Energy Efficient Transformers

Low Voltage General Purpose


Dry Type

Class 7400
Catalog
7400CT0601R3/07

07

CONTENTS
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page
Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Three-Phase Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
240/120 Four-Wire Delta Connection Transformers. . . . . . . . . . . . . . . . . . 8
Single-Phase Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Non-Linear Energy Efficient Transformers . . . . . . . . . . . . . . . . . . . . . . . . 11
Watchdog Low Temperature Rise Transformers . . . . . . . . . . . . . . . . . . 12
Made-To-Order Transformers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Enclosure Diagrams and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
NEC Reference: Installing and Connecting Transformers . . . . . . . . . . . . 33
Wire Range Part Numbers and Lug Kits . . . . . . . . . . . . . . . . . . . . . . . . . 34
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Frequently Asked Questions and Answers . . . . . . . . . . . . . . . . . . . . . . . 38
Energy Efficient Transfomers
Product Description

Product Description

Key Features of the Square D Energy Policy Act


Energy Efficient Dry-Type
The Energy Policy Act of 2005 declared the following information regarding
Transformers low voltage dry-type distribution transformers:

Smaller total area used, with 3 in. (76 mm) The efficiency of a low voltage dry-type distribution transformer
clearance from ventilated openings instead manufactured on or after January 1, 2007 shall be the Class I Efficiency
of 6 in. (152 mm), reducing the distance from Levels for distribution transformers specified in Table 4-2 of the Guide for
the wall to the front of the device by 3 in. Determining Energy Efficiency for Distribution Transformers, published by
(76 mm) the National Electrical Manufacturers Association (NEMA TP-12002).
Terminals are sized to handle lug kits that Schneider Electric introduced the first TP1-compliant low voltage dry-type
are coordinated with other Square D distribution transformers in December 1998. With the 2005 Energy Act,
products, increasing the ease of installation Schneider Electric is expanding its offering of TP-1-compliant products by
when used with other Square D equipment launching a new line of TP-1 qualified transformers.
Increased wiring compartments provide a NATURAL RESOURCES CANADA
bending radius for 250% primary cables and
multiple feeds on the secondary Natural Resources Canada declared the following information regarding
All units have 200% neutral to allow dry-type transformers and the energy performance test procedure:
customers to feed standard and non-linear Dry-Type Transformers
panels
The Office of Energy Efficiency (OEE) of Natural Resources Canada
220 C UL Listed insulation system (NRCan) has amended Canada's Energy Efficiency Regulations to require
Decreased weight for easier handling of units Canadian dealers to comply with minimum energy performance standards
for dry-type transformers imported or shipped inter-provincially for sale or
lease in Canada.
These regulations and subsequent amendments were published in the
Canadian Gazette Part 1 in May 2006.
Energy Performance Test Procedure
The Canadian Standards Association standard CAN/CSA-C802.2-00,
Minimum Efficiency Values for Dry-Type Transformers, is the test procedure
for transformers under regulation.
The test procedure is the same as that in the National Electrical
Manufacturers Association (NEMA TP-11996), Guide for Determining
Energy Efficiency for Distribution Transformers and associated document
TP-21998, Standard Test Method for Measuring the Energy Consumption
of Distribution Transformers, in the United States.

2
19992007 Schneider Electric All Rights Reserved 04/2007
Energy Efficient Transformers
General Information

General Information

Saving Money by Saving Energy


Minimum efficiencies have been established for each size of transformer, and extensive design, testing,
and manufacturing time has been spent to ensure each transformer meets or exceeds these efficiencies.
Surveys show that typical loading of low voltage dry-type transformers on a 24-hour average basis is
only 35% of full-load rating. At such loading levels, Square D Lean Power Energy Efficient
Transformers manufactured by Schneider Electric provide the best combination of optimal
performance and superior quality.
The Square D Energy Efficient transformer offering includes all of the popular options including low
temperature rise, 115 C and 80 C, and aluminum or copper windings. These transformers are part of
a complete line of Lean Power products from Schneider Electric. Our power conservation,
management and monitoring products, systems, and services help to reduce energy consumption in
business and industry environments.

Table 1: Transformer Efficiency Levels

Single-Phase Three-Phase

kVA % Efficiency kVA % Efficiency


15.0 97.7 15.0 97.0
25.0 98.0 30.0 97.5
37.5 98.2 45.0 97.7
50.0 98.3 75.0 98.0
75.0 98.5 112.5 98.2
100.0 98.6 150.0 98.3
167.0 98.7 225.0 98.5
250.0 98.8 300.0 98.6
333.0 98.9 500.0 98.7
750.0 98.8
1000.0 98.9
Temperature: 75 C, 35% of full-load capacity

Three-phase energy efficient transformer


(top cover, and all panels removed)

3
04/2007 19992007 Schneider Electric All Rights Reserved
Energy Efficient Transformers
Three-Phase Transformers

Three-Phase Transformers

Refer to Tables 29 for three-phase transformer information.

Table 2: 480 V Delta Primary to 208Y/120 V Secondary

Weight Primary Secondary

Wiring Diagram
pages 1627)
(lbs) Current Current

Enclosure1
(Refer to
Part C

Nameplate

Nameplate
kVA Cu NEC NEC NEC
Number (Add Rise Max Max Max
Al
CU Rating Rating Rating
suffix)2 125% 250% 125%
15 EE15T3H 17D 220 310 150 18.0 25 45 41.7 60
30 EE30T3H 17D 260 340 150 36.1 45 90 83.4 110
45 EE45T3H 18D 320 372 150 54.2 70 125 125.1 175
75 EE75T3H 20D Figure 1 410 527 150 90.3 125 225 208.4 275
on
112.5 EE112T3H 21D page 28 620 725 150 135.5 175 300 312.6 400
150 EE150T3H 22D 800 920 150 180.6 225 450 416.9 500
225 EE225T3H 24D 1110 1090 150 271.0 300 600 625.3 800
300 EE300T3H 25D 1359 1535 150 361.3 450 900 833.7 1000
500 EE500T68H 30D Figure 2 1870 2300 150 602.1 800 1500 1389.5 1600
on
750 EE750T68H 31D page 29 3060 3710 150 903.2 1000 2000 2084.3 2500

10003 150 1202.8 1500 3000 2775.7 3000


1
NEMA Type 2 drip-proof enclosure. Weathershields available to upgrade the enclosures to NEMA Type 3R (suitable for outdoor
use). Standard transformers up through 75 kVA three-phase and 75 kVA single-phase can be mounted directly on wall via
mounting brackets.
2
Example of copper part number: EE75T3HCU
3
Contact your local Schneider Electric representative to obtain information about the 1000 kVA offering
(part number, enclosure, wiring diagram, and weights).

Table 3: 600 V Delta Primary to 208Y/120 V Secondary

Weight Primary Secondary


Wiring Diagram
pages 1627)

(lbs) Current Current


Enclosure1
(Refer to

Part C
Nameplate

Nameplate
kVA Cu NEC NEC NEC
Number (Add Rise Max Max Max
Al
CU Rating Rating Rating
suffix)2 125% 250% 125%
15 EE15T65H 17D 220 310 150 14.5 25 35 41.7 60
30 EE30T65H 17D 260 340 150 28.9 40 70 83.4 110
45 EE45T65H 18D 320 372 150 43.4 60 100 125.1 175
75 EE75T65H 20D Figure 1 410 527 150 72.3 100 175 208.4 275
on
112.5 EE112T65H 21D page 28 620 725 150 108.4 150 250 312.6 400
150 EE150T65H 22D 800 920 150 144.5 200 350 416.9 500
225 EE225T65H 24D 1110 1090 150 216.8 275 500 625.3 800
300 EE300T65H 25D 1359 1535 150 289.0 400 700 833.7 1000
500 EE500T79H 30D Figure 2 1870 2300 150 481.7 600 1200 1389.5 1600
on
750 EE750T79H 31D page 29 3060 3710 150 722.5 900 1600 2084.3 2500

10003 150 962.3 1200 2000 2775.7 3000


1
NEMA Type 2 drip-proof enclosure. Weathershields available to upgrade the enclosures to NEMA Type 3R (suitable for outdoor
use). Standard transformers up through 75 kVA three-phase and 75 kVA single-phase can be mounted directly on wall via
mounting brackets.
2
Example of copper part number: EE75T65HCU
3
Contact your local Schneider Electric representative to obtain information about the 1000 kVA offering
(part number, enclosure, wiring diagram, and weights).

4
19992007 Schneider Electric All Rights Reserved 04/2007
Energy Efficient Transformers
Three-Phase Transformers
Type

Table 4: 240 V Delta Primary to 208Y/120 V Secondary

Primary Secondary

Wiring Diagram
pages 1627)
Current Current

Enclosure1
(Refer to
Weight
Part C

Nameplate

Nameplate
kVA (lbs) NEC NEC NEC
Number Rise Max Max Max
Al
Rating Rating Rating
125% 250% 125%
15 EE15T67H 17D 240 150 36.1 50 90 41.6 60
30 EE30T67H 17D 260 150 72.2 100 175 83.3 110
45 EE45T67H 18D 380 150 108.3 150 250 124.9 175
75 EE75T67H 20D Figure 1 590 150 180.4 250 450 208.2 275
on
112.5 EE112T67H 21D page 28 620 150 270.6 350 600 312.3 400
150 EE150T67H 22D 805 150 360.8 500 800 416.4 600
225 EE225T67H 24D 975 150 541.3 700 1200 624.5 800
300 EE300T67H 25D 1570 150 721.7 1000 1600 832.7 1200
500 EE500T239H 30D Figure 7 1870 150 1202.8 1600 3000 1387.9 2000
on
750 EE750T239H 31D page 31 3010 150 1804.2 2500 4000 2081.8 3000
1 NEMA Type 2 drip-proof enclosure. Weathershields available to upgrade the enclosures to NEMA Type 3R (suitable for outdoor
use). Standard transformers up through 75 kVA three-phase and 75 kVA single-phase can be mounted directly on wall via
mounting brackets.

