34-SDMS-02
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 19-10-2003G
34-SDMS-02
SPECIFICATIONS
FOR
TABLE OF CONTENTS
1.0 SCOPE 3
9.0 TESTING 7
10.0 INSPECTION 8
11.0 MARKING 9
13.0 GUARANTE 10
14.0 SUBMITTAL 10
Page 2 of 17
Saudi Electricity Company
34-SDMS-02
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 19-10-2003G
1. SCOPE
This SEC distribution material specification (SDMS) describes the minimum technical
requirements for design, manufacturing, testing, inspection, and performance of MV and
LV fuse links to be used in distribution system of the Saudi Electricity Company (SEC).
2 CROSS REFERENCES
2.1 This specification shall be read in conjunction with the SEC general specification No. 01-
SDMS-01 latest revision titled General requirements for all equipment / materials,
which shall be considered as an integral part of this SDMS.
2.2 This specification shall also be read in conjunction with SEC purchase orders/contracts
scope of work and technical specifications for projects as applicable.
The latest revision of the following codes and standards shall be applicable for the
equipment / material covered in this specification. In case of any deviation from the
below listed standards, the vendor / manufacturer may propose equipment / material
conforming to an alternate codes or standards and it should be indicated in the list of
deviations submitted by the supplier.
However, the provision of SEC standards shall supercede the provisions of these
alternate standards in case of any difference.
ANSI C37 . 41 Design tests for high voltage fuses, Distribution enclosed Single Pole
air switches, fuse disconnecting switches & accessories.
ANSI C37 . 43 Specifications for distribution fuse links for use in distribution
enclosed, open, and open - link cutouts.
Page 3 of 17
Saudi Electricity Company
34-SDMS-02
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 19-10-2003G
4. SERVICE CONDITIONS:
4.1 The fuse links shall be suitable for operation under the service conditions as per SEC
latest revision of general specification No.01-SDMS-01.
4.2 The fuse links shall withstand the effects of direct solar radiation at their installed
locations. The temperature of surfaces exposed to direct solar radiation shall be as
75C excluding internal heating.
5. SYSTEM PARAMETERS:
6. DESIGN REQUIREMENTS:
Design requirements for voltage rating, and min.current breaking capacity of fuse links
are given below in table - 6.1. Current ratings are given in fuse links selection tables
clause-8.
Page 4 of 17
Saudi Electricity Company
34-SDMS-02
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 19-10-2003G
MV Current LV fuses
Description Expulsion type K limiting fuses (HRC)
fuses (HRC)
Voltage 15.2 KV 36 KV 17.5 KV 500 V
rating
Rated breaking 8 KA 8 KA 40 KA 80 KA
Capacity symm.
Table-6.1
Voltage rating and breaking capacity of Fuse links
7 CONSTRUCTION REQUIREMENTS
The wire expulsion fuse links shall be removable button head type K as per IEC
60282-2 and NEMA SG2 of current ratings as given below in table 7.1 and shown in
figure No.1. The fuses should be of speed ratio 6 through 8.1. The strain wire tensile
strength should be much enough to withstand pull forces and any mechanical shock in
excess of 4.5Kg (10 lb)min. Button head and contact washer should be Tin/Silver
platted.The cable shall be corrosion resistant. Standard length of fuse links shall be
787mm (31inchs).
Table 7.1
Current ratings of type K fuse links
High Rutpure Capacity MV current limiting fuse shall be ferrule connection type,
length 442mm, striker pin action with indicating device, in performance to conform to
IEC 60282-1. The ceramic tube should be of high mechanical and thermal strength to
withstand any shock and stresses. The dimensions of the fuse links, to be used
in13.8KV SF-6 ring main units, to DIN-43625 are shown in figure No.SEC/FL-2.
Page 5 of 17
Saudi Electricity Company
34-SDMS-02
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 19-10-2003G
High Rupture Capacity LV fuse shall be 200A knife type, NH size 2, non slotted,
silver plated and copper blade contacts as shown in figure No.3. The operation
indicator shall be actuated once the fuse element is blown. The fuse power losses
should not be more than 34 watts. The ceramic body of the fuse should withstand
mechanical shocks and dynamic stresses. The performance characteristics should be in
accordance with VDE 0636-2 class of operation gL and IEC 60269-2 class of
operation gI, and dimensions as per DIN 43620.
The fuse link must be large enough to withstand the combined transformer inrush
and cold load pick up currents, including the effects of high ambient temperature, in
accordance with its time current characteristics.
