Signal List: RPLC Project

Download as pdf or txt
Download as pdf or txt
You are on page 1of 21

RPLC PROJECT

Sheet 1 of 21
Rev D

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

CURRENT L1 (A) AO x x ETHERNET =D06+R06 Grid Incomer A0


1

CURRENT L2 (A) AO x x ETHERNET =D06+R06 Grid Incomer A0


2

CURRENT L3 (A) AO x x ETHERNET =D06+R06 Grid Incomer A0


3

VOLTAGE L1-L3 (V) AO 0-230kV x x ETHERNET =D06+R06 Grid Incomer A0


4

ACTIVE POWER (MW) AO x x ETHERNET =D06+R06 Grid Incomer A0


5

REACTIVE POWER (MVAR) AO x x ETHERNET =D06+R06 Grid Incomer A0


6

POWER FACTOR AO x x ETHERNET =D06+R06 Grid Incomer A0


7

FREQUENCY AO x x ETHERNET =D06+R06 Grid Incomer A0


8

ENERGY CONSUMPTION (MWH) AO x x ETHERNET =D06+R06 Grid Incomer A0


9

TRIP CIRCUIT 1 MONITORING 74 DO x x x HARDWIRED =D06+R06 Grid Incomer A0


10

TRIP CIRCUIT 2 MONITORING 74 DO x x x HARDWIRED =D06+R06 Grid Incomer A0


11

LOCKOUT RELAY OPERATED 86 DO x x x HARDWIRED =D06+R06 Grid Incomer A0


12

MAIN PROTECTION LP1 ON TEST DO x x HARDWIRED =D06+R06 Grid Incomer A0


13

BACKUP PROTECTION LP2 PROTECTION ON TEST DO x x HARDWIRED =D06+R06 Grid Incomer A0


14

MAIN PROTECTION LP1 UNAVAILABLE DO x x x HARDWIRED =D06+R06 Grid Incomer A0


15

BACKUP PROTECTION LP2 UNAVAILABLE DO x x x HARDWIRED =D06+R06 Grid Incomer A0


16

OVERCURRENT TRIP 51 DO x x x ETHERNET =D06+R06 Grid Incomer A0


17

EARTH FAULT TRIP 51N DO x x x ETHERNET =D06+R06 Grid Incomer A0


18

DIRECT TRANSFER TRIP SENT 87L DO x x x ETHERNET =D06+R06 Grid Incomer A0


19

DIRECT TRANSFER TRIP RECEIPT 87L DO x x x ETHERNET =D06+R06 Grid Incomer A0


20

SYNCHRO CHECK RUNNING 25 DO x x ETHERNET =D06+R06 Grid Incomer A0


21

+R06 PANEL AC FEEDER FAULT DO x x x HARDWIRED =D06+R06 Grid Incomer A0


22

SELECTOR SWITCH POSITION REMOTE STATUS DO x x HARDWIRED =D06+S1 Grid Incomer A0


23
RPLC PROJECT

Sheet 2 of 21
Rev D

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

SELECTOR SWITCH POSITION LOCAL STATUS DO x x HARDWIRED =D06+S1 Grid Incomer A0


24

CIRCUIT BREAKER OPEN STATUS Q0 DO x x HARDWIRED =D06+S1 Grid Incomer A0


25

CIRCUIT BREAKER CLOSED STATUS Q0 DO x x HARDWIRED =D06+S1 Grid Incomer A0


26

GENERAL LOCKOUT SF6 * DO x x x HARDWIRED =D06+S1 Grid Incomer A0


27

MAINTENANCE EARTHING SWITCH Q51 OPEN STATUS DO x x HARDWIRED =D06+S1 Grid Incomer A0
28

MAINTENANCE EARTHING SWITCH Q51 CLOSED STATUS DO x x HARDWIRED =D06+S1 Grid Incomer A0
29

MAINTENANCE EARTHING SWITCH Q52 OPEN STATUS DO x x HARDWIRED =D06+S1 Grid Incomer A0
30

MAINTENANCE EARTHING SWITCH Q52 CLOSED STATUS DO x x HARDWIRED =D06+S1 Grid Incomer A0
31

BB DISCONNECTOR OPEN STATUS Q1 DO x x HARDWIRED =D06+S1 Grid Incomer A0


32

BB DISCONNECTORCLOSED STATUS Q1 DO x x HARDWIRED =D06+S1 Grid Incomer A0


33

HIGH SPEED EARTHING SWITCH OPEN STATUS Q8 DO x x HARDWIRED =D06+S1 Grid Incomer A0
34

HIGH SPEED EARTHING SWITCH CLOSED STATUS Q8 DO x x HARDWIRED =D06+S1 Grid Incomer A0
35

LINE DISCONNECTOR OPEN STATUS Q9 DO x x HARDWIRED =D06+S1 Grid Incomer A0


36

LINE DISCONNECTOR CLOSED STATUS Q9 DO x x HARDWIRED =D06+S1 Grid Incomer A0


37

MASTER INTERLOCK OVERRIDE DO x x HARDWIRED =D06+S1 Grid Incomer A0


38

ISOLATING LINK Q6 IN DO x x HARDWIRED =D06+S1 Grid Incomer A0


39

ISOLATING LINK Q6 OUT DO x x HARDWIRED =D06+S1 Grid Incomer A0


40

CIRCUIT BREAKER Q0 OPEN COMMAND DI x x x HARDWIRED =D06+S1 Grid Incomer A0


41

CIRCUIT BREAKER Q0 CLOSE COMMAND DI x x x HARDWIRED =D06+S1 Grid Incomer A0


42

MANTEINANCE EARTHING SWITCH Q51 OPEN COMMAND DI x x x HARDWIRED =D06+S1 Grid Incomer A0
43

MANTEINANCE EARTHING SWITCH Q51 CLOSE COMMAND DI x x x HARDWIRED =D06+S1 Grid Incomer A0
44

BB DISCONNECT SWITCH Q1 OPEN COMMAND DI x x x HARDWIRED =D06+S1 Grid Incomer A0


45

BB DISCONNECT SWITCH Q1 CLOSE COMMAND DI x x x HARDWIRED =D06+S1 Grid Incomer A0


46
RPLC PROJECT

Sheet 3 of 21
Rev D

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

MAINTENANCE EARTHING SWITCH Q52 OPEN COMMAND DI x x x HARDWIRED =D06+S1 Grid Incomer A0
47

MAINTENANCE EARTHING SWITCH Q52 CLOSE COMMAND DI x x x HARDWIRED =D06+S1 Grid Incomer A0
48

HIGH SPEED EARTHING SWITCH Q8 OPEN COMMAND DI x x x HARDWIRED =D06+S1 Grid Incomer A0
49

HIGH SPEED EARTHING SWITCH Q8 CLOSE COMMAND DI x x x HARDWIRED =D06+S1 Grid Incomer A0
50

LINE DISCONNECT SWITCH Q9 OPEN COMMAND DI x x x HARDWIRED =D06+S1 Grid Incomer A0