Table 5: 208 V Delta Primary to 208Y/120 V Secondary

Primary Secondary
Wiring Diagram
pages 1627)

Current Current
Enclosure1
Refer to

Weight
Part C

Nameplate

Nameplate
kVA (lbs) NEC NEC NEC
Number Rise Max Max Max
Al
Rating Rating Rating
125% 250% 125%
15 EE15T211H 17D 210 150 41.6 60 100 41.6 60
30 EE30T211H 17D 260 150 83.3 110 200 83.3 110
45 EE45T211H 18D 375 150 124.9 175 300 124.9 175
75 EE75T211H 20D 450 150 208.2 275 500 208.2 275
112.5 EE112T211H 21D Figure 7 605 150 312.3 400 700 312.3 400
on
150 EE150T211H 22D page 31 800 150 416.4 600 1000 416.4 600
225 EE225T211H 24D 1000 150 624.5 800 1200 624.5 800
300 EE300T211H 25D 1425 150 832.7 1200 2000 832.7 1200
500 EE500T211H 30D 1870 150 1387.9 2000 3000 1387.9 2000
750 EE750T211H 31D 3000 150 2081.8 3000 5000 2081.8 3000
1
NEMA Type 2 drip-proof enclosure. Weathershields available to upgrade the enclosures to NEMA Type 3R (suitable for outdoor
use). Standard transformers up through 75 kVA three-phase and 75 kVA single-phase can be mounted directly on wall via
mounting brackets.

5
04/2007 19992007 Schneider Electric All Rights Reserved
Energy Efficient Transformers
Three-Phase Transformers

Table 6: 480 V Delta Primary to 480Y/277 V Secondary

Primary Secondary

Wiring Diagram
pages 1627)
Current Current

Enclosure1
(Refer to
Weight
Part C

Nameplate

Nameplate
kVA (lbs) NEC NEC NEC
Number Rise Max Max Max
Al
Rating Rating Rating
125% 250% 125%
15 EE15T1814H 17D 220 150 18.0 25 45 18.0 25
30 EE30T1814H 17D 260 150 36.1 45 90 36.1 45
45 EE45T1814H 18D 320 150 54.2 70 125 54.2 70
75 EE75T1814H 20D Figure 1 410 150 90.3 125 225 90.3 125
on
112.5 EE112T1814H 21D page 28 620 150 135.5 175 300 135.5 175
150 EE150T1814H 22D 800 150 180.6 225 450 180.6 225
225 EE225T1814H 24D 1110 150 271.0 300 600 271.0 300
300 EE300T1814H 25D 1359 150 361.3 450 900 361.3 450
500 EE500T76H 30D Figure 2 1870 150 602.1 800 1500 602.1 800
on
750 EE750T76H 31D page 29 3060 150 903.2 1000 2000 903.2 1000
1 NEMA Type 2 drip-proof enclosure. Weathershields available to upgrade the enclosures to NEMA Type 3R (suitable for outdoor
use). Standard transformers up through 75 kVA three-phase and 75 kVA single-phase can be mounted directly on wall via
mounting brackets.

Table 7: 208 V Delta Primary to 480Y/277 V Secondary

Primary Secondary
Wiring Diagram
pages 1627)

Current Current
Enclosure1
(Refer to

Weight
Part C

Nameplate

Nameplate
kVA (lbs) NEC NEC NEC
Number Rise Max Max Max
Al
Rating Rating Rating
125% 250% 125%
15 EE15T212H 17D 220 150 41.7 60 100 18.0 25
30 EE30T212H 17D 260 150 83.4 110 200 36.1 45
45 EE45T212H 18D 320 150 125.1 175 300 54.2 70
75 EE75T212H 20D 410 150 208.4 275 500 90.3 125
112.5 EE112T212H 21D Figure 6 620 150 312.6 400 700 135.5 175
on
150 EE150T212H 22D page 31 800 150 416.9 600 1000 180.6 225
225 EE225T212H 24D 1110 150 625.3 800 1200 271.0 300
300 EE300T212H 25D 1359 150 833.7 1200 2000 361.3 450
500 EE500T212H 30D 1870 150 2000 3000 602.1 800
750 EE750T212H 31D 3060 150 3000 5000 903.2 1000
1
NEMA Type 2 drip-proof enclosure. Weathershields available to upgrade the enclosures to NEMA Type 3R (suitable for outdoor
use). Standard transformers up through 75 kVA three-phase and 75 kVA single-phase can be mounted directly on wall via
mounting brackets.

6
19992007 Schneider Electric All Rights Reserved 04/2007
Energy Efficient Transformers
Three-Phase Transformers

Table 8: 480 V Delta Primary to 240 V Delta Secondary

Primary Secondary

Wiring Diagram
pages 1627)
Current Current

Enclosure1
(Refer to
Weight
Part C

Nameplate

Nameplate
kVA (lbs) NEC NEC NEC
Number Rise Max Max Max
Al
Rating Rating Rating
125% 250% 125%
15 EE15T6H 17D 240 150 18.0 25 45 36.1 50
30 EE30T6H 17D 260 150 36.1 45 90 72.2 100
45 EE45T6H 18D 380 150 54.2 70 125 108.3 150
75 EE75T6H 20D Figure 3 590 150 90.3 125 225 180.4 250
on
112.5 EE112T6H 21D page 30 620 150 135.5 175 300 270.6 350
150 EE150T6H 22D 805 150 180.6 225 450 360.8 500
225 EE225T6H 24D 975 150 271.0 300 600 541.3 700
300 EE300T6H 25D 1570 150 361.3 450 900 721.7 1000
500 EE500T63H 30D Figure 4 1870 150 602.1 800 1500 1202.8 1600
on
750 EE750T63H 31D page 30 3010 150 903.2 1000 2000 1804.2 2500
1 NEMA Type 2 drip-proof enclosure. Weathershields available to upgrade the enclosures to NEMA Type 3R (suitable for outdoor
use). Standard transformers up through 75 kVA three-phase and 75 kVA single-phase can be mounted directly on wall via
mounting brackets.

Table 9: 480 V Delta Primary to 380Y/220 V Delta Secondary

Primary Secondary
Wiring Diagram
pages 1627)

Current Current
Enclosure1
(Refer to

Weight
Part C

Nameplate

Nameplate
kVA (lbs) NEC NEC NEC
Number Rise Max Max Max
Al
Rating Rating Rating
125% 250% 125%
15 EE15T1755H 17D 210 150 46.1 60 100 22.8 25
30 EE30T1755H 17D 260 150 83.3 110 200 45.6 50
45 EE45T1755H 18D 375 150 124.9 175 300 68.5 70
75 EE75T1755H 20D Figure 1 450 150 208.2 275 500 114.1 125
on
112.5 EE112T1755H 21D page 28 605 150 312.3 400 700 171.1 175
150 EE150T1755H 22D 800 150 416.4 600 1000 228.2 250
225 EE225T1755H 24D 1000 150 624.5 800 1200 342.3 350
300 EE300T1755H 25D 1425 150 832.7 1200 2000 456.3 500
500 EE500T96H 30D Figure 2 1870 150 1387.9 2000 3000 760.3 800
on
750 EE750T96H 31D page 29 3000 150 2081.8 3000 5000 1140.9 1200
1
NEMA Type 2 drip-proof enclosure. Weathershields available to upgrade the enclosures to NEMA Type 3R (suitable for outdoor
use). Standard transformers up through 75 kVA three-phase and 75 kVA single-phase can be mounted directly on wall via
mounting brackets.

7
04/2007 19992007 Schneider Electric All Rights Reserved
Energy Efficient Transformers
240/120 Four-Wire Delta Connection Transformers

240/120 Four-Wire Delta Connection Transformers

Applications

240 Delta transformers with 120 center taps (CTs) have historically been limited to 510% capacity. This
limit normally meets new installation requirements since the center tap is used for deriving a ground
and/or maintenance for 120 loads (small load of lights and outlets around the 240 distribution panel).
However, for retrofit applications where the utility company or customers upgrade their systems from a
240/120 high leg system to a 480Y/277 systemexisting 240/120 panels still need to be fed. In this
case, the 510% 120 capacity does not meet upgrade requirements.
Possible solutions in the past have been to:
Separate the 120 into a single-phase panel and the 240 into a three-phase panel.
Use two single-phase transformers in open Delta.
Have a special three-phase Wye to Delta transformer manufactured.

New Standard Offering

A three-phase Wye to Delta transformer is now a Square D standard product offering from
Schneider Electric.

Product Description:

480 Y Primary, 240 Delta with 120 center tap Secondary, 30 C phase shift between Primary and
Secondary
Sizing of transformer is based on 120 V requirements and 240 V requirements (not limited to 5%)

Use the following formula to size the units.

