0% found this document useful (0 votes)
313 views1 page

Proctor Compaction Test 06.04.12

This document contains the results of a standard proctor compaction test conducted on soil samples from a sewage treatment plant construction site. The test involved compacting the wet soil in layers in a 1000cc mould and recording the weight and density at each trial. The maximum dry density was found to be 1.64 g/cc at an optimum moisture content of 18.85%. A graph plotting dry density against moisture content showed the peak density was achieved at around 18-19% moisture content.

Uploaded by

Shesha Shayan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
313 views1 page

Proctor Compaction Test 06.04.12

This document contains the results of a standard proctor compaction test conducted on soil samples from a sewage treatment plant construction site. The test involved compacting the wet soil in layers in a 1000cc mould and recording the weight and density at each trial. The maximum dry density was found to be 1.64 g/cc at an optimum moisture content of 18.85%. A graph plotting dry density against moisture content showed the peak density was achieved at around 18-19% moisture content.

Uploaded by

Shesha Shayan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 1

FIELD Quality plan

Sewage Treatment Plants at


Doddabele,Yellamalappachetty
KEC-WATERLEAU QP.No-1
and Intermediate Sewage pumping Station and
(JV) REV.no-0
Pumping Mains at Sadarmangala

PROCTOR'S COMPACTION TEST


(STANDARD PROCTOR) As per IS 2720 (PART 7)

Sample No Lab Ref No.


Source ID Inside Plant Date of Sampling
Loaction of Sampling Date of Test
Mould No : wt. of Mould, W1 (g) : 1966 Volume of mould , V (cc) : 1000
Trial No : I II III IV V VI

wt. of Wet Soil + Mould, W2 (g) 3503 3610 3840 3820 3790 3730
wt. of Wet Soil, W3=(W2-W1) (g) 1539 1644 1874 1854 1774 1784
Wet Density, Yb = W3/V (g/cc) 1.539 1.644 1.874 1.854 1.774 1.784
Container No. 107 105 24 21 12 71
wt. of Container,W5 (g) 45.17 45.87 57.91 56.1 48.95 46.27
wt. of Wet Soil + Cont., W6 (g) 145.2 140.08 160.9 170.2 149.2 150.1
wt. of Dry Soil + Cont.,W7 (g) 135.05 125.8 144.8 152.1 130.2 128.9
wt. of Water, W8=(W6-W7) (g) 10.15 14.28 16.1 18.1 19 21.2
wt. of Dry Soil, W9=(W7-W5) (g) 89.88 79.93 86.89 96 81.25 82.63
Water Content w =W8/W9 (%) 11.29 14.90 16.53 18.85 23.38 25.66
Dry Density Yd = 100x(Yb/100+w) (g/cc) 1.38 1.41 1.50 1.64 1.44 1.42

1.85

1.80
Rammer Wt. : 2.6 kg
1.75
Blows/layer : 25/55 blows
1.70 No. of layers : 3 layers

1.65

1.60
Dry Density

1.55
RESULTS
1.50
MDD = 1.64
1.45 OMC = 18.85%

1.40

1.35

1.30
0.00 2.00 4.00 6.00 8.00 10.00 12.00 14.00 16.00 18.00 20.00 22.00 24.00 26.00

OMC

Remarks :

For KJIP For (CCD) For (FQA)