51

LINE DISCONNECT SWITCH Q9 CLOSE COMMAND DI x x x HARDWIRED =D06+S1 Grid Incomer A0


52

CURRENT L1 (A) AO x x ETHERNET =D08+R08 Grid Incomer B0


53

CURRENT L2 (A) AO x x ETHERNET =D08+R08 Grid Incomer B0


54

CURRENT L3 (A) AO x x ETHERNET =D08+R08 Grid Incomer B0


55

VOLTAGE L1-L3 (V) AO 0-230kV x x ETHERNET =D08+R08 Grid Incomer B0


56

ACTIVE POWER (MW) AO x x ETHERNET =D08+R08 Grid Incomer B0


57

REACTIVE POWER (MVAR) AO x x ETHERNET =D08+R08 Grid Incomer B0


58

POWER FACTOR AO x x ETHERNET =D08+R08 Grid Incomer B0


59

FREQUENCY AO x x ETHERNET =D08+R08 Grid Incomer B0


60

ENERGY CONSUMPTION (MWH) AO x x ETHERNET =D08+R08 Grid Incomer B0


61

TRIP CIRCUIT 1 MONITORING 74 DO x x x HARDWIRED =D08+R08 Grid Incomer B0


62

TRIP CIRCUIT 2 MONITORING 74 DO x x x HARDWIRED =D08+R08 Grid Incomer B0


63

LOCKOUT RELAY OPERATED 86 DO x x x HARDWIRED =D08+R08 Grid Incomer B0


64

MAIN PROTECTION LP1 ON TEST DO x x HARDWIRED =D08+R08 Grid Incomer B0


65

BACKUP PROTECTION LP2 PROTECTION ON TEST DO x x HARDWIRED =D08+R08 Grid Incomer B0


66

MAIN PROTECTION LP1 UNAVAILABLE DO x x x HARDWIRED =D08+R08 Grid Incomer B0


67

BACKUP PROTECTION LP2 UNAVAILABLE DO x x x HARDWIRED =D08+R08 Grid Incomer B0


68

OVERCURRENT TRIP 51 DO x x x ETHERNET =D08+R08 Grid Incomer B0


69
RPLC PROJECT

Sheet 4 of 21
Rev D

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

EARTH FAULT TRIP 51N DO x x x ETHERNET =D08+R08 Grid Incomer B0


70

DIRECT TRANSFER TRIP SENT 87L DO x x x ETHERNET =D08+R08 Grid Incomer B0


71

DIRECT TRANSFER TRIP RECEIPT 87L DO x x x ETHERNET =D08+R08 Grid Incomer B0


72

SYNCHRO CHECK RUNNING 25 DO x x ETHERNET =D08+R08 Grid Incomer B0


73

+R08 PANEL AC FEEDER FAULT DO x x x HARDWIRED =D08+R08 Grid Incomer B0


74

SELECTOR SWITCH POSITION REMOTE STATUS DO x x HARDWIRED =D08+S1 Grid Incomer B0


75

SELECTOR SWITCH POSITION LOCAL STATUS DO x x HARDWIRED =D08+S1 Grid Incomer B0


76

CIRCUIT BREAKER OPEN STATUS Q0 DO x x HARDWIRED =D08+S1 Grid Incomer B0


77

CIRCUIT BREAKER CLOSED STATUS Q0 DO x x HARDWIRED =D08+S1 Grid Incomer B0


78

GENERAL LOCKOUT SF6 * DO x x x HARDWIRED =D08+S1 Grid Incomer B0


79

MAINTENANCE EARTHING SWITCH Q51 OPEN STATUS DO x x HARDWIRED =D08+S1 Grid Incomer B0
80

MAINTENANCE EARTHING SWITCH Q51 CLOSED STATUS DO x x HARDWIRED =D08+S1 Grid Incomer B0
81

MAINTENANCE EARTHING SWITCH Q52 OPEN STATUS DO x x HARDWIRED =D08+S1 Grid Incomer B0
82

MAINTENANCE EARTHING SWITCH Q52 CLOSED STATUS DO x x HARDWIRED =D08+S1 Grid Incomer B0
83

BB DISCONNECTOR OPEN STATUS Q1 DO x x HARDWIRED =D08+S1 Grid Incomer B0


84

BB DISCONNECTORCLOSED STATUS Q1 DO x x HARDWIRED =D08+S1 Grid Incomer B0


85

HIGH SPEED EARTHING SWITCH OPEN STATUS Q8 DO x x HARDWIRED =D08+S1 Grid Incomer B0
86

HIGH SPEED EARTHING SWITCH CLOSED STATUS Q8 DO x x HARDWIRED =D08+S1 Grid Incomer B0
87

LINE DISCONNECTOR OPEN STATUS Q9 DO x x HARDWIRED =D08+S1 Grid Incomer B0


88

LINE DISCONNECTOR CLOSED STATUS Q9 DO x x HARDWIRED =D08+S1 Grid Incomer B0


89

MASTER INTERLOCK OVERRIDE DO x x HARDWIRED =D08+S1 Grid Incomer B0


90

ISOLATING LINK Q6 IN DO x x HARDWIRED =D08+S1 Grid Incomer B0


91

ISOLATING LINK Q6 OUT DO x x HARDWIRED =D08+S1 Grid Incomer B0


92
RPLC PROJECT

Sheet 5 of 21
Rev D

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

CIRCUIT BREAKER Q0 OPEN COMMAND DI x x x HARDWIRED =D08+S1 Grid Incomer B0


93

CIRCUIT BREAKER Q0 CLOSE COMMAND DI x x x HARDWIRED =D08+S1 Grid Incomer B0


94

MANTEINANCE EARTHING SWITCH Q51 OPEN COMMAND DI x x x HARDWIRED =D08+S1 Grid Incomer B0
95

MANTEINANCE EARTHING SWITCH Q51 CLOSE COMMAND DI x x x HARDWIRED =D08+S1 Grid Incomer B0
96

BB DISCONNECTOR Q1 OPEN COMMAND DI x x x HARDWIRED =D08+S1 Grid Incomer B0


97

BB DISCONNECTOR Q1 CLOSE COMMAND DI x x x HARDWIRED =D08+S1 Grid Incomer B0


98

HIGH SPEED EARTHING SWITCH Q52 OPEN COMMAND DI x x x HARDWIRED =D08+S1 Grid Incomer B0
99

HIGH SPEED EARTHING SWITCH Q52 CLOSE COMMAND DI x x x HARDWIRED =D08+S1 Grid Incomer B0
100

HIGH SPEED EARTHING SWITCH Q8 OPEN COMMAND DI x x x HARDWIRED =D08+S1 Grid Incomer B0
101

HIGH SPEED EARTHING SWITCH Q8 CLOSE COMMAND DI x x x HARDWIRED =D08+S1 Grid Incomer B0
102

LINE DISCONNECTOR Q9 OPEN COMMAND DI x x x HARDWIRED =D08+S1 Grid Incomer B0


103

LINE DISCONNECTOR Q9 CLOSE COMMAND DI x x x HARDWIRED =D08+S1 Grid Incomer B0


104

BUS BAR VOLTAGE L1-L3 (V) AO 0-230kV x x ETHERNET =D07+R07 Bus A VT


105

BUS BAR VOLTAGE L1-L3 (V) AO 0-230kV x x ETHERNET =D07+R07 Bus B VT


106

TRIP CIRCUIT 1 MONITORING 74 DO x x x HARDWIRED =D07+R07 Bus coupler BT


107

TRIP CIRCUIT 2 MONITORING 74 DO x x x HARDWIRED =D07+R07 Bus coupler BT


108

SYNCHROCHECK START 25 DO x x ETHERNET =D07+R07 Bus coupler BT


109

CIRCUIT BREAKER Q0 OPEN STATUS DO x x HARDWIRED =D07+S1 Bus coupler BT


110

CIRCUIT BREAKER Q0 CLOSED STATUS DO x x HARDWIRED =D07+S1 Bus coupler BT


111

GENERAL LOCKOUT SF6 * DO x x x HARDWIRED =D07+S1 Bus coupler BT


112

MAINTENANCE EARTHING SWITCH Q51 OPEN STATUS BT A DO x x HARDWIRED =D07+S1 Bus coupler BT
113

MAINTENANCE EARTHING SWITCH Q51 CLOSED STATUS BT A DO x x HARDWIRED =D07+S1 Bus coupler BT
114

BB DISCONNECTOR Q1 OPEN OPEN STATUS BT A DO x x HARDWIRED =D07+S1 Bus coupler BT


115
RPLC PROJECT

Sheet 6 of 21
Rev D

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

BB DISCONNECTOR Q1 OPEN CLOSED STATUS BT A DO x x HARDWIRED =D07+S1 Bus coupler BT


116

MAINTENANCE EARTHING SWITCH Q52 OPEN STATUS BT B DO x x HARDWIRED =D07+S1 Bus coupler BT
117

MAINTENANCE EARTHING SWITCH Q52 CLOSED STATUS BT B DO x x HARDWIRED =D07+S1 Bus coupler BT
118

BB DISCONNECTOR Q10 OPEN OPEN STATUS BT B DO x x HARDWIRED =D07+S1 Bus coupler BT


119

BB DISCONNECTOR Q10 OPEN CLOSED STATUS BT B DO x x HARDWIRED =D07+S1 Bus coupler BT


120

CIRCUIT BREAKER Q0 OPEN COMMAND DI x x x HARDWIRED =D07+S1 Bus coupler BT