(2.5 x 120 single-phase loads) + balance 240 three-phase loads = kVA required
Example: 80 A of 120 V and 120 A of 240 balanced loads
80 x 120 = 9600 VA
120 x 240 x 1.73 = 49,824 VA
(2.5 x 9600) + 49,824 = 73,824 VA = 73.8 kVA
Use next standard size: 75 kVA
Table 10: 480 V to 240 Delta with 120 Center Tap (CT)

Primary Secondary
Wiring Diagram
pages 1627)

Current Current
Enclosure1
(Refer to

Weight
Part C
Nameplate

Nameplate

kVA (lbs) NEC NEC NEC


Number Rise Max Max Max
Al
Rating Rating Rating
125% 250% 125%
15 EE15T151HCT 17D 220 150 18.0 25 45 36.1 50
30 EE30T151HCT 17D 260 150 36.1 45 90 72.2 100
45 EE45T151HCT 18D 320 150 54.2 70 125 108.3 150
75 EE75T151HCT 20D 410 150 90.3 125 225 180.4 250
112.5 EE112T151HCT 21D Figure 5 620 150 135.5 175 300 270.6 350
on
150 EE150T151HCT 22D page 31 800 150 180.6 225 450 360.8 500
225 EE225T151HCT 24D 1110 150 271.0 300 600 541.3 700
300 EE300T151HCT 25D 1359 150 361.3 450 900 721.7 1000
500 EE500T151HCT 30D 1870 150 602.1 800 1500 1202.8 1600
750 EE750T151HCT 31D 3060 150 903.2 1000 2000 1804.2 2500
1
NEMA Type 2 drip-proof enclosure. Weathershields available to upgrade the enclosures to NEMA Type 3R (suitable for outdoor
use). Standard transformers up through 75 kVA three-phase and 75 kVA single-phase can be mounted directly on wall via
mounting brackets.
8
19992007 Schneider Electric All Rights Reserved 04/2007
Energy Efficient Transformers
240/120 Four-Wire Delta Connection Transformers

Table 11: Standard Matrix: LoadingSizing: 5, 10, and 15 Percent

5% 120 LoadingSizing 10% 120 LoadingSizing 15% 120 LoadingSizing

120 Balance 120 Balance 120 Balance


kVA kVA kVA
Loads 240 Loads Loads 240 Loads Loads 240 Loads
15 0.75 13.13 15 1.50 11.25 15 2.25 9.38
30 1.50 26.25 30 3.00 22.50 30 4.50 18.75
45 2.25 39.38 45 4.50 33.75 45 6.75 28.13
75 3.75 65.63 75 7.50 56.25 75 11.25 46.88
112.5 5.63 98.44 112.5 11.25 84.38 112.5 16.88 70.31
150 7.50 131.25 150 15.00 112.50 150 22.50 93.75
225 11.25 196.88 225 22.50 168.75 225 33.75 140.63
300 15.00 262.50 300 30.00 225.00 300 45.00 187.50
500 25.00 437.50 500 50.00 375.00 500 75.00 312.50
750 37.50 656.25 750 75.00 562.50 750 112.50 468.75

Table 12: Standard Matrix: LoadingSizing: 20, 25, and 30 Percent

20% 120 Loading - Sizing 25% 120 Loading - Sizing 30% 120 Loading - Sizing

120 Balance 120 Balance 120 Balance


kVA kVA kVA
Loads 240 Loads Loads 240 Loads Loads 240 Loads
15 3.00 7.50 15 3.75 5.63 15 4.50 3.75
30 6.00 15.00 30 7.50 11.25 30 9.00 7.50
45 9.00 22.50 45 11.25 16.88 45 13.50 11.25
75 15.00 37.50 75 18.75 28.13 75 22.50 18.75
112.5 22.50 56.25 112.5 28.13 42.19 112.5 33.75 28.13
150 30.00 75.00 150 37.50 56.25 150 45.00 37.50
225 45.00 112.50 225 56.25 84.38 225 67.50 56.25
300 60.00 150.00 300 75.00 112.50 300 90.00 75.00
500 100.00 250.00 500 125.00 187.50 500 150.00 125.00
750 150.00 375.00 750 187.50 281.25 750 225.00 187.50

Using the Matrix Tables

(1) Determine 240 V balance three-phase load.


(240 x amps x 1.73)/1000 = kVA
Go to the next standard size (used in step (3))
(2) Determine 120 V single-phase load.
(120 x amps)/1000 = kVA
(3) Divide the answer from (2) by the standard kVA from (1) to obtain % 120 loading.
(4) Check the table above and below % of 120 loading. Verify the three-phase kVA will be met with standard kVA.
Using Table
(1) Size three-phase load: 49.9 kVA: Next higher size 75 kVA
(2) Size single-phase load: 9.6 kVA
(3) 9.6/75 = 12.8%
Check the 10% and 15% for three-phase capacity on 75 kVA:
10% >> 56.25 kVA for 240 balance three phase
15% >> 46.88 kVA for 240 balance three phase
75 kVA will work for the application using the tables.

9
04/2007 19992007 Schneider Electric All Rights Reserved
Energy Efficient Transformers
Single-Phase Transformers

Single-Phase Transformers

Refer to Tables 13 and 14 for single-phase transformer information.

Table 13: 240 x 480 V Primary to 120/240 V Secondary

Primary Primary Secondary


Weight Current Current Current
Wiring Diagram
pages 1623)

(lbs)
Enclosure1

240 Vac or
(Refer to

480 Vac 240 Vac 120 Vac


Part C 120/240 Vac
kVA
Number Rise

Nameplate

Nameplate

Nameplate

Nameplate
Cu NEC NEC NEC NEC NEC NEC
(Add Max Max Max Max Max Max
Al
CU Rating Rating Rating Rating Rating Rating
suffix)2 125% 250% 125% 250% 125% 125%
15 EE15S3H 17D 215 300 150 31.3 40 70 62.5 80 150 62.5 80 125.0 175
25 EE25S3H 17H 285 380 150 52.1 70 125 104.2 150 250 104.2 150 208.3 275
37.5 EE37S3H 18H 340 380 150 78.1 100 175 156.3 200 350 156.3 200 312.5 400
50 EE50S3H 18H Figure 8 395 460 150 104.2 150 250 208.3 275 500 208.3 275 416.7 500
on
75 EE75S3H 21D page 32 619 650 150 156.3 200 350 312.5 400 700 312.5 400 625.0 800
100 EE100S3H 22D 682 825 150 208.3 275 500 416.7 500 1000 416.7 500 833.3 1000
167 EE167S3H 24D 982 1190 150 347.9 450 800 695.8 800 1600 695.8 800 1391.7 1600
2503 EE250S3H 150 520.8 700 1200 1041.7 1200 2500 1041.7 1200 2083.3 2500
3334 150 693.8 800 1600 1387.5 1600 3000 1387.5 1600 2775.0 3000
1
NEMA Type 2 drip-proof enclosure. Weathershields available to upgrade the enclosures to NEMA Type 3R (suitable for outdoor use).
Standard transformers up through 75 kVA three-phase and 75 kVA single-phase can be mounted directly on wall via mounting brackets.
2
Example of copper part number: EE50S3HCU
3
Contact your local Schneider Electric representative to obtain information about the 250 kVa single-phase offering (enclosure and weights).
4 Contact your local Schneider Electric representative to obtain information about the 333 kVA single-phase offering
(part number, enclosure, wiring diagram, and weights).

Table 14: 600 V Primary to 120/240 V Secondary

Secondary
Weight Primary Current
Wiring Diagram
pages 1623)

(lbs) Current
1

240 Vac or
Enclosure
(Refer to

120 Vac
Part C 120/240 Vac
kVA
Number Rise
Nameplate

Nameplate

Nameplate

Cu NEC NEC NEC NEC


(Add Max Max Max Max
Al
CU Rating Rating Rating Rating
suffix)2 125% 250% 125% 125%
15 EE15S3534H 17D 215 300 150 25.0 35 60 62.5 80 125.0 175
25 EE25S3534H 17H 285 380 150 41.7 60 100 104.2 150 208.3 275
37.5 EE37S3534H 18H 340 380 150 62.5 80 150 156.3 200 312.5 400
Figure 9
50 EE50S3534H 18H on 395 460 150 83.3 110 200 208.3 275 416.7 500
page 32
75 EE75S3534H 21D 619 650 150 125.0 175 300 312.5 400 625.0 800
100 EE100S3534H 22D 682 825 150 166.7 225 400 416.7 500 833.3 1000
167 EE167S3534H 24D 982 1190 150 278.3 350 600 695.8 800 1391.7 1600
2503 EE250S3534H 150 416.7 500 1000 1041.7 1200 2083.3 2500
3334 150 555.0 700 1200 1387.5 1600 2775.0 3000
1
NEMA Type 2 drip-proof enclosure. Weathershields available to upgrade the enclosures to NEMA Type 3R (suitable for outdoor use).
Standard transformers up through 75 kVA three-phase and 75 kVA single-phase can be mounted directly on wall via mounting brackets.
2 Example of copper part number: EE50S3534HCU
3
Contact your local Schneider Electric representative to obtain information about the 250 kVa single-phase offering (enclosure and weights).
4
Contact your local Schneider Electric representative to obtain information about the 333 kVA single-phase offering
(part number, enclosure, wiring diagram, and weights).

10
19992007 Schneider Electric All Rights Reserved 04/2007
Energy Efficient Transformers
Non-Linear Energy Efficient Transformers

Non-Linear Energy Efficient Transformers

Type NL and NLP are dry-type transformers intended to supply power to applications such as computers, copiers, printers,
FAX machines, video display terminals, and other equipment having switched-mode power supplies. The standard type NL
model and the premium type NLP model are built to handle high current distortion harmonics associated with such loads. The
NLP transformer is designed particularly for more severe non-linear load applications.

