement is a func-
other on computed stresses. In the former, the mini- tion of (bt*d) cross-sectional area, at the face-of-
mum reinforcement applies to the combined contri- support the cross-sectional area including the drop
butions of stressed and non-stressed reinforcement. panel is used.
Hence, the participation of each is based according
to the strength it provides, the prestressing steel is Cross-sectional Area
accounted for with higher values. The reinforcement bt = 10350 mm
requirement for crack control is handled separately. Drop panel width = 3,600 mm
Drop panel depth below slab = 200 mm
Unbonded and Bonded Tendons Tributary cross-sectional area = 10,350*240 +
Supports 3,600*200 = 3.204*106 mm2
At section A (Fig. 7.2-1): fctm = 0.3*40(2/3)= 3.51 MPa
Asmin (0.26* fctm*bt*d/fyk) 0.0013* bt*d (i) Asmin = 0.26* fctm*bt* d/fyk
Two-Way Floor Design Example 6-23
= 0.26* 3.51* 3.204*106/460 = 6,356 mm2 Required: Reinforcement for Crack Control
(ii) Asmin = 0.0013* bt* d s = fyk = 460 MPa
= 0.0013* 3.204* 106 = 4,165.2 mm2 k=1
Therefore, Asmin = 6,356 mm2 Depth of tension zone at bottom, using Fig. 7.4-1
Contribution of reinforcement from bonded Prestress- = 3.7*240/(3.7 + 5.2) = 100 mm
ing: Act = 100*10350=10.35e+5 mm2
Aps*(fpk/fyk) = 23* 99*1860/460 k c = 0.4* [1-( c /( k1 (h/h*) fct,eff)]
= 9207 mm2 > 6356 mm2 c = NED /bh = 1.10 MPa (average precompression)
Hence, no additional bonded reinforcement is required. h* = h = 240 mm
k 1 = 1.5 (since section is in compression)
Span
At section C in span (Fig. 7.2-1) Criteria
bt = 10350 mm fct,eff = fctm = 0.3*(40)(2/3) = 3.51 MPa
(i) Asmin = 0.26* fctm*bt*d/fyk
= 0.26*3.51* 10350*212/460 = 4353 mm2 Design
(ii)Asmin = 0.0013*bt*d k c = 0.4* [1-( 1.10 /( 1.5 (240/240) 3.51)] = 0.32
= 0.0013*10350* 212 = 2852 mm2 Asmin = kc k fct,eff Act /s
Hence, Asmin = 4353 mm2 Asmin = 0.32* 1* 3.51* 10.35e+5 /460 = 2499 mm2
Contribution of reinforcement from bonded Prestressing:
Aps*(fpk/fyk) =
C. Based on TR-43
23* 99*1860/460 =9207 mm2 > 4353 mm2
If the hypothetical tensile stress calculated for a
Hence, no additional bonded reinforcement is required.
panel (design strip as used in this example) exceeds
the specified threshold given below, add non-pre-
Minimum Reinforcement for Crack Control
stressed rebar in addition to the prestressing to re-
sist Nc 32
In EC2 necessity of reinforcement for crack control is
triggered, where computed tensile stresses exceed a
(i) where unbonded tendons are used, and the hypo-
code-specified threshold.
thetical full tributary tensile stress exceeds 0.3 fctm,fl ;
and
At all the three locations selected for code compliance,
the hypothetical tensile stress of concrete is below the
(ii) where bonded tendons are used, and the hypo-
threshold for crack control. Hence, no crack control re-
thetical full tributary tensile stress exceeds 0.9 fctm,fl.
inforcement is required.
The amount of non-tensioned reinforcement de-
pends on the tensile force (Nc) developed in the ten-
EXAMPLE sile zone of the location being considered. The area
For demonstration of EC230 procedure for crack con- of (As + Aps) shall be adequate to resist Nc, where
trol, let the maximum hypothetical tensile stress Aps is the area of available bonded reinforcement.
in concrete exceed the threshold set in the code
(3.51MPa). Determine the required crack control re- Unbonded Tendons
inforcement for the section reinforced with unbond- TR43 specifies a minimum amount of non-prestressed
ed tendons.31 reinforcement over the supports. The required minimum
is based on both the cross-sectional geometry of the
Given design strip and the computed tensile stresses.
