This document provides instructions for assembling a communication cable to connect a Mitsubishi PLC, including FX0, FX0N, FX0S, FX2N, FX1S, FX1N, or FX2NC models, to a Maple Systems OIT. The cable requires a DE-9S connector at the OIT end, a mini-DIN 8-pin connector at the PLC end, and a 3-pair twisted cable. A green wire and shield wire should be twisted and soldered together for connecting to chassis ground on both ends.

Uploaded by

nelhani01
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (2 votes)
1K views1 page

10230024

This document provides instructions for assembling a communication cable to connect a Mitsubishi PLC, including FX0, FX0N, FX0S, FX2N, FX1S, FX1N, or FX2NC models, to a Maple Systems OIT. The cable requires a DE-9S connector at the OIT end, a mini-DIN 8-pin connector at the PLC end, and a 3-pair twisted cable. A green wire and shield wire should be twisted and soldered together for connecting to chassis ground on both ends.

Uploaded by

nelhani01
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

C A B L E A S S E M B L Y I N S T R U C T I O N

Controller Model: Mitsubishi FX0, FX0N, FX0S, FX2N, FX1S, FX1N,


and FX2NC
Maple OIT Model: Silver Series
Communication Type: RS-422/ RS485 with Mini DIN 8 Pin Connector at PLC

Use the wiring diagram and illustration to assemble a communication cable for use with a
Mitsubishi FX0, FX0N, FX0S, FX2N, FX1S, FX1N or FX2NC PLC.

18 AWG Green wire


4-40 x 1/2 Retainer
To Chassis Ground
Screw, 2 places
DE9S Connector Mini-DIN 8-Pin
& DE9 Backshell Connector
A

3 Pair Twisted A
24 AWG Shielded cable
OIT END PLC END
NOTES:
1 Twist together 18 AWG green wire and shield wire. Solder
wires and insulate with heatshrink to avoid shorting.
2 Connect shield wire to metal housing of the mini-DIN 8-pin connector.

1
Green
To Chassis Ground
Shield
OIT 2 Mini PLC 1 2
9S DIN8
RXD- 1 4 TXD- 3 4 5
8
RXD+ 2 7 TXD+ 6 7
Return 5 3 Signal Ground
Pin Configuration
TXD- 3 1 RXD- Mini-DIN8
TXD+ 4 2 RXD+ View A-A
(Solder Side)
PLC[RS485]

1023-0024, Rev 03