General Features

Three-phase dry-type transformers, 480 Delta208Y/120


Aluminum or copper windings
Electrostatic shield
Class 220 insulation
Double size neutral terminal for additional customer neutral cables
Additional coil capacity to compensate for higher non-linear load loss
cULus Listed

Table 15: 480 V Delta Primary to 208Y/120 SecondaryK-4 RatedAluminum Windings; 115 C Rise
Wiring Diagram

Weight (lbs) Primary Current Secondary Current


pages 1627)
Enclosure
(Refer to

Part

Nameplate

Nameplate
C NEC NEC NEC
kVA Number Cu
Rise Max Max Max
(Al) Al (Add CU
Rating Rating Rating
before NL)1
125% 250% 125%
15 EE15T3HFISNL 17D 256 260 115 18.0 25 45 41.7 60
30 EE30T3HFISNL 18D 320 430 115 36.1 45 90 83.4 110
45 EE45T3HFISNL 20D 600 730 115 54.2 70 125 125.1 175
Figure 1
75 EE75T3HFISNL 21D on 535 490 115 90.3 125 225 208.4 275
page 28
112.5 EE112T3HFISNL 22D 800 900 115 135.5 175 300 312.6 400
150 EE150T3HFISNL 24D 1110 1120 115 180.6 225 450 416.9 500
225 EE225T3HFISNL 25D 1349 1477 115 271.0 300 600 625.3 800
300 EE300T68HFISNL 30D Figure 2 1880 1880 115 361.3 450 900 833.7 1000
on
500 EE500T68HFISNL 31D page 29 2295 2625 115 602.1 800 1500 1389.5 1600
1
Example of copper part number: EE75T3HFISCUNL

Table 16: 480 V Delta Primary to 208Y/120 SecondaryK-13 RatedAluminum Windings;115 C Rise
Wiring Diagram

Weight (lbs) Primary Current Secondary Current


pages 1627)
Enclosure
(Refer to

Part
Nameplate

Nameplate

C NEC NEC NEC


kVA Number Cu
Rise Max Max Max
(Al) Al (Add CU
Rating Rating Rating
before NL)1
125% 250% 125%
15 EE15T3HFISNLP 17D 256 260 115 18.0 25 45 41.7 60
30 EE30T3HFISNLP 18D 375 430 115 36.1 45 90 83.4 110
45 EE45T3HFISNLP 20D 500 730 115 54.2 70 125 125.1 175
Figure 1
75 EE75T3HFISNLP 21D on 560 640 115 90.3 125 225 208.4 275
page 28
112.5 EE112T3HFISNLP 22D 800 985 115 135.5 175 300 312.6 400
150 EE150T3HFISNLP 24D 1110 1135 115 180.6 225 450 416.9 500
225 EE225T3HFISNLP 25D 1335 1477 115 271.0 300 600 625.3 800
300 EE300T68HFISNLP 30D Figure 2 1898 1895 115 361.3 450 900 833.7 1000
on
500 EE500T68HFISNLP 31D page 29 3200 2625 115 602.1 800 1500 1389.5 1600
1
Example of copper part number: EE75T3HFISCUNLP

11
04/2007 19992007 Schneider Electric All Rights Reserved
Energy Efficient Transformers
Watchdog Low Temperature Rise Transformers

Watchdog Low Temperature Rise Transformers

Watchdog transformers are designed to maximize energy efficiency and supplies the highest efficient levels for 24-hour loading
greater than 50 percent. Their extra long life expectancy using a 220 C insulation system is designed for full load operation at a
maximum temperature rise of 115 C or 80 C instead of 150 C. Continuous emergency overload capability is used for
15 percent on 115 C rise and 30 percent on 80 C rise. These transformers meet the efficiency standards in The Guide for
Determining Energy Efficiency for Distribution Transformers, published by the NEMA (NEMA TP12002).

Three-Phase

Table 17: 115 C Rise 480 V Delta Primary to 208Y/120 Secondary

Weight Primary Secondary


Wiring Diagram
pages 1627)

(lbs) Current Current


Enclosure1
(Refer to

Part
C

Nameplate

Nameplate
kVA Number Cu NEC NEC NEC
(Add Rise Max Max Max
(Al) Al
CU Rating Rating Rating
Suffix)2 125% 250% 125%
15 EE15T3HF 17D 260 340 115 18.0 25 45 41.7 60
30 EE30T3HF 18D 320 372 115 36.1 45 90 83.4 110
45 EE45T3HF 20D 410 527 115 54.2 70 125 125.1 175
Figure 1
75 EE75T3HF 21D on 620 725 115 90.3 125 225 208.4 275
page 28
112.5 EE112T3HF 22D 800 920 115 135.5 175 300 312.6 400
150 EE150T3HF 24D 1110 1090 115 180.6 225 450 416.9 500
225 EE225T3HF 25D 1359 1535 115 271.0 300 600 625.3 800
300 EE300T68HF 30D Figure 2 1870 2300 115 361.3 450 900 833.7 1000
on
500 EE500T68HF 31D page 29 3060 3710 115 602.1 800 1500 1389.5 1600
1
NEMA Type 2 drip-proof enclosure. Weathershields available to upgrade the enclosures to NEMA Type 3R (suitable for outdoor
use). Standard transformers up through 45 kVA three-phase and 45 kVA single-phase can be mounted directly on wall via
mounting brackets.
2
Example of copper part number: EE75T3HFCU

Table 18: 80 C Rise 480 V Delta Primary to 208Y/120 Secondary

Weight Primary Secondary


Wiring Diagram
pages 1627)

(lbs) Current Current


Enclosure1
(Refer to

Part
C
Nameplate

Nameplate

kVA Number Cu NEC NEC NEC


(Al) (Add Rise Max Max Max
Al
CU Rating Rating Rating
Suffix)2 125% 250% 125%
15 EE15T3HB 17D 260 340 80 18.0 25 45 41.7 60
30 EE30T3HB 18D 320 372 80 36.1 45 90 83.4 110
45 EE45T3HB 20D 410 527 80 54.2 70 125 125.1 175
Figure 1
75 EE75T3HB 21D on 620 725 80 90.3 125 225 208.4 275
page 28
112.5 EE112T3HB 22D 800 920 80 135.5 175 300 312.6 400
150 EE150T3HB 24D 1110 1090 80 180.6 225 450 416.9 500
225 EE225T3HB 25D 1359 1535 80 271.0 300 600 625.3 800
300 EE300T68HB 30D Figure 2 1870 2300 80 361.3 450 900 833.7 1000
on
500 EE500T68HB 31D page 29 3060 3710 80 602.1 800 1500 1389.5 1600
1 NEMA Type 2 drip-proof enclosure. Weathershields available to upgrade the enclosures to NEMA Type 3R (suitable for outdoor
use). Standard transformers up through 45 kVA three-phase and 45 kVA single-phase can be mounted directly on wall via
mounting brackets.
2 Example of copper part number: EE75T3HBCU

12
19992007 Schneider Electric All Rights Reserved 04/2007
Energy Efficient Transformers

Watchdog Low Temperature Rise Transformers

Single-Phase Transformers

Table 19: 115 C Rise 240 x 480 V Primary to 120/240 V Secondary

Primary Current Primary Current Secondary Current

Wiring Diagram
pages 1723)
Enclosure1
Cu 240 V 480 V 120 V 240 V
(Refer to
Part Weight
(Add C
kVA Number (lbs)

Nameplate

Nameplate

Nameplate

Nameplate
CU Rise NEC NEC NEC NEC NEC NEC
(Al) Al Max Max Max Max Max Max
Suffix)2
Rating Rating Rating Rating Rating Rating
125% 250% 125% 250% 125% 125%
15 EE15S3HF 17H 275 375 115 31.3 40 70 62.5 80 150 62.5 80 125.0 175
25 EE25S3HF 18H 340 395 115 52.1 70 125 104.2 150 250 104.2 150 208.3 275
37.5 EE37S3HF 18H 420 465 115 78.1 100 175 156.3 200 350 156.3 200 312.5 400
Figure 8
50 EE50S3HF 21D on 620 660 115 104.2 150 250 208.3 275 500 208.3 275 416.7 500
page 32
75 EE75S3HF 22D 795 890 115 156.3 200 350 312.5 400 700 312.5 400 625.0 800
100 EE100S3HF 24D 945 1075 115 208.3 275 500 416.7 500 1000 416.7 500 833.3 1000
167 EE167S3HF 25D 1120 115 347.9 450 800 695.8 800 1600 695.8 800 1391.7 1600
1 NEMA Type 2 drip-proof enclosure. Weathershields available to upgrade the enclosures to NEMA Type 3R (suitable for outdoor use). Standard transformers up
through 45 kVA three-phase and 45 kVA single-phase can be mounted directly on wall via mounting brackets.
2
Example of copper part number: EE50S3HFCU

