Shell Diala S3 ZX-IG Dried

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Technical Data Sheet

Replaces: Shell Diala GX Dried

EXTRA PERFORMANCE
RELIABLE PERFORMANCE
Shell Diala S3 ZX-IG Dried MEETS IEC 60296
MEETS ASTM D3487 TYPE II
Premium Inhibited Electrical Insulating Oil
Shell Diala S3 ZX-IG Dried is a premium inhibited insulating oil manufactured from highly
refined mineral oils. It offers very high oxidation stability, good dielectric strength and gas
absorbing behaviour. Shell Diala S3 ZX-IG Dried has excellent low temperature properties
and is dried to achieve a higher breakdown voltage than required by standard industry
norms.
Shell Diala S3 ZX-IG Dried meets both the established and new industry copper corrosion
tests.

Applications Shell Diala S3 ZX-IG Dried is specially dried and


handled to achieve a low water content and
Transformers retain a high breakdown voltage at point of
All Power transformer types and applications (e.g. delivery. This enables it to be used in many
generator transformers, shunt reactors, distribution applications without further treatment.
transformers) and high voltage DC (HVDC) converter
stations
Specification and Approvals
Electrical equipment
IEC 60296 (2003), Table 2 Transformer Oil (I),
Components such as rectifiers, circuit breakers,
inhibited
bushings, instrument transformers and switchgears
Baader oxidation test of (obsolete) DIN 57370-1
Advice on applications not covered in this leaflet may (1978)
be obtained from your Shell Representative.

Storage precautions
Performance Features and Advantages The critical electrical properties of Shell Diala S3 ZX-
Extended oil life IG Dried are easily compromised by trace
Shell Diala S3 ZX-IG Dried is a fully inhibited oil contamination with foreign material. Typically
giving outstanding oxidation performance and an encountered contaminants include moisture,
extended oil life. particles, fibres and surfactants. Therefore, it is
Diala S3 ZX-IG Dried provides gas absorbing imperative that electrical insulating oils be kept clean
performance in transformers running under very and dry.
high voltage and electrical stress. This makes it It is strongly recommended that storage containers
particularly suitable for Generator transformer and be dedicated for electrical service and include air-
HVDC converter applications. tight seals. It is further recommended that electrical
insulating oils be stored indoors in climate-controlled
Transformer protection
environments.
Shell Diala S3 ZX-IG Dried is non-corrosive towards
copper, with no need for additional passivation.
Shell Diala S3 ZX-IG Dried meets all relevant tests Health and Safety
for copper corrosion, namely the established DIN Guidance on Health and Safety is available on the
51353 (Silver Strip Test), ASTM D1275, and also the appropriate Material Safety Data Sheet which can
latest more severe tests: IEC 62535 and ASTM be obtained from your Shell representative.
D1275B.
Shell Diala S3 ZX-IG Dried is free from
System efficiency
polychlorinated biphenyls (PCB).
The good low temperature properties of the oil
ensures proper heat transfer inside the transformer,
even from very low starting temperatures.

Shell Lubricants Page 1 of 2 November 2009


Technical Data Sheet

Protect the environment


Take used oil to an authorized collection point. Do not
discharge into drains, soil or water.

Typical Physical Characteristics


Property Units Method IEC 60296 Requirement Shell Diala S3 ZX-IG
Dried

Appearance IEC 60296 Clear, free from sediment Complies


and suspended matters

Density at 15 C kg/m3 ISO 3675 - 890

Density at 20 C kg/m3 ISO 3675 Max. 895 886

Kinematic viscosity at 40 C mm2/s ISO 3104 Max. 12 8,0

Kinematic viscosity at 30 C mm2/s ISO 3104 Max. 1.800 1.100

Flashpoint P.M. C ISO 2719 Max. 135 136

Pourpoint C ISO 3016 Max. -40 -57

Neutralisation value mg KOH/g IEC 62021-1 Max. 0,01 < 0,01

Corrosive Sulphur DIN 51353 Not corrosive Not corrosive

Corrosive Sulphur IEC 62535 Not corrosive Not corrosive

Corrosive Sulphur ASTM D 1275 B - Not corrosive

Breakdown voltage kV IEC 60156


As delivered Min. 30 >60
After treatment Min. 70 >70
Dielectric Dissipation Factor (DDF) IEC 60247 Max. 0,005 0,002
at 90 C

Gassing mm/min IEC 60628 A - -14

Oxidation Stability IEC 61125 C


(500 h /120 C)

Total acidity mg KOH/g Max.1,2 1,0

Sludge %m Max. 0,8 0,45

DDF at 90 C IEC 60247 Max. 0,5 0,12

Oxidation Stability DIN 51554 -


Baader (28 d /110 C)
Neutralisation value mg KOH/g 0,1
Sludge content %m 0,01
DDF at 90C 0,01

These characteristics are typical of current production.