Techtopics52rev0 X
Techtopics52rev0 X
Techtopics52rev0 X
52
Revision 0
TechTopics Date:Sept. 25, 2006
We occasionally receive queries from users or their installation contractors regarding the need for insulation
of the users power connections to metal-clad switchgear. The answer is that the users power connections
must be insulated to the same performance levels as are required of the switchgear itself. The users power
connections are typically insulated with tape in accordance with the manufacturers instructions, or may be
insulated with optional preformed boots available from most switchgear manufacturers.
ANSI/IEEE C37.20.2 for metal-clad switchgear defines metal-clad as, among other things, switchgear in
which the primary bus conductors and connections are covered with insulating material throughout (clause
3.1.5.e). The standard goes on to explain the rationale for requiring that primary conductors and
connections be insulated in clause 7.9, which says (in part)
This insulating covering is a requirement of metal-clad switchgear (see 3.1.5) and is provided to
minimize the possibility of communicating faults and prevent the development of bus faults that would
result if foreign objects momentarily contacted bare bus. This insulating covering is usually only a part
of the primary insulation system, and in such cases the outer surface of this insulating covering will
not be at ground potential. It should not be assumed, therefore, that personnel can contact this
insulating covering with complete safety.
This paragraph contains multiple nuggets of wisdom on the subject of insulation in metal-clad switchgear,
in general, and on insulation of users power terminations.
In addition, the manufacturer has to consider power frequency voltage withstand capability (as discussed
earlier in this issue), and must also consider impulse withstand capability. The manufacturer conducts
lightning impulse withstand tests to verify the performance of their designs. Equipment designed to have
insulated user power terminations is not likely to meet the lightning impulse withstand performance levels of
the design if the terminations are not insulated.
Some users request special designs to accommodate uninsulated user power terminations, such as by
installing insulating barriers between the phases and between the outer phases and ground in the users
power termination areas. This can be done, but is generally undesirable for these reasons:
Since the terminations would not be insulated, it causes the switchgear to fail to comply with IEEE
C37.20.2 standards for metal-clad switchgear.
Addition of barriers increases the cost of the equipment.
The manufacturer may add barriers but may not have performed design tests to IEEE C37.20.2 to verify
that the equipment meets the dielectric performance requirements of the standard, including both the
power frequency (one-minute) withstand voltage and the lightning impulse withstand voltage levels.
Addition of interphase / outerphase barriers increases the clutter in the termination area. If the barriers
must be removed to provide access for examination of the main bus, the barriers make the operation
more difficult, and may also make it less likely that the main bus area will be periodically inspected.
Summary
Insulated user power terminations are required by the standards for metal-clad switchgear
Insulation reduces the likelihood of occurrence of arcing faults
Insulation is required to meet the dielectric performance levels of the standards
T. W. (Ted) Olsen
Manager, Technology