Table 20: 80 C Rise 240 x 480 V Primary to 120/240 V Secondary

Primary Current Primary Current Secondary Current


Wiring Diagram
pages 1723)
Enclosure1

Cu 240 V 480 V 120 V 240 V


(Refer to

Part Weight
(Add C
kVA Number (lbs)
Nameplate

Nameplate

Nameplate

Nameplate
CU Rise NEC NEC NEC NEC NEC NEC
(Al) Al Max Max Max Max Max Max
Suffix)2
Rating Rating Rating Rating Rating Rating
125% 250% 125% 250% 125% 125%
15 EE15S3HB 17H 275 375 80 31.3 40 70 62.5 80 150 62.5 80 125.0 175
25 EE25S3HB 18H 340 395 80 52.1 70 125 104.2 150 250 104.2 150 208.3 275
37.5 EE37S3HB 18H 420 465 80 78.1 100 175 156.3 200 350 156.3 200 312.5 400
Figure 8
50 EE50S3HB 21D on 620 660 80 104.2 150 250 208.3 275 500 208.3 275 416.7 500
page 32
75 EE75S3HB 22D 795 890 80 156.3 200 350 312.5 400 700 312.5 400 625.0 800
100 EE100S3HB 24D 985 1075 80 208.3 275 500 416.7 500 1000 416.7 500 833.3 1000
167 EE167S3HB 25D 1120 80 347.9 450 800 695.8 800 1600 695.8 800 1391.7 1600
1
NEMA Type 2 drip-proof enclosure. Weathershields available to upgrade the enclosures to NEMA Type 3R (suitable for outdoor use). Standard transformers up
through 45 kVA three-phase and 45 kVA single-phase can be mounted directly on wall via mounting brackets.
2 Example of copper part number: EE50S3HBCU

13
04/2007 19992007 Schneider Electric All Rights Reserved
Energy Efficient Transformers
Made-To-Order Transformers

Made-To-Order Transformers

Schneider Electric manufactures made-to-order energy efficient transformers to meet the specific
needs of particular applications and are designed for 60 hertz systems. The Square D Transformer
Product Selector allows the customer to derive part numbers for these applications.
Options that are supported via the Product Selector include:
Winding material:
Standard aluminum
Optional copper
Enclosure:
NEMA Type 2
NEMA Type 3R with field installed accessories
Open no enclosure: IP00
Material:
Standard painted cold rolled steel
Optional painted 316 stainless steel
Sound level (NEMA ST-20)

kVA Standard dB 3 dB Below 6 dB Below


1050 45 42 39
51150 50 47 44
151300 55 52 49
301500 60 57 54
501700 62 59 56
7011000 64 61 58

Temperature rise: 220 C insulation


Standard 150 C rise
Optional 115 C rise or 80 C rise
Electrostatic shielding available on all unitsinstalled between primary and secondary windings

14
19992007 Schneider Electric All Rights Reserved 04/2007
Energy Efficient Transformers
Made-To-Order Transformers

Special Three-Phase Voltage Combinations

Refer to Table 21 for available special three-phase voltage combinations. The primary voltages are
Delta configurations because they can be used on both three-wire and four-wire (Wye) systems.

Table 21: Three-Phase Voltage Combinations: Made-to-Order Transformers

Secondary Primary Voltage


Voltage 600 Delta 480 Delta 440 Delta 240 Delta 208 Delta
208Y/120
Primary: United States Primary: Mexico
240 Delta Primary: North America Primary: United States Primary: United States
and Canada Secondary:
Secondary: North Secondary: North Secondary: North
480Y/277 Secondary: North North American
American Distribution American Distribution American Distribution
American Distribution Distribution
480 Delta
600 Delta Primary: United States Primary: Mexico
Primary: North America Primary: United States Primary: United States
and Canada Secondary:
Secondary: Canadian Secondary: Canadian Secondary:Canadian
600Y/346 Secondary: Canadian Canadian
Distribution Distribution Distribution
Distribution Distribution
Primary: United States Primary: Mexico
Primary: North America Primary: United States Primary: United States
and Canada Secondary:
220Y/127 Secondary: Mexican Secondary: Mexican Secondary: Mexican
Secondary: Mexican Mexican
Distribution Distribution Distribution
Distribution Distribution
415Y/240
Primary: United States Primary: Mexico
416Y/240 Primary: North America Primary: United States Primary: United States
and Canada Secondary:
Secondary: Overseas Secondary: Overseas Secondary: Overseas
400Y/230 Secondary: Overseas Overseas
Equipment Equipment Equipment
Equipment Equipment
380Y/220

Special Single-Phase Voltage Combinations


Refer to Table 22 for available special single-phase voltage combinations.

Table 22: Single-Phase Voltage Combinations: Made-to-Order Transformers

Secondary Primary Voltage


Voltage 600 480 240 120 208 277 240 X 480 120 X 240
Primary: United States and Canada Primary: United States
120/240 Secondary: 3-Wire Output, 120 Line-to-Neutral, 240 Secondary: 3-Wire Output, 120 Line-to-Neutral,
Line-to-Line, or 240 Line-to-Neutral 240 Line-to-Line, or 240 Line-to-Neutral
Primary: United States & Canada Primary: United States
208
Secondary: Line to Line 208 (No 120) Secondary: Line-to-Line 208 (No 120)
Primary: United States and Canada Primary: United States
277
Secondary: Line-to-Neutral Secondary: Line-to-Neutral
Primary: United States and Canada Primary: United States
480
Secondary: Line-to-Line 480 Secondary: Line-to-Line 480
Primary: United States and Canada Primary: United States
600
Secondary: Line-to-Line 600 Secondary: Line-to-Line 600
Primary: United States and Canada Primary: United States and Canada
200/400 Secondary: 200 Line-to-Line or 400 Line-to-Line Secondary: 200 Line-to-Line or 400 Line-to-Line
(Overseas Equipment) (Overseas Equipment)
220
230
Primary: United States and Canada Primary: United States & Canada
415
Secondary: Overseas Equipment Line-to-Line Voltages Secondary: Overseas Equipment Line-to-Line Voltages
416
380

Other voltages are available:


575 V: It is suggested to use 600 V as the system voltage.
460 V: It is suggested to use 480 V as the system voltage.
Export primary voltages include:
416 V, 415 V, 400 V, 380 V, and 200 V.
15
04/2007 19992007 Schneider Electric All Rights Reserved
Energy Efficient Transformers
Enclosure Diagrams and Accessories

Enclosure Diagrams and Accessories

Enclosure Parts and Accessories

Refer to pages 1627 for enclosure type and accessory information.

Weathershield

Places

Wall mounting brackets

Accessories
Ceiling
mounting Weathershield WS363
brackets
Wall mounting bracket WMB361-362
Ceiling mounting bracket CMB363

Enclosure Parts
Top cover 4310191501
in. Slot
Places Places Front1 4310191601
Rear 4310191601
Sides (ends) 4310191701
Base 4310191401
1
When replacing a front panel, specify the
transformer part number and with nameplate
and labels on the order.

Enclosure 17DDry-Type Transformer


16
19992007 Schneider Electric All Rights Reserved 04/2007
Energy Efficient Transformers
Enclosure Diagrams and Accessories

Weathershield

Places

Wall mounting brackets

Ceiling
mounting
brackets

Accessories
Weathershield WS363
Wall mounting bracket WMB361-362
in. Slot
Places Places Ceiling mounting bracket CMB363

Enclosure Parts
Top cover 4310191501
Front1 4305502003
Rear 4305502003
Sides (ends) 4310191702
Base 4310191401
1
When replacing a front panel, specify the
transformer part number and with nameplate
and labels on the order.

Enclosure 17HDry-Type Transformer

17
04/2007 19992007 Schneider Electric All Rights Reserved
Energy Efficient Transformers
Enclosure Diagrams and Accessories

Weathershield

Places

Wall mounting brackets

Ceiling
mounting
brackets

Accessories
Weathershield WS363
Wall mounting bracket WMB363-364
Ceiling mounting bracket CMB363
in. Slot
Places Places
Enclosure Parts
Top cover 4305502101
Front1 4305502001
Rear 4305502001
Sides (ends) 4305501001
Base 4305501801
1
When replacing a front panel, specify the
transformer part number and with nameplate
and labels on the order.

Enclosure 18DDry-Type Transformer

18
19992007 Schneider Electric All Rights Reserved 04/2007
Energy Efficient Transformers
Enclosure Diagrams and Accessories

Weathershield

Places

Wall mounting brackets

Ceiling
mounting
brackets

Accessories
Weathershield WS363
Wall mounting bracket WMB363-364
Ceiling mounting bracket CMB363
in. Slot
Places Places Enclosure Parts
Top cover 4305502101
Front1 4305502003
Rear 4305502003
Sides (ends) 4310179701
Base 4305501801
1
When replacing a front panel, specify the
transformer part number and with nameplate
and labels on the order.

Enclosure 18HDry-Type Transformer

19
04/2007 19992007 Schneider Electric All Rights Reserved
Energy Efficient Transformers
Enclosure Diagrams and Accessories

Weathershield

Places

Wall mounting brackets

Ceiling
mounting
brackets

in. Slot Places


Places
Accessories
Weathershield WS364
Wall mounting bracket WMB363-364
Ceiling mounting bracket CMB364

Enclosure Parts
Top cover 4305501201
Front1 4305501101
Rear 4305501101
Sides (ends) 4305501001
Base 4305500901
1
When replacing a front panel, specify the
transformer part number and with nameplate
and labels on the order.

Enclosure 19DDry-Type Transformer


20
19992007 Schneider Electric All Rights Reserved 04/2007
Energy Efficient Transformers
Enclosure Diagrams and Accessories

Weathershield

Places

Wall mounting brackets

Ceiling
mounting
brackets

Accessories
Weathershield WS364
Places
in. Slot Wall mounting bracket WMB363-364
Places
Ceiling mounting bracket CMB364

Enclosure Parts
Top cover 4305501201
Front1 4310192201
Rear 4310192201
Sides (ends) 4310179701
Base 4305500901
1
When replacing a front panel, specify the
transformer part number and with nameplate
and labels on the order.

