CHB Wall Design2

The document provides details on the vertical and horizontal reinforcement design for a concrete wall. For the vertical reinforcement, with a moment of 1.98 kN-m, rebar diameter of 12mm and spacing of 600mm is required to provide an area of 174.628 mm^2. For the horizontal reinforcement, a moment of 2.18 kN-m is resisted by 12mm diameter rebar spaced at 400mm intervals to provide an area of 192.267 mm^2.

Uploaded by

gon972001
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
278 views1 page

CHB Wall Design2

The document provides details on the vertical and horizontal reinforcement design for a concrete wall. For the vertical reinforcement, with a moment of 1.98 kN-m, rebar diameter of 12mm and spacing of 600mm is required to provide an area of 174.628 mm^2. For the horizontal reinforcement, a moment of 2.18 kN-m is resisted by 12mm diameter rebar spaced at 400mm intervals to provide an area of 192.267 mm^2.

Uploaded by

gon972001
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

CHB Wall Reinforcement Design

Vertical Reinforcement

f'm = 4.83 Mpa d= 75 mm


fy = 275 Mpa
Rebar diameter = 12 mm

Output moment from STAAD, Mu = 1.98 kN-m


phi = 0.85

Required As = 174.628 mm^2


1.54405

Required spacing = 647.648 mm

Use 12 mm diameter bar @ 600 mm spacing

Horizontal Reinforcement

f'm = 4.83 Mpa d= 75 mm


fy = 275 Mpa
Rebar diameter = 12 mm

Output moment from STAAD, Mu = 2.18 kN-m


phi = 0.85

Required As = 192.267 mm^2


1.70001

Required spacing = 588.23 mm

Use 12 mm diameter bar @ 400 mm spacing