fb = 3.7 MPa (tension) at bottom
ft = -5.2 MPa (compression) at top At Support
Depth of section = 240 mm Based on Geometry33
Width of section = 10,350 mm Asmin = 0.00075 Acf
Acf = cross-sectional area of the design strip in direc-
30 EN 1992-1-1:2004(E), Section 7.3.2(3) tion of analysis
31 For members reinforced with grouted tendons, the cross-
sectional area of grouted tendons can be used to contribute 32 TR-43 2nd Edition, Section 5.8.1; Table 4
to the minimum required area for crack control. 33 TR-43 2nd Edition, Section 5.8.8
6-24 Design of Post Tensioned Buildings
ous analysis is initiated, only where the parameters Load combination for long-term deflection, using a fac-
of design and applied loads are more reliably known. tor of 0.3 for sustained quasi-permanent live load:
In most cases, post-tensioned members are sized ac- (1.0*DL + 1.0*PT + 0.3*LL)*(1 + 2)
cording to recommended span/depth ratio proven to Long-term deflection: (1 + 2)*(3.4 + 0.3*2.1) = 12.1 mm
perform well in deflection.35 Deflection ratio = 12.1/(10.5*1000) = 1/867 < 1/250 OK
The simplified procedure includes: Instantaneous Deflection Due to Design Live Load
Live load deflection = 2.1 mm
(i) For visual and functional effects, total long-term Deflection ratio = 2.1/(10.5*1000) = 1/5000
deflection from the day supporting shutters are <1/480 or 1/500 OK
removed not to exceed a value that depending on
the code used varies between (span/250 EC2) and Deflection does not generally govern the design for
(span/240 USA). Camber can be used to offset the members dimensioned within the limits of the rec-
impact of displacement. ommended values in ACI 318 and balanced within
the recommended range, and when subject to load-
(ii) Immediate deflection under design live load ing common in building construction. For such cases,
not to exceed (span/500 for EC2/TR43 designs) or deflections are practically always within the permis-
(span/480 for USA).36 sible code values.
Both ACI 318/IBC and EC2 (EN 1992-1-1:2004(E)), 8 CODE CHECK FOR STRENGTH
tie the deflection adequacy to displacement subse-
quent to the installation of members that are likely to 8.1 Load Combinations
be damaged. This requires knowledge of construction ACI-318/IBC
schedule and release of structure for service. In the 1.2*DL + 1.6*LL + 1* Hyp
following the common design practice is followed. 1.4*DL + 1*HYP
= 0.005 0 OK
Moments about Support 1 = -82.44*2-17.73*2
+4.87*2 + 26.51*2 + 92.73*2 + 19.82*9 +0.42*19 +
5.529*29.6-9.924*40.1 = -0.05 kNm 0 OK
Using ACI/IBC
Design moments are:
MU1 = 1.2* MD + 1.6* ML + 1.0* MHYP
MU2 = 1.4* MD + 1.0* MHYP
TABLE 8.4-3 Envelope of Reinforcement for FIGURE C8.4-2 Demand and Capacity Moments (P500)
Serviceability (SLS) and Strength Conditions
(ULS) (mm2) (T165SI)
Based on EC2
Tension = fcteff = 2.90 MPa
Compression = 0.60* 30 = -18 MPa
Based on TR-43
Tension = 0.4fctm = 1.16 MPa
Note: Section properties I, A, Stop, Sbot are the same Compression = 0.40* 30 = -12 MPa
as used for service condition stress check Ft and Fb are Farthest fiber stresses are calculated in a similar man-
allowa-ble stresses at top and bottom respectively ner with to service condition as outlined earlier. The out-
come is summarized in the following table.
10 - DETAILING
REFERENCES
Tension = 0.25* 30 = 1.37 MPa ACI 318-11, (2011), Building Code Requirements for
Compression = 0.60* 30 = -18 MPa Structural Concrete (ACI 318-11) and Commentary,
6-30 Design of Post Tensioned Buildings
ADAPT-TN179, (2005), Design of Post-Tensioned TR43, 2005, Post-Tensioned Concrete Floors Design
Members in Bending Using ACI 318-2002 Simplified Handbook, The Concrete Society.
Procedure, Redwood City, California, www.adapt-