Enclosure 20DDry-Type Transformer


21
04/2007 19992007 Schneider Electric All Rights Reserved
Energy Efficient Transformers
Enclosure Diagrams and Accessories

Weathershield

Ceiling
mounting
brackets

Accessories
Weathershield WS364
in. Slot
Places Ceiling mounting bracket CMB364
Places
Enclosure Parts
Top cover 4305512501
Front1 4300507404
Rear 4300507404
Sides (ends) 4305512601
Base 4305512450
1
When replacing a front panel, specify the
transformer part number and with nameplate
and labels on the order.

Enclosure 21DDry-Type Transformer

22
19992007 Schneider Electric All Rights Reserved 04/2007
Energy Efficient Transformers
Enclosure Diagrams and Accessories

Weathershield

Ceiling
mounting
brackets

Accessories
Weathershield WS380
Ceiling mounting bracket CMB380

Enclosure Parts
Top cover 4310189001
Places
Places Front1 4310189102
Rear 4310189102
Sides (ends) 4310189201
Base 4310189550
1
When replacing a front panel, specify the
transformer part number and with nameplate
and labels on the order.

Enclosure 22DDry-Type Transformer

23
04/2007 19992007 Schneider Electric All Rights Reserved
Energy Efficient Transformers
Enclosure Diagrams and Accessories

Weathershield

Ceiling
mounting
brackets

Accessories
Weathershield WS381
Ceiling mounting bracket CMB381

Places Enclosure Parts


Places
Top cover 4310190701
Front1 4310190802
Rear 4310190802
Sides (ends) 4310190901
Base 4310191250
1
When replacing a front panel, specify the
transformer part number and with nameplate
and labels on the order.

Enclosure 24DDry-Type Transformer

24
19992007 Schneider Electric All Rights Reserved 04/2007
Energy Efficient Transformers
Enclosure Diagrams and Accessories

Weathershield

Accessories
Weathershield WS382

Enclosure Parts
Top cover 4310189901
Front1 4310190001
Rear 4310190001
Sides (ends) 4310190101
Base 4310190450
1 When replacing a front panel, specify the
transformer part number and with nameplate
and labels on the order.
Places

Enclosure 25DDry-Type Transformer

25
04/2007 19992007 Schneider Electric All Rights Reserved
Energy Efficient Transformers
Enclosure Diagrams and Accessories

Weathershield

Accessories
Weathershield WS383

Enclosure Parts
Top cover 4310192601
Front upper1 4310192901
Front lower 4310193001
Rear upper 4310192901
Rear lower 4310193001
Sides (ends) 4310192801
Base 4310193450
1
When replacing a front upper panel, specify the
transformer part number and with nameplate
Places and labels on the order.

Enclosure 30DDry-Type Transformer

26
19992007 Schneider Electric All Rights Reserved 04/2007
Energy Efficient Transformers
Enclosure Diagrams and Accessories

Weathershield

Accessories
Weathershield WS384

Enclosure Parts
Top cover 4313505501
Front upper1 4313505701
Front lower 4313505801
Rear upper 4313505701
Rear lower 4313505801
Sides (ends) 4313505601
Places
Base 4313506250
1 When replacing a front upper panel, specify the
transformer part number and with nameplate
and labels on the order.

Enclosure 31DDry-Type Transformer

27
04/2007 19992007 Schneider Electric All Rights Reserved
Energy Efficient Transformers
Wiring Diagrams

Wiring Diagrams
Refer to Figures 19 for wiring diagram information.

Figure 1: Voltage Codes 3, 65, 67, 1814, and 1755


Voltage Code 3
Primary 22.5% FCAN
Secondary Voltage
Voltage 42.5% FCBN Tap
504 1
492 2
480 3
468 4 208Y/120
456 5
444 6
432 7
Voltage Code 65
Primary 22.5% FCAN
Secondary Voltage
Voltage 42.5% FCBN Tap
630 1
615 2
600 3
585 4 208Y/120
570 5
H2 X2 555 6
540 7
X1 X0 Voltage Code 67
Primary 22.5% FCAN
H3 Secondary Voltage
H1 X3 Voltage 42.5% FCBN Tap
252 1
H1 H2 H3 246 2
240 3
234 4 208Y/120
7654321 7654321 7654321 228 5
222 6
216 7
Voltage Code 1814
Primary 22.5% FCAN
Secondary Voltage
X3 Voltage 42.5% FCBN Tap
X0 X1 X2
504 1
492 2
480 3
468 4 480Y/277
456 5
444 6
432 7
Voltage Code 1755
Primary 22.5% FCAN
Secondary Voltage
Voltage 42.5% FCBN Tap
504 1
492 2
480 3
468 4 380Y/220
456 5
444 6
432 7

28
19992007 Schneider Electric All Rights Reserved 04/2007
Energy Efficient Transformers
Wiring Diagrams

Figure 2: Voltage Codes 68, 79, 239, 76, and 96


Voltage Code 68
Primary 22.5% FCAN
Secondary Voltage
Voltage 22.5% FCBN Tap
504 1
492 2
480 3 208Y/120
468 4
456 5
Voltage Code 79
Primary 22.5% FCAN
Secondary Voltage
Voltage 22.5% FCBN Tap
H2 X2
630 1

X1 X0 615 2
600 3 208Y/120

X3 585 4
H1 H3
X2 570 5
Voltage Code 239
H1 H2 H3 Primary 22.5% FCAN
Secondary Voltage
Voltage 22.5% FCBN Tap
252 1
54321 54321 54321 246 2
240 3 208Y/120
234 4
228 5
Voltage Code 76

X0 X1 X2 X3 Primary 22.5% FCAN


Secondary Voltage
Voltage 22.5% FCBN Tap
504 1
492 2
480 3 480Y/277
468 4
456 5
Voltage Code 96
Primary 22.5% FCAN
Secondary Voltage
Voltage 22.5% FCBN Tap
504 1
492 2
480 3 380Y/220
468 4
456 5

29
04/2007 19992007 Schneider Electric All Rights Reserved
Energy Efficient Transformers
Wiring Diagrams

Figure 3: Voltage Code 6


Voltage Code 6
Primary 22.5% FCAN
Secondary Voltage
Voltage 42.5% FCBN
504 1
492 2
480 3
468 4 240 Delta
456 5
444 6
432 7

Figure 4: Voltage Code 63


Voltage Code 63
Primary 22.5% FCAN
Secondary Voltage
Voltage 42.5% FCBN
504 1
492 2
480 3 240 Delta
468 4
456 5

30
19992007 Schneider Electric All Rights Reserved 04/2007
Energy Efficient Transformers
Wiring Diagrams

Figure 5: Voltage Code 151


Voltage Code 151
120 V center tap on one phase only. Primary 15% FCAN
Secondary Voltage
kVA = > 2.5 x 1 phase kVA plus 3 phase kVA. Voltage 15% FCBN Tap
480 1
456 2 240 Delta
432 3

Figure 6: Voltage Code 212


Voltage Code 212
Primary 15% FCAN
Secondary Voltage
Voltage 25% FCBN Tap
218 1
208 2
480Y/277
198 3
188 4

Figure 7: Voltage Codes 211 and 239


Voltage Code 211
Primary 15% FCAN
Secondary Voltage
Voltage 25% FCBN Tap
218 1
208 2
208Y/120
198 3
188 4
Voltage Code 239
Primary 15% FCAN
Secondary Voltage
Voltage 25% FCBN Tap
252 1
240 2
208Y/120
228 3
216 4

31
04/2007 19992007 Schneider Electric All Rights Reserved
Energy Efficient Transformers
Wiring Diagrams

Figure 8: Voltage Code 3


480 V Connection
Connect H2 to H3
Connect Lines to H1 and H4
H1 H4
H3 H2 22.5% FCAN
42.5% FCBN Tap
1 2 3 4 5 6 7 8 Primary Voltage Connect to Taps
504 1 and 8
492 1 and 7
480 2 and 7
X1 X3 X2 X4 468 2 and 6
456 3 and 6
SERIES CONNECTION
444 3 and 5
H1 H4
H3 H2 432 4 and 5
240 V Connection
1 2 3 4 5 6 7 8 Connect H1 to H3 and H2 to H4
Connect Lines to H1 and H4
15% FCAN
25% FCBN Tap
Primary Voltage Connect to Taps
X1 X3 X2 X4 252 1 and 8
PARALLEL CONNECTION 240 2 and 7
228 3 and 6
216 4 and 5

Figure 9: Voltage Code 3534


600 V Connection
H1 H2 Connect Lines to H1 and H2
22.5% FCAN
42.5% FCBN Tap
1 2 3 4 5 6 7 8
Primary Voltage Connect to Taps
630 1 and 8
615 1 and 7
600 2 and 7
X1 X3 X2 X4
585 2 and 6
SERIES CONNECTION 570 3 and 6

H1 H2 555 3 and 5
540 4 and 5

1 2 3 4 5 6 7 8

X1 X3 X2 X4

PARALLEL CONNECTION

32
19992007 Schneider Electric All Rights Reserved 04/2007
Energy Efficient Transformers
NEC Reference: Installing and Connecting Transformers