121

CIRCUIT BREAKER Q0 CLOSE COMMAND DI x x x HARDWIRED =D07+S1 Bus coupler BT


122

MAINTENANCE EARTHING SWITCH Q51 OPEN COMMAND BT A DI x x x HARDWIRED =D07+S1 Bus coupler BT
123

MAINTENANCE EARTHING SWITCH Q51 CLOSE COMMAND BT A DI x x x HARDWIRED =D07+S1 Bus coupler BT
124

BB DISCONNECTOR Q1 OPEN COMMAND OPEN COMMAND BT A DI x x x HARDWIRED =D07+S1 Bus coupler BT


125

BB DISCONNECTOR Q1 OPEN COMMAND CLOSE COMMAND BT A DI x x x HARDWIRED =D07+S1 Bus coupler BT


126

MAINTENANCE EARTHING SWITCH Q52 OPEN COMMAND BT B DI x x x HARDWIRED =D07+S1 Bus coupler BT
127

MAINTENANCE EARTHING SWITCH Q52 CLOSE COMMAND BT B DI x x x HARDWIRED =D07+S1 Bus coupler BT
128

BB DISCONNECTOR Q10 OPEN COMMAND OPEN COMMAND BT B DI x x x HARDWIRED =D07+S1 Bus coupler BT
129

BB DISCONNECTOR Q10 OPEN COMMAND CLOSE COMMAND BT B DI x x x HARDWIRED =D07+S1 Bus coupler BT
130

+R07 PANEL AC FEEDER FAULT DO x x x HARDWIRED =D07+R07 Bus coupler BT


131

SELECTOR SWITCH POSITION REMOTE STATUS DO x x HARDWIRED =D07+S1 Bus coupler BT


132

SELECTOR SWITCH POSITION LOCAL STATUS DO x x HARDWIRED =D07+S1 Bus coupler BT


133

EARTHING SWITCH ON BUSBAR Q15 OPEN STATUS DO x x HARDWIRED =D07+S1 Bus A


134

EARTHING SWITCH ON BUSBAR Q15 CLOSED STATUS DO x x HARDWIRED =D07+S1 Bus A


135

EARTHING SWITCH ON BUSBAR Q15 OPEN COMMAND DI x x x HARDWIRED =D07+S1 Bus A


136

EARTHING SWITCH ON BUSBAR Q15 CLOSE COMMAND DI x x x HARDWIRED =D07+S1 Bus A


137

EARTHING SWITCH ON BUSBAR Q16 OPEN STATUS DO x x HARDWIRED =D07+S1 Bus B


138
RPLC PROJECT

Sheet 7 of 21
Rev D

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

EARTHING SWITCH ON BUSBAR Q16 CLOSED STATUS DO x x HARDWIRED =D07+S1 Bus B


139

EARTHING SWITCH ON BUSBAR Q16 OPEN COMMAND DI x x x HARDWIRED =D07+S1 Bus B


140

EARTHING SWITCH ON BUSBAR Q16 CLOSE COMMAND DI x x x HARDWIRED =D07+S1 Bus B


141

MASTER INTERLOCK OVERRIDE DO x x HARDWIRED =D07+S1 Bus coupler BT


142

OVERCURRENT PROTECTION ON TEST DO x x HARDWIRED =D07+R07 Bus coupler BT


143

87B PROTECTION ON TEST DO x x HARDWIRED =D07+R07 Bus coupler BT


144

OVERCURRENT PROTECTION ON UNAVAILABLE DO x x x HARDWIRED =D07+R07 Bus coupler BT


145

87B PROTECTION UNAVAILABLE DO x x x HARDWIRED =D07+R07 Bus coupler BT


146

LOCKOUT RELAY OPERATED 86 DO x x x HARDWIRED =D07+R07 Bus coupler BT


147
TRANSFORMER
TRIP CIRCUIT MONITORING 1 74 DO x x x HARDWIRED =D02+R02
148 MS-XFR-604A
TRANSFORMER
TRIP CIRCUIT MONITORING 2 74 DO x x x HARDWIRED =D02+R02
149 MS-XFR-604A
TRANSFORMER
LOCKOUT RELAY OPERATED 86 DO x x x HARDWIRED =D02+R02
150 MS-XFR-604A
TRANSFORMER
OVERCURRENT TRIP 51 DO x x x ETHERNET =D02+R02
151 MS-XFR-604A
TRANSFORMER
EARTH FAULT TRIP 51N DO x x x ETHERNET =D02+R02
152 MS-XFR-604A
TRANSFORMER
87L TRIP 87L DO x x x ETHERNET =D02+R02
153 MS-XFR-604A
TRANSFORMER
+R02 PANEL AC FEEDER FAULT DO x x x HARDWIRED =D02+R02
154 MS-XFR-604A
TRANSFORMER
SELECTOR SWITCH POSITION REMOTE STATUS DO x x HARDWIRED =D02+S1
155 MS-XFR-604A
TRANSFORMER
SELECTOR SWITCH POSITION LOCAL STATUS DO x x HARDWIRED =D02+S1
156 MS-XFR-604A
TRANSFORMER
CIRCUIT BREAKER Q0 CLOSED STATUS DO x x HARDWIRED =D02+S1
157 MS-XFR-604A
TRANSFORMER
CIRCUIT BREAKER Q0 OPEN STATUS DO x x HARDWIRED =D02+S1
158 MS-XFR-604A
TRANSFORMER
GENERAL LOCKOUT SF6 * DO x x x HARDWIRED =D02+S1
159 MS-XFR-604A
TRANSFORMER
BB DISCONNECTOR Q1 OPEN STATUS DO x x HARDWIRED =D02+S1
160 MS-XFR-604A
TRANSFORMER
BB DISCONNECTOR Q1 CLOSED STATUS DO x x HARDWIRED =D02+S1
161 MS-XFR-604A
RPLC PROJECT

Sheet 8 of 21
Rev D

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 OPEN STATUS DO x x HARDWIRED =D02+S1
162 MS-XFR-604A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 CLOSED STATUS DO x x HARDWIRED =D02+S1
163 MS-XFR-604A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 OPEN STATUS DO x x HARDWIRED =D02+S1
164 MS-XFR-604A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 CLOSED STATUS DO x x HARDWIRED =D02+S1
165 MS-XFR-604A
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 OPEN STATUS DO x x HARDWIRED =D02+S1
166 MS-XFR-604A
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 CLOSED STATUS DO x x HARDWIRED =D02+S1
167 MS-XFR-604A
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 OPEN STATUS DO x x HARDWIRED =D02+S1
168 MS-XFR-604A
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 CLOSED STATUS DO x x HARDWIRED =D02+S1
169 MS-XFR-604A
TRANSFORMER
CIRCUIT BREAKER Q0 OPEN COMMAND DI x x x HARDWIRED =D02+S1
170 MS-XFR-604A
TRANSFORMER
CIRCUIT BREAKER Q0 CLOSE COMMAND DI x x x HARDWIRED =D02+S1
171 MS-XFR-604A
TRANSFORMER
BB DISCONNECTOR Q1 OPEN COMMAND DI x x x HARDWIRED =D02+S1
172 MS-XFR-604A
TRANSFORMER
BB DISCONNECTOR Q1 CLOSE COMMAND DI x x x HARDWIRED =D02+S1
173 MS-XFR-604A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 OPEN COMMAND DI x x x HARDWIRED =D02+S1
174 MS-XFR-604A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 CLOSE COMMAND DI x x x HARDWIRED =D02+S1
175 MS-XFR-604A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 OPEN COMMAND DI x x x HARDWIRED =D02+S1
176 MS-XFR-604A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 CLOSE COMMAND DI x x x HARDWIRED =D02+S1
177 MS-XFR-604A
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 OPEN COMMAND DI x x x HARDWIRED =D02+S1
178 MS-XFR-604A
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 CLOSE COMMAND DI x x x HARDWIRED =D02+S1
179 MS-XFR-604A
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 OPEN COMMAND DI x x x HARDWIRED =D02+S1
180 MS-XFR-604A
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 CLOSE COMMAND DI x x x HARDWIRED =D02+S1
181 MS-XFR-604A
TRANSFORMER
CURRENT L2 (A) AO x x ETHERNET =D02+R02
182 MS-XFR-604A
TRANSFORMER
MASTER INTERLOCK OVERRIDE DO x x HARDWIRED =D02+S1
183 MS-XFR-604A
TRANSFORMER
MAIN PROTECTION TP1 ON TEST DO x x HARDWIRED =D02+R02
184 MS-XFR-604A
RPLC PROJECT

