PLC Connection Guide

Siemens S7-200
Supported Series: Siemens S7-200 series PLC
(CPU212/214/215/216/221/222/224/226/226XM)
Website: http://www.siemens.com/entry/cc/en/

HMI Setting:
Parameters Recommen Options Notes
PLC type ded
SIEMENS S7-200
PLC I/F RS485 2w RS485 2w
The HMI which has a sticker
Baud rate 9600 9600, 19200, 187.5K MPI187.5 on the rear cover
supports 187.5K
Data bits 8 7,8
Parity Even Even, Odd, None
Stop bits 1 1, 2
PLC sta. no. 2 1 ~ 126
Turn around delay 5
(ms) ACK delay(ms)
Send 30

Online simulator YES Extend address mode NO


Broadcast command NO

PLC Setting:
Communication Set station number to 2
mode

Device Address:
Bit/Word Device type Format Range Memo
B I DDDDo 0 ~ 40957 Input (I)
B Q DDDDo 0 ~ 40957 Output (O)
B M DDDDo 0 ~ 40957 Bit Memory
B VW_Bit DDDDDo 0 ~ 102397 V Memory Bit Address
B S DDDDo 0 ~ 40957 SCR
B SM DDDDo 0 ~ 40957 Special Memory
B T_Bit DDD 0 ~ 255 Timer
B C_Bit DDD 0 ~ 255 Counter
PLC Connection Guide
Bit/Word Device type Format Range Memo
Byte VB DDDDD 0 ~ 10239 V Memory
W VW DDDDD 0 ~ 10239 V Memory
W VW_Odd DDDDD 0 ~ 10239 V Memory
DW VD DDDDD 0 ~ 10239 V Memory Double Word
DW VD_Odd DDDDD 0 ~ 10239 V Memory Double Word
W VW_String DDDDD 0 ~ 10239 String
W VW_String_Odd DDDDD 0 ~ 10239 String
DW VD_String DDDDD 0 ~ 10239 String
DW VD_String_Odd DDDDD 0 ~ 10239 String
Byte MB DDDDD 0 ~ 10239 Byte Memory
W MW DDDDD 0 ~ 10239 Word Memory
W MW_Odd DDDDD 0 ~ 10239 Word Memory
DW MD DDDDD 0 ~ 10239 Word Memory
Byte SB DDDDD 0 ~ 10239 SCR
W SW DDDDD 0 ~ 10239 SCR
DW SD DDDDD 0 ~ 10239 SCR
Byte SMB DDDDD 0 ~ 10239 Special Memory
W SMW DDDDD 0 ~ 10239 Special Memory
DW SMD DDDDD 0 ~ 10239 Special Memory
W T DDD 0 ~ 255 Timer
W C DDD 0 ~ 255 Counter
Double word and floating point value must use VD device type.

How to Import Tag:


The tags created in the Symbol Table in Step7-MicroWIN software can be imported to
EasyBuilder.
1. In Symbol Table create the tags. Select all the tags and click the right mouse button
then copy the tags.
PLC Connection Guide
2. Launch EasyBuilder, add the driver in the device list in System Parameter Settings,
and then click Import Tag button.

3. Paste the tags copied in step 1 and then click OK.

4. Select all the tags and then click OK.


PLC Connection Guide
5. If succeeded, the following message window shows.

Wiring Diagram:
Diagram 1
cMT Series cMT3151

eMT Series eMT3070/ eMT3105 / eMT3120 / eMT3150

HMI PLC
COM1 COM3 RS485 2W
RS485 2W RS485 2W 9P D-Sub
9P Male 9P Male Male
Data- 1 6 8
Data+ 2 9 3
GND 5 5 5

Diagram 2
cMT Series cMT-SVR

mTV mTV

HMI PLC
COM2 COM3 RS485 2W
RS485 2W RS485 2W 9P D-Sub
9P Female 9P Female Male
Data- 7 4 8
Data+ 6 1 3
GND 5 5 5
PLC Connection Guide
Diagram 3
MT-iE MT8070iE / MT6070iE / MT8100iE / MT8121iE / MT8150iE

MT-XE MT8121XE / MT8150XE

HMI PLC
COM1 COM3 RS485 2W
RS485 2W RS485 2W 9P D-Sub
9P Male 9P Male Male
Data- 1 7 8
Data+ 2 8 3
GND 5 9 5

Diagram 4
MT-iE MT8071iE / MT6071iE / MT8072iE / MT6072iE / MT8073iE /
MT8101iE / MT8102iE / MT8103iE
MT-XE MT8090XE / MT8092XE

MT-iP MT6103iP

HMI PLC
COM2 COM3 RS485 2W
RS485 2W RS485 2W 9P D-Sub
9P Male 9P Male Male
Data- 1 6 8
Data+ 2 9 3
GND 5 5 5
PLC Connection Guide

Diagram 5
MT-iE MT8050iE

MT-iP MT6051iP

HMI PLC
COM1 COM3 RS485 2W
RS485 2W RS485 2W 9P D-Sub
9P Female 9P Female Male
Data- 1 7 8
Data+ 2 8 3
GND 5 5 5

Diagram 6
MT-iP MT6071iP / MT8071iP

HMI PLC
COM2 RS485 2W
RS485 2W 9P D-Sub
9P Female Male
Data- 1 8
Data+ 2 3
GND 5 5