NEC Reference: Installing and (C) Other Space Used for Environmental Air

Connecting Transformers (2) Electric equipment with a metal enclosure, or with a nonmetallic
enclosure listed for the use and having adequate fire-resistant and
low smoke-producing characteristics, and associated wiring material
450.9 Ventilation suitable for the ambient temperature shall be permitted to be installed in
such other space unless prohibited elsewhere in this code. (450.13 above
Ventilation should be adequate to dispose of the limits the kVA capacity for other space.)
transformer full load losses without creating a FPN: The space over a hung ceiling used for environmental air-handling is
temperature rise that is in excess of the an example of the type of other space to which this section applies.
transformer rating.
Transformers with ventilated openings shall be 450.21(B) Dry-Type Transformers Installed Indoors
installed so that the ventilated openings are not
blocked by walls or other obstructions. Individual dry-type transformers of more than 112.5 kVA rating shall be
The required clearance shall be marked clearly on installed in a transformer room of fire-resistant construction. Unless
the transformer. specified otherwise in this article, the term fire resistant means a
construction having a minimum fire rating of 1 hour.
Square D Energy Efficient transformers
minimum clearance: three inches (76 mm). Exception 1 to this rule is relative to transformers with insulation Class 155
or higher and separations from combustible materials by space or a
fire-resistant, heat-insulation barrier.
450.13 Accessibility
Exception 2 is relative to transformers with insulation Class 155 or higher
All transformers and transformers vaults shall be and of the completely enclosed type, except for ventilating openings.
readily accessible to qualified personnel for All Square D Energy Efficient transformers are completely enclosed
inspection and maintenance, or meet the (except for ventilated openings) and use Class 220 insulation.
requirements of (A) or (B).

(A) Open Installations 450.12 Terminal Wiring Space

Dry-type transformers 600 volts, nominal, or less, Minimum wire bending space at fixed, 600 V and below terminals of
located in the open on walls, columns, or transformer line and load connections shall be as required by 312.6.
structures, shall not be required to be readily Terminal:
accessible.
A) A conducting element of an equipment or a circuit intended for
NEC 110.26(A)(3) other equipment that is connection to an external conductor
associated with the electrical installation and is
B) A device attached to a conductor to facilitate connection with
located above or below the electrical equipment
another conductor
shall be permitted to extend not more than
6 inches (152 mm). Square D Distance from Terminals to Bottom of the Compartment
NEC 110.26(E) Headroom 6.50 feet (1.8 m) (Does not Include X0)

kVA (Three-Phase: kVA (Single-Phase:


(B) Accessibility 150 C Rise
Inches (mm)
150 C Rise
Inches (mm)

15 8-3/4 (222 mm) 15 8-3/4 (222 mm)


Dry-type transformers 600 volts, nominal, or less
and not exceeding 50 kVA shall be permitted in 30 8-3/4 (222 mm) 25 8-3/4 (222 mm)

hollow spaces of buildings not permanently closed 45 11 (279 mm) 37.5 16-5/16 (414 mm)
in by structure in accordance with the following: 75 15-1/2 (394 mm) 50 16-5/16 (414 mm)
112.5 15-11/16 (398 mm) 75 15-13/16 (402 mm)
Meet the ventilation requirements of
150 18-6/16 (467 mm) 100 18-5/16 (465 mm)
Section 450.9.
225 18-1/2 (470 mm) 167 18-1/16 (459 mm)
Separated from combustible materials as
300 18-6/16 (467 mm)
outline in 450.21(A).
500 19-3/16 (487 mm)
Transformers so installed shall not be required to 750 19 (483 mm)
be readily accessible
Section 300-22 Wiring in Ducts, Plenums, and
Other Air-Handling Space
33
04/2007 19992007 Schneider Electric All Rights Reserved
Energy Efficient Transformers
Wire Range Part Numbers and Lug Kits

Wire Range Part Numbers and Lug Kits


New primary and secondary mechanical lug kits from Schneider Electric can be coordinated with standard wire ranges for
primary Square D circuit breakers, safety switches, and panelboards. Refer to the Tables 2327 for a listing of mechanical lug
kits and wire ranges. Also, refer to catalog no. 7400CT0501 for information regarding lug kit selection and conductor and
mounting hardware torque requirements.

Table 23: Primary Mechanical Lug Kits

Cap Screws Handles Same Standard Wire Range1


Wire Range
Part Number Lugs per Kit Square D Square D Safety Switch
(Aluminum or Copper) Quantity Size
Circuit Breaker Frame Amperage Rating
F-Frame, G-Frame
DASKP100 3 1/014 STR.2 3 1/4 x 1 in 100 A
Powerpact Q 3, Powerpact H
DASKP250 3 350 kcmil6 STR. 3 1/4 x 1 in Powerpact Q 4, Powerpact J 200 A
600 kcmil4 STR.
DASKP400 3 3 1/4 x 1 in Q4-Frame, L-Frame (400 A) 400 A
(2) 250 kcmil1/0 STR.5
600 kcmil4 STR.
DASKP600 6 6 1/4 x 1 in L-Frame (600 A) 600 A
(2) 250 kcmil1/0 STR.5
DASKP1000 9 600 kcmil2 STR. 9 3/8 x 2 in Powerpact M 800 A
DASKP1200 12 600 kcmil2 STR. 12 3/8 x 2 in Powerpact P 1200 A
1 Does not handle the full range of safety switches, but is acceptable since extra capacity is for voltage drop. Normally, this is not an issue because of the National
Electrical Code (NEC) for primary protection distance on transformers.
2
STR. = Strand
3 Handles through 1/0, not 300 kcmil
4
Does not handle 814 STR
5
7400DASKP400 and 7400DASKP600 require two (2) wires per lug

Table 24: Secondary Mechanical Lug Kits

Cap Screws Handles Same Standard Wire Range 1 Bonding Lugs


Lugs Square D Circuit Safety
Wire Range Panelboards: Lugs Wire Range
Part Number per Breaker Frame Switch
(Aluminum or Copper) Qty. Size -Main Lugs Main per (Aluminum or
Kit (Molded Case Amp.
- Circuit Breaker Kit Copper)
Switches) Rating
F-Frame
100 A NQOD
DASKS100 5 1/014 STR.2 6 1/4 x 1 in G-Frame 100 A 1 214 STR.
100 A I-Line
Powerpact Q 3
225 A NQOD
Q-Frame 4
DASKS250 5 350 kcmil6 STR. 6 1/4 x 1 in 250 A NF 200 A 1 214 STR.
Powerpact J
225 A I-Line
400 A NQOD 6
600 kcmil4 STR. Q4-Frame
DASKS400 5 6 1/4 x 1 in 400 A NF 6 400 A 1 1/014 STR.
(2) 250 kcmil1/0 STR.5 L-Frame (400 A)
400 A I-Line
600 A NQOD
(Main Lug Only)
DASKS600 10 600 kcmil2 STR. 11 1/4 x 1 in L-Frame (600 A) 600 A 1 250 kcmil6 STR.
600 A NF 6
600 A I-Line
600 A NQOD
(Main Breaker Only)
DASKS1000 15 600 kcmil2 STR. 16 3/8 x 2 in Powerpact M 800 A 1 250 kcmil6 STR.
800 A NF
800 A I-Line
DASKS1200 20 600 kcmil2 STR. 21 3/8 x 2 in Powerpact P 1200 A I-Line 1200 A 1 250 kcmil6 STR.
DASKS2000 25 600 kcmil2 STR. 26 3/8 x 2 in 1 350 kcmil6 STR.
1
Does not handle the full range of safety switches, but is acceptable since extra capacity is for voltage drop. Normally, this is not an issue because of the NEC for
primary protection distance on transformers.
2
STR. = Strand
3
Handles through 1/0 not 300 kcmil
4 Does not handle 814 STR
5
7400DASKS400 allows for two conductors (2) wire range supplied
6
(2) 250 kcmil not 300 kcmil (Main Lug) - (1) 600 kcmil not 750 kcmil (Main Lug)
34
19992007 Schneider Electric All Rights Reserved 04/2007
Energy Efficient Transformers
Wire Range Part Numbers and Lug Kits

Table 25: Three-Phase, 480 V Primary

Primary Primary NEC 450-3 (125%) Max. Amp. Primary NEC 450-3 (250%) Max. Amp. Primary
kVA
Voltage Current Ratings per NEC 240.6 Lug Kit Ratings per NEC 240.6 Lug Kit
15 18.06 25 DASKP100 45 DASKP100
30 36.13 50 DASKP100 90 DASKP100
DASKP100
45 54.19 70 125 DASKP250
DASKP250
DASKP250 DASKP250
75 90.32 125 225
DASKP400 DASKP400
DASKP250 DASKP250
112.5 480 135.48 175 300
DASKP400 DASKP400
DASKP250
150 180.64 225 450 DASKP600 1
DASKP400
DASKP400 DASKP600
225 270.95 350 600
DASKP600 DASKP1000 1
300 361.27 450 DASKP600 800 DASKP1000 1
500 602.12 800 DASKP1000 1200 DASKP1200 1
1
Terminals are designed for back to back mounting.