Sheet 9 of 21
Rev D

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

TRANSFORMER
BACKUP PROTECTION TP2 ON TEST DO x x HARDWIRED =D02+R02
185 MS-XFR-604A
TRANSFORMER
MAIN PROTECTION TP1 UNAVAILABLE DO x x x HARDWIRED =D02+R02
186 MS-XFR-604A
TRANSFORMER
BACKUP PROTECTION TP2 UNAVAILABLE DO x x x HARDWIRED =D02+R02
187 MS-XFR-604A
TRANSFORMER
TRIP CIRCUIT MONITORING 1 74 DO x x x HARDWIRED =D03+R03
188 MS-XFR-603A
TRANSFORMER
TRIP CIRCUIT MONITORING 2 74 DO x x x HARDWIRED =D03+R03
189 MS-XFR-603A
TRANSFORMER
LOCKOUT RELAY OPERATED 86 DO x x x HARDWIRED =D03+R03
190 MS-XFR-603A
TRANSFORMER
OVERCURRENT TRIP 51 DO x x x ETHERNET =D03+R03
191 MS-XFR-603A
TRANSFORMER
EARTH FAULT TRIP 51N DO x x x ETHERNET =D03+R03
192 MS-XFR-603A
TRANSFORMER
87L TRIP 87L DO x x x ETHERNET =D03+R03
193 MS-XFR-603A
TRANSFORMER
+R03 PANEL AC FEEDER FAULT DO x x x HARDWIRED =D03+R03
194 MS-XFR-603A
TRANSFORMER
SELECTOR SWITCH POSITION REMOTE STATUS DO x x HARDWIRED =D03+S1
195 MS-XFR-603A
TRANSFORMER
SELECTOR SWITCH POSITION LOCAL STATUS DO x x HARDWIRED =D03+S1
196 MS-XFR-603A
TRANSFORMER
CIRCUIT BREAKER Q0 CLOSED STATUS DO x x HARDWIRED =D03+S1
197 MS-XFR-603A
TRANSFORMER
CIRCUIT BREAKER Q0 OPEN STATUS DO x x HARDWIRED =D03+S1
198 MS-XFR-603A
TRANSFORMER
GENERAL LOCKOUT SF6 * DO x x x HARDWIRED =D03+S1
199 MS-XFR-603A
TRANSFORMER
BB DISCONNECTOR Q1 OPEN STATUS DO x x HARDWIRED =D03+S1
200 MS-XFR-603A
TRANSFORMER
BB DISCONNECTOR Q1 CLOSED STATUS DO x x HARDWIRED =D03+S1
201 MS-XFR-603A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 OPEN STATUS DO x x HARDWIRED =D03+S1
202 MS-XFR-603A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 CLOSED STATUS DO x x HARDWIRED =D03+S1
203 MS-XFR-603A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 OPEN STATUS DO x x HARDWIRED =D03+S1
204 MS-XFR-603A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 CLOSED STATUS DO x x HARDWIRED =D03+S1
205 MS-XFR-603A
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 OPEN STATUS DO x x HARDWIRED =D03+S1
206 MS-XFR-603A
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 CLOSED STATUS DO x x HARDWIRED =D03+S1
207 MS-XFR-603A
RPLC PROJECT

Sheet 10 of 21
Rev D

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 OPEN STATUS DO x x HARDWIRED =D03+S1
208 MS-XFR-603A
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 CLOSED STATUS DO x x HARDWIRED =D03+S1
209 MS-XFR-603A
TRANSFORMER
CIRCUIT BREAKER Q0 OPEN COMMAND DI x x x HARDWIRED =D03+S1
210 MS-XFR-603A
TRANSFORMER
CIRCUIT BREAKER Q0 CLOSE COMMAND DI x x x HARDWIRED =D03+S1
211 MS-XFR-603A
TRANSFORMER
BB DISCONNECTOR Q1 OPEN COMMAND DI x x x HARDWIRED =D03+S1
212 MS-XFR-603A
TRANSFORMER
BB DISCONNECTOR Q1 CLOSE COMMAND DI x x x HARDWIRED =D03+S1
213 MS-XFR-603A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 OPEN COMMAND DI x x x HARDWIRED =D03+S1
214 MS-XFR-603A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 CLOSE COMMAND DI x x x HARDWIRED =D03+S1
215 MS-XFR-603A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 OPEN COMMAND DI x x x HARDWIRED =D03+S1
216 MS-XFR-603A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 CLOSE COMMAND DI x x x HARDWIRED =D03+S1
217 MS-XFR-603A
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 OPEN COMMAND DI x x x HARDWIRED =D03+S1
218 MS-XFR-603A
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 CLOSE COMMAND DI x x x HARDWIRED =D03+S1
219 MS-XFR-603A
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 OPEN COMMAND DI x x x HARDWIRED =D03+S1
220 MS-XFR-603A
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 CLOSE COMMAND DI x x x HARDWIRED =D03+S1
221 MS-XFR-603A
TRANSFORMER
CURRENT L2 (A) AO x x ETHERNET =D03+R03
222 MS-XFR-603A
TRANSFORMER
MASTER INTERLOCK OVERRIDE DO x x HARDWIRED =D03+S1
223 MS-XFR-603A
TRANSFORMER
MAIN PROTECTION TP1 ON TEST DO x x HARDWIRED =D03+R03
224 MS-XFR-603A
TRANSFORMER
BACKUP PROTECTION TP2 ON TEST DO x x HARDWIRED =D03+R03
225 MS-XFR-603A
TRANSFORMER
MAIN PROTECTION TP1 UNAVAILABLE DO x x x HARDWIRED =D03+R03
226 MS-XFR-603A
TRANSFORMER
BACKUP PROTECTION TP2 UNAVAILABLE DO x x x HARDWIRED =D03+R03
227 MS-XFR-603A
TRANSFORMER
TRIP CIRCUIT MONITORING 1 74 DO x x x HARDWIRED =D04+R04
228 MS-XFR-602A
TRANSFORMER
TRIP CIRCUIT MONITORING 2 74 DO x x x HARDWIRED =D04+R04
229 MS-XFR-602A
TRANSFORMER
LOCKOUT RELAY OPERATED 86 DO x x x HARDWIRED =D04+R04
230 MS-XFR-602A
RPLC PROJECT