The standard ratings of type K fuse links for different capacities of the pole
mounted transformers which are fed from over head lines and controlled by
drop out cutouts are enlisted below in table - 8.1.
100 15 K 6 K
200 20 / 25* K 10 K
300 30 / 40* K 15 K
Table-8.1
Primary MV fuse link ratings for
Transformers controlled by dropout cutouts
Page 6 of 17
Saudi Electricity Company
34-SDMS-02
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 19-10-2003G
The standard ratings of MV HRC current limiting fuse links are enlisted below in
table No. 8.2 as specified in SEC specification No.32-SDMS-01 of 13.8KV SF6
RMUs indoor or outdoor, for the control and protection of distribution unit / package
substations and pad mounted transformers
300 31.5 A
500 50 A
1000 80/100 A
1500 125 A
Table-8.2
13.8 KV HRC Fuse links for unit / Package substations
and pad mounted transformers controlled by SF6 RMUs
LV fuse links knife type NH size 2 of current rating 200 amps shall be installed in
distribution pillars and fuse boxes to protect low voltage circuits and prevent damage
to transformers secondary.
9 TESTS
Page 7 of 17
Saudi Electricity Company
34-SDMS-02
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 19-10-2003G
Page 8 of 17
Saudi Electricity Company
34-SDMS-02
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 19-10-2003G
10 INSPECTION:
SEC may wish to witness tests or visit the factory during manufacturing of any
or all items covered by this specification. Accordingly the supplier shall give SEC
adequate notice of manufacturing and testing schedules. However for detailed
inspection conditions refer to the latest revision of SEC general specification No 01-
SDMS-01 clause 6.
11 MARKING:
Each fuse link shall be clearly marked with the following information as minimum,
in English and /or Arabic.
12.1 Each fuse shall be individually packed in transparent plastic bag complete with
identification markings. Individually packed fuses shall be packed in crates or
boxes in such a manner to prevent damage during transportation and handling up to
the installation site. Packing shall be designed to prevent entry of dust, ingress of
moisture and other foreign materials. Each container shall have the following
information stenciled on it in English and /or Arabic.
Manufacturers name.
Year of manufacture
Country of origin.
SEC item number.
SEC purchase order/tender number
Weight in kilogram.
Handling instruction.
Voltage and current rating.
No. of fuse links in each box/crate.
Page 9 of 17
Saudi Electricity Company
34-SDMS-02
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 19-10-2003G
12.2 Other packing and shipping requirements shall be as given in SEC General
Spec.No. 01-SDMS-01 (latest revision). The supplier shall contact material
department for additional packing, handling and shipment instructions as
applicable.
12.3 Packing note in Arabic and/or English shall be included in each case giving
description of goods packed.
13 GUARANTEE:
13.1 The manufacturer / vendor shall guarantee against all the defects arising out
of faulty design, workmanship or defective material for a period of two (2) years
from the date of delivery, unless and otherwise specified in tender documents.
14 SUBMITTALS
Page 10 of 17
Saudi Electricity Company
34-SDMS-02
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 19-10-2003G
SEC VENDOR
S.No. DESCRIPTION. UNIT. SPECIFIED PROPOSED
VALUES. VALUES.
1 System operation voltage. kV 13.8 or 33
Note: Separate technical data sheet should be used for each type of fuse link.
Page 11 of 17
Saudi Electricity Company
34-SDMS-02
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 19-10-2003G
SEC VENDOR
S.No. DESCRIPTION. UNIT. SPECIFIED PROPOSED
VALUES. VALUES.
1 System operation voltage. kV 13.8
10 Dimensions mm
kg
11 Weight
Note: Separate technical data sheet should be used for each type of fuse link.
Page 12 of 17
Saudi Electricity Company
34-SDMS-02
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 19-10-2003G
SEC VENDOR
S.No. DESCRIPTION. UNIT. SPECIFIED PROPOSED
VALUES. VALUES.
220/127
1 System operating voltage. V
380/220
2 Max design voltage. V 500
200
3 Continuous current capacity. A
Rated Max. breaking capacity
4 kA 80
(symmetrical).
5 Melting current & time A/sec
6 Min. breaking current A
Page 13 of 17
Saudi Electricity Company
34-SDMS-02
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 19-10-2003G
MANUFACTURER
Name of company
Page 14 of 17
Saudi Electricity Company
34-SDMS-02
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 19-10-2003G
Page 15 of 17
Saudi Electricity Company
34-SDMS-02
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 19-10-2003G
Page 16 of 17
Saudi Electricity Company
34-SDMS-02
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 19-10-2003G
Page 17 of 17