Table 26: Three-Phase, 600 V Primary

Primary Primary NEC 450-3 (125%) Max. Amp. Primary NEC 450-3 (250%) Max. Amp. Primary
kVA
Voltage Current Ratings per NEC 240.6 Lug Kit Ratings per NEC 240.6 Lug Kit
15 14.45 20 DASKP100 45 DASKP100
DASKP100
30 28.90 40 DASKP100 90
DASKP250
45 43.35 60 DASKP100 125 DASKP250
DASKP100 DASKP250
75 72.25 100 225
DASKP250 DASKP400
DASKP250 DASKP250
112.5 600 108.38 150 300
DASKP400 DASKP400
DASKP250 DASKP400
150 144.51 200 450
DASKP400 DASKP600 1
DASKP400 DASKP600
225 216.76 300 600
DASKP600 DASKP1000 1
300 289.02 400 DASKP600 800 DASKP1000 1
500 481.70 700 DASKP1000 1200 DASKP1200 1
1 Terminals are designed for back to back mounting.

Table 27: Three-Phase, 208Y/120 V Secondary

Secondary Secondary NEC 450-3 (125%) Max. Amp. Secondary


kVA
Voltage Current Ratings per NEC 240.6 Lug Kit
15 41.69 60 DASKS100
30 83.37 110 DASKS250 Lug from
DASKS400 kit
45 125.06 175 DASKS250 mounted on a
DASKS250 EE75T3H
75 208.43 300 X terminal
DASKS400
112.5 208Y/120 312.64 400 DASKS400
150 416.85 600 DASKS600
225 625.28 800 DASKS1000 1
300 833.70 1200 DASKS1200

500 1389.51 2000 DASKS2000


1
Terminals are designed for back to back mounting.

35
04/2007 19992007 Schneider Electric All Rights Reserved
Energy Efficient Transformers
Specifications

2.02 Ratings information


Specifications
A. All insulating materials are to exceed NEMA ST20 standards and be
Part 1 General
rated for 220 C UL component recognized insulation system.
1.01 Section Includes B. Transformers 15 kVA and larger shall be 150 C temperature rise above
40 C ambient. Transformers 25 kVA and larger shall have a minimum of
Dry-type energy efficient transformers per
42.5% full capacity primary taps. Exact voltages and taps to be as
NEMA TP-1 and CSA 802.2-00, with primary
designated on the plans or the transformer schedule.
and secondary voltages of 600 V and less and
capacity ratings 15 kVA through 750 kVA. C. The maximum temperature of the top of the enclosure shall not exceed
50 C rise above a 40 C ambient.
NOTE: Paragraphs and words marked in
D. Transformers shall be low loss type with minimum efficiencies per the
brackets [ ] are alternates. Select only one.
table below when operated at 35% of full load capacity. Efficiency shall
1.02 References be tested in accordance with NEMA TP-2 and CSA 802.2-00.

A. NFPA 70National Electrical Code Single-Phase Three-Phase


B. NEMA ST20
kVA % Efficiency kVA % Efficiency
C. UL 1561
15.0 97.7 15.0 97.0
D. CSA C22.2 25.0 98.0 30.0 97.5
E. NEMA TP-2 37.5 98.2 45.0 97.7
F. NEMA TP-1 50.0 98.3 75.0 98.0
G. CSA 802.2-00 75.0 98.5 112.5 98.2
100.0 98.6 150.0 98.3
1.03 Submittals
167.0 98.7 225.0 98.5
Suppliers asking considerations as an approved 250.0 98.8 300.0 98.6
equal shall submit complete, warranted 333.0 98.9 500.0 98.7
performance data and physical dimensions for 750.0 98.8
similar transformers. Data shall be submitted for Table per NEMA TP-1 CSA 802.2-00 and Energy Act of 2005 (US Public Law 109-58)
each size specified, and shall be received by the
consultant engineer no less that 10 days prior to E. The transformer(s) shall be rated as indicated in the following schedule:
the bid due date for consideration.
Identification number(s)
1.04 Standards kVA rating
A. Transformers 750 kVA and smaller shall be Voltages
listed by third party testing agency. Phase
B. Transformers conform to the requirements of Frequency
ANSI/NFPA 70.
C. Transformers are to be manufactured and 2.03 Construction
tested in accordance with NEMA ST20 and
CSA22.2 No. 47. A. Transformer coils shall be of the continuous wound construction and
shall be impregnated with non hygroscopic, thermosetting varnish.
Part 2 Products B. All cores to be constructed with low hysteresis and eddy current losses.
2.01 Manufacturers Magnetic flux densities are to be kept well below the saturation point to
prevent core overheating. Cores for transformers greater than 500 kVA
A. Transformers shall be as manufactured by shall be clamped utilizing insulated bolts through the core laminations to
Schneider Electric or approved equal. ensure proper pressure throughout the length of the core. The completed
B. Approved manufacturers shall be registered core and coil shall be bolted to the base of the enclosure, but isolated by
firms in accordance with ISO 9001: 1994 means of rubber vibration-absorbing mounts. There shall be no
SIC 3612 (US), which is the design and metal-to-metal contact between the core and coil and the enclosure except
manufacture of low voltage dry-type power, for a flexible safety ground strap. Sound isolation systems requiring the
distribution, and specialty transformers. complete removal of all fastening devices will not be acceptable.

36
19992007 Schneider Electric All Rights Reserved 04/2007
Energy Efficient Transformers
Specifications
C. The core of the transformer shall be visibly grounded to the enclosure by
means of a flexible grounding conductor sized in accordance with
applicable [UL and NEC] [CSA and CEC] standards.
D. The transformer enclosures shall be ventilated and be fabricated of
heavy gauge, sheet steel construction. The entire enclosure shall be
finished utilizing a continuous process consisting of degreasing,
cleaning, and phosphatizing, followed by electrostatic deposition of
polymer polyester powder coating and baking cycle to provided uniform
coating of all edges and surfaces. The coating shall be UL recognized
for outdoor use. The coating color shall be ANSI 49.

2.04 Sound Levels

Sound levels shall be warranted by the manufacturer not to exceed the


following:

kVA Rating Sound Level


15 to 50 kVA 45 dB
51 to 150 kVA 50 dB
151 to 300 kVA 55 dB
301 to 500 kVA 60 dB
501 to 700 kVA 62 dB
701 to 1000 kVA 64 dB
1001 to 1500 kVA 65 dB
1501 to 2000 kVA 66 dB

NOTE: Lower sound levels may be desirable for critical areas such as
hospitals, schools, or office areas. Contact your local Schneider Electric
representative for specific recommendations.

2.05 Optional Accessories

A. [Provide weathershields for units ID#______ 750 kVA max.]


B. [Provide wall mounted brackets for units ID#______ 75 kVA max. for
three-phase, 50 kVA max. for single-phase]
C. [Provide ceiling mounting brackets for units ID#______ 150 kVA max.]

Part 3 Execution

3.01 Installation
Not used.

37
04/2007 19992007 Schneider Electric All Rights Reserved
Energy Efficient Transformers
Frequently Asked Questions and Answers

Frequently Asked Questions and Answers

What is an Energy Efficient Transformer?


Square D Type EE Energy Efficient Transformers are designed to meet NEMA Standard TP-1
efficiency standards. Lower core loss and emphasis on maximizing efficiency at typical average
loading levels of 35 percent are keys to reduced energy costs in low voltage dry-type Energy Efficient
Transformers.
How do the dimensions of Energy Efficient Transformers compare with standard General
Purpose Transformers?
Type EE transformers have the same dimensions as standard, 150 C rise General Purpose
Transformers.
What is the typical difference in price between Type EE Transformers and standard 150 C rise
General Purpose Transformers?
The price of Type EE Transformers can be as high as 35 percent more than standard transformers.
However, that increased initial cost can typically be paid back in energy cost savings in five to six years
based on $.075 per kWh utility rate. Therefore, the long-term cost of ownership for Type EE
Transformers is actually less than General Purpose Transformers.
Approximately how many watts can these transformers save?
At typical average load of 35 percent, the average loss in watts for Type EE Transformers is 30 percent
lower than standard, 150 C rise General Purpose Transformers. The improvement in efficiency at that
loading level is primarily a result of significantly reduced core loss. However, even at full load, the
savings in watts is typically 15 percent.
When should I specify a Type EE transformer over a standard one?
A Type EE transformer can be beneficial in any situation where energy savings is a concern. We all
have a stake in preserving world energy reserves. The opportunity to contribute towards reduced
energy consumption and to provide pay back in the long run for your customers are compelling
reasons to specify an Energy Efficient transformer.
What is the difference between Square D Energy Savings Watchdog Transformers and Energy
Efficiency Transformers.
Watchdog transformers have far lower full-load losses than either Type EE or General Purpose
Transformers. That advantage rapidly disappears as loading is reduced, typically reaching a trade
off at 50 75 percent load. Surveys show that average loading is 35 percent for low voltage
transformers over a typical 24-hour period. Use of Watchdog transformers at that loading level would
actually represent a loss penalty over standard transformers because of the inherently greater core
loss. Type EE transformers are designed to replace Watchdog transformers in the role of energy
savings at more typical levels of loading.
How does the presence of harmonics, such as in high-density office computer and network
load currents, affect energy efficiency?
Harmonics do lessen the efficiency of all transformers. Harmonics cause somewhat higher losses
in transformer windings (as much as 30 percent for most Square D Transformers). Type EE
transformers are no more susceptible than any other transformer to the effect of harmonics. Type EE
transformers provide the same percentage of loss reduction compared with General Purpose
Transformers, or even K-Factor rated transformers under the same load conditions. Because the
average loading of low voltage transformers is normally only 35 percent, a K-factor rating is not
necessary for Type EE transformers.

38
19992007 Schneider Electric All Rights Reserved 04/2007