Sheet 11 of 21
Rev D

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

TRANSFORMER
OVERCURRENT TRIP 51 DO x x x ETHERNET =D04+R04
231 MS-XFR-602A
TRANSFORMER
EARTH FAULT TRIP 51N DO x x x ETHERNET =D04+R04
232 MS-XFR-602A
TRANSFORMER
87L TRIP 87L DO x x x ETHERNET =D04+R04
233 MS-XFR-602A
TRANSFORMER
+R04 PANEL AC FEEDER FAULT DO x x x HARDWIRED =D04+R04
234 MS-XFR-602A
TRANSFORMER
SELECTOR SWITCH POSITION REMOTE STATUS DO x x HARDWIRED =D04+S1
235 MS-XFR-602A
TRANSFORMER
SELECTOR SWITCH POSITION LOCAL STATUS DO x x HARDWIRED =D04+S1
236 MS-XFR-602A
TRANSFORMER
CIRCUIT BREAKER Q0 CLOSED STATUS DO x x HARDWIRED =D04+S1
237 MS-XFR-602A
TRANSFORMER
CIRCUIT BREAKER Q0 OPEN STATUS DO x x HARDWIRED =D04+S1
238 MS-XFR-602A
TRANSFORMER
GENERAL LOCKOUT SF6 * DO x x x HARDWIRED =D04+S1
239 MS-XFR-602A
TRANSFORMER
BB DISCONNECTOR Q1 OPEN STATUS DO x x HARDWIRED =D04+S1
240 MS-XFR-602A
TRANSFORMER
BB DISCONNECTOR Q1 CLOSED STATUS DO x x HARDWIRED =D04+S1
241 MS-XFR-602A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 OPEN STATUS DO x x HARDWIRED =D04+S1
242 MS-XFR-602A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 CLOSED STATUS DO x x HARDWIRED =D04+S1
243 MS-XFR-602A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 OPEN STATUS DO x x HARDWIRED =D04+S1
244 MS-XFR-602A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 CLOSED STATUS DO x x HARDWIRED =D04+S1
245 MS-XFR-602A
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 OPEN STATUS DO x x HARDWIRED =D04+S1
246 MS-XFR-602A
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 CLOSED STATUS DO x x HARDWIRED =D04+S1
247 MS-XFR-602A
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 OPEN STATUS DO x x HARDWIRED =D04+S1
248 MS-XFR-602A
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 CLOSED STATUS DO x x HARDWIRED =D04+S1
249 MS-XFR-602A
TRANSFORMER
CIRCUIT BREAKER Q0 OPEN COMMAND DI x x x HARDWIRED =D04+S1
250 MS-XFR-602A
TRANSFORMER
CIRCUIT BREAKER Q0 CLOSE COMMAND DI x x x HARDWIRED =D04+S1
251 MS-XFR-602A
TRANSFORMER
BB DISCONNECTOR Q1 OPEN COMMAND DI x x x HARDWIRED =D04+S1
252 MS-XFR-602A
TRANSFORMER
BB DISCONNECTOR Q1 CLOSE COMMAND DI x x x HARDWIRED =D04+S1
253 MS-XFR-602A
RPLC PROJECT

Sheet 12 of 21
Rev D

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 OPEN COMMAND DI x x x HARDWIRED =D04+S1
254 MS-XFR-602A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 CLOSE COMMAND DI x x x HARDWIRED =D04+S1
255 MS-XFR-602A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 OPEN COMMAND DI x x x HARDWIRED =D04+S1
256 MS-XFR-602A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 CLOSE COMMAND DI x x x HARDWIRED =D04+S1
257 MS-XFR-602A
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 OPEN COMMAND DI x x x HARDWIRED =D04+S1
258 MS-XFR-602A
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 CLOSE COMMAND DI x x x HARDWIRED =D04+S1
259 MS-XFR-602A
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 OPEN COMMAND DI x x x HARDWIRED =D04+S1
260 MS-XFR-602A
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 CLOSE COMMAND DI x x x HARDWIRED =D04+S1
261 MS-XFR-602A
TRANSFORMER
CURRENT L2 (A) AO x x ETHERNET =D04+R04
262 MS-XFR-602A
TRANSFORMER
MASTER INTERLOCK OVERRIDE DO x x HARDWIRED =D04+S1
263 MS-XFR-602A
TRANSFORMER
MAIN PROTECTION TP1 ON TEST DO x x HARDWIRED =D04+R04
264 MS-XFR-602A
TRANSFORMER
BACKUP PROTECTION TP2 ON TEST DO x x HARDWIRED =D04+R04
265 MS-XFR-602A
TRANSFORMER
MAIN PROTECTION TP1 UNAVAILABLE DO x x x HARDWIRED =D04+R04
266 MS-XFR-602A
TRANSFORMER
BACKUP PROTECTION TP2 UNAVAILABLE DO x x x HARDWIRED =D04+R04
267 MS-XFR-602A
TRANSFORMER
TRIP CIRCUIT MONITORING 1 74 DO x x x HARDWIRED =D05+R05
268 MS-XFR-601A
TRANSFORMER
TRIP CIRCUIT MONITORING 2 74 DO x x x HARDWIRED =D05+R05
269 MS-XFR-601A
TRANSFORMER
LOCKOUT RELAY OPERATED 86 DO x x x HARDWIRED =D05+R05
270 MS-XFR-601A
TRANSFORMER
OVERCURRENT TRIP 51 DO x x x ETHERNET =D05+R05
271 MS-XFR-601A
TRANSFORMER
EARTH FAULT TRIP 51N DO x x x ETHERNET =D05+R05
272 MS-XFR-601A
TRANSFORMER
87L TRIP 87L DO x x x ETHERNET =D05+R05
273 MS-XFR-601A
TRANSFORMER
+R05 PANEL AC FEEDER FAULT DO x x x HARDWIRED =D05+R05
274 MS-XFR-601A
TRANSFORMER
SELECTOR SWITCH POSITION REMOTE STATUS DO x x HARDWIRED =D05+S1
275 MS-XFR-601A
TRANSFORMER
SELECTOR SWITCH POSITION LOCAL STATUS DO x x HARDWIRED =D05+S1
276 MS-XFR-601A
RPLC PROJECT

Sheet 13 of 21
Rev D

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

TRANSFORMER
CIRCUIT BREAKER Q0 CLOSED STATUS DO x x HARDWIRED =D05+S1
277 MS-XFR-601A
TRANSFORMER
CIRCUIT BREAKER Q0 OPEN STATUS DO x x HARDWIRED =D05+S1
278 MS-XFR-601A
TRANSFORMER
GENERAL LOCKOUT SF6 * DO x x x HARDWIRED =D05+S1
279 MS-XFR-601A
TRANSFORMER
BB DISCONNECTOR Q1 OPEN STATUS DO x x HARDWIRED =D05+S1
280 MS-XFR-601A
TRANSFORMER
BB DISCONNECTOR Q1 CLOSED STATUS DO x x HARDWIRED =D05+S1
281 MS-XFR-601A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 OPEN STATUS DO x x HARDWIRED =D05+S1
282 MS-XFR-601A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 CLOSED STATUS DO x x HARDWIRED =D05+S1
283 MS-XFR-601A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 OPEN STATUS DO x x HARDWIRED =D05+S1
284 MS-XFR-601A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 CLOSED STATUS DO x x HARDWIRED =D05+S1
285 MS-XFR-601A
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 OPEN STATUS DO x x HARDWIRED =D05+S1
286 MS-XFR-601A
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 CLOSED STATUS DO x x HARDWIRED =D05+S1
287 MS-XFR-601A
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 OPEN STATUS DO x x HARDWIRED =D05+S1
288 MS-XFR-601A
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 CLOSED STATUS DO x x HARDWIRED =D05+S1
289 MS-XFR-601A
TRANSFORMER
CIRCUIT BREAKER Q0 OPEN COMMAND DI x x x HARDWIRED =D05+S1
290 MS-XFR-601A
TRANSFORMER
CIRCUIT BREAKER Q0 CLOSE COMMAND DI x x x HARDWIRED =D05+S1
291 MS-XFR-601A
TRANSFORMER
BB DISCONNECTOR Q1 OPEN COMMAND DI x x x HARDWIRED =D05+S1
292 MS-XFR-601A
TRANSFORMER
BB DISCONNECTOR Q1 CLOSE COMMAND DI x x x HARDWIRED =D05+S1
293 MS-XFR-601A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 OPEN COMMAND DI x x x HARDWIRED =D05+S1
294 MS-XFR-601A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 CLOSE COMMAND DI x x x HARDWIRED =D05+S1
295 MS-XFR-601A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 OPEN COMMAND DI x x x HARDWIRED =D05+S1
296 MS-XFR-601A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 CLOSE COMMAND DI x x x HARDWIRED =D05+S1
297 MS-XFR-601A
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 OPEN COMMAND DI x x x HARDWIRED =D05+S1
298 MS-XFR-601A
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 CLOSE COMMAND DI x x x HARDWIRED =D05+S1
299 MS-XFR-601A
RPLC PROJECT

