Cast Steel
Cast Steel
Cast Steel
02-J
PN 40, DN 15/4 50 mm GB-1
Characteristics Dimensioning
Nominal pressure PN 40 For sizing of control valves and selection
k of actuators, please see "Quick Choice"
Regulating capability kvs > 25
vr
leaflet no. 9.0.00.
Single-seated, tight closing
Quadratic characteristic
Design
Applications The valve components - spindle, seat and
cone - are made of stainless steel.
Control valves type H1F are designed
The valve body is made of cast steel
for regulating hot water, steam and hot
GP240GH (GS-C25) with flanges drilled
oil systems.
according to EN 1092-1 or ANSI B16.5
The valves are used in conjunction with
Class 150. The thread for the actuator
our temperature or pressure differen-
connection is G1B ISO 228.
tial regulators for controlling industrial
The valves are single-seated and designed
processes, district or central heating
for tight closure. The leakage rate is less Function
plants or marine installations.
than 0.05% of the full flow (according to
Without the actuator being connected, the
VDI/VDE 2174).
valve is held in open position by means
of a spring. With pressure on the spindle
Pressure/Temperature Diagram the valve will close.
Quality assurance In connection with our thermostats or
All valves are manufactured under an ISO electronic actuators, the valves will close
Bar
9001 certification and are pressure and at rising temperatures. For cooling circuits
40
leakage tested before shipment. a reverse acting valve can be used.
For marine applications the valves can The quadratic characteristic will not cease
30
be supplied with relevant test certificates until the flow has dropped below 4% of
24
from recognized classification societies. the full flow.
20
10
Technical Data
Materials:
-10 120 200 300 350 oC
Valve body Cast steel
GP240GH
(GS-C25)
- trim Stainless steel
- bolts, nuts 24 CrMo 4/A4
Specifications Nominal pressure PN 40
Flange connection Opening kvs-value Lifting height Weight Seating Single seated
Type
DN in mm mm m3/h mm kg Flow characteristic Quadratic
k
15 / 4 H1F 15 4 0.20 6 3.3 Regulating capability kvs > 25
vr
15 / 6 H1F 15 6 0.45 6 3.3 Seat leakage 0.05% of kvs
15 / 9 H1F 15 9 0.95 6 3.4 Temperature range See diagram
15 / 12 H1F 15 12 1.7 6 3.4 Mounting See page 2
15 H1F 15 15 2.75 6 3.4 Flanges drilled
20 / 4 H1F 20 4 0.2 6.5 4.7 according to EN 1092-1 PN 40
20 / 6 H1F 20 6 0.45 6.5 4.7 or ANSI B16.5
20 / 9 H1F 20 9 0.95 6.5 4.7 Class 150
20 H1F 20 20 5 6.5 4.9 Counter flanges DIN 2635
25 H1F 25 25 7.5 7 6.1 Colour Green
32 H1F 32 32 12.5 8 9.0
40 H1F 40 40 20 9 10.8
50 H1F 50 50 30 10 15.5
Subject to changes without notice.
Definition of kvs-value
The kvs-value is identical to the IEC flow Dimension sketch
coefficient kv and defined as the water
flow rate in m3/h through the fully open
G1B
valve by a constant differential pressure,
pv, of 1 bar.
b
Mounting H1
Up to 170C the valve can be installed
vertically as well as horizontally. For
media temperature above 170C, a D k
cooling unit of type KS has to be applied.
It must then be installed with actuator/
H2
thermostats downwards, and according d
to the following instructions:
Cooling units with built-in bellow glands, replacing stuffing box of thermostat (KS-5) or
valve motor (KS-6). Must be applied at valve temperatures above 250C. Subject to changes without notice.