Sheet 14 of 21
Rev D

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 OPEN COMMAND DI x x x HARDWIRED =D05+S1
300 MS-XFR-601A
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 CLOSE COMMAND DI x x x HARDWIRED =D05+S1
301 MS-XFR-601A
TRANSFORMER
CURRENT L2 (A) AO x x ETHERNET =D05+R05
302 MS-XFR-601A
TRANSFORMER
MASTER INTERLOCK OVERRIDE DO x x HARDWIRED =D05+S1
303 MS-XFR-601A
TRANSFORMER
MAIN PROTECTION TP1 ON TEST DO x x HARDWIRED =D05+R05
304 MS-XFR-601A
TRANSFORMER
BACKUP PROTECTION TP2 ON TEST DO x x HARDWIRED =D05+R05
305 MS-XFR-601A
TRANSFORMER
MAIN PROTECTION TP1 UNAVAILABLE DO x x x HARDWIRED =D05+R05
306 MS-XFR-601A
TRANSFORMER
BACKUP PROTECTION TP2 UNAVAILABLE DO x x x HARDWIRED =D05+R05
307 MS-XFR-601A
TRANSFORMER
TRIP CIRCUIT MONITORING 1 74 DO x x x HARDWIRED =D09+R09
308 MS-XFR-601B
TRANSFORMER
TRIP CIRCUIT MONITORING 2 74 DO x x x HARDWIRED =D09+R09
309 MS-XFR-601B
TRANSFORMER
LOCKOUT RELAY OPERATED 86 DO x x x HARDWIRED =D09+R09
310 MS-XFR-601B
TRANSFORMER
OVERCURRENT TRIP 51 DO x x x ETHERNET =D09+R09
311 MS-XFR-601B
TRANSFORMER
EARTH FAULT TRIP 51N DO x x x ETHERNET =D09+R09
312 MS-XFR-601B
TRANSFORMER
87L TRIP 87L DO x x x ETHERNET =D09+R09
313 MS-XFR-601B
TRANSFORMER
+R09 PANEL AC FEEDER FAULT DO x x x HARDWIRED =D09+R09
314 MS-XFR-601B
TRANSFORMER
SELECTOR SWITCH POSITION REMOTE STATUS DO x x HARDWIRED =D09+S1
315 MS-XFR-601B
TRANSFORMER
SELECTOR SWITCH POSITION LOCAL STATUS DO x x HARDWIRED =D09+S1
316 MS-XFR-601B
TRANSFORMER
CIRCUIT BREAKER Q0 CLOSED STATUS DO x x HARDWIRED =D09+S1
317 MS-XFR-601B
TRANSFORMER
CIRCUIT BREAKER Q0 OPEN STATUS DO x x HARDWIRED =D09+S1
318 MS-XFR-601B
TRANSFORMER
GENERAL LOCKOUT SF6 * DO x x x HARDWIRED =D09+S1
319 MS-XFR-601B
TRANSFORMER
BB DISCONNECTOR Q1 OPEN STATUS DO x x HARDWIRED =D09+S1
320 MS-XFR-601B
TRANSFORMER
BB DISCONNECTOR Q1 CLOSED STATUS DO x x HARDWIRED =D09+S1
321 MS-XFR-601B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 OPEN STATUS DO x x HARDWIRED =D09+S1
322 MS-XFR-601B
RPLC PROJECT

Sheet 15 of 21
Rev D

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 CLOSED STATUS DO x x HARDWIRED =D09+S1
323 MS-XFR-601B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 OPEN STATUS DO x x HARDWIRED =D09+S1
324 MS-XFR-601B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 CLOSED STATUS DO x x HARDWIRED =D09+S1
325 MS-XFR-601B
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 OPEN STATUS DO x x HARDWIRED =D09+S1
326 MS-XFR-601B
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 CLOSED STATUS DO x x HARDWIRED =D09+S1
327 MS-XFR-601B
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 OPEN STATUS DO x x HARDWIRED =D09+S1
328 MS-XFR-601B
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 CLOSED STATUS DO x x HARDWIRED =D09+S1
329 MS-XFR-601B
TRANSFORMER
CIRCUIT BREAKER Q0 OPEN COMMAND DI x x x HARDWIRED =D09+S1
330 MS-XFR-601B
TRANSFORMER
CIRCUIT BREAKER Q0 CLOSE COMMAND DI x x x HARDWIRED =D09+S1
331 MS-XFR-601B
TRANSFORMER
BB DISCONNECTOR Q1 OPEN COMMAND DI x x x HARDWIRED =D09+S1
332 MS-XFR-601B
TRANSFORMER
BB DISCONNECTOR Q1 CLOSE COMMAND DI x x x HARDWIRED =D09+S1
333 MS-XFR-601B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 OPEN COMMAND DI x x x HARDWIRED =D09+S1
334 MS-XFR-601B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 CLOSE COMMAND DI x x x HARDWIRED =D09+S1
335 MS-XFR-601B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 OPEN COMMAND DI x x x HARDWIRED =D09+S1
336 MS-XFR-601B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 CLOSE COMMAND DI x x x HARDWIRED =D09+S1
337 MS-XFR-601B
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 OPEN COMMAND DI x x x HARDWIRED =D09+S1
338 MS-XFR-601B
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 CLOSE COMMAND DI x x x HARDWIRED =D09+S1
339 MS-XFR-601B
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 OPEN COMMAND DI x x x HARDWIRED =D09+S1
340 MS-XFR-601B
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 CLOSE COMMAND DI x x x HARDWIRED =D09+S1
341 MS-XFR-601B
TRANSFORMER
CURRENT L2 (A) AO x x ETHERNET =D09+R09
342 MS-XFR-601B
TRANSFORMER
MASTER INTERLOCK OVERRIDE DO x x HARDWIRED =D09+S1
343 MS-XFR-601B
TRANSFORMER
MAIN PROTECTION TP1 ON TEST DO x x HARDWIRED =D09+R09
344 MS-XFR-601B
TRANSFORMER
BACKUP PROTECTION TP2 ON TEST DO x x HARDWIRED =D09+R09
345 MS-XFR-601B
RPLC PROJECT

Sheet 16 of 21
Rev D

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

TRANSFORMER
MAIN PROTECTION TP1 UNAVAILABLE DO x x x HARDWIRED =D09+R09
346 MS-XFR-601B
TRANSFORMER
BACKUP PROTECTION TP2 UNAVAILABLE DO x x x HARDWIRED =D09+R09
347 MS-XFR-601B
TRANSFORMER
TRIP CIRCUIT MONITORING 1 74 DO x x x HARDWIRED =D10+R10
348 MS-XFR-602B
TRANSFORMER
TRIP CIRCUIT MONITORING 2 74 DO x x x HARDWIRED =D10+R10
349 MS-XFR-602B
TRANSFORMER
LOCKOUT RELAY OPERATED 86 DO x x x HARDWIRED =D10+R10
350 MS-XFR-602B
TRANSFORMER
OVERCURRENT TRIP 51 DO x x x ETHERNET =D10+R10
351 MS-XFR-602B
TRANSFORMER
EARTH FAULT TRIP 51N DO x x x ETHERNET =D10+R10
352 MS-XFR-602B
TRANSFORMER
87L TRIP 87L DO x x x ETHERNET =D10+R10
353 MS-XFR-602B
TRANSFORMER
+R10 PANEL AC FEEDER FAULT DO x x x HARDWIRED =D10+R10
354 MS-XFR-602B
TRANSFORMER
SELECTOR SWITCH POSITION REMOTE STATUS DO x x HARDWIRED =D10+S1
355 MS-XFR-602B
TRANSFORMER
SELECTOR SWITCH POSITION LOCAL STATUS DO x x HARDWIRED =D10+S1
356 MS-XFR-602B
TRANSFORMER
CIRCUIT BREAKER Q0 CLOSED STATUS DO x x HARDWIRED =D10+S1
357 MS-XFR-602B
TRANSFORMER
CIRCUIT BREAKER Q0 OPEN STATUS DO x x HARDWIRED =D10+S1
358 MS-XFR-602B
TRANSFORMER
GENERAL LOCKOUT SF6 * DO x x x HARDWIRED =D10+S1
359 MS-XFR-602B
TRANSFORMER
BB DISCONNECTOR Q1 OPEN STATUS DO x x HARDWIRED =D10+S1
360 MS-XFR-602B
TRANSFORMER
BB DISCONNECTOR Q1 CLOSED STATUS DO x x HARDWIRED =D10+S1
361 MS-XFR-602B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 OPEN STATUS DO x x HARDWIRED =D10+S1
362 MS-XFR-602B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 CLOSED STATUS DO x x HARDWIRED =D10+S1
363 MS-XFR-602B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 OPEN STATUS DO x x HARDWIRED =D10+S1
364 MS-XFR-602B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 CLOSED STATUS DO x x HARDWIRED =D10+S1
365 MS-XFR-602B
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 OPEN STATUS DO x x HARDWIRED =D10+S1
366 MS-XFR-602B
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 CLOSED STATUS DO x x HARDWIRED =D10+S1
367 MS-XFR-602B
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 OPEN STATUS DO x x HARDWIRED =D10+S1
368 MS-XFR-602B
RPLC PROJECT

Sheet 17 of 21
Rev D

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 CLOSED STATUS DO x x HARDWIRED =D10+S1
369 MS-XFR-602B
TRANSFORMER
CIRCUIT BREAKER Q0 OPEN COMMAND DI x x x HARDWIRED =D10+S1
370 MS-XFR-602B
TRANSFORMER
CIRCUIT BREAKER Q0 CLOSE COMMAND DI x x x HARDWIRED =D10+S1
371 MS-XFR-602B
TRANSFORMER
BB DISCONNECTOR Q1 OPEN COMMAND DI x x x HARDWIRED =D10+S1
372 MS-XFR-602B
TRANSFORMER
BB DISCONNECTOR Q1 CLOSE COMMAND DI x x x HARDWIRED =D10+S1
373 MS-XFR-602B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 OPEN COMMAND DI x x x HARDWIRED =D10+S1
374 MS-XFR-602B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 CLOSE COMMAND DI x x x HARDWIRED =D10+S1
375 MS-XFR-602B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 OPEN COMMAND DI x x x HARDWIRED =D10+S1
376 MS-XFR-602B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 CLOSE COMMAND DI x x x HARDWIRED =D10+S1
377 MS-XFR-602B
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 OPEN COMMAND DI x x x HARDWIRED =D10+S1
378 MS-XFR-602B
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 CLOSE COMMAND DI x x x HARDWIRED =D10+S1
379 MS-XFR-602B
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 OPEN COMMAND DI x x x HARDWIRED =D10+S1
380 MS-XFR-602B
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 CLOSE COMMAND DI x x x HARDWIRED =D10+S1
381 MS-XFR-602B
TRANSFORMER
CURRENT L2 (A) AO x x ETHERNET =D10+R10
382 MS-XFR-602B
TRANSFORMER
MASTER INTERLOCK OVERRIDE DO x x HARDWIRED =D10+S1
383 MS-XFR-602B
TRANSFORMER
MAIN PROTECTION TP1 ON TEST DO x x HARDWIRED =D10+R10
384 MS-XFR-602B
TRANSFORMER
BACKUP PROTECTION TP2 ON TEST DO x x HARDWIRED =D10+R10
385 MS-XFR-602B
TRANSFORMER
MAIN PROTECTION TP1 UNAVAILABLE DO x x x HARDWIRED =D10+R10
386 MS-XFR-602B
TRANSFORMER
BACKUP PROTECTION TP2 UNAVAILABLE DO x x x HARDWIRED =D10+R10
387 MS-XFR-602B
TRANSFORMER
TRIP CIRCUIT MONITORING 1 74 DO x x x HARDWIRED =D11+R11
388 MS-XFR-603B
TRANSFORMER
TRIP CIRCUIT MONITORING 2 74 DO x x x HARDWIRED =D11+R11
389 MS-XFR-603B
TRANSFORMER
LOCKOUT RELAY OPERATED 86 DO x x x HARDWIRED =D11+R11
390 MS-XFR-603B
TRANSFORMER
OVERCURRENT TRIP 51 DO x x x ETHERNET =D11+R11
391 MS-XFR-603B
RPLC PROJECT

Sheet 18 of 21
Rev D

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

TRANSFORMER
EARTH FAULT TRIP 51N DO x x x ETHERNET =D11+R11
392 MS-XFR-603B
TRANSFORMER
87L TRIP 87L DO x x x ETHERNET =D11+R11
393 MS-XFR-603B
TRANSFORMER
+R11 PANEL AC FEEDER FAULT DO x x x HARDWIRED =D11+R11
394 MS-XFR-603B
TRANSFORMER
SELECTOR SWITCH POSITION REMOTE STATUS DO x x HARDWIRED =D11+S1
395 MS-XFR-603B
TRANSFORMER
SELECTOR SWITCH POSITION LOCAL STATUS DO x x HARDWIRED =D11+S1
396 MS-XFR-603B
TRANSFORMER
CIRCUIT BREAKER Q0 CLOSED STATUS DO x x HARDWIRED =D11+S1
397 MS-XFR-603B
TRANSFORMER
CIRCUIT BREAKER Q0 OPEN STATUS DO x x HARDWIRED =D11+S1
398 MS-XFR-603B
TRANSFORMER
GENERAL LOCKOUT SF6 * DO x x x HARDWIRED =D11+S1
399 MS-XFR-603B
TRANSFORMER
BB DISCONNECTOR Q1 OPEN STATUS DO x x HARDWIRED =D11+S1
400 MS-XFR-603B
TRANSFORMER
BB DISCONNECTOR Q1 CLOSED STATUS DO x x HARDWIRED =D11+S1
401 MS-XFR-603B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 OPEN STATUS DO x x HARDWIRED =D11+S1
402 MS-XFR-603B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 CLOSED STATUS DO x x HARDWIRED =D11+S1
403 MS-XFR-603B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 OPEN STATUS DO x x HARDWIRED =D11+S1
404 MS-XFR-603B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 CLOSED STATUS DO x x HARDWIRED =D11+S1
405 MS-XFR-603B
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 OPEN STATUS DO x x HARDWIRED =D11+S1
406 MS-XFR-603B
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 CLOSED STATUS DO x x HARDWIRED =D11+S1
407 MS-XFR-603B
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 OPEN STATUS DO x x HARDWIRED =D11+S1
408 MS-XFR-603B
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 CLOSED STATUS DO x x HARDWIRED =D11+S1
409 MS-XFR-603B
TRANSFORMER
CIRCUIT BREAKER Q0 OPEN COMMAND DI x x x HARDWIRED =D11+S1
410 MS-XFR-603B
TRANSFORMER
CIRCUIT BREAKER Q0 CLOSE COMMAND DI x x x HARDWIRED =D11+S1
411 MS-XFR-603B
TRANSFORMER
BB DISCONNECTOR Q1 OPEN COMMAND DI x x x HARDWIRED =D11+S1
412 MS-XFR-603B
TRANSFORMER
BB DISCONNECTOR Q1 CLOSE COMMAND DI x x x HARDWIRED =D11+S1
413 MS-XFR-603B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 OPEN COMMAND DI x x x HARDWIRED =D11+S1
414 MS-XFR-603B
RPLC PROJECT

Sheet 19 of 21
Rev D

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 CLOSE COMMAND DI x x x HARDWIRED =D11+S1
415 MS-XFR-603B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 OPEN COMMAND DI x x x HARDWIRED =D11+S1
416 MS-XFR-603B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 CLOSE COMMAND DI x x x HARDWIRED =D11+S1
417 MS-XFR-603B
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 OPEN COMMAND DI x x x HARDWIRED =D11+S1
418 MS-XFR-603B
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 CLOSE COMMAND DI x x x HARDWIRED =D11+S1
419 MS-XFR-603B
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 OPEN COMMAND DI x x x HARDWIRED =D11+S1
420 MS-XFR-603B
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 CLOSE COMMAND DI x x x HARDWIRED =D11+S1
421 MS-XFR-603B
TRANSFORMER
CURRENT L2 (A) AO x x ETHERNET =D11+R11
422 MS-XFR-603B
TRANSFORMER
MASTER INTERLOCK OVERRIDE DO x x HARDWIRED =D11+S1
423 MS-XFR-603B
TRANSFORMER
MAIN PROTECTION TP1 ON TEST DO x x HARDWIRED =D11+R11
424 MS-XFR-603B
TRANSFORMER
BACKUP PROTECTION TP2 ON TEST DO x x HARDWIRED =D11+R11
425 MS-XFR-603B
TRANSFORMER
MAIN PROTECTION TP1 UNAVAILABLE DO x x x HARDWIRED =D11+R11
426 MS-XFR-603B
TRANSFORMER
BACKUP PROTECTION TP2 UNAVAILABLE DO x x x HARDWIRED =D11+R11
427 MS-XFR-603B
TRANSFORMER
TRIP CIRCUIT MONITORING 1 74 DO x x x HARDWIRED =D12+R12
428 MS-XFR-604B
TRANSFORMER
TRIP CIRCUIT MONITORING 2 74 DO x x x HARDWIRED =D12+R12
429 MS-XFR-604B
TRANSFORMER
LOCKOUT RELAY OPERATED 86 DO x x x HARDWIRED =D12+R12
430 MS-XFR-604B
TRANSFORMER
OVERCURRENT TRIP 51 DO x x x ETHERNET =D12+R12
431 MS-XFR-604B
TRANSFORMER
EARTH FAULT TRIP 51N DO x x x ETHERNET =D12+R12
432 MS-XFR-604B
TRANSFORMER
87L TRIP 87L DO x x x ETHERNET =D12+R12
433 MS-XFR-604B
TRANSFORMER
+R12 PANEL AC FEEDER FAULT DO x x x HARDWIRED =D12+R12
434 MS-XFR-604B
TRANSFORMER
SELECTOR SWITCH POSITION REMOTE STATUS DO x x HARDWIRED =D12+S1
435 MS-XFR-604B
TRANSFORMER
SELECTOR SWITCH POSITION LOCAL STATUS DO x x HARDWIRED =D12+S1
436 MS-XFR-604B
TRANSFORMER
CIRCUIT BREAKER Q0 CLOSED STATUS DO x x HARDWIRED =D12+S1
437 MS-XFR-604B
TRANSFORMER
CIRCUIT BREAKER Q0 OPEN STATUS DO x x HARDWIRED =D12+S1
438 MS-XFR-604B
TRANSFORMER
GENERAL LOCKOUT SF6 * DO x x x HARDWIRED =D12+S1
439 MS-XFR-604B
TRANSFORMER
BB DISCONNECTOR Q1 OPEN STATUS DO x x HARDWIRED =D12+S1
440 MS-XFR-604B
RPLC PROJECT

Sheet 20 of 21
Rev D

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

TRANSFORMER
BB DISCONNECTOR Q1 CLOSED STATUS DO x x HARDWIRED =D12+S1
441 MS-XFR-604B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 OPEN STATUS DO x x HARDWIRED =D12+S1
442 MS-XFR-604B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 CLOSED STATUS DO x x HARDWIRED =D12+S1
443 MS-XFR-604B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 OPEN STATUS DO x x HARDWIRED =D12+S1
444 MS-XFR-604B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 CLOSED STATUS DO x x HARDWIRED =D12+S1
445 MS-XFR-604B
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 OPEN STATUS DO x x HARDWIRED =D12+S1
446 MS-XFR-604B
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 CLOSED STATUS DO x x HARDWIRED =D12+S1
447 MS-XFR-604B
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 OPEN STATUS DO x x HARDWIRED =D12+S1
448 MS-XFR-604B
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 CLOSED STATUS DO x x HARDWIRED =D12+S1
449 MS-XFR-604B
TRANSFORMER
CIRCUIT BREAKER Q0 OPEN COMMAND DI x x x HARDWIRED =D12+S1
450 MS-XFR-604B
TRANSFORMER
CIRCUIT BREAKER Q0 CLOSE COMMAND DI x x x HARDWIRED =D12+S1
451 MS-XFR-604B
TRANSFORMER
BB DISCONNECTOR Q1 OPEN COMMAND DI x x x HARDWIRED =D12+S1
452 MS-XFR-604B
TRANSFORMER
BB DISCONNECTOR Q1 CLOSE COMMAND DI x x x HARDWIRED =D12+S1
453 MS-XFR-604B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 OPEN COMMAND DI x x x HARDWIRED =D12+S1
454 MS-XFR-604B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 CLOSE COMMAND DI x x x HARDWIRED =D12+S1
455 MS-XFR-604B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 OPEN COMMAND DI x x x HARDWIRED =D12+S1
456 MS-XFR-604B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 CLOSE COMMAND DI x x x HARDWIRED =D12+S1
457 MS-XFR-604B
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 OPEN COMMAND DI x x x HARDWIRED =D12+S1
458 MS-XFR-604B
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 CLOSE COMMAND DI x x x HARDWIRED =D12+S1
459 MS-XFR-604B
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 OPEN COMMAND DI x x x HARDWIRED =D12+S1
460 MS-XFR-604B
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 CLOSE COMMAND DI x x x HARDWIRED =D12+S1
461 MS-XFR-604B
TRANSFORMER
CURRENT L2 (A) AO x x ETHERNET =D12+R12
462 MS-XFR-604B
TRANSFORMER
MASTER INTERLOCK OVERRIDE DO x x HARDWIRED =D12+S1
463 MS-XFR-604B
TRANSFORMER
MAIN PROTECTION TP1 ON TEST DO x x HARDWIRED =D12+R12
464 MS-XFR-604B
TRANSFORMER
BACKUP PROTECTION TP2 ON TEST DO x x HARDWIRED =D12+R12
465 MS-XFR-604B
TRANSFORMER
MAIN PROTECTION TP1 UNAVAILABLE DO x x x HARDWIRED =D12+R12
466 MS-XFR-604B
RPLC PROJECT

Sheet 21 of 21
Rev D

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

TRANSFORMER
BACKUP PROTECTION TP2 UNAVAILABLE DO x x x HARDWIRED =D12+R12
467 MS-XFR-604B
+P00 PANEL AC FEEDER FAULT DO x x x HARDWIRED =D00+P00 ANNUNCIATOR PANEL
468
ANNUNCIATOR PANEL 1 -F091 FEEDER FAULT DO x x x HARDWIRED =D00+P00 ANNUNCIATOR PANEL
469
125VCC DISTRIBUTION TO TRANSFORMER MS-XFR-604A ON FAULT DO x x x HARDWIRED =D00+P00 ANNUNCIATOR PANEL
470
125VCC DISTRIBUTION TO TRANSFORMER MS-XFR-603A ON FAULT DO x x x HARDWIRED =D00+P00 ANNUNCIATOR PANEL
471
125VCC DISTRIBUTION TO TRANSFORMER MS-XFR-602A ON FAULT DO x x x HARDWIRED =D00+P00 ANNUNCIATOR PANEL
472
125VCC DISTRIBUTION TO TRANSFORMER MS-XFR-601A ON FAULT DO x x x HARDWIRED =D00+P00 ANNUNCIATOR PANEL
473
125VCC DISTRIBUTION TO LINE A FROM PAL ON FAULT DO x x x HARDWIRED =D00+P00 ANNUNCIATOR PANEL
474
125VCC DISTRIBUTION TO BUSBAR COUPLER ON FAULT DO x x x HARDWIRED =D00+P00 ANNUNCIATOR PANEL
475
ANNUNCIATOR PANEL 2 -F092 FEEDER FAULT DO x x x HARDWIRED =D00+P00 ANNUNCIATOR PANEL
476
125VCC DISTRIBUTION TO LINE B FROM PAL ON FAULT DO x x x HARDWIRED =D00+P00 ANNUNCIATOR PANEL
477
125VCC DISTRIBUTION TO TRANSFORMER MS-XFR-601B ON FAULT DO x x x ETHERNET =D00+P00 ANNUNCIATOR PANEL
478
125VCC DISTRIBUTION TO TRANSFORMER MS-XFR-602B ON FAULT DO x x x HARDWIRED =D00+P00 ANNUNCIATOR PANEL
479
125VCC DISTRIBUTION TO TRANSFORMER MS-XFR-603B ON FAULT DO x x x HARDWIRED =D00+P00 ANNUNCIATOR PANEL
480
125VCC DISTRIBUTION TO TRANSFORMER MS-XFR-604B ON FAULT DO x x x HARDWIRED =D00+P00 ANNUNCIATOR PANEL
481
ANNUNCIATOR PANEL 1 UNAVAILABLE DO x x x HARDWIRED =D00+P00 ANNUNCIATOR PANEL
482
ANNUNCIATOR PANEL 2 UNAVAILABLE DO x x x HARDWIRED =D00+P00 ANNUNCIATOR PANEL
483

* Note: Maintenance network switch shall be provided for diagnostic and troubleshooting in PSCS

TOTAL DI DO AI AO HARDWIRED ETHERNET

134 305 28 404 63

You might also like